NYC Administrative Code Title 28, Chapter 3 Maintenance of Buildings, part 2 of 3
§ 28-309.1 to § 28-318.3.6: 100 sections.
§ 28-309.1. General
The energy and water use of city buildings and covered buildings shall be benchmarked in accordance with this article.
§ 28-309.2. Definitions
As used in this article, the following terms shall have the following meanings:
BENCHMARK. To input and submit to the benchmarking tool the total use of energy and water for a building for the previous calendar year and other descriptive information for such building as required by the benchmarking tool.
BENCHMARKING TOOL. The internet-based database system developed by the United States environmental protection agency, and any complementary interface designated by the office of long-term planning and sustainability, to track and assess the energy and water use of certain buildings relative to similar buildings.
CITY BUILDING. A building that is more than 10,000 gross square feet (929 m 2 ), as it appears in the records of the department of finance, that is owned by the city or for which the city regularly directly pays all of the annual energy bills, provided that two or more buildings on the same tax lot shall be deemed to be one building.
Exception: The term "city building" shall not include:
1. Any building owned by the city that participates in the tenant interim lease apartment purchase program; or
2. Any building owned by the city that (i) is 25,000 gross square feet (2323 m 2 ) or less, as it appears in the records of the department of finance, and (ii) participates in a program administered by the department of housing preservation and development.
COVERED BUILDING. As it appears in the records of the department of finance: (i) a building that exceeds 25,000 gross square feet (2323 m 2 ), (ii) two or more buildings on the same tax lot that together exceed 100,000 gross square feet (9290 m 2 ), (iii) two or more buildings held in the condominium form of ownership that are governed by the same board of managers and that together exceed 100,000 gross square feet (9290 m 2 ), or (iv) a city building.
Exceptions: The term "covered building" shall not include:
1. Any building owned by the city that participates in the tenant interim lease apartment purchase program.
2. Real property classified as class one pursuant to subdivision 1 of section 1802 of the real property tax law.
3. Real property, not more than three stories, consisting of a series of attached, detached or semi-detached dwellings, for which ownership and the responsibility for maintenance of the HVAC systems and hot water heating systems is held by each individual dwelling unit owner, and with no HVAC system or hot water heating system in the series serving more than two dwelling units, as certified by a registered design professional to the department.
DATA CENTER. A room or rooms used primarily to house high-density computing equipment, such as server racks, used for data storage and processing.
DWELLING UNIT. A single unit consisting of one or more habitable rooms, occupied or arranged to be occupied as a unit separate from all other units within a building, and used primarily for residential purposes and not primarily for professional or commercial purposes.
ENERGY. Electricity, natural gas, fuel oil and steam.
OWNER. The owner of record, provided that "owner" shall be deemed to include: (i) the net lessee in the case of a building subject to a net lease with a term of at least 49 years, inclusive of all renewal options, (ii) the board of managers in the case of a condominium, and (iii) the board of directors in the case of a cooperative apartment corporation.
TENANT. Any tenant, tenant-stockholder of a cooperative apartment corporation, condominium unit owner or other occupant.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.3. Benchmarking required for city buildings
No later than every May first, any city building shall be benchmarked by the agency or entity primarily responsible for the management of such building, in coordination with the department of citywide administrative services with respect to energy use, and with the New York city department of environmental protection with respect to water use. Benchmarking of water use shall not be required unless the building was equipped with automatic meter reading equipment by the New York city department of environmental protection for the entirety of the previous calendar year. The city shall maintain such documents as the department determines are necessary for the purpose of carrying out the provisions of this article.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.4. Benchmarking required for covered buildings other than city buildings
The owner of a covered building, other than a city building, shall annually benchmark such covered building no later than May first. Benchmarking of water use shall not be required unless the building was equipped with automatic meter reading equipment by the New York city department of environmental protection for the entirety of the previous calendar year. The owner or the owner's representative performing the benchmarking shall consult with the operating staff of the building, as appropriate. Information submitted to the benchmarking tool must be accurate and complete.
Exception: The first mandatory benchmarking for a covered building, other than a city building, that (i) does not exceed 50,000 gross square feet (4645 m 2 ), (ii) is not one of two or more buildings on the same tax lot that together exceed 100,000 gross square feet (9290 m 2 ) and (iii) is not one of two or more buildings held in the condominium form of ownership that are governed by the same board of managers and that together exceed 100,000 gross square feet (9290 m 2 ), shall be completed on or before May first of the first year that commences after the department determines and sets forth in a rule that the utility company providing energy to such buildings will, upon request of an owner, directly upload information necessary to benchmark such buildings.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.4.1. Obligation to report energy use for all utility accounts and addresses connected to the building
The owner shall submit information to the benchmarking tool for all utility accounts and addresses connected to the building, including those for separately metered tenant spaces. The owner shall obtain information for separately metered tenant spaces from the utility. If the utility does not have a program to provide such information, the owner shall make reasonable efforts to obtain such information from the tenant. Tenants shall have the obligation to provide such information.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016)
§ 28-309.4.2. Preservation of documents, inspection, and audit
An owner of a covered building shall maintain such records as the department determines are necessary for carrying out the purposes of this article, including but not limited to energy and water bills and reports or forms received from utilities and tenants. Where energy use within separately metered tenant spaces is omitted, records shall be maintained documenting the owner's efforts to obtain such information. All records shall be preserved for a period of three years, provided that the commissioner may consent to their destruction within that period or may require that such records be preserved longer than such period. At the request of the department, such records shall be made available for inspection and audit by the department at the place of business of the owner or at the offices of the department during normal business hours.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016)
§ 28-309.4.3. Violations
It shall be unlawful for the owner of a covered building to fail to benchmark pursuant to section 28-309.4. The commissioner shall classify such violation as a lesser violation. If, upon audit of a benchmarking report, the department finds that information submitted to the benchmarking tool was substantially inaccurate or incomplete, the department may reject the purported benchmarking and the owner shall be liable for a violation of section 28-309.4 as if no benchmarking had been performed.
Exception: Notwithstanding section 28-204.2, no civil penalty shall be imposed on the owner of a covered building for a violation of this section for such covered building if:
1. Such covered building (i) does not exceed 50,000 gross square feet (4645 m 2 ), (ii) is not two or more buildings on the same tax lot that together exceed 100,000 gross square feet (9290 m 2 ), (iii) is not two or more buildings held in the condominium form of ownership that are governed by the same board of managers and that together exceed 100,000 gross square feet (9290 m 2 ), and (iv) is not a city building;
2. Such owner requested, from the department or another agency designated pursuant to section 28-309.11, benchmarking assistance in connection with such building, and such request was made at least 60 days before the due date of the benchmarking report for which such violation was issued; and
3. Such owner corrects such violation within 60 days after the date of the notice of such violation.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.5. Direct upload
Information shall be directly uploaded to the benchmarking tool in accordance with the following:
§ 28-309.5.1. Direct upload by a utility company or other source
The office of long-term planning and sustainability shall encourage and facilitate any utility company or any other source authorized by the office of long-term planning and sustainability to upload directly to the benchmarking tool, as soon as practicable, information necessary to benchmark a building.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016)
§ 28-309.5.2. Direct upload by the department of environmental protection
The department of environmental protection shall upload directly to the benchmarking tool information on water use at all buildings that were equipped with automatic meter reading equipment by the department of environmental protection for the entirety of the previous calendar year and that are subject to the benchmarking requirements of this article.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.6. Suspension
The director of the office of long-term planning and sustainability may suspend all or part of the requirement to benchmark pursuant to this article upon a written finding that a technological deficiency in the benchmarking tool precludes compliance with this article. The director of the office of long-term planning and sustainability may lift all or part of any such suspension upon a written finding that such deficiency has been corrected. The office of long-term planning and sustainability shall notify the speaker of the city council, the department, the department of citywide administrative services, the department of environmental protection and the department of finance promptly upon issuing a suspension or lifting a suspension pursuant to this section.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.7. Notification and transmission of information
The department of finance shall:
1. Annually notify owners of covered buildings of their obligation to benchmark pursuant to section 28-309.4, provided that the failure of the department of finance to notify any such owner shall not affect the obligation of such owner to benchmark pursuant to such section.
2. Notify owners of covered buildings of any suspension or lifting of a suspension pursuant to section 28-309.6.
3. Make available to the department information regarding owners of covered buildings for which no benchmarking information was generated by the benchmarking tool.
§ 28-309.8. Disclosure
The department of finance shall make information generated by the benchmarking tool available to the public on the internet no later than September first of the year in which the covered buildings are benchmarked. Such information shall include, but need not be limited to: (i) the energy use intensity, (ii) the water use per gross square foot, (iii) where available, a rating or score that compares the energy and water use of the building to that of similar buildings, and (iv) a comparison of data across calendar years for any years such building was benchmarked.
Exception: Ratings or scores generated by the benchmarking tool for a covered building that contains a data center, television studio, and/or trading floor that together exceed ten percent of the gross square footage of any such building shall not be disclosed until the office of long-term planning and sustainability determines that the benchmarking tool can make adequate adjustments for such facilities. When the office of long-term planning and sustainability determines that the benchmarking tool can make such adjustments, it shall report such determination to the mayor and the speaker of the city council. Until such determination is made, the office of long-term planning and sustainability shall report biennially to the mayor and the speaker of the city council that the benchmarking tool is unable to make such adjustments.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.9. Report
No later than December 31 of each year, the office of long-term planning and sustainability shall prepare, submit to the mayor and the speaker of the city council, and post on the internet a report reviewing and evaluating the administration and enforcement of this article and analyzing data obtained from the benchmarking tool. Such report shall contain information regarding: (i) the energy and water efficiency of buildings in the city, (ii) the accuracy of benchmarked data and whether there is a need to train and/or certify individuals who benchmark, (iii) compliance with the requirements of this article, (iv) any administrative and legislative recommendations for strengthening the administration and enforcement of this article, (v) the effectiveness of the benchmarking tool in accounting for New York city conditions, including, but not limited to, high density occupancies, use of steam, large building size, and specific high-energy uses such as data centers, television studios, and trading floors, and (vi) such other information and analyses as the office of long-term planning and sustainability deems appropriate.
(Am. L.L. 2016/133, 10/31/2016, eff. 10/31/2016)
§ 28-309.10. Rules
The department, the department of finance and the office of long-term planning and sustainability may promulgate such rules as deemed necessary to carry out the provisions of this article.
§ 28-309.11. Benchmarking assistance
The department or another agency designated by the mayor shall establish a system to receive and respond to requests from owners for assistance with respect to fulfilling the benchmarking requirements of this section. Such assistance may include, but need not be limited to, trainings, the provision of reference guides, and a publicized telephone number and electronic mail address to receive direct questions. The annual notice required by section 28-309.7 shall notify covered building owners that such assistance is available and shall describe how such assistance can be obtained.
(L.L. 2016/133, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-309.12. Energy efficiency scores and energy efficiency grades
Energy efficiency scores and grades for buildings shall be obtained, assigned and disclosed in accordance with this section.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033.
§ 28-309.12.1. Definitions
As used in section 28-309.12, the following terms shall have the following meanings:
ENERGY EFFICIENCY GRADE. The term "energy efficiency grade" means, for a covered building, a grade based on an energy efficiency score assigned through the benchmarking tool in accordance with this section as follows:
1. If such score is equal to or greater than 85 the energy efficiency grade shall be A;
2. If such score is equal to or greater than 70 but less than 85, the energy efficiency grade shall be B;
3. If such score is equal to or greater than 55 but less than 70, the energy efficiency grade shall be C;
4. If such score is less than 55, the energy efficiency grade shall be D;
5. If the owner of such building has not complied with section 28-309.12.2, and such owner has had an opportunity to be heard with respect to such non-compliance, the energy efficiency grade shall be F; and
6. If, in accordance with the rules of the department, it is not feasible to obtain an energy efficiency score for such building or if such building is subject to the exception in section 28-309.8, the energy efficiency grade shall be N.
ENERGY EFFICIENCY SCORE. The term "energy efficiency score" means, for a building, the Energy Star rating for such building or a score that assesses the energy use of such building relative to similar buildings that is assigned through the benchmarking tool.
ENERGY STAR RATING. The rating that a building earns using the United States Environmental Protection Agency ENERGY STAR portfolio manager to compare building energy performance to similar buildings in similar climates.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018; Am. L.L. 2019/095, 5/19/2019, eff. 5/19/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033.
§ 28-309.12.2. Energy efficiency score and energy efficiency grade required
In 2020 and in each calendar year thereafter, an owner of a covered building shall use the benchmarking tool to provide an energy efficiency score for such building to the department in accordance with the rules of the department unless, in accordance with such rules, the building is a type of building for which it is not feasible to obtain an energy efficiency score. In each such year, the department shall issue an energy efficiency grade to the owner in accordance with such rules.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033.
§ 28-309.12.3. Display of energy efficiency score and energy efficiency grade
Within 30 days after the owner of a covered building obtains an energy efficiency grade, such owner shall post such grade and the energy efficiency score upon which such grade was based in a conspicuous location near each public entrance to such building, in a form and manner established by the department.
Exception: This section shall not apply to posting of the energy efficiency score of a building with an energy efficiency grade of N.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033 and L.L. 2021/126.
§ 28-309.12.4. Publication of energy efficiency grades and energy efficiency scores
For each building for which an energy efficiency grade or energy efficiency score is generated pursuant to this section, the department shall make information generated in connection with such grade and score publicly available online by no later than May 1 of the year following such generation.
Exception: This section shall not apply to information generated with respect to a building with an energy efficiency grade of N.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033 and L.L. 2021/126.
§ 28-309.12.5. Audits
The department shall, from time to time, audit information submitted for buildings in connection with energy efficiency grades and energy efficiency scores. Such audits shall occur at least annually and shall involve appropriate sample size of buildings, as determined by the department.
(L.L. 2018/033, 1/8/2018, eff. 1/8/2018)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2018/033.
§ 28-309.13. Outreach to building owners regarding making energy efficiency improvements
Each year, the department shall provide information regarding energy efficiency improvements to owners of buildings of all sizes, including buildings connected to gas lines. Such information shall also be posted on the department's website. The information shall include but not be limited to making energy efficiency improvements including the use of fossil fuel alternatives, the benefits of energy efficiency improvements, compliance with the New York city energy conservation code, and compliance with other laws aimed at reducing building energy use and carbon emissions.
(L.L. 2020/093, 9/27/2020, eff. 3/26/2021)
Title 28, Chapter 3, Article 310. Required Upgrade of Lighting Systems
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-310.1. General
Lighting systems in covered buildings shall be upgraded as provided for in this article.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-310.2. Definitions
As used in this article, the following terms shall have the following meanings:
COVERED BUILDING. As it appears in the records of the department of finance: (i) a building that exceeds 25,000 gross square feet (2323 m 2 ), (ii) two or more buildings on the same tax lot that together exceed 100,000 gross square feet (9290 m 2 ), or (iii) two or more buildings held in the condominium form of ownership that are governed by the same board of managers and that together exceed 100,000 gross square feet (9290 m 2 ).
Exceptions: The term "covered building" shall not include:
1. Real property classified as class one pursuant to subdivision 1 of section 1802 of the New York state real property tax law; or
2. Real property, not more than three stories, consisting of a series of attached, detached or semi-detached dwellings, for which ownership and the responsibility for maintenance of the HVAC systems and hot water heating systems is held by each individual dwelling unit owner, and with no HVAC system or hot water heating system in the series serving more than two dwelling units, as certified by a registered design professional to the department.
(Am. L.L. 2016/134, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088, L.L. 2021/126, and L.L. 2023/077.
§ 28-310.3. Upgrade of lighting systems of covered buildings required
No later than January 1, 2025 the lighting systems of covered buildings shall be in compliance with the standards for new systems set forth in the New York city energy conservation code and/or applicable standards referenced in such energy code. The owner of a covered building shall ensure that the upgrade of the lighting system of the entire covered building is completed on or prior to such date and shall file a report with the department, in accordance with the rules of the department, prepared by a registered design professional or a licensed master or special electrician certifying that such upgrade has been completed and that the work is in compliance with the technical standards of the New York city electrical code. The department may impose a fee for filing and review of such reports.
Exceptions:
1. An element of a lighting system that is in compliance with the standards of the New York city energy conservation code and/or applicable standards referenced in such code as in effect for new systems installed on or after July 1, 2010.
2. Lighting power densities in any space bounded by permanent floor-to-ceiling partitions and/or closable doors that are in compliance with the standards of the New York city energy conservation code and/or applicable standards referenced in such code as in effect for new systems installed on or after July 1, 2010.
3. The lighting system within dwelling units classified in occupancy group R-2 or R-3.
4. The lighting system within a space classified in occupancy group A-3 that is within a house of worship.
(Am. L.L. 2016/134, 10/31/2016, eff. 10/31/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088 and L.L. 2021/126.
Title 28, Chapter 3, Article 311. Installation of Electrical Sub-Meters In Tenant Spaces
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-311.1. General
Sub-meters shall be installed in covered buildings as provided in this article.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-311.2. Definitions
As used in this article, the following terms shall have the following meanings:
COVERED BUILDING. As it appears in the records of the department of finance: (i) a building that exceeds 25,000 gross square feet (2323 m 2 ), (ii) two or more buildings on the same tax lot that together exceed 100,000 gross square feet (9290 m 2 ), or (iii) two or more buildings held in the condominium form of ownership that are governed by the same board of managers and that together exceed 100,000 gross square feet (9290 m 2 ).
Exceptions: The term "covered building" shall not include:
1. Real property classified as class one pursuant to subdivision one of section 1802 of the real property tax law; or
2. Real property, not more than three stories, consisting of a series of attached, detached or semi-detached dwellings, for which ownership and the responsibility for maintenance of the HVAC systems and hot water heating systems is held by each individual dwelling unit owner, and with no HVAC system or hot water heating system in the series serving more than two dwelling units, as certified by a registered design professional to the department.
COVERED TENANT SPACE. (i) A tenant space larger than 5,000 gross square feet (465 m 2 ) on one or more floors of a covered building let or sublet to the same person, or (ii) a floor, of a covered building, larger than 5,000 gross square feet (465 m 2 ) consisting of tenant spaces let or sublet to two or more different persons.
Exception: The term "covered tenant space" shall not include dwelling units classified in occupancy group R-2 or R-3.
METER. A device installed by an electrical utility company or corporation that measures the flow of electricity supplied to a building or to a defined space within a building and used by the utility to bill consumers for electrical service.
SUB-METER. A device meeting the standards of the department or, where applicable, the public service commission, installed within a building's electrical distribution system that measures the flow of electricity within a defined space within the building and that may, but need not, be used for apportioning the cost of electricity among the building's tenants or subtenants.
TENANT SPACE. Space within a covered building that is let or sublet to another person by the owner or a lessee of such space.
(Am. L.L. 2016/132, 10/31/2016, eff. 10/31/2016)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-311.3. Sub-meters required for covered tenant spaces
On and after January 1, 2025, the electrical consumption of each covered tenant space shall be measured by one or more sub-meters. Sub-meters shall be installed in existing covered tenant spaces by the owner or the lessor of such space on or before January 1, 2025 and thereafter as new covered tenant spaces are created within the building. If the covered tenant space is a floor with multiple tenancies, each tenancy that is 5,000 gross square feet (465 m 2 ) or less shall (i) have a separate sub-meter, (ii) share a sub-meter with other tenant spaces on the floor, or (iii) share a sub-meter covering the entire floor.
Exception: Covered tenant space for which the electrical consumption within such space is measured by a meter dedicated exclusively to that space.
(Am. L.L. 2016/132, 10/31/2016, eff. 10/31/2016)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-311.4. Monthly statements
Each tenant or subtenant within a covered tenant space that has a sub-meter or sub-meters to measure electrical consumption shall be provided with a monthly statement showing the amount of electricity measured by the sub-meter for such tenant or subtenant during the month, and any amount charged to the tenant or subtenant for electricity. If the covered tenant space is a floor with multiple tenancies and the tenant's sub-meter covers other tenant spaces, the statement for such tenant shall show the electrical consumption for the area covered by the sub-meter and the percentage of that area that is leased by the tenant.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
§ 28-311.5. Reports
The owner of each covered building shall file a report in accordance with the rules of the department prepared by a registered design professional or a licensed master or special electrician certifying that sub-meters have been installed in all covered tenant spaces in such building as required by this article or that covered tenant spaces are subject to the exception set forth in section 28-311.3. The department may impose a fee for filing and processing such reports.
(Am. L.L. 2016/132, 10/31/2016, eff. 10/31/2016)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/088.
Title 28, Chapter 3, Article 312. Carbon Monoxide, Smoke and Natural Gas Alarms
(Am. L.L. 2016/157, 12/6/2016, eff. 5/1/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2011/075, L.L. 2013/112, and L.L. 2016/157.
§ 28-312.1. General
Required carbon monoxide, smoke and natural gas alarms shall comply with the provisions of this article.
(Am. L.L. 2016/157, 12/6/2016, eff. 5/1/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2013/112 and L.L. 2016/157.
§ 28-312.2. Periodic replacement of carbon monoxide alarms
Carbon monoxide alarms required pursuant to section 915.1 of the New York city building code or sections 27-981.1, 27-981.2 and 27-981.3 of the 1968 building code shall be replaced when the time elapsed since the installation of such alarm exceeds the manufacturer's suggested useful life of the alarm.
Exception: A carbon monoxide alarm installed before April 25, 2012 shall be replaced when the time elapsed since the installation of such alarm exceeds the manufacturer's suggested useful life of the alarm.
(Am. L.L. 2016/157, 12/6/2016, eff. 5/1/2019; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2011/075, L.L. 2013/112, L.L. 2016/157, and L.L. 2021/126.
§ 28-312.3. Audible notification of expiration of useful life of carbon monoxide alarms
All carbon monoxide alarms installed after April 25, 2012 shall comply with UL 2034 and be of a type that emits an audible notification at the expiration of the useful life of such alarm.
(Am. L.L. 2016/157, 12/6/2016, eff. 5/1/2019; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2011/075, L.L. 2013/112, L.L. 2016/157, and L.L. 2021/126.
§ 28-312.4. Periodic replacement of smoke alarms
Smoke alarms required pursuant to section 907.2 of the New York city building code or sections 27-978, 27-979, 27-980 and 27-981 of the 1968 building code shall be replaced when the time elapsed since the installation of such alarm exceeds the manufacturer's suggested useful life of the alarm.
Exception: A smoke alarm installed before April 1, 2014 and whose end of useful life is not known shall be replaced with an alarm that complies with section 28-312.5 by no later than April 1, 2021.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2013/112 and L.L. 2021/126.
§ 28-312.5. Audible notification of expiration of useful life of smoke alarms
All smoke alarms installed after April 1, 2014 shall comply with UL 217, shall employ a non-removable, non-replaceable battery that powers the alarm for a minimum of 10 years, and shall be of the type that emits an audible notification at the expiration of the useful life of the alarm.
(Am. L.L. 2016/157, 12/6/2016, eff. 5/1/2019; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2013/112, L.L. 2016/157, and L.L. 2021/126.
§ 28-312.6. Periodic replacement of natural gas alarms.*
* Editor's note: there are two sections designated as § 28-312.6.
Natural gas alarms required pursuant to section 908.10 of the New York city building code shall be replaced when the time elapsed since the installation of such alarm exceeds the manufacturer's suggested useful life of the alarm.
(L.L. 2016/157, 12/6/2016, eff. 5/1/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2016/157.
§ 28-312.6. Location of smoke alarms and smoke detectors.*
* Editor's note: there are two sections designated as § 28-312.6.
On or after January 1, 2021, smoke alarms and smoke detectors installed or replaced in group R occupancies shall be installed in accordance with section 907.2.11.6 of the New York city building code.
(L.L. 2018/113, 6/9/2018, eff. 6/9/2018; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126 and L.L. 2023/077.
§ 28-312.7. Audible notification of expiration of useful life of natural gas alarms
All natural gas alarms installed after the effective date of the local law that added this section 28-312.7 shall comply with a standard established or adopted by department rule and shall be of the type that emits an audible notification at the expiration of the useful life of the alarm.
(L.L. 2016/157, 12/6/2016, eff. 5/1/2019)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2016/157.
§ 28-313.1. Retroactive requirement for directional signage at building entrances
The provisions of section 1111.2 of the New York city building code requiring directional signage to be posted at inaccessible building entrances indicating the route to the nearest accessible entrance shall apply retroactively to all buildings that have such accessible entrances. Such directional signage shall be maintained in good condition.
Exception: Directional signage posted at building entrances in compliance with the Americans with Disabilities Act of 1990 shall be deemed to be in compliance with section 1111.2 of the New York city building code.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-313.2. Retroactive requirement for accessible building entrances
The provisions of item 4 of section 1111.1 of the New York city building code requiring signage to be posted at accessible entrances where an inaccessible building entrance exists shall apply retroactively to all buildings that have such accessible entrances.
Exception: Accessible entrance signs that are posted at building entrances in compliance with the Americans with Disabilities Act of 1990 shall be deemed to be in compliance with section 1111.1 of the New York city building code subject to the inclusion on or adjacent to such signage of a contact telephone number or instructions to gain access if an otherwise accessible building entrance is subject to locking.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-313.3. Retroactive requirement for signage and safety requirements for portable ramps at inaccessible building entrances where such ramps are permissible
The provisions of item 7 of section 1111.3 of the New York city building code requiring that signage stating a portable ramp is available, if provided by the building, and the phone number to request such ramp, be posted at inaccessible building entrances shall apply retroactively to all prior code buildings that have such portable ramps where use of such a ramp is permissible. The use of a portable ramp by any building must comply with all applicable laws, and must comply with Section 405 (Ramps) of ICC A117.1 except to the extent the commissioner has waived a requirement pursuant to section 28-313.3.1. All signage posted pursuant to this section shall comply with Section 1111 of the New York city building code and be maintained in good condition. Nothing in this section shall be construed to authorize the provision of a portable ramp where such provision would not otherwise be lawful.
(L.L. 2019/122, 6/29/2019, eff. 1/1/2020; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2019/122 and L.L. 2021/126.
§ 28-313.3.1. Waiver of requirements related to portable ramps at inaccessible building entrances where such ramps are permissible
The commissioner may waive the requirement of section 28-313.3 that all portable ramps used by prior code buildings must comply with Section 405 (Ramps) of ICC A117.1, provided, however, that such waiver would not significantly adversely affect safety and that equally safe and proper alternatives are prescribed and, further, that such waiver is based upon a specific finding by the commissioner that strict compliance with the requirement:
1. Would create an undue economic burden;
2. Would not achieve its intended objective;
3. Would be physically or legally impossible;
4. Would be unnecessary in light of alternatives which ensure the achievement of the intended objective or which, without a loss in the level of safety, achieve the intended objective more efficiently, effectively or economically; or
5. Would entail a change so slight as to produce a negligible additional benefit.
(L.L. 2019/122, 6/29/2019, eff. 1/1/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2019/122.
§ 28-313.3.2. Waiver application process
Each application for a waiver under section 28-313.3.1 shall be made to the commissioner in writing, setting forth each requirement of Section 405 (Ramps) of ICC A117.1 sought to be waived and the specific reason or reasons therefore. The commissioner shall determine, under all of the circumstances presented by such application, which of such requirements may appropriately be waived. The commissioner shall render such determination in a writing, which shall set forth in detail the commissioner's findings and conclusions with respect to each requirement sought to be waived. A copy of such written determination shall be forwarded to the applicant. Such written determination shall be filed with the department and shall be available for public inspection.
(L.L. 2019/122, 6/29/2019, eff. 1/1/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2019/122.
§ 28-313.3.3. Waiver recommendation
The mayor's office for people with disabilities, or its successor agency shall be consulted by and shall advise the commissioner concerning each application for a waiver under section 28-313.3.1.
(L.L. 2019/122, 6/29/2019, eff. 1/1/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2019/122.
Title 28, Chapter 3, Article 314. Reserved
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.1. General
Buildings must be in compliance with the retroactive requirements of the provisions of this code. Such requirements are listed in this article along with the dates by which compliance must be achieved. The retroactive requirements of the 1968 building code continue in effect under this code in accordance with section 28-102.4.1 of this code. The dates for compliance with the retroactive requirements of the 1968 building code are as set forth in the applicable provisions of such 1968 building code. Failure to comply with a retroactive requirement of this code or of the 1968 building code by the date specified for such compliance is a violation of this code.
§ 28-315.2. Fire protection systems
The work specified in this section to enhance the fire protection systems of buildings shall be completed by the dates specified herein.
§ 28-315.2.1. Painting of certain exposed portions of sprinkler systems
The painting of exposed risers, cross connections and handles of valves of sprinkler systems in accordance with the retroactive requirements of section 903.6.3 of the New York city building code shall be completed by June 2, 2010 and certification of such painting shall be maintained in accordance with section 903.6.5 of such code.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.2.2. Painting of certain exposed portions of standpipe systems
The painting of exposed portions of standpipe systems and handles of valves serving such systems in accordance with the retroactive requirements of section 905.11.3 of the New York city building code shall be completed by June 2, 2010 and certification of such painting shall be maintained in accordance with section 905.11.6 of such code.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.2.3. Animal service facilities
By December 31, 2016, animal service facilities shall comply with the retroactive requirements of section 903.2.2.2 of the New York city building code and owners of such facilities shall file with the department a report certifying either that sprinklers have been installed or that the facility is in compliance with one of the exceptions set forth in such section.
(L.L. 2015/078, 9/2/2015 , eff. 12/31/2015 )
§ 28-315.2.4. Natural gas alarms
On or before January 1, 2027, natural gas alarms shall be provided and installed in accordance with section 908.13 of the New York city building code.
(L.L. 2016/157, 12/6/2016, eff. 5/1/2019; Am. L.L. 2025/102, 7/30/2025, eff. 7/30/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2016/157.
§ 28-315.2.4.1. Market availability
No later than July 1, 2026, the commissioner shall submit to the mayor and the speaker of the council a determination of the market availability of battery-powered natural gas alarms. Such determination shall indicate whether the department has identified 4 or more distinct manufacturers of battery-powered natural gas alarms that comply with the requirements of section 908.13. If such determination indicates less than 4 such manufacturers, the commissioner shall by rule extend the date by which such alarms must be installed in accordance with section 28-315.2.4 to January 1, 2029.
(L.L. 2025/102, 7/30/2025, eff. 7/30/2025)
§ 28-315.3. Sustainability
The work specified in this section to enhance the sustainability of buildings must be completed by the dates specified herein.
§ 28-315.3.1. Lighting systems
By January 1, 2025, the lighting systems of certain buildings shall be in compliance with article 310 of this chapter and the owners of such buildings shall file a report in accordance with the rules of the department, prepared by a registered design professional or a licensed master or special electrician, certifying compliance with such section and compliance with the technical standards of the New York city electrical code. The department may impose a fee for filing and reviewing such reports.
(Am. L.L. 2016/134, 10/31/2016, eff. 10/31/2016)
§ 28-315.3.2. Electrical sub-meters
By January 1, 2025, the installation of electrical sub-meters in tenant spaces in certain buildings in accordance with article 311 of this chapter shall be completed and the owners of such buildings shall file a report in accordance with the rules of the department, prepared by a registered design professional or a licensed master or special electrician, certifying compliance with such section. The department may impose a fee for filing and reviewing such reports.
(Am. L.L. 2016/132, 10/31/2016, eff. 10/31/2016)
Editor's note: L.L. 2016/132 numbered this section as § 28-315.3.1; renumbered at the discretion of the editor.
§ 28-315.4. Elevator safety
The work specified in this section to improve the safety of existing elevators shall be completed by the dates specified herein.
§ 28-315.4.1. Compliance with ASME A17.3 of 2015
Existing elevators and escalators shall, at a minimum, comply with ASME A17.3 of 2015, as modified by Chapter K3 of Appendix K of the New York city building code.
Exceptions:
1. Spaces below hoistways. Spaces below hoistways shall be protected in accordance with Section 2.5 of Chapter K3 of such appendix by December 14, 2010.
2. Car doors and gates. Car doors and gates shall be in compliance with Section 3.4.2 of Chapter K3 of such appendix by December 14, 2012.
3. Car illumination. Car illumination shall be in compliance with Section 3.4.5 of Chapter K3 of such appendix by December 14, 2010.
4. Traction elevators. Traction elevators with single plunger brakes shall be in compliance with Section 3.8.4.1 of Chapter K3 of such appendix by January 1, 2027.
5. Electrical protective devices. Electrical protective devices shall be in compliance with Section 3.10.4 of Chapter K3 of such appendix by December 14, 2010.
6. Automatic passenger and freight elevators. Automatic passenger and freight elevators shall be in compliance with Section 3.10.12 of Chapter K3 of such appendix by January 1, 2020.
7. Hydraulic elevators. Hydraulic elevators shall be in compliance with Section 4.3.3 of Chapter K3 of such appendix by December 14, 2014.
8. Escalator skirt obstruction devices. Escalator skirt obstruction devices shall be in compliance with Section 5.3.7 of Chapter K3 of such appendix by January 1, 2014.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.5. Fuel gas systems
The work specified in this section to enhance the safety of fuel gas systems shall be completed by the dates specified herein.
§ 28-315.5.1. Outside gas shut-off
Existing gas services shall be provided with an outside emergency shutoff device acceptable to the commissioner and the fire commissioner in accordance with the retroactive requirements of item 1 of section E.6 of Appendix E of the New York city fuel gas code. Installation of such a device shall be completed no later than January 1, 2010.
Exception: For R-3 occupancies, the installation of such a device shall be completed no later than January 1, 2020.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.6. Accessibility
The work specified in this section to enhance the accessibility of buildings shall be completed by the dates specified herein.
§ 28-315.6.1. Directional signage at inaccessible building entrances
The posting of directional signage at inaccessible building entrances in accordance with the retroactive requirements of section 28-313.1 of this code shall be completed on or before August 1, 2013.
§ 28-315.6.2. Signage at accessible building entrances
The posting of signage at accessible building entrances in accordance with the retroactive requirements of section 28-313.2 of this code shall be completed on or before August 1, 2013.
§ 28-315.6.3. Signage for portable ramps at inaccessible building entrances where such ramps are permissible
The posting of signage for portable ramps at inaccessible building entrances where such a ramp is permissible in accordance with the requirements of item 7 of Section 1111.3 of the New York city building code shall be completed on or before March 1, 2020.
(L.L. 2019/122, 6/29/2019, eff. 1/1/2020; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022; Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2019/122, L.L. 2021/126, and L.L. 2023/077.
§ 28-315.7. Building security
The work specified in this section to enhance building security shall be completed by the dates specified herein.
§ 28-315.7.1. Security grilles on buildings in occupancy groups B or M. [Repealed]
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022; repealed L.L. 2026/123, 7/30/2026, eff. 7/30/2026)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.8. Resiliency
The work specified in this section to enhance building resiliency shall be completed by the dates specified herein.
§ 28-315.8.1. Emergency source of water for residential occupancies
As of December 31, 2022, existing buildings greater than five stories in occupancy groups I-1, R-1, R-2, and R-3 that supply potable water from the public water main to occupants with the assistance of pumps, other than pumps connected to an emergency or a standby power system that complies with the requirements of chapter 27 of the New York city building code, shall be equipped with additional fixtures capable of supplying potable water to occupants utilizing only the available pressure from the public water main in compliance with section 614 of the New York city plumbing code.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.8.2. Connections for temporary external generators
For the following buildings, the provision of connections for temporary external generators in accordance with the retroactive requirements of section G312.2 of appendix G of the New York city building code shall be completed by January 1, 2033, and a report detailing compliance with such requirements shall be filed with the department in accordance with section G312.2.2 of such appendix by such date:
1. Buildings whose main use or dominant occupancy is group I-1 and that are located in a special flood hazard area, as such term is defined in appendix G of the New York city building code;
2. Buildings whose main use or dominant occupancy is an adult home, enriched housing, community residence or intermediate care facility classified as occupancy group R pursuant to an exception to section 308.3.1 or 308.3.2 of the New York city building code and that are located in a special flood hazard area, as such term is defined in appendix G of the New York city building code;
3. Buildings whose main use or dominant occupancy is group I-2 hospital and that are located in a special flood hazard area or shaded X-Zone, as such terms are defined in appendix G of the New York city building code;
4. Buildings whose main use or dominant occupancy is group I-2 nursing home and that are located in a special flood hazard area, as such term is defined in appendix G of the New York city building code; and
5. Buildings whose main use or dominant occupancy is group I-2, other than hospitals and nursing homes, and that are located in a special flood hazard area, as such term is defined in appendix G of the New York city building code.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.8.2.1. Modification to the flood hazard area
Where the special flood hazard area or shaded X-Zone, as established in appendix G of the New York city building code, is modified on or after the effective date of this section, any building identified in section 28-315.8.2 of this code and newly identified as being within such modified special flood hazard area or shaded X-Zone shall, no later than 20 years following the adoption of such modification, comply with the retroactive requirements of section G312.2 of appendix G of the New York city building code. The owner of such building shall, no later than 20 years following the adoption of such modification, file with the department a report detailing compliance with such requirements in accordance with section G312.2.2 of such appendix.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.8.3. Connections for temporary external boilers and chillers
For buildings whose main use or dominant occupancy is group I-2 hospital and that are located in a flood hazard area, as such term is defined in appendix G of the New York city building code, the provision of connections for temporary external boilers and chillers in accordance with the retroactive requirements of section G312.3 of appendix G of the New York city building code shall be completed by January 1, 2033, and a report detailing compliance with such requirements shall be filed with the department in accordance with section G312.3.2 of such appendix by such date.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.8.3.1. Modification to the flood hazard area
Where the special flood hazard area or shaded X-Zone, as established in appendix G of the New York city building code, is modified on or after the effective date of this section, any building whose main use or dominant occupancy is group I-2 hospital and that is newly identified as being within such modified special flood hazard area or shaded X-Zone shall, no later than 20 years following the adoption of such modification, comply with the retroactive requirements of section G312.3 of appendix G of the New York city building code. The owner of such building shall, no later than 20 years following the adoption of such modification, file with the department a report detailing compliance with such requirements in accordance with section G312.3.2 of such appendix.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.9. Single-occupant toilet rooms
Notwithstanding any other provision of law or rule requiring separate facilities for each sex, on and after January 1, 2017, all single-occupant toilet rooms shall be made available for use by persons of any sex in accordance with section 403.2.2 of the New York city plumbing code. Nothing in this section shall be construed to require physical alteration of a single-occupant toilet room except for the posting and maintenance of appropriate signage in accordance with section 403.4 such code.
(L.L. 2016/079, 6/28/2016, eff. 10/26/2016; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.10. Self-closing doors
All doors providing access to interior corridors or stairs in occupancy groups R-1 and R-2 shall be equipped with a device that will ensure the door, when opened and released, returns to the closed position and self-latches shut by July 31, 2021.
(L.L. 2018/111, 6/9/2018, eff. 6/9/2018; Am. L.L. 2022/063, 6/1/2022, eff. 7/16/2022 and 11/7/2022)
§ 28-315.11. Buildings that are equipped with a fire alarm system and that contain Group A-1, A-2, A-3, Group B or Group M occupancies
By July 1, 2021, existing buildings equipped with a fire alarm system and that contain group A-1, A-2 or A-3, Group B or Group M occupancies shall comply with the retroactive requirements of section 915.1.2.1 of the New York city building code.
(L.L. 2018/191, 12/1/2018, eff. 8/28/2019; L.L. 2021/013, 1/17/2021, retro. eff. 1/1/2021; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-315.12. Electric vehicle supply equipment (EVSE)
Parking garages and open parking lots shall be capable of supporting and equipped with EVSE as set forth in sections 28-315.12.1 and 28-315.12.2, and in accordance with the New York city electrical code.
(L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/055.
§ 28-315.12.1. EVSE requirements for department of consumer and worker protecton licensed parking garages and open parking lots
Parking garages and open parking lots with 10 or more parking spaces that are required to be licensed by the department of consumer and worker protection or successor agency in accordance with section 20-321 shall ensure that no less than 20 percent of parking spaces in existing parking garages and open parking lots shall be equipped with level 2 charging stations and 40 percent of parking spaces be capable of supporting level 2 charging stations by January 1, 2035. For purposes of compliance with this section, the installation of 1 direct current fast charging station shall be considered to be the equivalent of 10 level 2 charging stations, provided the installation of direct current fast charging stations shall not be used to satisfy more than 50 percent of the level 2 charging stations required. Owners of such parking garages and open parking lots shall submit a report of compliance with this section to the department within 60 days after final inspection of such installation in a form and manner specified by the department.
Exceptions. The commissioner may grant an adjustment to or waiver of any of the provisions of this section with respect to a parking garage or open parking lot where:
1. The project costs exceed the baseline costs for EVSE installation as determined by the department in accordance with recommendations of the department of transportation, and the owner is complying with the requirements of this section to the maximum extent practicable and has availed itself of all available federal, state, city, private, and utility incentive programs related to EVSE for which it reasonably could participate;
2. For a parking garage or open parking lot that utilizes equipment that enables vehicles to be parked vertically and the owner demonstrates that such vertical parking would make the use of EVSE infeasible, an adjustment may be granted so that only spaces where EVSE could feasibly be used will be required to do so to the maximum extent practicable to meet the requirements under this section;
3. The owner demonstrates that compliance with this section would compromise the structural integrity of the parking structure; or
4. The owner demonstrates that compliance with this section is not feasible for other reasons as established by the department by rule.
(L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/055.
§ 28-315.12.2. EVSE requirements for unlicensed parking garages and open parking lots
Parking garages and open parking lots with 10 or more spaces that are not required to be licensed by the department of consumer and worker protection or successor agency shall be equipped with EVSE and be capable of supporting EVSE in accordance with a schedule established by the department by rule. Such schedule shall be based on recommendations of the department of transportation pursuant to the report published by such department pursuant to section 5 of the local law that added this section and may include such exceptions as the commissioner determines to be appropriate or necessary, including the exceptions set forth in section 28-315.12.1 and any exceptions determined by the commissioner to be appropriate pursuant to the report required by section 5 of the local law that added this section. No later than January 1, 2027, the department shall promulgate rules as required to implement this section.
(L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/055.
§ 28-315.12.3. Annual EVSE installation report
No later than March 31, 2027, and no later than March 31 of every year thereafter, the department shall submit a report to the mayor and the speaker of the council on compliance with this section. Such report shall include, but not be limited to, data on the number of parking garages and open parking lots complying with the requirements of this section, along with the number of EVSE installed for the preceding calendar year.
(L.L. 2024/055, 4/6/2024, eff. 12/21/2025)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2024/055.
§ 28-316.1. Required insulation of certain concealed piping exposed during alteration or repair
Where concealed existing piping is exposed in the course of the alteration or repair of a building, the owner of the building shall provide for the insulation of the exposed piping. The exposed piping shall be insulated to the extent required by the New York city energy conservation code for newly installed pipe of the same specifications and serving the same function as the exposed pipe. The entire exposed length of the piping shall be insulated as well as any further length of concealed pipe that can be directly accessed through openings made in the course of such alteration or repair.
Exceptions:
1. Exposed pipe with 1 inch (25 mm) thick continuous coverage of existing insulation in good condition.
2. Where the length of concealed pipe which may be directly accessed through openings made in the course of such alteration or repair is less than three feet (914 mm).
3. Where there is not sufficient space to insulate pipes to the extent required by the New York city energy conservation code due to conflicts with existing construction, pipes shall be insulated to the extent that space allows.
(Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/012 and L.L. 2021/126.
§ 28-317.1. General
All owners of cooling towers shall comply with this article and the rules of the department.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077.
§ 28-317.2. Definitions
As used in this article, the following terms shall have the following meanings:
COOLING TOWER. The term "cooling tower" means a cooling tower, evaporative condenser or fluid cooler that is part of a recirculated water system incorporated into a building's cooling, industrial process, refrigeration, or energy production system.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077.
§ 28-317.3. Registration
All owners of cooling towers shall register such towers with the department prior to initial operation in a form and manner as required by the commissioner and shall include, at a minimum, the following information:
1. Address of the building at which the cooling tower is located;
2. Intended use of cooling tower;
3. Name, address, telephone number and electronic mail address of owner;
4. Manufacturer of the cooling tower;
5. Model number of the cooling tower;
6. Specific unit serial number of the cooling tower;
7. Cooling capacity (tonnage) of the cooling tower;
8. Basin capacity of the cooling tower; and
9. Commissioning date of the cooling tower.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077 and L.L. 2021/126.
§ 28-317.3.1. Discontinued use
The owner or operator of a cooling tower shall notify the department within 30 days after removing or permanently discontinuing use of a cooling tower. Such notice shall include a statement that such cooling tower has been drained and sanitized in compliance with the requirements of the department of health and mental hygiene for discontinuance of a cooling tower.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077.
§ 28-317.4. Inspecting, cleaning, disinfecting and testing
All cooling towers shall be inspected, tested, cleaned and disinfected in accordance with section 17-194.1 of the New York city administrative code and the rules of the department of health and mental hygiene.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077 and L.L. 2021/126.
§ 28-317.5. Biannual certification
The owner or operator of a cooling tower shall file a biannual certification that such cooling tower was inspected, tested, cleaned and disinfected in compliance with section 17-194.1 of this chapter and the rules of the department of health and mental hygiene, and that a maintenance program and plan has been developed and implemented as required by such section. Such biannual certification shall be submitted in January and July of each year, or by dates otherwise specified in the rules of the department. The department of health and mental hygiene shall send an electronic reminder to each owner or operator of a cooling tower at least 30 days before each certification submission deadline. Such electronic reminder shall include a link to the website where such certifications may be submitted.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022; Am. 2026 N.Y. Laws Ch. 206, 8/5/2026, eff. 11/3/2026)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077 and L.L. 2021/126.
§ 28-317.6. Fees
The department may charge filing fees for registration, discontinuing of use and annual certification as set forth in the rules of the department.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077.
§ 28-317.7. Enforcement
Failure to register a cooling tower or submit a certification or statement required by this article shall be classified as a major violation.
(L.L. 2015/077, 8/18/2015, eff. 8/18/2015)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2015/077.
§ 28-318.1. General
Building gas piping systems, other than gas piping systems of buildings classified in occupancy group R-3, shall be periodically inspected in accordance with this article.
Exceptions:
1. A building that contains no gas piping and for which the owner of such building has submitted to the commissioner, in a form and manner determined by the commissioner, a certificate of a registered design professional, a licensed master plumber or an individual under the direct and continuing supervision of a licensed master plumber, or a person satisfying other qualifications that the commissioner may establish, that such building contains no gas piping.
2. A building that contains gas piping but that is not currently supplied with gas, that does not contain any appliance connected to any gas piping and that complies with section 28-318.3.5.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016; Am. L.L. 2021/138, 11/21/2021, retro eff. 1/1/2020; Am. L.L. 2021/126, 11/7/2021, eff. 11/7/2022)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2021/126.
§ 28-318.2. Frequency of inspection
An inspection of a building's gas piping system shall be conducted at periodic intervals as set forth by rule of the commissioner, but such inspection shall be conducted at least once every five years.
Exceptions:
1. If the New York state public service commission adopts a rule or other requirement for periodic inspections of service lines, as defined in section 255.3 of title 16 of the New York codes, rules and regulations, with a frequency other than five years, the commissioner may, by rule, require that the periodic inspections required by this article be conducted with such frequency.
2. The initial inspection for a new building shall be conducted in the tenth year after the earlier of (i) the issuance by the department of a letter of completion or, if applicable, a temporary or final certificate of occupancy for such building or (ii) the date such building was completed as determined by department rule.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016)
§ 28-318.3. Inspection process
Gas piping systems shall be inspected and tested in accordance with sections 28-318.3.1 through 28-318.3.4.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016)
§ 28-318.3.1. Inspection entity
Inspections of gas piping systems shall be conducted on behalf of the building owner by a licensed master plumber or by an individual holding a journeyman plumber registration issued in accordance with article 409 of chapter 4 of title 28 and working under the direct and continuing supervision of a licensed master plumber, with appropriate qualifications as prescribed by department rule but shall include successful completion of a training program acceptable to the department. The department shall require proof of such qualifications on any report and certification as required under section 28-318.3.3.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016; Am. L.L. 2025/142, 10/25/2025, eff. 2/22/2026)
§ 28-318.3.2. Scope
At each inspection, in addition to the requirements prescribed by this article or by the commissioner, all exposed gas piping, which includes gas piping that is open to view, from point of entry of gas piping into a building through the point of connection to any appliance that uses gas supplied by such piping, shall be inspected for evidence of unsafe or hazardous conditions, illegal connections, and non-code compliant installations. The inspection entity shall also conduct a leak survey of all exposed gas piping, which includes gas piping that is open to view, from the point of entry of gas piping into a building through the point of connection to any appliance that uses gas supplied by such piping to determine if there is any indication of a gas leak. Public spaces, hallways, and corridors on floors that contain gas piping or gas utilization equipment, including mechanical and boiler rooms, shall also be leak surveyed. The leak survey shall be conducted utilizing an instrument approved for leak surveys by the New York state department of public service.
Exception: Other than as required to provide access to the point of entry of gas piping into the building, gas piping, equipment, and appliances, and the point of connection of such equipment located inside of a dwelling unit, as defined by section 202 of the New York city building code, shall not be required to be inspected.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016; Am. L.L. 2025/142, 10/25/2025, eff. 2/22/2026)
§ 28-318.3.3. Report and certificate of inspection
The inspection entity conducting an inspection of a building pursuant to this article and the owner of such building shall comply with the following requirements:
1. No later than 30 days after such inspection, such inspection entity shall submit to such owner (i) a report of such inspection, on a form and in a manner determined by the department, and (ii) a certification of the licensed master plumber who performed or exercised direct and continuing supervision over such inspection that an inspection pursuant to this article has been completed for such building. Such report shall be certified by such licensed master plumber and, where applicable, by any individual who performed such inspections under the direct and continuing supervision of such licensed master plumber, and shall include, for each gas piping system inspected, a list of conditions including instances where a part or parts of such system is worn to such an extent that the safe and reliable operation of such system may be affected, gas leaks, any observed non-code compliant installations or illegal connections, any conditions described in section 28-318.3.4 and any additional information required by the department.
2. No later than the due date for such inspection, in accordance with department rules, and no earlier than 60 days before such due date, such owner shall submit a certification from a licensed master plumber that an inspection pursuant to this article has been completed by such licensed master plumber for such building, provided that the department may by rule establish an alternative timeframe for such submissions.
3. No later than 90 days after the due date for such inspection, in accordance with department rules, such owner shall electronically submit, or cause to be submitted by such inspection entity, such report to the utility company providing gas service to such building. Such submission shall only be required if, before the date that such submission would be required, the department has determined and set forth in a rule that such utility company will accept such electronic submission at no cost to such owner.
4. No later than 120 days after the due date for such inspection, in accordance with department rules, such owner shall submit to the department, in a form and manner determined by the department, (i) a certification from a licensed master plumber that all conditions that were identified in the inspection report for which a certification was submitted pursuant to item 2 of this section have been corrected, except that such certification may note that correction of one or more conditions identified in such report, other than conditions referred to in section 28-318.3.4, will reasonably take additional time to complete and (ii) a certification from such owner that such owner is in compliance with item 3 of this section. If such certification notes that one or more conditions will take additional time to complete, such owner shall, no later than 180 days after the due date for such inspection, or by such later date as the department shall determine, submit to the department, in a form and manner determined by the department, a certification from a licensed master plumber that all conditions identified in such report have been corrected.
5. All reports and certifications required by this section shall be kept on file by the inspection entity and the building owner for at least eight years after the date of inspection and made available to the department at the department's request.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016; Am. L.L. 2021/138, 11/21/2021, retro eff. 1/1/2020)
§ 28-318.3.4. Reporting and correction of unsafe or hazardous condition
If an inspection reveals any of the following conditions, the inspection entity shall notify the building owner, the utility and the department immediately and the building owner shall immediately take action to correct such condition in compliance with the New York city construction codes:
1. A gas leak;
2. Evidence of illegal connections or non-code compliant installations; or
3. Any other condition which (i) if verified by a utility company or utility corporation, would constitute a class A condition as described in part 261 of title 16 of the New York codes, rules and regulations or (ii) constitutes an imminently dangerous condition.
(L.L. 2016/152, 12/6/2016, eff. 12/6/2016)
§ 28-318.3.5. Buildings without active gas service
A building otherwise required to undergo an inspection pursuant to section 28-318.1 that is not currently supplied with gas, and that has no appliance connected to any gas piping, shall not be required to undergo such inspection when the following is submitted to the department:
1. A signed statement from a person with authority to sign such statement on behalf of any utility company that would be responsible for the provision of gas service if such service were provided containing the following:
1.1. A certification that the building no longer receives gas service, including the last date upon which gas was supplied to such building; and
1.2. A certification that the building was fully deactivated from service being provided by the utility, including the date upon which gas service was no longer provided to the building.
2. A signed statement from the owner of such building containing the following:
2.1. A certification that the building no longer receives gas service; and
2.2. A certification that the building no longer contains appliances connected to gas piping.
(L.L. 2021/138, 11/21/2021, retro eff. 1/1/2020; Am. L.L. 2025/142, 10/25/2025, eff. 2/22/2026)
§ 28-318.3.6. Resumption of gas service
Where the owner of a building that has complied with section 28-318.3.5 seeks to resume gas service to such building, the owner must:
1. Obtain a certificate of approval of gas installation from the department; and
2. Comply with the inspection and certification requirements of sections 28-318.1, 28-318.2 and 28-318.3 and the rules of the department before gas service is resumed, regardless of whether such inspection and certification would otherwise be required for that building at that time.
(L.L. 2021/138, 11/21/2021, retro eff. 1/1/2020)