2 RCNY Chapter 4 Regulations Applicable to Existing Installations*, part 1 of 2

§ 4-01 to § 4-09: 9 sections.

§ 4-01. Scope

Open this section

The rules set forth in this chapter govern the design, installation, operation and maintenance of devices, equipment and systems in certain occupancies. In general, these rules were applicable to buildings constructed prior to December 6, 1968. Consult the applicable provisions of the New York City Building or Construction Codes in effect on or after December 6, 1968, to determine whether these rules apply to buildings constructed or altered on or after December 6, 1968.

(Added City Record 4/4/2019, eff. 5/5/2019)

§ 4-02. Automatic Door Operators

Open this section

All doors for which approved automatic operators which open by swinging inwardly or by sliding are used shall not constitute more than 50 percent of the required exits for any one particular building, and when such a door operator is used, only half the width of that door can be counted towards the total exit space required for a particular building. All such door operators shall meet the following requirements:

(a) They shall be equipped so that in the event of power failure or fire they may be opened manually in the direction of exit travel by not more than a 30 pound force; and,

(b) They may be closed manually when necessary to safeguard a means of egress; and,

(c) Swinging panels shall provide a clear opening width in the 90° open position of not less than 32 inches, with no single leaf less than 24 inches in width; and,

(d) When swinging panels are contained in sliding door units, they shall be operable when the sliding leaf or leaves retract to any point in the opening cycle; and,

(e) They shall meet the requirements of the American National Standard for Power Operated Doors, ANSI A156.10-1979; and

(f) They shall meet the requirements of ANSI/UL 325 (or ANSI/UL 1578 when it is adopted), shall be listed or labeled by a nationally recognized independent testing laboratory, and shall be under an inplant follow-up inspection service. These requirements shall be applicable to all such door operators approved in the past and those which shall be approved in the future, but shall not be applicable to particular installations of approved door operators which were installed before April 15, 1980.

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-03. Marking of Transparent Glass Doors and Fixed Adjacent Glass Sidelights

Open this section

(a) Scope. These rules shall be applicable to all structures or any part thereof excepting one and two family structures.

(b) Definitions.

Sidelights. Fixed panels of transparent glass which form part of or are immediately adjacent to and within six feet horizontally of the vertical edge of an opening in which transparent glass doors are located. For purposes of this section, a sidelight shall consist of transparent glass in which the transparent area above a reference line 18 inches above the adjacent ground, floor or equivalent surface is 80 percent or more of the remaining area of the panel above such reference line.

Transparent glass. Material predominantly ceramic in character which is not opaque and through which objects lying beyond are clearly visible. For the purpose of this section, rigid transparent plastic material shall be construed as transparent glass.

Transparent glass door. A door, manually or power actuated, fabricated of transparent glass, in which the transparent area above a reference line 18 inches above the bottom edge of the door is 80 percent or more of the remaining area of the door above such reference line.

Transparent safety glazing materials. Materials which will clearly transmit light and also minimize the possibility of cutting or piercing injuries resulting from breakage of the material. Materials covered by this definition include laminated glass, tempered glass (also known as heat-treated glass, heat-toughened glass, case-hardened glass or chemically tempered glass), wired glass, and rigid plastic.

(c) Requirements.

(1) Transparent glass doors and fixed adjacent transparent glass sidelights shall be marked in two areas on the glass surface thereof.

(2) Fixed adjacent transparent glass sidelights 20 inches or less in width with opaque stiles at least one and three-quarters inches in width shall be exempt from the marking requirements.

(3) Where the ground, floor or equivalent surface area in the path of approach to a fixed adjacent transparent glass sidelight from either side for a minimum distance of three feet from such sidelight is so arranged, constructed or designed as to deter persons from approaching such sidelight or a permanent barrier is installed in the path of approach, the sidelight shall be exempt from this requirement.

(4) Decorative pools, horticultural planting or similar installations shall be considered as indicating that the ground, floor or equivalent surface area is not a path of approach. Planters, benches and similar barriers which are securely fastened to the floor or wall to prevent their removal shall be considered as blocking the path of approach provided they shall be not less than 18 inches in height from the ground, floor or equivalent surface and extend across at least 2/3 of the total width of the glazed area of the sidelight.

(5) Fixed adjacent transparent glass sidelights which are supported by opaque sill and wall construction of at least 18 inches above the ground, floor or equivalent surface immediately adjacent shall be exempt from the marking requirements.

(6) Display windows in any establishment, building or structure which fall within the definition of a sidelight shall be exempt from the marking requirements if the top of the supporting sill and wall construction is not less than 18 inches above the ground, floor or equivalent surface immediately adjacent and the interior area is occupied with merchandise or similar displays to clearly indicate to the public that it is not a means of ingress or egress.

(d) Marking locations.

(1) One such area shall be located at least 30 inches but not more than 36 inches and the other at least 60 inches but not more than 66 inches above the ground, floor or equivalent surface below the door or sidelight. The use of horizontal separation bars, muntin bars or equivalent at least one and one-half inches in vertical dimension that extend across the total width of the glazed area and are located at least 40 inches but not more than 50 inches above the bottom of the door or sidelight is permitted in lieu of markings.

(2) The marking design shall be at least four inches in diameter if circular or four inches in its least dimension if elliptical or polygonal, or shall be at least 12 inches in horizontal dimension if the marking is less than four inches in its least dimension. In no event shall the vertical dimension of any marking including lettering be less than one and one-half inches in height. In addition to horizontal muntin bars, separation bars or equivalent, any of the following methods may be used to alert persons to the presence of transparent glass doors and fixed adjacent transparent glass sidelights in their path of movement:

(i) Chemical etching

(ii) Sand blasting

(iii) Adhesive strips not less than one and one-half inches in vertical dimension extending across at least two-thirds of the total glazed area

(iv) Decals

(v) Paint, gilding or other opaque marking materials

(vi) Opaque door pulls or push bars extending across at least two-thirds of the total width of the glazed area.

(e) Replacement and new installations.

(1) Any transparent glazing material used for replacement in existing transparent glass doors after January 1, 1969 shall be transparent safety glazing material. Transparent safety glazing material shall be used in all new transparent glass doors installed after January 1, 1969. The manufacturer's permanent identification mark denoting safety glazing materials shall be visible on the glass after installation of the door.

(2) Replacement of fixed adjacent transparent glass sidelights after January 1, 1969 shall be of transparent safety glazing material or annealed glass at least one-half inch in thickness. New fixed adjacent transparent glass sidelights installed after January 1, 1969 shall be of transparent safety glazing material or annealed glass at least one-half inch in thickness. The manufacturer's permanent identification mark denoting safety glazing material shall be visible on the glass after installation of the sidelight. Note: If safety glazing material is not immediately available as replacement glass in transparent glass doors and fixed adjacent transparent glass sidelights, temporary relief from the requirements rule may be sought by petitioning the Board of Standards and Appeals of the City of New York for a modification.

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-04. Dry Load Capacity of Dry Cleaning Units

Open this section

In connection with Article II, § 4, Subsection 53, Subdivision (a) of the Zoning Resolution, the dry load capacity of a dry cleaning unit shall be figured on the basis of 2.8 lbs. per cu. ft.

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-05. Dry Cleaning Establishments Pursuant to the Zoning Resolution

Open this section

(a) Application of rules. These rules shall be deemed to apply only to those excepted dry cleaning establishments existing or hereafter established, pursuant to Article II, §§ 4(a), Subd. 53, 4-A, 4-B and 4-C of the Zoning Resolution. These rules shall not be deemed to modify or repeal Chapter 4 of Title 27 of the Administrative Code of the City of New York.

(b) Definitions. For the purpose of these rules, the following definitions shall apply.

Dry cleaning establishment. The term "dry cleaning establishment" shall mean any room, place or space in which dry cleaning is performed, as defined in the Zoning Resolution.

(i) Dry cleaning establishments to which these rules shall apply shall be divided into two classes: Class A and Class B.

(ii) Class A dry cleaning establishments shall mean dry cleaning establishments in which the dry cleaning solvent used in the dry cleaning unit shall be non-flammable and non-combustible when tested in a Tagliabue open cup tester and as rated by the Fire Commissioner.

(iii) Class B dry cleaning establishments shall mean dry cleaning establishments in which the dry cleaning solvent used in the dry cleaning unit shall have a flashpoint of not lower than 138.2 F. when tested in a Tagliabue open cup tester and as rated by the Fire Commissioner.

(iv) For other purposes a dry cleaning establishment shall be as defined in Chapter 4 of Title 27 of the Administrative Code.

Existing. The term "existing" shall mean those dry cleaning establishments established prior to January 1, 1953.

Flammable liquid solvents. The term "flammable liquid solvents" shall mean such as will emit a flammable vapor at a temperature below 100 degrees Fahrenheit when tested in a Tagliabue open cup tester.

Hereafter established. The term "hereafter established" shall mean those dry cleaning establishments established after January 1, 1953.

"Retail", "retail purposes" and "retail business". For the purposes of §§ 4-A and 4-C of the Zoning Resolution the terms "retail", "retail purposes" and "retail business" shall refer only to those dry cleaning establishments which perform services on articles conveyed directly by a retail customer to such dry cleaning establishment or collected directly from and delivered to the retail customer by any vehicle or any other means of effecting the same and such dry cleaning establishment directly processes such articles for such customer.

"Spotting" or "Sponging". The term "spotting" or "sponging" shall mean the local application of a "flammable liquid solvent" to remove spots of dirt, grease, paint or stains from wear-apparel, textiles, fabrics or articles of any other sort. All other terms used shall be as defined in the Zoning Resolution, Administrative Code, Multiple Dwelling Law, or Labor Law, when not inconsistent with the specific terms defined herein.

(c) Approvals.

(1) It shall be unlawful to use any premises for any hereafter established dry cleaning establishments without filing plans of that portion of the premises to be so used with the Department of Buildings and obtain its approval. Any prior approval shall be in compliance with this rule.

(2) The requirements of 2 RCNY § 4-05(c)(1) shall not apply to existing dry cleaning establishments.

(3) No dry cleaning unit shall be installed unless such unit is approved by the Board of Standards and Appeals.

(4) The use of any existing commercial premises, as defined in Article 4, Administrative Code, for any dry cleaning establishment shall not be deemed to be a Change of Occupancy within the meaning of § C26-185.0 of the Administrative Code.

(5) The dry load capacity of all dry cleaning units shall be rated by the Board of Standards and Appeals on the basis of 2.8 pounds per cubic foot of the volume of the washing compartment for each washing cycle.

(6) No dry cleaning solvent shall be used unless such solvent has been tested and rated by the Fire Commissioner.

(7) It shall be unlawful in any dry cleaning unit approved by the Board to use any solvent having a flashpoint other than that for which the dry cleaning unit has been approved by the Board.

(8) No non-conforming existing dry cleaning establishment shall be enlarged or extended unless such extension or enlargement be made in a conforming manner.

(d) Restrictions on locations and areas.

(1) No hereafter established dry cleaning establishment shall have a gross floor area exceeding the aggregate of 2,000 square feet to be used for dry cleaning, pressing and incidental operations as well as space used for storage, service of customers and the convenience of employees. The square foot area limitation shall apply to the aggregate of all space so used on all floors and mezzanines of the premises involved above the cellar or basement thereof. Additional space may be used on a lower floor which is either a basement or cellar provided that on such floor there shall be no dry cleaning and no storage of recently cleaned articles, but such area may include, in conjunction with the dry cleaning establishment, unless otherwise prohibited by law, ordinary storage, boilers, washing equipment, compressors, pumps and filtration equipment. In calculating the gross floor area pursuant to this paragraph (1), the area restriction shall not include the area used by lawful non-dry cleaning operations of a multiple use type of service establishment where, in addition to dry cleaning, there may be a launderette, shirt laundering, shoe repairing, and fur storage.

(2) No Class B dry cleaning establishment hereafter established shall be permitted within any building, except that this paragraph (2) shall not apply to those establishments created prior to the effective date of these rules:

(i) which is of wood frame construction;

(ii) which is classified as a public building pursuant to § C26-235.0 of the Administrative Building Code;

(iii) any part of which establishment is within 20 feet of any public building, as defined in § C26-235.0 of the Administrative Code.

(e) Egress. The means of egress in all dry cleaning establishments shall be in conformity with the applicable provisions of the building laws and regulations governing such establishments. In addition thereto, all establishments shall conform to the following:

(1) A three foot (3 feet 0 inches) wide aisle providing access from the main work area to the required means of egress shall be provided. Such required aisle shall not be obstructed by any fixed obstruction in any manner whatsoever.

(2) In all hereafter established dry cleaning establishments all required exit doorways shall be arranged to swing outwardly in the direction of the egress.

(f) Fire prevention – Class B establishments. All hereafter established Class B dry cleaning establishments shall comply with the following, except that subdivision (f) shall not apply to those establishments created prior to the effective date of these rules:

(1) (i) No power or heating boiler shall be permitted in the same area or space where dry cleaning units are located, whether on the cleaning floor or floors or cellar or basement level unless either

(A) the boiler or boilers shall be enclosed in a 3-hour unpierced masonry enclosure and entered only from the outer air; or

(B) the boiler or boilers shall be enclosed in a 3-hour masonry enclosure with a one-hour fireproof self-closing door which opens into a ventilated vestibule similarly enclosed and entered by a one-hour fireproof self-closing door opening onto the interior of the premises or establishment.

(ii) The ceiling of all such boiler rooms as required in 2 RCNY § 4-05(f)(1)(i) and the adjoining entrance vestibule referred to in 2 RCNY § 4-05(f)(1)(i)(B) above shall be fire-retarded with one-hour fire resistive material.

(2) Non-fireproof enclosing partitions and ceilings within six feet of any dry cleaning unit shall be fire-retarded with one-hour fire resistive materials and doors and with two approved automatic wet pipe sprinkler heads located over the cleaning unit which may have its source of supply from the house water system.

(3) All openings from any such dry cleaning establishment leading to a fire escape shall be equipped with a one-hour fireproof self-closing door or fireproof window assembly.

(4) Except as provided in 2 RCNY § 4-05(f)(1)(i), there shall not be employed in any such dry cleaning establishments any device or apparatus employing flame or fire which is likely to produce an exposed spark except electric apparatus placed at least five feet above the floor, or approved type of "explosion proof electric motors". In such establishments all lighting shall be fitted with keyless sockets and all switches and receptacles shall be placed at least four feet above the floor. Nothing contained in this paragraph (4) or 2 RCNY § 4-05(f)(1)(i) shall prohibit the installation of any gas, oil or electric heating device of a type approved by the Fire Commissioner under such conditions as he shall prescribe.

(g) Fire prevention – Class A establishments. All hereafter established Class A dry cleaning establishments shall comply with the following, except that this subdivision (g) shall not apply to those establishments created prior to the effective date of these rules:

(1) Unless otherwise specifically exempted by law, no power or heating boiler shall be permitted in the same area or space where dry cleaning units are located unless such boiler or boilers shall be enclosed in a one-hour fireproof partition and entered by a one-hour fireproof self-closing door whether from the interior of the premises or establishments or to the outer air.

(2) All ceilings of all such boiler rooms as provided in 2 RCNY § 4-05(g)(1) shall be fire-retarded with one-hour fire resistive material.

(3) All openings from any such dry cleaning establishment leading to a fire escape shall be equipped with a fireproof self-closing door or fireproof window assembly.

(h) Fire prevention – all dry cleaning establishments. All existing or hereafter established dry cleaning establishments whether Class A or Class B shall comply with the following: (1) The provisions of § 27-4265 of the Administrative Code.

(2) It shall be unlawful to store any flammable liquids or solvents in quantities aggregating more than five gallons without a permit as provided in Subchapter 9 of Chapter 4 of Title 27 of the Administrative Code.

(3) All flammable liquids and solvents used for spotting and sponging shall be contained in approved individual metal containers not exceeding two-quart capacity each.

(4) All sludge or residue removed from a dry cleaning unit shall be placed in a metal container not exceeding 55 gallons of capacity with a tight fitting cover and shall be removed from the premises and disposed of in a lawful manner.

(5) All solvent used in the dry cleaning unit shall be either

(i) received and stored in metal containers not exceeding 55 gallons each and pumped directly into a dry cleaning unit or units by means of a detachable leakproof pump and pipe system, or

(ii) received and stored in a tank or tanks in accordance with the rules of the Board of Standards and Appeals relating to the receiving and storing of fuel oils and pumped directly into a dry cleaning unit or units by means of a closed leakproof pipe and pump system.

(i) Ventilation.

(1) All hereafter established dry cleaning establishments whether Class A or Class B shall be equipped with adequate ventilation to provide at least four complete changes of air volume an hour of such establishments during the operation of any dry cleaning units, and such ventilation as is otherwise required by law.

(2) All Class A dry cleaning establishments shall have sufficient ventilation so as to prevent an excessive concentration of solvent vapors in the dry cleaning establishment. An excessive concentration of solvent vapors shall be that which exceeds the average of 200 parts of solvent vapors per one million parts of air during any working day.

(3) The direct equipment exhausts or vents of all dry cleaning establishments whether Class A or Class B shall terminate to the outer air in the following manner:

(i) At least 7 feet above the roof, street, yard or court grade on which it opens of the premises in which said establishment shall be located, and

(ii) The exhaust shall be under static pressure by reason of a mechanical fan, and

(iii) The terminal of the exhaust shall be at least five feet from any window or ventilating opening if said ventilating window or ventilating opening lies on the same plane as the exhaust terminal and when the ventilating windows, or other ventilating openings lie on a plane which faces in the direction of the exhaust terminal such terminal shall be at least 10 feet away from the same, and

(iv) All direct equipment exhausts or vents shall be provided with mesh lint arrestors which shall be kept clean unless lint traps are provided on the units, and

(v) The requirements of 2 RCNY § 4-05(i)(3)(i) and (iii) shall not apply to those establishments created prior to the effective date of these rules.

(j) Operating precautions.

(1) A printed notice embodying these rules shall be posted in a conspicuous place in all dry cleaning establishments.

(2) The proprietor of any Class A establishment shall furnish to any person cleaning out a dry cleaning unit an approved type respirator for his use during the process of cleaning out any such unit.

(3) All equipment shall be installed in such manner as to minimize noise, vibration, smoke, and odors, and other forms of nuisances to the occupants of the premises in which such cleaning establishment may be located or to the occupants of any adjacent premises.

(k) Penalties. Any violation of these rules shall be subject to the penalties prescribed in the Zoning Resolution therefor, in addition to other penalties prescribed by law.

(l) Severability. If any term, part or provision of any of the aforesaid rules shall be held unconstitutional or ineffective in whole or in part, such determination shall not be deemed to invalidate the remaining terms, parts or provisions of these rules.

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-06. Installation of Interior Fire Alarm Signal Systems

Open this section

(a) Scope. These rules apply to all hotels, as defined in the Administrative Code and the Multiple Dwelling Law; to all lodging houses having more than 15 sleeping rooms, or accommodating more than 15 lodgers above the first or ground story; to all public and private hospitals and asylums having more than 15 rooms, or accommodating more than 15 patients or inmates above the first or ground story; to all nurseries accommodating more than 30 children, or having a Board of Health permit for the accommodation of more than 30 children; to all Turkish or other special treatment bath houses where there are sleeping accommodations for more than fifteen persons on the premises; to all department stores having two or more departments where the public is admitted above the second floor; to all public schools, and to all single and tenant factory buildings, as defined in the Labor Law and specifically required by § 279 of said Law.

(b) Definitions.

Approved. The term "approved" shall mean approved by the Board of Standards and Appeals.

Coded closed circuit fire alarm signal systems. The term "coded closed circuit fire alarm signal systems" shall mean a fire alarm signal system consisting of sending stations and signaling devices operated on supervised closed electric circuits which transmits rounds of coded signals to indicate the floor or portion of the same from which the alarm was sent.

Commissioner. The term "Commissioner" shall mean the Fire Commissioner of the fire department specifically charged with the enforcement of law relating to interior fire alarm systems in the City of New York.

Hereafter. The term "hereafter" shall mean after December 31, 1936.

Heretofore. The term "heretofore" shall mean before December 31, 1936.

Non-coded closed circuit fire alarm signal system. The term "non-coded closed circuit fire alarm signal system" shall mean a fire alarm signal system consisting of sending stations and signaling devices operated on supervised closed electric alternating current circuits, so arranged that the operation of any station will automatically sound the signaling devices throughout all portions of the building.

(c) General

(1) All fire alarm signal systems and devices shall be approved by the Board of Standards and Appeals.

(2) All devices and equipment that have been approved by the Board, shall have securely fastened thereon, a manufacturer's plate bearing the words "Approved by the Board of Standards and Appeals – No _____ ", together with any other electrical data that the Commissioner may require.

(d) Examination and approval of plan. Before the installation or extension of any fire alarm system, specifications and plans thereof, showing complete details of the proposed installation, shall be submitted by the owner or his agent to the Commissioner for examination and approval.

(e) Classification.

(1) Fire alarm signal systems shall be classified as follows:

(i) Non-coded closed circuit fire alarm systems.

(ii) Coded closed circuit fire alarm systems. The code numbers that are used shall be submitted for approval to the Commissioner and shall be sounded at least four (4) times for each operation of sending station.

(2) A non-coded closed circuit system shall be so arranged that the operation of any station will automatically sound the signaling devices until hook is restored to its original position; and in the break-glass type until the glass has been replaced.

(3) Coded closed circuit system shall be divided into three (3) classes:

Class 1 – General Systems.

Class 2 – Pre-signal or dual operation systems.

Class 3 – Unit and general systems – or Duplex systems.

Special systems.

(4) Class 1 systems shall be a general alarm system of the coded closed circuit type so arranged that the operation of any station will cause the signaling devices to sound the code number of that station at least four (4) times throughout the entire building.

(5) Class 2 system shall be a pre-signal or dual operation system of the coded closed circuit type so arranged that the operation of any station will cause the sounding of the signaling devices located in the engine room, elevator shafts, basement or other places in the building where the members of the fire brigade work or assemble.

(i) Approved means shall be provided at each station, so arranged that a subsequent operation of any station shall cause the sounding of all signaling devices throughout the building.

(ii) This subsequent operation shall be performed with the aid of a key or plug designed so as to prevent unauthorized sounding of the general alarm.

(iii) The pre-signal or dual operation key or plug shall be so designed that it can be readily identified by the person whose duty it would be to use same.

(6) Class 3 system shall be a unit and general alarm or Duplex system of the coded closed circuit type so arranged that the operation of a station within a unit will cause all of the signaling devices in that unit and all of the signaling devices on the general alarm circuit to sound the code numbers of the unit and zone at least four (4) times.

(i) A register and time stamp, acceptable to the Commissioner, may be used in connection with a Class 3 system.

(ii) The register, if of closed circuit type, shall be operated from a separate closed circuit control board or from separate panel isolated by barrier from main control panel in main control board cabinet.

(iii) Approved closed circuit trouble and unit annunciators shall be installed as part of all Class 3 systems when required by the Commissioner.

(7) Special systems shall include a complete Class 1, 2 or 3 systems supplemented by special circuits for the operation of other fire alarm devices in the systems; or electric control systems for stopping machinery, closing doors or ventilators as may be required by the Commissioner; or to call the central station of a private operating company or the fire department. Automatic fire detecting systems may be connected to operate an interior fire alarm system when connected thereto by an approved coded transmitter. In no case shall the transmitter be considered to replace the standard approved interior fire alarm station, except where a transmitter has been approved for both purposes. The special control circuits shall be separate and distinct from the fire alarm system but shall be brought into action whenever the fire alarm system is set in operation.

(f) Systems permitted in factory and other buildings.

(1) Non-coded closed circuit fire alarm systems shall be permitted only in a factory building not exceeding five (5) stories in height having not more than twenty-five hundred (2,500) square feet in area in any one story and having not more than one hundred (100) persons in a single factory; nor more than fifty (50) persons in a multiple tenant factory above the first or ground floor.

(2) Coded closed circuit systems shall be required in a factory building exceeding the requirements of 2 RCNY § 4-06(f)(1).

(3) Special fire alarm signal systems shall be permitted in factory buildings at the direction of the Commissioner.

(4) Coded closed circuit systems shall be required in all other types of buildings requiring an interior alarm system.

(g) Installation and construction requirements.

(1) All work in connection with the installation of a fire alarm signal system shall be performed in a neat and workmanlike manner to the satisfaction of the Commissioner.

(2) In any fire alarm system there shall be not more than fourteen (14) direct nor more than ten (10) alternating current gongs or other approved sounding devices connected in one circuit.

(3) There shall not be in any fire alarm system more than twenty (20) stations connected to one circuit or loop.

(4) All gongs and signaling devices shall be located not less than eight (8) feet to the center above the floor.

(5) All fire alarm stations shall be located five (5) feet three (3) inches from handle to floor.

(6) An instruction card properly marked and framed under glass shall be installed at each fire alarm station.

(7) All materials and devices used in fire alarm signal systems shall be securely fastened in position in a manner satisfactory to the Commissioner.

(8) For fastening to masonry walls, through bolts, metal expansion shields or toggle bolts shall be used.

(9) Wood screws shall be used for fastening equipment to wood surfaces.

(10) The use of nails or wood or fibre plugs is prohibited.

(11) When fire alarm apparatus is mounted upon a wooden back board, such back board shall be not less than seven-eighths (7/8) inch thick, impregnated with a non-absorptive compound. The back board shall be so mounted as to provide an air space of at least one-quarter (1/4) inch between the back board and the wall for free circulation of air.

(12) All electrical conductors shall be installed in standard rigid metal conduits, in accordance with the Electrical Code of the City of New York.

(13) All conduits shall be grounded to a water pipe by approved ground clamps with a conductor equal to the largest conductor used on the system and the smallest size ground conductors used shall not be less than No. 10 B. & S. gauge.

(14) The wiring used and the connections made between component parts of the alarm system shall conform to the requirements of the Electrical Code of the City of New York.

(15) Electrical conduits shall enter only at the side or the bottom of the control cabinet.

(16) In coded fire alarm systems using break glass type stations, at least one (1) extra glass shall be provided for each station in the system.

(17) All openings in walls, floors or ceilings where conduits pass through, shall be properly fire stopped.

(18) Conduits shall contain only conductors used in connection with the fire alarm system.

(19) Where wires pass underground from one building to another, they shall be enclosed in conduits, and shall be lead encased. Wires between buildings, when not run in conduit, shall be at least equivalent in conductivity and tensile strength to No. 8 B. & S. gauge copper wire for box and signaling circuits and shall be supported at least every seventy-five (75) feet on approved glass insulators and brackets, and be protected by approved lightning arrestors when required by the Commissioner. As far as possible, they shall run under, rather than over, electric light or power wires.

(h) Sending stations. There shall be at least one (1) fire alarm sending station in each story of any building requiring a manual fire alarm signal system, located in a natural path of escape from fire at a readily accessible location designated by the Commissioner, which always shall be kept unobstructed. Additional sending stations shall be installed so that no point on any floor in a non-fireproof building shall be more than one hundred (100) feet distant from the nearest sending station upon such floor. In fireproof or sprinklered buildings, the distance shall not be more than one hundred and fifty (150) feet.

(i) Sounding devices. Sounding devices shall be sufficient in number to be clearly audible to all occupants of the building.

(j) Subdivided buildings. Where a building is subdivided by fire walls, each section shall be deemed a separate building for the purpose of fire alarm signal system installations. One control board may be used, if so arranged, as to operate the signaling devices in each section of the building independently; or may be operated as one unit when deemed necessary by the Commissioner.

(k) Mixed occupancy. In buildings requiring fire alarm signal system, of which parts are occupied by other than factory tenants and in which the condition of construction and occupancy warrant the establishment of a local fire brigade, the Commissioner may accept dual operation systems.

(l) Existing installations. Fire alarm signal systems heretofore installed in buildings in the City of New York and installed in accordance with the rules then in force, shall be accepted as long as they are maintained in proper working order.

(m) Sources of electrical energy.

(1) Sources of electrical energy used in operating fire alarm signal systems shall be:

(i) Generated electric power, not exceeding a potential of 250 volts, including:

(A) Central Stations

(B) Isolated Plants

(ii) Storage battery power Either source of power shall be used under conditions and limitations as set forth by the Commissioner.

(2) One source of energy shall be connected to the fire alarm system at all times. All auxiliary sources of energy when required shall be so arranged and controlled by an automatic switch that when the primary source of energy fails, the secondary source will be automatically connected to the fire alarm signal system.

(3) Central stations. When the energy for a fire alarm signal system is supplied by a central station power system it shall be accepted as the sole source of supply; connections shall be made on the street side of the service switch except that in case where the master meter is within thirty (30) feet of the main switch of the premises, permission may be given by the Commissioner to connect to the house side of the meter when a certificate of recent date from an authority of competent jurisdiction has certified that the electrical wiring throughout the premises is in a safe condition. When a house side connection is made, the fire alarm cutout shall be the first connection and as near as possible to the meter. Same shall be enclosed in a locked or sealed metal cabinet, painted fire department red and stenciled "Interior Fire Alarm." Fuses shall be of the enclosed cartridge type. Screw plug fuses will not be accepted. The cutout shall be a three pole cartridge fuse cutout with neutral fuse replaced by a solid copper bar. The smallest size fuse used on a fire alarm system shall be fifteen (15) amperes.

(4) Isolated plants. Energy from isolated electric light and power plants shall be used for fire alarm signal systems only when there is more than one generating unit and the plant is always in operation when the building is occupied. When only one generator unit is employed, the source of energy shall be supplemented by storage battery or other auxiliary service. The fire alarm service connection shall be taken from the main bus of the house switchboard and installed in accordance with the service requirements under central stations. When a house side connection is made, the fire alarm cutout shall be the first connection and as near as possible to the meter. Same shall be enclosed in a locked or sealed metal cabinet, painted fire department red and stenciled "Interior Fire Alarm." Fuses shall be of the enclosed cartridge type. Screw plug fuses will not be accepted. The cutout shall be a three pole cartridge fuse cutout with neutral fuse replaced by a solid copper bar. The smallest size fuse used on a fire alarm system shall be fifteen (15) amperes.

(5) Storage battery.

(i) When a storage battery equipment is used as the sole source of current for a fire alarm signal system, the storage battery shall be provided in duplicate; or an approved type trickle charger may be substituted for the duplicate storage battery located in a room sufficiently ventilated. Such installations shall be equipped with a switchboard or panel of approved material on which are mounted volt meters, ammeters, circuit breakers, fuses, resistances, switches, starting devices for motors, field rheostats for generator and other apparatus required for charging and operating the battery.

(ii) Storage batteries shall be so located and ventilated as to avoid danger of sparking contacts igniting flammable gases or vapors. In no case shall a storage battery be located in the same room with a gas meter.

(n) [Repealed.]

(o) [Repealed.]

(p) [Repealed.]

(q) Alarm boxes.

(1) In fire alarm signal systems the metal case enclosing the exposed or surface alarm boxes shall be of cast iron or other approved cast metal, and drilled and tapped to receive the conduit. When exposed to moisture the box shall be enclosed in a suitable weatherproof outer shell. In new buildings, approved back-boxes embedded in the wall may be used and the conduits shall be properly secured by lock nuts and bushings.

(2) All current carrying parts shall be insulated from parts of opposite polarity with approved insulating material.

(3) All coded pull lever type stations shall be fitted with a door to protect the pull lever against accidental injury. Such door shall have a handle rigidly secured thereon and be so constructed as to open readily. The wording "In Case of Fire Open Door and Pull Down Lever" in raised letters or equivalent instructions shall appear on the door.

(4) All break-glass type fire alarm boxes shall be provided with suitable hammers on chains of approved type attached to or near the boxes with which the glass can readily be broken; or other methods may be used to break the glass when approved by the Commissioner.

(5) All break-glass boxes shall have in raised letters on the fronts, the words "Fire Alarm – In Case of Fire Break Glass," and such additional instructions as may be necessary to send an alarm.

(6) The box or station shall be so designed that once started, the proper transmission of a complete set of signals cannot be interfered with by manipulation of its starting device.

(7) Each closed circuit coded box or station shall be arranged to send a definite code of signals to indicate the floor or portion of same on which it is located.

(8) No less than three (3) or more than twenty (20) taps or blasts shall be given at each revolution of the code wheel.

(9) The code wheel shall revolve at least four (4) times for each operation of its starting device and be of factory machine cut metal or other approved material properly insulated from ground.

(10) Boxes or stations used in systems in which whistles, vibrating bells or horns are employed shall be so timed that the sounding devices will give the code signals clearly.

(11) Contact point shall be in multiple.

(12) Contact points and contacts of the testing devices shall be of silver or other approved material and be of the scraping type, secured in a substantial manner to phosphor bronze or other approved material springs, and be so designed as to positively break a circuit carrying one-tenth (1/10) ampere at two hundred and fifty (250) volts actual working conditions.

(13) Lever boxes shall be so designed as to automatically wind when the lever is pulled for an alarm. Boxes requiring glass replacements shall be so arranged that replacement cannot be made without resetting mechanism for another alarm.

(14) Where it becomes necessary to install more than one set of contacts operating from code wheel, permission in writing in advance must be obtained from the Commissioner. This shall not include pre-signal features.

(15) The box shall have plainly marked thereon its code signal number.

(r) Non-coded boxes.

(1) Non-coded closed circuit fire alarm stations may be operated by a break-glass or pull lever device so arranged that the alarm cannot be interfered with except by resetting or replacement of the glass by an authorized person.

(2) The construction and materials shall be equal to that of the standard approved type coded closed circuit station except that the contacts shall be of ample capacity to safely carry the entire operating current of the gong circuit without excessive heating.

(s) Station testing devices.

(1) Each fire alarm system shall be provided with an auxiliary device to test the signaling devices located in one of the alarm boxes or mounted on the control board. Such testing devices shall be arranged to make the test without operating the break wheel of the box or interfering with the dual operating feature.

(2) Provision shall be made for a silent test of coded alarm box mechanisms without operating the signaling devices. Such device shall be designed to prevent any person except those in authority from operating the same and to prevent the possibility of the box being left inoperative after the test.

(t) Supervising current.

(1) A small current flow to constantly supervise each circuit shall be maintained. A milliammeter, or other approved current indicator shall be provided and so connected as to indicate the supervising current.

(2) The supervising circuit shall be provided with a trouble bell operating on open circuit arranged to ring continuously in case of failure of the system. The trouble bell shall be so located that it will be within audible range of some responsible person in the building and shall be connected to the electric light or power service in the building. Permission may be granted by the Commissioner to connect the trouble bell to battery of approved type.

(3) Trouble bells shall not be fitted with silencing switches except in such a manner that the act of silencing the bell by the operation of the switch, automatically and positively transfers the trouble signal to a red lamp on the control board fed by some auxiliary source of current supply. This auxiliary source of current shall be a house lighting circuit or any other approved source.

(4) The trouble bell shall be of an approved design of the vibrating type and give a distinctive signal.

(u) Protection of sending and sounding devices.

(1) In fire alarm signal systems, all moving parts of sending stations and sounding devices shall be enclosed in metal casing, made dust-proof and damp-proof when necessary, and clearly marked with instructions for use.

(2) Whenever necessary, hammer rods of gongs shall be suitably protected against mechanical injury or derangement by the use of a guard or other suitable means. If subject to mechanical injury, the entire device shall also be enclosed in a protecting case made of suitable wire mesh netting or perforated metal. All casings shall be insulated from current carrying parts, and shall be grounded to the conduit.

(v) Standards of electric alarm apparatus.

(1) All electrically actuated apparatus used in fire alarm systems shall be so designed and constructed that it will operate satisfactorily at a current flow of twenty-five (25) percent above or below the normal operating current.

(2) Insulation.

(i) Insulating materials used in electric fire alarm signal systems shall be varnished, cambric, bakelite, mica or other approved insulating material. The use of fibre or paper as an insulating material for fire alarm signal systems shall not be permitted.

(ii) The insulating material used on electric fire alarm signal systems shall be capable of withstanding an insulation break-down test of one thousand (1,000) volts A.C. plus twice operating voltage applied for one (1) minute.

(3) Electro-magnets.

(i) Electro-magnet windings shall be impregnated with an insulating moisture repelling compound or shall be of silk enameled wire.

(ii) Electro-magnet coils to be used on alternating current when composed of enameled wire shall have an additional approved insulation on each wire. The coils may be of the form wound type.

(iii) A protective cover to prevent mechanical injury shall be provided over the entire coil.

(iv) Electro-magnet coils shall be securely fastened to prevent floating.

(v) Electro-magnet cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.

(vi) Electro-magnet cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and promote efficiency.

(vii) Electro-magnet cores of relays and gongs shall be treated to prevent corrosion. Paint or varnish for this purpose shall not be used.

(viii) Non-magnetic freeze pins shall be used which will prevent two magnet surfaces coming in actual contact.

(4) Gongs.

(i) Gong shells shall be pinned to prevent turning and then securely fastened to its support by a machine cap screw at least three-eighths (3/8) inch in diameter.

(ii) Gong shells shall be covered with an approved rust preventive.

(iii) The gong shell support and gong frames shall be cast in one piece.

(5) Wiring.

(i) All connections shall be properly protected, securely made and where subject to motion shall be of approved flexible wire.

(ii) All wiring of control board, station and gong circuits shall conform to the Electrical Code of the City of New York.

(iii) Binding posts shall be of such a character that the wire is held between two flat surfaces.

(iv) Binding posts shall be mounted on an approved terminal block or insulating strip spaced not nearer than one-half (1/2) inch to each other, unless separated by approved barriers.

(6) Relays.

(i) The armatures of all relays shall depend on gravity or magnetic attraction for their operation.

(A) This action may be assisted by flat type springs.

(B) The use of spiral springs is prohibited.

(ii) Adjustments shall be of such a character that they can be securely locked.

(iii) Contact points shall be ample in area not only to take care of current used in operation but to insure long life and shall be of pure silver, or other approved material, properly riveted to their support.

(iv) Contact arms shall be of phosphor bronze and be of the dead beat type.

(v) Contact assemblies shall be of such a character that their operation will be of a scraping self-cleansing nature.

(vi) The use of condensers across contacts to absorb the arc or in any part of a fire alarm circuit is prohibited.

(vii) Relays shall be free from objectionable hum when used on alternating current.

(w) Time limit delay device.

(1) All gong circuits shall and special signal apparatus may, when required by the Commissioner, be protected by a Time Limit Delay Device. Note: This time limit delay device shall consist of a heating coil so designed that the normal operating current will have little or no effect upon a thermostatic bi-metal bar or strip contained therein. Any abnormal increase over operating current or the continued accumulative heating effect thereof after a period of not less than three (3) minutes nor more than twenty (20) minutes shall cause the thermostatic element to expand. The expansion of this element shall automatically open the source of current supply to the gongs or devices protected.

(2) The operation of the time limit delay device shall cause the trouble bell to ring.

(3) Time limit delay devices shall be so connected in the fire alarm circuit that their operation will not open the fire alarm box circuits.

(4) Where due to the extent of the installation, it becomes necessary to install a number of time limit delay devices, the operation of a single time limit delay device shall not affect other sounding devices similarly protected.

(5) A contactor relay to operate the sounding devices shall be provided on all direct current gong circuits exceeding three (3) and all alternating current gong circuits exceeding two (2) in number.

(6) Gong circuits not requiring contactor relays shall be operated by contacts properly placed on the armature of the box circuit relay.

(7) A separate time limit delay device, contactor relay, contactor supervisory relay and gong supervisory relay shall be provided for each four (4) gong circuits or fraction thereof.

(8) Switches. Triple pole, double throw, broken back knife switches properly supervised and connected to emergency resistors shall be provided on all box and gong circuits when they exceed three (3) in number.

(9) Instruments. A separate approved milliammeter or other approved current indicating device shall be provided for the box circuit and each four (4) gong circuits on the control board when the gong circuits exceed three (3) in number. A separate milliammeter shall be provided to indicate the supervisory current of contactor relays and emergency switch circuits. This meter shall be know as the Board Meter.

(10) Resistors.

(i) Resistors shall be mounted on the front or face of control panels and shall be of vitreous enameled type. Note: Wire wound resistors, when protected by a suitable metal guard, may be used in special cases when approved by the Commissioner.

(ii) Ferrule or knife contact type resistors shall not be used.

(iii) A protective resistor shall be placed in the negative or live lead of all box circuits to protect the contacts of the boxes in the event of a ground. This resistor shall be not less than three hundred (300) nor more than seven hundred and fifty (750) ohms resistance.

(x) Control boards.

(1) All relays, current indicators, resistances, time delay devices and other apparatus used in connection with the operation and supervision of closed circuit fire alarm signal systems shall be properly mounted on a panel of approved material, in a metal cabinet provided with lock and key. The control board shall be located in a place subject to the least vibration, free from moisture, flammable gases, dust and mechanical injury and under frequent view of a responsible occupant of the building delegated by the owner to be in charge and holding a Certificate of Fitness issued by the Commissioner.

(2) Control board panels shall be of insulating material such as ebony asbestos, bakelite or other approved materials at least one-half (1/2) inch in thickness.

(3) Control boards mounted in each cabinet shall be fastened in each corner.

(4) Provision shall be made for ample wire gutted space around the panel.

(5) Conduit knockouts shall not be provided in top of control board cabinet.

(6) A wiring diagram of the alarm system and card of instructions properly marked and securely fastened shall be provided within the control board cabinet. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be properly framed under glass.

(7) All control board cabinets shall be provided with sight hole and glass panel to make meters on the inside of the cabinets visible from the outside.

(8) Wire in gutter spaces shall be properly laced in a neat and workmanlike manner on all control boards having a capacity for more than three (3) gong circuits.

(y) Battery cabinets.

(1) All electrical batteries for fire alarm signal systems shall be placed in substantial protecting cabinets thoroughly ventilated, elevated not less than one (1) nor more than five (5) feet above the floor and located in clean, dry and cool places where the temperature will not be less than forty (40) nor more than one hundred and ten (110) degrees Fahrenheit. Main battery cabinets shall be so constructed that the condition of the elements may be observed without disturbing the cells.

(2) Metal battery cabinets shall be constructed of sheet iron or steel, not less than No. 15 U.S. gauge in thickness, properly reinforced by angle irons with self-closing doors provided with lock and key and wood shelves not less than seven-eighths (7/8) of an inch thick, unless the battery is of the spray-proof type, properly fastened and secured to prevent sagging. The interior and the exterior of the cabinet shall be protected with three (3) coats of asphaltum compound, each coat to be thoroughly dry before the next is applied, or with baked enamel.

(3) Wood battery cabinets shall be constructed of the first grade of kiln dried wood and not less than seven-eighths (7/8) of an inch thick and shall be provided with self-closing door and approved lock. The shelves shall not be less than seven-eighths (7/8) of an inch thick properly fastened and secured to prevent sagging. The cabinet shall be of substantial construction painted on the interior with three (3) coats of asphaltum compound and on the exterior with three (3) coats of lead paint or two (2) coats of varnish.

(4) Storage batteries may be placed on enameled metal battery racks, provided the batteries are installed in a place where they will not be subject to mechanical injury, and will be ventilated as required in 2 RCNY § 4-06(m)(5)(ii).

(z) Painting of equipment. All enclosing cases for fire alarm apparatus shall be finished in fire department red, except where special permission is given by the Commissioner to deviate from this requirement.

(aa) Closed circuit annunciators.

(1) Annunciators used in connection with Class 3 fire alarm systems shall be of an approved closed circuit type.

(2) The annunciators shall have approved type of relays equipped with a suitable target, shutter or other indicating device. The indicating device shall have marked thereon a suitable description of the purpose it serves.

(3) The printed designation on unit or building annunciator's indicators shall be legible. The mechanism shall be so arranged that once operated the indicating device shall be reset manually.

(4) A unit annunciator shall be so designed that the operation of any station in the unit shall cause a visible and audible signal.

(5) The unit annunciator shall be actuated by contact on code wheel of the fire alarm station or by contact on a relay connected to the fire alarm box circuit. In no case shall the station fire alarm circuit be used for this purpose.

(6) Trouble annunciators shall be so arranged that the indicating device will reset automatically when cause of trouble has been removed.

(7) The trouble annunciator shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit, control board or unit annunciators.

(8) The trouble annunciator shall be actuated by the operation of contacts on all supervisory relays. Each relay of this annunciator shall be provided with two (2) sets of contacts so arranged that one will operate the one hundred and ten (110) volt trouble signal, the other set to actuate the register if a register is used.

(9) A trouble buzzer switch and lamp shall be mounted on the inside of each unit annunciator cabinet on the panel.

(10) A trouble bell, switch and lamp shall be mounted on the inside of each trouble annunciator cabinet on the panel. Trouble bell may be placed at a distance from the annunciator by special permission of the Commissioner.

(11) Relay drops of annunciator shall be so designed that vibration from without or that caused by the trouble signal within will not operate the indicating devices.

(12) All annunciators shall be installed in a separate red enameled steel cabinet provided with an approved lock and key.

(13) Annunciators shall be properly marked with white letters at least one (1) inch high with the words: "Fire Alarm Annunciator," Zone – or "Fire Alarm Trouble Annunciator," whichever the case may be.

(bb) Licensed contractors. No person shall install, alter or repair or cause to be installed, altered, or repaired electrical wiring or apparatus for fire alarm systems in any building, except a person holding a license, or a special license in accordance with Chapter 3 of Title 27 of the Administrative Code. The enforcing authority shall not approve any installation, alteration or repair done in violation of this rule.

(cc) Used or rebuilt apparatus. Used apparatus shall not be re-used for any interior fire alarm system under these rules and regulations until the same has been reconditioned in the shop of a reliable manufacturer building interior fire alarm apparatus which has been approved by the Board of Standards and Appeals. Approval in writing shall be obtained from the enforcing authority prior to installation. The enforcing authority shall not approve for use, used or reconditioned apparatus that may not give satisfactory service.

(Renumbered and amended, City Record 4/4/2019, eff. 5/5/2019)

§ 4-07. Minimum Sound Levels of Audible Alarms of Smoke Detectors

Open this section

The requirement of the Board of a minimum sound level of 85 decibels in a 10 foot radius from the source of audible alarms of smoke detectors is applicable to approvals of all smoke detectors.

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-08. Automatic Fire Extinguishing Systems

Open this section

(a) Definitions.

Automatic fire extinguishing system. The term "automatic fire extinguishing system" shall mean:

(i) A system of piping connected to one or more acceptable sources of water supply, which system is provided with approved distributing devices so arranged and located as to automatically discharge an effective spray over the interior of the building in the event of fire therein; or

(ii) A system of piping and distributing devices automatically controlled, connected to an adequate supply of chemical fire extinguishing media of an approved type suitable for the hazard involved.

Factory building. The term "factory building" shall mean a factory building as defined by Section 10 of the New York State Labor Law. Section 10. "Factory building" means a building, shed or structure which or any part of which, is occupied by or used for a factory, and in which at least one-tenth or more than twenty-five of all the persons employed in the building are engaged in work for a factory, but shall not include a building in a city having a population of more than one million, used exclusively by one employer and in which not more than one-tenth of all the persons employed therein are engaged in work for a factory and which, except for such factory work, would be classified as a mercantile establishment. The provisions of this chapter shall apply to any part of a building occupied or used as a factory, except as otherwise provided by this subdivision.

Non-flammable.

(i) The term "non-flammable" as used in these rules when applied to solids shall mean materials which will not ignite and continue to burn when brought in contact for five seconds with an open flame or when in contact with glowing materials.

(ii) The term "non-flammable" as used in these rules when applied to liquids shall mean any liquid which will not generate a flammable vapor at a temperature of 300° F or less when tested in a Tagliabue open cup tester.

Volatile flammable oils or solvents. The term "volatile flammable oils or solvents" as used in these rules shall mean any liquid mixture or compound that will generate a flammable vapor at a temperature of 110° F or less when in a Tagliabue open cup tester.

(b) Medium hazards.

Bagging, manufacturing

Bags, Cloth, Paper or Burlap, manufacturing

Bakeries except retail bakeries and except bakeries where all products baked are consumed on the premises

Bamboo or Rattan Products, manufacturing

Baskets (other than metal), manufacturing

Bookbinding Boots or Shoes, manufacturing

Burlap, manufacturing Buttons, manufacturing, except non-flammable buttons

Candles, or wax products, manufacturing

Canvas, manufacturing

Cardboard, manufacturing

Cereal Mills

Chemical Works (except where volatile flammable oils or solvents are used, stored or manufactured)

Cloth, Backing

Cloth, Dyeing or Printing Works

Cloth, manufacturing

Confectionery Products, manufacturing

Cotton Batting or Waste, manufacturing

Dry Cleaning and Dyeing Industrial Plants (except those using volatile flammable oils)

Distilleries

Envelope, manufacturing

Excelsior or Excelsior Products, manufacturing or storage

Feed, Flour or Grist Mills

Felt or Felt Products, manufacturing

Furniture, manufacturing, repairing or refinishing

Furs or Fur Products, manufacturing or processing

Gloves, manufacturing

Handbags, Luggage or Trunks, manufacturing

Hats, manufacturing

Knitting, Weaving or Embroidering

Laundries

Leather Goods, manufacturing

Lithographing

Millinery, manufacturing (except custom)

Paper Pulp Mills

Paper Boxes or Cartons, manufacturing

Pencil, manufacturing

Picture Frame, manufacturing

Plastic Articles (except non-flammable)

Printing except incidental to primary use with area not exceeding 2,000 feet

Rag sorting or processing

Rope, Cordage and Twine, manufacturing

Rubber Products, manufacturing

Rugs, manufacturing

Shades, Window, manufacturing

Silk, manufacturing

Straw Goods, manufacturing

Synthetic Yarns or Fabric, manufacturing, except non-flammable

Tanneries

Tobacco Products, manufacturing

Umbrella, manufacturing

Upholstering

Woodworking

(c) High hazards.

Aluminum, powdered, manufacturing

Artificial Flowers, manufacturing

Artificial Leather, manufacturing

Carpet cleaning, using volatile flammable oils or solvents

Chemical manufacturing using volatile flammable oils or solvents

Combustible or flammable mixtures, manufacturing

Compressed Gases, manufacturing, flammable or explosive

Cotton Picking and Opening Operations

Dry Cleaning Plants, using volatile flammable solvents

Enameling (except vitrous enameling) using more than 2 qts. per day or storing more than 20 gals.

Essential Oils or Perfumes, manufacturing

Feathers, processing

Fireworks

Linoleum, manufacturing

Linseed Oil

Mills

Lithographing Inks (except non-flammable), manufacturing

Magnesium (powdered), manufacturing or processing (Chemical Extinguishing system only)

Mattress manufacturing or repairing

Matches, manufacturing

Nail Polish, manufacturing

Nitrocellulose Products, manufacturing or processing

Painting or Lacquering using more than 2 qts. per day or storing more than 20 gals.

Paint, Varnish, Enameling, Lacquers, Lithographing ink (except non-flammable), manufacturing

Pharmaceutical Products, manufacturing

Plastics, manufacturing, except non-flammable

Raincoats, manufacturing (using rubber)

Rubber Cement, manufacturing

Shoddy Mills

Silk Screen Printing

Starch or Sugar Mills

Surgical Sutures, manufacturing, processing or packing

Solvent Extracting (other than non-flammable)

Tallow, manufacturing

Tires (rubber), re-capping, re-treading or vulcanizing

Volatile, Flammable Oils, Solvents, or Mixtures, manufacturing

Woodworking with painting, varnishing, lacquering or shellacking

(Renumbered City Record 4/4/2019, eff. 5/5/2019)

§ 4-09. Fire Extinguishing Appliances – Sprinkler Systems

Open this section

(a) General requirements. The rules contained herein cover the general details of a sprinkler equipment only. Before an equipment is installed or before a present equipment is remodeled, involving 10 or more heads on any floor, complete working plans shall be submitted for approval to Fire Department, with such specification forms as may be required by the Fire Commissioner, except for the installation of the connection to the water main service pipe and meter setting, which shall be approved by the Bureau of Water Supply and Wastewater Collection.

(b) Plans. These plans shall be drawn to an indicated scale; give correct address and points of compass; show longitudinal and cross sections of the building with story heights, and the essential features of the construction, viz., size, location and direction of joists, timbers or other structural members. They shall also indicate the location and size of water supplies, connecting pipes, feed mains and risers, gate, check, alarm and dry-pipe valves, as well as the location, spacing, number and type of sprinklers. Plans for non-automatic dry-pipe systems shall indicate the location and number of actuating devices.

(c) Final approval. Upon approval of preliminary plans such number of sets of clean, corrected plans on cloth as the Fire Commissioner may require, not exceeding three (3), shall be filed for final approval of the Fire Commissioner. A certified copy of the approved plans shall be forwarded to the Department of Buildings by the Bureau of Fire Prevention. If the structure is equipped with a standpipe (fire line) the plans shall include a note to that effect. When entirely completed in accordance with the approved plans, application shall be made to the Bureau of Fire Prevention for test and acceptance of the completed installation. When the sprinkler equipment is approved the applicant will be so advised in writing by the Bureau of Fire Prevention.

(d) Definitions.

Automatic extinguisher systems. "Automatic extinguisher systems" shall consist of a system of piping connected to one or more acceptable sources of water supply, provided with distributing devices so arranged and located as to discharge and diffuse automatically an effective stream or spray over the interior of the building area.

(e) Classification of sprinkler systems. For the purpose of these rules, sprinkler systems shall be classified as:

(1) Automatic Wet Pipe Systems, in which all pipes and sprinkler heads are at all times filled with water;

(2) Automatic Dry Pipe Systems, in which the pipes and sprinkler heads are filled with air, either compressed or at atmospheric pressure, and the water supply is controlled by a Dry Pipe Valve as defined in 2 RCNY § 4-09(11)(5).

(3) Non-Automatic Systems, in which all pipes and sprinkler heads are maintained dry, equipped with a siamese fire department connection. An automatic thermostatic or pneumatic fire alarm with direct connection to Central Office of one of the operating fire alarm companies or Fire Department Headquarters shall be provided in connection with all non-automatic sprinkler systems.

(f) Approved devices. Automatic sprinklers and accessory appliances shall include all devices approved as such by any recognized standard research laboratory on the endorsement of approval by resolution of the Board of Standards and Appeals.

(g) Water supply. Approved sources of water supply shall be classified as Automatic and Auxiliary.

(1) Automatic Sources shall include the Gravity Tank, the Pressure Tank, or direct connection to the Public Water System.

(2) Auxiliary Sources shall include the Fire Pump and the Fire Department siamese connection.

(h) Gravity tank. Gravity tanks shall contain an available quantity of water sufficient to supply twenty-five percent (25%) of the number of sprinkler heads in the average protected fire area for twenty (20) minutes, but not less than 5,000 gallons; and the bottom of the tank shall have an elevation of not less than twenty (20) feet above the highest line of sprinklers below the main roof. Gravity tank or tanks shall not be required to be elevated above the highest sprinklers in penthouse having an area less than 2,500 sq. ft., unless such penthouse contains a hazardous occupancy, or is used for the storage of combustible material. Where a split system is installed the bottom of the tank or tanks need not be elevated more than 3 feet above the main roof or 20 feet above the highest sprinkler fed from an intermediate tank. Where a tank capacity in excess of 25,000 gallons is required by this subdivision (h), the amount of water in excess of 25,000 gallons shall be provided in separate tanks not grouped together except when tanks of unlimited capacities are supported on structures altogether independent of buildings. The tank shall be filled through a fixed pipe, independent of the sprinkler piping, not less than two (2) inches in size, discharging into the top of the tank. The water supply and connections shall be capable of supplying the tank at a rate of not less than sixty-five (65) gallons per minute. The filling pipe shall be carried up inside a frost-proof casing and may extend through tank bottom to discharge at top of tank above full water level. The portion of pipe inside tank must be of brass or copper or other noncorrosive material. Tanks shall not be fed through sprinkler lines. The sprinkler and standpipe tanks may be fed from a common source of supply, either a pump or a direct service main connection, provided that there are separate feed mains from the basement or lowest story and a control valve in each feed line in a pump or engine room. The overflow pipe shall be not less than two (2) inches in diameter for tanks up to 30,000 gallons capacity and not less than three (3) inches in diameter for larger tanks. The top of the overflow pipe shall be three (3) inches below the top of the staves in wooden tanks and one (1) inch from the top in steel tanks. The pipe may extend through the bottom of tank provided the portion inside tank is of brass or copper or other non-corrosive metal and without joints or it may extend through side of tank. For tanks over roofs overflow pipes shall terminate not more than twenty-four (24) inches above roof and shall be fitted with a 90 degree elbow. At each gravity or pressure tank there shall be provided a 4 inch emergency drain, and for gravity tanks in excess of ten thousand (10,000) gallons capacity a six inch (6") emergency drain must be provided. Such drain to be equipped with an O.S. and Y. gate valve arranged to discharge on the roof of building not more than twenty-four (24") above roof and shall be fitted with a 90 degree elbow. When the tank or tanks are on a separate structure independent of buildings, drain connections to be arranged to discharge at ground level.

(i) Frost proofing.

(1) The discharge, heating or filling pipes where exposed to the weather shall be protected from freezing in the following manner:

(i) Pipes painted two (2) coats of red lead in linseed oil with a small percentage of litharge as a hardener.

(ii) One wrapping of tar paper equivalent to Asphalt Saturated Wool Felt paper weighing 12 lbs. per 100 sq. ft.

(iii) Three (3) layers of standard 1" high grade long cow's hair felt interposed and covered with one (1) layer of builder's paper equivalent to red rosin sized sheathing paper weighing 40 lbs. per 500 sq. ft.

(iv) One (1) covering of 8 oz. canvas, painted with two (2) coats of waterproofed paint.

(2) Application. All wrappings to be independently applied and securely fastened in place with heavy jute twine. Circumferential and longitudinal joints to have at least a 2" lap staggered with adjacent layers and opposing leakage to the hair felt.

(3) In groups of pipes each water pipe is to be wrapped separately with the tar paper, but subsequent layers of felt and paper may be applied collectively if space does not permit individual wrapping.

(4) Where a heating pipe is one of the group, the wrapping should be applied so that the hot line would serve all pipes in the enclosure. The initial wrapping of tar paper around each water pipe should be applied with laps down and the whole group wrapped with tar paper with laps up. If due to the position of the hot line sufficient air space would not insulate the hair felt, then protection to be effected by suitable separators, or a wrapping of asbestos paper instead of the tar paper around the group.

(5) On vertical pipes particular provision to be made to prevent slipping and tearing of insulation due to its weight.

(6) To prevent slipping away of insulation at point of entrance of pipes into a tank, and to shed leakage from slip joints, a 16 oz. duck to be provided, doubled and securely fastened to bottom of the tank overlapping inside and outside the insulation of the group for a distance of 18" below the tank. This duck to be well coated with paint. Loose hair felt to be packed about connections at tank bottom to safeguard against settling.

(j) Tank ladders and supports. Easy access to top of each tank shall be provided by means of a steel or wrought iron gooseneck ladder substantially constructed of flat iron side bars of not less than 2" × 1/2", or angle iron strings not less than 1 3/4" × 1 3/4" × 1/4", spaced not less than 14" apart, with rungs round or square not less than 5/8", spaced not more than 12" on centers, the ladder rigidly braced, and shall not tip outward from the vertical at any point, and when ladders exceed 20 feet in height an iron platform not less than 14" square, rigidly secured to strings of ladder and properly braced shall be provided near top of tank. Tanks above roofs shall be constructed according to the requirements of the Building Code and supporting structures shall be approved by the Buildings Superintendent. Tanks not enclosed and exposed to the weather shall be covered with a double roof of acceptable construction consisting of a tight flat cover of matched boards and above this a conical roof which shall be covered with an approved roofing. Where a gravity tank is located on a structure altogether independent of buildings the bottom shall not be less than 20 feet above the highest line of sprinklers below the main roof of the highest building in a group of buildings.

(k) Pressure tank. Pressure tanks shall contain sufficient water to supply twelve and one-half percent (12 1/2%) of the number of sprinklers in the average protected fire area for twenty (20) minutes, but not less than 3,000 gallons of water for a wet pipe system where supplemented by an auxiliary water supply, and not less than 5,000 gallons of water for a dry-pipe system. No single tank shall have a capacity greater than 6,000 gallons of water. The tank shall be kept two-thirds (2/3) full of water under a pressure of seventy-five (75) pounds per square inch, and shall be so proportioned and located that a pressure of not less than fifteen (15) pounds per square inch will be available on the highest line of sprinklers below the main roof. A pressure tank or tanks shall not be located below the highest line of sprinklers under the main roof supplied by such tank or tanks and shall not be required to be located above the highest line of sprinklers in a penthouse having an area less than 2,500 square feet unless such penthouse contains a hazardous occupancy or is used for the storage of combustible materials. Where a split system is installed the bottom of the intermediate tank shall be located above the highest line of sprinklers fed from such tanks. The water shall be supplied through a fixed pipe, independent of the sprinkler piping, not less than two inches in size. The water supply and connections shall be capable of supplying the tank at a rate of not less than sixty-five (65) gallons per minute without reducing the pressure in the tank. The tank shall have a fixed metallic horizontal line on the end opposite the glass gauge, or other acceptable device, to indicate the level of the water when the tank is two-thirds full. The air compressor shall be of sufficient capacity to increase the air pressure at the average rate of one (1) pound in two minutes in each pressure tank.

(l) Public water system. Direct connection to the city water supply shall be capable of furnishing water, at not less than fifteen (15) pounds per square inch static pressure at the highest line of sprinklers below the main roof.

(1) Where the average pressure from the city water supply does not comply with this subdivision (l) but is sufficient to give at least five pounds at the highest line of sprinklers as determined by test, an automatic, electrically driven pump installed for the purpose of boosting or increasing the city water pressure in the sprinkler system may be accepted under the following conditions: Pump to be a single stage, centrifugal, of approved design, to be of not less than 500 gallons per minute capacity and to otherwise comply with 2 RCNY § 4-09(m).

(2) Pump to be automatic, arranged to maintain 25 pounds at highest line of sprinklers at rated capacity and to be under the supervision and directly connected to the office of one of the fire alarm companies which is connected to Fire Department headquarters.

(3) The acceptance of this form of an automatic water supply shall be limited to an individual building not exceeding 80 feet in height, requiring not more than 100 sprinklers in the largest fire area.

(4) Subject to the requirements of the Bureau of Water Supply and Wastewater Collection, the size of each connection shall be as large as that of the main riser and not less than four (4) inches, and shall have a post indicator manually operated control valve, painted green, sealed open in an approved manner, located on the first story or at the sidewalk level near point of main entrance to building, and be provided with a sign secured to post reading: sprinkler control to city main.

(5) House service water supply connection may be taken from the sprinkler water supply connection to the city main on the inlet side of the fire meter, not exceeding 1 1/4 inches in diameter for a 4-inch connection, and 2 inches in diameter for a 6-inch or larger connection.

(6) A certificate establishing the fact that water supply conditions and pressures are as may be required shall be submitted to the Fire Department from the Bureau of Water Supply and Wastewater Collection.

(m) Fire pump. As auxiliary sources of water supply, steam or electric standard fire pumps shall receive water supply from a suction tank, a direct connection to the city water main or other approved sources capable of supplying the pump at its rated capacity for sixty (60) minutes. The rated capacity of the pump shall be not less than five hundred (500) gallons per minute, and shall be sufficient to supply twenty-five percent (25%) of the number of sprinklers in the average protected fire area. The pump shall be located in a room of fireproof construction, properly ventilated, lighted and drained, enclosed in eight (8) inch brick or concrete walls with approved fire doors at openings and with fireproof floor and ceiling construction. If located in the lowest story of the building, the pump shall be placed on a foundation not less than one (1) foot in height. The pump room shall be readily accessible with safe egress for the attendant. A reliable source of energy for driving the pump shall be provided. For steam pumps, provision shall be made for sufficient steam power to operate the pumps at full rated capacity, and a steam pressure of not less than fifty (50) pounds shall be maintained at the pump at all times. Where there is more than one boiler, the pipes and valves shall be so arranged to permit the cutting out of any one boiler without interrupting the steam supply to the pump from the other boilers. The boiler room shall be cut off from the remainder of the building by fireproof floor and wall construction with approved fire doors at all openings. Electrical energy from a public service plant shall be acceptable as a source of energy for driving electric fire pumps. When local power plants supply the energy for operating electric pumps, two motor generator units shall be provided, or one generator unit supplemented by a public service break-down switch. Local electric power plants shall be located in rooms of fireproof construction with approved fire doors at openings.

(n) Sprinkler discharge. For the purpose of computing the capacity of water supplies, standard one-half (1/2) inch sprinkler heads shall be assumed to have an average discharge of twenty (20) gallons per minute, and the discharge of larger heads shall be computed proportionately in the ratio of the areas of their respective orifices.

(o) Fire area. A fire area is any floor space enclosed on all sides by exterior walls or fire walls or a combination of both. In a non-fireproof building with mill or non-fireproof floors and roof, such wall shall be not less than 8 in. in thickness if of brick or stone, and not less than 6 in. if of reinforced concrete, and extending continuously from the lowest story to at least 3 ft. above the roof and be coped. In a fireproof building such wall or walls shall be of fireproof material not less than 6 in. in thickness, and shall extend from the fireproof floor to ceiling, or underside of fireproof roof. No opening shall exceed 66 in. in width, or 60 square feet in area, the center of every opening in such walls shall be at least 40 ft. from the center of every other opening therein at the same level. All openings shall be provided with approved automatic fire doors on each side of openings. The number of sprinklers in the average protected fire area shall be determined by the number of sprinklered stories in such section. In determining the required capacity of water supplies, the number of sprinklers in the average protected fire area need not include those located in low positions, such as under benches, low shelves, closets and platforms and between cars in car barns.

(p) Fire Department connection. All automatic sprinkler systems shall be provided with at least one two-way siamese connection on each street front of the building for connection to the fire department hose. Buildings fronting on only one street shall be provided with at least two siamese connections when the street frontage of building exceeds two hundred (200) feet. Where buildings have frontages on more than one street there shall be a fire department connection on each street front where frontage is not continuous but in all cases where more than one Fire Department connection is required they shall be located as the Fire Commissioner may direct and shall not be grouped. The siamese headers shall be of the same diameter as the largest riser or cross connection, but in no case less than 4 inches or more than 6 inches. All siamese hose connections hereinafter installed, except those on piers or warehouses intended for fire boat use, shall be three (3) inch, female connection. Siamese on piers, warehouses, etc., intended for fireboat use, except where the source of supply is from a direct connection to city main, shall be not less than 3 1/2-inch male connections with standard fire department threads. The siamese shall be placed at least eighteen (18) inches and not more than three (3) feet above the sidewalk, in a horizontal position accessible to the Fire Department. Each inlet shall be provided with a clapper valve machined to a true face. Each siamese connection shall be designated by raised letters at least one (1) inch in size, cast in the fitting in a clear and prominent manner and reading for the service designated, viz.: "Base. Spkr.," etc., as the case may be. If the entire building is sprinklered, the fitting shall be marked "Auto. Spkr." Siamese hose connections may project through a street wall not more than twelve (12) inches beyond the building line except that where there is an angle formed by the street wall and a check piece or the base of a column, pilaster or ornamental projection, they may be so located that no part extends more than fifteen (15) inches from either side of such angle in accordance with the provisions of the Building Code. In each Fire Department connection there shall be an approved straightway check valve installed in a horizontal position, the piping shall be arranged to drain between the check valve and the outside siamese coupling by either a ball drip having a one-half (1/2) inch pipe connection and one-half (1/2) inch orifice and a bronze ball of proper size, or by a three-quarter (3/4) inch drip connection arranged to drain to a sewer. All sprinkler siamese street risers, siamese wall collars and adjustable siamese caps shall be painted green.

(q) Sprinkler systems classified.

(1) One Source Systems, supplied with water from any one of the automatic sources or the automatic supervised fire pump specified in 2 RCNY § 4-09(l); and

(2) Two Source Systems, supplied with water from a combination of any two of the automatic sources; two pressure tanks with a total water capacity twice that required for a one source supply; direct connection to the city water supply on two different streets, so located that the closing of the controlling valve on one main will not eliminate the main on the other street; or a direct connection to the city water supply and one of the auxiliary sources provided the water supply connection is at least six (6) inches in size, the main is fed both ways and a two (2) inch test pipe at the top of the sprinkler riser shows a flowing pressure of fifteen (15) pounds per square inch between the hours of 6 a.m. to 6 p.m.

(r) Sprinkler spacing. Sprinkler heads and lines shall be spaced as herein provided: Mill construction. Under mill ceiling (smooth solid plank and timber construction, 5 to 12 foot bays) one line of sprinklers shall be placed in the center of each bay and the distance between the heads on each line shall not exceed the following:

(1) For Standard one-half (1/2) inch heads – 8 feet in 12 foot bays; 9 feet in 11 foot bays; 10 feet in 10 foot bays; 11 feet in 9 foot bays; 12 feet in 5 to 8 foot bays;

(2) For Conran* one (1) inch heads – 20 feet in 5 to 12 foot bays.

(3) For Conran one and one-quarter (1 1/4) inch heads – 25 feet in 5 to 12 foot bays.

(4) Vaults used for the storage of nitro-cellulose products and vaults used for the storage of flammable motion picture films shall have one standard one-half (1/2) inch head for each 62 1/2 cubic feet of available storage space, or one (1) inch Conran head for each 250 cubic feet of available storage space. Measurements shall be taken from center to center of timbers. Ceilings of modified mill construction having bays less than three (3) feet wide shall be treated as open joist construction and sprinkler heads and lines spaced accordingly. Bay timbers spaced three (3) feet or more on centers, but less than five (5) feet on centers, will require special ruling by the administrative official having jurisdiction.

(s) Joisted construction. Under open finish joisted construction ceilings, floor, decks and roofs, the sprinkler lines shall be run at right angles to the joists and the heads "Staggered spaced" so that heads on one line will be opposite a point halfway between heads on adjacent lines.

(1) One-half inch heads. For standard one-half (1/2) inch heads the distance between lines of sprinklers shall not exceed ten (10) feet, and the distance between heads on each line shall not exceed eight (8) feet, the end heads on alternate lines being spaced not more than two (2) feet from wall or partition. Permission may be given by the administrative official having jurisdiction to install but one line of sprinklers, in each bay where girders project below the underside of joists and divide the ceiling into bays ten (10) to eleven and one-half (11 1/2) feet wide from center to center of girders, and the heads shall then be spaced on each line so that the area covered by a single head does not exceed eighty (80) square feet. In all cases where such bays are over eleven and one-half (11 1/2) feet wide, two or more lines of sprinklers shall be installed in each bay as required by the rules for spacing. Where girders and joists are flush at the bottom, heads shall be spaced according to the general rule.

(2) One inch heads. For Conran* one (1) inch heads the distance between adjacent lines shall not exceed twenty (20) feet and the distance between the heads on each line shall not exceed sixteen (16) feet, the end heads on alternate lines being spaced not more than four (4) feet from wall or partition. Where girders project below the underside of joists and divide the ceiling into bays not exceeding twenty (20) feet in width, measured from center to center of girders, one line shall be placed in the center of each bay. In bays exceeding twenty (20) feet in width at least two (2) lines shall be installed in each bay and in no case shall the distance between adjacent lines exceed twenty (20) feet.

(3) One and one-quarter inch heads. For Conran one and one-quarter (1 1/4) inch heads the distance between adjacent lines shall not exceed twenty-five (25) feet and the distance between the head on each line shall not exceed twenty (20) feet, the end head on alternate lines being spaced not more than five (5) feet from wall or partition. Where girders project below the underside of joists and divide the ceiling into bays not exceeding twenty-five (25) feet in width, measured from center to center of girders, one line shall be placed in the center of each bay. In bays exceeding twenty-five (25) feet in width at least two (2) lines shall be installed in each bay, and in no case shall the distance between adjacent lines exceed twenty-five (25) feet.

(t) Smooth finish, sheathed or plastered ceilings. Under smooth finish, sheathed or plastered ceilings, in bays six (6) feet wide and over (measurements to be taken from center to center of timber, girder or other projection or support forming the bay), sprinkler heads and lines shall be spaced as follows:

(1) For standard one-half (1/2) inch heads – One line of sprinklers shall be placed in the center of each bay for bays not exceeding twelve (12) feet in width, and the distance between the heads on each line shall not exceed the following: 8 feet in 12 foot bays; 9 feet in 11 foot bays; 10 feet in 6 to 10 foot bays. Bays in excess of twelve (12) feet in width and less than twenty-three (23) feet in width, shall contain at least two (2) lines of sprinklers; bays twenty-three (23) feet in width or over shall have the lines therein not over ten (10) feet apart. In bays in excess of twelve (12) feet in width, not more than one hundred (100) square feet of ceiling area shall be allotted to any single head.

(2) For Conran one (1) inch heads – One line of sprinklers shall be placed in the center of each bay for bays not exceeding twenty (20) feet in width, and the distance between the heads on each line shall not exceed twenty (20) feet. Bays in excess of twenty (20) feet in width shall contain at least two (2) lines and in no case shall the distance between adjacent lines exceed twenty (20) feet.

(3) For Conran one and one-quarter (1 1/4) inch heads – One line of sprinklers shall be placed in the center of each bay for bays not exceeding twenty-five (25) feet in width and the distance between the heads on each line shall not exceed twenty-five (25) feet. Bays in excess of twenty-five (25) feet in width shall contain at least two (2) lines and in no case shall the distance between adjacent lines exceed twenty-five (25) feet.

(u) Fireproof construction. The rules of slow-burning mill construction shall apply as far as practicable. The rule may be modified, however, the intent being to arrange the spacing of heads to protect the contents rather than the ceilings; but in no case shall the distance between a head on one line and a head on an adjacent line exceed the following:

(1) For standard one-half (1/2) inch heads, 12 feet.

(2) For Conran* one (1) inch heads, 20 feet.

(3) For Conran* one and one-quarter (1 1/4) inch heads, 25 feet.

(v) Distance from walls. The distance from wall or partition to the first head on a sprinkler line shall not exceed one-half the allowable distance between the heads on such line. Additional heads may be required in the narrow pockets formed by bay timbers or beams and wall. Where beams, girders, columns, walls, partitions or other obstructions prevent the effective discharge of water, additional heads shall be installed to effectively sprinkle the area.

(w) Vertical shafts. In vertical shafts having flammable sides, heads shall be provided within the shaft in addition to the head or heads at the top of shafts, as follows:

(1) One standard one-half (1/2) inch head for each 200 square feet of flammable surface.

(2) One Conran one (1) inch head for each 400 square feet of flammable surface.

(3) One Conran one and one-quarter (1 1/4) inch head for each 500 square feet of flammable surface. Such head or heads shall be installed at each floor when practicable, and always when shaft is trapped. Where practicable, heads shall be "staggered" at the alternate floor levels, particularly when only one head is installed at each floor level.

(x) Pitched roofs. Under a pitched roof sloping more steeply than one (1) foot in three (3) feet, heads shall be located in peak of roof, and those on either side of the peak shall be spaced according to the foregoing requirements. The distance between heads shall be measured on a line parallel with the roof. Where the roof meets the side wall or the floor line, the heads shall be placed not more than the following distance from such intersection:

(1) For standard one-half (1/2) inch heads, 3 1/2 feet.

(2) For Conran one (1) inch heads, 7 feet.

(3) For Conran one and one-quarter (1 1/4) inch heads, 8 1/2 feet. Heads spaced not to exceed the following distance each way from the peak to roof, measured on a line parallel with the roof, may be used in lieu of heads located in peak of roof.

(4) For standard one-half (1/2) inch heads, 2 1/2 feet.

(5) For Conran one (1) inch heads, 5 feet.

(6) For Conran one and one-quarter (1 1/4) inch heads, 6 1/4 feet. In sawtooth roof construction, the end heads on the branch line shall be spaced not to exceed the following distance from the peak of the sawtooth:

(7) For standard one-half (1/2) inch heads, 2 1/2 feet.

(8) For Conran one (1) inch heads, 5 feet.

(9) For Conran one and one-quarter (1 1/4) inch heads, 6 1/4 feet.

(y) Special locations and variations. In special locations, such as over electric generating, power and transforming apparatus, over their controlling devices and switch-boards, where water from the fire extinguishing equipment would be detrimental, the sprinkler lines and heads may be omitted at the discretion of the administrative official having jurisdiction, and when in his judgment a slight variation of this subdivision (y) of spacing is desirable to effect a more efficient distribution of water for fire extinguishing purposes, the sprinkler lines and heads shall be spaced as he may direct.

(z) Sprinkler position. All sprinkler heads shall be located, wherever possible, in an upright position on top of the pipes, except that sprinkler heads on automatic wet pipe systems may be pendent on concealed piping and when construction or occupancy of a room or enclosure makes it preferable.

(1) Where standard one-half (1/2) inch heads are installed sprinkler deflectors shall be parallel to ceilings, roofs or the incline of stairs, but when installed in the peak of a pitched roof they shall be horizontal. Distance of deflectors from ceilings of mill or other smooth construction, or bottom of joists of open joist construction, shall be not less than three (3) inches nor more than ten (10) inches. In fireproof buildings, the distance between deflectors and panel ceilings shall not exceed fifteen (15) inches.

(2) Where Conran heads are installed, the top of head shall be located the same distance below joists or ceiling as specified for deflectors in paragraph (1) of this subdivision (2); except that when heads are located under pitched roofs of piers or similar structures, they shall in general be installed in the upright position (not normal to slope of roof) and three (3) feet vertically below the underside of roof. When the administrative official having jurisdiction deems a variation of this subdivision (z) advisable to obtain a more efficient distribution of water, the heads shall be located with respect to joists or ceiling, as he may direct.

(aa) Spray clearance. Not less than eighteen (18) inches effective clear space shall be left below the sprinkler heads, so that they may discharge an unbroken spray blanket from sprinkler to sprinkler and sides of room when in operation. Any stock piles, racks or other obstructions interfering with such action shall not be permitted. Sprinkler system piping shall not be used for the support of stock, clothing, etc.

(bb) Pipe sizes. The number of heads on a given size pipe in one fire area in any story shall not exceed the following:

(1) For standard one-half (1/2) inch heads.

Size of Pipe Maximum No. of Heads Allowed 3/4 inch 1 head 1 inch 2 heads 1 1/4 inch 3 heads 1 1/2 inch 5 heads 2 inch 10 heads 2 1/2 inch 20 heads 3 inch 36 heads 3 1/2 inch 55 heads 4 inch 80 heads 5 inch 140 heads 6 inch 200 heads 7 inch 300 heads 8 inch 420 heads

(2) For Conran one (1) inch heads.

Size of Pipe Maximum No. of Heads Allowed 1 inch 1 head 1 1/4 inch 2 heads 1 1/2 inch 3 heads 2 inch 4 heads 2 1/2 inch 6 heads 3 inch 9 heads 4 inch 18 heads 5 inch 34 heads 6 inch 51 heads 7 inch 75 heads 8 inch 105 heads

(3) For Conran one and one-quarter (1 1/4) inch heads.

Size of Pipe Maximum No. of Heads Allowed 1 1/4 inch 1 head 1 1/2 inch 2 heads 2 inch 3 heads 2 1/2 inch 4 heads 3 inch 6 heads 4 inch 12 heads 5 inch 31 heads 6 inch 40 heads 7 inch 60 heads 8 inch 84 heads

When it is desired to use pipe of larger size than eight (8) inches in diameter, special ruling will be required by the administrative official having jurisdiction as to the permissibility of its use and the number of heads that may be fed thereby. Where practicable, it is desirable to arrange the piping so that the number of heads on a branch line will not exceed eight. When the piping is arranged on the "gridiron" plan, the permissible number of heads may be doubled, provided the feed main is of the size indicated in the schedule for the total number of heads. Where feed mains supply branch lines of only two heads each, the conditions approach those of long single lines. Such feed mains shall usually be centrally supplied where there are over eight (8) or ten (10) branch lines. Branch lines up to fourteen (14) in number may be fed from end, provided a two and one-half (2 1/2) inch pipe does not supply more than sixteen (16) standard one-half (1/2) inch heads, in lieu of twenty (20). Buildings having slatted floors, or large unprotected floor openings without approved stops, shall be treated as one room with reference to the pipe sizes, and the feed main shall be of sufficient size to accommodate the number of heads called for. Larger pipe sizes than are allowed in the schedule for a given number of heads may be required wherever the construction or conditions introduce unusually long runs of feed mains or many angles. Buildings with blind attics with small, unprotected openings to floor below, may be piped from the system on the ceiling of floor below, provided pipe size schedule is not overloaded on sizes three (3) inches or under.

(cc) Feed mains. The size of feed mains shall not be less than the size of riser and shall be arranged to run as direct as possible from source of water supply to riser. Feed mains for stair or other towers without approved stops between floors, when piped on independent riser, shall be of sufficient size to accommodate the total number of sprinklers in such tower.

(dd) Risers. There shall be one or more separate risers in each building and in each section of the building divided by fire walls. Risers shall be arranged to provide "Center Central" or "Side Central" supply to feed main. Each riser shall be of sufficient size to supply all the heads on said riser in one story, according to the schedule of pipe sizes in 2 RCNY § 4-09(r). If the conditions warrant, special permission will be granted allowing the heads in a fire section of small area to be fed from the risers in another section, provided the total number of heads in such area does not exceed the following number per floor:

(1) For standard one-half (1/2) inch heads, 48.

(2) For Conran one (1) inch heads, 12.

(3) For Conran one and one-quarter (1 1/4) inch heads, 8. Risers shall not be located close to windows, properly protected from mechanical injury and freezing and shall be properly supported on foundations and by floor plates, clamps, couplings or approved hangers.

(ee) Connections prohibited. No connections, such as for sill cocks, house service or hose outlets, shall be made with a sprinkler system riser or any part thereof except as provided for in 2 RCNY § 4-09(l).

(ff) Air lock adjustment. Where gravity and pressure tanks feed through a common discharge pipe or "dead riser" to the foot of a riser and an air lock is likely to develop the discharge pipe of the gravity tank shall connect with the discharge pipe, or "dead riser," forty (40) feet below the bottom of the pressure tank.

(gg) Pipes and fittings. All pipe shall be full-weight standard wrought iron or steel threaded pipe, well reamed and screwed up tight into fittings without reducing the waterway. Fittings shall be standard cast iron fittings, and shall be long turn pattern on feed mains and risers. Such fittings shall be designed and guaranteed for a working pressure of 150 pounds per square inch and must be capable of withstanding a hydrostatic test pressure of 750 pounds per square inch without failure. All pipe shall be secured to the ceiling, walls and other parts of the building with standard steel, wrought or malleable iron hangers. Extra heavy fittings shall be employed where the normal pressure in the pipe system exceeds one hundred and fifty (150) pounds per square inch, and shall be designed for a working pressure of 250 pounds per square inch and be capable of withstanding a hydrostatic test pressure of 1,250 pounds per square inch without failure. All underground pipe shall comply with the specifications for cast iron pipe of the American Water Works Association.

(hh) Protection of pipes and sprinklers. When exposed to moisture, sprinkler pipes and hangers shall be protected against corrosion whenever found necessary by thoroughly cleaning the pipe of all scale and grease and painting with a coat of red lead and linseed oil paint or other acceptable moisture resistive paint. When exposed to chemical fumes, the pipe and fittings shall be coated with graphite or other approved chemical resistive paint. Care shall be taken not to paint the sprinkler heads. Supply pipes of risers in low basements or low spaces under ground floors exposed to frost, shall be properly protected by a masonry or wood enclosure, properly heated, or filled with mineral wool, sawdust or tax mixed with granulated cork, extending below bottom of pipe and through the top flooring of ground floor, or the pipe shall be protected with three alternate layers of one-inch hair felt and building paper or by other approved method. When of wood, such enclosure shall be constructed double with a layer of tar paper between the two thicknesses of wood. Where risers, drains, heating pipes, etc., pass through cinder concrete floors or partitions, they shall be protected with a metal sleeve or be grouted with cement mortar. Wherever sprinklers are exposed to corrosion, the heads shall be protected with an approved hermetically sealed cover, or with an approved wax coating.

(ii) Drainage. All sprinkler pipe and fittings shall be so installed that they can be thoroughly drained, and where practicable, all piping shall be arranged to drain at the main drips. Drains or drip pipes shall be so arranged as not to expose any part of the sprinkler system to frost, and shall be so connected, either by check valves or other means, that they will not overflow domestic service or other connections to the same sewer or house drain, or if carried through the wall and exposed to the weather, they shall be fitted with hoods or down-turned elbows. Drains, pitched not less than one-quarter (1/4) inch in ten (10) feet, shall be installed: At the base of the main riser; At each alarm valve; At each dry-pipe valve; At each gravity tank; At each pressure tank; At each fire department connection; On each floor, if independent floor control valves are used; and At each supply main, when the water in the same cannot be removed through any of the above drains. Such drains shall be installed with controlling valves so that flowing tests may be made to determine if the water supplies or connections from yard mains to the inside of the building are in order without causing water damage or overflowing service connections to the same house drain. Any such drain shall be not less than two (2) inches in size except that drains at independent floor valves shall be not less than 1 inch in size where floor valves are not over 2 1/2 inches in size and 1 1/4 inches where floor valves are larger and connected to a main drain riser of not less than 1 1/2 inches in size. The drain at the main riser shall discharge into a cone or sight drain, or if carried through the wall and exposed to the weather, it shall be fitted with a hood or down-turned elbow. At an alarm valve at the top of a riser in a down-fed system a drain shall not be required. On automatic wet pipe systems, the horizontal branch pipes shall be pitched not less than one-quarter (1/4) inch in ten (10) feet to drain towards the sources of supply with drip valves at the low points. On automatic dry-pipe systems, branch pipes shall be pitched at least one-half (1/2) inch in ten (10) feet.

(jj) Test pipe. In all wet-pipe automatic sprinkler systems a test pipe of not less than 3/4 inch in diameter shall be connected directly with each system but shall be connected to a pipe of not less than 1 1/4 inches in diameter in upper story and arranged to discharge through a 1/2-inch brass outlet, preferably to a point where it can readily be seen. With long runs or many angles, size of test pipe should be increased to one (1) inch or larger. Controlling valve should be located at a sufficient distance from where the test pipe passes through the wall of the building so as to reduce to a minimum the chance of freezing of water in test pipe. In all dry-pipe automatic sprinkler systems a 3/4-inch inspector's test pipe shall be installed at the end of the most distant branch line and fitted with a 3/4-inch shut-off valve stopped with a brass plug.

(kk) Pressure gauges. A four and one-half (4 1/2) inch double-spring Bourdon pressure gauge shall be provided in all automatic sprinkler systems as follows: Above dry-pipe valves; Below dry-pipe valves; At the pressure tank; At the air compressor; Above the alarm valve; Below the alarm valve; and In the connections from city water supply. Provision may be made for taking the pressure both above and below the alarm valve and the dry-pipe valve with only one gauge at each valve. A gauge shall not be required at an alarm valve located at the top of a riser in a down-fed system. Gauge connections shall be taken from the supply main or riser and not from the two-inch drain or test pipe. Gauges shall be installed in a suitable place protected from freezing and be controlled by a valve with arrangements for draining. A plugged outlet, not less than one-quarter (1/4) inch in size, shall be located between each valve and gauge for purpose of installing the inspector's gauge.

(ll) Valves.

(1) All valves two (2) inches in diameter and under shall be of brass or bronze, or other approved non-corrodible material. Valves over two (2) inches in diameter shall be of brass, or bronze or iron body, brass mounted, or of other approved non-corrodible material. All sidewalk siamese inlet valves, caps and chains shall be of galvanized cast iron or other approved non-corrodible material. All gate valves shall be solid or double wedge disc, stuffing box pattern with hand wheel, outside screw and yoke, or other approved indicator pattern. All check valves shall be approved straightway regrinding pattern, so built that the clappers may be readily removed for repairs.

(2) Water supply gate valves. The piping connecting each source of water supply with sprinkler system shall be provided with a gate valve of the outside screw and yoke type, sealed open and tagged to designate its purpose, so located as to control each source of water supply except that from Fire Department hose connections. All such gate valves shall be located within the building where easily visible and readily accessible and as close as possible to the supply inlet.

(3) Water supply check valves. The piping connecting each source of water supply with the sprinkler system, including Fire Department connections, shall be provided with a check valve. On two-source systems, check valves shall have a gate valve on each side to permit repair of check without shutting off both supplies, except that where the two sources of supply consist of tanks located above the highest line of sprinklers, a gate valve need only be provided on the downstream side of each check valve .

(4) Control valves. All automatic sprinkler systems shall be provided with a main control or shut-off valve arranged to be readily accessible as near the stairways or fire tower as possible and sealed in the open position; except that when the sprinkler system is fed from water supplies on the roof of the building, independent and readily accessible floor control valves, sealed in the open position, may be installed. When not more than ten (10) standard one-half (1/2) inch sprinkler heads or three (3) Conran heads in any automatic wet pipe system are exposed to cold and subject to freezing shut-off valves may be provided to discontinue the places which cannot be properly heated, shall be controlled by an automatic dry-pipe valve.

(5) Dry-pipe valves. A dry-pipe valve shall be taken to mean a valve automatically controlling the water supply of the sprinkler system in such a manner that under normal conditions its piping system beyond the valve is maintained dry, but in the event of fire, the valve automatically releases the water into the sprinkler system, for fire extinguishing purposes. Dry-pipe valves shall, for the purpose of these rules, be classified as follows: Type A, in which the valve is actuated by the release of compressed air in the sprinkler piping system, due to the opening of a sprinkler head; and Type B, in which the valve is actuated by an approved trip under electric control of an approved automatic thermostatic fire alarm system. Dry-pipe valves shall be located as near as practicable to the sprinkler system in an enclosed and accessible place protected from mechanical injury and freezing. Automatic wet-pipe sprinkler systems in which only twenty-five percent (25%) of the heads are required to be maintained dry for protection from freezing, shall have only such heads under dry-pipe valve control.

(i) When "Type A" valve is installed, the air pressure in sprinkler systems under such dry-pipe valve control shall not exceed forty (40) pounds per square inch, nor be permitted to fall below twenty-five (25) pounds per square inch, nor shall it be less than one-sixth (1/6) of the water pressure in any case. The air compressor shall have a capacity of not less than eleven (11) cubic feet per minute and the air supply for the pump shall be taken, if possible, from a room containing dry air, or it shall be passed through a drying chamber containing calcium chloride, in order to avoid the introduction of moisture into the system. The air pressure on such dry-pipe systems shall be maintained throughout the year. Not more than the following number of heads shall be controlled by one "Type A" dry-pipe valve:

(ii) For standard one-half (1/2) inch heads.....400

(iii) For Conran one (1) inch heads.....100

(iv) For Conran one and one-quarter (1 1/4) inch heads.....64

Where equipped with an approved quick-opening device the following number of heads may be controlled by one "Type A" dry-pipe valve:

(v) For Conran one (1) inch heads.....150

(vii) For Conran one and one-quarter (1 1/4) inch heads.....96

(viii) When "Type B" valve is installed the actuating alarm system shall be designed to operate at a temperature lower than that required to open the sprinkler heads, and all connections between the alarm system and the dry-pipe valve shall be adequately protected against injury of any kind. When required by the administrative official having jurisdiction, the dead end of every feed main in such dry-pipe system shall be provided with an air relief valve or vent, so constructed as to be normally open in order to permit the free escape of air from the system, but to close automatically against the escape of water. Not more than the following number of heads shall be controlled by one "Type B" dry-pipe valve:

(ix) For standard one-half (1/2) inch heads.....600

(x) For Conran one (1) inch heads.....150

(xi) For Conran one and one-quarter (1 1/4) inch heads.....96

(6) Alarm valve. All automatic wet pipe sprinkler systems shall be equipped with an alarm valve so constructed that a flow of water through a one-half (1/2) inch orifice will operate an electric or mechanical gong. When an electrically operated alarm is installed in connection with an alarm valve or dry pipe valve, the installation shall be made in conformity with the provision of 2 RCNY § 4-09(mm).

(mm) High and low water. Electric Alarm on Gravity and Pressure Tanks. All gravity tanks shall be equipped with a device to indicate when the water falls below or rises above the normal level in the tank, with an indicator and alarm located in the engineers' room near the pump. All gravity and pressure tanks shall be equipped with a high and low alarm as hereinafter specified. The high and low gravity and the high and low pressure electric alarm shall be so constructed and arranged that when the water falls below or rises above the normal level in the gravity tank, and when the pressure falls below or rises above the predetermined level in the pressure tank, an audible and visible signal will be given in either the pump room or engineer's room. The audible signaling device for high and low water and high and low pressure electric alarm shall consist of a vibrating gong of at least 3 inches in diameter of the enclosed type and arranged for conduit installation, the same to be operated automatically from an approved device indicating the level of water in the gravity tank and from the pressure gauge of pressure tank. The audible signaling device for the alarm and dry pipe valves shall consist of an enclosed type 6-inch vibrating gong arranged for conduit installation. A closed circuit annunciator shall be provided in connection with the alarm system. The high and low toll-tale electric connections shall be so constructed that it will not be affected by moisture and the parts shall be heavy and rugged. The float shall be of approved type. All wiring shall be installed in iron or steel conduits and the installation shall be in accordance with the provisions of Chapter 9 of the Code of Ordinances. Only approved closed circuit systems shall be installed. Control panels to operate the signaling equipment must be approved by the Board of Standards and Appeals. The control cabinet shall be located in the engineer's or pump room where it will be under the supervision of the person in charge of the sprinkler system. The following sources of energy may be employed and are given in their order of preference:

(1) Public utility electric light and power systems.

(2) Electric light or power system (public utility or isolated plant) supplemented by storage battery either controlled by an automatic throw-over device or floating on the line and protected by a reverse current circuit breaker.

(3) Storage batteries in duplicate.

(4) Primary batteries of the closed circuit type. When the system is connected to the 110 volt lighting service a suitable cut-out is to be provided and it shall be enclosed in a locked or sealed metal cabinet. The connection to the system shall be the first connection on the house side of and as near as practicable to the meter. When batteries are used to operate the system they shall be placed in an approved cabinet provided with a lock and key.

(nn) Heating of tanks. The water in all sprinkler tanks subject to freezing shall be protected by internally heating the water or enclosing the tank in a frost-proof house properly heated and lighted.

(oo) Concealed pipe systems. All pipe in concealed pipe systems shall be of standard full-weight wrought iron or steel, painted with two coats of protective paint, one before and one after installation. Such pipe as shall be installed in ducts or be encased in cement mortar shall be inspected prior to concealment. When installed in the concealed space between floor arches and ceiling, such pipe shall be supported by hangers and all pipe, fittings and hangers be protected with two coats of paint.

(pp) Preparation of building. Floor or wall openings and other structural defects which prevent the banking up of heated air and retard the automatic action of sprinkler heads shall be provided with the necessary curtain boards and draft stops to permit specific control of the fire by the local sprinklers. Curtain boards shall project at least three (3) inches below the lowest sprinkler.

(qq) Approval of sprinkler system. Before acceptance all automatic sprinkler systems, excluding the water supply tanks, shall be subjected after installation to a hydrostatic pressure test of at least one (1) hour's duration at not less than fifty (50) pounds per square inch in excess of that which will be normally carried and observed in the sprinkler system, such test pressure, however, to be not less than one hundred and fifty (150) pounds per square inch in any part of the system. All pressure tanks shall be tested after erection to a test pressure of one and one-half (1 1/2) times the working pressure. To prevent the possibility of serious water damage in case of a break, the pressure shall be maintained by a small pump, the main controlling gate being meanwhile kept shut. Brine or other corrosive chemicals shall not be used for testing systems. In automatic dry-pipe systems with "Type A" valve control, an air pressure of forty (40) pounds per square inch shall be pumped up, be held for twenty-four (24) hours, and all leaks stopped which allow a loss of pressure of over two (2) pounds per square inch for the twenty-four (24) hours. In the case of automatic dry-pipe systems with differential "Type A" valve, the valve shall be held off its seat during the test to prevent injuring the valve. Non-automatic systems shall be tested after installation at not less than fifty (50) pounds per square inch in excess of the pressure necessary to reach the highest line of sprinklers. All tests of installed systems shall be made by the contractor in the presence of the Fire Commissioner, or his authorized representative. No piping, devices nor any portion of a newly constructed sprinkler system shall be covered up or permanently concealed until tested by the Bureau of Fire Prevention and approved of in writing, except piping passing through floors, walls, partitions or beams for distances equal to the thickness of such floors, walls, partitions or beams.

(rr) Types of buildings.

(1) Non-fireproof business buildings. Automatic sprinklers required in non-fireproof business buildings under the provisions of Chapter 5, Article 4, Section 72, Subdivision L, Code of Ordinances, shall consist of at least a One Automatic Source System, except buildings used as freight depots, car barns, stables, garages, factories and grain elevators which sprinkler systems shall be supplied by any two of the automatic sources or one of the automatic sources and a fire pump as described in 2 RCNY § 4-09(l) and (m).

(2) Department stores. Wet sprinkler systems shall be required in all department stores and where the floor area on any story or cellar exceeds 20,000 square feet, the system shall be supplied by two of the automatic sources as provided for in 2 RCNY § 4-09(q).

(3) Factories and other buildings. Where the Labor Law or the Code of Ordinances require automatic sprinkler systems, or where any of the requirements of the Labor Law or Code of Ordinances are waived because of the installation of an automatic sprinkler system, such sprinkler systems, unless specifically otherwise required by the Fire Commissioner, Code of Ordinances, Labor Law, or these rules, shall have at least the following sources of supply installed in accordance with these rules:

(i) A gravity tank and siamese, or

(ii) A pressure tank and siamese, or

(iii) A direct 6 inch connection to the City water supply fed two ways, capable of furnishing water at not less than 15 pounds per square inch static – pressure at the highest line of sprinklers below the main roof, and the required siamese.

(4) Theatre buildings. Automatic sprinklers required in theatre buildings under the provisions of Chapter 5, Article 25, Section 524, Code of Ordinances, shall consist of at least a One Automatic Source Automatic System.

(5) Firework storage. Automatic sprinklers required in buildings in which fireworks are stored or sold under the provisions of Chapter 10, Article 6, Section 92, Code of Ordinances, shall consist of either of the two automatic sources as provided in 2 RCNY § 4-09(q).

(6) Nitro-cellulose products. Automatic sprinklers as required in buildings in which nitro-cellulose products are stored under the provisions of Chapter 10, Article 19, Section 232, Code of Ordinances, shall consist of a system supplied from both approved gravity tank supply and an approved pressure tank supply, except that no change shall be required in supplies to automatic sprinkler equipments previously approved by the Fire Commissioner as two source systems, in conformity with the provisions of this paragraph (6) as in force up to December 1, 1921. In buildings wherein are stored or handled only limited quantities of nitro-cellulose products, not exceeding 500 pounds, the automatic sprinklers may consist of either of the two automatic sources as provided for in 2 RCNY § 4-09(q).

(7) Flammable motion-picture films. Automatic sprinklers, required in buildings in which flammable motion-picture films are stored under the provisions of Chapter 10, Article 20, Section 241, Code of Ordinances, shall consist of a system supplied from both an approved gravity tank supply and an approved pressure tank supply except that no change shall be required in supplies to automatic sprinkler equipments previously approved by the Fire Commissioner as two source systems in conformity with the provisions of this paragraph (7) as in force up to December 1, 1921.

(8) Sprinkler protection for special hazards in non-sprinklered buildings not provided for by laws or ordinances or in these rules. Sprinkler heads and piping may be provided on ceiling of enclosed rooms, closets, shafts, or other spaces which are used as carpenter shops, upholstering rooms, paint shops, waste paper rooms, old record storerooms, trunk and general storage rooms in hotels, offices or other buildings, and in stores and showrooms or where nitro-cellulose products or flammable photographic or X-ray film is stored or used, or in ice boxes of cold storage plants. The number and type of sprinkler heads, spacing and size of pipe, location and number of valves, method of draining lines, water flow or other alarms, shall be as required by the Fire Commissioner to properly protect the special hazard. The source of water supply where required may be taken from the house supply tank or other sources of water supply, except that no connection shall be taken from the standpipe system or from the feed line to boilers. In all cases there shall be sufficient water to provide 20 gallons of water per head for 30 minutes and, further, that the pressure on any sprinkler line shall, where practicable, be not less than 15 pounds static pressure.

(ss) Existing installations and approvals. Automatic sprinkler systems and devices heretofore installed shall not be required to conform to these rules where the fire hazard due to construction and occupancy of the building is not increased or where substantial additions or extensions in height or area is made to the building when these rules shall apply if deemed advisable or necessary by the Fire Commissioner.

(tt) Communicating openings. When a building fully equipped with sprinklers communicates with another not so equipped the openings must be protected by approved fire doors on both sides of the wall, one of which must be automatic.

(uu) [Repealed.]

(Renumbered and amended, City Record 4/4/2019, eff. 5/5/2019)