3 RCNY Chapter 83 Pre-Existing Facilities, part 1 of 4

§ 8301-01 to § 8329-01: 29 sections.

§ 8301-01. Former Board of Standards and Appeals Rules

Open this section

(a) Scope. This section consolidates former Board of Standards and Appeals rules in effect on June 30, 2008, that are applicable to the design and installation of devices, equipment and systems in pre-existing facilities.

(b) Definitions. [Reserved.]

(c) General Provisions. The design, installation, operation and maintenance of devices, equipment and systems allowed or approved by the New York City Board of Standards and Appeals pursuant to provisions of former Board of Standards and Appeals rules 2 RCNY §§ 5-02, 8-01, 15-01 and 18-01, as set forth below, but not allowed by the Fire Code, and/or by the Building Code in effect on December 6, 1968 or thereafter, may be continued in preexisting facilities in compliance with such former rules and other applicable laws, rules and regulations in effect at such time of such allowance or approval and any subsequent alteration thereof, until such time as such facilities may be required to comply with the Construction Codes, Zoning Resolution, Fire Code, the rules, or other applicable law, rule or regulation, with respect to the design, installation, operation or maintenance of such devices, equipment and systems.

(d) Dry Cleaning Establishments (Former Board of Standards and Appeals Rule 2 RCNY § 5-02).

§ 5-02 Non-Coin-Operated Dry Cleaning Establishments.

(a) Definitions.

Combustible solvent. The term "combustible solvent" shall mean a liquid solvent that will either burn or will support combustion.

Dealing directly with the ultimate consumer. For the purpose of these rules and to carry into effect the provisions of § 32-15 A of the Zoning Resolution of the City of New York, the term "dealing directly with the ultimate consumer" shall refer only to those retail non-coin-operated dry cleaning establishments which perform services or articles conveyed directly by a retail customer to such establishment or collected directly from and delivered to the retail customer by an employee of such establishment or by any vehicle in the ownership, operation or control of such establishment.

Dry cleaning. For the purpose of these rules "dry cleaning" shall be deemed to be the insertion, into a dry cleaning machine or unit, of textiles, fabrics, garments or other articles for the purpose of cleaning them by the use of solvents (other than water) with a flash point of not less than 138.2 degrees Fahrenheit when tested in a Tagliabue open cut tester, and the removal of same from such machine by an employee or owner-operator of a dry cleaning establishment, with a rail, counter, or other divider separating the dry cleaning units from the customer space.

Dry cleaning establishment. For the purpose of these rules a "dry cleaning establishment" shall be deemed to be a non-coin-operated retail establishment used for dry cleaning, (as defined in § 5-02(a) "dry cleaning" of these rules) dealing directly with ultimate consumers, limited to 2,000 square feet of floor area per establishment and wherein the total aggregate dry load capacity of the dry cleaning machines shall not exceed 60 lbs. This definition and § 5-02(c)(1)(i) shall not apply to any premises where Use Group 16 is permitted.

Dry cleaning establishment using a combustible solvent and dry cleaning establishments using a non-combustible solvent. The terms "dry cleaning establishment using a combustible solvent" and "dry cleaning establishments using a non-combustible solvent" as used in these rules shall refer to the solvent used as the detergent in the dry cleaning units.

Dry cleaning unit. A "dry cleaning unit" is the machinery or equipment in which textiles, fabrics, garments or other articles are carried through a complete cleaning cycle. A "dry cleaning unit" may consist of one or more detached component machines.

Existing. The term "existing" shall mean those dry cleaning establishments established prior to December 15, 1961.

Flammable liquid solvents. The term "flammable liquid solvents" shall mean such as will omit a flammable vapor at a temperature below 100 degrees Fahrenheit when tested in a Tagliabue open cup tester.

Hereafter established. The term "hereafter established" shall mean those dry cleaning establishments established after December 14, 1961.

Non-combustible solvent. The term "non-combustible solvent" shall mean a liquid solvent that will not burn and will not support combustion.

Spotting or sponging. The term "spotting or sponging" shall mean the local application of a "flammable liquid solvent" to remove spots of dirt, grease, paint or stains from wearing apparel, textiles, fabrics or articles of any other sort. All other terms used shall be as defined in the Zoning Resolution, Administrative Code, Multiple Dwelling Law, or Labor Law, when not inconsistent with the specific terms defined herein.

(b) Approval.

(1) (i) It shall be unlawful to use any premises for any hereafter established non-coin-operated retail dry cleaning establishment unless application and plans have been filed with, and approved by, the Department of Buildings or the [Department of Ports and Trade] Department of Small Business Services in accordance with law.

(ii) The Department of Buildings shall have exclusive jurisdiction over inspections and enforcement of all provisions of these rules, except where such jurisdiction is specifically given to any other Agency in these rules or by the New York City Charter.

(2) The provisions of these rules shall not apply to any dry cleaning establishment for which plans were approved prior to the effective date of these rules, provided that such establishment complied with the rules in force at the time of approval.

(3) No dry cleaning unit shall be installed unless such unit is approved by the Board of Standards and Appeals.

(4) The dry load capacity of all dry cleaning units shall be rated by the Board of Standards and Appeals on the basis of 2.8 pounds per cubic foot of the volume of the washing compartment.

(5) No dry cleaning solvent shall be used unless such solvent has been tested and rated by the Fire Commissioner.

(6) It shall be unlawful in any dry cleaning unit approved by the Board to use any solvent other than that for which the dry cleaning unit has been approved by the Board.

(7) No non-conforming existing dry cleaning establishment shall be enlarged or extended unless such extension or enlargement be made in a conforming manner.

(c) Restrictions on locations and areas.

(1) (i) No dry cleaning establishment shall have a gross floor area exceeding 2,000 square feet to be used for dry cleaning and incidental operations, including space used for pressing, finishing, storage and for the service of customers. The square foot area limitation shall apply to the aggregate of all space so used on all floors and mezzanines of the premises involved above the cellar or basement thereof. Additional space may be used on a lower floor which is either a basement or cellar provided that on such floor there shall be no dry cleaning and no storage of recently cleaned articles. Such additional space may include ordinary storage, boilers, compressors, pumps and filtration equipment.

(ii) In calculating the gross floor area of a non-coin-operated dry cleaning establishment pursuant to § 5-02(c)(1)(i) such gross floor area in a multiple use type of service establishment, shall not include the area used for lawful non-dry-cleaning operations.

(2) No non-coin-operated retail dry cleaning establishment using a combustible solvent shall be permitted within any building which is:

(i) of wood frame (class 4) construction; or

(ii) which is classified as a public building pursuant to § 26-235 of the Administrative Code except when located in a portion of such building completely separated from the public use portion by unpierced fire-proof construction having a 3 hour fire rating provided § 5-02(c)(2)(iii) is complied with; or

(iii) where any part of such establishment is within 20 feet of the public use portion of a public building.

(d) Egress. Egress from all establishments subject to these rules shall comply with the Administrative Code and all other laws, rules and regulations applicable thereto and in addition thereto, all such establishments shall be provided with an unobstructed aisle not less than 3 feet wide leading from the main work area to all required means of egress. All required exit doors shall swing in the direction of egress.

(e) Fire prevention. All hereafter established dry cleaning establishments, subject to these rules, shall comply with the following:

(1) No boiler shall be permitted in the same area or space where dry cleaning units are located, nor in the cellar directly under or within 5 ft. (measured horizontally) from any dry cleaning unit, unless either

(i) the boiler or boilers shall be enclosed in a one hour fire resistive unpierced enclosure and entered only from the outer air; or

(ii) the boiler or boilers shall be enclosed in a one hour fire resistive enclosure with a one-hour fireproof self-closing door opening into a ventilated vestibule similarly enclosed and entered by a one-hour fireproof self-closing door opening into the interior of the premises or establishment.

(2) The ceiling of all such boiler rooms as required in § 5-02(e)(1) and the adjoining entrance vestibule referred to in § 5-02(e)(1)(ii) above, shall be fire-retarded with one-hour fire resistive material.

(3) Non-fireproof partitions and ceilings within six feet of any dry cleaning unit using a combustible solvent shall be fire-retarded with one-hour fire resistive materials and doors and with two approved automatic wet pipe sprinkler heads located over each cleaning unit; these sprinkler heads may have their source of supply from the house water system.

(4) All openings from any such dry cleaning establishment, using a combustible solvent, leading to a fire escape shall be equipped with a one-hour fireproof self-closing door or fireproof window assembly.

(5) Except as provided in § 5-02(e)(1), there shall not be employed in any such dry cleaning establishment using a combustible solvent any device or apparatus employing flame or fire or which is likely to produce an exposed spark except electric apparatus placed at least five feet above the floor, or approved type of "explosion proof electric motors." In such establishments all lighting shall be fitted with keyless sockets and all switches and receptacles shall be placed at least four feet above the floor. Nothing contained in this paragraph (5) or § 5-02(e)(1) shall prohibit the installation of any gas, or oil-fired heating device of a type approved by the Board for use in garages or in combustible or explosive atmospheres.

(6) In an establishment using a non-combustible solvent, no direct-fired clothes dryer shall be located within 25' of a dry cleaning unit unless an incombustible vapor tight partition (which may contain glass), equipped with self-closing doors, is provided between the dry cleaning unit and the flame producing device. This partition may provide either complete or partial separation, provided that any partial separation is so arranged that the line of air travel around the partition from the dry cleaners to the dryers is a minimum of 25'.

(i) The 25 feet separation between dry cleaning units and direct fired clothes dryers as required by § 5-02(e)(6) may be reduced to 15 feet where a solid incombustible vapor-tight partition is constructed extending from the top of direct-fired clothes dryers to the ceiling and all portions of the dryer enclosures are solid, except for self-closing access doors, so that vapors from the dry cleaning units cannot reach the dryer flame, provided adequate fresh air for combustion and drying is supplied to the dryers from the outer air.

(ii) Nothing contained in these rules shall prohibit the installation of suspended gas or oil-fired heaters approved by the Board, provided that such heaters are located at least 7' above the floor, and at least 5' (measured horizontally) from any dry cleaning unit using a non-combustible solvent.

(7) It shall be unlawful to store any flammable liquids or solvents in quantities aggregating more than five gallons without a permit as provided in Subchapter 9 of Chapter 4 of Title 27 of the Administrative Code.

(8) All flammable liquids and solvents used for spotting and sponging shall be contained in approved individual metal containers not exceeding two-quart capacity each.

(9) All sludge or residue removed from a dry cleaning unit shall be placed in a metal container not exceeding 55 gallons of capacity with a tight fitting cover and shall be removed from the premises and disposed of in a lawful manner.

(10) All solvent used in the dry cleaning unit shall be either

(i) received and stored in metal containers not exceeding 55 gallons each and pumped directly into a dry cleaning unit or units by means of a detachable leakproof pump and pipe system, or

(ii) received and stored in a tank or tanks constructed in accordance with the Oil Burner rules (§ 16-01) of the Board of Standards and Appeals, and pumped directly into a dry cleaning unit or units by means of a closed leakproof pipe and pump system.

(11) All non-coin-operated retail dry cleaning establishments shall be provided with at least two portable dry chemical fire extinguishers of not less than five pounds capacity each. The Fire Department shall have jurisdiction over the location of these fire extinguishers and shall make periodic inspection to insure that the fire extinguishers are in proper working order, and that proper housekeeping conditions are maintained on the premises and that the dry cleaning solvent used shall be of the type for which the dry cleaning unit was approved by the Board.

(f) Ventilation.

(1) All hereafter established dry cleaning establishments subject to these rules shall be equipped with adequate ventilation to provide at least four complete changes of air volume an hour of such establishments during the operation of any dry cleaning units, and such ventilation as is otherwise required by law. The ventilating system shall be so arranged that air surrounding the dry cleaning equipment shall not be drawn through or past any unprotected flame producing device. Sufficient make-up air shall be introduced into all parts of the establishment to equal the air exhaust by dry cleaning units, dryers, and exhaust ventilating system.

(2) The direct equipment exhausts or vents of all dry cleaning establishments subject to these rules shall terminate to the outer air in the following manner:

(i) At least 7 feet above the roof, street, yard, or court grade on which it opens in which said establishment is located, and

(ii) The exhaust shall be under negative pressure within the envelope of the building by means of a power operated fan, and

(iii) The terminal of the exhaust shall be at least five feet from any window or ventilating opening if the window or ventilating opening lies on the same plane as the exhaust terminal and when the windows, or ventilating openings lie on a plane which faces in the direction of the exhaust terminal such terminal shall be at least 10 feet from such opening, and

(iv) All direct equipment exhausts or vents shall be provided with approved mesh lint arrestors which shall be kept clean unless approved lint traps are provided on the units.

(g) Operating precautions

(1) A printed notice embodying these rules shall be posted in a conspicuous place in all dry cleaning establishments.

(2) All equipment shall be installed in such manner as to minimize noise, vibration, smoke, and odors, and other forms of nuisances to the occupants of the premises in which such cleaning establishment may be located or to the occupants of any adjacent premises.

(h) Penalties. Any violation of these rules shall be subject to the penalties prescribed in the Zoning Resolution therefor, in addition to other penalties prescribed by law.

* * *

(e) Daily and Monthly Testing of Interior Fire Alarm Systems (Former Board of Standards and Appeals Rule 2 RCNY § 8-01). The following testing requirements of former BSA rule 2 RCNY § 8-01, as amended by this section, shall apply to interior fire alarm systems in preexisting facilities, as set forth in 3 RCNY § 8301-01(c). All fire alarm systems designed and installed pursuant to former BSA rule 2 RCNY § 8-01 shall be operated and maintained in compliance with applicable Fire Code requirements, except as otherwise provided in this section.

§ 8-01 Installation of Interior Fire Alarm Signal Systems.

* * *

(o) Daily and monthly test

(1) Every fire alarm system shall be tested [each morning immediately after the hours of starting work] on a daily basis, except for fire alarm systems with a control panel capable of receiving and displaying supervisory or trouble signals indicating that particular components of the fire alarm system are not functioning, require servicing or are otherwise not in good working order. Fire alarm systems designed, installed, operated and maintained with such a control panel shall be tested in compliance with the requirements of FC 907.20.2.

(2) No [such] fire alarm system shall be used for any other purpose, except that the daily dismissal signals may be given if authorized by the Fire Commissioner. The use of the system for fire drill purposes may be considered a test of those parts of the system actually used.

[(2)] (3) Each sending station shall be tested at least once a month.

[(3)] (4) All apparatus requiring rewinding shall be rewound after each operation and kept in normal condition.

[(4)] (5) A complete record of monthly tests, fire drills and other operations of fire alarm systems shall be kept subject to inspection by the Fire Commissioner.

(f) Cryogenic Gases (Former Board of Standards and Appeals Rule 2 RCNY § 15-01).

§ 15-01 Clearance Between Storage Vessels and Adjacent Structures.

Every installation of liquid oxygen, nitrogen or argon storage vessels shall be made only outdoors as permitted by law. The minimum clearance between storage vessel and adjacent structures may be 1 foot if the walls are a minimum of 2 hours fire resistive construction and with no openings within 10 feet of the storage vessel unless such openings lead to rooms used exclusively for the storage of oxygen, nitrogen or argon and/or the charging of cylinders or suitable containers with oxygen, nitrogen or argon in which case the distance from storage vessel to wall opening may be reduced to 10 feet. No smoking, open flames or storage of combustible material shall be permitted in the area. All piping from the storage vessel and within the building shall be as required by the Fire Department. Each installation shall be serviced and periodically inspected by specially trained personnel holding Certificates of Fitness issued by the Fire Department. All electrical work shall be in accordance with the Electrical Code of the City of New York. Each installation shall bear a label as required in the original resolution.

(g) Spray Operations (Former Board of Standards and Appeals Rule 2 RCNY § 18-01).

§ 18-01 Use of Equipment for Spraying and Drying of Paints, Varnishes, Lacquers and Other Flammable Surface Coatings and Storage of Such Materials.

(a) [ Application ] Restrictions.

* * *

(3) Restrictions. No spraying, dipping or immersing of any article or thing within the City of New York with any flammable paints, varnishes, lacquers or any other flammable substances, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes shall be permitted in any premises or portion thereof as follows:

(i) Which is occupied as a class A or B multiple dwelling or a dwelling for one or two-families, except where a location is provided which is separated by fireproof construction from the residential occupancy and ventilated as provided in § 18-01(c).

(ii) Which is occupied as a place of public assembly except trade schools where the buildings are of Class I or Class II construction and spraying, dipping or immersing are demonstrated for instruction purposes only.

(iii) Which is artificially lighted by any means other than electricity.

(iv) Which is heated by other than the use of steam or hot water circulating systems and the boiler is located outside the space where spraying, dipping or immersing is carried on.

(b) Definitions.

Cabinet booth. The term "Cabinet Booth" when used in these rules shall mean a compartment with a back, top and two sides of incombustible materials over a substantial metal frame and equipped with air exhaust facilities, located within a room or any portion of any premises where spraying with any flammable paints, varnishes, lacquers or any other flammable substances, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes is carried on.

Canopy booth or hood. The term "Canopy Booth or Hood" when used in these rules shall mean an installation consisting of a metal canopy or hood, without any side or end panels enclosing the object sprayed and an air exhaust system under which spraying with any flammable paints, varnishes, lacquers or any other flammable substances, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes is carried on.

* * *

Dipping room. The term "Dipping Room" when used in these rules shall mean a fully-enclosed ventilated room approved for such use in which any article or thing is dipped, or immersed in any flammable paints, varnishes, lacquers or any other flammable substances, mixtures, or compounds commonly used for painting, varnishing, staining or similar purposes is carried on.

Fireproof or fire-resisting partitions. The term "Fireproof or Fire-Resisting Partitions" used in these rules shall mean the standards set in the Labor Law and the rules of the Board of Standards and Appeals for factory buildings (§ 7-01). All openings in this type of partition shall only be equipped with self-closing fireproof assemblies.

* * *

Spray or spraying space, dipping space or immersing space. The term "spray or spraying space" "dipping space or immersing space" when used in these rules shall mean that portion of the premises used for the actual work of spraying, dipping or immersing any article or thing with any flammable paints, varnishes, lacquers or any other flammable substances, mixtures or compounds, commonly used for painting, varnishing, staining or similar purposes in any booth or room.

Spray room. The term "spray room" when used in these rules shall mean a fully enclosed ventilated room approved for such use in which any article or thing is sprayed by any flammable paints, varnishes, lacquers or any other flammable substance, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes is carried on.

Storage room. The term "storage room" when used in these rules shall mean a fully-enclosed ventilated room used for the storage and mixing of any flammable paints, varnishes, lacquers or any flammable substances, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes.

Tunnel booth. The term "tunnel booth" when used in these rules shall mean a compartment consisting of two sides and top, equipped with an air exhaust system in which spraying with any flammable paints, varnishes, lacquers or any other flammable substances, mixtures or compounds commonly used for painting, varnishing, staining or similar purposes is carried on.

(c) Ventilation.

(1) Spraying or dipping spaces shall be ventilated when in operation so that the movement of air shall be at least one hundred (100') linear feet per minute in the breathing zone of the operator and be of sufficient capacity to prevent the accumulation of mist or vapors. For requirements of ventilation of storage rooms see § 18-0l(d)(4)(i).

(2) Air shall be admitted to the spraying, dipping or immersing spaces in an amount equal to the capacity of the fan or fans and in such a manner as to avoid short-circuiting the path of air in the working zone of such spaces. Exhaust fans shall be kept running constantly while spraying, mixing or dipping. Exhaust fan control shall be interconnected with spray gun so as to operate simultaneously. Exhaust fans shall, in addition, be arranged to operate independently of spray gun. Ventilation Equipment shall be kept in operation for a sufficient length of time thereafter to exhaust all vapors, fumes or residues of spraying materials from the spray booth, dip space or drying room. Air admitted to the spraying, dipping, immersing, drying spaces or storage rooms shall be fresh air taken from the outside of the building.

(3) Equipment. Motors shall be located outside of spraying, dipping or immersing spaces except as provided in § 18-01(d).

(d) Specification for spray booths, spray rooms, dip and immersing rooms, drying equipment and material storage rooms.

(1) Spray booths shall be constructed of metal or incombustible materials satisfactory to the administrative official having jurisdiction. Ventilation and lighting for spray booths, spray rooms, dipping rooms, drying rooms and storage rooms shall comply with requirements of these rules.

(i) Spray, dip and immersing rooms shall be enclosed on all sides with partitions constructed of incombustible materials with floors in such rooms of concrete. Where such rooms are located over wooden floors, such wooden floors shall be surfaced with 1" of grout adequately reinforced or a mixture of Portland cement and sand similarly reinforced. Ceilings over such rooms shall be protected by 5/8" unsanded gypsum plaster or 7/8" of cement or sanded gypsum plaster on approved 3.0 lb metal lath or other equivalent fire resisting ceiling protection. Ventilation, lighting and heating for these rooms shall comply with the requirements of these rules. Where additional fire fighting equipment is necessary such equipment shall be furnished in accordance with the direction of the Fire Commissioner. Floor drains leading to the house draining system or the public sewer shall not be permitted. Dip tanks shall be provided with hinged metal covers held open by a fusible link, such covers to be equipped with an opening to permit automatic flooding of the tank with fire extinguishing media of a type and so located as the Fire Commissioner shall direct. Where the work process, such as conveyorized operation, makes the use of a cover impractical, the dip tank and drain boards shall be protected by an adequate extinguishing system designed for manual and automatic operation satisfactory to the Fire Commissioner and such conveyor shall be interlocked with the extinguishing system so that in the event the extinguishing system is activated, the conveyor action shall be stopped.

(ii) Panels of polished wired glass or plate-glass at least one-quarter (1/4) of an inch thick, not exceeding seven hundred and twenty (720) square inches in area and not more than forty-eight (48") inches in any linear dimension may be used in the sides of a spray booth or room.

(iii) The inner sides of walls, ceilings and the floors of all spraying or dipping spaces shall have a smooth surface.

(iv) All openings in spray, dip or immersing rooms shall be protected by fireproof opening protective assemblies. Windows opening on a street may be used to provide ventilation but no window on a lot line or less than 20 ft. from any opening in a wall of an adjacent building shall be permitted except when the subject room is more than 20 ft., in the horizontal plane, above an adjoining building.

(v) Ferrous metals used in the construction of spraying, dipping or immersing spaces shall be thoroughly painted on the inside or be galvanized.

(vi) All spraying, dipping or immersing spaces shall be so constructed that at least three (3) feet of clear working space shall always be maintained for each operator spraying, dipping or immersing the material being processed.

(2) Storage rooms. Storage rooms shall be constructed of fireproof or fire resisting material and shall have a window opening to the outer air but such window shall not be on a lot line, enclosed court, nor opposite within twenty feet of windows of adjacent buildings nor part of the same premises, such window openings to be fireproofed and lower half provided with open louvers or ventilated by metal duct or fan at least 8 inches in diameter. The floors of all storage rooms shall be of incombustible non-ferrous materials. The sill of the door shall be at least 6 inches above the finished floor. All doors to be tin-clad, approved, fireproof and self-closing. The lighting equipment shall comply with §18-01(d)(5)(ii)(B) and shall have an electric switch located outside the room. Immediately adjacent to such room shall be provided such portable fire extinguishing equipment for use within the storage room as the Fire Commissioner shall direct.

(3) Drying equipment.

(i) Gas fired drying ovens. Gas fired drying ovens shall be of a type as approved by the Board. Such ovens shall be constructed of metal and incombustible materials so designed as to preclude the direct application of flame to the materials in process. Ventilation shall be provided for each oven of sufficient capacity to maintain an oven vapor concentration at all times during the drying process of less than 1/4 the low explosive limit of the solvent used. All oven openings shall be maintained at a negative pressure relative to room pressure for inward flow. The controls for the safety exhaust and recirculating fans shall be properly interlocked with the gas supply line so that when the gas is flowing the fans are in operation. A time delay relay shall be installed to provide a minimum of four oven volume changes with fresh air and in the case of an indirect fired type of oven simultaneous purging of the combustion chamber before the ignition system can be energized and gas flow started. Each oven shall be equipped with gas burning equipment approved for such use and with electrical controls so arranged as to shut off the gas valve when ignition fails or the gas supply pressure drops to 2 inches of water. The use of a continuous gas pilot light is prohibited unless an automatic gas shut off valve is provided which will shut the gas off at the pilot light when the flame is extinguished or the supply of gas cut off. Electrical pilot ignition shall be of the continuous type or equal in performance, designed for use in high temperatures, with controls so inter-locked as to shut off the gas supply when current is interrupted. An auxiliary manually operated gas shut off valve shall be located not nearer than 25 feet from the oven so as to control the gas supply in the event of an emergency. Such ovens shall be adequately insulated on all sides and top to limit the maximum surface temperature to 140°F and to 160°F on the base, unless the floor is protected by a 3 inch mat of reinforced concrete placed over and bonded into the existing concrete floor and projecting not less than 6 inches outside the projected area of the equipment or unless an unenclosed clear air space not less than 4 inches above the concrete floor is maintained between the floor and the underside of the oven. The burner section of gas fired drying ovens shall not be located nearer than 25 feet from spraying or dipping spaces except when separated by fire proof construction, in which case the distance between burner section and spray or dip space shall be not less than 25 feet measured in the shortest line of travel.

(ii) Electric infra-red ray drying ovens. Electric Infra-Red Ray Drying Ovens shall be of a type as approved by the Board. Such ovens shall be constructed of electric equipment installed in accordance with the National Electric Code and the requirements of the Bureau of Electrical Control. Ovens when erected shall be placed on concrete floors without any additional protection, provided that at least 12 inches of clear space above the floor is provided to permit adequate ventilation.

(A) In drying processed material involving the evaporation of considerable amounts of flammable solvents by infra-red lamps, such installations shall not be confined in small rooms unless such rooms are thoroughly ventilated by a power driven ventilation system of sufficient capacity to maintain a vapor concentration at all times during the drying process of less than 1/4 the low explosive limit of the solvent used; the controls of the ventilation system to be so inter-locked with the Infra-Red Ray System that the latter cannot function unless the ventilating system is in operation. When equipped with duct ventilating system, the Infra-Red Ray Oven shall be adequately secured so as to prevent moving.

(B) Where the evaporation of a considerable amount of flammable vapors are involved, ventilated hoods located as near to the floor as practicable or enclosures shall be provided at the initial stage of the process with adequate exhaust system to discharge the primary evaporation from the solvents to the outer air, so that when the processed material progresses through the lamp drying tunnels only a comparatively small amount of solvent is left for evaporation. A space between such ventilating section and the drying section shall be maintained.

(C) Lamps and other electrical equipment shall be kept free from flammable deposits and adequate cleaning shall be maintained.

(D) Lamp and resistance heater type drying units shall be separated from spraying and dipping processes complying with these rules by a distance of at least 15 feet or shall be installed in a separate fireproof room.

(E) Controls shall be arranged so that the lamps in the tunnels will be shut off automatically if and when the conveyor stops.

(F) Where there are no conveyors and the material being processed is left stationary in the dryer there shall be an excessive temperature switch to shut off the lamps or resistance heaters to avoid overheating the material being processed if it is not removed from the dryer in time.

(G) Material to be processed on the conveyors shall be rigidly supported so as not to be liable to displacement and cause lamp breakage and short circuits. Where there are no conveyors, materials should be fixed on dollies running on tracks or other equivalent method to accomplish the same result.

(iii) The temperature of the air contacting the processed material or of the material itself shall not be higher than that to which such material can be safely subjected.

(iv) Such fire fighting equipment suitable for electrical and solvent vapor fires shall be provided as the Fire Commissioner may direct.

(4) Specifications for ducts, pipes and fans.

(i) All ducts used for ventilating spray, dip or immersing spaces shall be constructed of approved incombustible materials or metal of not less than the following gauges of metal: Ducts twenty-four (24") inches or less in diameter No. 22 gauge. Ducts over twenty-four (24") inches and not over thirty-six (36") inches in diameter No. 20 gauge. Ducts exceeding thirty-six (36") inches in diameter No. 18 gauge.

(ii) Ducts shall be strongly constructed and be installed in a workmanlike manner. They shall be rigidly supported.

(iii) Ventilating ducts shall run as directly as practicable to the outer air and be protected with a hood against the weather. The exhaust terminal or hood shall also be protected with a screen of copper or bronze with a mesh not larger than one-quarter (1/4") inch.

(iv) Where a duct passes through a non-fireproof floor or roof, the duct shall be protected at such point by an outer pipe or sleeve with an air space of at least one (1") inch between the sleeve and pipe protected from the woodwork by at least a 1" blanket of [asbestos,] compressed [rockwood] rock wool or glasswool, or equivalent fire-resistive material extending through the entire depth of the ceiling construction and adequately secured to the outer pipe. The outer pipe shall be not less than two (2") inches from any woodwork and such woodwork shall be covered with at least 26 gauge metal or other incombustible material.

(v) Ventilating ducts shall not terminate within ten (10) feet measured horizontally of any chimney outlet, unprotected air intakes or within twenty (20) feet of any exit or any opening in an adjoining building.

(vi) If induced draft is used to create an air movement, the air shall be supplied from a point outside the spray or dip or immersing space. Fans and motor must be located outside the spray, or dip space, except approved explosion-proof motor and non-ferrous blade fans which, however, are not to be located where residues of spraying material may collect on such equipment.

(vii) The exhaust system from any spray, dip or immersing space shall not be connected to any other ventilating system or be discharged into a chimney or flue used for the purpose of conveying gases of combustion.

(viii) Exhaust fan blades shall be constructed of non-ferrous metal. All exhaust and ventilating fans to be permanently connected to their source of power, using metallic conduit. Rheostats in fan bases not permitted. Fan blades not coming in direct contact with spraying fumes need not comply with this requirement.

(ix) Adequate access doors or panels have tight fitting by means of screw bolts, clamps or springs shall be provided, to permit inspection and cleaning.

(5) Electrical equipment and lighting fixtures.

(i) No motors, switches, rheostats, lamps, fluorescent light or other electrical equipment shall be located in spray, dipping or immersing rooms or within ten (10') feet of the open end of any spray compartment, spray booth, immersing or dipping space unless such electrical equipment be of a type approved for use in explosive atmosphere and where a conduit leads from a hazardous location to a non-hazardous location, the conduit shall be sealed off by an approved sealing compound. Except that alternating current induction motors of the totally enclosed type, having no brushes make and break contacts, collectors or other arcing or sparking parts may be located within ten (10') feet of a spray booth, spray compartment or dipping space when approved by the administrative official having jurisdiction. No open flame shall be used within 25 ft. of spray, dip or coating space or paint storage room or cabinet except when separated by fireproof construction, except as provided in § 18-01(d)(3)(i) "gas fired drying ovens" and § 18-01(d)(3)(ii)(D) electric infra-red dry ovens. Nothing herein contained, nor in § 18-01(g)(5) shall prohibit the use of electrostatic paint spraying equipment of a type approved by the Board under such conditions as the Board shall prescribe in its approval.

(ii) Lighting fixtures.

(A) Artificial lighting shall be only by means of electricity.

(B) When lighting fixtures are located within 10' of a spray booth, spraying space, dipping space or within a storage room they shall be of the rigid stem type, enclosing all wiring and be equipped with keyless sockets having vapor proof globes. Where exposed to breakage, globes shall be adequately protected by substantial metal guards or equivalent means. Fluorescent tube type lighting fixtures when used in spray booths or in spray and dip spaces or in storage rooms or rooms containing inflammable vapors, shall be of a type approved for use in explosive atmospheres. The auxiliaries of mercury vapor lamps shall be offset at least ten (10') feet from spray booth, spray or dip spaces unless enclosed in explosion-proof protection.

(C) All electrical equipment shall be installed and grounded as provided by the Administrative Code covering electrical equipment and permanently connected to their source of current supply, using metallic conduit.

(D) No pin plug receptacles shall be used except when the use of receptacles and attachment plugs become necessary they shall be so connected to form a part of a unit device with explosion-proof interlocking switch precluding the removal of the plug when the switch is in the "on" position or by an approved explosion-proof enclosure which can seal the arc when the current is interrupted. Such receptacles and plugs shall be of the polarized type providing a connection for the grounding wire of the portable cords.

(E) All electric wiring shall be enclosed in rigid standard weight metallic conduits with explosion proof joints and fittings. Joints in metallic conduit having threaded couplings shall not have less than five (5) fully engaged threads. Where flexible connections are required a flexible fitting approved for explosive atmospheres shall be used.

(F) The use of portable cords or trailer lights are prohibited, except when flexible cord approved for hard usage containing one (1) extra insulated conductor properly connected to form a grounding connection for metal lamp guards, motor frames and all other exposed metal portions of such portable lamps and devices may be used. When portable lamps are used they shall be enclosed in a manner approved for explosive atmospheres and with substantial guards of metal to prevent breakage. Sockets shall be of the keyless moulded composition type with no exposed metal parts.

* * *

(f) Material storage and mixing.

(1) Main supplies of spray coating and dipping materials and thinners shall be kept in an outside storage building, storage rooms or in vented metal cabinets in accordance with the following amounts:

(i) Spraying materials not in excess of 100 gallons may be stored in single walled metal cabinets ventilated to the outer air. Such cabinet to be metal covered on all sides, including the doors and arranged for ventilation at top and bottom.

(ii) Spraying materials not in excess of 200 gallons may be stored in double-walled metal cabinets ventilated to the outer air or wood cabinets metal covered on all sides, including the door, and arranged for ventilation at top and bottom, to the outer air.

(iii) Spraying materials in excess of 200 gallons shall be stored in a separate exterior storage building of fire-proof or fire-resisting material with ventilated plain glass skylight or in a storage room constructed fire-proof in a fireproof building or fire-resisting in a non-fireproof building. The maximum amount of spraying materials to be stored in a storage room of a non-fireproof building shall be determined by the administrative official having jurisdiction.

(iv) Mixing or thinning of coating materials shall be conducted in a storage building or storage room, except that containers of total capacity not exceeding ten gallons may be opened and their contents mixed in the spray room or room in which booths are located while the air exhaust system is operating.

(v) Working supplies sufficient for not more than one day's use but not exceeding twenty gallons to each booth, nor a total of hundred gallons, may be kept in the spray room or room in which spray booths are located; covers of containers must be kept thereon when such containers are not actually in use. This amount is in addition to the amount allowed in § 18-01(f)(1)(vii).

(vi) Gravity feed material containers for supplying spray guns shall not exceed ten gallons in capacity and shall be supported by wire cables or metal brackets having a factor of safety of four when filled with the heaviest spraying materials used.

(vii) Pressure feed tanks and other equipment for use in connection with direct spraying under air pressure shall be restricted to tanks of not more than sixty gallons, individual capacity, designed, constructed and approved for this specific purpose by the Board of Standards and Appeals. Each tank shall be provided with a safety valve set at a pressure not exceeding eighty pounds. All gravity feed containers and other spraying equipment shall be approved as above.

(viii) The installation of all electrical wiring, switches, lighting and all other electrical equipment, and the provisions of these rules against carrying matches or smoking and prohibiting flame or spark-producing devices, shall also apply to storage or mixing rooms.

(2) Storage of materials where nitro cellulose products are manufactured. Storage of spraying, dipping and immersing materials shall be as provided in § 18-01(f)(1)(i) through (iii), but in a building in which nitro cellulose products are manufactured, stored or kept the amount shall be not over twenty-five (25) gallons as per § 27-4200, subdivision (h) of the Administrative Code.

(3) Sprinklers. Sprinkler heads shall be provided in all spray, dip or immersing spaces and storage rooms and shall be installed in accordance with the Sprinkler rules of the Board of Standards and Appeals § 10-02, except in non-sprinklered buildings where sprinkler connection may be made to the house water supply, provided the size of the house water supply line is adequate for the number of sprinkler heads.

(4) Maintenance of sprinkler heads. Sprinkler heads in spraying, dipping and immersing spaces shall be cleaned at least once a week under the supervision of the person holding the certificate of fitness and a coating of light grease or vaseline shall be applied after each cleaning to prevent the formation of a hard deposit and render the sprinkler useless in case of fire. The use of paper bags or other materials about sprinkler heads is prohibited.

* * *

(h) Existing spray booths and installations. These sections shall be retroactive in the following respects;

§ 18-01(a)(3)(iv) Heating of Rooms § 18-01(c)(1) Air Exhaust System § 18-01(c)(2) Air Supply and Mixing § 18-01(d) Specifications for Spray Booths, Spray Rooms, Dip and Immersing Rooms, New Drying Equipment, and Material Storage Rooms § 18-01(d)(1)(iii) Surfacing of Booths § 18-01(d)(1)(v) Surfacing of Metal in Booths § 18-01(d)(3)(ii) Maintenance of Ducts § 18-01(d)(4)(vi) Method of Induced Draft § 18-01(d)(5)(i) Electrical Equipment § 18-01(d)(5)(ii) Electrical Lighting * * * * * * § 18-01(e)(12) Motor vehicles in booths or rooms § 18-01(e)(13) Spraying Elevator Cabs § 18-01(f) Material, Storage and Mixing § 18-01(g) General Requirements § 18-01(h) Section 18-01(f)(1), (2), (3) and (4) may not be applied in fireproof buildings equipped with an approved existing automatic sprinkler system where the general conditions of cleanliness are properly maintained at all times

* * *

(Added City Record 4/4/2019, eff. 5/5/2019; renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8302-01. Pre-Existing Definitions

Open this section

(a) Scope. This section sets forth definitions of terms used in the Fire Prevention Code and former Fire Department rules in effect on June 30, 2008 that are consolidated in 3 RCNY Chapter 83.

(b) Definitions.

Board of Standards and Appeals. New York City Board of Standards and Appeals.

Department of Buildings. New York City Department of Buildings.

Department of Small Business Services. New York City Department of Small Business Services.

Multiple dwelling. A multiple dwelling, as defined in subdivision seven of section four of the multiple dwelling law, including any portion of such dwelling used for other than living or sleeping purposes, or for any business, commercial or other non-residential purpose. (Fire Prevention Code, former Administrative Code § 27-4002(27a))

Structure. Any building or construction of any kind. (Fire Prevention Code, former Administrative Code § 27-4002(38)(c))

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8303-01. General Precautions Against Fire in Pre-Existing Facilities

Open this section

(a) Scope. This section consolidates the Fire Prevention Code and former Fire Department rules in effect on June 30, 2008 that are applicable to the design and installation of fire safety precautions in pre-existing facilities.

(b) Definitions. [Reserved.]

(c) Boatyards, Marinas and Similar Facilities. Boatyards, marinas and similar facilities in compliance with former Fire Department rule § 5-01 are allowed and would be approved under the provisions of the Fire Code and the rules, and accordingly, such facilities shall be designed and installed in compliance with the requirements of 3 RCNY § 301-01, except that in pre-existing facilities with fire apparatus access roads less than 38 feet wide, such fire apparatus access roads shall be continued in compliance with the provisions of former Fire Department rule § 5-01(b) until such time as such facilities may be required to comply with the Fire Code and the rules with respect to such access roads.

(1) Former Fire Department Rule § 5-01(b)

§ 5-01 Fire Protection of Boatyards, Marinas and Similar Occupancies.

(b) For firefighting purposes, adequate unobstructed aisles and cross aisles of at least 20 foot width shall be provided for both length and width of premises and maintained clear in all directions so that no point in the yard is further than 75 feet from an access aisle in any direction.

(d) Automotive salvage and wrecking facilities. Automotive salvage and wrecking facilities in compliance with former Fire Department rule § 4-01 are allowed and would be approved under the provisions of the Fire Code and the rules, and accordingly, such facilities shall be designed and installed in compliance with the requirements of FC 316, except that in pre-existing facilities with fire apparatus access roads less than 38 feet wide, such fire apparatus access roads shall be continued in compliance with the provisions of the former Fire Department rule § 4-01(e)(2)(i) until such time as such facilities may be required to comply with the Fire Code and the rules with respect to such access roads.

(1) Former Fire Department Rule § 4-01(e)(2)(i)

§ 4-01 Fire Protection of Automotive Salvage and Wrecking Establishments.

(e) Fire protection requirements.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(2) Access and separation.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(i) Driveways having a minimum width of fifteen feet shall be provided and shall be so spaced that a maximum grid system of not over fifty feet by one hundred feet is produced. Driveways shall be maintained unobstructed to provide access for Fire Department equipment.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8304-01. Pre-Existing Emergency Planning and Preparedness

Open this section

(a) Scope. This section consolidates the Fire Prevention Code and former Fire Department rules in effect on June 30, 2008 that are applicable to the design and installation of pre-existing facilities for purposes of emergency planning and preparedness.

(b) Definitions. [Reserved.]

(c) General Provisions. Pre-existing facilities, the design and installation of which for emergency planning and preparedness purposes would not be allowed or approved under the Fire Code, but which, pursuant to FC 102.3 and 3 RCNY § 102-01, may be continued with respect to such emergency planning and preparedness under the applicable laws, rules and regulations in effect prior to the Fire Code, shall continue to comply with the provisions of such laws, rules and regulations, including former Fire Department rules § 34-02, as applicable, with respect to such emergency planning and preparedness, until such time as such facilities may be required to comply with the Fire Code and the rules with respect to the design and installation of such emergency planning and preparedness.

(d) Life Safety Requirements for Schools with Physically Handicapped Students.

(1) Former Fire Department Rule § 34-02.

§ 34-02 Life Safety Requirements for Schools with Physically Handicapped Students. The following life safety requirements shall apply to those public schools included in the Board of Education, Division of School Buildings, ABR/COH Facilities Accessibility Program which is contained in the Jose P. vs Ambach, et al. (Index No. 79 Civ. 270) judgment plan, appendices and stipulations and shall apply to private preschools through secondary schools.

(a) Buildings to be of class 1 (1938 [Administrative] Building Code) construction, or Group 1A, lB, or 1C (1968 Administrative Code), shall conform to the structural, service equipment and occupancy requirement of Chapter 1 of Title 27 of the [Administrative] 1968 Building Code and to the regulations of the Department of Buildings.

. . . . . . . . . .

(c) At no time shall occupancy by non-ambulatory students be permitted in basement or cellar area of school unless entire area of basement or cellar is fully sprinklered by a wet automatic sprinkler system (electrical rooms excluded).

(1) Where terrain configuration places cellar or basement Holdings Area(s) in a position that affords accessibility to Fire Department personnel, sprinkler requirements as per subdivision (c) above, may be waived. Such relief is subject to approval of Bureau of Fire Prevention.

(2) Where terrain configuration places cellar or basement space intended for use by non-ambulatory student on a level where egress may be made directly and unencumbered to the exterior of the building via exits constructed for such purpose, the Holding Area(s) requirements in such cellar or basement space may be waived. Relief from Holding Area(s) provision in this case is subject to approval of Bureau of Fire Prevention.

(d) Holding Area(s) shall be provided on each floor above and below grade level where occupancy by non-ambulatory students is to be permitted.

(1) Holding Area(s) shall be designated room(s) fully enclosed in non-combustible partitions with all door openings therein either of non-combustible material or of solid wood construction located adjacent to an exit stairwell. Egress from the Holding Area(s) shall be by way of a corridor. These rooms shall be provided with a 2-way voice communication system acceptable to the Fire Commissioner that shall be connected to both the custodian's office and the principal's office. The communication system shall be properly maintained in working order at all times. Inspections, test maintenance and record keeping requirements shall be the responsibility of the person holding the certificate of fitness for [the Interior Fire Alarm System] supervision of fire alarm system maintenance, and shall conform to the requirements of [§ 27-4265(g) of the Administrative Code] FC 901.6.1.

(2) Holding Area(s) shall face on a street accessible to Fire Department apparatus and be free from physical impediments (e.g. trees) that may interfere with the positioning of Fire Department apparatus.

(3) Windows in Holding Area(s) designated [from] for removal of handicapped students shall provide, when opened, an area free of obstructions that is at least 32" wide and 48" high accessible to Fire Department equipment. Such windows shall be readily openable without the use of a key.

(4) Window sills on windows designated for removal of handicapped students shall be not more than 36" above the floor level of associated Holding Area(s) and shall be painted red, inside and outside, with a sign attached outside, top window pane. This sign shall read "F.D. ACCESS" and shall be not less than 12" × 18" in size. Sign shall be made of metal or other durable non-combustible material with 4" red lettering in bold type on a white background. Sign shall be properly maintained.

(5) Holding Area(s) shall line up vertically on the facade of each floor of the building.

(6) Doors leading to Holding Area(s) shall be provided with a sign 5" x 18". This sign shall read "HOLDING AREA". Sign shall be made of metal or other durable non-combustible material with 3" red lettering in bold type on a white background. Signs shall be mounted on the lower half of the door and be properly maintained.

(7) Holding Area(s) shall have movable seats and desks and be capable of holding the total number of wheelchairs required to use the Holding Area. Minimum net floor area shall be calculated at 25 square feet per wheelchair and be free of all encumbrances.

(8) Holding Area(s) shall have ceilings and floors which have a minimum one and one-half hour fire rating. Walls shall have a minimum one hour fire rating and all door openings shall be equipped with appropriately rated fire-proof self-closing doors with a minimal vision panel. The maximum size of vision panel shall be 144 square inches. No opening shall be permitted in wall, ceilings or floors unless properly protected.

(9) Holding Area(s) shall be [equipped with a 2 1/2 gallon pressurized water extinguisher] provided with a portable fire extinguisher with at least a 2-A rating. . . . . .

(10) All ducts/vents which breach or otherwise cause integrity of Holding Area to be violated shall be equipped with an approved combination smoke/heat damper.

(11) Smoke barriers, in accordance with the provisions of § 27-369(c) of the [Administrative] 1968 Building Code, shall be provided in corridors. Such smoke barriers shall separate the Holding Area and the adjacent exit stairwell from the rest of the building. Doors in such smoke barriers shall comply with the provisions of § 27-371(c) of the [Administrative] 1968 Building Code except that these smoke stop doors may also be left open if they are arranged to close automatically by an approved smoke detector on the ceiling immediately adjacent to and on both sides of the doors.

(e) The auditorium shall be fitted to accommodate all persons using wheelchairs in attendance. These accommodations shall be immediately adjacent to and at the same level as a main exit. Existing required aisles, passageways and exits shall not be reduced or obstructed, and legal occupant load shall not be exceeded.

(f) All existing and newly installed elevators shall be equipped with [firemen] firefighter service keys to conform with Fire Department requirements.

(g) Interior Fire Alarm system shall be provided with visual warning signals in addition to the required gongs. Such visual warning signals shall be visible from any location in all corridors and in unsupervised rooms occupied by handicapped students. The visual signal shall be on a separate circuit and control panel. Visual signal shall continue flashing after the four rounds of the Fire Alarm box have run out, and must be manually reset.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8305. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8305 at American Legal Publishing.

§ 8306. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8306 at American Legal Publishing.

§ 8307. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8307 at American Legal Publishing.

§ 8308. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8308 at American Legal Publishing.

§ 8309-01. Fire Protection Systems in Pre-Existing Facilities

Open this section

(a) Scope. This section consolidates the Fire Prevention Code and former Fire Department rules in effect on June 30, 2008 that are applicable to the design and installation of fire protection systems in pre-existing facilities.

(b) Definitions. [Reserved.]

(c) General Provisions. Pre-existing facilities with fire protection systems the design and installation of which would not be allowed or approved under the Fire Code, but which, pursuant to FC 102.3 and 3 RCNY § 102-01, may be continued with respect to such fire protection systems under the applicable laws, rules and regulations in effect prior to the Fire Code, shall continue to comply with the provisions of such laws, rules and regulations, including former Fire Department rules §§ 15-04, 17-01(d)(3)(iii), 17-07 and 17-08, as applicable, with respect to such fire protection systems, until such time as such facilities may be required to comply with the Fire Code and the rules with respect to the design and installation of such fire protection systems.

(d) Commercial Cooking Fire Extinguishing Systems.

(1) Former Fire Department Rule § 15-04

§ 15-04 Extinguishing Systems for Hoods, Vent Pipes, Flues or Ducts*

[*FOOTNOTE IN ORIGINAL: Section is applicable to systems installed on or after 12/14/62 but before 12/6/68. Systems or system changes made post 12/6/68 shall be in accordance with RS 13-3 (Building Code) and NYC Administrative Code §§ 27-4275 & 27-779.]

(a) Plans. The installer or occupant shall submit three (3) sets of paper cloth drawings to the Bureau of Fire Prevention for approval before any work is commenced. These shall show the entire installation in plan and section, viz: all hoods; ducts; dampers; heat detector units; pipes; nozzles; fans; gas controls; automatic trip devices; manual operating controls; all other details for compliance with these regulations.

(b) Tests. The completed system shall be tested by the installer or occupant, at his or her own risk, in the presence of a Fire Department representative before an approval shall be issued.

(c) Cleaning. The hood and exhaust ducts shall be thoroughly cleaned and be in good repair before the system is installed. They shall be so maintained at all times.

(d) Operation and control. The extinguishing system shall be automatic or both automatic and manual in operation. The manual controls shall be accessibly located at least ten (10) feet from the range and sealed in the closed position with a light wire seal or a break glass control. A sign to indicate the purpose of such valve or control shall be affixed thereto. The automatic operation shall be arranged to shut off the gas, exhaust fans and close the dampers in the exhaust system. The automatic releasing equipment and heat detecting units shall be Underwriters Laboratories approved.

. . . . . . . . . .

(f) Location of nozzles and heat detectors. The entire duct system and any deep frying units shall be provided with an adequate number of nozzles. One nozzle shall be installed at the inlet of each duct and one at the inlet side of the damper. Duct nozzles shall not exceed ten (10) feet on centers. Heat detecting units shall be located at all duct inlets.

. . . . . . . . . .

(h) Carbon dioxide.

(1) Where carbon dioxide is used: There shall be provided at least one fifty (50) pound cylinder of such gas for each installation up to four hundred (400) cubic feet of hood and duct volume up to the damper. For every additional four hundred (400) cubic feet, or portion thereof, an additional fifty (50) pound cylinder shall be installed.

(2) Electrical requirements for the installation of thermostatic detection systems and the operation of safety devices when carbon dioxide systems are used as the extinguishing agent in hoods, vent pipes, flues or ducts to exhaust interior cooking spaces are:

(i) Plans. The plans submitted for approval shall have marked thereon the location of the thermostatic detectors, the damper locations, all alarms, the electrical and mechanical operations of the safety devices as hereby required.

(ii) Equipment approval. All the electrical equipment shall be approved by the Board of Standards and Appeals or the Underwriters Laboratory for the installation for the class of detection, operation and alarm.

(iii) Wiring. The electrical equipment shall be operated on closed circuits, 120 volt systems. The wire shall be rubber covered RHW #14 AWG, installed in rigid iron or steel conduits.

(iv) Operation requirements.

(A) The thermostatic device shall be either of a type that is manually reset or the control system shall be so arranged that some manual operation is required to restart the fan after the thermostat has operated. The thermostats shall operate on a 350°F. temperature. The thermostats shall be installed in a manner to enable the removal of the thermostat for repair or testing.

(B) A light, normally on, installed within the hood installation room, to give indication that the source of current for the carbon dioxide system is out of service shall be required.

(C) An alarm bell will be required when two or more 50 lb. carbon dioxide cylinders are required. The alarm shall sound upon the operation of the thermostatic device.

(D) An emergency manual control, preferably in the form of a break glass station, to operate the system is required.

(E) The fan shut down, gas valve closure, damper operations may be electrically or mechanically operated to operate the electric controls.

(i) Fine water spray. Where a fine water spray is used: All pipe sizes shall conform with and all valve sizes shall conform to the Building Code of the City of New York. The minimum static pressure at the highest nozzle shall not be less than thirty (30) p.s.i. One half (1/2) inch open, wide pattern nozzles shall be installed throughout. A water flow alarm may be installed if desired.

(j) Steam. Where steam is used: A continuous source of steam supply of not less than fifteen (15) p.s.i. shall be provided. The pipe sizes at the source of supply shall not be less than one and one-half (1 1/2) inches in diameter and not less than three quarter (3/4) inch for the last steam jet or outlet. Such outlet shall be a standard one-half (1/2) inch open sprinkler head. The pipe fittings and valve shall be steam standard. A control valve sealed open shall be located at the source of steam supply. A steam trap shall be installed on the steam line in such a location so as to remove all condensation up to the automatic control valve located at or near the ranges or ducts.

(k) Application. These rules shall apply to all new installations and to existing systems hereafter altered in any manner.

(e) Fire Alarm Systems.

(1) Former Fire Department Rule § 17-07

§ 17-07 Installation of Interior Fire Alarm Signal Systems in Multiple Dwellings Having Single Room Occupancies.

(a) In every such building there shall be provided an adequate and reliable electric, closed circuit interior fire alarm system in accordance with the requirements of the Fire Commissioner.

(1) Buildings exceeding six stories in height, or having more than five thousand square feet in area in any one story, shall be provided with a coded system.

(2) Buildings not exceeding six stories in height, or having more than five thousand (5,000) square feet in area in any one story, shall be provided with a coded system or a non-coded system.

(b) The interior fire alarm system shall be installed in a workmanlike manner and in accordance with standard trade practices.

(c) The alarm system shall be so arranged and connected that the operation of any fire alarm station shall sound an alarm on the sounding devices simultaneously throughout the premises.

(d) Sending stations.

(1) There shall be provided, on each story, and in the basement at least one fire alarm sending station located in a natural path of escape from fire at a readily accessible location designated by the Fire Chief and Commissioner, which always shall be kept unobstructed.

(2) Additional sending stations may be required where the travel distance from any one point, on the floor, exceeds one hundred and fifty (150) feet to the fire alarm station. (Not more than twenty (20) stations will be permitted on any one circuit or loop.)

(e) Sounding devices.

(1) There shall be provided sufficient sounding devices, such as bells, gongs, horns, or whistles, so that the signals will be clearly audible to all the occupants of the building. In no case shall the sounding devices be less than two (2) in number.

(2) Not more than fourteen (14) direct, nor more than ten (10) alternating current gongs will be permitted on any one gong circuit.

(f) Control board.

(1) There shall be provided in the basement pump room, engine room of janitors quarters, an approved control board designed to operate the alarm system.

(2) The control board shall be provided with an approved type trouble bell so connected that any disarrangement of the circuit wiring will sound a distinctive signal continually.

(g) Wiring.

(1) All electric wiring for the interior fire alarm system shall be of copper, rubber insulated, protected by a braid, and be not less than number 14 Brown & Sharpe wire gauge. The wiring shall be protected from mechanical injury by standard weight, rigid iron conduit, properly bonded and grounded.

(2) The conduit shall be grounded to a water pipe by at least number 10 B. & S. gauge copper wire and approved copper ground clamps.

(h) Sources of electric energy.

(1) The source of energy used to operate the interior fire alarm system shall be obtained from the public service companies' mains, and shall not exceed a potential of 240 volts, either alternating or direct current.

(2) When energy cannot be obtained from a central station power system, storage batteries in duplicate may be accepted when specifically approved by the Fire Chief and Commissioner.

(3) When energy is supplied by a central station power system, the fire alarm cutout shall be the first connection, and as near as possible to the electric meter registering current consumed by the hall lighting system.

(4) The fusible cutout shall be contained in a sealed or locked metal cabinet painted Fire Department red, and stenciled, "Interior Fire Alarm." Not less than fifteen (15) ampere, enclosed type cartridge fuse will be accepted. Screw plug fuses are prohibited.

(i) Layout. Before the installation or extension of any fire alarm system, specifications thereof, showing complete details of the proposed installation shall be submitted by the owner or agent to the Fire Chief and Commissioner for examination and approval.

(j) Instruction cards.

(1) There shall be provided an approved instruction card, properly marked, framed under glass and securely mounted at each fire alarm station.

(2) The location of the nearest street fire alarm box or the quarters of the nearest engine or truck company shall be shown on this card.

(k) Watchmen's time detector system.

(1) There shall be provided an approved system of watchmen's time detectors to record the movements or patrol of the watchmen.

(2) The watchmen's time detector stations shall be so located that the watchman will be compelled to cover all public portions of the premises at least once every two hours to record complete round of signals upon the watchman's time detector clock.

. . . . . . . . . .

(2) Former Fire Department Rule § 17-08

. . . . . . . . . .

(f) Watchman's Time Detector Systems and Watchman Service.

(1) Former Fire Department Rule § 41-01

§ 17-08 Telegraphic Alarm Communications in Theaters, Opera Houses and Concert Halls.

(a) By virtue of the authority vested in the Fire Commissioner under § 15-127(b)(1) of the Administrative Code, telegraphic communication to the Fire Department shall be required from theaters, opera houses, concert halls and similar places of amusement if such occupancies are provided with a stage, scenery and dressing rooms, seating capacity exceeds 299 persons and live performances are presented. The telegraphic communication (alarm box) shall be tested daily and prior to each performance and maintained unobstructed and in proper working order at all times.

(b) Telegraphic alarm communications to the Fire Department shall not be required from motion picture theaters or common show motion picture theaters. A motion picture theater is a public hall or room in which motion pictures are displayed, in which the seating capacity does not exceed 600 persons and in which no stage or scenery is provided. A common show motion picture theater is a theater, with or without stage, scenery and dressing rooms, in which the seating capacity exceeds 600 persons and motion pictures only are exhibited.

(c) A common show motion picture theater provided with stage, scenery and dressing rooms may periodically present live performances. In so doing, such occupancies convert to live performance theaters and as such, telegraphic communications to the Fire Department shall be required in accordance with subdivision (a) above, except that such telegraphic communications shall not be required if six or less live performances are presented annually and the following is complied with:

(1) Licensee shall notify the Bureau of Fire Prevention, in writing, at least five (5) days in advance of the time and dates of such live performances.

(2) A non-coin operated telephone without connection through any switchboard shall be installed backstage prior to any live performance. This telephone shall be for the exclusive purpose of transmitting a telephone alarm in the event of fire or other emergency. A card of instructions for reporting a fire or other emergency to the Fire Department shall be posted at the location of the telephone. Such card shall be approved by the Bureau of Fire Prevention.

(3) Two (2) competent persons in the employ of the licensee shall be constantly available during the live performances to perform the following emergency duties:

(i) One (1) such person shall remain near the backstage telephone during the performance for the exclusive purpose of transmitting an alarm via the phone in the event of fire in the theater. Such person shall not be required to perform any other duties during the live presentation.

(ii) The second person shall be assigned by the licensee as a "street box runner" who shall be familiar with the nearest city fire alarm box and how to operate same. He or she shall be required to perform no other duties during the live presentation than to transmit any necessary alarm from the street box.

(d) Any of the foregoing notwithstanding, theaters constructed in accordance with the provisions of the 1968 Building Code shall be provided with telegraphic alarm communications to the Fire Department, as required by the 1968 Building Code as follows:

(1) All occupancies classified by the Department of Buildings as F-1a occupancies, regardless of seating capacity. F-1a occupancy is an occupancy in which persons assembled comprise a seated or otherwise passive audience to a performance or presentation and have their attention focused in a common direction and in which scenery and scenic elements are used. (§ 27-255) Typical occupancies are theaters, playhouses and opera houses (§ 27-239-Table 3-2). F-1a occupancies shall be provided with an emergency control panel located in stage area equipped with an alarm system and intercom system connected to manager's office, the dressing rooms, and to supervisory central fire station. (§ 27-546(b)(10)). Emergency control panel in F-1a occupancies shall be manned in accordance with the requirements of the Fire Department. Since the fire control panel alarm system is a required system, a person holding a Certificate of Fitness shall be required. (§§ 27-546(b)(1) and 27-4265(g)).

(2) All occupancies classified by the Department of Buildings as F-3 or F-4 occupancies, having stages with scenery or scenic elements, regardless of seating capacity. F-3 occupancy is an occupancy in which persons assembled are physically active and do not have a common center of attention (§ 27-257). Typical occupancies are exhibition halls, galleries and museums. (§ 27-239-Table 3-2) F-4 occupancy is an occupancy in which persons assemble for dancing, eating or for a combination of dancing, eating, drinking, or entertainment. (§ 27-258) Typical occupancies are night clubs, cabarets, dance halls and banquet halls. (§ 27-239-Table 3-2) Section 27-549(a) of the Building (Administrative) Code provides that F-3 or F-4 occupancies having stages with scenery of scenic elements regardless of capacity shall comply with the provisions of the Building (Administrative) Code applicable to F-1a occupancies. As indicated in subdivision (d)(1) above emergency control panels with an alarm system connected to a control station is required in F-1a occupancies. A Certificate of Fitness is required for person manning such emergency control panel. Note: Theater management shall be required to record Certificate of Fitness information in the Theater Inspection Log Book. See § 31-04 of these rules.

(e) When non-required telegraphic alarm communication systems are installed, such systems shall be maintained in proper working order or shall be removed from the premises.

§ 41-01 Installation of Watchman's Time Detector Systems and [Watchman] Night Watch Service.

(a) [Watchman] Night watch. In every building used or occupied as a hotel, lodging house, public or private hospital or asylum there shall be employed by the owner or proprietor, or other person having the charge or management thereof, one or more [watchmen] night watch whose exclusive duty it shall be to visit every portion of such building at regular and frequent intervals, as hereafter provided under regulations established by the commissioner, for the purpose of detecting fire, or other danger, and giving timely warning thereof to the occupants of the building. There shall be provided a [watchman's] night watch clock or other device to be approved by the commissioner, by means of which the movements of the [watchman] night watch may be recorded. The commissioner may, however, in his or her discretion, accept an automatic fire alarm system in lieu of [watchmen] night watch and time detectors.

(b) Scope. This section shall apply to all hotels and lodging houses and single room occupancies as defined in the Multiple Dwelling Law, to all public and private hospitals and asylums having more than 15 rooms or accommodating more than 15 patients or inmates above the first or ground story, and to all Turkish or special treatment bath-houses where there are sleeping accommodations for more than 15 persons on the premises.

(c) [Watchman] Night watch service. [Watchman] Night watch service shall be performed every night. Patrol tours shall be made at least every two hours, beginning at 10 p.m. and continuing until the day staff of employees have assumed their duties. Persons employed as [watchmen] night watch shall be physically and mentally competent to perform required duties and shall not be assigned to any other work that will interfere or prevent them from making their proper tours. A proprietor, clerk or other employee may be permitted to serve as a [watchman] night watch in a lodging house, provided his or her duties are such as will not interfere with proper performance of tours.

(d) Time detectors, types.

(1) Central station system, approved by commissioner. Central station system shall consist of watch-boxes of approved type, used for no other purpose and located so watchman in making rounds must visit every portion of the building (see partial occupancy). Boxes shall be arranged so fire signals distinct from watch signals may be sent from each station installed. Before acceptance of any system operating through a central station, the company furnishing such service shall file with the Bureau of Fire Prevention a general description of the apparatus it proposes to install, together with sample boxes and such detailed information and drawings necessary to the complete understanding of the operation of the system. Diagrams showing means of delivering signals to patrol and fire headquarters shall also be furnished.

(2) Local or private station system, approved by Commissioner. Local or private station system. Approved single station clocks or a portable [watchman's] night watch clock may be used to record the movements of [watchmen] the night watch. Single station clock for each station, or portable clock, shall be so located as to compel watchmen to visit every portion of the building in making tours. (See partial occupancy). Records shall be made by embossing or perforating paper dials which shall be clearly legible. Dials shall be of sufficient size so that time at which record is made can be accurately determined. Both single stations and portable clocks shall be made so that watch record dials cannot be seen without opening case, also the opening or closing of the case will make distinctive record on the dial of such action. Keys for portable clocks shall be of a type difficult to duplicate and shall be of a pattern susceptible to variations tending to reduce the probability that a set of keys fitted for one clock will operate other clocks. Key stations shall be fixed so that they cannot be removed without giving evidence of the fact.

(e) Numbering of stations. Stations shall be numbered in the order that the [watchman] night watch is required to make his or her patrol. The location number and order of stations shall be subject to the approval of the Bureau of Fire Prevention.

(f) Reports of [watchman] night watch service. Central station system companies shall furnish such daily reports to the Bureau of Fire Prevention as may be required, of all buildings equipped by them with time detectors. Where either single station clocks or portable watchmen's clocks are used, records shall be maintained for at least thirty (30) days which shall be subject to inspection by the fire department. The insertion and removal of record dials from the time clock, indicating the hours of [watchman] night watch patrol shall be performed by owner, proprietor or supervisor only. [Watchmen] Night watch shall not be permitted to perform this function. Each dial shall be dated upon insertion and removal from the time clocks and initialled by person charged with this duty. Only one dial may be inserted in the clock at any one time.

(g) Exception. Where an automatic closed circuit, automatic thermostatic fire alarm system, or an automatic wet sprinkler system is installed to cover all portions of the building and are so arranged that the operation of either system will sound all of the gongs on the interior fire alarm system, a watchman's time detector system [of time detectors] shall not be required.

(h) Existing installations. Time detectors heretofore installed in compliance with orders of the commissioner may be accepted in lieu of the above requirements, provided they are properly maintained so as to render the service intended.

(i) Partial occupancy of building. Where any hotel, lodging house, hospital or asylum occupies only a portion of a building and such portion does not include all of the floors above and below ground levels, provisions shall be made whereby [watchmen] night watch shall cover all portions so occupied and, in addition, all portions which are at the same level above or below the floors occupied by the hotel, lodging house, hospital or asylum.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8310-01. Means of Egress in Pre-Existing Facilities

Open this section

(a) Scope. This section consolidates the Fire Prevention Code and former rules in effect on June 30, 2008, that are applicable to the design and installation of means of egress in pre-existing facilities.

(b) Definitions. [Reserved.]

(c) General Provisions. Pre-existing facilities with means of egress the design and installation of which would not be allowed or approved under the Fire Code, but that, pursuant to FC 102.3 and 3 RCNY § 102-01, may be continued with respect to such means of egress under the applicable laws, rules and regulations in effect prior to the Fire Code, shall continue to comply with the provisions of such laws, rules and regulations, including former Fire Department rule § 17-05, until such time as such facilities may be required to comply with the Fire Code and the rules with respect to the design and installation of such means of egress.

(d) Electro-Magnetic Door Holders.

(1) Former Fire Department Rule § 17-05

§ 17-05 Voluntary Installation of Electro-Magnetic Door Holders.

(a) Scope. To provide rules for the installation of electro-magnetic door holders or similar approved devices and to carry out the provisions of the Board of Standards and Appeals resolution as adopted under Cal. 109-63 S.A., printed in Bulletin No. 11, Vol. L, dated March 18, 1965.

(b) Definitions.

Approved. "Approved" shall mean by the Board of Standards and Appeals and bearing the label indicating such approval.

Electro-Magnetic Door Holders. "Electro-magnetic door holders" are a hold-open device for swinging fire doors to be utilized with approved self-closing door closers and automatic detection, or sensing devices, and/or approved interior fire alarm system, whichever applies.

Voluntary Installations. "Voluntary installations" are installations which are not required by any law, regulations, or violation.

. . . . . . . . . .

(d) Permissible installations.

(1) Electro-magnetic door holders may only be installed for double swinging fire and smoke barrier doors installed by order of the Fire Department to subdivide corridors for fire and smoke barriers.

(2) Where other doors are required to be closed, or to be self-closing by any provisions of the Administrative Code, the installation of such devices may only be made after the Board of Standards and Appeals has granted permission for specific locations.

(e) Electrical requirements.

(1) The electro-magnetic device shall be so interconnected that the operation of the interior fire alarm system shall de-energize the device thereby permitting the doors to close.

(2) The control system shall be of a closed circuit type.

(3) The control release panel which shall consist of relays, terminal plates, etc., of approved type mounted in an approved manner.

(4) A master relay shall be installed to lock the system in a non-operating condition until set manually.

(5) For every fifteen electro-magnetic door holders a separate contact or relay shall be installed.

(6) A trouble relay which will indicate any defects in the control system shall be provided. A trouble bell shall be installed which will indicate any defects and shall be actuated by the trouble relay. Such system shall be connected to the house side of the current transformer buss, through an approved cut-out without use of transformers, or rectifiers utilizing 120-208 volt service.

(7) A test means shall be provided to test the system and to operate the system manually.

(8) The equipment and installation shall be in conformance with interior fire alarm requirements and as stated in the Board of Standards and Appeals rules governing the installation of interior fire alarm systems (§ 811 of the B.S.A. rules).

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8311. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8311 at American Legal Publishing.

§ 8312. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8312 at American Legal Publishing.

§ 8313. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8313 at American Legal Publishing.

§ 8314. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8314 at American Legal Publishing.

§ 8315. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8315 at American Legal Publishing.

§ 8316. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8316 at American Legal Publishing.

§ 8317. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8317 at American Legal Publishing.

§ 8318. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8318 at American Legal Publishing.

§ 8319. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8319 at American Legal Publishing.

§ 8320. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8320 at American Legal Publishing.

§ 8321. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8321 at American Legal Publishing.

§ 8322-01. Pre-Existing Motor Fuel-Dispensing Facilities and Repair Garages

Open this section

This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read 3 RCNY § 8322-01 at American Legal Publishing.

(a) Scope. This section consolidates the Fire Prevention Code and Fire Department rules in effect on June 30, 2008, that are applicable to the design and installation of pre-existing motor fuel-dispensing facilities and repair garages.

(b) Definitions. [Reserved.]

(c) Facilities in Compliance With Former Fire Department Rules in Effect on June 30, 2008. Liquid motor fuel storage and dispensing facilities, marine liquid motor fuel-dispensing facilities, compressed natural gas motor fuel-dispensing facilities, and repair garages in compliance with former Fire Department Rules §§ 21-20, 21-21, 23-01, and/or 26-01, as applicable, in effect on June 30, 2008, are allowed and would be approved under the provisions of the Fire Code and the rules, and accordingly, such facilities shall be designed and installed in compliance with the requirements of FC Chapter 22 and the rules, except that where the distance of vent lines and fill and vapor recovery connections to lot lines in pre-existing liquid motor fuel-dispensing facilities and marine motor fuel-dispensing facilities is not in compliance with FC 3404.2.7.3.3 and 3404.2.7.5.2, compliance with such clearance distance requirements is not required until such time as such facilities are required to comply with the Fire Code and the rules with respect to such clearance distances.

(d) Pre-Existing Facilities. Liquid motor fuel-dispensing facilities, marine fuel-dispensing facilities and CNG motor fuel-dispensing facilities lawfully not in compliance with former Fire Department Rules §§ 21-20, 21-21 and/or 23-01, as applicable, in effect on June 30, 2008, shall be designed and installed in compliance with applicable laws, rules and regulations, as set forth in 3 RCNY § 102-01(c)(3). Pre-existing firehouses with diesel motor fuel dispensing systems shall continue to comply with the requirements set forth in former Fire Department Rule § 21-14 until such time as such facilities are required to comply with the Fire Code and the rules with respect to the design and installation of such motor fuel dispensing systems.

(e) Diesel Liquid Motor Fuel Dispensing Systems in Existing Firehouses.

(1) Former Fire Department Rule § 21-14

§ 21-14 Installation of Diesel Fuel Storage Systems in Existing Firehouses.

(a) Scope.

(1) No person or agency shall install diesel fuel oil storage equipment for use in existing firehouses except as provided in these rules.

(2) These rules shall not apply to installations in other than existing firehouses.

(3) All installations made under these rules shall be made by a licensed installer.

(4) For the purpose of these rules the term "licensed installer" shall be interpreted to mean a person licensed to install fuel oil systems or gasoline storage systems or a licensed plumber.

(b) General requirements.

(1) Diesel storage systems for existing firehouses shall consist of two (2) tanks of 275 gallons capacity or one (1) tank of 550 gallons capacity. See subdivision (m) of this section for schematic drawing of installation.

(2) Two (2) tank systems shall be equipped with valves to permit each tank to be isolated from the other.

(3) All installations shall conform with the provisions of Article 17 of Subchapter 14 of Chapter 1 of Title 27 of the Administrative Code insofar as they apply to the installation of storage tanks except as hereinafter provided for.

(c) Oil permitted. Oil stored in storage systems installed under these rules shall be diesel fuel oil as defined in § 27-4002(10)(b) of the Administrative Code of the City of New York.

(d) Material and construction of tanks.

(1) All tanks for the storage of diesel fuel oil shall be built of steel plates made by the open hearth or basic oxygen process. Such plates shall be free from physical imperfections, such as laminations, cracks, mill scale, etc. All steel must be new, in good condition and free from rust.

(2) All tanks shall be welded. Flanges or other pipe connections shall be sealed. Filler of any kind between plates is prohibited.

(3) Plate thickness.

(i) Tanks of 275 gallons capacity shall have a minimum thickness of shell and head plate No. 10 manufacturer's standard gauge (.134") steel plate.

(ii) Tanks of 550 gallons capacity shall be subject to the following requirements:

(A) Tanks 36" in diameter and less-at least 1/4" shell and 1/4" heads.

(B) Tanks 37" to 72" in diameter-at least 1/4" shell and 5/16" heads.

(4) Tanks shall be cylindrical, oval, elongated oval or round and shall have dished heads with a curvature the radius of which is not greater than the diameter of the tank. Dished heads shall be formed with an adequate cylindrical extension rim to provide a welding surface.

(5) At time of installation all storage tanks shall bear a permanently fixed plate, spot-welded or equivalent, bearing the name of tank manufacturer, the gauge of material and capacity of tank. All shop fabricated storage tanks shall be installed without structural alteration.

(6) All openings shall be through the top of the storage tanks except that tanks shall be provided with a 1" capped opening in the bottom for cleaning and protection against corrosion.

(7) Tanks shall be painted with two (2) coats black asphaltum and stenciled with the lettering "Diesel Fuel Only." Letters to be white and 4" high.

(e) Location of tanks.

(1) Storage tanks shall be installed in the cellar above ground. Bottom of tanks shall be 12" above slab mounted on substantial incombustible supports and located not less than seven feet (7') of clear unobstructed space measured horizontally from any furnace or source of exposed flame unless protected as provided in §§ 27-829(a)(2) or (3) of the Administrative Code and at least two feet (2') from any surface where the temperature exceeds 165 deg. F.

(2) Tanks shall be located as near as practicable below the location of the dispensing pump which shall be located on the apparatus floor.

(f) Piping.

(1) Materials.

(i) All piping shall be new, standard, full-weight black steel, properly marked and duly approved.

(ii) Fittings shall be malleable iron.

(2) Installation.

(i) Piping shall be run in a substantial and workmanlike manner. Exposed piping shall be protected against mechanical injury and shall be securely supported with rigid metal fasteners or hangers. Pitch shall be a minimum 1/2" per 10' to tanks.

(ii) Fill suction and vent line connections to tanks shall have swing joints.

(iii) All joints shall be made with Litharge and Glycerine or Board of Standards and Appeals approved pipe joint compound.

(3) Vent pipe.

(i) An open vent of steel, without trap and draining to the tank, shall be provided for each storage tank. The lower end of the vent pipe shall not extend through the top of the storage tank more than one inch (1"). Cross connection between vent pipe and fill pipe is prohibited.

(ii) Vent pipes may not be run into a common header.

(iii) Vent pipes shall not be less than one and one-quarter inches (1 1/4") in diameter.

(iv) Vent pipes shall be provided with an approved weatherproof hood having a free area of not less than the pipe size area and shall terminate not less than two feet (2') nor more than twelve feet (12') above the fill pipe terminal. Vent pipe terminal shall be visible from location of the fill pipe terminal.

(v) Each tank shall be equipped with a "Scully Vent Alarm" or equal and shall be audible from the location of the fill pipe terminal.

(4) Fill pipe.

(i) Fill pipe shall terminate outside the building. The fill pipe terminal shall be located on the building wall a minimum eighteen inches (18") and a maximum two feet (2') above grade and at least (2') from any building opening and five feet (5') from any subway grating at or below the level of the fill pipe terminal.

(ii) A common fill pipe and header shall be installed in two (2) tank systems. The area of a common header pipe shall be no smaller than the largest branch fill pipe. Where a common fill pipe and header is installed, a shut-off valve shall be installed at each tank. Valve shall be sealed open. See § 21-14(m) for schematic drawing of installation.

(iii) Fill pipe terminal shall be 2" or 3" left hand thread "Flagg Fill Pipe Terminal," Board of Standards and Appeals Calendar No. 345-35-SA or approved equal. The outer flange of the fill pipe terminal or the seal cap shall be provided with letters reading "Diesel Oil" and the calendar number under which the fill pipe terminal and the seal cap have been approved. Where there is a storage system of a volatile flammable oil and/or a storage system for fuel oil and a storage system for diesel fuel oil is to be used in the same premises, the terminal of the diesel oil fill pipe shall be provided with a left hand thread and the fill pipe fitting shall be a different size than the fill pipe(s) for the volatile flammable oil system and/or the fuel oil system. In lieu of the foregoing fill boxes may be of a type approved by the Board of Standards and Appeals and shall have cast in its cover an identifying name or symbol to differentiate between fuel oil for heating and diesel oil as motor fuel.

(iv) A porcelain enameled metal sign with 2" lettering reading "Diesel Oil" shall be permanently attached two feet (2') above the fill box on an adjacent wall.

(v) Where the top of the storage tank is above the fill pipe terminal, the fill pipe shall have connected to the top of the tank and be provided with a shut-off valve and swing check valve which shall be located at the fill pipe terminal, or the shut-off valve may be located inside the building at or below the level of the fill pipe terminal, in an accessible location.

(5) Suction lines.

(i) Suction lines shall be one and one-half inch (1 1/2") black steel.

(ii) Suction lines shall extend to within four inches (4") of the bottom of each tank.

(iii) In two (2) tank systems suction lines from each tank shall be run into a common header. Where a common suction line and header is installed, a check valve and a shut-off valve shall be installed at each tank. See § 21-14(m) for schematic drawing of installation.

(g) Valves and control of oil flow.

(1) All valves shall be brass gate type suitable for use with oil.

(2) In a two (2) tank system, a shut-off valve shall be installed in the suction line and in the fill line to each tank. Valves shall be sealed open. See § 21-14(m) for schematic drawing of installation.

(3) A check valve shall be installed in the suction line to each tank. See § 21-14(m) for schematic drawing of installation. All check valves shall be angle check double poppet, similar to Buckeye No. 464 or approved equal.

(h) Oil level indicating devices and test wells.

(1) Oil level indicating devices.

(i) Individual approved direct reading liquid level gauges shall be mounted on each tank calibrated in gallons to the rated capacity of each tank.

(ii) Oil level indicating devices shall be constructed of substantial materials so designed that there can be no leakage of oil or oil vapor.

(2) Test wells shall not be permitted. Unused tank openings shall be permanently sealed to prevent removal of plugs or cover

(i) Dispensing pump.

(1) Specifications.

(i) Pump shall be electric, not-computer, explosion proof type, model #U535 of the A.O. Smith Corporation (Board of Standards and Appeals Calendar No. 483-55-SA) or approved equal. All parts of pumps coming in contact with liquid shall be either galvanized or brass.

(ii) Pump shall be equipped with a discharge register and fitted with a tumbler lock equipped with two (2) keys.

(iii) Pump shall be equipped with a filter having a replaceable element (WIX or equivalent), fifteen feet (15') of hose and an automatic shut-off nozzle. Hose and nozzle shall be of a type approved by the Board of Standards and Appeals for use in dispensing diesel fuel.

(iv) Pump shall be equipped with a crank for manual operation in case of power failure.

(v) Pump to have words "Diesel Fuel" stenciled across the front panel in white letters 1" high.

(2) Location.

(i) Pump shall be located on the apparatus floor in a location near apparatus doors and convenient for supplying tanks of motor vehicles directly by means of dispensing hose.

(ii) Where practicable, pump shall be located above the storage tank which shall be located in the cellar.

(iii) Pump shall be mounted on a concrete pad 30" long by 18" wide by 12" high.

(j) Permits, plans and inspection of storage tanks and piping.

(1) Permits. No diesel fuel oil storage system installed under these rules shall be operated until it is inspected and approved by a representative of the fire commissioner except that temporary operation shall be permitted upon the filing by the licensed installer of a certified statement that such equipment and the installation conforms with the plan for the installation and with applicable provisions of law.

(2) Plans.

(i) Plans for the installation of diesel fuel oil storage tanks in existing firehouses shall be prepared by the Fire Department buildings unit and submitted to the Bureau of Fire Prevention for approval before installation of the system. All such plans shall show compliance with these rules.

(ii) Plans for the installation of diesel fuel storage tanks in existing firehouses being remodeled under a modernization program shall be prepared by the agency charged with the modernization and shall be submitted by such agency to the Bureau of Fire Prevention for approval before installation of the system. All such plans shall show compliance with these rules.

(k) Fire protection. Tanks, pumps and piping shall be maintained oil tight and kept clear at all times.

. . . . . . . . . .

(m) Schematic drawings.

(1) Schematic drawing for two (2) 275 gallon tanks.

(2) Schematic drawing for 550 gallon tank.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8323. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8323 at American Legal Publishing.

§ 8324. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8324 at American Legal Publishing.

§ 8325. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8325 at American Legal Publishing.

§ 8326. Reserved

Open this section

BetaNYC's copy has no text for this section. Read 3 RCNY § 8326 at American Legal Publishing.

§ 8327-01. Storage of Hazardous Materials in Pre-Existing Facilities

Open this section

This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read 3 RCNY § 8327-01 at American Legal Publishing.

(a) Scope. This section consolidates the New York City Fire Prevention Code and former Fire Department rules in effect on June 30, 2008, that are applicable to the design and installation of hazardous material installations in pre-existing facilities.

(b) Definitions. The following terms shall, for purposes of this section and as used elsewhere in 3 RCNY Chapter 83, have the meanings shown herein:

Retail drug store. A store or building used for the compounding and dispensing, usually in the form of physicians' prescriptions, or for the selling of small quantities of medicinal preparations, proprietary articles, drugs, chemicals, oils, volatile solvents and other substances which, alone or in combination with any other article or substance, are of a highly combustible, flammable or explosive nature. (Fire Prevention Code, former Administrative Code § 27-4002(35))

Technical establishment. A building or place where explosive, flammable or highly combustible substances are produced, used or stored for use, or where chemicals or other materials entering into the production of such substances are stored or used, excepting those establishments which are specifically treated under other classifications in Subchapters 1 through 27 of this chapter. (Fire Prevention Code, former Administrative Code § 27-4002(39))

Tenement house. A class A multiple dwelling as defined in subdivision four of section four of the multiple dwelling law. (Fire Prevention Code, former Administrative Code § 27-4002(40))

(c) General Provisions. Pre-existing facilities with hazardous material installations the design and installation of which would not be allowed or approved under the Fire Code, but which, pursuant to FC 102.3 and 3 RCNY § 102-01, may be continued with respect to such hazardous material installations under the applicable laws, rules and regulations in effect prior to the Fire Code, and shall continue to comply with the provisions of such laws, rules and regulations, including former Administrative Code §§ 27-4234, 27-4236, 27-4237, 27-4238, 27-4240, 27-4241, 27-4242 and 27-4246, and former Fire Department Rules §§ 10-01, 15-05 and 34-01, as applicable, until such time as such facilities may be required to comply with the Fire Code and the rules with respect to their design and installation.

(d) Technical Establishments.

(1) Former Administrative Code § 27-4234.

§ 27-4234 Restrictions. It shall be unlawful to store for use, or to use in any technical establishment any liquid acetylene, acetylide of copper or other metallic acetylide; fulminate of mercury, or any other fulminate or fulminating compound; nitroglycerine; chloride of nitrogen; amide or amine; blasting powder; smokeless powder; or gunpowder in any form; or any volatile product of petroleum (except rhigoline) having a boiling point lower than sixty degrees Fahrenheit.

(e) Wholesale Drug Stores and Drug and Chemical Supply Houses.

(1) Former Administrative Code § 27-4237.

§ 27-4237 Restrictions. No permit shall be issued for a wholesale drug store or drug and chemical supply house in any building:

1. Which is situated within fifty feet of the nearest wall of any building which is occupied as a school, hospital, theatre, or other place of public amusement or assembly;

2. Which is not equipped with a fire extinguishing system approved by the commissioner;

3. Where the building does not comply with the requirement of the building code regulating high hazard occupancies for buildings erected after the sixth day of December, nineteen hundred sixty-eight; or where a building or building section erected prior thereto is not fully equipped with an approved automatic sprinkler system.

(2) Former Administrative Code § 27-4238.

§ 27-4238 Laboratory.

a. Construction. The operation of compounding medicinal preparations, proprietary articles and similar materials, or analyzing or testing drugs, chemicals, medicinal preparations, proprietary articles and similar materials, when explosive or flammable substances are required, shall be conducted only in a room or part of the premises designed and constructed in accordance with all applicable provisions of the building code.

. . . . . . . . . .

(3) Former Administrative Code § 27-4240.

§ 27-4240 Prohibited materials. It shall be unlawful to manufacture or store in a wholesale drug store or drug and chemical supply house any of the following substances:

1. Acetylide of copper;

2. Amide or amine explosive;

3. Chloride of nitrogen;

4. Colored fire in any form;

5. Cymogene or any volatile product of petroleum (except rhigoline) or coal tar having a boiling point lower than sixty degrees Fahrenheit;

6. Flashlight powders;

7. Fulminate or any fulminating compound;

8. Guncotton;

9. Gunpowder in any form;

10. Liquid acetylene;

11. Nitro-glycerine, except in official U. S. pharmacopoeia solution, or in the form of pills, tablets, or granules containing not more than one-fiftieth of a grain each;

12. Picrates;

13. Potassium chlorate in admixture with organic substances or with phosphorus or sulphur; provided that this restriction shall not apply to the manufacture or storage of tablets of chlorate of potash intended for use solely for medicinal purposes;

14. Rubber shoddy.

(4) Former Administrative Code § 27-4241.

§ 27-4241 Quantities of supplies allowed. No permit shall be issued for the storage in a wholesale drug store or drug and chemical supply house of any of the following substances in quantities greater than those set forth in the following schedule:

1. Explosives. Amyl nitrate in bottles 25 pounds Amyl nitrate in pearls 100 gross Carbon bisulphide 50 pounds Collodions 100 pounds in all Gases, liquefied: Anhydrous ammonia 2 cylinders Carbon dioxide 2 cylinders Nitrous oxide 2 cylinders Oxygen 2 cylinders Sulphur dioxide 2 cylinders Nitroglycerine, one percent solution in alcohol 20 pounds Picric acid 25 pounds Soluble cotton 25 pounds in all 2. Volatile flammable liquids (insoluble). Benzine, benzole or naphthas of any kind 150 gallons in all Coal tar 1 barrel Coal tar oils (heavy) 10 barrels Crude petroleum 1 barrel Ethyl chloride and other ethers 200 pounds in all Ether, nitrous 100 pounds in five pound packages or less Ether, sulphuric 500 pounds Rhigoline 2 dozen one pound tins Varnishes, lacquers, etc. 275 gallons in all Wood creosote 5 barrels 3. Volatile flammable liquids (soluble). Acetone 1 barrel Alcohol, denatured 10 barrels Alcohol, ethyl 10 barrels Alcohol, methyl 10 barrels Aldehyde, ethyl 5 gallons 4. Non-volatile flammable liquids (insoluble). Amyl acetate 10 barrels Amyl alcohol 10 barrels Aniline oil 5 drums Cumol 5 barrels Essential oils 10,000 pounds in all Kerosene 1 barrel Nitrobenzole 5 drums Terebene 100 pounds Toluol 350 pounds Turpentine 10 barrels Xylol 100 pounds 5. Non-volatile flammable liquids (soluble). Glycerine 5,000 pounds 6. Combustible solids. Metallic magnesium 100 pounds Phosphorus 11 pounds Phosphorus, red 11 pounds Sulphur 25 barrels in all 7. Gums, resins, pitch, etc. Burgundy pitch 5,000 pounds Camphor 8,000 pounds Gum thus 5 barrels Naphthaline 50 barrels in all Pitch (coal tar pitch) 2 barrels Resins, balsams and other varnish gums 8,000 pounds in all Rosin 5 barrels Shellac 2,500 pounds Stockholm tar 1,000 pounds Tar, refined (wood) 10 barrels Venice turpentine 2,000 pounds 8. Combustible fibres and powders (vegetable). Cotton, absorbent 2,000 pounds Cotton batting 10 bales Excelsior 25 bales Flax 20 bales Jute 25 bales Lampblack 10 barrels Lycopodium 2,000 pounds Oakum 2 bales Pulverized charcoal 10 barrels Sawdust 15 bags Straw, packing 10 bales 9. Dangerously corrosive acids. Anhydrous acetic 500 pounds Carbolic 15,000 pounds Glacial acetic 2,000 pounds Hydrochloric 15 carboys Hydrofluoric 500 pounds Sulphuric 15 carboys 10. Acids. Chromic 100 pounds Iodic 5 pounds Nitric 3 carboys Nitric, fuming 25 pounds Periodic 2 pounds 11. Peroxides. Barium 2 casks Calcium 100 pounds Hydrogen, U.S.P. 5,000 pounds Other hydrogen peroxides, over three percent, not to exceed fifteen percent 500 pounds Potassium 10 pounds Sodium 25 pounds 12. Chlorates. Barium 500 pounds Other metallic 100 pounds in all Potassium 1,000 pounds Sodium 1,000 pounds 13. Perchlorates. Potassium 10 pounds Other metallic perchlorates 10 pounds in all 14. Permanganates. Potassium 1,000 pounds Sodium 100 pounds Other metallic permanganates 100 pounds in all 15. Nitrates. Barium 1,200 pounds Bismuth subnitrate 2,500 pounds Cobalt 1,000 pounds Copper 100 pounds Iron, ferric 200 pounds Mercury (mercuric) 100 pounds Mercury (mercurous) 10 pounds Potassium 2,000 pounds Silver 50 pounds Sodium 1,000 pounds Strontium 1,200 pounds Other metallic 500 pounds in all 16. Metallic oxides. Lead binoxide 25 pounds Lead (litharge) 1,200 pounds Lead (red) 500 pounds Mercury; yellow precipitate (mercurous) 200 pounds Mercury; red precipitate (mercuric) 100 pounds Silver 10 pounds 17. Substances made dangerous by contact with other substances. Calcium carbide 60 pounds Metallic potassium 5 pounds Metallic sodium 5 pounds All other metals of the alkalies or alkalone earths 5 pounds in all Phosphides 10 pounds Unslaked lime 2 barrels Zinc dust 100 pounds

The commissioner may, in his or her discretion and when no unusual hazard is presented thereby, authorize the storage of greater quantities than those set forth in the foregoing schedule, or the storage of other substances not specified therein.

(5) Former Administrative Code § 27-4242.

§ 27-4242 Storage.

. . . . . . . . . .

b. Liquids. The storage of acids or liquid chemicals which may cause explosions or combustion by flowing into, upon or among chemicals or other substances, shall be provided with safety catch basins or a similar device, so that, in case of the leakage of such acids or liquids, no danger to life or property will result. Carboys containing nitric acid shall be stored only in premises designed and constructed in accordance with all applicable provisions of the building code; and it shall be unlawful to permit sawdust, hay, excelsior, or any organic substance, or other acids or chemicals in close proximity to such carboys or stocks of nitric acid. A sufficient quantity of sand or infusorial earth shall be provided for absorbing all waste liquids from floors.

. . . . . . . . . .

(6) Former Fire Department Rule § 15-05.

§ 15-05 Fire Protection in Wholesale Drug and Chemical Supply Houses. The following shall be deemed to be in compliance with § 27-4237(3) of the Administrative Code of the City of New York:

. . . . . . . . . .

(d) Where such storage does not exceed 75 percent of the quantities allowed in § 27-4241, Administrative Code. For each 2,500 square feet of floor area or major portion thereof:

. . . . . . . . . .

Thermostatic alarm

(e) Where the storage exceeds 75 percent of the allowable quantity, an automatic sprinkler system is required.

(f) When the building exceeds four stories, an automatic sprinkler system is required.

(g) In any building where explosives and flammable substances are used or handled, if the area exceeds 5,000 square feet per floor an automatic sprinkler system is required.

(h) In any building exceeding 10,000 square feet per floor, an automatic sprinkler system is required.

(f) Retail Drug Stores.

(1) Former Administrative Code § 27-4246.

§ 27-4246 Quantities of supplies allowed. It shall be unlawful to store, sell or use in a retail drug store any of the following substances in quantities greater than those set forth in the following schedule:

1. Acids. Carbolic 100 pounds Hydrochloric 200 pounds Nitric 15 pounds Picric 1 ounce Sulphuric 200 pounds 2. Volatile flammable liquids. Acetone 5 pounds Amyl acetate 1 gallon Amyl alcohol 1 gallon Amyl nitrate 2 ounces in one ounce bottles six dozen pearls Ethyl alcohol 1 barrel Benzine, benzole and naphtha of any kind 5 gallons in four ounce bottles or pint tins Carbon bisulphide 3 pounds Collodion 5 pounds Denatured alcohol 1 barrel Ether, sulphuric 5 pounds Methyl alcohol 1 barrel Other ethers, in all 2 pounds Turpentine 1 barrel 3. Flammable liquids. Essential oils 100 pounds in all Glycerine 500 pounds Pine tar 10 pounds 4. Combustible solids. Aluminum (powder) 1 pound Balsams and resins 50 pounds in all Camphor 350 pounds Charcoal, powdered 10 pounds Lampblack 10 pounds Magnesium (powder) 8 ounces Magnesium (ribbon) 8 ounces Naphthalene 4 barrels Phosphorus, red 2 ounces Phosphorus, yellow 1 ounce Rosin 10 pounds Sulphur and brimstone 250 pounds in all 5. Combustible fibres. Cotton, absorbent 150 pounds in cartons Cotton, batts 10 pounds in closed boxes or other containers Cotton, loose 5 pounds in closed boxes or other containers Excelsior, hay and straw 2 bales (except in stores located in tenement houses) Lint 10 pounds in closed boxes or other containers Oakum 10 pounds in closed boxes or other containers 6. Oxidizers. Barium peroxide 1 pound Bismuth subnitrate 20 pounds Calcium peroxide 5 pounds Chromic acid 1 pound Lead oxide (red) 5 pounds Lime, unslaked 200 pounds in sealed metal cans All other metallic bichromates or chromates 50 pounds in all Mercuric oxide (red) 2 pounds Mercurous oxide 2 pounds Mercury nitrate 1 pound Phosphides 10 ounces in all Potassium bichromate 10 pounds Potassium chlorate 25 pounds in five pound containers or less Potassium nitrate 50 pounds Potassium perchlorate 1 ounce Potassium permanganate 5 pounds Silver nitrate 1 pound Silver oxide 1 ounce Sodium bichromate 10 pounds Sodium chlorate 5 pounds Sodium nitrate 25 pounds Sodium permanganate 1 pound

The commissioner may, in his or her discretion, when no extra hazard is permitted thereby, authorize the storage of larger quantities of substances than those set forth in the foregoing schedule, or of other explosives or flammable substances not specifically named therein.

(g) Non-Production Chemical Laboratories.

(1) Former Fire Department Rule § 10-01.

§ 10-01 Storage and Use of Chemicals, Acids and Gases in College, University, Hospital, Research and Commercial Laboratories.

(a) Definitions.

. . . . . . . . . .

Laboratory. Laboratory means a generic term denoting a building, space, equipment or operation, wherein testing, research or experimental work is conducted and shall include laboratories used for instructional purposes.

Laboratory Building. Laboratory building means a structure consisting wholly or principally of one or more laboratory units.

Laboratory Unit. Laboratory unit means an enclosed, fire rated space used for testing, research, experimental or educational purposes. Laboratory units may or may not include offices, lavoratories, and other contiguous rooms maintained for, or used by, laboratory personnel, and corridors within the units. It may contain one or more separate laboratory work areas.

Laboratory Work Area. Laboratory work area means a room or space within a laboratory unit for testing, analysis, research, instruction, or similar activities which involve the use of chemicals or gases. A work area may or may not be enclosed.

Exception: This section shall not apply to physical, electronic, instrument or similar laboratories which use small quantities (less than 32 oz. flammable liquids, 0.5 lb. oxidizing materials, and 0.15 cu.ft. water container capacity of flammable gases) for incidental purposes such as cleaning, maintenance or repair and these substances are not used directly in experimental chemical research work.

. . . . . . . . . .

Storage Cabinet. Storage cabinet means a cabinet for the storage of not more than 60 gallons of flammable liquid which is designed and constructed in accordance with "OSHA General Industry Standards-Flammable and Combustible Liquids".

Storage Room. Storage room means a room where chemicals or gases regulated by this directive are stored and not otherwise used or reacted.

Unstable (Reactive) Chemical. Unstable (reactive) chemical means a substance, other than one classified as an explosive or blasting agent, which will vigorously and energetically react, is potentially explosive, will polymerize or decompose instantaneously, undergo uncontrollable auto-reaction or can be exploded by heat, shock, pressure or combinations thereof. Examples are: organic peroxides, nitromethane, and ammonium nitrate.

. . . . . . . . . .

(d) Storage.

(1) Storage of chemicals for use in individual laboratory units shall be in accordance with Table I below. Any amounts in addition to the maxima set forth in Table I below shall be at the discretion of the Commissioner and shall be in storage cabinets.

(2) Determination of the fire rating of laboratory unit enclosures shall be in accordance with the criteria of the Building Code, except that, in partitions not required to have a fire rating under the provisions of that Code, fire dampers shall not be required to be installed in existing ducts penetrating existing laboratory partitions.

(3) Storage of volatile flammable oils shall be in accordance with Table I of this section.

Table I Maximum Laboratory Unit Storage Limits

Lab Type Fire Rating Fire Protection Flammable Liquids and Flammable Solids Oxidizing Materials Unstable Reactive I 2 Hours Sprinklers 30 gals 15 lbs 50 lbs 12 lbs II 1 Hour Sprinklers 25 gals 10 lbs 40 lbs 6 lbs III 2 Hours No Sprinklers 20 gals 6 lbs 30 lbs 3 lbs IV 1 Hour No Sprinklers 15 gals 3 lbs 20 lbs 2 lbs

. . . . . . . . . .

(5) Storage and use of flammable gases within laboratory units shall be in accordance with Table II below, except that no storage of flammable gases shall be allowed in any laboratory unit where there is not an on-going operation requiring their use. On-going operations shall allow storage of flammable gases sufficient to meet the operating requirements of the equipment in that laboratory unit plus an equal reserve.

Table II Storage of Flammable Gases

Area of Laboratory in square feet** up to 500 sq. ft. per additional 100 sq. ft. Maximum per Laboratory Unit Maximum Capacity 9.24 1.54 15.4

**Water container capacity

. . . . . . . . . .

(9) Storage rooms shall be of a minimum 2 hour rated construction and shall be provided with:

(i) a constant mechanical exhaust system to the exterior capable of providing at least six changes of air per hour;

(ii) a sill at the doorway (except that no sill shall be required at doorways of flammable gas storage rooms);

(iii) a sprinkler system providing at least one head per 90 sq. ft.

. . . . . . . . . .

(13) All fixed electrical equipment within cold rooms where flammable liquids or flammable gases are used shall be explosion proof in accordance with subdivision (f)(3) of this section. Cold rooms shall not be used for storage of principal stock of flammable gases or flammable liquids.

(e) Signs and warning placards.

(1) A sign prohibiting smoking shall be conspicuously posted at the exterior of entrances to storage and laboratory areas and within such areas.

(2) Signs with RED letters of minimum size two inches high by three-eighths inch stroke on a contrasting background shall be posted at entrances to areas:

(i) Where materials which react with water are stored or used.

(ii) Where flammable gases or explosives are stored or used.

(3) Warning placards in conformance with Federal, State and Local regulations shall be posted at entrances to areas:

(i) Where radioactive material is stored or used;

(ii) Where biohazardous material is stored or used;

(iii) Where poisonous gases are stored or used.

(4) The outside of each chemical laboratory unit door shall have a sign, as detailed below, or metal or other durable material, with RED letters on a white background which shall be located in the area of the mid-point of the height of the door.

(f) Fire prevention and protection.

(1) In laboratories and storage rooms which are sprinkled, the protection area per sprinkler head shall not exceed 90 sq. ft., except that the protection area per sprinkler head shall not exceed 100 sq. ft. where the system is hydraulically designed.

(2) In existing buildings, water supply to sprinkler systems may be taken off existing standpipes provided that the system is hydraulically designed.

(3) All electrical equipment in all flammable liquid and all flammable gas storage rooms shall conform with the requirements of the New York City Electrical Code set forth in § 27-3198(4), Administrative Code, irrespective of whether such room would be classified as a Class I Location by § 27-3197(1) of such code.

(4) Laboratory units and laboratory work areas shall be considered as unclassified electrically with respect to § 27-3197 of the Administrative Code.

(5) Fume hoods shall be provided and utilized in conformance with these requirements and those of such other agencies as have jurisdiction over operations and special storage conditions which give off noxious odors or flammable or poisonous vapors, or radioactive materials.

(6) Fume hoods shall be so vented that a minimum average face velocity of 100 feet per minute, with minimum face velocity at any point not less than 75 feet per minute, is provided.

(7) Fume hoods shall be located away from doors, windows that may be opened, principal traffic lanes or room air outlets or returns which may cause drafts sufficient to interfere with exhaust operations of fume hoods.

(8) Every fume hood used for handling perchloric acids, strong oxidizing agents or highly reactive chemicals shall be served by an independent duct.

(9) Common ducts may be permitted for fume hoods in the same laboratory unit. Hoods in different laboratory units shall not have their ducts combined. Hoods in common ducts must be so arranged or equipped that exhaust from one duct cannot be forced out through any other hood served by the common duct.

(10) Exhaust ducts shall have the minimum number of turns, bends or obstructions as is practical, and shall have adequate air movement in the duct for the number of hoods vented by that duct and sufficient to prevent any back up into the hood.

(11) Washdown provisions shall be provided for hoods and ducts in which perchloric acid is heated above ambient temperature and in which vapors are not trapped or scrubbed before entering the hood exhaust system.

(12) Exhaust fans for ducts shall, wherever possible, be located outside the building and as close as possible to the terminal so that negative pressure is maintained in ducts within the building.

(13) A system of explosion hazard control consisting of explosion prevention, explosion suppression, explosion venting, area ventilation, extinguishment system(s), barrier protection, separation and isolation, remove controlled apparatus or any combination thereof, shall be provided in laboratories or storage rooms where any of the following conditions occur:

(i) Storage of materials which in themselves are readily capable of detonation or of an explosive decomposition or explosive reaction at normal ambient temperature and pressure.

(ii) Use of materials which explode, violently decompose or produce rapid increases in pressure and temperature upon:

(A) Vacuum distillation;

(B) Being subjected to slight or moderate shock;

(C) Exposure to ultraviolet or visible light;

(D) Exposure to pressure or more than one atmosphere;

(E) Exposure to temperature in excess of 122(degrees)F. or 50(degrees)C.;

(F) Exposure to air;

(G) Increase in the concentration above which the substance is not longer stable;

(H) Standing (i.e. spontaneously).

(iii) Highly exothermic reactions which also involve rapid increases in pressure, such as certain polymerizations, oxidations, nitrations, peroxidations, hydrations, or organometallic reactions.

(iv) Use or formation of materials whose chemical structure or functional group indicate potential hazard, but whose properties have not been established. Examples would be triple bonds, epoxy radicals, nitro and [nitroso] nitrous compounds, and peroxides.

(14) The commissioner shall evaluate the method of explosion hazard control, on an individual basis, considering in each instance the following criteria:

(i) The nature and quantity of the constituent material(s);

(ii) The nature of the process;

(iii) The potential energy release;

(iv) Isolation of the equipment;

(v) The particular physical location and exposures.

. . . . . . . . . .

(2) Former Fire Department Rule § 34-01

§ 34-01 Storage and Use of Limited Quantities of Chemicals, Acids, and Flammables for Instruction Purposes in [Public High] Schools Through the Twelfth Grade .

(a) No liquefied chlorine may be stored in any school.

(b) No more than five (5) gallons of volatile flammable oils derived from petroleum, shale oil or coal tar should be stored at any one time.

(c) No more than twenty-five (25) pounds of potassium and/or sodium chlorate is permitted to be stored.

(d) No chemicals or substances as listed under §§ 27-4240 and 27-4234 of the Administrative Code should be stored in a school.

. . . . . . . . . .

(i) The storage of dangerous chemicals, volatile flammable oils and liquids shall be confined to metal cabinets vented at top and bottom. A cardholder should be provided for a visible record of the contents and maximum amount stored therein; also, a caution sign, if applicable to read: "In case of fire do not use water."

. . . . . . . . . .

Note: The foregoing rules shall be the basis for the issuance of Fire Department permits to schools throughout the City of New York.

(l) Listed below are the maximum quantities of combustibles and dangerous chemicals which may be stored in [public high] schools through the twelfth grade:

Explosives Picric Acid 1 lb. Carbon Bisulphide 10 lbs. Carbon Dioxide 1 lb. Anhydrous Ammonia 1 lb. Sulphur Dioxide 1 lb. Nitrous Oxide 1 lb. Oxygen 1 lb.

Volatile Flammable Liquids (Insoluble) Crude Petroleum 2 lbs. Benzine, Benzola or Naphthas of any kind 2 lbs. Ether, Sulphuric 10 lbs. Varnishes, Lacquers, etc. 2 lbs.

Volatile Flammable Liquids (Soluble) Acetone 1 lb. Alcohol, Denatured 5 gals. Aylcohol, Methyl 5 gals.

Non-Volatile Flammable Liquids (Insoluble) Amyl Acetate 2 lbs. Amyl Alcohol 2 lbs. Aniline Oil 1 lb.

Non-Volatile Flammable Liquids (Insoluble) Kerosene 2 lbs. Turpentine 1/2 gal. Tuluol 1 gal. Xylol 1 gal. Essential Oils 2 lbs.

Non-Volatile Flammable Liquids (Soluble) Glycerine 5 lbs.

Combustible Solids Phospherous 1/4 lb. Phospherous, Red 5 lbs. Sulphur 15 lbs. Metallic Magnesium 1 lb.

Gums, Resins, Pitch, Etc. Camphor 1 lb. Resin 11 lb. Venice Turpentine 1 lb. Naphthaline 1 lb. Shellac 1 lb.

Combustible Fibres and Powders (Vegetable) Pulverized Charcoal 5 lbs. Cotton, Absorbent 5 lbs. Lampblack 2 lbs. Lycopodium 1 lb.

Dangerously Corrosive Acids Glacial Acetic Acid 5 gals. Hydrofluoric Acid 1 lb. Hydrochloric Acid 12 gals. Sulphuric Acid 12 gals. Carbolic Acid 1 lb.

Acids Acid, Chromic 1 lb. Acid, Nitric 12 gals.

Peroxides Hydrogen Peroxide, U.S.P. 0 lbs. Sodium Peroxide 2 lbs. Barium Peroxide 2 lbs. Other Hydrogen Peroxides over 3 percent, not to exceed 15 percent 5 lbs.

Chlorates Potassium Chlorate 15 lbs.

Permanganates Potassium Permanganates 1 lb.

Nitrates Barium Nitrate 1 lb. Stontium Nitrate 1 lb. Cobalt Nitrate 1 lb. Copper Nitrate 1 lb. Iron Nitrate, Ferric Mercury Nitrate (mercuric) 1 lb. Mercury Nitrate (mercurous) lb. Potassium Nitrate 10 lbs. Silver Nitrate 5 lbs. Sodium Nitrate 15 lbs. Other Metallic Nitrates 5 lbs.

Metallic Oxides Lead Oxide (red) 5 lbs. Lead Oxide (Litharge) 10 lbs. Oxide of Mercury red precipitate (mercuric) 10 lbs. Oxide of Mercury; yellow precipitate (mercurous) 5 lbs.

Substances Made Dangerous by Contact with Other Substances Calcium Carbide 5 lbs. Metallic Potassium 1/2 lb. All other Metals of the Alkalies or Alkaline Earths 2 lbs. Metallic Sodium 1/2 lb. Zinc Dust 5 lbs. Slaked Lime 25 lbs.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8328-01. Storage of Aerosols in Pre-Existing Facilities

Open this section

(a) Scope. This section consolidates the New York City Fire Prevention Code and former Fire Department rules in effect on June 30, 2008, that are applicable to the design and installation of aerosol storage in pre-existing facilities.

(b) Definitions. The following terms shall, for purposes of this section and as used elsewhere in 3 RCNY Chapter 83, have the meanings shown herein:

Combustible pressurized product. A pressurized product that has a flashpoint at or above 100 degrees Fahrenheit and below 300 degrees Fahrenheit, or where a flame projection exceeds three (3) inches but not more than eighteen (18) inches at full valve opening when tested by a method described in the regulations of the United States Department of Transportation, as set forth in Title 49, Part 173 of the Code of Federal Regulations. (Former Fire Department rule § 32-01(b))

Extremely flammable pressurized product. A pressurized product that has a flashpoint below 20 degrees Fahrenheit and where a flashback (a flame extending back to the dispenser) is obtained at any degree of the valve opening when tested by a method described in the regulations of the United States Consumer Product Safety Commission, as set forth in Title 16, Part 1500 of the Code of Federal Regulations. (Former Fire Department rule § 32-01(b))

Flammable pressurized product. A pressurized product that has a flashpoint at or above 20 degrees Fahrenheit and below 100 degrees Fahrenheit, or where a flame projection exceeds eighteen (18) inches at full valve opening or a flashback (a flame extending back to the dispenser) is obtained at any degree of valve opening when tested by a method described in the regulations of the United States Consumer Product Safety Commission, as set forth in Title 16, Part 1500, of the Code of Federal Regulations, or the regulations of the United States Department of Transportation, as set forth in Title 49, Part 173 of the Code of Federal Regulations. (Former Fire Department rule § 32-01(b))

Pressurized product. The product in a pressurized container with a propellant that causes the product to be expelled from the container through a valve. This term includes all such products, irrespective of the ingredients of the product, the type of propellant, or form in which the product is dispensed. (Former Fire Department rule § 32-01(b))

(c) General Provisions. Pre-existing facilities with aerosol storage the design and installation of which would not be allowed or approved under the Fire Code, but which, pursuant to FC 102.3 and 3 RCNY § 102-01, may be continued with respect to such aerosol storage under the applicable laws, rules and regulations in effect prior to the Fire Code, shall continue to comply with the provisions of such laws, rules and regulations, including former Fire Department rule § 32-01, until such time as such facilities may be required to comply with the Fire Code and the rules with respect to their design and installation.

(d) Pressurized Products.

(1) Former Fire Department Rule § 32-01.

§ 32-01 Manufacture, Storage and Use of Pressurized Products.

. . . . . . . . . .

(e) Storage and use requirements.

. . . . . . . . . .

(2) Combustible, flammable or extremely flammable pressurized products in quantities exceeding the following amounts shall comply with the following additional storage requirements:

(i) Combustible, flammable or extremely flammable pressurized products in quantities exceeding a total of fifty (50) gallons but not more than a total of two hundred (200) gallons shall be stored in an area protected by an automatic fire sprinkler system, an area having natural ventilation, or an area which is vented to the outdoors by a duct having a cross-section of at least eight (8) inches.

(ii) Combustible, flammable or extremely flammable pressurized products in quantities exceeding a total of two hundred (200) gallons shall be stored as follows:

(A) in non-combustible (fireproof) buildings, in a fireproof storage room, unless the building is equipped with an automatic fire sprinkler system or other fire extinguishing system approved by the Department;

(B) in combustible (non-fireproof) buildings, in a fire-resistive storage room that is vented to the outdoors and that is equipped with an automatic fire sprinkler system or other extinguishing system approved by the Department.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)

§ 8329-01. Storage of Combustible Fibers in Pre-Existing Facilities

Open this section

(a) Scope. This section consolidates the New York City Fire Prevention Code and former Fire Department rules in effect on June 30, 2008, that are applicable to the design and installation of combustible fiber storage in pre-existing facilities.

(b) Definitions. [Reserved.]

(c) Facilities in Compliance With Former Fire Department Rules in Effect on June 30, 2008.

(1) Combustible fiber storage on waterfront structures. Combustible fiber storage on waterfront structures in compliance with former Fire Department rule § 30-01 in effect on June 30, 2008, is allowed and would be approved under the provisions of the Fire Code and the rules, and accordingly, such facilities shall be designed and installed in compliance with the requirements of FC 2906.

(Renumbered City Record 9/20/2023, eff. 10/20/2023)