§ 28-1101.1. Enactment of the New York city electrical code
The 2020 edition of the National Fire Protection Association NFPA 70 National Electrical Code is hereby adopted as the minimum requirements for the design, installation, alteration, or repair of electric wires and wiring apparatus and other appliances used or to be used for the transmission of electricity for electric light, heat, power, signaling, communication, alarm, and data transmission in the city of New York subject to the amendments adopted by local law and set forth in section 28-1101.3. Such amendments shall be known and cited as "the New York city amendments to the 2020 National Electrical Code". Such 2020 edition of the National Fire Protection Association NFPA 70 National Electrical Code with such New York city amendments shall together be known and cited as the “New York city electrical code”.
(L.L. 2024/128, 12/21/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/128.
§ 28-1101.2. Update
No later than the third year after the effective date of this section and every third year thereafter, the commissioner shall submit to the city council proposed amendments that they determine should be made to this code to bring it up to date with the latest edition of the National Fire Protection Association NFPA 70 National Electrical Code or otherwise modify the provisions thereof. In addition, prior to the submission of such proposal to the city council, such proposal shall be submitted to an advisory committee established by the commissioner for review and comment.
(L.L. 2024/128, 12/21/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/128.
§ 28-1101.3. The New York city amendments to the 2020 National Electrical Code
The following New York city amendments to the 2020 National Electrical Code are hereby adopted to read as follows:
(L.L. 2024/128, 12/21/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/128.
Title 28, Chapter 11, New York City Amendments to the 2020 National Electrical Code
New sections EC 80 through EC 87 are added to read as follows:
Section EC 80. General
80.1 Title.
This code shall be known and may be cited as the “ New York City Electrical Code ,” “NYCEC” or “EC.” All section numbers in this code shall be deemed to be preceded by the designation “EC.”
80.2 Scope.
The provisions of this code shall apply to the installation, alteration, maintenance, repair, or demolition of electric wires and wiring apparatus and other appliances used or to be used for the transmission of electricity for electric light, heat, power, signaling, communication, alarm, or data transmission.
80.3 Intent.
The purpose of this code is to provide minimum standards to safeguard life or limb, health, property, public welfare, and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation, and maintenance or use of electrical systems.
80.4 Severability.
If a section, subsection, sentence, clause, or phrase of this code is for any reason held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this code.
Section EC 81. Applicability
81.1 General.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern. Where, in any specific case, different sections of this code specify different materials, methods of construction, or other requirements, the most restrictive shall govern.
81.2 Existing installations.
Except as otherwise specifically provided, electrical installations lawfully in existence at the time of the adoption or a subsequent amendment of this code shall be permitted to have their use and maintenance continued if the use, maintenance, or repair is in accordance with the original design and no hazard to life, health, or property is created by such installations.
81.2.1 Existing buildings.
Additions, alterations, renovations, or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable.
81.2.2 References to the New York City Building Code.
For existing buildings, a reference to a section of the New York City Building Code in this code shall also be deemed to refer to the equivalent provision of the 1968 Building Code , as applicable in accordance with Chapter 1 of Title 28 of the Administrative Code .
81.3 Maintenance.
Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards that are required by this code shall be maintained in compliance with the applicable provisions under which they were installed.
81.3.1 Owner responsibility.
The owner or the owner’s designated agent shall be responsible for maintenance of electrical installations. To determine compliance with this provision, the commissioner shall have the authority to require any electrical installation to be inspected.
81.4 Design, installation, alterations, or repairs.
The design, installation, alteration, or repair of electric wires and wiring apparatus and other appliances used or to be used for the transmission of electricity for electric lights, heat, power, signaling, communication, alarm, or data transmission shall conform to the requirements of this code. Alterations or repairs shall not cause an existing installation to become unsafe, hazardous, or overloaded.
81.4.1 Special provisions for prior code buildings.
In addition to the requirements of section 81.4, the provisions of sections 81.4.1.1 through 81.4.1.2 shall apply to prior code buildings.
81.4.1.1 Seismic supports.
For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. Any applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9-6 of such code.
81.4.1.2 Wind resistance.
For prior code buildings, equipment, appliances, and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code.
81.5 Change in occupancy.
Refer to Chapter 1 of Title 28 of the Administrative Code .
81.6 Reserved.
81.7 Reserved.
81.8 Reserved.
81.8.1 Reserved.
81.9 Requirements not covered by code.
Requirements necessary for the strength, stability, or proper operation of an existing or proposed electrical installation, or for the public safety, health, and general welfare, not specifically covered by this code, shall be determined by the commissioner.
81.10 Application of references.
Reference to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
81.11 Federal and state buildings.
Nothing in this code shall be construed to apply to any building, the electrical equipment of which is under the control of the United States of America or the state of New York or of any department, bureau, or office thereof.
81.12 City departments.
The various departments, boards, and offices of the city of New York shall be subject to the provisions of this code.
Section EC 82. Department of Buildings
82.1 Enforcement agency.
Refer to the New York City Charter and Chapter 1 of Title 28 of the Administrative Code .
Section EC 83. Duties and Powers of the Commissioner of Buildings
83.1 General.
The commissioner shall have the authority to render interpretations of this code and to adopt rules, policies and procedures in order to clarify and implement its provisions. Such interpretations, policies, procedures, and rules shall be in compliance with the intent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of the Commissioner of Buildings.
83.2 Scope.
The commissioner is authorized to exercise all powers necessary to enforce the electrical code, including but not limited to:
1. Cause any wiring or appliances for electrical light, heat, power, signaling communication, alarm, or data transmission to be examined and inspected and the approval thereof to be certified in writing,
a. by an officer or employee of the department designated by the commissioner for that purpose, or
b. by any inspection agency certified by the commissioner in accordance with rules promulgated by the commissioner.
2. Order the remedying of any defect or deficiency that exists in the installation, alteration, or repair of electric wires and wiring apparatus and other appliances used or to be used for the transmission of electricity for electric light, heat, power, signaling, communication, alarm, or data transmission.
3. Order any person or corporation engaged in supplying electrical energy to discontinue such supply as specified in such order if the wiring or appliances for electric light, heat, power, signaling, communication, alarm, or data transmission is deemed dangerous to persons or property therein.
4. Appoint, in accordance with the rules of the department and at the commissioner’s discretion, special boards or committees to provide advice or assistance in the implementation, interpretation, variation, or amendment of any provision of the electrical code or any rule promulgated by the department.
Section EC 84. Permits
84.1 General.
Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code and with requirements found elsewhere in this code.
84.2 Required.
Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert, or replace any electrical, gas, mechanical, or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit.
84.3 Work exempt from permit.
Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or rules.
84.4 Validity of permit.
The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of errors in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other law.
84.5 Notice of unlicensed electrical work.
Whenever a master electrician business or special electrician files an application for a permit covering electrical work installed by an unlicensed or unauthorized person, it shall be their duty to specify such fact upon the application.
84.6 Electric utility meter installation.
The department shall not issue a permit or, if applicable, an electrical sign-off pursuant to an application that involves the energizing of a utility meter in a one-, two-, three-, or four-family dwelling if the department finds that such action will cause the total number of utility meters for the building to exceed the number of dwelling units specified for such building in the certificate of occupancy, or if there is no certificate of occupancy, as determined by the department, except as permitted herein. A building specified as a one-family residence in the certificate of occupancy or, if there is no certificate of occupancy, as determined by the department, shall have only 1 utility meter. A building in which there are 2 or more dwelling units in accordance with the certificate of occupancy, or if there is no certificate of occupancy, as determined by the department, shall have 1 utility meter for each dwelling unit, and 1 additional utility meter for the common areas of the building is permitted, provided that smoke detecting devices are installed in all common areas in accordance with departmental requirements. Such common areas may include boiler rooms, shared hallway lighting, shared stairway lighting, and outdoor perimeter lighting, but shall not include any habitable space. In the event that a utility meter has been found to have been installed or to exist in violation of this section, the department may take action leading to the disconnecting of such utility meter in accordance with the notice requirements set forth in section 87.2.
84.7 Statement of authorization and compliance.
Any application for a permit filed with the department in relation to a request for the authorization to power or energize electrical wiring or appliances or power generating equipment or in relation to work that will result in the issuance of a new or amended certificate of occupancy must include a statement, signed and sealed by the master or special electrician, that the building owner or their authorized representative has authorized in writing the work to be performed. This signed authorization must be available upon request by the department. In addition, any electrical application filed with the department involving the energizing of a meter must include a statement, signed, and sealed by the master or special electrician, that the building owner or their authorized representative has indicated in writing the intended use or purpose of such meter and has affirmed that such meter will be maintained in compliance with the provisions of this section. This statement must be available upon request by the department.
84.8 Documentation of overcurrent protection.
Any permit application filed with the department that requires the selective coordination of overcurrent protective devices must include documentation from a professional engineer demonstrating how selective coordination was achieved, including but not limited to short circuit overlay curves and calculations. Such documentation shall be submitted to the department prior to sign off.
Section EC 85. Construction Documents
85.1 General.
Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards as applicable. Such construction documents shall be coordinated with architectural, structural, and means of egress plans. Requirements for electrical plans and drawings shall be in accordance with department rules.
Section EC 86. Inspections and Testing
86.1 General.
Electrical work for which a permit is required, except for minor electrical work as defined in section 28-101.5, shall be subject to inspection by the department as directed by the commissioner. It shall be the duty of the permit holder to schedule such inspection and ensure that all applicable laws and rules are followed. A satisfactory inspection by the department shall not be construed to be an approval by the department of a violation of the provisions of this code or any other provision of law. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code and applicable rules of the department relating to inspections.
(Am. L.L. 2026/042, 1/17/2026, eff. 1/17/2026)
86.2 Required inspections and testing.
In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be required:
1. Energy code compliance inspections. Inspections required by the New York City Energy Conservation Code shall be made in accordance with the rules of the department, as applicable.
2. Final inspection. It shall be the duty of the permit holder to notify the department when work requiring final inspection, pursuant to this code or rules of the department, is ready to be inspected and to schedule such inspection.
(Am. L.L. 2026/042, 1/17/2026, eff. 1/17/2026)
86.2.1 Access to electrical work.
It shall be the duty of the permit holder to cause the work to remain accessible for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection.
86.3 Testing.
Electrical work and installations shall be tested as required in this code and in accordance with sections 86.3.1 through 86.3.3. Tests shall be conducted by the department, as applicable.
86.3.1 New, altered, extended, or repaired installations.
New installations and parts of existing installations that have been altered, extended, renovated, or repaired shall be tested as prescribed herein to ensure compliance with the electrical code and rules of the department.
86.3.2 Apparatus, instruments, material, and labor for tests.
When required by the department, apparatus, instruments, material, and labor required for testing an electrical installation or part thereof shall be furnished by the permit holder.
86.3.3 Reinspection and testing.
Where any work or electrical installation does not pass any initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or electrical installation shall then be resubmitted to the department for inspection and testing.
86.4 Sign-off of completed work.
If, after inspection, such wiring or appliances shall be found to have been installed, altered, or repaired in conformity with the requirements of this code, and the rules of the department, and the required fees paid, the commissioner shall issue to the applicant a sign-off of the approved work completed.
86.5 Temporary connection.
The commissioner shall have the authority to authorize the temporary connection of the building or system to the utility source for the purpose of inspecting or testing the electrical installation or for use under a temporary certificate of occupancy.
86.6 Connection of electrical service utilities.
Refer to Title 28 of the Administrative Code.
Section EC 87. Violations
87.1 General.
Refer to chapters 2 and 3 of Title 28 of the Administrative Code .
87.2 Authority to disconnect electrical energy supply.
The commissioner may authorize wires or appliances to be disconnected from the supply of electrical energy and to seal the wiring and appliances, after due inspection or where in the commissioner’s judgment the continued use of such electric wiring or appliances in or on any building or structure is unsafe or dangerous to persons or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure, or service system of the decision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as practicable thereafter.
87.3 Connection after order to disconnect.
No person shall cause or permit electrical energy to be supplied to the wiring or appliances so sealed until the same shall have been made safe and the commissioner shall have authorized the reconnection and use of such wiring or appliances. When an installation is maintained in violation of this code, and in violation of a notice issued pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation.
Title 28, Chapter 11, Article 100. Definitions
Part 1. General
Part I – Add new definitions for “Coordination (Limited Level)”, “Electrical Equipment Room”, and “Public Parts (Common Areas)” to part I of article 100 in alphabetical order to read as follows:
Coordination (Limited Level). Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the selection and installation of overcurrent protective devices and their ratings or settings having time-current ratings that do not intersect at a time of 0.1 seconds (6 cycles at 60Hz) or longer.
Electrical Equipment Room. A room designed for and dedicated to the purpose of containing electrical distribution equipment such as vertical risers, bus ducts, transformers, or panelboards.
Public Parts (Common Areas). Public parts of multifamily dwelling include a public hall and any space used in common by the occupants of 2 or more apartments or rooms, or by persons who are not tenants, or exclusively for mechanical equipment of such dwelling or for storage purposes.
§ 110.1
Section 110.1 – Revise the Informational Note in Section 110.1 to read as follows:
Informational Note: For information regarding the mounting height for the operable parts, see ICC A117.1 as referenced in the New York City Building Code for dwelling units and commercial occupancies.
§ 110.2
Section 110.2 – Revise Section 110.2 to read as follows:
110.2 Approval of Electrical Materials, Equipment and Installations.
(A) Equipment. The conductors and equipment required or permitted by this Code shall be acceptable only if approved.
(B) Special Installations. No electrical installations described in (1) through (5) below shall be constructed unless a submission for approval has been made to the commissioner and approval has been granted. For the purpose of this section, an electrical “installation” shall refer to the installation of service equipment, transformers, Uninterruptible Power Supply (UPS) systems, generators, generator paralleling equipment, or other sources, including, but not limited to, Energy Storage Systems, Fuel Cells, Photovoltaic Systems, DC or AC Micro Grids, Co-generation Plants, and Stationary Batteries.
(1) A new installation of equipment totaling 1,000 kVA or larger.
(2) Any change in an installation with a rating of 1,000 kVA or larger, up to and including 2nd level overcurrent protection unless it was fully described and approved as “future” on the original approved plan.
(3) Any addition to an existing installation, which would bring the total to 1,000 kVA or larger.
(4) The addition of any equipment in a room, which would affect clearances around the equipment of a 1,000 kVA installation or larger.
(5) A new installation or revised installation above 1000V AC or 1500V DC nominal irrespective of kVA rating.
Exception No. 1: No submission is required solely for fire alarm service taps.
Exception No. 2: No submission is required for the addition of 1 2nd level overcurrent protection device 200 amperes or less.
(C) Capacity.
(1) The capacity of a utility service, in kVA, shall be determined by summing the maximum ampere ratings of each service disconnecting means and calculating total kVA at the operating voltage. Service disconnecting means supplying fire pumps shall be included at 125 percent of the fire pump full load amps. The calculation shall include all new and existing service disconnecting means supplied from the common service entrance.
(2) The capacity of a transformer, UPS system, generator, or other source shall be its maximum kVA output rating.
Informational Note: See 90.7, Examination of Equipment for Safety, and 110.3, Examination, Identification, Installation, and Use of Equipment. See definitions of Approved, Identified, Labeled, and Listed.
§ 110.3
Section 110.3(D) – Add a new Section 110.3(D) to read as follows:
110.3(D) Electrical Equipment Rooms. Electrical equipment rooms shall be dedicated to electrical equipment not limited to fire alarm equipment, Building Management Systems, and lighting controls. All electrical equipment in the electrical equipment room shall be installed by a licensed electrician. Electrical equipment rooms shall be identified as such, shall be sized to provide the applicable working space requirements, and shall not be used for any other purpose including storage.
Exception: Electrical Equipment Rooms shall conform to requirements of 110.3(D) except as permitted in 800.133(C), 820.133(C) and 830.133(C).
Informational Note: Refer to Section BC 509, Table 509, and Section 903.2 of the New York City Building Code for additional construction requirements and Section 605.3.1 of the New York City Fire Code for signage requirements.
§ 110.4
§ 110.11
Section 110.11 – Revise Section 110.11 to read as follows:
110.11 Environmental Protection of Equipment
(A) Deteriorating Agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures.
Informational Note No. l: See 300.6 for protection against corrosion.
Informational Note No. 2: Some cleaning and lubricating compounds can cause severe deterioration of many plastic materials used for insulating and structural applications in equipment.
Equipment not identified for outdoor use and equipment identified only for indoor use, such as "dry locations", "indoor use only", "damp locations", or enclosure Types 1, 2, 5, 12, 12K, or 13, shall be protected against damage from the weather during construction.
Informational Note No. 3: See Table 110.28 for appropriate enclosure-type designations.
(B) Electrical Utilities and Equipment. The metering equipment, panelboards, load centers, main disconnect switches, all service disconnecting means, and all circuit breakers shall be located at or above the design flood elevation specified in Appendix G of the New York City Building Code.
Exception: For buildings or structures that are nonresidential, utilities and equipment shall be permitted to be located below the design flood elevation (DFE) when dry floodproofing is provided in accordance with the New York City Building Code and Appendix G of such code.
Informational Note: In flood zones, electric utilities and equipment must be protected from flood damage and associated deteriorating effects of flood exposure. For further requirements for electrical installations in flood zones refer to the 2022 New York City Building Code, Appendix G, ‘Flood Resistant Construction’; and ASCE-24-14, ‘Flood Resistant Design and Construction’.
§ 110.26
Section 110.26(A)(1) – Add a new Informational Note at the end of Section 110.26(A)(1) to read as follows:
Informational Note: For Service Rooms or areas with equipment totaling 1,000 kVA or larger, see 230.64 for minimum clearance requirements.
Section 110.26(G) – Add a new Section 110.26(G) to read as follows:
(G) Network Compartments. All network compartments shall have at least 2 means of access. Each door shall access an area that leads to a legal exit.
§ 110.33
Section 110.33(A) – Revise Section 110.33(A) to read as follows:
(A) Entrance. At least 1 entrance to enclosures for electrical installations as described in 110.31 not less than 30 in. (762 mm) wide and 6 1/2 ft (2 m ) high shall be provided to give access to the working space around the electrical equipment.
§ 110.34
Section 110.34(A) – Revise Section 110.34(A) to read as follows:
(A) Working Space. Except as elsewhere required or permitted in this Code, equipment likely to require examination, adjustment, servicing, or maintenance while energized shall have clear working space in the direction of access to live parts of the electrical equipment and shall be not less than specified in Table 110.34(A). Distances shall be measured from the live parts, if such are exposed, or from the enclosure front or opening if such are enclosed.
Exception: Working space shall not be required in back of equipment such as switchgear or control assemblies where there are no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on nonelectrical parts on the back of enclosed equipment, a minimum working space of 36 in. (900 mm) horizontally shall be provided.
Informational Note: For Service Rooms or areas with equipment totaling 1,000 kVA or larger, see 230.64 for minimum clearance requirements.
§ 210.11
Section 210.11 (C)(4) – Add a new Informational Note to Section 210.11(C)(4) to read as follows:
Informational Note: See Residential Provision of the New York City Energy Conservation Code, for additional Electrical Vehicle (EV) requirements.
Section 210.11(C)(5) – Add a new Section 210.11(C)(5) to read as follows:
(5) Air-Conditioning Branch Circuit. In addition to the number of branch circuits required by other parts of this section, an individual branch circuit shall be provided for each air-conditioning receptacle outlet required by 210.52(J).
§ 210.12
Section 210.12(A) – Retitle the “Exception” in 210.12(A) “Exception No. 1” and add a new Exception, “Exception No. 2”, immediately following which reads:
Exception No. 2: AFCI protection shall not be required for the following outlets in multifamily dwellings greater than 3 stories:
a) In kitchens, all receptacle outlets.
b) In laundry areas, all receptacle outlets supplying laundry equipment such as washers, dryers and leak-detection equipment. This exception does not apply to convenience outlets in laundry areas that may supply irons, steamers or similar appliances.
§ 210.19
Section 210.19(A) – Revise Section 210.19(A) to add a new opening paragraph to read as follows:
(A) Branch Circuits Not More Than 600V. The maximum total voltage drop from the service point to the farthest outlet shall not exceed 5 percent on both feeders and branch circuits combined. Where compliance with the applicable New York City Energy Conservation Code is mandated, the voltage drop requirements of that code shall apply.
Section 210.19(A) – Revise Informational Note No. 3 in Section 210.19(A) to read as follows:
Informational Note No. 3: DELETED.
§ 210.50
Section 210.50 – Revise the Informational Note in Section 210.50 to read as follows:
Informational Note: See Informative Annex J for information regarding ADA accessibility design. See requirements in ICC A117.1 as referenced in the New York City Building Code for information regarding the mounting height for the operable parts for dwelling units that are classified as accessible units.
§ 210.52
Section 210.52(J) – Add a new Section 210.52(J) to read as follows:
(J) Outlet Requirements For Residential-Type Occupancies. In addition to the requirements set forth in (A) through (I) of this section, living rooms, bedrooms, dining rooms or similar rooms shall have at least 1 receptacle outlet installed for air conditioners. Such receptacle outlets shall be supplied by an individual branch circuit.
Exception: For buildings with central air conditioning systems, a separate receptacle outlet shall not be required in any living room, bedroom, dining room, or other similar room served by such system.
§ 215.2
Section 215.2(A)(1) – Revise the opening paragraph in Section 215.2(A)(1) to read as follows:
(1) General. Feeder conductors shall have an ampacity not less than the larger of 215(A)(1)(a) or (A)(1)(b) and shall comply with 110.14(C). The maximum total voltage drop from the service point to the farthest outlet shall not exceed 5 percent on both feeders and branch circuits combined. The minimum feeder size feeding a dwelling unit shall be 3 conductors with minimum 8 AWG copper or 6 AWG aluminum or copper-clad aluminum conductors. Where compliance with the applicable New York City Energy Conservation Code is mandated, voltage drop requirements of that code shall apply.
Section 215.2(A)(1) – Revise Informational Note No. 2 in Section 215.2(A)(1) to read as follows:
Informational Note No. 2: DELETED.
Section 215.2(A)(1) – Revise Informational Note No. 3 in Section 215.2(A)(1) to read as follows:
Informational Note No. 3: See 210.19(A) for voltage drop for branch circuits.
§ 220.14 (American Legal id 0-0-0-231984)
Section 220.14 – Revise the opening paragraph of Section 220.14 to read as follows:
220.14 Other Loads – All Occupancies. In all occupancies, the minimum load for each outlet for general-use receptacles and outlets not used for general illumination shall not be less than that calculated in 220.14(A) through (N), the loads shown being based on nominal branch-circuit voltages.
Exception: The loads of outlets serving switchboards and switching frames in telephone exchanges shall be waived from the calculations.
§ 220.14 (American Legal id 0-0-0-231988)
Section 220.14(A) – Revise Section 220.14(A) to read as follows:
(A) Specific Appliances or Loads. An outlet for a specific appliance or other load not covered in 220.14(B) through (N) shall be calculated based on the ampere rating of the appliance or load served.
Section 220.14(N) – Add a new Section 220.14(N) to read as follows:
(N) Air Conditioning Circuits. A load of not less than 1500VA shall be calculated for each required branch circuit specified in 210.52(J). It shall be permitted to be included with the appliance load specified in 220.53.
§ 220.87
Section 220.87 – Revise Section 220.87 to read as follows:
220.87 Determining Existing Loads. The calculation of a feeder or service load for existing installations shall be permitted to use actual maximum demand to determine the existing load under all of the following conditions:
(1) The maximum demand data is available for a 1-year period.
Exception: If the maximum demand data for a 1-year period is not available, the calculated load shall be permitted to be based on the maximum demand (the highest average kilowatts reached and maintained for a 15-minute interval) continuously recorded over a minimum 30-day period using a recording ammeter or power meter connected to the highest loaded phase of the feeder or service, based on the initial loading at the start of the recording. The recording shall reflect the maximum demand of the feeder or service by being taken when the building or space is occupied and shall include by measurement or calculation the larger of the heating or cooling equipment load, and other loads that might be periodic in nature due to seasonal or similar conditions. This exception shall not apply if the feeder or service has a renewable energy system (i.e., solar photovoltaic or wind electric) or employs any form of peak load shaving.
(2) The maximum demand at 125 percent plus the new load does not exceed the ampacity of the feeder or rating of the service.
(3) The feeder has overcurrent protection in accordance with 240.4, and the service has overload protection in accordance with 230.90.
§ 225.11
Section 225.11 – Revise Section 225.11 to read as follows:
225.11 Overhead Branch Circuits Attached to Buildings or Structures. Overhead branch circuits and feeders attached to buildings or structures shall be installed in accordance with the requirements of 230.54.
Informational Note: Refer to Part II of Article 225 for underground installation.
§ 225.30
Section 225.30 – Revise the opening paragraph in Section 225.30 to read as follows:
225.30 Number of Supplies. Where more than 1 building or other structure is on the same property and under single management, each additional building or other structure that is served by a branch circuit or feeder on the load side of a service disconnecting means shall be supplied by only 1 feeder or branch circuit unless permitted in 225.30(A) through (F). For the purpose of this section, a multiwire branch circuit shall be considered a single circuit.
§ 225.31
Section 225.31 – Revise Section 225.31 to read as follows:
225.31 Disconnecting Means. Means shall be provided for disconnecting all ungrounded conductors that supply or pass through the building or structure. Disconnecting means required by this section shall comply with 230.64.
§ 225.34
Section 225.34(A) – Add a new Informational Note at the end of Section 225.34(A) to read as follows:
Informational Note: In existing buildings, if 1 or more of the 2 to 6 disconnects are not able to be grouped due to space constraints, they may be located in a remote location, if special permission is granted by the AHJ, provided signage is installed in accordance with 225.37. Proof of hardship may be required.
§ 225.37
Section 225.37 – Add a new Informational Note at the end of Section 225.37 to read as follows:
Informational Note: Where additional approved disconnects are installed in accordance with 225.34, a permanent plaque or directory installed at the entrances of both disconnect locations may be required.
§ 225.52
Section 225.52(B) – Revise Section 225.52(B) to read as follows:
(B) Type. Each building or structure disconnect shall simultaneously disconnect all ungrounded supply conductors it controls and shall have a fault-closing rating not less than the fault current at its supply terminals. The disconnecting means shall comply with 230.64.
Exception: Where the individual disconnecting means consists of fused cutouts, the simultaneous disconnection of all ungrounded supply conductors shall not be required if there is a means to disconnect the load before opening the cutouts. A permanent legible sign shall be installed adjacent to the fused cutouts and shall read DISCONNECT LOAD BEFORE OPENING CUTOUTS.
Where fused switches or separately mounted fuses are installed, the fuse characteristics shall be permitted to contribute to the fault- closing rating of the disconnecting means.
§ 225.60
Section 225.60 – Retitle the Informational Note in Section 225.60 “Informational Note No. 1” and add a new Informational Note at the end of Section 225.60 to read as follows:
Informational Note No. 2: The utility company’s requirements for vertical and horizontal clearance for overhead service conductors may be more stringent.
§ 225.61
Section 225.61 – Retitle the Informational Note in Section 225.61 “Informational Note No. 1” and add a new Informational Note at the end of Section 225.61 to read as follows:
Informational Note No. 2: The utility company’s requirements for vertical and horizontal clearance for overhead service conductors may be more stringent.
§ 230.6
Section 230.6 – Add a new Item (6) to the list of items in Section 230.6 to read as follows:
(6) Where installed in electric service rooms
§ 230.9
Section 230.9 – Add a new Informational Note at the end of Section 230.9 to read as follows:
Informational Note: The utility company’s requirements for vertical and horizontal clearance for overhead service conductors may be more stringent.
§ 230.24
Section 230.24(B)(5) – Add a new Informational Note at the end of Section 230.24 (B)(5) to read as follows:
Informational Note: The utility company’s requirements for vertical and horizontal clearance for overhead service conductors may be more stringent.
§ 230.28
Section 230.28 – Add a new Informational Note at the end of Section 230.28 to read as follows:
Informational Note: The utility company may have more stringent requirements for service mast and service drop installations.
§ 230.30
Section 230.30(A) – Revise the Exception in Section 230.30(A) to read as follows:
Exception: DELETED.
Section 230.30(B) – Add a new Informational Note at the end of Section 230.30(B) to read as follows:
Informational Note: The utility company may have more stringent requirements regarding the use of PVC conduits.
Section 230.30(B)(7) – Revise Item (7) in the list of items in Section 230.30(B) to read as follows:
(7) DELETED.
§ 230.33
Section 230.33 – Revise Section 230.33 to read as follows:
230.33 Spliced Conductors. Service conductors shall be permitted to be spliced or tapped in accordance with 300.5(E), 300.13, and 300.15. For underground service conductors, the requirements of 230.46(C) shall apply.
§ 230.41
Section 230.41 – Revise the Exception after the opening paragraph in Section 230.41 to read as follows:
Exception: A grounded conductor shall be permitted to be uninsulated bare copper, aluminum, or copper-clad aluminum when used as part of a jacketed cable assembly.
§ 230.42
Section 230.42(D) – Add a new Section 230.42(D) to read as follows:
(D) Service Busway. Service busway shall be constructed as required by 368.119.
Section 230.42(E) – Add a new Section 230.42(E) to read as follows:
(E) Services 1,000 kVA and over. Ampacity of the service-entrance conductors for services 1,000 kVA and larger shall not be less than the sum of the maximum ampere ratings of the service disconnecting means. When including fire pump disconnects in the calculation, 125 percent of the fire pump full load amperes shall be added.
Exception: The ampacity of service-entrance conductors need not exceed the maximum demand calculated in accordance with Article 220 for up to a maximum of 4000-ampere per service. For services under 4000-ampere, calculations shall be available upon request by the AHJ.
Informational Note: See 110.2(B)(1) for determining service capacity.
§ 230.43
Section 230.43 – Revise Section 230.43 to read as follows:
230.43 Wiring Methods for 1,000 Volts, Nominal, or Less. Service-entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods:
(1) Rigid metal conduit (RMC)
(2) Intermediate metal conduit (IMC)
(3) Electrical metallic tubing (EMT)
(4) Metallic wireways
(5) Busways
(6) Metallic auxiliary gutters
(7) Rigid polyvinyl chloride conduit (PVC) when installed in accordance with 230.6(1), (2) or (4).
Exception: Exposed PVC service masts on the exterior of residential buildings are permitted within 3,000 feet (914.4 m) of a body of salt water.
(8) Cable bus.
(9) Mineral-insulated, metal-sheathed cable, Type MI
(10) Flexible metal conduit (FMC) not over 6 ft (1.83 m) long or liquidtight flexible metal conduit (LFMC) not over 6 ft (1.83 m) long between a raceway, or between a raceway and service equipment, with a supply-side bonding jumper routed with the flexible metal conduit (FMC) or the liquidtight flexible metal conduit (LFMC) according to the provisions of 250.102(A), (B), (C), and (E).
(11) High density polyethylene conduit (HDPE), underground
(12) Nonmetallic underground conduit with conductors (NUCC)
(13) Reinforced thermosetting resin conduit (RTRC)
Service entrance conductors shall not run within the hollow spaces of frame buildings.
Informational Note: The utility company may have additional or more stringent requirements.
§ 230.44
Section 230.44 – Revise Section 230.44 to read as follows:
230.44 Cable trays. Cable tray systems shall be permitted to support service-entrance conductors. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors listed for use in cable trays and shall be limited to Type MI Cable.
Such cable trays shall be identified with permanently affixed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after installation with a spacing not to exceed 10 ft (3 m) so that the service-entrance conductors are able to be readily traced through the entire length of the cable tray.
§ 230.46
Section 230.46 – Revise Section 230.46 to read as follows:
230.46 Spliced and Tapped Conductors. Service entrance conductors shall be permitted to be spliced or tapped in accordance with 300.5(E), 300.13, 300.15, and 230.46(A) through 230.46(C). Power distribution blocks, pressure connectors, and devices for splices and taps shall be listed. Power distribution blocks installed on service conductors shall be marked “suitable for use on the line side of the service equipment” or equivalent.
Pressure connectors and devices for splices and taps installed on service conductors shall be marked “suitable for use on the line side of the service equipment” or equivalent.
(A) Spliced or tapped service-entrance conductors in the form of multi-section service busway, fabricated and installed in accordance with 368.119, shall be permitted.
(B) Service-entrance conductors shall be permitted to be spliced or tapped at the following locations when using listed terminals and are installed in accordance with applicable equipment standards and 110.2 within a:
(1) Service end box.
(2) Copper detail tap box.
(3) Utility metering enclosure.
(4) Service disconnect enclosure.
(5) Service panelboard.
(6) Service switchboard or service switchgear.
(7) Service busway fabricated and installed in accordance with 368.119.
(8) Power Distribution Block
(C) Spliced or tapped service conductors not installed in accordance with A or B shall utilize listed irreversible compression connectors. All splices and taps shall be located within an identified enclosure and be located outside of the building in accordance with 230.6.
Informational Note: The utility company may have more stringent requirements.
§ 230.52
Section 230.52 – Revise Section 230.52 to read as follows:
230.52. DELETED.
§ 230.54
Section 230.54(C) – Add a new Informational Note at the end of Section 230.54 (C) to read as follows:
Informational Note: Confirm location and requirements of service heads with the electric utility having jurisdiction over the electrical service installation.
Section 230.54(E) – Revise the Exception in Section 230.54(E) to read as follows:
Exception: DELETED.
§ 230.64
Section 230.64 – Add a new Section 230.64 to Part V to read as follows:
230.64 Special Requirements. Where service equipment capacity is 1,000 kVA or larger, 230.64(A) through (F) shall apply.
Informational Note: See 110.2(B) to determine service equipment kVA capacity.
(A) Service rooms shall have a 2-hour fire rating and be constructed of non-combustible materials.
(B) Minimum working space in front of all service disconnecting means shall be 5 ft (1.52 m). When disconnecting means are located face-to-face, the minimum working space shall be 7 ft (2.13 m).
Exception: This requirement shall not apply to service disconnecting means rated 100 amperes or less.
(C) Minimum distance from the floor to uninsulated live parts within the equipment shall be 12 in. (300 mm).
(D) Service equipment requiring rear access shall have a minimum of 3 ft (914 mm) clearance on each side in addition to complying with 110.26(A) or 110.34(A) for rear working space.
(E) If the equipment does not require rear access and the distance from the rear of the equipment to the opposite wall is less than 3 ft (914 mm), then physical barriers shall be installed to prevent access behind the equipment.
Exception: Barriers shall not be required if the rear clearance is 12 in. (300 mm) or less.
(F) There shall be 2 means of egress from the required working space for electrical equipment. A means of egress shall be accessible from each end of the working space. A single means of egress from the working space shall be permitted where either of the conditions in 230.64(F)(1) or 230.64(F)(2) is met.
(1) Unobstructed Egress. Where the location permits a continuous and unobstructed way of egress travel, a single entrance to the working space shall be permitted.
(2) Extra Working Space. Where double the working space specified in Table 110.26(A)(1) or Table 110.34(A) is provided, a single means of egress shall be permitted. The single means of egress shall be located such that the distance from the equipment to the nearest edge of the egress doorway is not less than the minimum clear distance specified in Table 110.26(A)(1) or Table 110.34(A) for equipment operating at that voltage and in that condition. Working space in front of service disconnecting means shall not be less than that required in 230.64(B).
§ 230.70
Section 230.70(B) – Revise Section 230.70(B) to read as follows:
(B) Marking. Each service disconnect shall be permanently marked to identify it as a service disconnect. Legally required labels shall be visible and unobstructed.
Section 230.70(D) – Add a new Section 230.70(D) to read as follows:
(D) Signage. Signage shall be provided when a service is located above street level at the following locations. Such signage shall indicate the specific location of the main electric service room. Signage shall be clearly visible and unobstructed.
(1) All Building Entrances.
(2) Fire Alarm Control Panel location.
§ 230.71
Section 230.71 – Revise Section 230.71 as follows:
230.71 Maximum Number of Disconnects. Each service shall have only 1 disconnecting means unless the requirements of 230.71(B) are met.
(A) General. For the purpose of this section, disconnecting means installed as part of listed equipment and used solely for the following shall not be considered a service disconnecting means:
(1) Power monitoring equipment
(2) Surge-protective device(s)
(3) Control circuit of the ground-fault protection system
(4) Power-operable service disconnecting means
(B) Two to Six Service Disconnecting Means. Two to six service disconnects shall be permitted for each service permitted by 230.2 or for each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5.
(C) Equipment Arrangement. For all new and existing one- and two-family dwellings and other than one-or two-family dwellings for which an application for construction document approval is filed after the effective date of the local law that enacted this code, the 2 to 6 service disconnecting means shall consist of a combination of any of the following:
(1) Separate enclosures with a main service disconnecting means in each enclosure
(2) Panelboards with a main service disconnecting means in each panelboard enclosure
(3) Switchboard(s) where there is only 1 service disconnect in each separate vertical section where there are barriers separating each vertical section
(4) Service disconnects in switchgear or metering centers where each disconnect is located in a separate compartment
Informational Note No. 1: Metering centers are addressed in UL 67, Standard for Panelboards.
Informational Note No. 2: Examples of separate enclosures with a main service disconnecting means in each enclosure include but are not limited to motor control centers, fused disconnects, circuit breaker enclosures, and transfer switches that are suitable for use as service equipment.
§ 230.72
Section 230.72(A) – Add Informational Note at the end of Section 230.72(A) to read as follows:
Informational Note: In existing buildings, if 1 or more of the 2 to 6 disconnects are not able to be grouped due to space constraints, they may be located in a remote location, if special permission is granted by the AHJ, provided signage is installed in accordance with 225.37. Proof of hardship may be required. Where additional approved disconnects are installed, a permanent plaque or directory installed at the entrances of both disconnect locations may be required.
§ 230.85
Section 230.85 – Add an Exception at the end of Section 230.85 to read as follows:
Exception: If the emergency disconnecting means cannot be located in a readily accessible outdoor location, or if the utility metering equipment is located indoors, 1 of the following disconnecting means shall be permitted:
1. A remote disconnecting means provided by the utility
2. An indoor shunt-trip disconnecting means with the control device located in a readily accessible outdoor location and marked, “Remote Emergency Disconnect”
3. An approved equivalent means.
§ 230.96
Section 230.96 – Add a new Section 230.96 to Part VII to read as follows:
230.96 Electrical System Coordination. For systems 1,000 volts and below where the service overcurrent protective device (OCPD) rating or setting is 1200 amperes and above, limited level coordination at 0.1 seconds and above on the time-current curve shall be required between the service OCPD and the next downstream OCPD. For systems exceeding 1,000 volts, full selective coordination shall be required.
Informational Note: See definitions for Coordination, Selective and Coordination, Limited Level.
Exception No. 1: Coordination shall not be required between 2 OCPDs in series with 1 another when no loads are connected in parallel with the downstream device.
Exception No. 2: When the second level OCPD is a single main device having the same ampere rating or setting as the service OCPD, coordination shall be required between the third level devices and the 2 upstream devices.
Exception No. 3: When only 1 OCPD is provided on the transformer secondary, limited level coordination shall be required between the transformer primary and secondary OCPD’s and the third level devices.
§ 250.35
Section 250.35(B) – Revise Section 250.35(B) to read as follows:
(B) Nonseparately Derived System. If the generator is installed as a nonseparately derived system, and overcurrent protection is not integral with the generator assembly, a supply-side bonding jumper shall be installed between the generator equipment grounding terminal and the equipment grounding terminal, bar, or bus of the disconnecting mean(s). The supply-size bonding jumper shall be sized in accordance with 250.102(C) based on the size of the conductors supplied by the generator. Generators that supply 3 wire loads with no grounded conductor, or 4 wire loads with grounded conductor and supply conductors smaller than what is required in 250.102(C) and 445.13 shall be installed as a separately derived system in accordance with 250.35(A).
§ 250.68
Section 250.68(C)(1) – Revise the Exception in Section 250.68(C)(1) to read as follows:
Exception: DELETED.
§ 250.119
Section 250.119 – Revise the Exception No. 1 in Section 250.119 to read as follows:
Exception No. 1: Power-limited Class 2 or Class 3 cables, or communications cables containing only circuits operating at less than 50 volts ac or 60 volts dc where connected to equipment not required to be grounded shall be permitted to use a conductor with green insulation or green with 1 or more yellow stripes for other than equipment grounding purposes.
§ 300.3
Section 300.3(C)(1)(a) – Add a new third paragraph to Section 300.3(C)(1) to read as follows:
Barriers shall be provided to isolate conductors energized from different sources when the system voltage exceeds 250 volts nominal and conductors are protected by first or second level overcurrent protective devices. Sources include service entrance points, secondaries of different transformers, generators, and UPS systems.
§ 300.6
Section 300.6(B) – Revise Section 300.6(B) to read as follows:
(B) Aluminum Metal Equipment. Aluminum raceways, cable trays, cable bus, auxiliary gutters, cable armor, boxes, cable sheathing, cabinets, elbows, couplings, nipples, fittings, supports, and support hardware shall not be embedded in concrete or come in direct contact with the earth unless provided with a protective coating by the manufacturer that is listed for use in direct burial and concrete encasement applications.
§ 300.25
Section 300.25 – Revise the Informational Note in Section 300.25 to read as follows:
Informational Note: For more information, refer to Section 1023.5 of the New York City Building Code.
§ 310.16
Table 310.16 – Modify Table 310.16 as follows:
Delete Type XHWN from the 90 degree columns for copper and aluminum or copper-clad aluminum conductors.
§ 310.17
Table 310.17 – Modify Table 310.17 as follows:
Delete Type XHWN from the 90 degree columns for copper and aluminum or copper-clad aluminum conductors.
§ 310.20
Table 310.20 – Modify Table 310.20 as follows:
Delete Type XHWN from the 90 degree columns for copper and aluminum or copper-clad aluminum conductors.
§ 326.10
Section 326.10 – Revise Section 326.10 to read as follows:
326.10 Uses Permitted. Type IGS cable shall be permitted for use underground, including direct burial in the earth as feeder or branch-circuit conductors.
§ 330.10
§ 330.12
Section 330.12 – Add new Sections 330.12(3) and 330.12(4) to read as follows:
(3) Where used as service conductors.
(4) In any building exceeding 3 floors above grade, where the cable has an outer jacket of PVC, unless the PVC jacketed cable is concealed within non-plenum walls, floors, or ceilings constructed with materials providing a listed 1-hour fire rated assembly.
§ 334.10
Section 334.10 – Revise Items (2), (3), (4), and (5) in Section 334.10 to read as follows:
(2) Multifamily dwellings.
(3) DELETED.
(4) DELETED.
(5) DELETED.
Section 334.10(A) – Revise Item (1) in the list of items in Section 334.10(A) to read as follows:
(1) For both exposed and concealed work in normally dry locations.
Section 334.10(B)(1) – Revise Item (1) in the list of items in Section 334.10(B) to read as follows:
(1) For both exposed and concealed work in dry, moist, damp, or corrosive locations.
§ 334.12
Section 334.12(A)(1) – Revise Item (1) in the list of items in Section 334.12(A) to read as follows:
(1) In any one- or two-family dwelling or multifamily dwelling and any attached or detached garages and storage buildings exceeding 3 floors above grade.
Section 334.12(A)(11) – Add a new Item (11) to Section 334.12(A) to read as follows:
(11) In non-residential buildings.
§ 336.10
Section 336.10 – Revise Item (6) in the list of items in Section 336.10 to read as follows:
(6) DELETED.
§ 336.12
Section 336.12 – Add a new Item (4) to the list of items in Section 336.12 to read as follows:
(4) As fire alarm circuit wiring.
§ 336.104
Section 336.104(A) – Revise Section 336.104(A) to read as follows:
(A) DELETED.
§ 344.10
Section 344.10(A)(2) – Revise Section 344.10(A)(2) to read as follows:
(2) Aluminum RMC. Aluminum RMC shall be permitted to be installed where judged suitable for the environment. Rigid aluminum conduit encased in concrete or in direct contact with the earth shall be provided with listed supplementary corrosion protection.
Section 344.10(B)(2) – Revise Section 344.10(B)(2) to read as follows:
(2) Supplementary Protection of Aluminum RMC. Aluminum RMC shall be provided with listed supplementary corrosion protection where encased in concrete or in direct contact with the earth.
§ 350.12
§ 352.10
Section 352.10 – Add new Sections 352.10(J) and 352.10(K) to read as follows:
(J) Buildings Not Exceeding 3 Stories. In any building or dwelling unit not exceeding 3 stories above grade.
(K) Buildings Exceeding 3 Stories. Unless prohibited elsewhere by other articles of this code; in any building exceeding 3 stories above grade where the PVC conduit is concealed within non-plenum walls, floors, or ceilings constructed with materials providing a listed 1-hour fire rated assembly or PVC conduit encased in concrete, minimum 2 inches (50.8 mm) thick.
§ 355.10
Section 355.10(J) – Add a new Section 355.10(J) to read as follows:
(J) Buildings Exceeding 3 Stories. In any building exceeding 3 stories above grade, only Phenolic type RTRC is permitted.
§ 356.12
Section 356.12 – Add a new Item (5) to the list of items in Section 356.12 to read as follows:
(5) In any building exceeding 3 stories above grade, unless encased in at least 2 in. (50 mm) of concrete or limited to 6 ft (1.8 m) of length exposed.
§ 362.10
Section 362.10(2) – Revise the opening paragraph of Item (2) in the list of items in Section 362.10 to read as follows:
(2) In any building exceeding 3 floors above grade, ENT shall be concealed within walls, floors, and ceilings where the walls, floors, and ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies. The 1-hour-finish-rated thermal barrier shall be permitted to be used for combustible or noncombustible walls, floors, and ceilings.
Section 362.10(2) – Revise the Exception in Section 362.10(2) to read as follows:
Exception to (2): DELETED.
Section 362.10(5) – Revise Item (5) in the list of items in Section 362.10 to read as follows:
(5) Above suspended ceilings where the suspended ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies, except as permitted in 362.10(1)(a).
Section 362.10(5) – Revise the Exception at the end of Section 362.10(5) to read as follows:
Exception to (5): DELETED.
§ 362.12
§ 366.12
Section 366.12 – Add a new Item (3) to the list of items in Section 366.12 to read as follows:
(3) In any building exceeding 3 stories above grade non-metallic auxiliary gutters are prohibited.
§ 368.2
Section 368.2 – Revise the opening Section of Section 368.2 to read as follows:
368.2 Definitions. The definitions in this section shall apply within this article and throughout the Code.
Section 368.2 – Revise Section 368.2 to add a new definition for “Service Busway” in alphabetical order to read as follows:
Service Busway. Busway used to connect from the service point to the line terminals of the service equipment.
§ 368.119
Section 368.119 – Add a new Section 368.119 to Part III to read as follows:
368.119 Service Busway. Service busway shall conform to the specifications in (A) through (I) below or be a listed busway suitable for services.
(A) Ampacity and Ratings of Busbars. Ampacity and ratings of busbars shall be in accordance with 230.42(A).
(B) Length. Service busway shall be limited to a maximum of 10 ft (3.0 m) in length, unless otherwise approved by special permission.
(C) Insulation. Busbars and busbar joints shall be insulated with a material listed for the purpose and rated for use at a minimum of 600 volts.
(D) Enclosure. Enclosure shall be fabricated from aluminum, minimum 1/8 in. (3.2 mm) thick, or other non-magnetic material approved by the commissioner.
(E) Enclosure Vents. Ventilating openings shall be permitted in the sides and bottom of the enclosure. The top of the enclosure must be solid.
(F) Mounting. Busbars shall be mounted on insulating supports, properly spaced and braced to withstand the maximum available short circuit current.
(G) Clearance. A minimum clearance of 4 in. (102 mm) shall be provided from the phase bars to the enclosure.
(H) Plating. All busbar joints and connections shall be plated with silver, tin or nickel.
(I) Accessibility. All busbar joints and connections shall be accessible.
Title 28, Chapter 11, Article 382. Nonmetallic Extensions
Section 382 Part II – After subheading “Part II. Installation” of the Article, add a sentence to read as follows and delete remainder of the Article:
Part II. Installation
382.12 Uses Not Permitted. Installation of non-metallic extensions shall not be permitted.
382.10 DELETED.
382.15 DELETED.
382.26 DELETED.
382.30 DELETED.
382.40 DELETED.
382.42 DELETED.
382.56 DELETED.
382.100 DELETED.
382.104 DELETED.
382.112 DELETED.
382.120 DELETED.
§ 388.12
Section 388.12 – Add a new Item (8) to the list of items in Section 388.12 to read as follows:
(8) In any building exceeding 3 stories above grade.
§ 392.10
Section 392.10(D) – Revise Section 392.10(D) to read as follows:
(D) Nonmetallic Cable Tray. Nonmetallic cable tray shall be listed and its use shall be limited to corrosive areas and areas requiring voltage isolation.
§ 394.12
Article 394 Part II – After subheading “Part II. Installation” of the Article, add a sentence to read as follows and delete remainder of the Article.
Part II. Installation
394.12 Uses Not Permitted. Installation of Concealed Knob-and-Tube Wiring shall not be permitted.
394.10 DELETED.
394.17 DELETED.
394.19 DELETED.
394.23 DELETED.
394.30 DELETED.
394.42 DELETED.
394.56 DELETED.
394.104 DELETED.
§ 404.10
Section 404.10(A) – Revise Section 404.10(A) to read as follows:
(A) DELETED.
§ 406.2
Section 406.2 – Revise the opening paragraph in Section 406.2 to read as follows:
406.2 Definitions. The definitions in this section shall apply only within this article.
Section 406.2. Revise the definition of “Child Care Facility” in Section 406.2 to read as follows:
Child Care Facility. A building or structure, or portion thereof, for educational, supervisory, or personal care services for more than 2 children 7 years old or less.
§ 408.10
Section 408.10 – Add a new Section 408.10 to Part I to read as follows:
408.10 Listing Requirements. Switchboards, Switchgear, and Panelboards shall be listed.
Informational Note: For further information on listing standards, see UL 891 for Switchboards, UL 1558 for Switchgear, and UL 67 for Panelboards.
§ 408.11
Section 408.11 – Add new Section 408.11 to Part I read as follows:
408.11 Modification of Equipment. For the purpose of this section, the modification of equipment shall be considered equipment that is changed in rating, dimension, configuration, or altered from the original manufacturer's design.
The modification of equipment shall use design qualified parts verified under applicable standards and shall be performed by an approved qualified person in accordance with any instructions provided by the manufacturer.
The modified equipment shall be marked with the name, trademark, or other descriptive marking by which the organization responsible for modification of the electrical equipment can be identified, along with the date and description of the modification.
§ 408.60
Section 408.60 – Add a new Section 408.60 to Part IV to read as follows:
408.60 Freestanding Switchboards and Switchgear. Freestanding switchboards and switchgear, which require rear access, shall have hinged rear doors fastened by captive screws or suitable latches. Freestanding switchboards and switchgear, which do not require rear access, shall have non-removable rear covers.
§ 408.61
Section 408.61 – Add a new Section 408.61 to Part IV to read as follows:
408.61 Barriers in Switchboards and Switchgear Rated Over 150 Volts to Ground. Barriers fabricated from materials identified for the use shall be placed between adjacent sections of the switchboard and between the switchboard and its pull box, whether located at the top or bottom of the equipment. All openings in the barriers for busbars and cables shall be as small as practicable.
§ 410.151
Section 410.151(B) – Add an Informational Note to Section 410.151(B) to read as follows:
Informational Note: For energy code compliance, see the applicable provisions of the New York City Energy Conservation Code.
§ 422.12
Section 422.12 – Add an Informational Note at the end of “Exception No. 2” in Section 422.12 to read as follows:
Informational Note: For Safety, Controls, and Electrical requirement for Low-Pressure Steam-Heating Boiler and Low-Pressure Hot-Water Heating Boiler, see New York City Mechanical Code, Chapter 10, “Safety and Pressure Relief Valves and Controls”. For definition of Low-Pressure Hot Water Heating Boiler and Low-Pressure Steam-Heating Boiler refer to the New York City Mechanical Code.
§ 430.5
Table 430.5 – Revise Table 430.5 to add 2 new lines after the line beginning “Resistors and reactors” to read as follows:
Equipment / Occupancy Article Section Services 230 Switchboards, Switchgears, and Panelboards 408
§ 445.10
Section 445.10 – Revise the Informational Note in Section 445.10 to read as follows:
Informational Note: See NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, for information on the location of generator exhaust. Also see New York City Mechanical Code Chapter 8, Section MC 811.
§ 450.14
Section 450.14 – Revise Section 450.14 to read as follows:
450.14 Disconnecting Means.
(A) Location. Transformers, other than Class 2 or Class 3 transformers, shall have a disconnecting means located either in sight of the transformer or in a remote location. Where located in a remote location, the disconnecting means shall be lockable open in accordance with 110.25, and its location shall be field marked on the transformer.
(B) Rating. For all step-up transformer applications over 225 kVA, the selection of the Primary Disconnect and Step-Up Transformer shall be considered as an engineered system and shall be installed in accordance with 110.3(B) and in compliance with 110.9 and 110.10. The Primary Disconnect device shall be capable of handling the maximum inrush current of the specific transformer being installed. The selection shall be made by a registered design professional engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system.
§ 450.25
Section 450.25 – Revise Section 450.25 to read as follows:
450.25 Askarel-Insulated Transformers. New installation of Askarel-insulated transformers shall not be permitted.