28 RCNY Chapter 25 Multiple Dwellings, part 1 of 2

§ 25-01 to § 25-173: 40 sections.

§ 25-01. Scope

Open this section

These rules shall govern the installation and maintenance of gas-fueled space and water heaters in the residence portions of multiple dwellings in the City of New York, including but not limited to the installation of such devices in multiple dwellings which are installed in lieu of centrally supplied heat and hot water under the provisions of §§ 27-2028, 27-2031, 27-2032, and 27-2034 of the Administrative Code, and in one and two family residences not heated by a central heating system.

§ 25-06. Applications and Plans

Open this section

(a) Before commencing the installation of a gas-fueled space or water heater in a dwelling a plumbing repair slip or building notice, as specified below must be filed in the borough office of the Department of Buildings where the installation is to be made, giving the address of the dwelling and all pertinent information required on the forms.

(b) Before filing these forms in the offices of the Department of Buildings the applicant shall have the house numbers and the block and lot checked in the offices of the borough president where that procedure is followed in a particular borough, and in addition obtain a certification from the Department of Housing Preservation and Development of the classification of the multiple dwelling in which the appliances are to be installed.

(c) When applications are filed for permits to install gas-fueled space and water heaters the plumbing repair slips, the building notice forms and the envelopes in which they are placed shall be stamped by the plan clerk with a stamp reading: "GAS APPLIANCES".

(d) Plumbing repair slips shall be accepted only where gas appliances will be connected to flues in existing brick chimneys, and where no other venting or other work is required to be done. They shall not be accepted for installation of gas-fueled heaters in sleeping rooms. Plumbing repair slips shall clearly state the type of appliance to be installed, the floors, apartments and rooms in which they are to be placed, including the number of rooms in the apartment and the occupancy of each room, whether sleeping room or otherwise. They shall describe the condition of the chimney flue to be used and state whether the draft is satisfactory. If a gas meter is to be installed its location shall be given.

(e) Where vent pipes are to be installed, or other work done in connection with the installation of gas-fueled heaters, a building notice application shall be filed. It shall indicate the type of each such device, the floor on which, and the apartment and the occupancy of the room in which such appliance is to be installed, the material and dimensions of the vent pipe or flue, and the dimensions of the court or yard to which the exhaust vent will be carried. If a gas meter is to be installed, its location shall be shown. No plumbing specification sheet or plumbing repair slip need be filed with such a building notice.

(f) Application for permits to install gas-fueled space heaters and water heaters may be made separately or together on one application but each such application shall indicate that all apartments in the building will be provided with gas-fueled space and/or water heaters as the case may be. The location, type, make, and capacity of all such appliances previously installed or to be installed in a building shall be specified. If any of the appliances have been installed in multiple dwellings prior to December 9, 1955, which the owner desires to maintain, the necessary work to make them comply with these rules should be indicated.

§ 25-07. Examination and Approval of Applications

Open this section

(a) Plumbing repair slips, when filed, shall be processed in the usual manner and forwarded to the inspectors of plumbing.

(b) Building notices calling for the installation of gas-fueled space and water heaters shall be expedited and may be taken out of turn, except that they shall be processed in the order in which they were received. They shall be examined for compliance with these rules and all other laws and regulations applicable to such installations. If any chimney or metal stack is to be installed, examiners shall check such construction for compliance with Subchapter 15 of Chapter 1 of Title 27 of the Administrative Code (Building Code). They shall require that the foundations shall be carried not less than four feet below the surface of the ground, and that the soil on which it is build to be not overloaded. They shall require that new chimneys be strapped to the existing walls.

(c) Only applications calling for the installation of gas-fueled space or water heaters, approved by the Department of Health, specifying the make and model shall be approved. All such gas appliances shall be of types approved also by the American Gas Association. However, where an owner desires to continue to use any gas appliance installed in a multiple dwelling prior to December 9, 1955, clearly shows on the plan the data required by paragraph f of 28 RCNY § 25-06 and prominently marks the appliances that have not been approved by the Department of Health, the application may be conditionally approved pending the approval of the appliances by the Department of Health.

§ 25-08. Commencement of Work

Open this section

(a) It shall be unlawful to commence any construction for which a building notice has been filed until a permit for the proposed work has been issued by the borough superintendent, and it shall be unlawful to commence the installation of piping of any gas appliance until a registered plumber has filed a signed statement with the borough superintendent containing the address of said plumber and stating the he is duly authorized to proceed with the work.

(b) The plumber shall notify in writing the borough superintendent of the Department of Buildings of the borough in which any gas-fueled space or water heater is to be installed when such work is to begin and when it will be ready for operation and inspection.

§ 25-09. Inspection of Gas-Fueled Space and Water Heaters

Open this section

(a) Where a plumbing repair slip has been filed it shall be the responsibility of the inspectors of plumbing to see that gas-fueled space and water heaters are installed in dwellings, apartments and rooms where such heaters are permitted to be installed in lieu of central heat or supply of hot water. They shall see to it that the appliances are of types approved by the Department of Health and the American Gas Association, and are installed in compliance with these rules. Inspectors shall require the filing of a building notice where an appliance is to be placed in sleeping room where vent pipes are to be installed, or other work done.

(b) A building notice covering the installation of these appliances in dwellings shall be forwarded directly to the plumbing inspectors when approved as a permit. The installation of such appliances including Type B and other gas vents, but not chimneys, shall be inspected by inspectors of plumbing. If a building notice application does not call for construction of a masonry or metal chimney, it shall be reported as completed, by the plumbing inspector, provided the work was satisfactory with a note on his report "no structural work".

(c) If the building notice calls for the erection of a masonry or metal chimney, it shall be forwarded by the plumbing inspector to the construction inspector as soon as the plumbing inspector has found the installation of these gas appliances and vent connections satisfactory. The construction inspector shall report such an application completed if the construction of the chimney has been satisfactorily performed

§ 25-10. Issuing Approvals

Open this section

(a) A gas-fueled space or water heater installed after December 18, 1957, and a gas-fueled space heater installed prior to that date, in the residence portion of a multiple dwelling and installed after October 1, 1964, in one and two family dwellings, shall be approved by the Department of Buildings only if it is of a type approved by the Department of Health and the American Gas Association, and if it has been installed in compliance with these rules. A gas-fueled water heater installed in a multiple dwelling prior to December 18, 1957, and in a one or two family dwelling prior to October 1, 1964 shall be approved by this department only after it has been made to comply with all the requirements of these rules. The certification of approval of type of appliance by the Department of Health of such water heaters shall be attached to the plumbing repair slip or building notice.

(b) A building notice or plumbing repair slip which has been filed to cover the installation of only gas-fueled space heaters or only gas-fueled water heaters shall be reported as being satisfactorily completed only if all apartments in the building have been provided with either space or water heaters as the particular application specified. If an application calls for the installation of both space heaters and water heaters it shall be reported as being satisfactorily completed only if all apartments in the building have been provided with both space heaters and water heaters. Nor shall any application be reported as being satisfactorily completed unless all new appliances have been installed in compliance with these rules and all existing appliances have been made to conform with them.

(c) When the plumbing section signs off, as satisfactorily completed, a plumbing repair slip or a building notice application which provides for the installation of gas-fueled space heaters in all apartments of a multiple dwelling, including the apartments where gas-fueled space heaters may have been installed prior to December 18, 1957, they shall make a list of such premises and send a copy of the list to the Department of Housing Preservation and Development. Where water heaters also have been satisfactorily installed, that fact should be noted on the list. The list shall contain the premises and the application number under which the appliances have been installed, and shall be forwarded weekly.

§ 25-16. Substitution for Central Heating or Hot Water Supply

Open this section

Gas-fueled space or water heaters may be used in lieu of centrally supplied heat or hot water only in an apartment in a dwelling which complies with all the following requirements:

(a) The apartment shall consist of two or more living rooms.

(b) The apartment shall consist entirely of rooms used in Class A occupancy, or in one or two family dwellings.

(c) The apartment shall not be, in whole or in part, arranged, designed or intended to be used for single room occupancy.

(d) The apartment shall not have been formed, in whole or in part, as a result of work done to increase the number of apartments of a converted dwelling or a tenement under an application or plan filed with the department on or after December 9, 1955.

(e) The apartment shall not be located in a building which has been vacant under conditions and for periods which render it subject to the provisions of § 27-2089 of the Administrative Code.

(f) The apartment shall not have been converted or altered under plans filed with the department on or after December 9, 1955 so as to cause any existing or newly created portion of a Class A or Class B converted dwelling not previously constituting an apartment consisting of rooms used for Class A occupancy to become such an apartment.

(g) The apartment shall not be a part of Class A or Class B multiple dwelling which is or was converted to such dwelling from a single family or two-family dwelling under an application or plan filed with the department on or after December 9, 1955.

(h) The apartment shall not be in a tenement which, after being used or occupied as other than a tenement, is or was reconverted to a tenement under any application or plan filed with the department on or after December 9, 1955.

§ 25-21. Required Approvals of Appliances

Open this section

Gas-fueled space and water heaters, installed after December 18, 1957, in apartments in multiple dwellings, in lieu of centrally supplied heat or hot water where such centrally supplied heat or hot water supply is required by the Multiple Dwelling Code, and in one and two family dwellings installed after October 1, 1964 shall be types approved by the Department of Health and the American Gas Association.

§ 25-22. Prohibited Types of Water Heaters

Open this section

On and after December 18, 1957, it shall be unlawful to install in any apartment in any multiple dwelling, and after October 1, 1964 in a one or two family dwelling a gas-fueled water heater, so designed and arranged that it heats water in pipe coils placed at a distance from the hot water storage tank.

§ 25-23. Number and Capacity of Gas-Fueled Heaters

Open this section

(a) Where gas fueled heaters are permitted to be installed in lieu of the required centrally supplied heat, each "living room", as such term is defined in subdivision 18 of § 4 of the Multiple Dwelling Law, shall be heated by a heater placed in such room or in an adjoining room which connects with it except that a room whose exterior walls are exposed only on a fully enclosed inner court may be heated by a heater located one room removed from such room. For this purpose, an inner court shall be considered fully enclosed even though some of the enclosure walls are located on an adjoining lot. The aggregate input capacity of the heater or heaters installed in any apartment shall not be less than the number of living room times ten thousand (10,000) British thermal units per hour.

(b) Notwithstanding the provisions of the subdivision (a) of this section, there shall be installed and continuously maintained by the owner in each apartment gas-fueled heaters in such numbers and at such locations as shall be sufficient to heat such apartment to the minimum temperature which would be required to be maintained therein by the owner under the provisions of the Sanitary Code of the city relating to the heating of buildings, if such owner were required to furnish centrally supplied heat in such apartment.

(c) The requirements of subdivisions (a) and (b) of this section are not applicable when an apartment in a multiple dwelling is heated by gas-fueled space heater or heaters which were installed by a tenant prior to December 18, 1957, and in a one or two family dwelling prior to October 1, 1964 and owned by such tenant or successor tenant.

§ 25-24. Capacity of Water Heaters

Open this section

Gas-fueled water heaters shall be automatic storage types having a capacity of not less than twenty gallons and shall, in any event, be adequate to provide a supply of hot water as defined in § 27-2031 and § 27-2034 of the Housing Maintenance Code, and 24 RCNY Health Code § 131.042.

§ 25-25. Shut-Off Devices

Open this section

Each gas-fueled space or water heater installed in an apartment in a dwelling shall be equipped with an effective device which will automatically shut off the gas supply to such heater in the event that its pilot light or other constantly burning flame is extinguished, or in the event of an interruption of the gas supply to such heater. Such automatic gas shut-off device shall be of a type which, after it has shut off the supply of gas to a heater, will not permit such heater to be relighted unless such shut-off device is first reset manually.

§ 25-26. Gas Piping

Open this section

(a) The sizes of gas piping shall be such as to give an adequate volumetric flow of gas to all appliances. The minimum diameter of gas piping shall be three-quarters of an inch (3/4") except that a branch supplying only one appliance may be one-half inch (1/2") diameter.

(b) Each gas-fueled space and water heater shall be rigidly connected to the gas piping supplying gas to the apartment.

§ 25-27. Appliances in Sleeping Rooms

Open this section

(a) Gas-fueled water heaters shall not be installed in a room occupied for sleeping purposes, in bathrooms, or in any occupied room normally kept closed.

(b) It shall be unlawful to install a gas-fueled space heater in a room occupied for sleeping purposes except when the space heater is so designed, installed and operated for it:

(1) Obtains combustion air directly from the outside of the building or through a duct leading to the outside.

(2) It vents directly to space outside of the building other than an inner court, or is connected through a flue or outlet pipe with an outside chimney which conforms with the requirements of subarticle three of article twelve of the Building Code. A flue in an existing brick chimney may be used if it is in good condition and tests show that it will provide adequate draft.

§ 25-28. Clearances from Combustible Materials

Open this section

(a) Space heaters and water heaters approved by the American Gas Association Laboratories, shall have clearance from combustible materials in accordance with the terms of their approval.

(b) Gas-fueled space and water heaters shall be installed also in conformity with any applicable requirements of specifications Z21.30 of 1954 of the American Standards Association, except where these rules otherwise provide.

(c) Vent connectors and vent and outlet pipes shall be installed so as to provide a minimum clearance of three inches on all sides from combustible material. Vent and outlet pipes shall not pass through a floor. Where a vent or outlet pipe passes through partition or roof constructed wholly or in part of combustible material, a ventilated metal thimble not less than six inches larger in diameter than the pipe shall be provided. Any material used to fill the space between the vent pipe and the thimble shall be incombustible.

§ 25-29. Venting of Gas Appliances

Open this section

(a) Definitions. A flue, vent or outlet pipe is a conduit or passageway, vertical or nearly so, for conveying flue gases to the outer air. A vent connector is a pipe connecting an appliance with the flue, vent, outlet pipe or chimney.

(b) Every vent or outlet pipe serving a gas space or water heater shall be provided with a draft hood of a type approved by the American Gas Association, Inc., laboratories of the Underwriters' Laboratories, Inc., as conforming to accepted standards, unless the heater has an approved built-in draft hood, or has been approved by the American Gas Association without a draft hood. The draft hood shall be installed at the flue collar or as near to the appliance as possible and in the position for which it was designed, with reference to horizontal and vertical planes. The relief opening of the draft hood shall not be obstructed. A suitable cap shall be provided at top of vent pipes.

(c) Each gas-fueled space or water heater installed in an apartment in lieu of the required centrally supplied heat and hot water supply, respectively, shall be connected to a chimney flue, outlet pipe, or type B vent, complying with the requirements of subdivision (h) of this section, which shall be carried four feet above a flat roof and two feet above the highest part of a peaked roof, except that type B vents need not comply with this provision when equipped with a vent cap approved by the Department of Buildings or previously approved by the Board of Standards and Appeals for the prevention of downdraft. A flue in an existing chimney may be used if a licensed plumber certifies that he has made a smoke test of the flue and found no gas escaping through its walls, and made a test of the draft and found it adequate. However, window or wall type heaters of the sealed combustion chamber type which have been approved by the Department of Buildings or previously approved by the Board of Standards and Appeals may be vented in accordance with the approval of the Board, except as provided in subdivision (d) of this section.

(d) No gas-fueled space heater, including a window or wall type recessed heater and no gas-fueled water heater, installed in a dwelling, shall be vented to an inner court unless it is connected to a chimney complying with the requirements of Subchapter 15 of Chapter 1 of Title 27 of the Administrative Code (Building Code). Standard steel steam or water pipes are acceptable in such locations.

(e) Gas-fueled water heaters shall be located as close as practicable to a vent or flue. They should be so located as to provide short runs of piping to fixtures.

(f) Vent connectors shall consist of galvanized iron of not less than No. 26 U.S. gauge in thickness, cement-asbestos pipe, approved type B vents, enameled steel pipe of a quality acceptable to the superintendent as heat and corrosion resistant, or other materials satisfactory to the superintendent.

(g) Vent connectors shall have a cross-sectional area at least equal to the area of the vent outlets of the appliance and shall have a minimum diameter or dimension of three inches.

(h) Outlet pipes and vents, on the exterior of a building, shall consist of standard water, steam or soil pipes, cement-asbestos pipe, type B vents approved by the Department of Buildings or previously approved by the Board of Standards and Appeals, or other corrosion resistant materials satisfactory to the superintendent, all so connected as to prevent leakage at joints. Outlet pipes and vents on the exterior of a building shall be adequately supported and braced. Flues inside of building shall be constructed as low temperature chimneys. Type B vents may be used inside buildings when installed in accordance with the requirements of § 27-887(d) of the Administrative Code (Building Code) and with the conditions of their approval.

(i) Only vent connections serving appliances located in one story of a building may be made to any flue. The cross-sectional area of any flue shall be equal to or greater than the total cross-sectional area of all vents connected to it, but in any case the least internal dimensions shall be three inches.

(j) Vent connections may be made to a flue serving other heat producing appliances, above the connection of the other heat producing appliances, or the smoke pipe or vent connection from the gas appliance and the other heat producing device may enter the flue through a single opening if joined together by a Y fitting located as close as practical to the flue. The angle of intersection between the branch and the stem of the Y shall not exceed forty-five degrees. The area of the common outlet pipe shall not be less than the combined areas of the outlet pipes joined by the Y fitting.

(k) The horizontal run of vent pipe connectors shall not exceed three-fourths of the vertical rise of the flue to which the vent is attached, measured from the connection of the appliance to the top of the flue. A vent connector shall be pitched upward from the gas appliance with a slope of not less than one-fourth inch vertically for each foot of horizontal run.

(l) No dampers, steel wool or other obstructions shall be placed in any vent pipe or flue.

§ 25-30. Gas-Fueled Space Heaters Installed Prior to December 18, 1957

Open this section

(a) Gas-fueled space heaters installed prior to December 18, 1957, if of a type not approved by the Department of Health and the American Gas Association, shall be replaced by centrally supplied heat or by gas heaters approved by the said authorities on or before November 1, 1958, in any tenement and converted dwelling which contains ten or more apartments, and on or before November 1, 1959, in other tenements and converted dwellings.

(b) On or before the applicable dates given in subdivision (a) of this section, gas-fueled space heaters installed prior to December 18, 1957, in tenements and converted dwellings prescribed in said paragraph shall be made to comply with all the requirements of 28 RCNY §§ 25-23 to 25-29.

§ 25-31. Gas-Fueled Water Heaters Installed Prior to December 18, 1957

Open this section

(a) On or before November 1, 1958, in any tenement and converted dwelling which contains ten or more apartments, and on or before November 1, 1959, in other tenements and converted dwellings, any gas-fueled water heater installed prior to December 18, 1957, if of a type not approved by the Department of Health, shall be replaced by a supply of hot water or by a water heater approved by said department.

(b) On or before the applicable dates given in 28 RCNY § 25-30(a), gas-fueled dwellings described in said paragraph shall be made to comply with all the applicable requirements of 28 RCNY §§ 25-23 to 25-29, and all gas-fueled water heaters that have water heaters installed prior to December 18, 1957, in tenements and converted dwellings' sleeping rooms shall be removed.

(c) Any gas-fueled water heater so designed and arranged that it heats water in pipe coils placed at a distance from the hot water storage tank, installed prior to December 18, 1957, may be maintained in tenements and converted dwellings described in subdivision (a) of this section on and after the applicable dates given in said rule only if it is of a type approved by the Department of Health. However, no gas-fueled water heater shall be maintained in a sleeping room or bathroom.

§ 25-32. Maintenance of Space and Water Heaters

Open this section

(a) The owner of the tenement or converted dwelling and of the one and two family dwelling in which gas-fueled space and water heaters have been installed by him shall maintain each such appliance in a condition of good repair and in good operating condition.

(b) On and after November 1, 1958, in any tenement and converted dwelling which contains ten or more apartments, and on and after November 1, 1959, in any other tenement and converted dwelling, where a tenant provided a space or water heater on October 1, 1957, each such appliance shall be made to comply with all the applicable requirements of these rules and shall be maintained in a condition of repair and in good operating condition by the tenant.

(c) Should a tenant fail to comply with the requirements of subdivision (b) of this section, it shall be the duty of the owner of the tenement or converted dwelling to provide centrally supplied heat and a supply of hot water, or if such apartment is eligible therefore and he so elects, to install and continuously maintain space and water heaters therein which shall comply with the requirements of these rules.

(d) On and after November 1, 1958, in any tenement and converted dwelling which contains ten or more apartments, and on and after November 1, 1959, in any other tenement and converted dwelling, where gas-fueled space or water heaters were provided by the tenant, and the ownership of such appliances passes from the tenant or successor tenant, or if any such space or water heaters are removed from gas-fueled space or water heater, or temporarily for the purpose of repairs, then such an apartment, except for the purpose of immediate replacement by another owner will be subject to the duties imposed on an owner by subdivision (c) of this section.

§ 25-33. Existing Appliances in Ineligible Locations

Open this section

Where a gas-fueled space heater or water heater has heretofore been installed in a dwelling not complying with all the requirements of 28 RCNY § 25-16, nothing in these rules shall be construed to relieve the owner of his responsibility to provide for such dwelling centrally supplied heat and a supply of hot water.

§ 25-34. Instruction to Tenants

Open this section

The owner or the authorized agent of the owner shall instruct the tenant of each apartment wherein a space or water heater is located as to the proper method of using and operating such appliance.

§ 25-35. Variations

Open this section

Where there is a practical difficulty in carrying out the strict letter of the provisions of these rules, the borough superintendent may vary such provisions for a specific installation, provided the necessary safety is secured and the variance is not in conflict with the Administrative Code.

§ 25-51. Conduct and Maintenance of Lodging Houses

Open this section

(a) Lodging house, defined. As used in these rules, the term lodging house shall mean any house or building or portion thereof, in which persons are harbored, or received, or lodged, for hire for a single night, or for less than a week at one time, or any party of which is let for any person to sleep in, for any term less than a week. The term lodging house shall not be deemed to include a Class A multiple dwelling used or let for single room occupancy.

(b) Permits required. It shall be unlawful to conduct, maintain or operate a lodging house containing rooms in which there are more than three beds for the use of lodgers, or in which more than six persons are allowed to sleep unless a permit therefor has been issued by the Commissioner of Housing Preservation and Development.

(c) Procedure for obtaining a permit.

(1) Information to be given in application. Each application for a permit shall file with the Department of Housing Preservation and Development in duplicate, a written application, dated, signed by himself, and correctly setting forth:

(i) The full name and address of the proprietor of the lodging house and of the owner of the premises.

(ii) The location of the lodging house.

(iii) The portions of the building intended to be used as a lodging house.

(2) Certificate from the Fire Department. The applicant shall procure from the Fire Department of the City of New York a certificate to the effect that the premises for which a permit is desired complies with all laws, rules and regulations enforceable by the Fire Department.

(d) Conduct, maintenance and operation of lodging houses.

(1) Every permittee shall conduct, maintain and operate such lodging house in accordance with the terms of his permit and the rules and regulations of the Department of Housing Preservation and Development.

(2) Permit to be displayed. The permit of the Department of Housing Preservation and Development issued for such lodging house shall be continuously and conspicuously displayed in the office or hall of such lodging house.

(3) Numbers of lodgers permitted.

(i) No keeper of a lodging house shall receive lodgers therein without displaying continuously and conspicuously in each room a card issued for such room by the Department of Housing Preservation and Development setting forth the maximum number of lodgers permitted to be accommodated in such room, and also a copy of these rules and regulations.

(ii) No keeper of a lodging house shall accommodate in any sleeping room thereof a number of lodgers greater than the number set forth on the card issued for such room by the Department of Housing Preservation and Development; nor shall he accommodate any lodgers in any room in which a card, duly issued therefor, is not displayed as above described.

(4) Ventilation.

(i) In every lodging house each room shall be adequately ventilated as required by law and to the satisfaction of the Department of Housing Preservation and Development.

(ii) In every sleeping room there shall be provided not less than 400 cubic feet of air space per bed.

(iii) Neither side of any bed shall at any time be nearer than two feet to the side of any other bed.

(iv) All beds shall be so arranged that the air shall circulate freely under each of them.

(v) In the ease of all lodging houses for which permits are for the first time applied for after the year 1919, no beds or bunks shall be placed one above another.

(5) Airing, etc.

(i) Except when extreme severity of the weather prevents, all windows of sleeping rooms, waterclosets, washrooms and bathrooms shall be kept open not less than one foot at the bottom and one foot at the top at least four hours daily.

(ii) Beds occupied at night shall be vacated by 10 a.m. or 12 m., and the bedding thereof shall be turned over and exposed to the air from 10 a.m. to 2 p.m. or from 12 m. to 4 p.m. daily, as prescribed by the permits issued for each lodging house.

(iii) For the accommodations of lodgers working by night, special beds or rooms shall be set apart for their use during the day, but the bedding of such beds must be turned over and exposed to the air in a room with outside windows, open as above prescribed, for at least four consecutive hours daily.

(iv) Only servants at work or lodgers accommodated as per-subparagraph (iii) of this subdivision, shall be allowed in sleeping rooms during the four-hour period for airing, as specified in the permit issued for such lodging house, in any lodging house in which accommodations are provided for male lodgers, no female servants shall be employed; likewise, where accommodations are provided for female lodgers, no male servants shall be employed.

(6) Beds and bedding.

(i) In every lodging house there shall be provided for each lodger a separate bed with bedspread, bedding and bedclothes satisfactory to the Department of Housing Preservation and Development.

(ii) All portions of the building, including all furniture, bed clothing, mattresses and pillows shall always be kept clean and free from vermin.

(iii) Sheets and pillow cases shall be kept in a condition clean and satisfactory to the Department of Housing Preservation and Development.

(iv) In the case of all lodging houses for which permits are for the first time applied for after the year 1910, the frames of all beds shall be of metal.

(7) Waterclosets.

(i) In every lodging house there shall be provided waterclosets in the ratio of at least one watercloset to every fifteen beds or fraction thereof.

(ii) In every lodging house for which a permit shall be first applied for after February 1st, 1911, there shall be provided at least one watercloset on each floor, and watercloset shall be provided on every floor in the ratio of at least one to every fifteen beds or fraction thereof on such floors.

(iii) Every watercloset shall be properly ventilated by an unobstructed opening to the outer air.

(iv) No gas or offensive odors shall be allowed to escape from any water closet, sewer or outlet into any sleeping room or part thereof. Each watercloset shall be provided with a self-closing door, which shall be cut away at the bottom so as to provide adequate ventilation.

(v) In no lodging house shall any person be allowed to sleep in a room in which there is a watercloset.

(vi) In every lodging house for which a permit shall be first applied for after February 1st, 1911, there shall be provided at least one washroom on each floor.

(vii) In every lodging house there shall be provided washrooms with running water, set wash basins or other individual washing appliances satisfactory in character to the Department of Housing Preservation and Development. Such individual appliances shall be provided in proportion to the number of beds in the lodging house as follows: One such appliance for every ten beds or fraction thereof.

(8) Baths.

(i) In every lodging house shower baths shall be provided in the ration of at least one shower bath to every fifty beds or fraction thereof, or tub baths shall be provided in the ration of at least one tub bath to every twenty-five beds or fraction thereof.

(ii) All such baths shall be provided with hot and cold running water, and shall be at all times accessible for the use of lodgers free of charge.

(9) Water and towels. An adequate supply of water and clean individual towels shall be provided. The use of common towel is prohibited.

(10) Floors and walls of waterclosets, etc. In every lodging house the floors of all waterclosets, washrooms and bathrooms, and the walls thereof to a height of at least four feet above the floor shall be constructed of such durable, waterproof material as may be approved by the Department of Housing Preservation and Development.

(11) Cleanliness and repair.

(i) Every lodging house and every part thereof shall be at all times kept clean and free from dirt, filth garbage and rubbish in or on the premises belonging to or connected with the same.

(ii) All waterclosets, washbasins, baths, windows, fixtures, fitting and painted surfaces shall be at all times kept thoroughly clean and in good repair.

(iii) The floors, walls and ceilings of all rooms, passages, and stairways must be at all times kept clean and in good repair.

(iv) If painted with oil, all walls and ceilings shall be thoroughly washed with soap and water at least twice yearly, and at such other times as the Department of Housing Preservation and Development may direct.

(12) Spitting and cuspidors.

(i) In each hall, room, cubicle, watercloset, washroom and bathroom of every lodging house there shall be provided a sufficient number of cuspidors or spittoons.

(ii) In every such room, etc., there shall be continuously and conspicuously a sing: "SPITTING FORBIDDEN EXCEPT IN PROPER RECEPTACLES."

(iii) All such cuspidors or spittoons shall be of durable waterproof material and shall be thoroughly cleaned at least once daily, and shall be at all times maintained in a condition satisfactory to the Department of Housing Preservation and Development.

(13) Method of sweeping regulated. Sweeping of any portions of such lodging houses shall be so performed as to avoid the raising of dust in the process. Dry sweeping prohibited.

(14) Illness. It shall be the duty of the keeper, agent, or owner of every lodging house to immediately report to the Department of Health the occurrence of any illness in such house.

(15) No Women or Children lodged. In no lodging house in which men are lodged shall any women or girl be lodged or any boy under the age of sixteen years, unless accompanied by his father or legal male guardian.

(e) Violations, revocation or suspension of permit. A violation of any of the foregoing rules and regulations shall constitute sufficient cause for the revocation or suspension of a permit by the Commissioner of Housing Preservation and Development.

§ 25-61. Signs at Incinerator Service Openings

Open this section

(a) Signs on doors leading to the service openings shall be not less than eight inches wide and not less than 3 inches high, and shall have letters not less than one-quarter inch in height.

(b) Signs placed on the walls over the hoppers shall be not less than ten inches wide and four inches in height and shall have letters not less than five-sixteenths of an inch in height.

(c) The lettering of the signs shall be of the bold type and shall be properly spaced to provide good legibility, and the letters and the background shall be of contrasting colors.

(d) Signs on doors shall be located on the hall side and approximately five feet above the floor.

(e) Signs shall be durable and shall be substantially secured to the door wall.

(f) Lighting shall be sufficient to make the signs easily legible at all times.

§ 25-71. Signs Showing the Maximum Lawful Occupancy for Sleeping Purposes of Apartments, Suites of Rooms and Single-Room Units Constituting "Accommodations for Transients."

Open this section

(a) (1) Except as otherwise provided in paragraph (5) of this subdivision (a), the owner of every multiple dwelling containing any accommodations for transients (see definition of accommodations for transients in subdivision (b) hereof), except structures containing not less than 200 rooms and classified by the department as hotels (whether a class A or class B multiple dwelling), shall install and maintain signs therein in accordance with the applicable requirements set forth in paragraph two, three, four and five of this subdivision.

(2) There shall be displayed in each apartment, suite of rooms and single-room unit constituting such accommodations for transients, a sign which shall show both the currently applicable total maximum lawful occupancy, for sleeping purposes, of such apartment, suite or unit, and the currently applicable maximum lawful occupancy, for sleeping purposes, of each living room constituting a part of each such apartment or suite.

(3) In addition, in each room in any such apartment or suite, there shall be displayed a sign showing the maximum lawful occupancy, for sleeping purposes, of such room.

(4) Such signs shall be displayed in each such apartment, suite of rooms, single-room unit and living room, in conformity with the applicable requirement of paragraphs two, three and four of this subdivision.

(5) Such signs need not be displayed in any apartment, suite of rooms, single-room unit or dormitory in a hotel (whether a class A or class B multiple dwelling), which apartment, suite, unit or dormitory consists of a room or rooms used for class B occupancy (see definitions of "room used for class B occupancy") lawfully, during any time while such apartment, suite, unit or dormitory is occupied for sleeping purposes by any person or persons, none of whom has occupied same for such purposes for a continuous period exceeding eighty-five days.

(b) Accommodations for Transients.

(1) Any apartment, suite of rooms or single-room unit, consisting in whole or in part of any room or rooms used for class B occupancy, or any portion of any such apartment or suite, or

(2) any dormitory, or

(3) any apartment or portion thereof used for single room occupancy.

(c) Application. These rules shall apply to the signs which are required by § 27-2080 of the Administrative Code to be installed and maintained in each apartment, suite of rooms and single-room unit constituting "accommodations for transients" as described in subdivision (b) of this section.

(d) Material. Signs shall be constructed of metal, slow-burning plastic or other material approved by the Commissioner, and shall be substantial, rigid and durable in construction. Signs of cardboard or heavy paper may be used if such material is encased in strong metal, wood or plastic frames and is covered by clear plastic or glass not less than one sixteenth inch (1/16") in thickness and if provided with substantial backing. Signs shall be provided with means for fastening securely to the wall.

(e) Room signs. The following information shall appear on signs required in rooms in which not more than one (1) adult is permitted to sleep:

Department of Housing Preservation and Development City of New York Premises: ________________________________________ (address of building) Room No. ________________________________________ on ________________________________________ story. Not more than ONE (1) ADULT permitted to sleep in this room. § 27-2075, Administrative Code.

The following information shall appear on signs required in rooms in which not more than two (2) adults are permitted to sleep:

Department of Housing Preservation and Development City of New York Premises: ________________________________________ (address of building) Room No. ________________________________________ on ________________________________________ story. Not more than TWO (2) ADULTS permitted to sleep in this room. § 27-2075 of the Administrative Code. In both of the above instances the address of the premises and the location of the room must be shown, in addition to the number of persons permitted to sleep in such room.

(f) Apartment signs. The following information shall appear on signs required in apartments and suites of rooms showing the total maximum occupancy for sleeping purposes of entire apartment or suite of rooms:

Department of Housing Preservation and Development City of New York Premises: ________________________________________ (address of building) Apartment

(or suite) No. ______________ on ______________ story. Not more than a TOTAL OF ______________ ADULTS permitted to sleep in this apartment (or suite). § 27-2075, Administrative Code.

The permitted lawful occupancy for sleeping purposes of each room in this apartment is as follows: Room No. ______________ not more than ______________ ADULTS Room No. ______________ not more than ______________ ADULTS

(Provide separate line for each room in apartment or suite.)

The above sign must show the address of the premises, the location of the apartment or suite of rooms, the total maximum lawful occupancy for sleeping purposes of the entire apartment or suite, and the permitted lawful occupancy for sleeping purposes of each individual room in said apartment or suite. The maximum lawful occupancy for sleeping purposes of each room shall be shown on a separate line, with a proper designation by room number in order to identify each room.

(g) Size of sign and lettering. The lettering shall be of the Gothic type. The letters forming "DEPARTMENT OF HOUSING PRESERVATION AND DEVELOPMENT", and the letters and numerals showing the number of ADULTS, shall be not less than one-quarter inch (1/4") in height. All other letters and numerals shall be not less than three-sixteenths inch (3/16") in height. Letters shall be of such width and spacing as will provide the greatest legibility. The letters and the background of the sign shall be of contrasting colors. The size of sign shall be sufficient to accommodate the required lettering and to provide a margin of not less than one-quarter inch (1/4") about the lettering on all sides.

(h) Location of signs. Signs shall be located at a distance of not less than five feet (5') or more than six feet (6') above the floor. Where a sign is required to be displayed in a room, same shall be so located that it is visible at all times to the occupant or occupants of such room. Where a sign showing the total maximum occupancy for sleeping purposes of an entire apartment or suite of rooms is required to be displayed in such apartment or suite, such signs shall be located in a portion of such apartment or suite through which it is necessary for every occupant to pass after entering or before departure from such apartment or suite. Such sign shall be visible at all times to the occupants of such apartment or suite.

(i) Lighting. Sufficient lighting shall be provided so that the sign will be plainly legible at all times when the apartment or room is occupied.

(j) Maintenance. Signs shall be maintained in a clean and legible condition. Signs that are damaged shall be repaired or replaced immediately. Signs that are painted over shall be replaced or restored to the original condition. Signs that become loose shall be securely fastened.

§ 25-81. Signs Identifying Owner, Managing Agent and Superintendent; Plans on Premises

Open this section

(a) (1) Identification signs for the purpose of identifying the owners and managing agents of multiple dwellings by the display of the serial number, shall comply with the applicable provisions of these rules.

(2) Identification signs for the purpose of identifying the superintendents, janitors or housekeepers of multiple dwellings, wherein such employees are required by the provisions of § 83, Multiple Dwelling Law, shall comply with the applicable provisions of these rules.

(b) Signs shall be constructed of metal, slow-burning plastic or other material approved by the Commissioner and shall be substantial, rigid and durable, in construction. Signs of cardboard or heavy paper may be used if such material is encased in strong metal, wood or plastic frames and is covered by clear plastic or glass not less than one-sixteenth inch in thickness and if provided with substantial backing. Signs shall be provided with means for fastening securely to the wall.

(c) (1) The following information shall appear on the sign, prescribed in paragraph (1) of subdivision (a) of this section, in four lines of lettering as indicated and in the order indicated:

Department of Housing Preservation and Development City of New York Serial Number Street Address of Building

(2) The following information shall appear on the sign, prescribed in paragraph (2) of subdivision (a) of this section, in four lines of lettering as indicated and in the order indicated:

Title (Superintendent, Janitor or Housekeeper) Name of Superintendent, Janitor or Housekeeper Address of Superintendent, Janitor or housekeeper (including apartment number, if any)

(d) Telephone number of superintendent, janitor or housekeeper. The size of sign shall be sufficient to accommodate the required lettering and provide a margin of not less than one-fourth inch about the lettering on all sides.

(e) (1) Serial numbers, as specified in § 27-2104 shall be determined and assigned by the Department of Housing Preservation and Development. No serial number shall be changed or ordered without the approval of the Department of Housing Preservation and Development. The serial number shall be placed on the sign by the owner or his representative.

(2) The street address of the building consisting of the house number and the street shall be placed on each sign by the owner or his representative.

(3) The lettering shall be gothic type. The numbers composing the serial number shall be not less than one-half inch in height. The letters forming "Department of Housing Preservation and Development" and the street address shall not be less than one-fourth inch in height. All other letters shall be not less than three-sixteenth of an inch in height. Letters shall be of such width and whatever as will provide the greatest legibility.

(f) The lettering of signs, as specified in § 27-2104, shall be Gothic type and shall not be less than three-sixteenths of an inch in height. Letters shall be of such width and spacing as will provide the greatest legibility.

(g) The letters and the background of the sign shall be of contrasting colors.

(h) Signs shall be approved by the Department of Housing Preservation and Development before installation.

(i) Signs shall be located in the entrance hall at the main entrance to the building at the street floor. Signs shall be placed preferably over the mail boxes but, in any case, shall be conspicuously displayed in a prominent location in the entrance hall. Signs shall be located between 7 feet and 9 feet above the floor.

(j) Signs shall be fastened directly to the wall by screws or bolts in a rigid, substantial manner, or by other means as may be approved by the Department of Housing Preservation and Development.

(k) Sufficient lighting shall be provided so that the sign will be plainly legible at all times.

(1) Signs that are defaced, damaged or removed, shall be promptly repaired or replaced. Signs shall be maintained in such manner as to be easily read at all times.

§ 25-91. Rules for Enforcement of Subdivision (4) of § 27-2098 of the Administrative Code of the City of New York

Open this section

(a) The words "may be reached at all hours and time" within the meaning of subdivision (4) of § 27-2098 of the Administrative Code shall be construed to mean a telephone number at or through which in the normal course of events a person might reasonably be expected to be reached at all times and this shall be deemed to include:

(1) the telephone number of the residence of such person; or

(2) the telephone number of an agent fully authorized to act on behalf of the owner; or

(3) the telephone number of a person, firm or corporation, including an answering service, which has in its possession at all times a telephone number at which the person or agent can be reached at all times. A corporation may comply with this subdivision by any of the means as hereinabove set forth.

(b) The term "emergency repairs" within the meaning of this subdivision shall be construed to designate a condition in a multiple dwelling which, in the opinion of the department, constitutes, or if not properly corrected, will constitute, a fire hazard or a serious threat to the life, health or safety of occupants thereof.

§ 25-101. Owner's Right of Access and Requirements for Notification

Open this section

(a) (1) Owner to give notice. Where an owner or his or her representative seeks access to a dwelling unit, suite of rooms or to a room, under the provisions of § 27-2008 in order to make an inspection for the purpose of determining whether such places are in compliance with the provisions of the multiple dwelling law or the Administrative Code, such owner or representative shall notify the tenants not less than twenty-four hours in advance of such time of inspection.

(2) Where an owner or his or her representative seeks access to make improvements required by law or to make repairs to a dwelling unit, suite of rooms or to a room, such owner or representative shall give written notice to the tenant not less than one week in advance of the time when the improvements or repairs are to be started, except where otherwise provided in paragraph (3) of this subdivision.

(3) Where an owner or his or her representative seeks access to make repairs (i) that are urgently needed to a dwelling unit, suite of rooms or a room, as in the case where a class C violation of the Housing Maintenance Code has been issued, except where such class C violation is for the existence of a lead-based paint hazard, or (ii) in the case of an emergency where repairs are immediately necessary to prevent damage to property or to prevent injury to persons, such as repairs of leaking gas piping or appliances, leaking water piping, stopped-up or defective drains, leaking roofs, or broken and dangerous ceiling conditions, such owner or representative shall not be required to provide written advance notice, but shall be required to notify the tenant or tenants by such actions as telephone, email, or by knocking on the occupant's door at a reasonable time when he or she would be expected to be present.

(4) Where an owner or his or her representative must make a repair in a public area or other area of a dwelling that may result in an interruption of essential services such as utilities (heat, hot water, cold water, gas, electricity, or elevator) that is expected to continue for more than two hours, the owner or his or her representative shall provide written notice to the tenants by posting a notice in a prominent place within the public part of the building and on each floor of such building at least twenty-four hours prior to such interruption. However, if such interruption is not expected to continue for more than two hours or is due to emergency repairs that were not anticipated and must begin immediately, advance notice is not required, provided that notice shall be posted as soon as possible if such work continues for two or more hours. Such notice shall identify the service to be interrupted, the type of work to be performed, the expected start and end dates of the service interruption, and shall be updated as necessary. Such notice shall be provided in English, Spanish, and such other language as the owner deems necessary to adequately provide notice to the tenants. Such notice shall remain posted until the interruption of essential services interruption ends. A sample notification form is provided in subdivision (e) of this section.

(b) Notices to be in writing. Where an owner is required to give notice in advance of seeking access to a dwelling unit, suite of rooms or to a room, as required by subdivision (a) of this section, such notice shall be in writing, dated, and shall contain a statement of the nature of the improvement or repairs to be made, unless specifically stated otherwise in these rules.

(c) Authorization to be in writing. Where a representative of an owner seeks access to a dwelling unit, suite of rooms, or rooms, the authorization of the owner shall be in writing and the representative shall exhibit such authorization to the tenant when access is requested.

(d) Hours when access to be permitted. Except as provided in paragraph (3) of subdivision (a) of this section, access to a dwelling unit, suite of rooms, or rooms, shall be limited to the hours between nine antemeridian and five post-meridian, unless otherwise agreed to by the tenant. Access shall not be required on Saturdays, Sundays or legal holidays, unless otherwise agreed to by the tenant, except as provided in paragraph (3) of subdivision (a) of this section.

(e) Sample Notification Form for Interruption of Essential Services.

NOTICE OF INTERRUPTION OF SERVICES

Please be advised that due to repair work in the building located at _________________, there will be an interruption in the following building services:

o heat o hot water o cold water o gas o electricity o elevator

The interruption in service is expected to begin on ______________ and to end on ______________.

The repair work is for the purpose of

_______________________________________________________________

_______________________________________________________________

AVISO DE INTERUPCION DE SERVICIOS

Por favor tenga en cuenta que debido a reparaciones en el edificio localizado en _________________, habrá una interrupción en los siguientes servicios del edifico:

o Calefacción o Agua Caliente o Agua Fria o Gas o Electricidad o Elevador

La interrupción en servicio se espera comenzar en ______________ y terminar en ______________.

El trabajo de reparación es para el propósito de

_______________________________________________________________

_______________________________________________________________

(f) For any notice provided pursuant to paragraph (4) of subdivision (a) of this section, an owner may, in lieu of posting a physical notice, instead install a digital sign that otherwise complies with such paragraph. Such digital sign must comply with the requirements of 28 RCNY § 12-01(f) and be programmed in a manner to distinguish the unique and temporary nature of the interruption of services sign from all other digital signs, provided that, if the digital sign becomes inoperable, the owner must forthwith display physical notices as described in this section until such time as the digital sign is made operable.

(g) The display of a digital sign in a prominent place within the public part of the building where other digital signs are located does not relieve an owner of the requirement set forth in paragraph (4) of subdivision (a) of this section to post a written notice of the relevant service interruption on each floor of the building. Such additional signs on each floor of the building are not required to be digital signs that comply with the requirements of subdivision (f) of this section.

(h) If an owner installs a digital sign as allowed pursuant to subdivision (f) of this section, such owner must also install a digital sign as described in 28 RCNY § 12-01(e) (notice regarding smoke detecting devices), 28 RCNY § 12-06(c) (notice regarding carbon monoxide alarm requirements), 28 RCNY § 12-09.1(f) (notice regarding natural gas detecting devices), 28 RCNY § 25-201(c) (notice regarding collection and disposal of garbage), 28 RCNY § 46-01(b) (notice regarding housing information guide), 28 RCNY § 56-03(c) (notice regarding temperature reporting device), and 28 RCNY § 59-01(c) (notice regarding bedbug infestation).

(Amended City Record 7/21/2015, eff. 8/20/2015; amended City Record 1/2/2026, eff. 2/1/2026)

§ 25-111. Boiler Room Enclosure for Multiple Dwellings with Central Heat

Open this section

(a) A separate enclosure shall not be required when the central heating plant is located in a cellar that is used for no other purpose, provided that

(1) The building is occupied entirely for residential purposes.

(2) The first tier is of fireproof construction with no opening to the upper stories.

§ 25-121. Signs Indicating Floors in Multiple Dwellings Pursuant to § 27-2047 Administrative Code

Open this section

(a) Signs may be posted or painted and may consist of numerals or letters only.

(b) Numerals or letters shall be not less than three inches in height and except for the numeral one (1), shall be not less than two inches in width and shall be sufficiently large to be easily read.

(c) Numerals or letters shall be of a color which will contrast with the background. The numerals or letters may or may not be fixed to other material.

(d) Lighting shall be sufficient to make the signs legible at all times. Lighting within the sign or in back of the sign shall not be required if other illumination is sufficient to make the sign legible.

(e) Signs shall be durable and shall be substantially secured to the walls.

(f) The superintendent may vary the provisions of these rules where strict compliance would produce unnecessary hardship, provided the intent of the law and rules is obtained.

§ 25-131. House Numbers

Open this section

(a) On each building erected or altered after the effective date of these rules there shall be affixed in a conspicuous location at or near the main entrance of a building, the house number of the building.

(b) House numbers shall be of such size and shall be so located as to be clearly visible from the public sidewalk during daylight hours. Where the building is remote from the sidewalk, the number of the building and a directional arrow indicating the building location shall be provided in addition to the conspicuous number at the entrance to the building.

(c) House numbers shall be constructed of durable material and shall be maintained in such condition as to be readily visible as required by subdivision (b) of this section.

§ 25-141. Measuring Floor Area of Public Halls, Stairs, Fire-Stairs and Fire-Towers in Multiple Dwellings to Determine Lighting Requirements

Open this section

(a) To compute the square feet of floor area of public halls in multiple dwellings having an unenclosed stair, the floor area of the public hall and the horizontal area of the stair opening shall be added. At the lowest story, where there is an ascending flight of stairs but no descending flight of stairs, only the area of the actual flight of stairs shall be added to the floor area of such lowest story.

(b) To compute the square feet of floor area of a fire-stair or a fire-tower in a multiple dwelling, one-half of the horizontal area of such fire-stair or fire-tower, measured from the wall of the stair landing on one level to the wall of the stair landing on the next level, shall be deemed to be the floor area at each such level.

(c) Where the light from the fixture at the highest story provides adequate illumination, in the opinion of the department, no lighting fixture shall be required at the roof level of the stair bulkhead.

§ 25-151. Entrance Doors, Locks and Intercommunication Systems

Open this section

(a) Bulkhead doors and scuttles shall have no key locks and shall not be locked by a key at any time. The only permissible and acceptable means of securing a bulkhead door or scuttle is by means of a movable bolt or hook on the inside.

(b) Subdivision (n) of 28 RCNY § 25-174 in its last un-numbered paragraph provides as follows: "All passageways required under these rules shall be not less than seven feet (7'0") in height and not less than three feet (3'0") in width and shall at all times be kept clear and unobstructed. Doors and gates at the end of such passageways are prohibited, except that a door or gate equipped with an approved-type knob or panic bolt which shall be readily openable from the inside will be permitted at the building line. Doors and gates provided with key locks or padlocks are prohibited."

(c) Where an entrance door leading from a vestibule to the main entrance hall or lobby is equipped with one or more automatic self-closing and self-locking doors, the entrance door from the street to the vestibule need not be equipped with automatic self-closing and self-locking doors.

(d) Every entrance from the street, court, yard or cellar to a class A multiple dwelling erected or converted after January 1, 1968 containing eight or more apartments shall be equipped with automatic self-closing and self-locking doors. Such multiple dwelling, as aforesaid, shall also be equipped with an intercommunication system to be located at the required main entrance door.

(e) On or after January 1, 1969, every entrance from the street, court, yard or cellar to a class A multiple dwelling erected or converted prior to January 1, 1968 containing eight or more apartments, provided that a majority of tenants in occupancy request or consent in writing, shall be equipped with automatic self-closing and self-locking doors and shall also be equipped with an intercommunication system.

(f) Every self-locking door required under this section shall be installed and maintained so as to be readily openable from the inside without the use of keys.

(g) The minimal devices acceptable for the intercommunication system shall be a bell or buzzer system, or a speaking and listening device to permit communication by voice between the occupant of each apartment and a person outside such required main entrance door, and a return buzzer mechanism to release or open the lock to the aforesaid required door.

(h) The bell and intercommunication system shall be located at the required main entrance door so that a person may readily reach the door when the unlocking buzzer is activated.

(i) No push button device shall be more than six feet from the floor and the speaking and listening device shall be installed to be not less than four feet and not more than five feet from the floor.

(j) The device or devices for the intercommunication system installed in the apartment shall be readily accessible to the occupant.

(k) The device or devices for the intercommunication system installed hereunder shall be of a type and kind approved by the Department of Buildings or previously approved by the Board of Standards and Appeals.

(1) Devices which have been previously installed and which are in good condition and performing in an adequate manner may, in the discretion of the department, be accepted.

§ 25-161. Installation of Peepholes

Open this section

(a) These new peepholes, or door interviewers, must bear a label showing the approval of the Department of Buildings or the previous approval of the Board of Standards and Appeals.

(b) The peepholes must be so located as to enable a person in such housing unit to view from the inside of the entrance door any person immediately outside.

(c) The distance above the inside finished floor to the center of the peephole shall be approximately 5 feet.

(d) The cutout shall not affect the adequacy of any stiffening member of the door.

(e) Peepholes installed prior to the enactment of the legislation will be acceptable unless the cutout for the peephole has affected the adequacy of any stiffening member of the door.

§ 25-162. Installation of Two 50 Watt Lights at Front Entrance Way

Open this section

(a) All electrical work shall be done in accordance with the requirements and approval of the Department of Buildings.

(b) The installation shall be a separate circuit or connected to the house line servicing the public halls.

(c) The lights shall be encased in a metal guard or shatterproof globe.

(d) The lights of at least 50 watts of incandescent or equivalent illumination shall be placed on each side of the front entrance-way at a height of between 7 to 11 feet above floor level adjacent to such entrance-way and adequate to light same.

§ 25-163. Installation of Viewing Mirrors in Self-Service Elevators

Open this section

(a) Mirrors shall be made of polished metal.

(b) Mirrors shall be of such size and so located on the car wall opposite the car entrance so that a person entering the elevator may have a complete view of the interior of the car. It shall not be necessary to provide a view of the floor and ceiling.

(c) The mirror shall be so located as not to interfere with or endanger passengers in the elevator.

(d) Mirrors shall be mounted and secured so that they cannot be readily removed by the public.

§ 25-164. Installation of Lights in Rear Yards, Side Yards, Front Yards and Courts

Open this section

(a) All electrical work shall be done in accordance with requirements and approval of the Department of Buildings.

(b) The installation shall be a separate circuit or connected to the house line servicing the public halls.

(c) The light or lights, of at least 40 watts of incandescent or equivalent illumination, shall be placed so as not to create a nuisance.

(d) The lights shall be so located as to adequately light all portions of the rear yards, side yards, front yards and courts.

(e) Lights are not required in an inner court that is accessible only from the interior of the building and to which access is restricted for clean-out purposes.

§ 25-171. Fire-Retarding of Entrance Halls, Stair Halls and Public Halls in Old Law Tenements and Converted Dwellings

Open this section

(a) Intent. The fire-retarding rules herewith set forth are approved by the Department of Buildings for old law tenements and converted dwellings where their entrance halls, stair halls and public halls are required, by § 189, subdivisions 1 and 4, § 238, subdivision 4, and § 218, subdivisions 5 and 6, Multiple Dwelling Law, and § 27-2044, Housing Maintenance Code, to be fire-retarded in a manner approved by the Department of Buildings.

(1) All entrance halls, stair halls and public halls, including service halls and stairs, shall be fire-retarded to the extent required by the Multiple Dwelling Law and the Multiple Dwelling Code and the Housing Maintenance Code.

(2) It is the intent that all wood structural members of partitions, ceilings and stair soffits shall be completely protected with fire-retarding materials where they may be exposed to fire in entrance, stair and public halls. To this extent these rules and regulations cover only general conditions and are not designed to cover specific or special cases. Where such may occur the owner is required to consult the Department of Buildings and receive instructions before work is started.

(3) Where existing dumbwaiter shafts are located in, or open on public halls which are required to be fire-retarded, such dumbwaiter shafts, when not constructed of fireproof or fire-retarding materials, shall be fire-retarded on the inner side, from the lowest story to the roof inclusive, in accordance with the requirements of paragraph (1) of subdivision (b) of this section or paragraph (2) of subdivision (b) of this section, except in cellar where such shafts shall be enclosed with fireproof materials. All doors opening from such dumbwaiter shafts shall be self-closing, and doors and assemblies when of wood or other non-fireproof construction shall be lined on both sides with No. 26 U.S. gauge metal, except in cellar where doors and assemblies shall have a fire-resistive of at least one (1) hour.

(4) It is not intended that these rules and regulations in themselves require plans to be filed. However, should any work involve structural changes, then plans are required to be filed in the Department of Buildings and such changes shall be subject to all other Rules and Regulations applicable thereto.

(5) Work shall not commence until satisfactory evidence has been submitted to the Department of Buildings that compensation insurance has been obtained in accordance with the provisions of the Workmen's Compensation Law. It is the intent of 238, subdivision 4, Multiple Dwelling Law, that every entrance hall, public hall and stair hall in every old law tenement four stories or more in height shall be fire-retarded. Every old law tenement three stories and a basement, or three stories, basement and cellar in height shall be deemed to be four stories in height when the main entrance from the grade is to the basement, and every entrance hall, public hall and stair hall in such building shall be fire-retarded. In old law tenements where the entrance halls, public halls and stair halls are required to be fire-retarded, existing wood stairs shall be fire-retarded in conformity with the requirements of these rules and regulations, whether or not such halls had been fire-retarded in accordance with plans filed with and approved by the former Tenement House Department or Department of Buildings, prior to the enactment of subdivision 4 of § 238 of the Multiple Dwelling Law.

(b) Partitions. All existing partitions separating from entrance halls, stair halls and public halls, or otherwise forming enclosing partitions of entrance halls, stair halls and public halls, shall be fire-retarded by any one of the following methods:

(1) Metal lath and cement of gypsum mortar. Completely remove all existing materials to face of studs or other structural members on hall side of partitions and recover with metal lath and two coats of cement of gypsum mortar. If cement mortar is used it shall be three-quarters inch (3/4") thick, if gypsum mortar is used it shall be one inch (1") thick. The second coat of mortar shall not be applied until the first coat has thoroughly set and in no case shall the second coat be applied on the same day that the first coat of mortar is applied. In lieu of the above method, completely remove all combustible materials from plaster face of partitions on hall side and repair existing plaster. After inspection, cover existing plaster with herringbone or similar approved type metal lath with rigid rib reinforcement to provide good bond between new and existing plaster. Cover lath with two coats (scratch and brown) of cement of gypsum mortar as above. The first coat of cement mortar (scratch) shall be composed of one (1) part of Portland cement to one and one-half (1 1/2) parts of sand, with an additional volume of hydrated lime not greater than ten (10) percent of the volume of Portland cement. The second coat (brown) shall be composed of one (1) part of Portland cement to three parts (3) of sand, with an additional volume of hydrated lime not greater than ten (10) percent of the volume of Portland cement. The first coat (scratch) of gypsum mortar shall be composed of one (1) part of gypsum to one (1) part of sand. The second coat (brown) of gypsum mortar shall be composed of one (1) part of gypsum to one and one-half (1 1/2) parts of sand.

(2) Plaster boards and gypsum mortar or stamped metal. Completely remove all existing materials to face of studs or other structural members on hall side of partitions and recover with plaster boards or perforated rock lath three-eights inch (3/8") thick, covered with two coats of gypsum mortar (scratch and brown) so that the aggregate thickness shall be at least one inch (1"), or in lieu thereof, recover same with plaster boards one-half inch (1/2") thick, covered with No. 26 U.S. gauge stamped metal. In lieu of the above method, completely remove all combustible material from plaster face of partitions on hall side and repair existing plaster. After inspection, plaster boards or perforated rock lath may be applied directly over the existing plaster face of partitions on hall side. Cover plaster boards or perforated rock lath with two coats of gypsum mortar as above, or plaster boards may be covered with No. 26 U.S. gauge stamped metal.

(3) Mineral wool. Fill solidly between partition uprights, from underside of flooring to ceiling with mineral wool blown in place by the pneumatic method, packed solidly to fill all spaces and voids.

(4) Brick, gypsum, etc. Fill solidly between partition uprights from underside of flooring to ceiling with brick, gypsum, or other acceptable material packed solidly to fill all spaces and voids. Where brick, gypsum, or other masonry material is intended to be used, application must be filed before installation with the Department of Buildings for approval of strength of existing members intended to support the proposed masonry fire-retarding.

(5) Other methods. No other method may be used unless same is acceptable to the Department of Buildings.

(6) Removal of windows in public hall partitions. When windows in walls or partitions are removed, both sides of the openings shall be sealed with fire-retarding materials, except that wood lath and plaster may be used on the room side of the opening when the existing surface of the room is constructed of wood lath and plaster.

(7) Electric meters. Where direct current (DC) electric meters of public utility companies are present or installed on partitions of public halls the fire-retarding shall continue unbroken behind the meters or the meters shall be mounted on a heavy slate back or non-magnetic fireproof equivalent, such as transite, asbestos board, etc., against which fire-retarding finished up tightly.

(8) Partitions in class B converted dwellings. Where fire-retarding is required in any class B converted dwelling referred to in paragraph (7) of subdivision (a) of this section, both sides of all enclosure partitions of entrance halls, stair halls and public halls throughout such building shall be fire-retarded in accordance with the provisions of paragraph (3) or (4) of subdivision (b) of this section.

(9) Partitions in altered old law tenements. In any old law tenement where the occupancy is increased on any story, the enclosing partitions of any entrance hall, stair hall or public hall on the story where the occupancy has been increased, shall be fire-retarded on both sides. Such requirements shall apply only to the walls of the entrance hall, stair hall or public hall adjoining the altered apartment. The enclosing partitions of such halls other than those adjoining the altered apartment, and the partitions on any story where the occupancy has not been increased, shall be fire-retarded on the hall side. The method of fire-retarding shall be as set forth in paragraph (1) or (2) of subdivision (b) of this section, or said partitions shall be fire-retarded in accordance with the provisions of paragraph (3) or (4) of subdivision (b) of this section.

(10) Newly constructed partitions. In any entrance hall, stair hall or public hall where any partition or part thereof is newly constructed, and where the plaster has been removed from any partition or part thereof, such partition shall be fire-retarded on both sides.

(c) Ceilings. Any approved method for fire-retarding partitions shall be acceptable for fire-retarding ceilings, provided that all existing materials are completely removed to face of joists. Mineral wool, brick gypsum or other masonry fill will not be accepted.

(1) Where any entrance hall, public hall or stair hall, or any other portion thereof, in any part of any old law tenement or converted dwelling is required to be fire-retarded that portion of any ceiling directly underneath any such entrance hall, public hall or stair hall shall be fire-retarded. Where such ceiling is located in any store, apartment or other space it shall also be fire-retarded as required for partitions by paragraph (1) or (2) of subdivision (b) of this section. Where the above method is impractical due to the existing ceiling construction in any such store, apartment or other space, the Department of Buildings may permit the fire-retarding of such ceilings to be applied from above by removing the floor of any such entrance hall, public hall or stair hall and installing between the floor beams, and directly against the ceiling below, a layer of heavy building paper over which there shall be placed a basket made of reinforced ribbed expanded metal lath weighing at least 3.4 pounds per square yard. Such basket shall be lined with Portland cement or gypsum mortar not less than one inch (1") in thickness. The building paper, metal lath and cement or gypsum mortar shall be carried at least halfway up on the sides of the beams. However, this method will not be accepted for the fire-retarding of any such ceiling located in a space used for a hazardous purpose or business, nor will it be accepted for the fire-retarding of any such ceiling located in the cellar or for the fire-retarding of any ceiling located in any store, apartment or other space when such ceiling is constructed of wood or of wood and metal applied directly to the beams. In such cases the ceilings shall be fire-retarded according to the requirements of paragraph (1) or (2) of subdivision (b) of this section.

(d) Existing wood stairs. Except where stairs of incombustible material are required in class B converted dwellings as set forth in paragraph (7) of subdivision (a) of this section, all wood railings, balustrades and newel posts shall be completely removed from every existing wood stairs and such stairs shall be provided with railings, balustrades and newel posts of metal or other hard incombustible material, of such size are secured in such manner to the existing stairs as may be approved by the Department of Buildings, except handrails may be hardwood. Soffits and stringers of existing wood stairs shall be fire-retarded in accordance with the methods set forth in subdivisions (e) and (f) of this section.

(e) Stair soffits. The soffits of every stair in every entrance hall, public hall, and stair hall, including any soffit extending beyond the enclosure partitions of any such hall, shall be fire-retarded. Any approved method for fire-retarding partitions shall be acceptable for fire-retarding stair soffits provided that all existing materials are completely removed to face of structural members of stair soffits.

(f) Fascia – stair and well. Fascia of outside stringer on rake of stairs, and well fascia at floor level, shall be fire-retarded their full depth to form complete seals with the soffits of stairs and ceilings of halls, respectively. Type of fire-retarding shall be one of those herein approved for ceilings of halls, or in lieu thereof, cover fascia with sheet asbestos not less than three-sixteenths inch (3/16") thick with joints well pointed over which there shall be an additional single layer of No. 26 U.S. gauge stamped metal or cover fascia with a single layer of No. 14 U.S. gauge steel.

(g) Fire-stopping. All partitions required to be fire-retarded shall be fire-stopped with incombustible material at floors, ceilings and roofs. Fire-stopping over partitions shall extend from the ceilings to the underside of the flooring or roofing above. Fire-stopping under partitions shall extend from the underside of flooring to ceiling below. All spaces between floor joints (directly over and under partitions) shall be completely filled the full depth of the joists. Any space from top of partition to underside of roof boarding shall be completely fire-stopped. Fire-stopping shall be done with brick, cinder concrete, gypsum, metal lath and Portland cement or gypsum mortar, mineral wool, or other materials acceptable to the Department of Buildings.

(h) Door openings. Except as provided in paragraphs (1) and (2) of this subdivision, all door openings into any public hall, entrance hall or stair hall which required to be fire-retarded shall be equipped with self-closing protective assemblies having a fire resistive rating of at least one hour.

(1) In old law tenements where the number of apartments is not being increased, existing wood doors opening into public halls, entrance halls or stair halls may remain provided such doors are made to be self-closing ("butterfly" spring hinges are not acceptable) and, provided further, all glazed transoms and panels in every such door are glazed with wire glass. All such transoms shall be made stationary.

(2) Where, in any old law tenement, the number of apartments is being increased on one or more stories, door openings into public halls, entrance halls or stair halls on each story or stories shall be equipped with self-closing protective assemblies having a fire-resistive rating of at least one hour. In such old law tenements existing wood doors opening into public halls, entrance halls or stair halls may remain on any story where there is no increase in the number of apartments, provided such doors and every transom and panel in same are made to conform to the requirements set forth in paragraph (1) of subdivision (h) of this section.

(3) All doors shall be properly fitted to their assemblies and there shall be no unnecessary spaces between doors and door bucks or saddles.

(i) Materials. All materials used in the process of fire-retarding shall be of a type and manufacture acceptable to the Department of Buildings. The following shall be considered as minimum requirements:

(1) Metal lath. Metal lath shall weigh at least 30 pounds per square yard, except lath used over existing plaster which lath shall weigh at least 3.4 pounds per square yard and be reinforced with rigid ribs not less than three eights inch (3/8") deep, spaced not more than eight (8") on center running full length of sheets. Where ribs exceed 4.8 inches on center, same shall have at least one intermediate one eight inch (1/8") inverted rib running the full length of sheets. Metal lath fastened to stubs shall be attached at least at six inch (6") intervals with 4-penny nails or one inch (1") roofing nails or No. 14 steel wire gauge wire staples, and to wood joists by at least 6-penny nails, one and one-quarter inch (1 1/4") roofing nails, or one inch (1") No. 14 steel wire gauge wire staples. When metal lath is applied over existing plastered surfaces, same shall be fastened with nails or staples of the same gauge and such nails or staples have anchorage of at least one-half inch (1/2")in studs and three-quarters inch (3/4") in joists. Laps between the studs or joists shall be securely tied or laced. Stiffened metal lath on wood studs, or joists, shall be nailed or stapled at least at eight inch (8") intervals, and the laps between studs similarly tied or laced. Metal lath shall be galvanized or painted.

(2) Plaster boards or perforated rock lath. Plaster boards or perforated rock lath shall be of type and manufacture acceptable to the Department of Buildings. Each board shall bear the name of manufacturer and brand stamped thereon for inspection after erection. Plaster boards or perforated rock lath nailed directly to wood studding or joists shall be fastened with one and one-eighth inches (1 1/8") wire nails of at least No. 13 steel wire gauge, with flat three-eighth inch (3/8") heads. When such boards are applied over existing plastered surfaces, same shall be fastened with nails of the same gauge and such nails shall have anchorage of at least one-half inch (1/2") in studs and three-quarters inch (3/4") in joists. The maximum space between nails shall be four inches (4"). The joints shall be broken at every other board. The wetting of such boards before plastering is forbidden.

(3) Stamped metal. Stamped metal shall be No. 26 U.S. gauge (equivalent thickness .018 inches or 3/160 inches) with one inch (1") lapped seams. Size of sheets shall be not more than twenty-four inches by ninety-six inches (24" x 96"), having a selvage consisting of a half-round bead sufficient to create a one inch (1") overlap at both seams. Nailing shall be secured direct to studs or joists with 6-penny smooth box nails (two inches (2") or No. 12 1/2" gauge) with nails on end seams spaced not more than three inches (3")apart. Nailing to plaster is forbidden and in all cases nails shall have anchorage of at least one-half inch (1/2") in studs and three-quarters inch (3/4") in joists. All beads at seam shall be chisel sealed, making a tight joint. All sheets shall be marked "26 U.S. Gauge" for identification and inspection after erection.

(4) Mineral wool. Mineral wool shall be of a type and manufacture acceptable to the Department of Buildings. Holes shall be cut approximately three inches (3") in diameter through the wood lath and plaster near the ceiling, in the panels between each two adjacent studs. As an alternative, holes may be cut approximately three inches by six inches (3" x 6") on every second stud. Check each stud panel with a weight and line to find out whether there is any obstruction. If any cross-bridging or other obstruction is encountered additional holes shall be cut until access has been gained to all open spaces within the stud panel in all specified partitions. Mineral wool shall then be blown into all spaces by the pneumatic method with air pressure sufficient to pack the insulation to a density acceptable to the Department of Buildings. Mineral wool for this work shall be in bags or containers marked with the manufacturer's name and label specifying its type.

(5) Other materials. No other material may be used unless same is acceptable to the Department of Buildings.

(j) Exceptions. Where any portion of any entrance hall, stair hall or public hall has been previously fire-retarded under the supervision of this department, the former Tenement House Department or various former Departments of Buildings, such fire-retarding will be accepted only to the extent that same has been previously approved, provided, however, that such entrance hall, stair hall or public hall is otherwise made to conform to all the requirements set forth in these rules.

§ 25-172. Fire-Retarding of Cellar Ceilings in Old Law Tenements and Converted Dwellings

Open this section

(a) Intent. The fire-retarding rules herewith set forth are approved by the Department of Buildings for the existing multiple dwellings where the ceilings of the cellar or other lowest story is required, by § 185 and § 240, subdivision 3, Multiple Dwelling Law, and by § 27-2044, Housing Maintenance Code, to be fire-retarded in a manner approved by the Department of Buildings.

(1) It is the intent of the law to provide a continuous fire-retarded covering over the entire ceiling of the cellar, or other lowest story, so as to prevent fire communicating with upper stories of a multiple dwelling. Where there is a space less than four feet six inches (4'-6") in height from the ground or floor level to the underside of the first tier of beams, such space shall be considered as an "air space" and not as a cellar. However, when such space opens to a cellar where fire-retarding of the ceiling is required, then such space shall be separated from the cellar with a partition constructed of incombustible material in which there is provided a self-closing door and assembly having a fire-resistive rating of at least one hour. Where the ceiling of the cellar or other lowest story is required to be fire-retarded, all openings in such ceilings for stairways not located directly under a main stair, also openings in ceiling such as pipe shafts, vent shafts, unenclosed dumbwaiter shafts, disused flues, etc., shall be properly closed. (Private stairs within duplex apartments extending into cellar or basement are not required to be enclosed.) New partitions erected to enclose existing stair referred to in the preceding paragraph shall be of incombustible materials. Existing partitions enclosing any such stair will be acceptable where same are of incombustible materials or where same are fire-retarded on both sides in accordance with the methods set forth in or 28 RCNY § 25-171(b)(1) or (2) and with materials conforming with the requirement of 28 RCNY § 25-171(i). Door openings in such enclosure partitions shall be equipped with self-closing protective assemblies having fire-resistive ratings of at least one hour. When existing shafts, including dumbwaiter shafts, extend below the ceiling a distance less than one-half (1/2) the height of the cellar, such shafts shall be considered as being part of the cellar ceiling and the enclosures of said shafts shall be fire-retarded in the same manner as required for cellar ceilings. All existing shafts, including dumbwaiter shafts, which extend below the ceiling a distance more than one-half (1/2) the height of the cellar shall be enclosed with incombustible materials. All shafts referred to in this paragraph shall have adequate cleanout at base consisting of fire-proof self-closing door and assembly having a fire-resistive rating of at least one hour. Where new partitions or enclosures are erected in a cellar they shall be constructed of incombustible materials.

(2) Wood girders, columns, posts, etc. The fire-retarding material of ceiling of cellar or other lowest story shall be carried down and around all non-fireproof ceiling projections, such as wood girders, etc., which are less than six inches (6" x 6") in diameter. The fire-retarding material also shall be turned down at least three inches (3") on all non-fire-retarding columns, posts, etc., which are less than six inches (6") in diameter.

(3) Non-fire-retarded cellar partitions. When non-fire-retarded partitions in cellar, or other lowest story, extend to the ceiling, the fire-retarding material of the ceiling shall be turned down at least three inches (3") on said partitions, or the partitions shall be cut off at top to permit the fire-retarding of the ceiling to be continuous. Where, in any old law tenement three (3) stories and basement in height, there is also a cellar under the basement story, the ceiling of such cellar shall be fire-retarded; and also, in any such old law tenement, where the main entrance from the grade is to the first story that portion of the basement ceiling which is directly under the first story entrance hall, public hall and stair hall shall be fire-retarded. In every old law tenement three (3) stories and basement in height with no cellar under the basement, where the main entrance from the grade is to the basement story, the ceiling of the basement story shall be fire-retarded throughout. In any such old law tenement where the main entrance from the grade is to the first story no such fire-retarding will be required.

(4) Heating appliances. The portion of the ceiling over any furnace, boiler or hot water heater shall be fire-retarded in accordance with the methods set forth in 28 RCNY § 25-171(b)(1) or (2) and such fire-retarding shall extend for a distance of at least four feet (4'-0") beyond the sides and rear, and eight feet (8'-0") in front of such furnace or boiler.

(5) It is not intended that these rules and regulations in themselves require plans to be filed. However, should any work involve structural changes, then plans are required to be filed in the Department of Buildings and such changes shall be subject to all other rules and regulations applicable thereto.

(6) Work shall not commence until satisfactory evidence has been submitted to the Department of Buildings that compensation insurance has been obtained in accordance with the provisions of the Workmen's Compensation Law.

(b) Methods. Cellar ceilings shall be fire-retarded according to any of the following methods: Metal lath and cement or gypsum mortar conforming to 28 RCNY § 25-171(b)(1). Plaster boards and gypsum mortar or stamped metal conforming to 28 RCNY § 25-171(b)(2).

No. 26 U.S. gauge stamped metal over existing plastered ceiling, when erected without damage to the plaster. Furring strips are not required, but if used, they shall be metal covered on both sides and on face surface. Stamped metal shall not be applied until after existing plastered ceiling has been inspected and approved by an inspector of the Department of Buildings.

(c) Materials. No other method may be used unless same are acceptable to the Department of Buildings. Materials used shall be in accordance with the provisions of 28 RCNY § 25-171(i)(1), (2) or (3). Mineral wool, brick, gypsum or other masonry fill will not be accepted for fire-retarding cellar ceilings. No other materials may be used unless same are acceptable to the Department of Buildings.

§ 25-173. Fire-Retarding of Cooking Spaces in all Multiple Dwellings

Open this section

(a) Intent. The rules herewith set forth are approved by the Department of Buildings for the protection of cooking spaces under §§ 33 and 176 of the Multiple Dwelling Law. As set forth in § 33 of the Multiple Dwelling Law, nothing in these rules shall be construed as permitting fire-retarding partitions in fireproof multiple dwellings.

(b) Section 33, Multiple Dwelling Law. Except when sprinkler heads are installed in conformity with subdivision (e) of this section, § 33 of the Multiple Dwelling Law requires fire-retarding of cooking spaces in existing and newly constructed class A and class B multiple dwellings.

(c) Ceilings and walls exclusive of doors. Walls and ceilings shall be fire-retarded according to any of the following methods: Metal lath and cement or gypsum mortar conforming to 28 RCNY § 25-171(b)(1). Plaster boards and gypsum mortar or stamped metal conforming to 28 RCNY § 25-171(b)(2).

No. 26 U.S. gauge stamped metal over existing plaster when erected without damage to the plaster. Furring strips are not required, but if used, they shall be metal covered on both sides and on face surface. Stamped metal shall not be applied until after existing plaster has been inspected and approved by an inspector of the Department of Buildings. Materials used shall be in accordance with the provisions of 28 RCNY § 25-171(i)(1), (2) or (3). No other methods or materials may be used unless same are acceptable to the Department of Buildings.

(d) Combustible material. In every cooking space, all combustible material immediately underneath or within one foot of any apparatus used for cooking or warming of food shall be fire-retarded in conformity with the applicable provisions of these rules or covered with asbestos at least three-sixteenths inch (3/16") in thickness and twenty-six gauge metal or with fire-resistive material of equivalent rating. There shall always be at least two feet (2'-0") of clear space above such apparatus.

(e) Sprinkler heads installed in ceilings of cooking spaces in lieu of fire-retarding the ceilings and walls. Where sprinkler heads are installed in the ceilings of cooking spaces in lieu of fire-retarding the ceilings and walls, all of the provisions of subdivisions (a) to (f) of this section inclusive, shall be complied with, except that it will not be required that the fire-retarding of the walls and ceilings of cooking spaces be complied with. Before the installation of sprinkler heads is begun a "Plumbing Repair Slip" shall be filed with and approved by the Department of Buildings. Sprinkler heads shall be of a type and manufacture approved by the Department of Buildings or previously approved by the Board of Standards and Appeals or by the Underwriters Laboratories Limited, and shall have fusible struts constructed to fuse at a temperature not higher than two hundred twelve degrees (212°) Fahrenheit. Every sprinkler head shall bear the year of manufacture clearly on its surface. No sprinkler head may be installed after December 31st of the year following the year of manufacture. There shall be provided at least one (1) sprinkler head for every fifty-nine (59) square feet or fraction thereof of the floor area of the cooking space. Sprinkler heads shall be connected with the water supply of the building through a pipe of at least one-half (1/2) inch inside diameter. Where practicable, sprinkler heads shall be located in an upright position on top of the sprinkler piping. There shall be kept available on the premises at all times a sufficient supply of extra sprinkler heads and also a sprinkler wrench for use to replace promptly any fused or damaged sprinkler heads. Any head which has opened or has been damaged shall be replaced immediately with a good sprinkler head. Painting or kalsomining of sprinkler heads is prohibited.

(f) Cooking spaces constructed after July 1, 1949. Application and plans must be filed with and approved by the Department before any work is started in connection with the construction of any cooking space after July 1, 1949.