NYC Administrative Code Title 28, Chapter 6 New York City Plumbing Code, part 3 of 4

Section PC 708 to Section PC 1301: 57 sections.

Section PC 708. Cleanouts

Open this section

708.1 Cleanouts required.

Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.12.

708.1.1 Horizontal drains and building drains.

Horizontal drainage pipes in buildings shall have cleanouts located at intervals of not more than 100 feet (30 480 mm). Building drains shall have cleanouts located at intervals of not more than 100 feet (30 480 mm).

Exception: Horizontal fixture drain piping serving a nonremovable trap shall not be required to have a cleanout for the section of piping between the trap and the vent connection for such trap.

708.1.2 Building sewers.

Building sewers smaller than 8 inches (203 mm) shall have cleanouts located at intervals of not more than 100 feet (30 480 mm). Building sewers 8 inches (203 mm) and larger shall have a manhole located not more than 200 feet (60 960 mm) from the junction of the building drain and building sewer and at intervals of not more than 400 feet (122 m). The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, a manhole or the end of the building sewer.

708.1.3 Building drain and building sewer junction.

The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet (3048 mm) of the developed length of piping upstream of the junction. For the requirements of this section, the cleanout access shall not be provided by water closet removal.

708.1.4 Changes of direction.

Where a horizontal drainage pipe, a building drain or a building sewer has a change of horizontal direction greater than 45 degrees (0.79 rad), a cleanout shall be installed at the change of direction. Where more than one change of horizontal direction greater than 45 degrees (0.79 rad) occurs within 40 feet (12 192 mm) of developed length of piping, the cleanout installed for the first change of direction shall serve as the cleanout for all changes in direction within that 40 feet (12 192 mm) of developed length of piping.

708.1.5 Cleanout size.

Cleanouts shall be the same size as the piping served by the cleanout, except that cleanouts for piping larger than 4 inches (102 mm) need not be larger than 4 inches (102 mm).

Exceptions:

1. A removable P-trap with slip or ground joint connections can serve as a cleanout for drain piping that is one size larger than the P-trap size.

2. Cleanouts located on stacks can be one size smaller than the stack size.

3. The size of cleanouts for cast-iron piping can be in accordance with the referenced standards for cast-iron fittings as indicated in Table 702.4 .

708.1.6 Cleanout plugs.

Cleanout plugs shall be of brass, plastic or other approved materials. Cleanout plugs for borosilicate glass piping systems shall be of borosilicate glass. Brass cleanout plugs shall conform to ASTM A 74 and shall be limited for use only on metallic piping systems. Plastic cleanout plugs shall conform to the referenced standards for plastic pipe fittings, as indicated in Table 702.4 . Cleanout plugs shall have a raised square head, a countersunk square head or a countersunk slot head. Where a cleanout plug will have a trim cover screw installed into the plug, the plug shall be manufactured with a blind end threaded hole for such purpose.

708.1.7 Manholes.

Manholes and manhole covers shall be of an approved type. Manholes located inside of a building shall have gas-tight covers that require tools for removal.

708.1.8 Installation arrangement.

The installation arrangement of a cleanout shall enable cleaning of drainage piping only in the direction of drainage flow.

Exceptions:

1. Test tees serving as cleanouts.

2. A two-way cleanout installation that is approved for meeting the requirements of Section 708.1.3.

708.1.9 Required clearance.

Cleanouts for 6-inch (153 mm) and smaller piping shall be provided with a clearance of not less than 18 inches (457 mm) from, and perpendicular to, the face of the opening to any obstruction. Cleanouts for 8-inch (203 mm) and larger piping shall be provided with a clearance of not less than 36 inches (914 mm) from, and perpendicular to, the face of the opening to any obstruction.

708.1.10 Cleanout access.

Required cleanouts shall be provided with access. Cleanouts on concealed piping or piping under a floor slab or in a crawl space of less than 24 inches (610 mm) in height or a plenum shall be extended through and terminate flush with the finished wall, floor or ground surface or shall be extended to the outside of the building. Cleanouts with openings at a finished wall shall have the face of the opening located within 1 1/2 inches (38 mm) of the finished wall surface. Cleanouts located below grade shall be extended to grade level so that the top of the cleanout plug is at or above grade. A cleanout installed in a floor or walkway that will not have a trim cover installed shall have a countersunk plug installed so the top surface of the plug is flush with the finished surface of the floor or walkway.

708.1.10.1 Cleanout plug trim covers.

Trim covers and access doors for cleanout plugs shall be designed for such purposes and shall be approved. Trim cover fasteners that thread into cleanout plugs shall be corrosion resistant. Cleanout plugs shall not be covered with mortar, plaster or any other permanent material.

708.1.10.2 Floor cleanout assemblies.

Where it is necessary to protect a cleanout plug from the loads of vehicular traffic, cleanout assemblies in accordance with ASME A112.36.2M shall be installed.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

708.1.11 Prohibited use.

The use of a threaded cleanout opening to add a fixture or to extend piping shall be prohibited except where another cleanout of equal size is installed with the required access and clearance.

708.1.12 Base of stack.

A cleanout shall be provided at the base of each waste or soil stack.

Section PC 709. Fixture Units

Open this section

709.1 Values for fixtures.

Drainage fixture unit values as given in Table 709.1 designate the relative load weight of different kinds of fixtures that shall be employed in estimating the total load carried by a soil or waste pipe, and shall be used in connection with Tables 710.1(1) and 710.1(2) of sizes for soil, waste and vent pipes for which the permissible load is given in terms of fixture units.

Table 709.1 Drainage Fixture Units for Fixtures and Groups

Fixture Type Drainage Fixture Unit Value as Load Factors Minimum Size of Trap (inches) Automatic clothes washers, commercial a, g 3 2 Automatic clothes washers, residential g 2 2 Bathroom group as defined in Section 202 f 5 – Bathtub b (with or without overhead shower or whirlpool attachments) 2 1 1/2 Bidet 1 1 1/4 Combination sink and tray 2 1 1/2 Dental lavatory 1 1 1/4 Dental unit or cuspidor 1 1 1/4 Dishwashing machine c , domestic 2 1 1/2 Drinking fountain 1/2 1 1/4 Emergency floor drain 0 2 Floor drains 2 h 3 Floor sinks Note h 2 Hand wash sinks and lavatories (circular or multiple) each faucet 2 1 1/2 Kitchen sink, domestic 2 2 Kitchen sink, domestic with food waste disposer and/or dishwasher 2 2 Laundry tray (1 or 2 compartments) 2 2 Lavatory 1 1 1/4 Multiple (gang) shower (based on the total flow rate through shower heads and body sprays) Flow rate: 5.7 gpm or less 2 2 Greater than 5.7 gpm to 12.3 gpm 3 2 Greater than 12.3 gpm to 25.8 gpm 5 3 Greater than 25.8 gpm to 55.6 gpm 6 4 Shower 2 2 Sink 2 2 Urinal 4 Note d Urinal, 1 gallon per flush or less 2 e Note d Urinal, nonwater supplied 1/2 Note d Water closet, flushometer, tank, public or private 4 e Note d

For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L, gpf = gallon per flushing cycle, gpm = gallon per minute.

a. For traps larger than 3 inches, use Table 709.2.

b. A showerhead over a bathtub or whirlpool bathtub attachment does not increase the drainage fixture unit value.

c. See Sections 709.2 through 709.4.1 for methods of computing unit value of fixtures not listed in this table or for rating of devices with intermittent flows.

d. Trap size shall be consistent with the fixture outlet size.

e. For the purpose of computing loads on building drains and sewers, water closets and urinals shall not be rated at a lower drainage fixture unit unless the lower values are confirmed by testing.

f. For fixtures added to a bathroom group, add the dfu value of those additional fixtures to the bathroom group fixture count.

g. See Section 406.3 for sizing requirements for fixture drain, branch drain and drainage stack for an automatic clothes washer standpipe.

h. See Sections 709.4 and 709.4.1.

709.2 Fixtures not listed in Table 709.1.

Fixtures not listed in Table 709.1 shall have a drainage fixture unit load based on the outlet size of the fixture in accordance with Table 709.2. The minimum trap size for unlisted fixtures shall be the size of the drainage outlet but not less than 1 1/4 inches (32 mm).

Table 709.2 Drainage Fixture Units for Fixture Drains or Traps

Fixture Drain or Trap Size (inches) Drainage Fixture Unit Value 1 1/4 1 1 1/2 2 2 3 2 1/2 4 3 5 4 6

For SI: 1 inch = 25.4 mm.

709.3 Values for continuous and semicontinuous flow.

Drainage fixture unit values for continuous and semicontinuous flow into a drainage system shall be computed on the basis that 1 gpm (0.06 L/s) of flow is equivalent to two fixture units.

709.4 Values for indirect waste receptor.

The drainage fixture unit load of an indirect waste receptor receiving the discharge of indirectly connected fixtures shall be the sum of the drainage fixture unit values of the fixtures that discharge to the receptor, but not less than the drainage fixture unit value given for the indirect waste receptor in Table 709.1 or 709.2.

709.4.1 Clear-water waste receptors.

Where waste receptors such as funnel drains, floor sinks and hub drains receive only clear-water waste from display cases, refrigerated display cases, ice bins, coolers and freezers, such receptors shall have a drainage fixture unit value of one-half.

Section PC 710. Drainage System Sizing

Open this section

710.1 Maximum fixture unit load.

The maximum number of drainage fixture units connected to a given size of building sewer, building drain or horizontal branch of the building drain shall be determined using Table 710.1(1). The maximum number of drainage fixture units connected to a given size of horizontal branch or vertical soil or waste stack shall be determined using Table 710.1(2).

Table 710.1(1) Building Drains and Sewers

Diameter of Pipe (inches) Maximum Number of Drainage Fixture Units Connected to any Portion of the Building Drain or the Building Sewer, Including Branches of the Building Drain a Slope per foot 1/16 inch 1/8 inch 1/4 inch 1/2 inch 1 1/4 — — 1 1 1 1/2 — — 3 3 2 — — 21 26 2 1/2 — — 24 31 3 — 36 42 50 4 — 180 216 250 5 — 390 480 575 6 — 700 840 1,000 8 1,400 1,600 1,920 2,300 10 2,500 2,900 3,500 4,200 12 3,900 4,600 5,600 6,700 15 7,000 8,300 10,000 12,000

For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.

a. The minimum size of any building drain serving a water closet shall be 3 inches.

Table 710.1(2) Horizontal Fixture Branches and Stacks a

Diameter of Pipe (inches) Total for horizontal branch Maximum Number of Drainage Fixture Units (dfu) Stacks b Total for Stack of Three Branch Intervals or Less Total for Stack Greater than Three Branch Intervals 1 1/2 3 4 8 2 6 10 24 2 1/2 12 20 42 3 20 48 72 4 160 240 500 5 360 540 1,100 6 620 960 1,900 8 1,400 2,200 3,600 10 2,500 3,800 5,600 12 2,900 6,000 8,400 15 7,000 Note c Note c

For SI:1 inch = 25.4 mm

a. Does not include branches of the building drain. Refer to Table 710.1(1).

b. Stacks shall be sized based on the total accumulated connected load at each story or branch interval. No soil or waste stack shall be smaller than any horizontal branch connection thereto.

c. Sizing load based on design criteria.

710.1.1 Horizontal stack offsets.

Horizontal stack offsets shall be sized as required for building drains in accordance with Table 710.1(1) , except as required by Section 711.3.

710.1.2 Vertical stack offsets.

Vertical stack offsets shall be sized as required for straight stacks in accordance with Table 710.1(2) , except where required to be sized as a building drain in accordance with Section 711.1.1.

710.2 Future fixtures.

Where provision is made for the future installation of fixtures, those provided for shall be considered in determining the required sizes of drain pipes.

Section PC 711. Offsets In Drainage Piping In Buildings of Five Stories or More

Open this section

711.1 Horizontal branch connections above or below vertical stack offsets.

If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with Section 907 .

711.1.1 Omission of vents for vertical stack offsets.

Vents for vertical offsets required by Section 711.1 shall not be required where the stack and its offset are sized as a building drain (see Table 710.1(1) , Column 5).

711.2 Horizontal stack offsets.

A stack with a horizontal offset located more than four branch intervals below the top of the stack shall be vented in accordance with Section 907 and sized as follows:

1. The portion of the stack above the offset shall be sized as for a vertical stack based on the total number of drainage fixture units above the offset.

2. The offset shall be sized in accordance with Section 710.1.1.

3. The portion of the stack below the offset shall be sized as for the offset or based on the total number of drainage fixture units on the entire stack, whichever is larger (see Table 710.1(2) , Column 4).

711.2.1 Omission of vents for horizontal stack offsets.

Vents for horizontal stack offsets required by Section 711.2 shall not be required where the stack and its offset are one pipe size larger than required for a building drain (see Table 710.1(1) , Column 5) and the entire stack and offset are not less in cross- sectional area than that required for a straight stack plus the area of an offset vent as provided for in Section 907 .

711.3 Offsets below lowest branch.

Where a vertical offset occurs in a soil or waste stack below the lowest horizontal branch, a change in diameter of the stack because of the offset shall not be required. If a horizontal offset occurs in a soil or waste stack below the lowest horizontal branch, the required diameter of the offset and the stack below it shall be determined as for a building drain in accordance with Table 710.1(1) .

Section PC 712. Ejectors

Open this section

712.1 Building subdrains.

Building subdrains that cannot be discharged to the sewer by gravity flow shall be discharged into a gas-tight covered and vented ejector pit/basin from which the liquid shall be lifted and discharged into the building gravity drainage system by automatic pumping equipment or other approved method.

712.2 Valves required.

A check valve and a full open valve located on the discharge side of the check valve shall be installed in the pump or ejector discharge piping between the pump or ejector and the gravity drainage system. Access shall be provided to such valves. Such valves shall be located above the sump cover required by Section 712.1 or, where the discharge pipe from the ejector is below grade, the valves shall be accessibly located outside the sump below grade in an access pit with a removable access cover.

712.3 Ejector design.

The ejector pit and discharge piping shall conform to the requirements of Sections 712.3.1 through 712.3.5.

712.3.1 Ejector pump.

The ejector pump capacity and head shall be appropriate to anticipated use requirements.

712.3.2 Ejector pit.

The ejector pit shall be not less than 18 inches (457 mm) in diameter and 24 inches (610 mm) in depth, unless otherwise approved. The pit shall be accessible and located such that all drainage flows into the pit by gravity. The ejector pit shall be constructed of tile, concrete, steel, plastic or other approved materials. The pit bottom shall be solid and provide permanent support for the pump. The ejector pit shall be fitted with a gas-tight removable cover that is installed flush with grade or floor level, or above grade or floor level. The cover shall be adequate to support anticipated loads in the area of use. The ejector pit shall be vented in accordance with Chapter 9 .

712.3.3 Discharge pipe and fittings.

Discharge pipe and fittings serving ejectors shall be constructed of materials in accordance with Sections 712.3.3.1 and 712.3.3.2 and shall be approved.

712.3.3.1 Materials.

Pipe and fitting materials shall be in accordance with Table 702.1 and Table 702.2 .

712.3.3.2 Ratings.

Pipe and fittings shall be rated for the maximum system operating pressure and temperature. Pipe fitting materials shall be compatible with the pipe material. Where pipe and fittings are buried in the earth, they shall be suitable for burial.

712.3.4 Maximum effluent level.

The effluent level control shall be adjusted and maintained to at all times prevent the effluent from rising to within 2 inches (51 mm) of the invert of the gravity drain inlet into the sump.

712.3.5 Waste pump and waste ejector connection to the drainage system.

Pumps connected to the drainage system shall connect to a building drain, soil stack, waste stack or horizontal branch drain. Where the discharge line connects into horizontal drainage piping, the connection shall be made through a wye fitting into the top of the drainage piping and such wye fitting shall be located not less than 10 pipe diameters from the base of any soil stack, waste stack or fixture drain.

712.4 Sewage pumps and sewage ejectors.

A sewage pump or sewage ejector shall automatically discharge the contents of the pit to the building drainage system downstream of the house trap .

Exceptions: Macerating toilet systems that comply with ASME A112.3.4/CSA B45.9 and installed in accordance with the manufacturer's instructions. Macerating toilet systems shall be permitted to discharge to a horizontal drain or stack in accordance with Section 712.3.5.

712.4.1 Capacity.

A sewage pump or sewage ejector shall have the capacity and head for the application requirements. Pumps or ejectors that receive the discharge of water closets shall be capable of handling spherical solids with a diameter of up to and including 2 inches (51 mm). Other pumps or ejectors shall be capable of handling spherical solids with a diameter of up to and including 1 inch (25 mm). The capacity of a pump or ejector based on the diameter of the discharge pipe shall be not less than that indicated in Table 712.4.1 .

Exceptions:

1. Grinder pumps or grinder ejectors that receive the discharge of water closets shall have a discharge opening of not less than 1 1/4 inches (32 mm).

2. Macerating toilet assemblies that serve single water closets shall have a discharge opening of not less than 3/4 inch (19.1 mm).

Table 712.4.1 Minimum Capacity of Sewage Pump or Sewage Ejector

Diameter of the Discharge Pipe (inches) Capacity of Pump or Ejector (gpm) 2 21 2 1/2 30 3 46

For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.

Section PC 713. Health Care Plumbing

Open this section

713.1 Scope.

This section shall govern those aspects of health care plumbing systems that differ from plumbing systems in other structures. Health care plumbing systems shall conform to this section in addition to the other requirements of this code. The provisions of this section shall apply to the special devices and equipment installed and maintained in the following occupancies: nursing homes; homes for the aged; orphanages; infirmaries; first aid stations; psychiatric facilities; clinics; professional offices of dentists and doctors; mortuaries; educational facilities; surgery, dentistry, research and testing laboratories; establishments manufacturing pharmaceutical drugs and medicines; and other structures with similar apparatus and equipment classified as plumbing.

713.2 Bedpan washers and clinical sinks.

Bedpan washers and clinical sinks shall connect to the drainage and vent system in accordance with the requirements for a water closet. Bedpan washers shall also connect to a local vent.

713.3 Indirect waste.

Sterilizers, steamers and condensers shall discharge to the drainage through an indirect waste pipe by means of an air gap. Where a battery of not more than three sterilizers discharges to an individual receptor, the distance between the receptor and a sterilizer shall not exceed 8 feet (2438 mm). The indirect waste pipe on a bedpan steamer shall be trapped.

713.4 Vacuum system station.

Ready access shall be provided to vacuum system station receptacles. Such receptacles shall be built into cabinets or recesses and shall be visible.

713.5 Bottle system.

Vacuum (fluid suction) systems intended for collecting, removing and disposing of blood, pus or other fluids by the bottle system shall be provided with receptacles equipped with an overflow prevention device at each vacuum outlet station.

713.6 Central disposal system equipment.

Central vacuum (fluid suction) systems shall provide continuous service. Systems equipped with collecting or control tanks shall provide for draining and cleaning of the tanks while the system is in operation. In hospitals, the system shall be connected to the emergency power system. The exhausts from a vacuum pump serving a vacuum (fluid suction) system shall discharge separately to open air above the roof.

713.7 Central vacuum or disposal systems.

Where the waste from a central vacuum (fluid suction) system of the barometric-lag, collection-tank or bottle-disposal type is connected to the drainage system, the waste shall be directly connected to the sanitary drainage system through a trapped waste.

713.7.1 Piping.

The piping of a central vacuum (fluid suction) system shall be of corrosion-resistant material with a smooth interior surface. A branch shall be not less than 1/2-inch (12.7 mm) nominal pipe size for one outlet and shall be sized in accordance with the number of vacuum outlets. A main shall be not less than 1-inch (25 mm) nominal pipe size. The pipe sizing shall be increased in accordance with the manufacturer's instructions as stations are increased.

713.7.2 Velocity.

The velocity of airflow in a central vacuum (fluid suction) system shall be less than 5,000 feet per minute (25 m/s).

713.8 Vent connections prohibited.

Connections between local vents serving bedpan washers or sterilizer vents serving sterilizing apparatus and normal sanitary plumbing systems are prohibited. Only one type of apparatus shall be served by a local vent.

713.9 Local vents and stacks for bedpan washers.

Bedpan washers shall be vented to open air above the roof by means of one or more local vents. The local vent for a bedpan washer shall be not less than a 2-inch-diameter (51 mm) pipe. A local vent serving a single bedpan washer is permitted to drain to the fixture served.

713.9.1 Multiple installations.

Where bedpan washers are located above each other on more than one floor, a local vent stack is permitted to be installed to receive the local vent on the various floors. Not more than three bedpan washers shall be connected to a 2-inch (51 mm) local vent stack, not more than six to a 3-inch (76 mm) local vent stack and not more than 12 to a 4-inch (102 mm) local vent stack. In multiple installations, the connections between a bedpan washer local vent and a local vent stack shall be made with tee or tee-wye sanitary pattern drainage fittings installed in an upright position.

713.9.2 Trap required.

The bottom of the local vent stack, except where serving only one bedpan washer, shall be drained by means of a trapped and vented waste connection to the sanitary drainage system. The trap and waste shall be the same size as the local vent stack.

713.9.3 Trap seal maintenance.

A water supply pipe not less than 1/4 inch (6.4 mm) in diameter shall be taken from the flush supply of each bedpan washer on the discharge or fixture side of the vacuum breaker, shall be trapped to form not less than a 3-inch (76 mm) water seal, and shall be connected to the local vent stack on each floor. The water supply shall be installed so as to provide a supply of water to the local vent stack for cleansing and drain trap seal maintenance each time a bedpan washer is flushed.

713.10 Sterilizer vents and stacks.

Multiple installations of pressure and nonpressure sterilizers shall have the vent connections to the sterilizer vent stack made by means of inverted wye fittings. Access shall be provided to vent connections for the purpose of inspection and maintenance.

713.10.1 Drainage.

The connection between sterilizer vent or exhaust openings and the sterilizer vent stack shall be designed and installed to drain to the funnel or basket-type waste fitting. In multiple installations, the sterilizer vent stack shall be drained separately to the lowest sterilizer funnel or basket-type waste fitting or receptor.

713.11 Sterilizer vent stack sizes.

Sterilizer vent stack sizes shall comply with Sections 713.11.1 through 713.11.4.

713.11.1 Bedpan steamers.

The minimum size of a sterilizer vent serving a bedpan steamer shall be 1 1/2 inches (38 mm) in diameter. Multiple installations shall be sized in accordance with Table 713.11.1 .

Table 713.11.1 Stack Sizes for Bedpan Steamers and Boiling-Type Sterilizers (Number of Connections of Various Sizes Permitted to Various-sized Sterilizer Vent Stacks)

Stack Size (inches) Connection Size 1 1/2 2" 1 1/2 a 1 or 0 2 a 2 or 1 2 b 1 and 1 3 a 4 or 2 3 b 2 and 2 4 a 8 or 4 4 b 4 and 4

For SI: 1 inch = 25.4 mm.

a. Total of each size.

b. Combination of sizes.

713.11.2 Boiling-type sterilizers.

The size of a sterilizer vent stack shall be not less than 2 inches (51 mm) in diameter where serving a utensil sterilizer and not less than 1 1/2 inches (38 mm) in diameter where serving an instrument sterilizer. Combinations of boiling-type sterilizer vent connections shall be sized in accordance with Table 713.11.1 .

713.11.3 Pressure sterilizers.

Pressure sterilizer vent stacks shall be 2 1/2 inches (64 mm) minimum. Those serving combinations of pressure sterilizer exhaust connections shall be sized in accordance with Table 713.11.3.

Table 713.11.3 Stack Sizes for Pressure Sterilizers (Number of Connections of Various Sizes Permitted To Various-sized Vent Stacks)

Stack Size (inches) Connection Size 3/4" 1" 1 1/4" 1 1/2" 1 1/2 a 3 or 2 or 1 — 1 1/2 b 2 and 1 — — 2 a 6 or 3 or 2 or 1 2 b 3 and 2 — — 2 b 2 and 1 and 1 — 2 b 1 and 1 and — 1 3 a 15 or 7 or 5 or 3 3 b 1 and 1 and 5 and 2 and 2 1

For SI: 1 inch = 25.4 mm.

a. Total of each size.

b. Combination of sizes.

713.11.4 Pressure instrument washer sterilizer sizes.

The diameter of a sterilizer vent stack serving an instrument washer sterilizer shall be not less than 2 inches (51 mm). Not more than two sterilizers shall be installed on a 2-inch (51 mm) stack, and not more than four sterilizers shall be installed on a 3-inch (76 mm) stack.

Section PC 714. Computerized Drainage Design

Open this section

714.1 Design of drainage system.

The sizing, design and layout of the drainage system shall be permitted to be designed by approved computer design methods.

714.2 Load on drainage system.

The load shall be computed from the simultaneous or sequential discharge conditions from fixtures, appurtenances and appliances or the peak usage design condition.

714.2.1 Fixture discharge profiles.

The discharge profiles for flow rates versus time from fixtures and appliances shall be in accordance with the manufacturer's specifications.

714.3 Selections of drainage pipe sizes.

Pipe shall be sized to prevent full-bore flow.

714.3.1 Selecting pipe wall roughness.

Pipe size calculations shall be conducted with the pipe wall roughness factor (k s ), in accordance with the manufacturer's specifications and as modified for aging roughness factors with deposits and corrosion.

714.3.2 Slope of horizontal drainage piping.

Horizontal drainage piping shall be designed and installed at slopes in accordance with Table 704.1.

Section PC 715. Backwater Valves

Open this section

715.1 Sewage backflow.

Where fixtures, floor drains, or area drains are subject to overflow as the result of backwater from the public sewer system, accessible backwater valves shall be installed in the fixture drain pipe from such fixture, in the branch drain to such area drain or group of fixtures, or in the building drain at its point of exit from the building and downstream from the building trap. Buildings located in flood hazard areas shall be deemed to be subject to overflow as the result of backwater from the public sewer system and shall be provided with backwater valves in accordance with the additional requirements of Section 7.3.3 of ASCE 24 as modified by Appendix G of the New York City Building Code .

715.2 Material.

Bearing parts of backwater valves shall be of corrosion-resistant material. Backwater valves shall comply with ASME A112.14.1, CSA B181.1 or CSA B181.2.

715.3 Seal.

Backwater valves shall be so constructed as to provide a mechanical seal against backflow. The flap shall be so designed as to hang partially open when not subject to backwater pressure.

715.4 Diameter.

Backwater valves, when fully opened, shall have a capacity not less than that of the pipes in which they are installed.

715.5 Accessibility.

Backwater valves shall be installed so that access is provided to the working parts for service and repair. Masonry access manholes shall be provided when the centerline of any drain line is 18 inches (457 mm) or more below a slab on grade.

Section PC 716. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section PC 716 at American Legal Publishing.

Section PC 717. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section PC 717 at American Legal Publishing.

Section PC 801. General

Open this section

801.1 Scope.

This chapter shall govern matters concerning indirect waste piping and special wastes. This chapter shall further control matters concerning food-handling establishments, sterilizers, clear-water waste, swimming pools, methods of providing air breaks or air gaps, and neutralizing devices for corrosive wastes.

801.2 Protection.

Devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that discharge to the drainage system, shall be provided with protection against backflow, flooding, fouling, contamination and stoppage of the drain.

Section PC 802. Indirect Wastes

Open this section

802.1 Where required.

Food-handling equipment, in other than dwelling units, clear-water waste, dishwashing machines and utensils, pots, pans and dishwashing sinks shall discharge through an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and Section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7 .

802.1.1 Food handling.

Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Each well of a multiple-compartment sink shall discharge independently to a waste receptor.

802.1.2 Floor drains in food storage areas.

Floor drains located within walk-in refrigerators or freezers in food service and food establishments shall be indirectly connected to the sanitary drainage system by means of an air gap. Where a floor drain is located within an area subject to freezing, the waste line serving the floor drain shall not be trapped and shall indirectly discharge into a waste receptor located outside of the area subject to freezing.

Exception: Where protected against backflow by a backwater valve, such floor drains shall be indirectly connected to the sanitary drainage system by means of an air break or an air gap.

802.1.3 Potable clear-water waste.

Where devices and equipment, such as sterilizers and relief valves, discharge potable water to the building drainage system, the discharge shall be through an indirect waste pipe by means of an air gap.

802.1.4 Swimming pools.

Where waste water from swimming pools, backwash from filters and water from pool deck drains discharge to the building drainage system, the discharge shall be through an indirect waste pipe by means of an air gap to a waste outlet.

802.1.5 Nonpotable clear-water waste.

Where devices and equipment such as process tanks, filters, drips and boilers discharge nonpotable water to the building drainage system, the discharge shall be through an indirect waste pipe by means of an air break or an air gap.

802.1.6 Domestic dishwashing machines.

Domestic dishwashing machines shall discharge indirectly through an air gap or air break into a waste receptor in accordance with Section 802.2, or discharge into a wye branch fitting on the tailpiece of the kitchen sink or the dishwasher connection of a food waste disposer. The waste line of a domestic dishwashing machine discharging into a kitchen sink tailpiece or food waste disposer shall connect to a deck-mounted air gap or the waste line shall rise and be securely fastened to the underside of the sink rim or counter.

802.1.7 Commercial dishwashing machines.

The discharge from a commercial dishwashing machine shall be through an air gap or air break into a waste receptor in accordance with Section 802.2.

802.1.8 Food utensils, dishes, pots and pans sinks.

Sinks, in other than dwelling units, used for the washing, rinsing or sanitizing of utensils, dishes, pots, pans or service ware used in the preparation, serving or eating of food shall discharge indirectly through an air gap or an air break.

Exception: Hand sinks may be directly connected to the drainage system.

802.2 Installation.

Indirect waste piping shall discharge through an air gap or air break into a waste receptor. Waste receptors shall be trapped and vented and shall connect to the building drainage system. Indirect waste piping that exceeds 30 inches (762 mm) in developed length measured horizontally, or 54 inches (1372 mm) in total developed length, shall be trapped.

Exception: Where a waste receptor receives only clear-water waste and does not directly connect to a sanitary drainage system, the receptor shall not require a trap.

802.2.1 Air gap.

The air gap between the indirect waste pipe and the flood level rim of the waste receptor shall be not less than twice the effective opening of the indirect waste pipe.

802.2.2 Air break.

An air break shall be provided between the indirect waste pipe and the trap seal of the waste receptor.

802.3 Waste receptors.

For other than hub drains that receive only clear-water waste and standpipes, a removable strainer or basket shall cover the outlet of waste receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, crawl spaces, attics, interstitial spaces above ceilings and below floors. Ready access shall be provided to waste receptors.

802.3.1 Size of receptors.

A waste receptor shall be sized for the maximum discharge of all indirect waste pipes served by the receptor. Receptors shall be installed to prevent splashing or flooding.

802.3.2 Hub drains.

A hub drain shall be in the form of a hub or a pipe extending not less than 1 inch (25 mm) above a water-impervious floor.

802.3.3 Standpipes.

Standpipes shall be individually trapped. Standpipes shall extend not less than 18 inches (457 mm) but not greater than 42 inches (1066 mm) above the trap weir. Access shall be provided to standpipes and drains for rodding.

Section PC 803. Special Wastes

Open this section

803.1 Wastewater temperature.

Steam pipes shall not connect to any part of a drainage or plumbing system and water above 150°F (66°C) shall not be discharged into any part of a drainage system. Such pipes shall discharge into an indirect waste receptor connected to the drainage system.

803.2 Neutralizing device required for corrosive wastes.

All discharges into the public sewers are subject to regulation by the Department of Environmental Protection. The Department of Environmental Protection may prohibit the discharge of any corrosive liquids, including but not limited to spent acids or other harmful chemicals that may destroy or injure a drain, sewer, soil or waste pipe, or create noxious or toxic fumes or interfere with sewage treatment processes or may require that such liquids be neutralized or treated prior to discharge in accordance with Department of Environmental Protection regulations. Where treatment prior to discharge is required by the Department of Environmental Protection, liquids shall not be discharged into the plumbing system without being thoroughly neutralized or treated in compliance with the rules of the Department of Environmental Protection.

803.3 Chemical waste system design.

A chemical drainage and vent system shall be designed and installed in accordance with this code. Chemical drainage and vent systems shall be completely separated from the sanitary systems. Chemical waste shall not discharge to a sanitary drainage system until such waste has been treated in accordance with Section 803.2.

803.3.1 Chemical drainage and vent pipe.

Chemical waste and vent pipe shall conform to one of the standards listed in Table 803.3.1 .

Table 803.3.1 Chemical Waste and Vent Pipe

Material Standard Chlorinated polyvinyl chloride (CPVC) plastic ASTM F 2618 Glass pipe ASTM C 1053 High silicon cast iron ASTM A 518 A / 518 M Polyolefin pipe ASTM F 1412; CSA B181.3 Polypropylene (PP) pipe ASTM F 1412 Polyvinylidene fluoride (PVDF) plastic pipe ASTM F 1673; CSA B181.3

803.3.2 Chemical drainage and vent pipe fittings.

Chemical waste and vent pipe fittings shall conform to one of the standards listed in Table 803.3.2 .

Table 803.3.2 Chemical Waste and Vent Pipe Fittings

Material Standard Chlorinated polyvinyl chloride (CPVC) plastic ASTM F 2618 Glass ASTM C 1053 High silicon iron ASTM A 861 Polyolefin pipe ASTM F 1412; CSA B181.3 Polypropylene (PP) pipe ASTM F 1412 Polyvinylidene fluoride (PVDF) plastic pipe ASTM F 1673; CSA B181.3

803.3.3 Chemical drainage and vent pipe installation.

The installation of chemical waste and vent pipe shall conform to Sections 704.1, 704.2, 704.3, 704.4, and 704.5.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

803.3.4 Chemical drainage and vent pipe joints.

This section contains provisions applicable to joints specific to chemical drainage and vent piping. Joints between different materials shall conform to Section 705 .

803.3.4.1 CPVC plastic.

Joints between CPVC plastic pipe or fittings shall comply with Sections 803.3.4.1.1, 803.3.4.1.2 and 803.3.4.1.3.

803.3.4.1.1 Mechanical joints.

Mechanical joints shall be installed in accordance with the manufacturer's instructions.

803.3.4.1.2 Solvent cementing.

Joint surfaces shall be clean and free from moisture. Joints shall be made in accordance with the pipe manufacturer's installation instructions. Where such instructions require that a primer be used, the primer shall be applied to the joint surfaces and a solvent cement orange in color and conforming to ASTM F 2618 shall be applied to the joint surfaces. Where such instructions allow for a one-step solvent cement, yellow in color and conforming to ASTM F 2618, to be used, the joint surfaces shall not require application of a primer before the solvent cement is applied. The joint shall be made while the cement is wet and in accordance with ASTM F 2618. Solvent cement joints shall be permitted above or below ground.

803.3.4.1.3 Threaded joints.

Threads shall conform to ASME B1.20.1. Schedule 80 or heavier pipe shall be permitted to be threaded with dies specifically designed for plastic pipe, but the pressure rating of the pipe shall be reduced by 50 percent. Thread by socket molded fittings shall be permitted. Approved thread lubricant or tape shall be applied on the male threads only.

803.3.4.2 Borosilicate glass joints.

Joints between Borosilicate glass pipe and fittings shall comply with Sections 803.3.4.2.1 and 803.3.4.2.2.

803.3.4.2.1 Mechanical joints.

Glass-to-glass connections shall be made with a bolted compression- type, 300 series stainless steel coupling with contoured acid-resistant elastomeric compression ring and a fluorocarbon polymer inner seal ring; or with caulked joints in accordance with Section 803.3.4.2.2.

803.3.4.2.2 Caulked joints.

Lead-caulked joints for hub and spigot soil pipe shall be firmly packed with oakum or hemp and filled with molten lead not less than 1 inch (25 mm) in depth and not to recede more than inch (3.2 mm) below the rim of the hub. Paint, varnish or other coatings shall not be permitted on the jointing material until after the joint has been tested and approved. Lead shall be run in one pouring and shall be caulked tight. Acid-resistant rope and acidproof cement shall be permitted.

803.3.4.3 High silicon cast iron.

Joints in high silicon cast iron system shall be in accordance with Section 705.4.

803.3.4.4 Polyolefin.

Joints between polyolefin plastic pipe and fittings shall comply with Sections 803.3.4.4.1 and 803.3.4.4.2.

803.3.4.4.1 Heat-fusion joints.

Heat-fusion joints for polyolefin pipe and tubing joints shall be installed with socket-type heat-fused polyolefin fittings or electrofusion polyolefin fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 1412 or CSA B181.3.

803.3.4.4.2 Mechanical and compression sleeve joints.

Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions, and in conformance with acceptance criteria established by the commissioner.

803.3.4.5 Polypropylene (PP) plastic.

Joints between PP plastic pipe and fittings shall comply with Section 803.3.4.5.1 or 803.3.4.5.2.

803.3.4.5.1 Heat-fusion joints.

Heat-fusion joints for polypropylene pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion polypropylene fittings or electrofusion polypropylene fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 1412.

803.3.4.5.2 Mechanical and compression sleeve joints.

Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions.

803.3.4.6 Polyvinylidene fluoride plastic.

Joints between polyvinylidene plastic pipe and fittings shall comply with Sections 803.3.4.6.1 and 803.3.4.6.2.

803.3.4.6.1 Heat-fusion joints.

Heat-fusion joints for polyvinylidene fluoride pipe and tubing joints shall be installed with socket-type heat-fused polyvinylidene fluoride fittings or electrofusion polyvinylidene fittings and couplings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 1673.

803.3.4.6.2 Mechanical and compression sleeve joints.

Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions, and in conformance with acceptance criteria established by the commissioner.

803.3.5 Chemical drainage and vent pipe cleanouts.

Chemical waste and vent pipe cleanouts shall conform to Sections 708.1.1, 708.1.4, 708.1.5, 708.1.6, 708.1.8, 708.1.9, 708.1.10 and 708.1.11.

803.3.6 Chemical drainage and vent pipe sizing.

Sizing of chemical waste and vent pipe shall conform to Sections 709 and 710 .

803.3.7 Offsets in chemical drainage and vent pipe sizing.

Offsets of chemical waste and vent pipe shall conform to Section 711 .

Section PC 804. Materials, Joints and Connections

Open this section

804.1 General.

The materials and methods utilized for the construction and installation of indirect waste pipes and systems shall comply with the applicable provisions of Chapter 7.

Section PC 901. General

Open this section

901.1 Scope.

The provisions of this chapter shall govern the materials, design, construction and installation of vent systems except for vent systems for methane and radon which shall be governed by this section.

901.1.1 Methane and radon venting.

The design and materials used in the installation of the methane and radon vent systems shall be approved by the commissioner and shall comply with all applicable rules of the Fire Department.

901.2 Trap seal protection.

The plumbing system shall be provided with a system of vent piping that will permit the admission or emission of air so that the seal of any fixture trap shall not be subjected to a pressure differential of more than 1 inch of water column (249 Pa).

901.2.1 Venting required.

Traps and trapped fixtures shall be vented in accordance with one of the venting methods specified in this chapter.

901.3 Chemical waste vent systems.

The vent system for a chemical waste system shall be independent of the sanitary vent system and shall terminate separately through the roof to the outdoors.

901.4 Use limitations.

The plumbing vent system shall not be utilized for purposes other than the venting of the plumbing system.

901.5 Tests.

The vent system shall be tested in accordance with Section 312 .

901.6 Engineered systems.

Engineered venting systems shall conform to the provisions of Section 919 .

Section PC 902. Materials

Open this section

902.1 Vents.

The materials and methods utilized for the construction and installation of venting systems shall comply with the applicable provisions of Section 702.

902.2 Sheet copper.

Sheet copper for vent pipe flashings shall conform to ASTM B 152 and shall weigh not less than 8 ounces per square foot (2.5 kg/m 2 ).

902.3 Sheet lead.

Sheet lead for vent pipe flashings shall weigh not less than 3 pounds per square foot (15 kg/m 2 ) for field-constructed flashings and not less than 2 1/2 pounds per square foot (12 kg/m 2 ) for prefabricated flashings.

Section PC 903. Vent Terminals

Open this section

903.1 Roof extension.

Open vent pipes that extend through a roof shall be terminated not less than 24 inches (610 mm) above the roof. Where a roof is to be used for assembly or as a promenade, observation deck, sun bathing deck or similar purposes, open vent pipes shall terminate not less than 7 feet (2134 mm) above the roof. Approved vandal-resistant vent caps may be used.

903.2 Frost closure.

Vent extensions through a roof or wall shall be not less than 4 inches (102 mm) in diameter. Any increase in the size of the vent shall be made not less than 1 foot (305 mm) inside the thermal envelope of the building.

903.3 Flashings.

The juncture of each vent pipe with the roof line shall be made water tight by an approved flashing.

903.4 Prohibited use.

A vent terminal shall not be used for any purpose other than a vent terminal.

903.5 Location of vent terminal.

Locations of vent terminals shall comply with Sections 903.5.1 and 903.5.2.

903.5.1 New vent terminals.

An open vent terminal from a drainage system of the new or altered building shall not be located directly beneath any door, operable window, or other air intake opening of the building or of an adjacent building, and any such vent terminal shall not be within 10 feet (3048 mm) horizontally of such an opening unless it is at least 3 feet (914 mm) above the top of such opening. When the consent of the owner of an adjoining taller building is obtained, the owner of the new or altered building shall be permitted to carry the new vent stack, with adequate support, to a level above the higher existing roof.

903.5.2 New openings.

A door, operable window, or other air intake opening of the new or altered building shall not be located within 10 feet (3048 mm) horizontally from an open vent terminal from a drainage system of an existing adjacent building unless the existing terminal is at least 3 feet (914 mm) above such opening. Whenever necessary, the owner of the new building shall at his or her own expense, and with approval of the adjoining owner, offset the vent stack of the adjacent existing building to a distance of 10 feet (3048 mm) or more from such openings, or shall extend such vent stack to a height of at least 3 feet (924 mm) above the topmost opening.

903.6 Reserved.

903.7 Reserved.

Section PC 904. Outdoor Vent Extensions

Open this section

904.1 Required vent extension.

The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors.

904.1.1 Installation.

The required vent shall be a dry vent that connects to the building drain or an extension of a drain that connects to the building drain. Such vent shall not be an island fixture vent as allowed by Section 916 .

904.1.2 Size.

The required vent shall be sized in accordance with Section 906.2 based on the required size of the building drain.

904.2 Vent stack required.

A vent stack shall be required for every drainage stack that has three branch intervals or more .

904.3 Vent termination.

Vent stacks or stack vents shall terminate outdoors above the roof or to the stack vent portion of the soil or waste stack, at least 6 inches (152 mm) above the flood level of the highest fixture connection discharging into the soil or waste stack.

904.4 Vent connection at base.

Vent stacks shall connect to the base of the drainage stack. The vent stack shall connect at or below the lowest horizontal branch. Where the vent stack connects to the building drain, the connection shall be located downstream of the drainage stack and within a distance of 10 times the diameter of the drainage stack.

904.5 Vent headers.

Stack vents and vent stacks connected into a common vent header at the top of the stacks and extending to the open air above the roof at one point shall be sized in accordance with the requirements of Section 906.1, but shall not be smaller than the smallest stack vent. The number of fixture units shall be the sum of all fixture units on all stacks connected thereto, and the developed length shall be the longest vent length from the intersection at the base of the most distant stack to the vent terminal in the open air, as a direct extension of one stack.

904.6 Sub-stack connections.

Where it is desired to terminate stacks at a point below the roof terminus of the main vent stack, the sub-stack may connect to the main vent stack provided the portion of the main vent stack above the connection is sized for the total fixture unit load connected thereto, and for the maximum developed length of the stack or sub-stack.

Section PC 905. Vent Connections and Grades

Open this section

905.1 Connection.

Individual, branch and circuit vents shall connect to a vent stack, stack vent, or extend to the open air above the roof.

905.2 Grade.

Vent and branch vent pipes shall be so graded and connected as to drain back to the drainage pipe by gravity.

905.3 Vent connection to drainage system.

Every dry vent connecting to a horizontal drain shall connect above the centerline of the horizontal drain pipe.

905.4 Reserved.

905.5 Height above fixtures.

A connection between a vent pipe and a vent stack or stack vent shall be made at not less than 6 inches (152 mm) above the flood level rim of the highest fixture served by the vent. Horizontal vent pipes forming branch vents, relief vents or loop vents shall be located not less than 6 inches (152 mm) above the flood level rim of the highest fixture served .

905.6 Vent for future fixtures.

Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed. The vent size shall be not less than one-half the diameter of the rough-in drain to be served. The vent rough-in shall connect to the vent system, or shall be vented by other means as provided for in this chapter. The connection shall be identified to indicate that it is a vent.

Section PC 906. Vent Pipe Sizing

Open this section

906.1 Size of stack vents and vent stacks.

The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 906.1 , but in no case shall the diameter be less than one-half the diameter of the drain served or less than 1 1/4 inches (32 mm).

Table 906.1 Size and Developed Length of Stack Vents and Vent Stacks

Diameter of Soil or Waste Stack (inches) Total Fixture Units Being Vented (dfu) Maximum Developed Length of Vent (feet) a Diameter of Vent (inches) 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8 10 12 1 1/4 2 30 — — — — — — — — — 1 1/2 8 50 150 1 1/2 10 30 100 2 12 75 200 — — — — — — — 2 20 30 50 150 2 1/2 42 26 30 100 300 3 10 — 42 150 360 1,040 — — — — — — 3 21 32 110 270 810 3 53 27 94 230 680 3 102 — 25 86 210 620 — — — — — 4 43 35 85 250 980 4 140 27 65 200 750 4 320 — — 23 55 170 640 — — — — 4 540 21 50 150 580 5 190 28 82 320 990 5 490 — — — 21 63 250 760 — — — — 5 940 18 53 210 670 5 1,400 16 49 190 590 6 500 — — — — 33 130 400 1,000 — — — 6 1,100 26 100 310 780 6 2,000 22 84 260 660 6 2,900 — — — — 20 77 240 600 — — 8 1,800 31 95 240 940 8 3,400 24 73 190 729 8 5,600 — — — — — 20 62 160 610 — 8 7,600 18 56 140 560 10 4,000 31 78 310 960 10 7,200 — — — — — — 24 60 240 740 — 10 11,000 20 51 200 630 10 15,000 18 46 180 571 12 7,300 — — — — — — — 31 120 380 940 12 13,000 24 94 300 720 12 20,000 20 79 250 610 12 26,000 — — — — — — — 18 72 230 500 15 15,000 40 130 310 15 25,000 31 96 240 15 38,000 — — — — — — — — 26 81 200 15 50,000 24 74 180

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

a. The developed length shall be measured from the vent connection to the open air.

906.2 Vents other than stack vents or vent stacks.

The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 710.1(2) . Vent pipes shall not be less than 1 1/4 inches (32 mm) in diameter. Vents shall be sized in accordance with Table 906.1 utilizing the drainage fixture units and the corresponding developed length. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 908.2.

906.3 Developed length.

The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.

906.4 Multiple branch vents.

Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit load being vented.

906.5 Ejector vents.

Ejector vent sizes shall be determined in accordance with Sections 906.5.1 and 906.5.2.

906.5.1 Sewage pumps and sewage ejectors other than pneumatic.

Drainage piping below sewer level shall be vented in the same manner as that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 906.5.1 . Where a building sump vent connects to a sanitary vent system, the sanitary branch vent shall be at least 3 inches (76 mm) in diameter.

Table 906.5.1 Size and Length of Sump Vents

Discharge Capacity of Pump (gpm) Maximum Developed Length of Vent (feet) a Diameter of vent (inches) 1 1/4 1 1/2 2 2 1/2 3 4 10 No limit b No limit No limit No limit No limit No limit 20 270 No limit No limit No limit No limit No limit 40 72 160 No limit No limit No limit No limit 60 31 75 270 No limit No limit No limit 80 16 41 150 380 No limit No limit 100 10 c 25 97 250 No limit No limit 150 Not permitted 10 c 44 110 370 No limit 200 Not permitted Not permitted 20 60 210 No limit 250 Not permitted Not permitted 10 36 132 No limit 300 Not permitted Not permitted 10 c 22 88 380 400 Not permitted Not permitted Not permitted 10 c 44 210 500 Not permitted Not permitted Not permitted Not permitted 24 130

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.

a. Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances shall be obtained from NBS Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not available.

b. Actual values greater than 500 feet.

c. Less than 10 feet.

906.5.2 Pneumatic sewage ejectors.

The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure, but shall be not less than 1 1/2 inches (38 mm) in size.

Section PC 907. Vents for Stack Offsets

Open this section

907.1 Vent for horizontal offset of drainage stack.

Horizontal offsets of drainage stacks shall be vented where five or more branch intervals are located above the offset. The offset shall be vented by venting the upper section of the drainage stack and the lower section of the drainage stack.

907.2 Upper section.

The upper section of the drainage stack shall be vented as a separate stack with a vent stack connection installed in accordance with Section 904.4. The offset shall be considered the base of the stack.

907.3 Lower section.

The lower section of the drainage stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch. The yoke vent connection shall be permitted to be a vertical extension of the drainage stack. The size of the yoke vent and connection shall be a minimum of the size required for the vent stack of the drainage stack.

Section PC 908. Relief Vents – Stacks of More than 10 Branch Intervals

Open this section

908.1 Where required.

Soil and waste stacks in buildings having more than 10 branch intervals shall be provided with a relief vent at each tenth interval installed, beginning with the top floor.

908.2 Size and connection.

The size of the relief vent shall be equal to the size of the vent stack to which it connects. The lower end of each relief vent shall connect to the soil or waste stack through a wye below the horizontal branch serving the floor, and the upper end shall connect to the vent stack through a tee or inverted wye not less than 3 feet (914 mm) above the floor.

Section PC 909. Fixture Vents

Open this section

909.1 Distance of trap from vent.

Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in Table 909.1 .

Exception: The developed length of the fixture drain from the trap weir to the vent fitting for self- siphoning fixtures, such as water closets, shall not be limited.

Table 909.1 Maximum Distance of Fixture Trap from Vent

Size of Trap (inches) Slope (inch per foot) Distance from Trap (feet) 1 1/4 1/4 5 1 1/2 1/4 6 2 1/4 8 3 1/8 12 4 1/8 16

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 inch per foot = 83.3 mm/m.

909.2 Venting of fixture drains.

The vent for a fixture drain, except where serving a fixture with integral traps, such as water closets, shall connect above the weir of the fixture trap being vented.

909.3 Crown vent.

A vent shall not be installed within two pipe diameters of the trap weir .

Section PC 910. Individual Vent

Open this section

910.1 Individual vent permitted.

Each trap and trapped fixture is permitted to be provided with an individual vent. The individual vent shall connect to the fixture drain of the trap or trapped fixture being vented in accordance with Section 909.1, but at a distance not to exceed 16 feet (4876 mm).

910.2 Floor drain vents.

No vents will be required for piping serving floor drains when the floor drain is located not more than 15 feet (4572 mm) from the vented line to which it connects.

Section PC 911. Common Vent

Open this section

911.1 Individual vent as common vent.

An individual vent is permitted to vent two traps or trapped fixtures as a common vent. The traps or trapped fixtures being common vented shall be located on the same floor level.

911.2 Connection at the same level.

Where the fixture drains being common vented connect at the same level, the vent connection shall be at the interconnection of the fixture drains.

Exception: Where wet vents are permitted by this code, the wet vent connection may be located downstream of the interconnection.

911.3 Connection at different levels.

Where the fixture drains connect at different levels, the vent shall connect as a vertical extension of the vertical drain. The vertical drain pipe connecting the two fixture drains shall be considered the vent for the lower fixture drain, and shall be sized in accordance with Table 911.3 . The upper fixture shall not be a water closet.

Table 911.3 Common Vent Sizes

Pipe Size (inches) Maximum Discharge from Upper Fixture Drain (dfu) 1 1/2 1 2 4 2 1/2 to 3 6

For SI: 1 inch = 25.4 mm.

Section PC 912. Wet Venting

Open this section

912.1 Horizontal wet vent permitted.

Any combination of fixtures within one bathroom group located in the same room is permitted to be vented by a horizontal wet vent. The wet vent shall be considered the vent for the fixtures and shall extend from the connection of the dry vent along the direction of the flow in the drain pipe to the most downstream fixture drain connection to the horizontal branch drain. Each wet-vented fixture drain shall connect independently to the horizontal wet vent. Only the fixtures within the bathroom groups shall connect to the wet-vented horizontal branch drain. Any additional fixtures shall discharge downstream of the horizontal wet vent.

912.1.1 Vertical wet vent permitted.

Any combination of fixtures within one bathroom group is permitted to be vented by a vertical wet vent. The vertical wet vent shall be considered the vent for the fixtures and shall extend from the connection of the dry vent down to the lowest fixture drain connection. Each wet-vented fixture shall connect independently to the vertical wet vent. Fixture drains shall connect above or at the same elevation as the water closet fixture drain. The dry-vent connection to the vertical wet vent shall be an individual or common vent serving one or two fixtures.

912.2 Dry-vent connection.

The required dry-vent connection for wet-vented systems shall comply with Sections 912.2.1 and 912.2.2.

912.2.1 Horizontal wet vent.

The dry-vent connection for a horizontal wet-vent system shall be an individual vent or a common vent for any bathroom group fixture, except an emergency floor drain. Where the dry-vent connects to a water closet fixture drain, the drain shall connect horizontally to the horizontal wet-vent system. Not more than one wet-vented fixture drain shall discharge upstream of the dry-vented fixture drain connection.

912.2.2 Vertical wet vent.

The dry-vent connection for a vertical wet-vent system shall be an individual vent or common vent for the most upstream fixture drain.

912.3 Size.

The dry vent serving the wet vent shall be sized based on the largest required diameter of pipe within the wet-vent system served by the dry vent. The wet vent shall be of a size not less than that specified in Table 912.3 , based on the fixture unit discharge to the wet vent.

Table 912.3 Wet Vent Size

Minimum Wet Vent Pipe Size (inches) Maximum Drainage Fixture Unit Load (dfu) 2 4 2 1/2 6 3 12

For SI: 1 inch = 25.4 mm.

Section PC 913. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section PC 913 at American Legal Publishing.

Section PC 914. Circuit Venting

Open this section

914.1 Circuit vent permitted.

A maximum of eight fixtures connected to a horizontal branch drain shall be permitted to be circuit vented. Each fixture drain shall connect horizontally to the horizontal branch being circuit vented. The horizontal branch drain shall be classified as a vent from the most downstream fixture drain connection to the most upstream fixture drain connection to the horizontal branch.

914.1.1 Multiple circuit-vented branches.

Circuit-vented horizontal branch drains are permitted to be connected together. Each group of a maximum of eight fixtures shall be considered a separate circuit vent and shall conform to the requirements of this section.

914.2 Vent connection.

The circuit vent connection shall be located between the two most upstream fixture drains. The vent shall connect to the horizontal branch and shall be installed in accordance with Section 905 . The circuit vent pipe shall not receive the discharge of any soil or waste.

914.3 Slope and size of horizontal branch.

The slope of the vent section of the horizontal branch drain shall be not greater than one unit vertical in 12 units horizontal ( 8.3-percent slope). The entire length of the vent section of the horizontal branch drain shall be sized for the total drainage discharge to the branch.

914.3.1 Size of multiple circuit vent.

Each separate circuit-vented horizontal branch that is interconnected shall be sized independently in accordance with Section 914.3. The downstream circuit-vented horizontal branch shall be sized for the total discharge into the branch, including the upstream branches and the fixtures within the branch.

914.4 Relief vent.

A relief vent shall be provided for circuit-vented horizontal branches receiving the discharge of four or more water closets and connecting to a drainage stack that receives the discharge of soil or waste from upper horizontal branches.

914.4.1 Connection and installation.

The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain of the circuit vent. The relief vent shall be installed in accordance with Section 905 .

914.4.2 Fixture drain or branch.

The relief vent is permitted to be a fixture drain or fixture branch for fixtures located within the same branch interval as the circuit-vented horizontal branch. The maximum discharge to a relief vent shall be four fixture units.

914.5 Additional fixtures.

Fixtures, other than the circuit-vented fixtures, are permitted to discharge to the horizontal branch drain. Such fixtures shall be located on the same floor as the circuit-vented fixtures and shall be either individually or common vented.

Section PC 915. Combination Waste and Vent System

Open this section

915.1 Types of fixtures.

A combination waste and vent system shall not serve fixtures other than floor drains, lavatories and drinking fountains. Combination waste and vent systems shall not receive the discharge from a food waste disposer or clinical sink.

915.2 Installation.

The combination waste and vent system shall be a horizontal piping system. The only vertical pipe of a combination waste and vent system shall be the connection between the fixture drain and the horizontal combination waste and vent pipe. The vertical distance shall not exceed 8 feet (2438 mm).

915.2.1 Slope.

The slope at a horizontal combination waste and vent pipe shall not exceed one-half unit vertical in 12 units horizontal (4-percent slope) and shall not be less than indicated in Table 704.1 .

915.2.2 Size and length.

The size of a combination waste and vent pipe shall be not less than that indicated in Table 915.2.2 . The horizontal length of a combination waste and vent system shall be unlimited.

Table 915.2.2 Size of Combination Waste and Vent Pipe

Diameter Pipe (inches) Maximum Number of Drainage Fixture Units (dfu) Connecting to a horizontal branch or stack Connecting to a building drain or building subdrain 2 3 4 2 1/2 6 26 3 12 31 4 20 50 5 160 250 6 360 575

For SI: 1 inch = 25.4 mm.

915.2.3 Connection.

The combination waste and vent system shall be provided with a dry vent connected at any point within the system or the system shall connect to a horizontal drain that serves vented fixtures located on the same floor. Combination waste and vent systems connecting to building drains receiving only the discharge from one or more stacks shall be provided with a dry vent. The vent connection to the combination waste and vent pipe shall extend vertically to a point not less than 6 inches (152 mm) above the flood level rim of the highest fixture being vented before offsetting horizontally.

915.2.4 Vent size.

The vent shall be sized for the total drainage fixture unit load in accordance with Section 906.2.

915.2.5 Fixture branch or drain.

The fixture branch or fixture drain shall connect to the combination waste and vent within a distance specified in Table 909.1 . The combination waste and vent pipe shall be considered the vent for the fixture.

Section PC 916. Island Fixture Venting

Open this section

916.1 Limitation.

Island fixture venting shall not be permitted for fixtures other than sinks and lavatories. Residential kitchen sinks with a dishwasher waste connection, a food waste disposer, or both, in combination with the kitchen sink waste, shall be permitted to be vented in accordance with this section.

916.2 Vent connection.

The island fixture vent shall connect to the fixture drain as required for an individual or common vent. The vent shall rise vertically to above the drainage outlet of the fixture being vented before offsetting horizontally or vertically downward. The vent or branch vent for multiple island fixture vents shall extend to a point not less than 6 inches (152 mm) above the highest island fixture being vented before connecting to the outside vent terminal.

916.3 Vent installation below the fixture flood level rim.

The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7 , except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout.

Section PC 917. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section PC 917 at American Legal Publishing.

Section PC 918. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section PC 918 at American Legal Publishing.

Section PC 919. Engineered Vent Systems

Open this section

919.1 General

Engineered vent systems shall comply with this section and Section 28-113.2.2 of the Administrative Code .

919.2 Individual branch fixture and individual fixture header vents.

The maximum developed length of individual fixture vents to vent branches and vent headers shall be determined in accordance with Table 919.2 for the minimum pipe diameters at the indicated vent airflow rates.

The individual vent airflow rate shall be determined in accordance with the following:

Q h,b = N n,b Q v (Equation 9-1)

For SI: Q h,b = N n,b Q v (0.4719 L/s)

where:

N n,b = Number of fixtures per header (or vent branch) ÷ total number of fixtures connected to vent stack.

Q h,b = Vent branch or vent header airflow rate (cfm).

Q v = Total vent stack airflow rate (cfm).

Q v (gpm) = 27.8 r s 2/3 (1 - r s ) D 8/3

Q v (cfm) = 0.134 Q v (gpm)

where:

D = Drainage stack diameter (inches).

Q w = Design discharge load (gpm).

r s = Waste water flow area to total area.

= Q w / 27.8 D 8/3

Individual vent airflow rates are obtained by equally distributing Q h,b into one-half the total number of fixtures on the branch or header for more than two fixtures; for an odd number of total fixtures, decrease by one; for one fixture, apply the full value of Q h,b .

Individual vent developed length shall be increased by 20 percent of the distance from the vent stack to the fixture vent connection on the vent branch or header.

Table 919.2 Minimum Diameter and Maximum Length of Individual Branch Fixture Vents and Individual Fixture Header Vents for Smooth Pipes

Diameter of Vent Pipe (inches) Individual Vent Airflow Rate (cubic feet per minute) Maximum developed length of vent (feet) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1/2 95 25 13 8 5 4 3 2 1 1 1 1 1 1 1 1 1 1 1 1 3/4 100 88 47 30 20 15 10 9 7 6 5 4 3 3 3 2 2 2 2 1 1 — — 100 94 65 48 37 29 24 20 17 14 12 11 9 8 7 7 6 6 1 1/4 — — — — — — — 100 87 73 62 53 46 40 36 32 29 26 23 21 1 1/2 — — — — — — — — — — — 100 96 84 75 65 60 54 49 45 2 — — — — — — — — — — — — — — — — — — — 100

For SI: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.4719 L/s, 1 foot = 304.8 mm

919.3 A Licensed Professional Engineer shall certify design.

An engineer shall also inspect and certify the system upon completion of the system.

Section PC 920. Computerized Vent Design

Open this section

920.1 Design of vent system.

The sizing, design and layout of the vent system shall be permitted to be determined by computer program design methods which shall be approved by the commissioner to insure compliance with the minimum standards of this code.

920.2 System capacity.

The vent system shall be based on the air capacity requirements of the drainage system under a peak load condition.

920.3 Design shall be certified by a Licensed Professional Engineer.

An engineer shall also inspect and certify the system upon completion of the system.

Section PC 1001. General

Open this section

1001.1 Scope.

This chapter shall govern the material and installation of traps, interceptors and separators.

Section PC 1002. Trap Requirements

Open this section

1002.1 Fixture traps.

Each plumbing fixture shall be separately trapped by a liquid-seal trap, except as otherwise permitted by this code. The vertical distance from the fixture outlet to the trap weir shall not exceed 48 inches (1220 mm), and the horizontal distance shall not exceed 30 inches (762 mm) measured from the centerline of the fixture outlet to the centerline of the inlet of the trap. The height of a clothes washer standpipe above a trap shall conform to Section 802.3.3. A fixture shall not be double trapped.

Exceptions:

1. This section shall not apply to fixtures with integral traps.

2. A combination plumbing fixture is permitted to be installed on one trap provided that one compartment is not more than 6 inches (152 mm) deeper than the other compartment and the waste outlets are not more than 30 inches (762 mm) apart.

3. A grease interceptor intended to serve as a fixture trap in accordance with the manufacturer's installation instructions shall be permitted to serve as the trap for a single fixture or a combination sink of not more than three compartments where the vertical distance from the fixture outlet to the inlet of the interceptor does not exceed 30 inches (762 mm), and the developed length of the waste pipe from the most upstream fixture outlet to the inlet of the interceptor does not exceed 60 inches (1524 mm).

4. Floor drains in multilevel parking structures that discharge to a building storm sewer shall not be required to be individually trapped. Where floor drains in multilevel parking structures are required to discharge to a combined building sewer system, the floor drains shall not be required to be individually trapped provided that they are connected to a main trap in accordance with Section 1103.1.

5. This section shall not apply to outdoor drinking fountains discharging to a drywell.

6. This section shall not apply where local acid neutralizing systems are utilized in accordance with the rules of the Department of Environmental Protection and Section 803.2 of this code.

1002.2 Design of traps.

Fixture traps shall be self-scouring. Fixture traps shall not have interior partitions, except where such traps are integral with the fixture or where such traps are constructed of an approved material that is resistant to corrosion and degradation. Slip joints shall be made with an approved elastomeric gasket and shall be installed only on the trap inlet, trap outlet and within the trap seal.

1002.3 Prohibited traps.

The following types of traps are prohibited:

1. Traps that depend on moving parts to maintain the seal.

2. Bell, pot, bottle traps and traps with interior partitions.

3. Crown-vented traps.

4. Traps not integral with a fixture and that depend on interior partitions for the seal, except those traps constructed of an approved material that is resistant to corrosion and degradation.

5. "S" traps.

6. Drum traps.

Exception: Drum traps used as solids interceptors and drum traps serving chemical waste systems shall be permitted.

1002.4 Trap seals.

Each fixture trap shall have a liquid seal of not less than 2 inches (51 mm) and not more than 4 inches (102 mm), or deeper for special designs relating to accessible fixtures.

1002.4.1 Trap seal protection.

Trap seals of emergency floor drain traps and trap seals subject to evaporation shall be protected by one of the methods in Sections 1002.4.1.1 through 1002.4.1.3.

1002.4.1.1 Potable water-supplied trap seal primer valve.

A potable water-supplied trap seal primer valve shall supply water to the trap. Water-supplied trap seal primer valves shall conform to ASSE 1018. The discharge pipe from the trap seal primer valve shall connect to the trap above the trap seal on the inlet side of the trap.

1002.4.1.2 Reclaimed or gray water-supplied trap seal primer valve.

A reclaimed or gray water-supplied trap seal primer valve shall supply water to the trap. Water-supplied trap seal primer valves shall conform to ASSE 1018. The quality of reclaimed or gray water supplied to trap seal primer valves shall be in accordance with the requirements of the manufacturer of the trap seal primer valve and this code. The discharge pipe from the trap seal primer valve shall connect to the trap above the trap seal, on the inlet side of the trap.

1002.4.1.3 Manual water-supplied trap priming.

A hose bib or similar manually operated plumbing fixture shall be provided within the same room and within a horizontal distance not to exceed 25 feet (7620 mm) and not more than 3 feet (914 mm) above the floor.

1002.5 Size of fixture traps.

Fixture trap size shall be sufficient to drain the fixture rapidly and not less than the size indicated in Table 709.1. A trap shall not be larger than the drainage pipe into which the trap discharges.

1002.6 Building traps.

Building (house) traps shall be installed on all building drains near the foundation wall of the structure, inside of the street line, and on the sewer side of all connections except the connection used to receive the discharge from a sewage ejector, oil separator or leader on combined systems. If such trap is placed outside of the foundation wall or below a cellar floor, it shall be made accessible in a manhole with a cover, or by extension of the two handholds that shall be provided with cleanouts at the cellar floor or grade. Handhold extensions shall be not more than 18 inches (457 mm) above the centerline of the drain. Building (house) traps shall be the same size as the building drain connected thereto and shall be provided with a fresh air inlet in accordance with Section 703.7.1.

1002.7 Trap setting and protection.

Traps shall be set level with respect to the trap seal and, where necessary, shall be protected from freezing.

1002.8 Recess for trap connection.

A recess provided for connection of the underground trap, such as one serving a bathtub in slab-type construction, shall have sides and a bottom of corrosion-resistant, insect- and vermin-proof construction.

1002.9 Acid-resisting traps.

Where a vitrified clay or other brittleware, acid-resisting trap is installed underground, such trap shall be embedded in concrete extending 6 inches (152 mm) beyond the bottom and sides of the trap.

1002.10 Plumbing in mental health centers.

In mental health centers, pipes and traps shall not be exposed.

Section PC 1003. Interceptors and Separators

Open this section

1003.1 Where required.

Interceptors and separators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the building drainage system, the public sewer, the private sewage system or the sewage treatment plant or processes.

1003.2 Approval.

The size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer's instructions and the requirements of this section based on the anticipated conditions of use. Wastes that do not require treatment or separation shall not be discharged into any interceptor or separator.

1003.3 Grease interceptors.

Grease interceptors shall comply with the requirements of Sections 1003.3.1 through 1003.3.6.

1003.3.1 Grease interceptors and automatic grease removal devices required.

A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with waste containing fats, oils, or grease located in food preparation areas and shall be in accordance with the requirements of the Department of Environmental Protection. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged.

1003.3.2 Reserved.

1003.3.3 Grease interceptors and automatic grease removal devices not required.

A grease interceptor or an automatic grease removal device shall not be required for individual dwelling units, any private living quarters, or non-culinary schools which only contain residential type stoves and sinks intended for teaching basic home cooking skills.

1003.3.4 Grease interceptor and automatic grease removal device sizing and standards.

Grease interceptors and automatic grease removal devices shall be sized in accordance with the rules of the Department of Environmental Protection. Grease interceptors and automatic grease removal devices shall be designed and tested in accordance with PDI G101, ASME A112.14.3 or ASME A112.14.4 and shall be installed in accordance with the manufacturer's instructions.

1003.3.4.1 Grease interceptor capacity.

Grease interceptors shall have a grease retention capacity in accordance with the rules of the Department of Environmental Protection.

1003.3.4.2 Rate of flow controls.

Grease interceptors shall be equipped with devices to control the rate of water flow so that the water flow does not exceed the rated flow. The flow-control device shall be vented and terminate not less than 6 inches (152 mm) above the flood rim level or be installed in accordance with the manufacturer's instructions.

1003.3.5 Automatic grease removal devices.

Where automatic grease removal devices are installed, such devices shall be located downstream of each fixture or multiple fixtures in accordance with the manufacturer's instructions. The automatic grease removal device shall be sized to pretreat the measured or calculated flows for all connected fixtures or equipment in accordance with the sizing requirements of the Department of Environmental Protection. Ready access shall be provided for inspection and maintenance.

1003.3.6 Direct connection.

The discharge piping from a grease interceptor shall be directly connected to the sanitary drainage system.

1003.4 Oil separators required.

At repair garages where floor or trench drains are provided, car washing facilities with engine or undercarriage cleaning capability, factories where oily and flammable liquid wastes are produced and hydraulic elevator pits, oil separators shall be installed into which oil-bearing, grease-bearing or flammable wastes shall be discharged before emptying into the building drainage system or other point of disposal.

Exception: An oil separator is not required in hydraulic elevator pits where an automatic shut-down system is installed for the prevention of accidental discharge of oil-laden waste water into the sanitary system. Such systems shall not terminate the operation of pumps utilized to maintain emergency operation of the elevator by fire fighters.

1003.4.1 Separation of liquids.

A mixture of treated or untreated light and heavy liquids with various specific gravities shall be separated in an approved receptacle.

1003.4.2 Oil separator design.

Oil separators shall be listed and labeled, or designed in accordance with Sections 1003.4.2.1 and 1003.4.2.2.

1003.4.2.1 General design requirements.

Oil separators shall have a depth of not less than 2 feet (610 mm) below the invert of the discharge drain. The outlet opening of the separator shall have not less than an 18-inch (457 mm) water seal.

1003.4.2.2 Garages and service stations.

Where automobiles are serviced, greased, repaired or washed or where gasoline is dispensed, oil separators shall have a capacity of not less than 6 cubic feet (0.168 m 3 ) for the first 100 square feet (9.3 m 2 ) of area to be drained, plus 1 cubic foot (0.028 m 3 ) for each additional 100 square feet (9.3 m 2 ) of area to be drained into the separator. Parking garages in which servicing, repairing or washing is not conducted, and in which gasoline is not dispensed, shall not require a separator. Areas of commercial garages utilized only for storage of automobiles are not required to be drained through a separator.

1003.5 Sand interceptors in commercial establishments.

Sand and similar interceptors for heavy solids shall be designed and located so as to be provided with ready access for cleaning, and shall have a water seal of not less than 6 inches (152 mm).

1003.6 Clothes washer discharge interceptor.

Clothes washers shall discharge through an interceptor that is provided with a wire basket or similar device, removable for cleaning, that prevents passage into the drainage system of solids 1/2 inch (12.7 mm) or larger in size, string, rags, buttons or other materials detrimental to the public sewage system.

Exceptions:

1. Clothes washers in individual dwelling units shall not be required to discharge through an interceptor.

2. A single clothes washer designed for use in individual dwelling units and installed in a location other than an individual dwelling unit shall not be required to discharge through an interceptor.

1003.7 Bottling establishments.

Bottling plants shall discharge process wastes into an interceptor that will provide for the separation of broken glass or other solids before discharging waste into the drainage system.

1003.8 Slaughterhouses.

Slaughtering room and dressing room drains shall be equipped with approved separators. The separator shall prevent the discharge into the drainage system of feathers, entrails and other materials that cause clogging.

1003.9 Venting of interceptors and separators.

Interceptors and separators shall be designed so as not to become air bound. Interceptors and separators shall be vented in accordance with one of the methods in Chapter 9 .

1003.10 Access and maintenance of interceptors and separators.

Access shall be provided to each interceptor and separator for service and maintenance, and for inspection by the department and the Department of Environmental Protection. Interceptors and separators shall be maintained by periodic removal of accumulated grease, scum, oil, or other floating substances and solids deposited in the interceptor or separator.

Section PC 1004. Materials, Joints and Connections

Open this section

1004.1 General.

The materials and methods utilized for the construction and installation of traps, interceptors and separators shall comply with this chapter and the applicable provisions of Chapters 4 and 7 . The fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow of the piping.

Section PC 1101. General

Open this section

This section has 3 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section PC 1101 at American Legal Publishing.

1101.1 Scope.

The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be in accordance with Department of Environmental Protection requirements. Extension requirements from the public storm or combined sewer to the building sewer shall be determined by the Department of Environmental Protection.

1101.2 Where required.

All roofs, paved areas, yards, courts and courtyards shall drain into a separate storm sewer system, or a combined sewer system, or to a place of disposal approved by the commissioner and in accordance with the requirements of the Department of Environmental Protection. An approved system for beneficial collection and use of storm water may be installed, in which case overflow from such a system shall be discharged to a safe location subject to the approval of the commissioner and the Department of Environmental Protection. See Section 107.6.2 of this code for required construction documents relating to provisions for discharge for stormwater runoff.

1101.2.1 Increases in existing impervious surfaces.

Whenever impervious surfaces on the lot are increased, such impervious surfaces shall drain into a storm sewer system, or a combined sewer system, or to an approved place of disposal.

Exception: An existing one- or two-family dwelling where the area of a proposed horizontal building enlargement plus any proposed increase in impervious surfaces in total is less than or equal to 200 square feet (19 m 2 ). In such cases, the storm water discharge may be accommodated by existing facilities. For the purposes of this exception, the 200 square feet (19 m 2 ) shall include all enlargements and increases cumulatively after July 1, 2008.

1101.2.2 Availability of public storm or combined sewer.

The determination as to whether a public storm sewer or public combined sewer is available to a building shall be made in accordance with applicable requirements of the Department of Environmental Protection.

1101.2.3 Feasibility of connecting to an available public storm or combined sewer.

The determination as to whether connection to an available public storm sewer or combined public sewer is feasible shall be made in accordance with applicable requirements of the Department of Environmental Protection.

1101.2.4 Extensions of public storm or combined sewers.

Extensions of public storm or combined sewers shall be made in accordance with the rules of the Department of Environmental Protection.

1101.3 Prohibited drainage.

Storm water shall not be drained into sewers intended for sewage only.

1101.4 Tests.

The conductors and the building storm drain shall be tested in accordance with Section 312 .

1101.5 Change in size.

The size of a drainage pipe shall not be reduced in the direction of flow.

Exception: Drainage pipe that is part of an approved detention or retention system.

1101.5.1 Detention systems.

Where a detention system is provided, the pipe leaving the detention tank shall be permitted to be reduced to the flow allowed by the Department of Environmental Protection, provided, however, that an emergency overflow shall be provided to protect the building from internal flooding.

1101.5.2 Detention and retention tanks.

Detention and retention tanks located within buildings in flood hazard areas shall be located above the design flood elevation or shall be designed and constructed to withstand the static pressure conditions the system will experience in the event of a flood condition.

1101.5.2.1 Emergency overflow.

Emergency overflow piping shall equal the full size of the incoming storm water flow. Emergency overflows and vent terminations for buildings located in flood hazard areas shall be located above the design flood elevation. Such emergency overflow shall discharge the overflow outside of the building into either of the following locations:

1. The tax lot; or

2. The public sewer, provided that the overflow piping is provided with a vent, of the same diameter as the overflow piping, that terminates on the front wall of the building facing the street and no more than 2 feet (610 mm) above the sidewalk See Figures 1101.5.2.1(1) , 1101.5.2.1(2) and 1101.5.2.1(3) .

Figure 1101.5.2.1(1) Detention Volume & Tank Above Grade (Within Building)

Figure 1101.5.2.1(2) Detention Volume Above Sewer, Tank Below Grade (Within Building)

Figure 1101.5.2.1(3) Detention Volume & Tank Below Grade (Within Building)

1101.6 Fittings and connections.

All connections and changes in direction of the storm drainage system shall be made with approved drainage-type fittings in accordance with Table 706.3 . The fittings shall not obstruct or retard flow in the system.

1101.7 Roof design.

Roofs shall be designed for the maximum possible depth of water that will pond thereon as determined by the relative levels of roof deck and overflow weirs, scuppers, edges or serviceable drains in combination with the deflected structural elements. In determining the maximum possible depth of water, all primary roof drainage means shall be assumed to be blocked. The maximum possible depth of water on the roof shall include the height of the water required above the inlet of the secondary roof drainage means to achieve the required flow rate of the secondary drainage means to accommodate the design rainfall rate as required by Section 1106 .

1101.8 Cleanouts required.

Cleanouts shall be installed in the storm drainage system and shall comply with the provisions of this code for sanitary drainage pipe cleanouts.

Exception: Subsurface drainage system.

1101.9 Backwater valves.

Storm drainage systems shall be provided with backwater valves as required for sanitary drainage systems in accordance with Section 715 .

1101.9.1 Backwater valves in flood hazard areas.

Backwater valves for all buildings located in flood hazard areas shall be installed in storm drainage systems in accordance with the requirements of this code and the additional requirements of Section 7.3.4 of ASCE 24 as modified by Appendix G of the New York City Building Code .

1101.10 Plastic pipe.

Plastic piping and fittings shall not be used.

Exceptions:

1. Plastic piping and fittings may be used in residential buildings five stories or less in height.

2. Corrugated polyethylene and corrugated polypropylene piping and fittings, with a diameter of 12 inches (305 mm) or more may be used in connection with any type of building for underground yard drainage and storm water piping when used outside of the foundation wall of the building and not connecting to any piping system from the interior of the building.

1101.11 Cured-in-place pipe.

Cured-in-place pipe (CIPP) and epoxy spray pipe lining systems shall not be used.

1101.12 Site grading.

Except as otherwise permitted by this code, no person shall perform site grading or land contour work, as defined in Section 19-137 of the Administrative Code , that would cause storm water to flow across sidewalks or onto an adjacent property. Site grading or land contour work performed on the site of a covered development project shall comply with the rules of the Department of Environmental Protection and this code.

Section PC 1102. Materials

Open this section

1102.1 General.

The materials and methods utilized for the construction and installation of storm drainage systems shall comply with this section and the applicable provisions of Chapter 7 .

1102.2 Storm drainage conductors and leaders.

Storm drainage conductors and leaders shall conform to Sections 1102.2.1 and 1102.2.2.

1102.2.1 Inside storm drainage conductors.

Inside storm drainage conductors installed above ground shall conform to one of the standards listed in Table 702.1 .

1102.2.2 Exterior storm drainage leaders.

Exterior storm drainage leaders installed above ground shall conform to one of the standards listed in Table 702.1 .

Exception: Exterior storm drainage leaders installed above ground for buildings in occupancy Group R- 3 and bulkheads draining to other roof surfaces.

1102.3 Underground building storm drain pipe.

Underground building storm drain pipe shall conform to one of the standards listed in Table 702.2 .

1102.4 Building storm sewer pipe.

Building storm sewer pipe shall conform to one of the standards listed in Table 1102.4 .

Table 1102.4 Building Storm Sewer Pipe

Material Standard Cast-iron pipe ASTM A 74; ASTM A 888; CISPI 301 Chlorinated polyvinyl chloride (CPVC) plastic b ASTM F 437; ASTM F 438; ASTM F 439 Concrete pipe ASTM C 14; ASTM C 76; CSA A257.1M; CSA A257.2M Copper or copper-alloy tubing (Type K or L) ASTM B 75; ASTM B 88; ASTM B 251 Ductile-iron pipe AWWA C151 Galvanized steel pipe ASTM A 53; ASTM A 123 High density polyethylene pipe (HDPE) a ASTM D 3350 Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100) b ASTM D 2665; ASTM D 3034; ASTM F 891; CSA B182.4; CSA B181.2; CSA B182.2 Stainless steel drainage systems, Type 316L ASME A112.3.1 Vitrified clay pipe ASTM C 4; ASTM C 700

a. Approved plastic sewer for piping 12 inches and larger in accordance with Section 1101.10, Exception 2.

b. Limited to residential buildings five stories or less in height.

1102.5 Subsoil drain pipe.

Subsoil drains shall be open jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table 1102.5 .

Table 1102.5 Subsoil Drain Pipe

Material Standard Cast-iron pipe ASTM A 74; ASTM A 888; CISPI 301 Polyethylene (PE) plastic pipe ASTM F 405; CSA B182.1; CSA B182.6; CSA B182.8 Polypropylene (PP) plastic pipe ASTM F 2764; ASTM F 3219 Polyvinyl chloride (PVC) Plastic pipe (type sewer pipe, SDR35, PS25, PS50 or PS100) a ASTM D 2729; ASTM D 3034; ASTM F 891; CSA B182.2; CSA B182.4 Porous concrete pipe ASTM C 654 Stainless steel drainage systems, Type 316L ASME A112.3.1 Vitrified clay pipe ASTM C 4; ASTM C 700

a. Limited to residential buildings five stories or less in height.

1102.6 Roof drains.

Roof drains shall conform to ASME A112.6.4 or ASME A112.3.1.

1102.7 Fittings.

Pipe fittings shall be approved for installation with the piping material installed, and shall conform to the respective pipe standards or one of the standards listed in Table 1102.7 . The fittings shall not have ledges, shoulders or reductions capable of retarding or obstructing flow in the piping. Threaded drainage pipe fittings shall be of the recessed drainage type.

Table 1102.7 Pipe Fittings

Material Standard Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters a ASTM D 2661; ASTM F 628; CSA B181.1 Acrylonitrile butadiene styrene (ABS) plastic pipe in sewer and drain diameters ASTM D 2751 Brass ASTM B 62 Cast-iron ASME B16.4; ASME B16.12; ASTM A 888; CISPI 301; ASTM A 74 Chlorinated polyvinyl chloride (CPVC) plastic a ASTM F 437; ASTM F 438; ASTM F 439 Copper or copper-alloy tubing (Type K, L) ASTM B 75; ASTM B 88; ASTM B 251 Ductile iron AWWA C110 Galvanized steel ASTM A 153; ASME B16.3 High-density polyethylene (HDPE) ASTM D 3350 Malleable iron ASME B16.3 Polyethylene (PE) plastic pipe a ASTM F 2306 / F 2306M Polyolefin a CSA B181.3; ASTM F 1412; ASTM D 2657 Polypropylene (PP) plastic pipe a ASTM F 2764; ASTM F 3219 Polyvinyl chloride (PVC) plastic a ASTM D 2464; ASTM D 2466; ASTM D 2467; CSA B137.2; ASTM D 2665; ASTM D 3311; ASTM F 1866 Polyvinyl chloride (PVC) plastic pipe in sewer and drain diameters a ASTM D 3034 Polyvinylidene fluoride (PVDF) plastic pipe a ASTM F 1673; CSA B181.3 Stainless steel drainage systems, Type 316L ASME A112.3.1 Vitrified clay ASTM C 425

a. Limited to residential buildings five stories or less in height.

Section PC 1103. Traps

Open this section

1103.1 Main trap.

Leaders and storm drains connected to a combined sewer shall be trapped. Individual storm water traps shall be installed on the storm water drain branch serving each conductor, or a single trap shall be installed in the main storm drain just before its connection with the combined building sewer or the public sewer. A hooded catch basin located within the property line shall be the equivalent of a building-house trap for the connection to a public sewer.

1103.2 Material.

Storm water traps shall be of an approved material in accordance with Table 1102.7 .

1103.3 Size.

Traps for individual conductors shall be the same size as the horizontal drain to which they are connected.

1103.4 Cleanout.

An accessible cleanout shall be installed on the building side of the trap.

Section PC 1104. Conductors and Connections

Open this section

1104.1 Prohibited use.

Conductor pipes shall not be used as soil, waste or vent pipes, and soil, waste or vent pipes shall not be used as conductors.

1104.2 Floor drains.

Floor drains shall not be connected to a storm drain.

1104.3 Combining storm with sanitary drainage.

The sanitary and storm drainage systems of a structure shall be entirely separate except for minor modifications to existing buildings having combined systems. Where a combined building drain is utilized, the building storm drain shall be connected in the same horizontal plane through a single-wye fitting to the building drain at least 10 feet (3048 mm) downstream from any soil stack. If a separate city storm sewer is not available, building sanitary drains shall be separate and shall only be permitted to connect to a common building combined drain downstream of building (house) trap.

1104.4 Clear water drains.

Drains carrying clear water, i.e., air-conditioning drips, pump drips, cooling water, etc., may discharge into the storm water drainage system through an indirect waste connection discharging into a trapped funnel or raised lip floor drain.

Exception: Cooling tower blow-down shall discharge into the sanitary drainage system.

1104.5 Parking garage floor drains.

Floor drains provided in open or enclosed parking garages shall drain to the storm drainage system.

Exception: Where the storm drainage system discharges to a dedicated storm sewer, parking garage floor drains shall be connected to the sanitary drainage system.

Section PC 1105. Roof Drains

Open this section

1105.1 General.

Roof drains shall be installed in accordance with the manufacturer's instructions. The inside opening for the roof drain shall not be obstructed by the roofing membrane material.

1105.2 Roof drain flow rate.

The published roof drain flow rate, based on the head of water above the roof drain, shall be used to size the storm drainage system in accordance with Section 1106 . The flow rate used for sizing the storm drainage piping shall be based on the maximum anticipated ponding at the roof drain.

Section PC 1106. Size of Conductors, Leaders and Storm Drains

Open this section

1106.1 General.

The size of the vertical conductors and leaders, gutters, building storm drains, building storm sewers and any horizontal branches of such drains or sewers shall be based on the 100-year hourly rainfall rate of 3 inches (76 mm) per hour. Sizing for secondary and combined primary and secondary conductors, leaders and drains shall be in accordance with Section 1108 .

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

1106.2 Size of storm drain piping.

Vertical and horizontal storm drain piping shall be sized based on the flow rate through the roof drain. The flow rate in storm drain piping shall not exceed that specified in Table 1106.2 .

Table 1106.2 Storm Drain Pipe Sizing

Pipe Size (inches) Capacity (gpm) Vertical Drain Slope of Horizontal Drain 1/16 inch per foot 1/8 inch per foot 1/4 inch per foot 1/2 inch per foot 2 34 15 22 31 44 3 87 39 55 79 111 4 180 81 115 163 231 5 311 117 165 234 331 6 538 243 344 487 689 8 1,117 505 714 1,010 1,429 10 2,050 927 1,311 1,855 2,623 12 3,272 1,480 2,093 2,960 4,187 14 4,204 1,312 1,856 2,621 3,713 15 5,543 2,508 3,546 5,016 7,093 16 5,543 2,508 3,546 5,016 7,093 18 8.218 3,100 4,386 6,192 8,773

1106.2.1 Values for continuous flow.

Where there is a continuous or semicontinuous discharge into the building storm drain or building storm sewer, such as from a pump, ejector, air conditioning plant or similar device, each gallon per minute of such discharge shall be computed as being equivalent to 32 square feet (2.97 m 2 ) of roof area, based on a rainfall rate of 3 inches (75 mm) per hour.

1106.3 Vertical leader sizing.

Vertical leaders shall be sized based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through vertical leaders shall not exceed that specified in Table 1106.3 .

Table 1106.3 Vertical Leader Sizing

Size of Leader (inches) Capacity (gpm) 2 30 2 × 2 30 1 1/2 × 2 1/2 30 2 1/2 54 2 1/2 × 2 1/2 54 3 92 2 × 4 92 2 1/2 × 3 92 4 192 3 × 4 1/4 192 3 1/2 × 4 192 5 360 4 × 5 360 4 1/2 × 4 1/2 360 6 563 5 × 6 563 5 1/2 × 5 1/2 563 8 1208 6 × 8 1208

For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.

1106.4 Vertical walls.

In sizing roof drains and storm drainage piping, one-fourth of the area of any vertical wall that diverts rainwater to the roof or the setback roof of a building shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping.

Exceptions:

1. Where vertical conductors or leaders and downstream piping has been sized for secondary roof drainage in accordance with Section 1108 , the contribution from vertical walls need not be added to the projected roof area.

2. Section 1106.4 shall not be applicable to vertical walls fronting a public right-of-way.

1106.5 Parapet wall scupper location.

Parapet wall roof drainage scupper and overflow scupper location shall comply with the requirements of Section 1503.4 of the New York City Building Code .

1106.6 Size of roof gutters.

Horizontal gutters shall be sized based on the flow rate from the roof surface. The flow rate in horizontal gutters shall not exceed that specified in Table 1106.6 .

Table 1106.6 Horizontal Gutter Sizing

Gutter Dimensions a (inches) Slope (inch per foot) Capacity (gpm) 1 1/2 × 2 1/2 1/4 26 1 1/2 × 2 1/2 1/2 40 4 1/8 39 2 1/4 × 3 1/4 55 2 1/4 × 3 1/2 87 5 1/8 74 4 × 2 1/2 1/4 106 3 × 3 1/2 1/2 156 6 1/8 110 3 × 5 1/4 157 3 × 5 1/2 225 8 1/16 172 8 1/8 247 4 1/2 × 6 1/4 348 4 1/2 × 6 1/2 494 10 1/16 331 10 1/8 472 5 × 8 1/4 651 4 × 10 1/2 1055

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 inch per foot = 83.3 mm/m.

a. Dimensions are width by depth for rectangular shapes. Single dimensions are diameters of a semicircle.

Section PC 1107. Siphonic Roof Drainage Systems

Open this section

1107.1 General.

Siphonic roof drains and drainage systems shall be designed in accordance with ASME A112.6.9 and ASPE 45.

Section PC 1108. Secondary (Emergency) Roof Drains

Open this section

1108.1 Secondary (emergency overflow) drains or scuppers.

Where roof drains are required, secondary (emergency overflow) roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. The inlet elevation of secondary (overflow) drains and the invert elevation of overflow scuppers should be not less than 2 inches (51 mm) or more than 4 inches (102 mm) above the low point of the (adjacent to) roof surface unless a safer water depth loading, including the required hydraulic head to maintain required flow rate out of the overflow drainage system that has been determined by the structural design. Where primary and secondary roof drains are manufactured as a single assembly, the inlet and outlet for each drain shall be independent.

1108.2 Separate systems required.

Secondary roof drain systems shall have the end point of discharge separate from the primary system. Discharge shall be above grade, in a location that would normally be observed by the building occupants or maintenance personnel.

Exception: Secondary drainage system may tie into the primary drainage system in the vertical conductors where separate systems are impractical or to prevent water from flowing over sidewalk or pedestrian walkways.

1108.3 Sizing of secondary drains.

Secondary (emergency) roof drain systems shall be sized in accordance with Section 1106 based on the rainfall rate of 3 inches (76 mm) per hour. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7. Scuppers shall have an opening dimension of not less than 4 inches (102 mm). The flow through the primary system shall not be considered when sizing the secondary roof drain system.

Exception: Where secondary drainage systems tie into primary drainage systems, the combined primary and secondary system shall be sized based on their combined rainfall rate of 6 inches (152 mm) per hour.

Section PC 1109. Combined Sanitary and Storm System

Open this section

1109.1 Size of combined drains and sewers.

Combined sanitary and storm sewers are not permitted in new installations. All sanitary and storm systems shall be separate up to a point located in accordance with the applicable requirements of the Department of Environmental Protection. With respect to repair of combined systems installed prior to the effective date of this section, the size of a combination sanitary and storm drain or sewer shall be computed in accordance with the method in Section 1106 . The fixture units shall be converted into an equivalent projected roof or paved area. Where the total fixture load on the combined drain is less than or equal to 256 fixture units, the equivalent drainage area in horizontal projection shall be taken as 1,333 square feet (124 m 2 ). Where the total fixture load exceeds 256 fixture units, each additional fixture unit shall be considered the equivalent of 5.2 square feet (0.48 m 2 ) of drainage area. These values are based on a rainfall rate of 3 inch (75 mm) per hour.

Section PC 1110. Controlled Flow Roof Drain Systems

Open this section

1110.1 General.

The roof of a structure shall be designed for the storage of water where the storm drainage system is engineered for controlled flow. The controlled flow roof drain system shall be an engineered system in accordance with this section and Section 28-113.2.2 of the Administrative Code . The controlled flow system shall be designed based on the design rainfall rate in accordance with Section 1106.1.

1110.2 Control devices.

The control devices shall be installed so that the rate of discharge of water per minute shall not exceed the values for controlled flow as allowed by the Department of Environmental Protection.

1110.3 Installation.

Runoff control shall be by control devices. Control devices shall be protected by strainers.

1110.4 Minimum number of roof drains.

Not less than two roof drains shall be installed in roof areas 10,000 square feet (929 m 2 ) or less and not less than four roof drains shall be installed in roofs over 10,000 square feet (929 m 2 ) in area.

Section PC 1111. Subsoil Drains

Open this section

1111.1 Subsoil drains.

Subsoil drains carrying groundwater shall be open-jointed, horizontally split or perforated pipe conforming to one of the standards listed in Table 1102.5 . Such drains shall not be less than 4 inches (102 mm) in diameter. Where the building is subject to backwater, the subsoil drain shall be protected by an accessibly located backwater valve. Subsoil drainage discharged into a public sewer shall be approved by the Department of Environmental Protection. The subsoil drains shall discharge into a readily accessible silt and sand interceptor before being connected into the gravity drainage or sump system. Subsoil drainage shall discharge to a trapped area drain, sump, dry well or approved location above ground. The subsoil sump shall not be required to have either a gas-tight cover or a vent. The sump and pumping system shall comply with Section 1113.1.

Section PC 1112. Building Subdrains

Open this section

1112.1 Building subdrains.

Building subdrains located below the public sewer level shall discharge into a sump or receiving tank, the contents of which shall be automatically lifted and discharged into the drainage system as required for building sumps. The sump and pumping equipment shall comply with Section 1113.1.

Section PC 1113. Sumps and Pumping Systems

Open this section

1113.1 Pumping system.

The sump pump, pit and discharge piping shall conform to Sections 1113.1.1 through 1113.1.4.

1113.1.1 Pump capacity and head.

The sump pump shall be of a capacity and head appropriate to anticipated use requirements.

1113.1.2 Sump pit.

The sump pit shall be not less than 18 inches (457 mm) in diameter and not less than 24 inches (610 mm) in depth, unless otherwise approved. The pit shall be accessible and located such that all drainage flows into the pit by gravity. The sump pit shall be constructed of tile, steel, plastic, cast iron, concrete or other approved material, with a removable cover adequate to support anticipated loads in the area of use. The pit floor shall be solid and provide permanent support for the pump.

1113.1.3 Electrical.

Electrical service outlets, when required, shall meet the requirements of the New York City Electrical Code .

1113.1.4 Piping.

Discharge piping shall meet the requirements of Section 1102.2, 1102.3 or 1102.4 and shall include a gate valve and a full flow check valve. Pipe and fittings shall be the same size as, or larger than, the pump discharge tapping.

Exception: In one- and two-family dwellings, only a check valve shall be required, located on the discharge piping from the pump or ejector.

Section PC 1114. Private On-Site Stormwater Disposal Systems

Open this section

This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section PC 1114 at American Legal Publishing.

1114.1 General.

Private on-site stormwater disposal systems shall comply with the provisions of Section 1114 .

1114.1.1 When permitted.

The use of private on-site stormwater disposal systems shall be permitted only in the following circumstances:

1. Pursuant to a certification issued by the New York City Department of Environmental Protection that a public storm or combined sewer is not available or that connection thereto is not feasible in accordance with Section 107.6.2.2, Item 1(i);

2. Pursuant to a certification submitted by the applicant to the New York City Department of Environmental Protection that a public storm or combined sewer is not available or that connection thereto is not feasible, in such cases where the availability and feasibility of connection to a public storm or combined sewer are allowed to be certified by the applicant pursuant to rules of the New York City Department of Environmental Protection, in accordance with Section 107.6.2.2, Item 1(ii);

3. Pursuant to a certification submitted by the applicant to the New York City Department of Environmental Protection authorizing on-site stormwater disposal in accordance with Section 107.6.2.1, Item 1;

4. For enlargements less than 1,000 square feet (93 m 2 ) in accordance with Section 107.6.2, Exception 2;

5. For outdoor drinking fountains; or

6. The disposal of foundation drainage as described in Section 1807.4.3 of the New York City Building Code .

1114.1.2 Acceptable systems.

Acceptable on-site stormwater disposal systems shall include:

1. Drywells;

2. Gravel beds;

3. Perforated pipe;

4. Stormwater chambers that facilitate infiltration; and

5. Alternate method of on-site disposal as approved by the department and the New York City Department of Environmental Protection.

1114.1.3 Minimum setbacks.

On-site stormwater disposal systems shall be located at least 5 feet (1524 mm) from all lot lines except where the lot line abuts a public right of way and 10 feet (3048 mm) from all foundations or walls existing on the date of application for a building permit or proposed under the application to construct the on-site stormwater disposal system. Systems shall be located 20 feet (6096 mm) from disposal fields and 20 feet (6096 mm) from seepage pits. On-site stormwater disposal systems shall not be located within the building footprint.

1114.2 Field investigation.

The size of an on-site stormwater disposal system shall be predicated on a field investigation performed prior to construction document approval that is performed at the site of a proposed on-site stormwater disposal system to assess the suitability of the soil and site. The investigation shall conform to Sections 1114.2.1 and 1114.2.2 and shall occur prior to approval of construction documents for the system. The field investigation shall be subject to special inspection in accordance with Section 1704.21 of the New York City Building Code .

1114.2.1 Classification of soil based on borings and test pits.

At least one boring and one test pit shall be made at the approximate site of each proposed on-site stormwater disposal system. Soil borings and sampling procedures shall in accordance with ASTM D 1586 and ASTM D 1587, and generally accepted engineering practice. Soil and rock samples shall be classified in accordance with Section 1802.3 of the New York City Building Code .

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

1114.2.2 Soil infiltration capabilities.

The suitability of the subsurface soils must be verified in place by either a percolation test or a permeability test. Where testing determines that the infiltration rate of the subsurface soils is less than 1/2 inch (12.7 mm) per hour, private on-site stormwater disposal systems shall not be permitted. Such tests shall conform to Section 1114.2.2.1 or 1114.2.2.2, as applicable.

1114.2.2.1 Percolation tests and procedures.

The infiltration rate of subsurface soils shall be verified with a percolation test. Percolation tests shall be performed in accordance with Sections 1114.2.2.1.1 through 1114.2.2.1.3 under the supervision of a special inspection agency in accordance with Section 1704.21.1 of the New York City Building Code . At least one percolation test in each system area shall be conducted. The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More percolation tests shall be made where necessary, depending on system design. The results of the percolation tests shall be filed with the department stating the suitability of the site and the capacity of the subsoil for the proposed use.

1114.2.2.1.1 Percolation test hole.

The test hole shall be dug or bored. The test hole shall have vertical sides and a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The bottom and sides of the hole shall be scratched with a sharp-pointed instrument to expose the natural soil. All loose material shall be removed from the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.

1114.2.2.1.2 Test procedure, sandy soils.

The hole shall be filled with clear water to a minimum of 12 inches (305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away shall be determined, and this procedure shall be repeated if the water from the second filling of the hole seeps away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6 inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference point, water levels shall be measured at 10-minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth exceed 6 inches (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall be stopped and a rate of less than 3 minutes per inch (7.2 s/mm) shall be reported. The final water level drop shall be used to calculate the percolation rate. Soils not meeting the above requirements shall be tested in accordance with Section 1114.2.2.1.3.

1114.2.2.1.3 Test procedure, other soils.

The hole shall be filled with clear water, and a minimum water depth of 12 inches (305 mm) shall be maintained above the bottom of the hold for a 4-hour period by refilling whenever necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed. Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 hours. Immediately after the soil swelling period, the measurements for determining the percolation rate shall be made as follows: Any soil sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30-minute intervals for a period of 4 hours, unless two successive water level drops do not vary by more than 1/16 inch (1.59 mm). At least three water level drops shall be observed and recorded. The hole shall be filled with clear water to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty. Adjustments of the water level shall not be made during the three measurement periods except to the limits of the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30 minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water depth shall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs during the final measurement period shall be used in calculating the percolation rate.

1114.2.2.2 Permeability tests.

Soil shall be evaluated for estimated percolation based on a permeability test performed in place, in accordance with procedures established by the New York City Department of Environmental Protection and accepted engineering practice.

1114.3 Design.

The design of on-site stormwater disposal systems shall comply with the provisions of Section 1114.3.1.

1114.3.1 Runoff rate.

The runoff rate shall be calculated using the rational method, Equation 11-1. The calculation shall incorporate the total site area with a rainfall intensity value of I = 5.95 inches per hour. The weighted runoff coefficient shall be calculated using Equation 11-2 and shall incorporate the different combinations of surfaces using the C values listed below.

Q = C w × I × A (Equation 11-1)

where:

Q = developed flow, cubic feet per second

C w = weighted runoff coefficient

I = the rainfall intensity value, 5.95 in/hr

A = the total site area, acres (ac)

C w = (1/ A ) S ( A k × C k ) (Equation 11-2)

where:

C w = weighted runoff coefficient

A = The total site area, acres (ac)

A k = The area of each surface coverage type, acres (ac)

C k = The runoff coefficient associated with each surface coverage type

The following C -values shall be used for calculating a site's weighted runoff coefficient:

0.95 = roof/concrete

0.85 = asphalt

0.7 = porous asphalt/concrete or permeable pavers

0.7 = green roof with four or more inches of growing media

0.65 = gravel parking lot

0.3 = undeveloped areas

0.2 = grass areas

0.2 = rain gardens, vegetated swales and other surface green infrastructure practices

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

1114.3.1.1 Storage volume.

The storage volume of an on-site stormwater disposal system shall be measured 3 feet (610 mm) above the level of the water table. The location of the water table shall be verified at the time of the field investigation conducted in accordance with Section 1114.2. Unless otherwise approved by the New York City Department of Environmental Protection, the storage volume of the on-site stormwater disposal system shall accommodate the total stormwater volume calculated in this section. The stormwater volume shall be calculated as follows:

1. Compute the runoff rate using Equations 11-1 and 11-2.

2. Calculate the outflow rate due to infiltration, in cubic feet per second, using Equation 11-3.

3. Calculate the outflow rate, in cubic feet per second per acre, of imperviousness using Equation 11-4.

4. Calculate the duration of the design storm in minutes using Equation 11-5.

5. Calculate the maximum required retention volume using Equation 11-6.

Q inf = ( FA min × i soil ) / 43,200 (Equation 11-3)

where:

Q inf = outflow rate due to infiltration in cubic feet per second

FA min = minimum footprint or surface area of the stormwater disposal system

i soil = soil infiltration rate in inches per hour

Q o = C WT × i x A T (Equation 11-4)

where:

Q o = the average outflow rate in cubic feet per second during the rainfall event

C WT = the weighted runoff coefficient for the tributary area

i = the average rainfall intensity in inches per hour for the event

A T = the area tributary to the detention facility in acres

t V = 0.27 × (C WT × A T /Q DRR ) 0.5 - 15 (Equation 11-5)

where:

t V = the duration of the storm in minutes, with a 10 year return frequency, requiring the maximum detention volume with a variable outflow

C WT = the weighted runoff coefficient for the area tributary to the detention facility

A T = the area tributary to the detention facility in square feet

Q DRR = the detention facility maximum release rate in cubic feet per second

V V = (0.19 × C WT × A t / ( t V + 15) - 40 × Q DRR ) × t V (Equation 11-6)

where:

V V = the maximum required detention volume in cubic feet with a variable outflow

C WT = the weighted runoff coefficient for the area tributary to the detention facility

A t = the area tributary to the detention facility in square feet

t V = the duration of the storm in minutes, with a 10 year return frequency, requiring the maximum detention volume with a variable outflow

Q DRR = the detention facility maximum release rate in cubic feet per second

1114.4 Required components.

On-site stormwater disposal systems shall be designed to provide adequate storage, support the use at the surface, and allow for operation and required maintenance. Systems shall be constructed with all necessary components and materials required by the manufacturers specifications. Drywell design shall incorporate a grit chamber, and where required, a sand column constructed in accordance with Figures 1114.4(1) and 1114.4(2) , respectively.

Figure 1114.4(1) Grit Chamber

Figure 1114.4(2) Detail of Drywell with Sand Column

1114.4.1 Grit chamber.

All drywells shall contain a grit chamber as part of the drywell system. Grit chambers shall be constructed in accordance with the following requirements:

1. Solid access cover with a minimum diameter of 15 inches (381 mm).

2. Grit chamber designed to support the maximum anticipated load.

3. Outlet invert elevation shall be a minimum of 1 inch (25 mm) lower than the lowest inlet elevation.

4. The sump shall be a minimum of 18 inches (450 mm) or two times the largest inlet pipe diameter, whichever is greater, as measured to the outlet invert elevation.

5. The interior dimensions shall be a minimum of 18 inches (450 mm) or four times the largest inlet pipe diameter whichever is greater.

1114.4.2 Reserved.

1114.5 On-site stormwater disposal system installation.

On-site stormwater disposal systems shall be installed in accordance the manufacturer's recommendations and shall conform to Sections 1114.5.1 through 1114.5.3.

1114.5.1 Support of excavation.

When an on-site stormwater disposal system installation requires an excavation deeper than 5 feet (1524 mm), the sides of the excavation shall be protected and maintained in accordance with Section 3304.4 of the New York City Building Code .

1114.5.2 Sand column installation.

Where the installation of an on-site stormwater disposal system requires the installation of a sand column, measures shall be taken to ensure the sand column is installed without contamination by impervious materials.

1114.5.3 Verification.

The department reserves the right to require a 24-hour test to verify the absorption of water in the installed on-site stormwater disposal system prior to final approval.

1114.6 Special inspection.

The installation of on-site stormwater disposal systems shall be subject to special inspection in accordance with Section 1704.21 of the New York City Building Code . Minor variations, based on actual site conditions, shall be acceptable at the discretion of the registered design professional of record.

1114.7 Maintenance.

The property owner shall maintain any on-site stormwater disposal system in proper working order in accordance with the rules of the Department of Environmental Protection.

1114.8 Signage.

Signage shall be attached to the house trap or fresh air pipe in the basement that states: AN ON-SITE STORMWATER DISPOSAL SYSTEM IS LOCATED ON THIS PROPERTY FOR STORMWATER DISPOSAL. INSPECTION AND MAINTENANCE OF THIS ON-SITE STORMWATER DISPOSAL SYSTEM IS REQUIRED BY THE RULES OF THE DEPARTMENT OF ENVIRONMENTAL PROTECTION. This signage shall depict the location of the system on the property.

1114.9 Post-construction stormwater management facilities required by stormwater pollution prevention plan.

A post-construction stormwater management facility that is constructed as part of a covered development project shall be designed, installed and maintained in accordance with the rules of the Department of Environmental Protection and this code.

Section PC 1201. General

Open this section

1201.1 Scope.

The provisions of this chapter shall govern the design and installation of piping and storage systems for nonflammable medical and nonmedical gas systems.

1201.2 Storage, handling, and use.

The storage, handling, and use of medical and nonmedical gases shall be in accordance with the New York City Fire Code.

Section PC 1202. Medical and Nonmedical Gases

Open this section

1202.1 Nonflammable medical and nonmedical gases.

Nonflammable medical and nonmedical gas systems shall be designed and installed in accordance with NFPA 99.

Exceptions:

1. This section shall not apply to portable systems or cylinder storage.

2. Vacuum system exhaust terminations shall comply with the New York City Mechanical Code.

Section PC 1203. Nonmedical Oxygen Systems

Open this section

1203.1 Design and installation.

Nonmedical oxygen systems shall be designed and installed in accordance with NFPA 55 and NFPA 51.

Section PC 1204. Other Cryogenic Systems

Open this section

1204.1 Design and installation.

Design and installation of cryogenic systems shall be in accordance with Sections 1202 and 1203.

1204.2 Storage, handling, and use.

Storage, handling, and use of cryogenic gases and fluids shall be in accordance with the New York City Fire Code .

Section PC 1301. General

Open this section

This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section PC 1301 at American Legal Publishing.

1301.1 Scope.

The provisions of Chapter 13 shall govern the materials, design, construction and installation of systems for the collection, storage, treatment and conveyance of nonpotable water. The use and application of nonpotable water shall comply with the New York City Construction Codes , and all applicable laws, and rules, including but not limited to those of the Department of Environmental Protection and the Department of Health and Mental Hygiene. Water from nonpotable systems shall be collected, stored, treated, conveyed and used on the same tax lot unless otherwise approved by the commissioner. The following water recycling uses are not addressed in this chapter:

1. Rainwater collected utilizing a retention system through rain barrels complying with the requirements of the Department of Environmental Protection;

2. Commercial car washing facilities; and

3. Water closet-sink combinations. A fixture that enables wastewater from a lavatory to discharge directly into the flushing tank of a water closet may be utilized provided it complies with the New York City Construction Codes , including all accessibility requirements. The water closet and lavatory shall be located in the same room.

1301.1.1 Uses of nonpotable water.

Nonpotable water end use applications shall be in accordance with the requirements established by the Department of Health and Mental Hygiene.

1301.2 Water quality.

Nonpotable water for each end use application shall meet the minimum water quality and treatment standards and requirements established by the Department of Health and Mental Hygiene.

1301.3 Identification required.

Conveyance piping shall be identified as containing nonpotable water. Piping identification shall be in accordance with Section 608.8.

1301.3.1 Spigots and hose bibs.

Spigots and hose bibs dispensing nonpotable water shall be secured from unauthorized use by a locking mechanism.

1301.3.2 Signage required.

Nonpotable water outlets such as hose connections, open ended pipes and faucets shall be identified at the point of use for each outlet with signage that reads as follows: "Nonpotable water is utilized for. CAUTION: NONPOTABLE WATER – DO NOT DRINK." The words shall be legibly and indelibly printed on a tag or sign constructed of corrosion-resistant waterproof material or shall be indelibly printed on the fixture. The letters of the words shall be not less than 0.5 inch (12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the required wordage, the pictograph shown in Figure 1301.3 shall appear on the signage required by this section.

Figure 1301.3 Pictograph – Do Not Drink

1301.4 Permits.

Permits shall be required for the construction, installation, and alteration of nonpotable water systems, and shall be required by the Department of Health and Mental Hygiene for review, commissioning and operation of nonpotable water systems.

Exception: Work outlined in Article 105.4 of Chapter 1 of Title 28 of the Administrative Code .

1301.5 Potable water connections.

Where a potable system is connected to a nonpotable water system, the potable water supply shall be protected against backflow by an air gap.

1301.6 Approved components and materials.

Piping, plumbing components and materials used in collection and conveyance systems shall be manufactured of material approved for the intended application and compatible with any disinfection and treatment systems used. Components and material shall comply with Sections 1301.6.1 through 1301.6.3.

1301.6.1 Above-ground piping.

Above-ground drain, waste and vent piping for nonpotable water systems shall conform to one of the standards listed in Table 702.1 .

1301.6.2 Underground piping.

Underground building drainage and vent piping for nonpotable water systems shall conform to one of the standards listed in Table 702.2 .

1301.6.3 Conveyance piping.

Conveyance piping for nonpotable water systems shall conform to one of the standards listed in Table 1301.6 and shall be purple in color, either manufactured, painted, or covered in a purple jacket and labeled in accordance with Section 1301.3.

Table 1301.6 Conveyance Pipe

Material Standard Brass pipe ASTM B 43 Chlorinated Polyvinyl Chloride (CPVC) a ASTM D 2846 Copper or copper-alloy pipe ASTM B 42; ASTM B 302 Copper or copper-alloy tubing (Type K, L) ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 Polypropylene a ASTM F 2389 Stainless steel pipe (Type 304/304L) ASTM A 312; ASTM A 778 Stainless steel pipe (Type 316/316L) ASTM A 312; ASTM A 778

a. Limited to residential buildings five stories or less in height.

1301.7 Insect and vermin control.

The system shall be protected to prevent the entrance of insects and vermin into storage tanks and piping systems. Screen materials shall be compatible with contacting system components and shall not accelerate the corrosion of system components.

1301.8 Freeze protection.

Where installations are subject to freezing temperatures, provisions shall be made to keep storage tanks and the related piping from freezing.

1301.9 Nonpotable water storage tanks.

Nonpotable water storage tanks shall comply with Sections 1301.9.1 through 1301.9.11. Nonpotable water storage tanks receiving multiple sources shall also comply with requirements established by the Department of Environmental Protection and the Department of Health and Mental Hygiene.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

1301.9.1 Sizing.

The holding capacity of the storage tank shall be sized in accordance with the anticipated demand.

Exception: Storage tanks also used for rainwater detention may be sized for the combined volume of detained water and the anticipated demand.

1301.9.2 Location.

Storage tanks shall be installed above or below grade. Above-grade storage tanks shall be protected from direct sunlight and shall be constructed using opaque, UV-resistant materials such as, but not limited to, heavily tinted plastic, fiberglass, lined metal, concrete, wood, or painted to prevent algae growth, or shall have specially constructed sun barriers including, but not limited to, installation in garages, crawl spaces or sheds. Storage tanks and their manholes shall not be located directly under soil piping, waste piping or any source of contamination.

1301.9.2.1 Separate nonpotable water storage tanks from multiple sources.

Separate collection tanks or compartments shall be provided for influent wastewater and rainwater sources.

1301.9.3 Materials.

Where collected on site, water shall be collected in an approved tank constructed of durable, nonabsorbent and corrosion-resistant materials. The storage tank shall be constructed of materials compatible with any disinfection systems used to treat water upstream of the tank and with any systems used to maintain water quality in the tank. Wooden storage tanks that are not equipped with a makeup water source shall be provided with a flexible liner.

1301.9.4 Foundation and supports.

Storage tanks shall be supported on a firm base capable of withstanding the weight of the storage tank when filled to capacity. Storage tanks shall be supported in accordance with the New York City Building Code . Tanks within an area of special flood hazard shall be designed, constructed and installed in accordance with Appendix G of the New York City Building Code .

1301.9.4.1 Ballast.

Where the soil can become saturated, an underground storage tank shall be ballasted, or otherwise secured, to prevent the tank from floating out of the ground when empty. The combined weight of the tank and hold down ballast shall meet or exceed the buoyancy force of the tank. Where the installation requires a foundation, the foundation shall be flat and shall be designed to support the weight of the storage tank when full, consistent with the bearing capability of adjacent soil.

1301.9.4.2 Structural support.

Where installed below grade, storage tank installations shall be designed to withstand earth and surface structural loads without damage and with minimal deformation when empty or filled with water.

1301.9.5 Makeup water.

Where an uninterrupted supply is required for the intended application, potable water shall be provided as a source of makeup water for the storage tank. The makeup water supply shall be protected against backflow by an air gap. A full-open valve located on the makeup water supply line to the storage tank shall be provided. Inlets to the storage tank shall be controlled by fill valves or other automatic supply valves installed to prevent the tank from overflowing and to prevent the water level from dropping below a predetermined point. Where makeup water is provided, the water level shall not be permitted to drop below the source water inlet or the intake of any attached pump.

Exception: Makeup water shall not be required for drip or subsurface landscape irrigation systems.

1301.9.6 Overflow.

The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table 606.5.4 . The overflow pipe shall be protected from insects or vermin. The overflow pipe shall be connected to the appropriate building drainage system in accordance with this code and the requirements of the Department of Environmental Protection. Overflow from a stormwater storage tank shall not discharge to the sanitary drainage system. Drainage from overflow pipes shall be directed to prevent freezing on roof walkways. The overflow drain shall not be equipped with a shutoff valve. A cleanout shall be provided on each overflow pipe in accordance with Section 708 .

1301.9.7 Access.

Not less than one access opening shall be provided to allow inspection and cleaning of the tank interior. Access openings shall have an approved locking device or other approved method of securing access. Below-grade storage tanks, located outside of the building, shall be provided with a manhole either not less than 24 inches (610 mm) square or with an inside diameter not less than 24 inches (610 mm). Manholes shall extend not less than 4 inches (102 mm) above ground or shall be designed to prevent water infiltration. Finished grade shall be sloped away from the manhole to divert surface water. Manhole covers shall be secured to prevent unauthorized access. Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter and shall be not less than 4 inches (102 mm) above the finished grade level. The service port shall be secured to prevent unauthorized access.

Exception: Storage tanks less than 800 gallons (3028 L) in volume and installed below grade shall not be required to be equipped with a manhole, but shall have a service port not less than 8 inches (203 mm) in diameter.

1301.9.7.1 Tanks accessed from within buildings.

Where access to a storage tank is provided from within a building, the tank access opening shall be gasketed and gas-tight.

1301.9.8 Venting.

Storage tanks shall be provided with a vent sized in accordance with Chapter 9 and based on the aggregate diameter of all tank influent pipes. The reservoir vent shall not be connected to sanitary drainage system vents. Vents shall be protected from contamination by means of an approved cap or U-bend installed with the opening directed downward. Vent outlets shall extend not less than 4 inches (102 mm) above grade or as necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the entrance of vermin and insects in accordance with the requirements of Section 1301.7.

1301.9.9 Draining of tanks.

Where tanks require draining for service or cleaning, tanks shall be drained by using a pump or by a drain located at the lowest point in the tank. The tank drain pipe shall be indirectly connected to the appropriate building drainage system and discharge as required for overflow pipes and shall not be smaller in size than specified in Table 606.5.7 . Not less than one cleanout shall be provided on each drain pipe in accordance with Section 708 .

1301.9.10 Marking and signage.

Each nonpotable water storage tank shall be labeled with its rated capacity. The contents of storage tanks shall be identified with the words "CAUTION: NONPOTABLE WATER – DO NOT DRINK." Where an opening is provided that could allow the entry of personnel, the opening shall be marked with the words, "DANGER – CONFINED SPACE." Markings shall be indelibly printed on the tank or on a tag or sign constructed of corrosion-resistant waterproof material that is mounted on the tank. The letters of the words shall be not less than 0.5 inch (12.7 mm) in height and shall be of a color in contrast with the background on which they are applied.

1301.9.11 Storage tank tests.

Storage tanks shall be tested in accordance with the following:

Storage tanks shall be filled with water to the overflow line prior to and during inspection. All seams and joints shall be left exposed and the tank shall remain water tight without leakage for a period of 24 hours.

1. After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper drainage of the overflow system and that there are no leaks.

2. The tank drain shall be observed for proper operation.

3. The makeup water system shall be observed for proper operation and successful automatic shutoff of the system at the refill threshold shall be verified.

1301.10 System abandonment.

If the owner of an on-site nonpotable water reuse system or rainwater collection and conveyance system elects to cease use of, or fails to properly maintain such system and is so ordered by the Department of Health and Mental Hygiene, the system shall be abandoned and shall comply with the following:

1. The conveyance piping system shall be replaced with an approved potable water supply piping system.

Exception : Where an existing conveyance pipe system is already in place, the fixtures may remain connected to the existing piping and supplied by the potable water system, in accordance with all of the following requirements:

1. The piping material, design and size comply with the requirements of Chapter 6 .

2. The piping system is disinfected in accordance with the requirements of Chapter 6 .

3. All piping connections between the potable and conveyance piping system shall be protected against backflow by an approved method in accordance with Chapter 6 .

4. The piping identification required by Section 1301.6.3 shall be maintained to identify the piping as nonpotable.

5. All piping connections to the abandoned components of the collection and treatment system shall be permanently disabled by removing a section of pipe.

2. The storage tank shall be secured from accidental access by sealing or locking tank inlets and access points, or filling with sand or equivalent.

3. Notification shall be provided to the Department and to the Department of Health and Mental Hygiene.

1301.11 Trenching requirements for nonpotable water piping.

Nonpotable water collection and conveyance piping shall be separated from the building sewer and potable water piping underground by 5 feet (1524 mm) of undisturbed or compacted earth. Nonpotable water collection and conveyance piping shall not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits. Buried nonpotable water piping shall comply with the requirements of Section 306 .

Exceptions:

1. The required separation distance shall not apply where the bottom of the nonpotable water pipe within 5 feet (1524 mm) of the sewer is not less than 12 inches (305 mm) above the top of the highest point of the sewer and the pipe materials conform to Table 702.3 .

2. The required separation distance shall not apply where the bottom of the potable water service pipe within 5 feet (1524 mm) of the nonpotable water pipe is a minimum of 12 inches (305 mm) above the top of the highest point of the nonpotable water pipe and the pipe materials comply with the requirements of Table 605.4 .

3. Nonpotable water pipe is permitted to be located in the same trench with a building sewer, provided that such sewer is constructed of materials that comply with the requirements of Table 702.2 .

4. The required separation distance shall not apply where a nonpotable water pipe crosses a sewer pipe, provided that the pipe is sleeved to at least 5 feet (1524 mm) horizontally from the sewer pipe centerline on both sides of such crossing, with pipe materials that comply with Table 702.2 .

5. The required separation distance shall not apply where a potable water service pipe crosses a nonpotable water pipe, provided that the potable water service pipe is sleeved for a distance of at least 5 feet (1524 mm) horizontally from the centerline of the nonpotable pipe on both sides of such crossing, with pipe materials that comply with Table 702.2 .

6. Irrigation piping located outside of a building and downstream of the backflow preventer is not required to meet the trenching requirements where nonpotable water is used for outdoor applications.

1301.12 Outdoor outlet access.

Sillcocks, hose bibbs, wall hydrants, yard hydrants and other outdoor outlets supplied by nonpotable water shall be located in a locked vault and shall also be operable only by means of a removable key. Such outlets shall comply with Section 1301.3.