15 RCNY K Notes, Terms, and Conditions

1. Reimbursement amounts shown are for the cost of the meter, fittings, and pipe work necessary for its installation and/or replacement only. Except for the installation of a strainer in meter replacement projects, the cost of any other work that may be necessary to correct deficiencies or improve a building’s piping or general construction work is not included in the scheduled amounts and will not be reimbursed. The reimbursement will be equal to the scheduled amount for each size and type of meter installed or the actual amount paid to a plumber, whichever is less. The NYC Licensed Plumber shall provide the owner with a one-year warranty on labor.

2. Meters installed in outdoor pits are only allowed for locations when a meter location indoors is not possible as determined and approved in writing by DEP. Failure to have DEP pre- inspect possible outdoor pit meter locations exposes the owner to the possibility that DEP will determine that an indoor installation could have been performed and that only reimbursement for an indoor installation will be provided. Outdoor pit installations are generally limited to a) homes that have finished basements where the water service enters the home and b) confined locations where neither a positive displacement nor a single-jet meter can be installed indoors. The reimbursement amounts indicated above include the cost of the meter, all required appurtenances, and the meter pit itself, which must conform to the DEP’s regulations and specifications for meter pit installations that are contained in the “List of Approved Water Meters and Related Equipment with Typical Water Meter Setting Details”. The “pit meter” reimbursement amounts apply only to pits dug outside. They do not apply to the expansion of concrete pits inside a basement, garage, or home.

3. All work must comply with the most recent version of “Rules and Regulations Governing and Restricting the Use and Supply of Water” (Rules of the City of New York, Title 15, Chapter 20) and DEP’s “List of Approved Water Meters and Related Equipment”.

4. As noted in Section C, the following meters and applications do not qualify for reimbursement: new construction meters required to comply with Local Law 53/1985 (substantial renovations or new construction), fire service meters on dedicated fire services, submeters of any kind, meters for an end use which may qualify for a wastewater allowance or billing program under the Water and Wastewater Rate Schedule, or the replacement of meters that were removed illegally.

5. The NYC Licensed Plumber and applicant shall follow the specific application procedures described in the Department’s Booklet, “Reimbursable Metering Program”.

6. The reimbursement for strainers applies only if the existing meter lacks a strainer. The NYC Licensed Plumber must submit photos of the “before” and “after” conditions.

7. Existing compound meters must be replaced with single-jet, advanced turbine (Sensus OMNI C2 or T2), or electromagnetic meters. Turbine meters will generally be replaced with either another approved turbine meter or an electromagnetic meter. A single-jet meter may be used to replace a turbine only if the maximum flow rate (in gallons per minute) on any building house pump does not exceed the maximum continuous flow rate for the meter. This must be reviewed and approved by the BCS Bureau Engineer.

8. Please refer to the Approved Meter List for circumstances under which hot water meters will be replaced with reimbursement. Only large consumers of hot water within flat-rate accounts will be considered.

9. This reimbursement schedule shall supersede all previous reimbursement schedules for permit applications submitted after the effective date.

10. DEP reserves the right to photograph installations.

11. Reimbursement for meter repairs shall be limited to those manufacturers that offer complete replacement measuring element kits for their products. A “repair” shall include replacement of the register head(s), measuring element(s), seals, gaskets, strainer basket, and any other additional parts included in the manufacturer’s “kit”. The completed permit must include a final reading from the old meter. “Repair” does not include conversion of a meter with mechanical or other non-magnetic couplings to modern functionality. Meters of such age must be replaced. Meter Repairs do not involve any repairs other than those specified here.