NYC Administrative Code § 760.48
Section 760.48 – Revise Section 760.48(A) to read as follows:
760.48 Conductors of Different Circuits in Same Cable, Enclosure, or Raceway.
(A) NPLFA Circuits. Non-power limited fire alarm circuit conductors shall not be permitted to occupy the same cable, enclosure, or raceway with circuit conductors of other systems.
Section 760.48 – Revise Section 760.48(B) to read as follows:
(B) Fire Alarm with Power-Supply Circuits. Power supply and fire alarm circuit conductors shall be permitted in the same enclosure only where connected to the same equipment.