Title 15, Chapter 20, Appendix

This section has 24 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Title 15, Chapter 20, Appendix at American Legal Publishing.

TABLES FOR 15 RCNY CHAPTER 20

Table 1 Fixture Units – Table of Equivalents

Fixture Dwellings Commercial/Industrial Buildings Kitchen & Laundry Kitchen Sink 2 4 Laundry Tray (1 to 3 Sections) 3 3 Dishwasher (1/2 Inch Outlet) 1 4 Washing Machine (Automatic) 2 See Commercial Washing Machine Fixture Units Below Bathroom, Washroom & Shower Bathroom Group: (Toilet, Sink & Tub/Shower) (a) Tank 6 11 (b) Flush Valve 8 15 Toilet (a) Tank 3 5 (b) Flush Valve 6 10 Wash Basin 1 2 * Bath Tub 2 4 * Shower 2 4 Urinal 3 6 Commercial Washing Machine & Other Plumbing Outlets Cold Water Only - 5/8 Inch & Smaller 1 2 Hot & Cold Water - 5/8 Inch & Smaller 2 4 Cold Water only - 3/4 Inch 2 4 Hot & Cold Water - 3/4 Inch 4 8 Cold Water Only - 1 Inch 3 6 Hot & Cold Water - 1 Inch 6 12

* A bath tub and the shower over it are considered to be a single fixture.

Table 2 Conversion of Fixture Units to Rate of Flow

Fixture Units Rate of Flow Premises with more than 20% flushometers Premises with less than 20% flushometers (gpm) – 10 8 – 15 12 – 20 15 5 30 20 10 40 25 15 60 33 25 80 39 35 108 43 50 125 49 65 150 55 75 175 60 90 200 64 100 210 66 110 225 70 125 250 74 150 270 78 175 300 83 200 340 92 250 375 100 300 410 105 325 450 115 358 475 120 400 500 130 450 550 135 500 600 140 550 630 150 600 700 155 650 720 165 700 750 170 750 800 180 800 850 185 850 875 190 900 925 195 950 950 200 1,000 1,000 205 1,500 1,500 270 2,000 2,000 330 2,500 2,500 380 3,000 3,000 440 3,500 3,500 490

Table 3 Minimum Size of Service Pipes, Corporation Stops (Taps) and Wet Connections Based on the Rate of Flow in Gallons

Length of Service Pipe (ft.) 10 20 25 30 40 50 55 60 80 100 150 200 250 300 350 400 450 500 550 600 Service Pipe Size (in.) Tap/W.C. Size (in.) Allowable Flow (gpm) 1 3/4 21 15 13 12 10 9 9 8 7 6 4 4 3 3 3 2 2 2 2 2 1 1 21 15 13 12 10 9 9 8 7 6 4 4 3 3 3 2 2 2 2 2 1 1/4 1 37 25 23 21 17 16 15 14 13 12 10 8 7 6 6 5 5 5 4 4 1 1/2 1 55 41 37 34 28 25 24 23 20 18 14 12 11 10 9 8 8 7 7 7 1 1/2 1 1/2 55 41 37 34 28 25 24 23 20 18 14 12 11 10 9 8 8 7 7 7 2 1 1/2 100 84 75 70 59 52 50 48 41 37 28 24 21 19 18 16 15 15 14 13 2 2 100 84 75 70 59 52 50 48 41 37 28 24 21 19 18 16 15 15 14 13 2 1/2 2 150 150 135 125 105 93 90 86 73 65 46 39 35 31 29 27 25 23 22 21 3 3 220 220 210 200 165 145 140 135 120 105 81 70 61 56 51 48 45 42 40 38 4 3 300 300 300 290 250 220 210 200 170 155 130 119 110 104 98 94 90 86 82 78 4 4 390 390 390 390 350 320 305 290 250 220 165 142 126 114 105 98 92 86 82 78 6 4 600 600 600 600 600 550 525 500 430 380 285 245 215 195 185 177 170 165 162 158 6 6 880 880 880 880 880 880 840 810 700 620 490 420 370 335 310 290 270 254 245 235 8 6 1,550 1,550 1,550 1,550 1,550 1,550 1,550 1,550 1,400 1,300 1,010 865 765 670 640 595 555 525 500 475 10 8 2,450 2,450 2,450 2,450 2,450 2,450 2,450 2,450 2,450 2,300 1,840 1,575 1,395 1,260 1,160 1,080 1,015 955 905 865 12 10 3,500 3,500 3,500 3,500 3,500 3,500 3,500 3,500 3,500 3,500 2,950 2,530 2,245 2,030 1,870 1,740 1,635 1,535 1,460 1,400

Flows are based on a maximum pressure loss of two (2) psi in the service pipe or a maximum velocity of ten (10) ft per second, whichever results in a lesser rate of flow

Assumptions:

(a) Hazen-Williams Coefficient C = 100

(b) Loss through tap is negligible

(c) Loss through curb valve and house control is negligible

(d) Loss through meter is negligible

(e) Loss through backflow preventer is negligible

(Amended City Record 7/26/2021, eff. 8/25/2021)

Table 4 Excavations for Corporation Stops (Taps) and Wet Connections

Wet Connections Corporation Stops Size Dimension of Openings Size Dimension of Openings Wet Conn. Water Main A B C D E Water Main F G H I 3" & 4" 6" 8'-2" 4'-0" 1'-0" 7'-2" 2'-0" 4" 4'-4" 3'-0" 2'-2" 1'-6" 3" & 4" 8" 8'-4" 4'-0" 1'-1" 7'-3" 2'-0" 6" 4'-6" 3'-0" 2'-3" 1'-6" 3" & 4" 12" 8'-8" 4'-6" 1'-3" 7'-5" 2'-3" 8" 4'-8" 3'-0" 2'-4" 1'-6" 3" & 4" 16" 9'-1" 4'-10" 1'-5" 7'-8" 2'-5" 12" 5'-0" 3'-0" 2'-6" 1'-6" 3" & 4" 20" 9'-5" 5'-2" 1'-7" 7'-10" 2'-7" 16" 5'-4" 3'-0" 2'-8" 1'-6" 6" 8" 8'-7" 5'-0" 1'-1" 7'-6" 2'-6" 20" 5'-8" 3'-0" 2'-10" 1'-6" 6" 12" 9'-0" 5'-0" 1'-3" 7'-9" 2'-6" 24" 6'-0" 3'-0" 3'-0" 1'-6" 6" 16" 9'-4" 5'-0" 1'-5" 7'-11" 2'-6" Where to corporation stops are placed in the same opening, make G 4'-0" for corporation stops up to and including 1" in size, and 5'-0" for corporation stops 1 1/2" and 2" in size. Note: Refer to Figure #1 for Dimensions of Openings. 6" 20" 9'-8" 5'-2" 1'-7" 8'-1" 2'-7" 8" 12" 9'-2" 5'-0" 1'-3" 7'-11" 2'-6" 8" 16" 9'-6" 5'-2" 1'-5" 8'-1" 2'-7" 8" 20" 9'-10" 5'-6" 1'-7" 8'-3" 2'-9" 12" 16" 9'-10" 5'-4" 1'-5" 8'-5" 2'-8" 12" 20" 10'-2" 5'-8" 1'-7" 8'-7" 2'-8" 16" 20" 10'-8" 5'-8" 1'-7" 8'-11" 2'-10"

Table 5 Specification 32-P-3:93, Division of Municipal Supply Services Red Brass Pipe

Nominal Size (Inches) Outside Diameter (Inches) Wall Thickness (Inches) Nominal Weight (Pounds Per Foot) 3/4 1.050 0.114 1.27 1 1.315 0.126 1.78 1 1/4 1.660 0.146 2.63 1 1/2 1.900 0.150 3.13 2 2.375 0.156 4.12 2 1/2 2.875 0.187 5.99 3 3.500 0.219 8.56 4 4.500 0.250 12.7

Table 6 Specification 32-T-1:94, Division of Municipal Supply Services Seamless Copper Tubing

Nominal Size (Inches) Outside Diameter (Inches) Wall Thickness (Inches) Nominal Weight (Pounds Per Foot) 3/4 0.875 .065 0.641 1 1.125 .065 0.839 1 1/4 1.375 .065 1.04 1 1/2 1.625 .072 1.36 2 2.125 .083 2.06

Table 7 Specification ANSI/AWWA/C151/a21.51-91 Ductile Iron Pipe

Nominal Size (Inches) Outside Diameter (Inches) Wall Thickness (Inches) Class Nominal Weight (Pounds Per Foot) 3 3.96 0.28 52 9.9 4 4.80 0.29 52 12.6 6 6.90 0.43 56 26.7 8 9.05 0.45 56 37.2 10 11.10 0.47 56 48.0 12 13.20 0.49 56 59.9 14 15.30 0.51 56 72.5 16 17.40 0.52 56 84.4 20 21.30 0.54 56 109.3

Table 8 Meter Size Selection Table

Meter Size Meter Type Max. Peak Flow Rate (gpm) 3/4" Displacement 25 1" Displacement 50 1 1/2" Displacement 100 2" Displacement 150 1 1/2" Vertical Turbine 100 2" Turbine 180 3" Turbine 1,000 4" Turbine 1,250 6" Turbine 2,500 8" Turbine 3,500 10" Turbine 5,500 12" Turbine 7,000 1" Single-jet 20 1 1/2" Single-jet 90 2" Single-jet 130 3" Single-jet 200 4" Single-jet 350 6" Single-jet 650 2" Compound 120 3" Compound 350 4" Compound 600 6" Compound 1,600 8" Compound 2,500 10" Compound 3,500

Figure 1. Excavation for Taps and Wet Connections.

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 2. Methods for Connecting Service Pipe.

Figure 3. House Service Pipe Connection.

Figure 4. Service Pipe in Subway Air Vent.

Figure 5. Swing Joint Connection Between City Water and Well Water Supply.

Figure 6. Arrangement for Use of a Backflow Preventer when Using a Fire Hydrant.

Figure 7. Typical Meter Setting for Displacement Meters. (N.T.S.)

(Amended City Record 7/26/2021, eff. 8/25/2021)

Figure 8. 1" – 2" Domestic Service with Fire Protection Sprinklers for Single-Jet or Electronic Meter

(Amended City Record 7/26/2021, eff. 8/25/2021)

Figure 9. Typical for Turbine Single-Jet, or Electronic Meters. (N.T.S.)

(Amended City Record 7/26/2021, eff. 8/25/2021)

Figure 10. Typical Meter Setting with By-Pass. Typical for Turbine, Single-Jet or Electronic Meters. (N.T.S.)

(Amended City Record 7/26/2021, eff. 8/25/2021)

Figure 11. Water Meter Enclosure for 3/4" - 2" Meters. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 12. Installation of 3/4" - 2" Water Meter in Enclosure with Service Pipe 4 Ft. or Less Below Grade. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 13. Installation of 3/4" & 2" Water Meter in Enclosure with Service Pipe More than 4 Ft. Below Grade. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 14. Detail: Brick Setting for Bottom Enclosure. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 15. Section Concrete Foundation for Bottom of Enclosure in Sidewalk and Driveway Areas. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 16. Pit Under Inclined Area. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 16A. Pit Under Inclined Area. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 16B. Pit Setter Stabilizer Bar. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 16C. Pit Setter Stabilizer Bar. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 17. Typical Meter Vault.

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 18. 2" or Larger Combined Service DCV Option. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 19. Typical Condominium Metering. Refer to 15 RCNY § 20-05 (1). (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 20. Meter in Existing Indoor Pit. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.

Figure 21. Wall Mounting Meter Setting. (N.T.S.)

Editor's note: the image displayed above is the highest quality available to the publisher.