NYC Administrative Code Title 28, Chapter 6 New York City Plumbing Code, part 4 of 4
Section PC 1302 to Section PC E202: 14 sections.
Section PC 1302. On-Site Nonpotable Water Reuse Systems
1302.1 General.
The provisions of Section 1302 shall govern the construction, installation, alteration and repair of on-site nonpotable water reuse systems for the collection, storage, treatment conveyance and application of on-site sources of nonpotable water as permitted by the New York City Construction Codes , and all applicable laws, and rules, including but not limited to those of the Department of Environmental Protection and the Department of Health and Mental Hygiene.
1302.2 Sources.
On-site nonpotable water reuse systems shall be permitted to collect waste discharge from only the allowed sources as established by the Department of Health and Mental Hygiene.
1302.3 Traps.
Traps serving fixtures and devices discharging waste water to on-site nonpotable water reuse systems shall comply with Section 1002.4.
1302.4 Collection pipe.
On-site nonpotable water reuse systems shall utilize drainage piping approved for use in plumbing drainage systems to collect and convey untreated water for reuse. Vent piping approved for use in plumbing venting systems shall be utilized for vents in the nonpotable system. Collection and vent piping materials shall comply with Section 702 , Table 702.1 and Table 702.2 .
1302.4.1 Installation.
Collection piping conveying untreated water for reuse shall be installed in accordance with Section 704 .
1302.4.2 Joints.
Collection piping conveying untreated water for reuse shall utilize joints approved for use with the conveyance piping and appropriate for the intended applications as specified in Section 705 .
1302.4.3 Size.
Collection piping conveying untreated water for reuse shall be sized in accordance with drainage sizing requirements specified in Section 710 .
1302.4.4 Labeling and marking.
Additional marking of collection piping containing untreated water for reuse shall be identified in accordance with Section 704.7.
1302.5 Filtration.
Untreated water collected for reuse shall be filtered as required for the intended nonpotable end use as established by the Department of Health and Mental Hygiene. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves immediately upstream and downstream to allow for isolation during maintenance.
1302.5.1 Filtration required.
Nonpotable water utilized for water closet and urinal flushing applications shall be filtered by a 100-micron or finer filter.
1302.6 Disinfection and treatment.
Untreated water collected for reuse shall be disinfected and treated as required for the intended nonpotable end use as established by the Department of Health and Mental Hygiene.
1302.7 Storage tanks.
Storage tanks utilized in on-site nonpotable water reuse systems shall comply with Sections 1301.9 and 1302.7.1 through 1302.7.4.
1302.7.1 Location.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1302.7.1 .
Table 1302.7.1 Location of Nonpotable Water Reuse Storage Tanks
Element Minimum Horizontal Distance from Storage Tank (feet) Critical root zone (CRZ) of protected trees 2 Lot line adjoining private lots 5 Seepage pits 5 Septic tanks 5 Water wells 50 Streams and lakes 50 Water service 5 Public water main 10
For SI: 1 foot = 304.8 mm.
1302.7.2 Design and construction.
Storage tanks shall be designed and constructed in accordance with Chapters 16 through 22 of the New York City Building Code and in accordance with the following standards, as appropriate for the material of the storage tank: AWWA D100, AWWA D115, AWWA D120, UL 58, UL 1746, UL 1316, UL 142, API 12F or API 12D.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1302.7.3 Inlets.
Storage tank inlets shall be designed to introduce collected water into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.
1302.7.4 Outlets.
Outlets shall be located not less than 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.
1302.8 Valves.
Valves shall be provided in accordance with Sections 1302.8.1 through 1302.8.3.
1302.8.1 Collection piping bypass valve.
One full-size three-way diverter valve shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated on-site reuse sources to the sanitary sewer to allow servicing and inspection of the system. Bypass valves shall be installed downstream of fixture traps and vent connections. Bypass valves shall be marked to indicate the direction of flow, connection and storage tank or drainfield connection. Bypass valves shall be installed in accessible locations. Two shutoff valves shall not be installed to serve as a bypass valve.
1302.8.2 Backwater valve.
One or more backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section 715 .
1302.8.3 Conveyance piping bypass valve.
One full-size three-way diverter valve shall be installed on the conveyance piping system upstream and downstream of all treated storage tanks, as applicable, to divert treated on-site nonpotable reuse water to the sanitary sewer to allow system testing, commissioning and bypass conditions.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1302.9 Pumping and control system.
Mechanical equipment including pumps, valves and filters shall be easily accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with Section 604 .
1302.10 Water pressure-reducing valve or regulator.
Where the water pressure supplied by the pumping system exceeds 85 psi (587 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the nonpotable water conveyance system piping to 85 psi (587 kPa) static or less. Pressure-reducing valves shall be specified and installed in accordance with Section 604.8.
1302.11 Conveyance pipe.
Conveyance piping utilized in on-site nonpotable water reuse systems shall comply with Sections 1302.11.1 through 1302.11.3.
Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.
1302.11.1 Materials, joints and connections.
Conveyance piping shall conform to the standards and requirements specified in Section 1301.6.
1302.11.2 Design.
On-site nonpotable water reuse conveyance piping systems shall be designed and sized in accordance with Section 604 for the intended application.
1302.11.3 Marking.
On-site nonpotable water conveyance piping labeling and marking shall comply with Section 1301.6.
1302.12 Tests and inspections.
Tests and inspections shall be performed in accordance with Sections 108 , 312 , and Sections 1302.12.1 through 1302.12.7. Special inspections of the nonpotable water systems shall be conducted in accordance with Chapter 17 of the New York City Building Code .
1302.12.1 Collection pipe and vent test.
Drain, waste and vent piping used for on-site water reuse systems shall be tested in accordance with Section 312 .
1302.12.2 Storage tank test.
Storage tanks shall be tested in accordance with Section 1301.9.11.
1302.12.3 Water supply system test.
The testing of makeup water supply piping and conveyance piping shall be conducted in accordance with Section 312.5.
1302.12.4 Inspection and testing of backflow prevention assemblies.
The testing of backflow preventers and backwater valves shall be conducted in accordance with Section 312.10.
1302.12.5 Inspection of vermin and insect protection.
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section 1301.7.
1302.12.6 Water quality test.
Water quality testing and monitoring shall be conducted in accordance with requirements of the Department of Health and Mental Hygiene.
1302.12.7 Inspection and testing of cross connection control.
Cross connection control inspection and testing shall be conducted in accordance with the requirements of the Department of Health and Mental Hygiene.
1302.13 Operation and maintenance manuals.
Operation and maintenance materials shall be supplied with nonpotable on-site water reuse systems in accordance with Sections 1302.13.1 through 1302.13.4 and in accordance with the requirements of the Department of Health and Mental Hygiene.
1302.13.1 Manual.
A detailed operations and maintenance manual shall be supplied in hardcopy form with all systems .
1302.13.2 Schematics.
The manual shall include a detailed system schematic, and the locations and a list of all system components, including manufacturer and model number.
1302.13.3 Maintenance procedures.
The manual shall provide a schedule and procedures for all system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.
1302.13.4 Operations procedures.
The manual shall include system startup and shutdown procedures. The manual shall include detailed operating procedures for the system.
Section PC 1303. Nonpotable Rainwater Collection and Conveyance Systems
1303.1 General.
The provisions of Section 1303 shall govern the construction, installation, alteration and repair of rainwater collection and conveyance systems for the collection, storage, treatment and conveyance of rainwater for nonpotable applications, as permitted by the New York City Construction Codes , and all applicable laws, and rules, including but not limited to those of the Department of Environmental Protection and the Department of Health and Mental Hygiene.
1303.2 Collection surface.
Rainwater shall be collected only from above-ground impervious roofing surfaces constructed from approved materials. Collection of water from vehicular parking or pedestrian surfaces shall be prohibited except where the water is used exclusively for landscape irrigation.
1303.2.1 Prohibited sources.
Roof mounted appliances and equipment including but not limited to evaporative coolers, cooling towers, water heaters, and solar water heaters shall not discharge onto rainwater collection surfaces.
1303.3 Debris excluders.
Downspouts and leaders shall be connected to a roof washer and shall be equipped with a debris excluder or equivalent device to prevent the contamination of collected rainwater with leaves, sticks, pine needles and similar material. Debris excluders and equivalent devices shall be self-cleaning.
1303.4 Roof washer.
A sufficient amount of rainwater shall be diverted at the beginning of each rain event, and not allowed to enter the storage tank, to wash accumulated debris from the collection surface. The amount of rainfall to be diverted shall be field adjustable as necessary to minimize storage tank water contamination. The roof washer shall not rely on manually operated valves or devices, and shall operate automatically. Diverted rainwater shall not be drained to the roof surface, and shall be discharged in a manner consistent with the storm water runoff requirements of the Department of Environmental Protection and this code. Roof washers shall be accessible for maintenance and service.
1303.5 Roof gutters and downspouts.
Gutters and downspouts shall be constructed of materials that are compatible with the collection surface and the rainwater quality for the desired end use. Joints shall be water tight.
1303.5.1 Slope.
Roof gutters, leaders and rainwater collection piping shall slope continuously toward collection inlets. Gutters and downspouts shall have a slope of not less than 1/8 inch per foot (10.4 mm/m) along their entire length, and shall not permit the collection or pooling of water at any point.
Exception: Siphonic drainage systems installed in accordance with the manufacturer's instructions shall not be required to have a slope.
1303.5.2 Size.
Gutters and downspouts shall be installed and sized in accordance with Section 1106 .
1303.5.3 Cleanouts.
Cleanouts shall be provided in accordance with Chapter 11 of this code in the water conveyance system and to allow access to all filters, flushes, pipes and downspouts.
1303.6 Drainage.
Water drained from the roof washer or debris excluder shall not be drained to the sanitary sewer. Such water shall be diverted from the storage tank and discharge in a location that will not cause erosion or damage to property in accordance with the New York City Building Code . Roof washers and debris excluders shall be provided with an automatic means of self-draining between rain events, and shall not drain onto roof surfaces.
1303.7 Collection pipe.
Rainwater collection and conveyance systems shall utilize drainage piping approved for use within plumbing drainage systems to collect and convey captured rainwater. Vent piping approved for use within plumbing venting systems shall be utilized for vents within the rainwater system. Collection and vent piping materials shall comply with Section 1102 .
1303.7.1 Installation.
Collection piping conveying captured rainwater shall be installed in accordance with Chapter 11 .
1303.7.2 Joints.
Collection piping conveying captured rainwater shall utilize joints approved for use with the piping and appropriate for the intended applications as specified in Chapter 11 .
1303.7.3 Size.
Collection piping conveying captured rainwater shall be sized in accordance with drainage sizing requirements specified in Section 1106 .
1303.7.4 Labeling and marking.
Additional marking of collection piping containing captured rainwater for reuse shall be identified in accordance with Section 704.7.
1303.8 Filtration.
Untreated rainwater collected for reuse shall be filtered as required for the intended nonpotable end use as established by the Department of Health and Mental Hygiene. Filters shall be accessible for inspection and maintenance. Filters shall utilize a pressure gauge or other approved method to provide indication when a filter requires servicing or replacement. Filters shall be installed with shutoff valves installed immediately upstream and downstream to allow for isolation during maintenance.
1303.8.1 Filtration required.
Nonpotable water utilized for water closet and urinal flushing applications shall be filtered by a 100-micron or finer filter.
1303.9 Disinfection.
Untreated rainwater collected for reuse shall be disinfected and treated as required for the intended nonpotable end use as established by the Department of Health and Mental Hygiene.
1303.10 Storage tanks.
Storage tanks utilized in nonpotable rainwater collection and conveyance systems shall comply with Sections 1301.9 and 1303.10.1 through 1303.10.4.
1303.10.1 Location.
Storage tanks shall be located with a minimum horizontal distance between various elements as indicated in Table 1303.10.1 .
Table 1303.10.1 Location of Rainwater Storage Tanks
Element Minimum Horizontal Distance from Storage Tank (feet) Critical root zone (CRZ) of protected trees 2 Lot line adjoining private lots 5 Seepage pits 5 Septic tanks 5
For SI: 1 foot = 304.8 mm.
1303.10.2. Design and construction.
Storage tanks shall be designed and constructed in accordance with Chapters 16 through 22 of the New York City Building Code and in accordance with the following standards, as appropriate for the material of the storage tank: AWWA D100, AWWA D115, AWWA D120, UL 58, UL 1746, UL 1316, UL 142, API 12F or API 12D.
1303.10.3 Inlets.
Storage tank inlets shall be designed to introduce collected rainwater into the tank with minimum turbulence, and shall be located and designed to avoid agitating the contents of the storage tank.
1303.10.4 Outlets.
Outlets shall be located at least 4 inches (102 mm) above the bottom of the storage tank and shall not skim water from the surface.
1303.11 Valves.
Valves shall be provided in accordance with Sections 1303.11.1 through 1303.11.3.
1303.11.1 Collection piping bypass valve.
One full-size three-way diverter valve shall be installed on collection piping upstream of each storage tank, or drainfield, as applicable, to divert untreated rainwater to the storm or combined sewer to allow servicing and inspection of the system. Bypass valves shall be marked to indicate the direction of flow, connection and storage tank or drainfield connection. Bypass valves shall be installed in accessible locations. Two shutoff valves shall not be installed to serve as a bypass valve.
1303.11.2 Backwater valve.
One or more backwater valves shall be installed on each overflow and tank drain pipe. Backwater valves shall be in accordance with Section 1101 .
1303.11.3 Conveyance piping bypass valve.
One full-size three-way diverter valve shall be installed on the conveyance piping system upstream and downstream of all treated storage tanks, as applicable, to divert treated on-site nonpotable reuse water to the sanitary sewer to allow system testing, commissioning and bypass conditions.
1303.12 Pumping and control system.
Mechanical equipment including pumps, valves and filters shall be easily accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow pressure delivered by the pumping system shall be appropriate for the application and in accordance with Section 604 .
1303.13 Water pressure-reducing valve or regulator.
Where the water pressure supplied by the pumping system exceeds 85 psi (587 kPa) static, a pressure-reducing valve shall be installed to reduce the pressure in the rainwater conveyance system piping to 85 psi (587 kPa) static or less. Pressure- reducing valves shall be specified and installed in accordance with Section 604.8.
1303.14 Conveyance pipe.
Conveyance piping utilized in rainwater collection and conveyance systems shall comply with Sections 1303.14.1 through 1303.14.3.
Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.
1303.14.1 Materials, joints and connections.
Conveyance piping shall conform to the standards and requirements specified in Section 1301.6.
1303.14.2 Design.
Rainwater reuse conveyance piping systems shall be designed and sized in accordance with Section 604 for the intended application.
1303.14.3 Marking.
Nonpotable rainwater conveyance piping labeling and marking shall comply with Section 1301.6.
1303.15 Tests and inspections.
Tests and inspections shall be performed in accordance with Sections 108 , 312 , and Sections 1303.15.1 through 1303.15.9. Special inspections of the nonpotable water systems shall be conducted in accordance with Chapter 17 of the New York City Building Code .
1303.15.1 Reserved.
1303.15.2 Roofwasher test.
Roofwashers shall be tested by introducing water into the gutters. Proper diversion of the first quantity of water in accordance with the requirements of Section 1303.4 shall be verified.
1303.15.3 Collection pipe and vent test.
Drain, waste and vent piping used for rainwater collection and conveyance systems shall be tested in accordance with Section 312 .
1303.15.4 Storage tank test.
Storage tanks shall be tested in accordance with Section 1301.9.11.
1303.15.5 Water supply system test.
The testing of makeup water supply piping and conveyance piping shall be conducted in accordance with Section 312.5.
1303.15.6 Inspection and testing of backflow prevention assemblies.
The testing of backflow preventers and backwater valves shall be conducted in accordance with Section 312.10.
1303.15.7 Inspection of vermin and insect protection.
Inlets and vents to the system shall be inspected to verify that each is protected to prevent the entrance of insects and vermin into the storage tank and piping systems in accordance with Section 1301.7.
1303.15.8 Water quality test.
Water quality testing and monitoring shall be conducted in accordance with requirements of the Department of Health and Mental Hygiene.
1303.15.9 Inspection and testing of cross connection control.
Cross connection control inspection and testing shall be conducted in accordance with the requirements of the Department of Health and Mental Hygiene.
1303.16 Operation and maintenance manuals.
Operation and maintenance manuals shall be supplied with rainwater collection and conveyance systems in accordance with Sections 1303.16.1 through 1303.16.4.
1303.16.1 Manual.
A detailed operations and maintenance manual shall be supplied in hardcopy form with all systems.
1303.16.2 Schematics.
The manual shall include a detailed system schematic, and locations and a list of all system components, including manufacturer and model number.
1303.16.3 Maintenance procedures.
The manual shall provide a maintenance schedule and procedures for all system components requiring periodic maintenance. Consumable parts, including filters, shall be noted along with part numbers.
1303.16.4 Operations procedures.
The manual shall include system startup and shutdown procedures. The manual shall include detailed operating procedures for the system.
Section PC 1304. Reserved
BetaNYC's copy has no text for this section. Read Section PC 1304 at American Legal Publishing.
Section PC 1401. General
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of subsurface landscape irrigation systems connected to nonpotable water from on-site water reuse systems.
1401.2 Materials.
Above-ground drain, waste and vent piping for subsurface landscape irrigation systems shall conform to one of the standards listed in Table 702.1 . Subsurface landscape irrigation, underground building drainage and vent pipe shall conform to one of the standards listed in Table 702.2 .
1401.3 Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance with Section 312 .
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107 .
1401.5 Disinfection.
Disinfection shall not be required for on-site nonpotable water reuse for subsurface landscape irrigation systems.
1401.6 Coloring.
On-site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to be dyed.
Section PC 1402. System Design and Sizing
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irrigation systems, gray water output shall be calculated according to the gallons-per-day-per-occupant number based on the type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A × B (Equation 14-1)
where:
A = Number of occupants:
Residential – Number of occupants shall be determined by the actual number of occupants, but not less than two occupants for one bedroom and one occupant for each additional bedroom.
Commercial – Number of occupants shall be determined by the New York City Building Code .
B = Estimated flow demands for each occupant*:
Residential – 25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day (56.7 lpd) per occupant for clothes washers or laundry trays.
Commercial – Based on type of fixture or water use records minus the discharge of fixtures other than those discharging gray water.
* Alternative estimated flow demands for each occupant shall be permitted based on actual calculated water usage for the building.
C = Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by percolation tests or permeability evaluation.
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted. The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More percolation tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The bottom and sides of the hole shall be scratched with a sharp-pointed instrument to expose the natural soil. All loose material shall be removed from the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test procedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches (305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away shall be determined, and this procedure shall be repeated if the water from the second filling of the hole seeps away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6 inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference point, water levels shall be measured at 10-minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth exceed 6 inches (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall be used to calculate the percolation rate. Soils not meeting the above requirements shall be tested in accordance with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth of 12 inches (305 mm) shall be maintained above the bottom of the hole for a 4-hour period by refilling whenever necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed. Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 hours. Immediately after the soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30-minute intervals for a period of 4 hours, unless two successive water level drops do not vary by more than 1/16 inch (1.59 mm). At least three water level drops shall be observed and recorded. The hole shall be filled with clear water to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty. Adjustments of the water level shall not be made during the three measurement periods except to the limits of the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30 minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water depth shall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equipment shall be of an approved type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture in accordance with accepted soil evaluation practices. Borings shall be made in accordance with Section 1402.2.1.1 for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be located at a point lower than the surface grade of any water well or reservoir on the same or adjoining lot. Where this is not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir. The soil absorption system shall be located with a minimum horizontal distance between various elements as indicated in Table 1402.3 . Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohibited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
Table 1402.3 Location of Subsurface Irrigation System
Element Minimum Horizontal Distance Storage tank (feet) Irrigation disposal field (feet) Buildings 5 10 Lot line adjoining private property 5 5 Water wells 50 100 Streams and lakes 50 50 Seepage pits 5 20 Septic tanks 0 5 Water service 5 5 Public water main 10 10
For SI: 1 foot = 304.8 mm.
Section PC 1403. Installation
1403.1 Installation.
Absorption systems shall be installed in accordance with Sections 1403.1.1 through 1403.1.5 to provide landscape irrigation without surfacing of water.
1403.1.1 Absorption area.
The total absorption area required shall be computed from the estimated daily gray water discharge and the design-loading rate based on the percolation rate for the site. The required absorption area equals the estimated gray water discharge divided by the design-loading rate from Table 1403.1.1 .
Table 1403.1.1 Design Loading Rate
Percolation Rate (minutes per inch) Design Loading Factor (gallons per square foot per day) < 1 Not suitable 1 - 5 1.20 6 - 7 1.00 8 - 10 0.90 11 - 15 0.80 16 - 20 0.70 21 - 30 0.60 31 - 45 0.50 46 - 60 0.45 61 - 120 0.20 > 120 Not Suitable
For SI: 1 minute per inch = min/25.4 mm, 1 gallon per square foot = 40.7 L/m 2 .
1403.1.2 Seepage trench excavations.
Seepage trench excavations shall be not less than 1 foot (304 mm) in width and not greater than 5 feet (1524 mm) in width. Trench excavations shall be spaced not less than 2 feet (610 mm) apart. The soil absorption area of a seepage trench shall be computed by using the bottom of the trench area (width) multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet (30 480 mm) in developed length.
1403.1.3 Seepage bed excavations.
Seepage bed excavations shall be not less than 5 feet (1524 mm) in width and have more than one distribution pipe. The absorption area of a seepage bed shall be computed by using the bottom of the trench area. Distribution piping in a seepage bed shall be uniformly spaced not greater than 5 feet (1524 mm) and not less than 3 feet (914 mm) apart, and greater than 3 feet (914 mm) and not less than 1 foot (305 mm) from the sidewall or headwall.
1403.1.4 Excavation and construction.
The bottom of a trench or bed excavation shall be level. Seepage trenches or beds shall not be excavated where the soil is so wet that such material rolled between the hands forms a soil wire. All smeared or compacted soil surfaces in the sidewalls or bottom of seepage trench or bed excavations shall be scarified to the depth of smearing or compaction and the loose material removed. Where rain falls on an open excavation, the soil shall be left until sufficiently dry so a soil wire will not form when soil from the excavation bottom is rolled between the hands. The bottom area shall then be scarified and loose material removed.
1403.1.5 Aggregate and backfill.
Not less than 6 inches in depth of aggregate, ranging in size from 1/2 to 2 1/2 inches (12.7 mm to 64 mm), shall be laid into the trench below the distribution piping elevation. The aggregate shall be evenly distributed not less than 2 inches (51 mm) in depth over the top of the distribution pipe. The aggregate shall be covered with approved synthetic materials or 9 inches (229 mm) of uncompacted marsh hay or straw. Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall be provided above the covering.
1403.2 Distribution piping.
Distribution piping shall be not less than 3 inches (76 mm) in diameter. Materials shall comply with Table 1403.2 . The top of the distribution pipe shall be not less than 4 inches (100 mm) or greater than 12 inches (300 mm) below the original surface. The slope of the distribution pipes shall be not less than 2 inches (51 mm) and not greater than 4 inches (102 mm) per 100 feet (30 480 mm).
Table 1403.2 Distribution Pipe
Material Standard Polypropylene (PP) pipe ASTM F 2389 Polyethylene (PE) plastic pipe ASTM F 405 Polyvinyl chloride (PVC) plastic pipe a ASTM D 2729 Polyvinyl chloride (PVC) plastic pipe with a 3.5-inch O.D. and solid cellular core or composite wall a ASTM F 1488
a. Limited to residential buildings five stories or less in height.
1403.2.1 Joints and fittings.
Joints and fittings in distribution pipe shall be made in accordance with Table 1403.2.1 .
Table 1403.2.1 Joints and Fittings
Material Standard Polyethylene (PE) plastic pipe ASTM F 405 Polypropylene (PP) pipe ASTM F 2389 Polyvinyl chloride (PVC) plastic in IPS diameters a ASTM D 2665; ASTM F 1866 Polyvinyl chloride (PVC) plastic pipe in sewer and drain diameters a ASTM D 3034 Polyvinyl chloride (PVC) plastic pipe with a 3.25-inch O.D. a ASTM D 2949
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
1403.2.2 Diversion valves.
Systems shall include a diversion valve to divert gray water to the building sanitary system when soils are saturated or frozen, there is a blockage or backup in the system, the maximum allowed gallons per day is reached, or when system maintenance is necessary.
1403.2.3 Overflow connection.
Systems shall have a piped connection to the building drainage system to accommodate tank overflow.
Section PC 1501. General
1501.1 General.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title and the section or sections of this document that reference the standard.
1501.2 Subsequent additions, modifications or deletions.
Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to these standards in accordance with Section 28-103.19 of the Administrative Code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1501.3 Applicability.
The application of the referenced standards shall be as specified in Section 102.8.
Section PC 1502. Standards
AHRI Air-Conditioning, Heating, & Refrigeration Institute 4100 North Fairfax Drive, Suite 200 Arlington, VA 22203 Standard reference number Title Referenced in code section number 1010—02 Self-contained, Mechanically Refrigerated Drinking-Water Coolers 410.1 810—16 Addendum 1 Performance Rating of Automatic Commercial Ice-makers 428.1.1
ANSI American National Standards Institute 25 West 43rd Street, Fourth Floor New York, NY 10036 Standard reference number Title Referenced in code section number A118.10—99 Specifications for Load Bearing, Bonded, Waterproof Membranes for Thin Set Ceramic Tile and Dimension Stone Installation 417.5.2.5, 417.5.2.6 Z4.3—95 Minimum Requirements for Nonsewered Waste-disposal Systems 311.1 Z21.22—99 (R2003) Relief Valves for Hot Water Supply Systems with Addenda Z21.22a—2000 (R2003) and Z21.22b—2001 (R2003) 504.2, 504.4, 504.4.1 CSA B45.5—11 / IAPMO Z124—11 Plastic Plumbing Fixtures 407.1, 415.1, 416.1, 416.2, 417.1, 418.1, 419.1, 420.1
API American Petroleum Institute 1220 L Street NW Washington, DC 20005-4070 Standard reference number Title Referenced in code section number 12D – 2008 Specification for Field Welded Tanks for Storage of Production Liquids, effective April 1, 2009 1302.7.2, 1303.10.2 12F – 2008 Specification for Shop Welded Tanks for Storage of Production Liquids, effective April 1, 2009 1302.7.2, 1303.10.2
ASCE/SEI American Society of Civil Engineers Structural Engineering Institute 1801 Alexander Bell Drive Reston, VA 20191-4400 Standard reference number Title Referenced in code section number 24—14 Flood Resistant Design and Construction 715.1, 1101.9.1
ASME American Society of Mechanical Engineers Three Park Avenue New York, NY 10016-5990 Standard reference number Title Referenced in code section number A112.1.2—2004 Air Gaps in Plumbing Systems 406.1, 409.2, Table 608.1, 608.13.1 A112.1.3—2000 (R2011) Air Gap Fittings for Use with Plumbing Fixtures, Appliances and Appurtenances 406.1, 409.2, Table 608.1, 608.13.1 A112.3.1—2007 Stainless Steel Drainage Systems for Sanitary, DWV, Storm and Vacuum Applications Above and Below Ground 412.1, Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, 1102.6, Table 1102.7 A112.3.4—2013 / CSA B45.9—2013 Macerating Toilet Systems and Related Components 712.4.1 A112.4.1—2009 Water Heater Relief Valve Drain Tubes 504.6 A112.4.2—2009 Water Closet Personal Hygiene Devices 424.9 A112.4.3—1999 (R2010) Plastic Fittings for Connecting Water Closets to the Sanitary Drainage System 405.4 A112.4.14—2004 (R2010) Manually Operated, Quarter-Turn Shutoff Valves for Use in Plumbing Systems Table 605.7 A112.6.1M—1997 (R2008) Floor-affixed Supports for Off-the-floor Plumbing Fixtures for Public Use 405.4.3 A112.6.2—2000 (R2010) Framing-affixed Supports for Off-the-floor Water Closets with Concealed Tanks 405.4.3 A112.6.3—2001 (R2007) Floor and Trench Drains 412.1 A112.6.4—2003 (R2008) Roof, Deck, and Balcony Drains 1102.6 A112.6.7—2010 Enameled and Epoxy-coated Cast-iron and PVC Plastic Sanitary Floor Sinks 427.1 A112.6.9—2005 (R2010) Siphonic Roof Drains 1107.1 A112.14.1—2003 Backwater Valves 715.2 A112.14.3—2000 Grease Interceptors 1003.3.4 A112.14.4—2001 (Reaffirmed 2007) Grease Removal Devices 1003.3.4 A112.18.1—2012 / CSA B125.1—2012 Plumbing Supply Fittings 424.1, 424.2, 424.3, 424.4, 424.6, 424.8, Table 605.7, 607.4, 608.2 A112.18.2—2011 / CSA B125.2—2011 Plumbing Waste Fittings 424.1.2 A112.18.3—2002 (Reaffirmed 2008) Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings 424.2, 424.6 A112.18.6 / CSA B125.6—2009 Flexible Water Connectors 605.6 A112.18.9—2011 Protectors/Insulators for Exposed Waste and Supplies on Accessible Fixtures 404.3 A112.19.1—2013 / CSA B45.2—2013 Enameled Cast Iron and Enameled Steel Plumbing Fixtures 407.1, 410.1, 415.1, 416.1, 418.1 A112.19.2 — 2013 / CSA B45.1—2013 Ceramic Plumbing Fixtures 401.2, 405.9, 407.1, 408.1, 410.1, 415.1, 416.1, 417.1, 418.1, 419.1, 420.1 A112.19.3— 2008 / CSA B45.4—2008 (R2013) Stainless Steel Plumbing Fixtures 405.9, 407.1, 415.1, 416.1, 418.1, 420.1 A112.19.5—2011 / CSA B45.15—2011 Flush Valves and Spuds for Water-closets, Urinals, and Tanks 425.4 A112.19.7M—2012 / CSA B45.10—2012 Hydromassage Bathtub Systems 421.1, 421.4 A112.19.12—2006 Wall Mounted and Pedestal Mounted, Adjustable, Elevating, Tilting and Pivoting Lavatory, Sink and Shampoo Bowl Carrier Systems and Drain Systems 416.4, 418.3 A112.19.14—2006 (R2011) Six-Liter Water Closets Equipped with a Dual Flushing Device 420.1 A112.19.15—2005 Bathtub/Whirlpool Bathtubs with Pressure Sealed Doors 407.4, 421.6 A112.19.19—2006 Vitreous China Nonwater Urinals 419.1 A112.21.3—1985 (R2007) Hydrants for Utility and Maintenance Use Table 608.1, 608.13.6 A112.36.2M—1991 (R2008) Cleanouts 709.1.10.2 ASSE 1016 / ASME A112.1016 / CSA B125.16—2011 Performance Requirements for Individual Thermostatic, Pressure Balancing and Combination Control Valves for Individual Fixture Fittings 424.3, 424.4, 607.4 B1.20.1—1983 (R2006) Pipe Threads, General Purpose (inch) 605.11.3, 605.13.4, 705.2.3, 705.3.3, 705.6.4, 705.9.1, 705.11.3, 803.3.4.1.3 B16.3—2011 Malleable Iron Threaded Fittings Classes 150 and 300 Table 702.4, Table 1102.7 B16.4—2011 Gray Iron Threaded Fittings Classes 125 and 250 Table 605.5, Table 702.4, Table 1102.7 B16.12—2009 Cast-iron Threaded Drainage Fittings Table 702.4, Table 1102.7 B16.15—2011 Cast Bronze Threaded Fittings Table 605.5, Table 702.4 B16.18—2012 Cast Copper Alloy Solder Joint Pressure Fittings Table 605.5, Table 702.4 B16.22—2001 (R2010) Wrought Copper and Copper Alloy Solder Joint Pressure Fittings Table 605.5, Table 702.4 B16.23—2011 Cast Copper Alloy Solder Joint Drainage Fittings (DWV) Table 702.4 B16.26—2011 Cast Copper Alloy Fittings for Flared Copper Tubes Table 605.5, Table 702.4 B16.29—2012 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings (DWV) Table 702.4 B31.9—2017 Building Services Piping 605.23.2 BPVC—2010 Boiler and Pressure Vessel Code 312.11.1, 501.2
ASPE American Society of Plumbing Engineers 8614 Catalpa Avenue, Suite 1007 Chicago, IL 60656-1116 Standard reference number Title Referenced in code section number 45—2013 Siphonic Roof Drainage Systems 1107.1
ASSE American Society of Sanitary Engineering 901 Canterbury Road, Suite A Westlake, OH 44145 Standard reference number Title Referenced in code section number 1001—08 Performance Requirements for Atmospheric Type Vacuum Breakers 425.2, Table 608.1, 608.13.6, 608.16.4.1 1002—08 Performance Requirements for Antisiphon Fill Valves (Ballcocks) for Gravity Water Closet Flush Tanks 425.3.1, Table 608.1 1003—09 Performance Requirements for Water Pressure Reducing Valves 604.8 1004—08 Performance Requirements for Backflow Prevention Requirements for Commercial Dishwashing Machines 409.1 1008—06 Performance Requirements for Plumbing Aspects of Food Waste Disposer Units 413.1 1010—04 Performance Requirements for Water Hammer Arresters 604.9 1011—04 Performance Requirements for Hose Connection Vacuum Breakers Table 608.1, 608.13.6 1012—09 Performance Requirements for Backflow Preventers with Intermediate Atmospheric Vent Table 608.1, 608.13.3, 608.16.2 1013—09 Performance Requirements for Reduced Pressure Principle Backflow Preventers and Reduced Pressure Principle Fire Protection Backflow Preventers Table 608.1, 608.13.2, 608.16.2 1015—09 Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies Table 608.1, 608.13.7 ASSE 1016 / ASME A112.1016 / CSA B125.16—2011 Performance Requirements for Individual Thermostatic, Pressure Balancing and Combination Control Valves for Individual Fixture Fittings 424.3, 424.4, 607.4, 613.1 1017—2010 Performance Requirements for Temperature Actuated Mixing Valves for Hot Water Distribution Systems 501.2.3, 613.1 1018—2010 Performance Requirements for Trap Seal Primer Valves; Potable Water Supplied 1002.4.1.1, 1002.4.1.2 1019—2010 Performance Requirements for Vacuum Breaker Wall Hydrants, Freeze Resistant, Automatic Draining Type Table 608.1, 608.13.6, 1020—04 Performance Requirements for Pressure Vacuum Breaker Assembly Table 608.1, 608.13.5 1022—03 Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment Table 608.1, 608.16.1, 608.16.10 1024—04 Performance Requirements for Dual Check Valve Type Backflow Preventers (for Residential Supply Service or Individual Outlets) Table 608.1, 608.13.10 1035—08 Performance Requirements for Laboratory Faucet Backflow Preventers Table 608.1, 608.13.6 1037—90 Performance Requirements for Pressurized Flushing Devices for Plumbing Fixtures 425.2 1047—2009 Performance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies Table 608.1, 608.13.2 1048—2009 Performance Requirements for Double Check Detector Fire Protection Backflow Prevention Assemblies Table 608.1, 608.13.7 1052—04 Performance Requirements for Hose Connection Backflow Preventers Table 608.1, 608.13.6 1055—2009 Performance Requirements for Chemical Dispensing Systems 608.13.9 1056—2010 Performance Requirements for Spill Resistant Vacuum Breaker Table 608.1, 608.13.5, 608.13.8 1060—2006 Performance Requirements for Outdoor Enclosures for Fluid Conveying Components 608.14.1 1061—2010 Performance Requirements for Removable and Nonremovable Push Fit Fittings Table 605.5, 605.14.4 1062—2006 Performance Requirements for Temperature Actuated, Flow Reduction Valves to Individual Supply Fittings 424.7 1066—2009 Performance Requirements for Individual Pressure Balancing In-line Valves for Individual Fixture Fittings 604.11 1069—05 Performance Requirements for Automatic Temperature Control Mixing Valves 424.4 1070—04 Performance Requirements for Water-temperature Limiting Devices 408.3, 416.5, 423.3, 424.5, 607.1.2 1079—2005 Performance Requirements for Dielectric Pipe Unions 605.24.1, 605.24.3 5013—2009 Performance Requirements for Testing Reduced Pressure Principle Backflow Prevention Assembly (RPA) and Reduced Pressure Fire Protection Backflow Preventers (RFP) 312.10.2 5015—2009 Performance Requirements for Testing Double Check Valve Backflow Prevention Assemblies (DC) and Double Check Fire Protection Backflow Prevention Assemblies (DCF) 312.10.2 5020—2009 Performance Requirements for Testing Pressure Vacuum Breaker Assemblies (PVBA) 312.10.2 5047—98 Performance Requirements for Testing Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies (RPDA) 312.10.2 5048—2009 Performance Requirements for Testing Double Check Valve Detector Assembly (DCDA) 312.10.2 5052—98 Performance Requirements for Testing Hose Connection Backflow Preventers 312.10.2 5056—98 Performance Requirements for Testing Spill Resistant Vacuum Breaker (SRVB) 312.10.2
ASTM ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428-2959 Standard reference number Title Referenced in code section number A 53/ A 53M—12 Specification for Pipe, Steel, Black and Hot-dipped, Zinc-coated Welded and Seamless Table 702.1, Table 702.3, Table 1102.4 A 74—13A Specification for Cast-iron Soil Pipe and Fittings Table 702.1, Table 702.2, Table 702.3, Table 702.4, 708.1.6, Table 1102.4, Table 1102.5, Table 1102.7 A 123—12 Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products Table 702.3, Table 1102.4 A 153 / A 153M—16a Specifications for Zinc Coating (Hot Dip) on Iron and Steel Hardware Table 702.4, Table 1102.7 A 312 / A 312M—13a Specification for Seamless, Welded, And Heavily Cold Worked Austenitic Stainless Steel Pipes Table 605.4, Table 605.4.1, Table 605.5, Table 1301.6 A 403 / A 403M—11 Specification for Wrought Austenitic Stainless Steel Piping Fittings Table 605.5, Table 605.8 A 518 / A 518M—99 (2012) Standard Specification for Corrosion-Resistant High- Silicon Iron Castings Table 803.3.1 A 778—01 (2009) e1 Specification for Welded Unannealed Austenitic Stainless Steel Tubular Products Table 605.4, Table 605.4.1, Table 605.5, Table 1301.6 A 861—04 (2017) Standard Specification for High-Silicon Iron Pipe and Fittings Table 803.3.2 A 888—13A Specification for Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Application Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7 B 32—08 Specification for Solder Metal 605.14.6, 705.6.3, 705.7.3 B 42—10 Specification for Seamless Copper Pipe, Standard Sizes Table 605.4, Table 605.4.1, Table 702.1, Table 1301.6 B 43—09 Specification for Seamless Red Brass Pipe, Standard Sizes Table 605.4, Table 605.4.1, Table 702.1, Table 1301.6 B 62—17 Specification for Composition Bronze or Ounce Metal Castings Table 605.5, Table 702.4, Table 1102.7 B 75—11 Specification for Seamless Copper Tube Table 605.4, Table 605.4.1, Table 702.1, Table 702.2, Table 702.3, Table 1102.4, Table 1102.7, Table 1301.6 B 88—09 Specification for Seamless Copper Water Tube Table 605.4, Table 605.4.1, Table 702.1, Table 702.2, Table 702.3, Table 1102.4, Table 1102.7, Table 1301.6, Figure E103.3(2), Figure E103.3(3) B 152 / B 152M—13 Specification for Copper Sheet, Strip Plate and Rolled Bar 402.3, 417.5.2.4, 425.3.3, 902.2 B 251—10 Specification for General Requirements for Wrought Seamless Copper and Copper-alloy Tube Table 605.3, Table 605.4, Table 605.4.1, Table 702.1, Table 702.2, Table 702.3, Table 1102.4, Table 1102.7, Table 1301.6 B 302—12 Specification for Threadless Copper Pipe, Standard Sizes Table 605.4, Table 605.4.1, Table 702.1, Table 1301.6 B 447—12a Specification for Welded Copper Tube Table 605.4, Table 605.4.1, Table 1301.6 B 687— (2011) Specification for Brass, Copper and Chromium-plated Pipe Nipples Table 605.8 B 813—10 Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube 605.14.6, 705.6.3, 705.7.3 B 828—02 (2010) Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings 605.14.6, 705.6.3, 705.7.3 C 4—04 (2009) Specification for Clay Drain Tile and Perforated Clay Drain Tile Table 702.3, Table 1102.4, Table 1102.5 C 14—11 Specification for Nonreinforced Concrete Sewer, Storm Drain and Culvert Pipe Table 702.3, Table 1102.4 C 76—13a Specification for Reinforced Concrete Culvert, Storm Drain and Sewer Pipe Table 702.3, Table 1102.4 C 425—04 (2009) Specification for Compression Joints for Vitrified Clay Pipe and Fittings Table 702.4, 705.12, 705.16, Table 1102.7 C 443—12 Specification for Joints for Concrete Pipe and Manholes, Using Rubber Gaskets 705.5, 705.16 C 564—12 Specification for Rubber Gaskets for Cast-iron Soil Pipe and Fittings 705.4.2, 705.4.3, 705.16 C 654—15 Standard Specification for Porous Concrete Pipe Table 1102.5 C 700—13 Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated Table 702.3, Table 702.4, Table 1102.4, Table 1102.5 C 1053—00 (2010) Specification for Borosilicate Glass Pipe and Fittings for Drain, Waste, and Vent (DWV) Applications Table 803.3.1, Table 803.3.2 C 1173—10e1 Specification for Flexible Transition Couplings for Underground Piping System 705.2.1, 705.5, 705.11.1, 705.12, 705.13.2, 705.16, C 1277—12 Specification for Shielded Coupling Joining Hubless Cast-iron Soil Pipe and Fittings 705.4.3 C 1440—08 Specification for Thermoplastic Elastomeric (TPE) Gasket Materials for Drain, Waste, and Vent (DWV), Sewer, Sanitary and Storm Plumbing Systems 705.16 C 1460—08 Specification for Shielded Transition Couplings for Use with Dissimilar DWV Pipe and Fittings Above Ground 705.16 C 1461—08 Specification for Mechanical Couplings Using Thermoplastic Elastomeric (TPE) Gaskets for Joining Drain, Waste and Vent (DWV) Sewer, Sanitary and Storm Plumbing Systems for Above and Below Ground Use 705.16 C 1540—11 Specification for Heavy Duty Shielded Couplings Joining Hubless Cast-iron Soil Pipe and Fittings 705.4.3 C 1563—13 Standard Test Method for Gaskets for Use in Connection with Hub and Spigot Cast Iron Soil Pipe and Fittings for Sanitary Drain, Waste, Vent and Storm Piping Applications 705.4.2 D 1586—11 Standard Test Method for Standard Penetration Test (SPT) and Split-barrel Sampling of Soils 1114.2.1 D 1587—15 Standard Practice for Thin-walled Tube Sampling of Soils for Geotechnical Purposes 1114.2.1 D 2235—04 (2011) Specification for Solvent Cement for Acrylonitrile- Butadiene-Styrene (ABS) Plastic Pipe and Fittings 705.2.2 D 2464—15 Specification for Threaded Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 Table 1102.7 D 2466—17 Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40 Table 1102.7 D 2467—15 Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 Table 1102.7 D 2564—12 Specification for Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Piping Systems 705.11.2 D 2657—07 Practice for Heat Fusion-joining of Polyolefin Pipe and Fitting Waste, and Vent Pipe and Fittings 705.13.1, Table 1102.7 D 2661—11 Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe and Fittings Table 702.1, Table 702.4, 705.2.2, Table 1102.7 D 2665—12 Specification for Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.7, Table 1403.2.1 D 2729—11 Specification for Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings Table 1102.5, Table 1403.2 D 2751—05 Specification for Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings Table 702.4, Table 1102.7 D 2846—09be1 Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Hot and Cold Water Distribution Systems Table 1301.6 D 2855—96 (2010) Standard Practice for Making Solvent-cemented Joints with Poly (Vinyl Chloride) (PVC) Pipe and Fittings 705.11.2 D 2949—10 Specification for 3.25-in Outside Diameter Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings Table 702.1, Table 702.4, Table 1403.2.1 D 3034—08 Specification for Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7, Table 1403.2.1 D 3212—07 Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals 705.2.1, 705.11.1, 705.13.2 D 3311—11 Specification for Drain, Waste and Vent (DWV) Plastic Fittings Patterns Table 1102.7 D 3350—14 Specification for High Density Polyethylene Pipe (HPDE) Table 1102.4, Table 1102.7 D 4068—09 Specification for Chlorinated Polyethlene (CPE) Sheeting for Concealed Water-containment Membrane 417.5.2.2 D 4551—12 Specification for Poly (Vinyl Chloride) (PVC) Plastic Flexible Concealed Water-containment Membrane 417.5.2.1 F 405—05 Specification for Corrugated Polyethylene (PE) Pipe and Fittings Table 1102.5, Table 1403.2, Table 1403.2.1 F 409—12 Specification for Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings 424.1.2 F 437—15 Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 Table 702.3, Table 702.4, Table 1102.4, Table 1102.7 F 438—17 Specification for Socket-type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40 Table 702.3, Table 702.4, Table 1102.4, Table 1102.7 F 439—13 Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 Table 702.3, Table 702.4, Table 1102.4, Table 1102.7 F 477—10 Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe 705.16 F 628—08 Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe with a Cellular Core Table 702.1, Table 702.4, 705.2.2, Table 1102.7 F 656—10 Specification for Primers for Use in Solvent Cement Joints of Poly (Vinyl Chloride) (PVC) Plastic Pipe and Fittings 705.11.2 F 891—10 Specification for Coextruded Poly (Vinyl Chloride) (PVC) Plastic Pipe with a Cellular Core Table 702.1 Table 702.2, Table 702.3, Table 1102.4, Table 1102.5 F 1412—09 Specification for Polyolefin Pipe and Fittings for Corrosive Waste Drainage Table 702.2, Table 803.3.1, Table 803.3.2, 803.3.4.4.1, 803.3.4.5.1, Table 1102.7 F 1488—09e1 Specification for Coextruded Composite Pipe Table 702.1, Table 702.2, Table 1403.2 F 1673—10 Polyvinylidene Fluoride (PVDF) Corrosive Waste Drainage Systems Table 803.3.1, Table 803.3.2, 803.3.4.6.1, Table 1102.7 F 1866—07 Specification for Poly (Vinyl Chloride) (PVC) Plastic Schedule 40 Drainage and DWV Fabricated Fittings Table 702.4, Table 1102.7, Table 1403.2.1 F 2306 / F 2306M—13 12'' to 60'' Annular Corrugated Profile-wall Polyethylene (PE) Pipe and Fittings for Gravity Flow Storm Sewer and Subsurface Drainage Applications Table 702.4, Table 1102.7 F 2389—10 Specification for Pressure-rated Polypropylene (PP) Piping Systems Table 1301.6, Table 1403.2, Table 1403.2.1 F 2618—15 Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe and Fittings for Chemical Waste Drainage Systems Table 803.3.1, Table 803.3.2, 803.3.4.1.2 F 2764—17e1 Standard Specification for 6 to 60 in. Polypropylene (PP) Corrugated Double and Triple Wall Pipe Table 1102.5 F 3219—17 Standard Specification for 3 to 30 in. (75 To 750 mm) Polypropylene (PP) Corrugated Single Wall Pipe and Fittings Table 1102.5
AWS American Welding Society 8669 NW 36 Street, #130 Doral, FL 33166 Standard reference number Title Referenced in code section number A5.8M / A5.8—2011 Specifications for Filler Metals for Brazing and Braze Welding 605.11.1, 605.13.1, 605.14.1, 705.3.1, 705.6.1, 705.7.1,
AWWA American Water Works Association 6666 West Quincy Avenue Denver, CO 80235 Standard reference number Title Referenced in code section number C110 / A21.10—12 Ductile-iron and Gray-iron Fittings Table 605.5, Table 702.4, Table 1102.7 C111 / A21.11—12 Rubber-gasket Joints for Ductile-iron Pressure Pipe and Fittings 605.12 C115 / A21.15—11 Flanged Ductile-iron Pipe with Ductile-iron or Gray-iron Threaded Flanges Table 605.4, Table 605.4.1 C151 / A21.51—02 Standard for Ductile-iron Pipe, Centrifugally Cast for Water Table 605.4, Table 605.4.1, Table 702.1, Table 702.2. Table 702.3, Table 1102.4 C153—00 / A21.53—11 Ductile-iron Compact Fittings for Water Service Table 605.5 C500—09 Standard for Metal-Seated Gate Valves for Water Supply Service Table 605.7 C504—10 Standard for Rubber-Seated Butterfly Valves Table 605.7 C507—11 Standard for Ball Valves, 6 In. Through 60 In Table 605.7 C510—07 Double Check Valve Backflow Prevention Assembly Table 608.1, 608.13.7 C511—07 Reduced-pressure Principle Backflow Prevention Assembly Table 608.1, 608.13.2, 608.16.2 C651—05 Disinfecting Water Mains 610.1 C652—11 Disinfection of Water-storage Facilities 610.1 D100—2005 Standard for Welded Carbon Steel Tanks for Water Storage 1302.7.2, 1303.10.2 D115—2006 Standard for Tendon Prestressed-Concrete Water Tanks 1302.7.2, 1303.10.2 D120—2009 Standard for Thermosetting Fiberglass Reinforced Plastic Tanks 1302.7.2, 1303.10.2
CISPI Cast Iron Soil Pipe Institute 5959 Shallowford Road, Suite 419 Chattanooga, TN 37421 Standard reference number Title Referenced in code section number 301—04a Specification for Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste and Vent Piping Applications Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7 310—11 Specification for Coupling for Use in Connection with Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste and Vent Piping Applications 308.5.1, 308.6.1, 705.4.3
CSA CSA Group 8501 East Pleasant Valley Cleveland, OH 44131-5516 Standard reference number Title Referenced in code section number A257.1M—2009 Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings Table 702.3, Table 1102.4 A257.2M—2009 Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings Table 702.3, Table 1102.4 A257.3M—2009 Joints for Circular Concrete Sewer and Culvert Pipe, Manhole Sections and Fittings Using Rubber Gaskets 705.5, 705.16 ASME A112.3.4—2013 / CSA B45.9—2013 Macerating Systems and Related Components 712.4.1 ASME A112.18.1—2012 / CSA B125.1—2012 Plumbing Supply Fittings 424.1, 424.2, 424.3, 424.4, 424.6, 424.8, Table 605.7, 607.4, 608.2 ASME A112.18.2—2011 / CSA B125.2—2011 Plumbing Waste Fittings 424.1.2 ASME A112.19.1—2013 / CSA B45.2—2013 Enameled Cast-iron and Enameled Steel Plumbing Fixtures 407.1, 410.1, 415.1, 416.1, 418.1 ASME A112.19.2—2013 / CSA B45.1—2013 Ceramic Plumbing Fixtures 401.2, 405.9, 407.1, 408.1, 410.1, 415.1, 416.1, 417.1, 418.1, 419.1, 420.1 ASME A112.19.3—2008 / CSA B45.4—08 (R2013) Stainless-steel Plumbing Fixtures 405.9, 407.1, 415.1, 416.1, 418.1, 420.1 ASME A112.19.5—2011 / CSA B45.15—2011 Flush Valves and Spuds for Water-closets, Urinals and Tanks 425.4 ASME A112.19.7—2012 / CSA B45.10—2012 Hydromassage Bathtub Systems 421.1, 421.4 ASSE 1016 / ASME A112.1016 / CSA B125.16—2011 Performance Requirements for Individual Thermostatic, Pressure Balancing and Combination Control Valves for Individual Fixture Fittings 424.3, 424.4, 607.4 CSA B45.5—11 / IAPMO Z124—2011 Plastic Plumbing Fixtures 407.1, 415.1, 416.1, 416.2, 417.1, 418.1, 419.1, 420.1 B64.1.1—11 Vacuum Breakers, Atmospheric Type (AVB) 425.2, Table 608.1, 608.13.6, 608.16.4.1 B64.1.2—11 Pressure Vacuum Breakers, (PVB) Table 608.1, 608.13.5 B64.1.3—11 Spill Resistant Pressure Vacuum Breaks (SRPVB) 608.13.8 B64.2—11 Vacuum Breakers, Hose Connection Type (HCVB) Table 608.1, 608.13.6 B64.2.1—11 Vacuum Breakers, Hose Connection (HCVB) with Manual Draining Feature Table 608.1, 608.13.6 B64.2.1.1—11 Hose Connection Dual Check Vacuum Breakers, (HCDVB) Table 608.1, 608.13.6 B64.2.2—11 Vacuum Breakers, Hose Connection Type (HCVB) with Automatic Draining Feature Table 608.1, 608.13.6 B64.3—11 Backflow Preventers, Dual Check Valve Type with Atmospheric Port (DCAP) Table 608.1, 608.13.3, 608.16.2 B64.4—11 Backflow Preventers, Reduced Pressure Principle Type (RP) Table 608.1, 608.13.2 B64.4.1—11 Reduced Pressure Principle for Fire Sprinklers (RPF) Table 608.1, 608.13.2 B64.5—11 Double Check Backflow Preventers (DCVA) Table 608.1, 608.13.7 B64.5.1—11 Double Check Valve Backflow Preventer for Fire Systems (DCVAF) Table 608.1 608.13.7 B64.6—11 Dual Check Backflow Preventers Valve (DuC) Table 608.1, 608.13.10 B64.7—11 Laboratory Faucet Vacuum Breakers (LFVB) Table 608.1, 608.13.6 B64.10—11 Manual for the Selection and Installation of Backflow Prevention Devices 312.10.2 B64.10.1—11 Maintenance and Field Testing of Backflow Preventers 312.10.2 B79—08 (R2013) Commercial and Residential Drains, and Cleanouts 412.1 B125.3—2012 Plumbing Fittings 408.3, 423.3, 424.4, 424.5, 425.2, 425.3.1, Table 605.7 B137.2—02 PVC Injection-Moulded Gasketed Fittings for Pressure Applications Table 1102.7 B137.3—13 Rigid Poly (Vinyl Chloride) (PVC) Pipe for Pressure Applications 705.11.2 B181.1—11 Acrylonitrile-butadiene-styrene ABS Drain, Waste and Vent Pipe and Pipe Fittings Table 702.1, Table 702.4, 705.2.2, 715.2, Table 1102.7 B181.2—11 Polyvinylchloride PVC and chlorinated polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings Table 702.1 Table 702.2, Table 702.3, 705.11.2, 715.2, Table 1102.4 B181.3—11 Polyolefin and Polyvinylidene Fluoride (PVDF) Laboratory Drainage Systems Table 803.3.1, Table 803.3.2, 803.3.4.4.1, Table 1102.7 B182.1—11 Plastic Drain and Sewer Pipe and Pipe Fittings 705.11.2, Table 1102.5 B182.2—11 PSM Type Polyvinylchloride PVC Sewer Pipe and Fittings Table 702.3, Table 1102.4, Table 1102.5 B182.4—11 Profile Polyvinylchloride PVC Sewer Pipe and Fittings Table 702.3, Table 1102.4, Table 1102.5 B182.6—11 Profile Polyethylene (PE) Sewer Pipe and Fittings for Leak- proof Sewer Applications Table 1102.5 B182.8—11 Profile Polyethylene (PE) Storm Sewer and Drainage Pipe and Fittings Table 1102.5 B356—10 Water Pressure Reducing Valves for Domestic Water Systems 604.8 B483.1—14 Drinking Water Treatment Units 611.1, 611.2 B602—10 Mechanical Couplings for Drain, Waste and Vent Pipe and Sewer Pipe 705.2.1, 705.4.3, 705.5, 705.11.1, 705.12, 705.13.2, 705.16
IAPMO IAPMO Group 4755 E. Philadelphia Ontario, CA 91761 Standard reference number Title Referenced in code section number PS 117—08 Copper and Copper Allow Tubing System Incorporating Press-type or Nail-type Connections 605.14.4 CSA B45.5—11 / IAPMO Z124—2011 Plastic Plumbing Fixtures 407.1, 415.1, 416.1, 416.2, 417.1, 418.1, 419.1, 420.1
ICC International Code Council, Inc. 500 New Jersey Ave, NW 6th Floor Washington, DC 20001 Standard reference number Title Referenced in code section number A117.1—2009 Accessible and Usable Buildings and Facilities 404.2, 410.1
ISEA International Safety Equipment Association 1901 N. Moore Street, Suite 808 Arlington, VA 22209 Standard reference number Title Referenced in code section number ANSI / ISEA Z358.1—2009 Emergency Eyewash and Shower Equipment 411.1
MSS Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. 127 Park St. NE Vienna, VA 22180-4602 Standard reference number Title Referenced in code section number SP-67—2011 Butterfly Valves Table 605.7 SP-70—2011 Gray Iron Gate Valves, Flanged and Threaded Ends Table 605.7 SP-71—2011 Gray Iron Swing Check Valves, Flanged and Threaded Ends Table 605.7 SP-72—2010 Ball Valves with Flanged or Butt-Welding Ends for General Service Table 605.7 SP-78—2011 Cast Iron Plug Valves, Flanged and Threaded Ends Table 605.7 SP-80—2008 Bronze Gate, Globe, Angle and Check Valves Table 605.7 SP-110—2010 Ball Valves, Threaded, Socket Welded, Solder Joint, Grooved and Flared Ends Table 605.7
NFPA National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 Standard reference number Title Referenced in code section number 51—13 Design and Installation of Oxygen-fuel Gas Systems for Welding, Cutting and Allied Processes 1201.1, 1203.1 55—13 Compressed Gases and Cryogenic Fluids Code 1201.1, 1203.1 99—15 Health Care Facilities Code 1201.1, 1202.1
NSF NSF International 789 Dixboro Road Ann Arbor, MI 48105 Standard reference number Title Referenced in code section number 3—2010 Commercial Warewashing Equipment 409.1 14—2011 Plastic Piping System Components and Related Materials 303.3, 611.3 18—2012 Manual Food and Beverage Dispensing Equipment 426.1 42—2011 Drinking Water Treatment Units-Aesthetic Effects 611.1, 611.3 44—2012 Residential Cation Exchange Water Softeners 611.1, 611.3 53—2011a Drinking Water Treatment Units—Health Effects 611.1, 611.3 58—2012 Reverse Osmosis Drinking Water Treatment Systems 611.2, 611.3 61—2012 Drinking Water System Components—Health Effects 410.1, 424.1, 605.4, 605.4.1, 605.5, 605.7, 606.5.4.2, 611.3 62—2012 Drinking Water Distillation Systems 611.1 372—2010 Drinking Water Systems Components—Lead Content 605.2
PDI Plumbing and Drainage Institute 800 Turnpike Street, Suite 300 North Andover, MA 01845 Standard reference number Title Referenced in code section number G101 (2012) Testing and Rating Procedure for Grease Interceptors with Appendix of Sizing and Installation Data 1003.3.4
UL UL LLC 333 Pfingsten Road Northbrook, IL 60062-2096 Standard reference number Title Referenced in code section number 58—1996 Steel Underground Tanks for Flammable and Combustible Liquids—with revisions through July 27, 1998 1302.7.2, 1303.10.2 142—2006 Steel Aboveground Tanks for Flammable and Combustible Liquids—with revisions through February 12, 2010 1302.7.2, 1303.10.2 174—2004 Household Electric Storage Tank Water Heaters—with revisions through September 2012 502.1 430—2009 Waste Disposers—with revisions through March 23, 2011 413.1 732—1995 Oil-fired Storage Tank Water Heaters—with revisions through April 2010 502.1 921—2004 Integral gas fired heating commercial dishwashers 409.1 1316—1994 Glass-Fiber Reinforced Plastic Underground Storage Tanks for Petroleum Products, Alcohols and Alcohol Gasoline Mixtures—with revisions through May 12, 2006 1302.7.2, 1303.10.2 1453—2004 Electric Booster and Commercial Storage Tank Water Heaters—with revisions through July 2011 502.1 1746—2007 External Corrosion Protection Systems for Steel Underground Storage Tanks 1302.7.2, 1303.10.2 1795—2009 Hydromassage Bathtubs including revisions through August 23, 2011 421.1
WaterSense WaterSense U.S. Environmental Protection Agency Office of Wastewater Management (4204M) 1200 Pennsylvania Avenue, N.W. Washington, D.C. 20460 Standard reference number Title Referenced in code section number v.1.0—October 1, 2007 High-efficiency Lavatory Faucet Specifications 604.4.1 v.1.0—October 8, 2009 WaterSense Specification for Flushing Urinals 604.4.1 v.1.0—December 17, 2015 WaterSense Specification for Flushometer-Valve Water Closets 604.4.1 v.1.1—July 26, 2018 WaterSense Specification for Showerheads 604.4.1 v.1.2—June 2, 2014 WaterSense Specification for Tank-Type Toilets 604.4.1
Section PC C101. Cutting, Notching and Boring
C101.1 Cutting, notching and boring in wood members.
The cutting, notching and boring of wood members shall comply with Sections C101.1.1 through C101.1.5.
C101.1.1 Engineered wood products.
Cuts, notches and holes bored in trusses, structural composite lumber, structural glued-laminated members or I-joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional.
C101.1.2 Solid non-engineered joist notches and holes.
Notches on the ends of the solid non-engineered joists shall not exceed one-fourth the joist depth. Notches in the top or bottom of joists shall not exceed one-sixth the depth, shall not be longer than one-third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (51 mm) of the top or bottom of the joist, and the diameter of any such hole shall not exceed one-third of the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (51 mm). See Figure 2308.5.8 of the New York City Building Code .
C101.1.3 Stud cutting and notching.
In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5.8 of the New York City Building Code .
C101.1.4 Bored holes in studs.
Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5/8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code .
C101.1.5 Drilling and notching of top plate.
When piping is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1/2 inches (38 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1/2 inches (38 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches past the opening. See Figure 2308.5.8 of the New York City Building Code .
Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing, additional fastening is not required.
C101.2 Cutting, notching and boring in steel members.
The cutting, notching and boring of steel members shall comply with Sections C101.2.1 through C101.2.4.
C101.2.1 Structural steel framing.
The cutting, notching and boring of holes in structural steel framing members shall be as prescribed by the registered design professional.
C101.2.2 Cold-formed steel framing.
Flanges and lips of load-bearing, cold-formed steel framing members shall not be cut or notched. Holes in webs of load-bearing, cold-formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, penetration spacing or minimum hole edge distance as prescribed by the registered design professional.
C101.2.3 Nonstructural cold-formed steel wall framing.
Flanges and lips of nonstructural cold- formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1/2 inches (38 mm) in width or 4 inches (102 mm) in length, and the holes shall not be spaced less than 24 inches (610 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end.
C101.2.4 Steel floor and roof decking.
Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional.
C101.3 Cutting, notching and coring into concrete.
The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional.
Section PC E101. General
E101.1 Scope.
E101.1.1
This appendix outlines the procedure that may be utilized for sizing a water piping system (see Section E103.3). The design procedure is based on the minimum static pressure available from the supply source, the head changes in the system caused by friction and elevation, and the rates of flow necessary for operation of various fixtures.
Section PC E102. Information Required
E102.1 Preliminary.
Obtain the necessary information regarding the minimum daily static service pressure in the area where the building is to be located. If the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow for meters in the range of sizes likely to be used. Friction loss data can be obtained from most manufacturers of water meters.
E102.2 Demand load.
E102.2.1
Estimate the supply demand of the building main and the principal branches and risers of the system by totaling the corresponding demand from the applicable part of Table E103.3(3).
E102.2.2
Estimate continuous supply demands in gallons per minute (L/m) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand for fixtures. The result is the estimated supply demand for the building supply.
Section PC E103. Selection of Pipe Size
This section has 6 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section PC E103 at American Legal Publishing.
E103.1 General.
Decide from Table 604.3 what is the desirable minimum residual pressure that should be maintained at the highest fixture in the supply system. If the highest group of fixtures contains flushometer valves, the pressure for the group should be not less than 15 pounds per square inch (psi) (103.4 kPa) flowing. For flush tank supplies, the available pressure should be not less than 8 psi (55.2 kPa) flowing, except blowout action fixtures must be not less than 25 psi (172.4 kPa) flowing.
E103.2 Pipe sizing.
E103.2.1 Pipe sizes can be selected according to the following procedure or by other design methods conforming to acceptable engineering practice and approved by the department. The sizes selected must not be less than the minimum required by this code.
E103.2.2 Water pipe sizing procedures are based on a system of pressure requirements and losses, the sum of which must not exceed the minimum pressure available at the supply source. These pressures are as follows:
1. Pressure required at fixture to produce required flow. See Sections 604.3 and 604.5.
2. Static pressure loss or gain (due to head) is computed at 0.433 psi per foot (9.8 kPa/m) of elevation change.
Example: Assume that the highest fixture supply outlet is 20 feet (6096 mm) above or below the supply source. This produces a static pressure differential of 20 feet by 0.433 psi/foot (6096 mm by 9.8 kPa/m), equaling 8.66 psi (59.8 kPa).
3. Loss through water meter. The friction or pressure loss can be obtained from meter manufacturers.
4. Loss through taps in water main.
5. Losses through special devices such as filters, softeners, backflow prevention devices and pressure regulators. These values must be obtained from the manufacturers.
6. Loss through valves and fittings. Losses for these items are calculated by converting to equivalent length of piping and adding to the total pipe length.
7. Loss due to pipe friction can be calculated when the pipe size, the pipe length and the flow through the pipe are known. With these three items, the friction loss can be determined using Figures E103.3(2), E103.3(3), E103.3(5), E103.3(6), and E103.3(7). For piping flow charts not included, use manufacturers' tables and velocity recommendations.
Note: For the purposes of all examples, the following metric conversions are applicable:
1 cubic foot per minute = 0.4719 L/s
1 square foot = 0.0929 m 2
1 degree = 0.0175 rad
1 pound per square inch = 6.895 kPa
1 inch = 25.4 mm
1 foot = 304.8 mm
1 gallon per minute = 3.785 L/m
E103.3 Segmented loss method.
The size of water service mains, branch mains and risers by the segmented loss method, must be determined according to water supply demand gpm (L/m), available water pressure psi (kPa) and friction loss caused by the water meter and developed length of pipe feet (m), including equivalent length of fittings. This design procedure is based on the following parameters:
• Calculation of the friction loss through each length of the pipe.
• Evaluation of pressure losses, the sum of which must not exceed the minimum pressure available at the street main or other source of supply.
• Pipe sizing shall be based on (1) estimated peak demand, (2) total pressure losses caused by difference in elevation, equipment, developed length and pressure required at most remote fixture, (3) loss through taps in water main, (4) losses through fittings, filters, backflow prevention devices, valves and pipe friction.
Because of the variable conditions encountered in hydraulic design, it is impractical to specify definite and detailed rules for sizing of the water piping system. Current sizing methods do not address the differences in the probability of use and flow characteristics of fixtures between types of occupancies. Creating an exact model of predicting the demand for a building is impossible and final studies assessing the impact of water conservation on demand are not yet complete. The following steps are necessary for the segmented loss method.
1. Preliminary. Obtain the necessary information regarding the minimum daily static service pressure in the area where the building is to be located. If the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow for meters in the range of sizes to be used. Friction loss data can be obtained from manufacturers of water meters. It is essential that enough pressure be available to overcome all system losses caused by friction and elevation so that plumbing fixtures operate properly. Section 604.6 requires the water distribution system to be designed for the minimum pressure available taking into consideration pressure fluctuations. The lowest pressure must be selected to guarantee a continuous, adequate supply of water. The lowest pressure in the public main usually occurs in the summer because of lawn sprinkling and supplying water for air-conditioning cooling towers. Future demands placed on the public main as a result of large growth or expansion should also be considered. The available pressure will decrease as additional loads are placed on the public system.
2. Demand load. Estimate the supply demand of the building main and the principal branches and risers of the system by totaling the corresponding demand from the applicable part of Table E103.3(3). When estimating peak demand sizing methods typically use water supply fixture units (see Table E103.3(2)). This numerical factor measures the load-producing effect of a single plumbing fixture of a given kind. The use of such fixture units can be applied to a single basic probability curve (or table), found in the various sizing methods (Table E103.3(3)). The fixture units are then converted into gallons per minute (L/m) flow rate for estimating demand.
2.1. Estimate continuous supply demand in gallons per minute (L/m) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand for fixtures. The result is the estimated supply demand for the building supply. Fixture units cannot be applied to constant use fixtures such as hose bibbs, lawn sprinklers and air conditioners. These types of fixtures must be assigned the gallon per minute (L/m) value.
3. Selection of pipe size. This water pipe sizing procedure is based on a system of pressure requirements and losses, the sum of which must not exceed the minimum pressure available at the supply source. These pressures are as follows:
3.1. Pressure required at the fixture to produce required flow. See Sections 604.3 and 604.5.
3.2. Static pressure loss or gain (because of head) is computed at 0.433 psi per foot (9.8 kPa/m) of elevation change.
3.3. Loss through a water meter. The friction or pressure loss can be obtained from the manufacturer.
3.4. Loss through taps in water main (see Table E103.3(4) ).
3.5. Losses through special devices such as filters, softeners, backflow prevention devices and pressure regulators. These values must be obtained from the manufacturers.
3.6. Loss through valves and fittings. Losses for these items are calculated by converting to equivalent length of piping and adding to the total pipe length. (see Tables E103.3(5) and E103.3(6) ).
3.7. Loss due to pipe friction can be calculated when the pipe size, the pipe length and the flow through the pipe are known. With these three items, the friction loss can be determined using Figures E103.3(2), E103.3(3), E103.3(5), E103.3(6), and E103.3(7). When using charts, use pipe inside diameters. For piping flow charts not included, use manufacturers' tables and velocity recommendations. Before attempting to size any water supply system, it is necessary to gather preliminary information which includes available pressure, piping material, select design velocity, elevation differences and developed length to most remote fixture. The water supply system is divided into sections at major changes in elevation or where branches lead to fixture groups. The peak demand must be determined in each part of the hot and cold water supply system which includes the corresponding water supply fixture unit and conversion to gallons per minute (L/m) flow rate to be expected through each section. Sizing methods require the determination of the "most hydraulically remote" fixture to compute the pressure loss caused by pipe and fittings. The hydraulically remote fixture represents the most downstream fixture along the circuit of piping requiring the most available pressure to operate properly. Consideration must be given to all pressure demands and losses, such as friction caused by pipe, fittings and equipment, elevation and the residual pressure required by Table 604.3. The two most common and frequent complaints about the water supply system operation are lack of adequate pressure and noise.
Problem: What size Type L copper water pipe, service and distribution will be required to serve a two-story factory building having on each floor, back-to-back, two toilet rooms each equipped with hot and cold water? The highest fixture is 21 feet (6401 mm) above the street main, which is tapped with a 2-inch (51 mm) corporation cock at which point the minimum pressure is 55 psi (379.2 kPa). In the building basement, a 2-inch (51 mm) meter with a maximum pressure drop of 11 psi (75.8 kPa) and 3-inch (76 mm) reduced pressure principle backflow preventer with a maximum pressure drop of 9 psi (621 kPa) are to be installed. The system is shown by Figure E103.3(1). To be determined are the pipe sizes for the service main and the cold and hot water distribution pipes.
Solution: A tabular arrangement such as shown in Table E103.3(1) should first be constructed. The steps to be followed are indicated by the tabular arrangement itself as they are in sequence, Columns 1 through 10 and Lines A through L.
Step 1 Columns 1 and 2: Divide the system into sections breaking at major changes in elevation or where branches lead to fixture groups. After point B (see Figure E103.3(1)), separate consideration will be given to the hot and cold water piping. Enter the sections to be considered in the service and cold water piping in Column 1 of the tabular arrangement. Column 1 of Table E103.3(1) provides a line-by-line recommended tabular arrangement for use in solving pipe sizing.
The objective in designing the water supply system is to ensure an adequate water supply and pressure to all fixtures and equipment. Column 2 provides the pounds per square inch (psi) to be considered separately from the minimum pressure available at the main. Losses to take into consideration are the following: the differences in elevation between the water supply source and the highest water supply outlet, meter pressure losses, the tap in main loss, special fixture devices such as water softeners and prevention devices and the pressure required at the most remote fixture outlet. The difference in elevation can result in an increase or decrease in available pressure at the main. Where the water supply outlet is located above the source, this results in a loss in the available pressure and is subtracted from the pressure at the water source. Where the highest water supply outlet is located below the water supply source, there will be an increase in pressure that is added to the available pressure of the water source.
Column 3: According to Table E103.3(3), determine the gpm (L/m) of flow to be expected in each section of the system. These flows range from 28.6 to 108 gpm. Load values for fixtures must be determined as water supply fixture units and then converted to a gallon-per-minute (gpm) rating to determine peak demand. When calculating peak demands, the water supply fixture units are added and then converted to the gallon-per-minute rating. For continuous flow fixtures such as hose bibbs and lawn sprinkler systems, add the gallon-per-minute demand to the intermittent demand of fixtures. For example, a total of 120 water supply fixture units is converted to a demand of 48 gallons per minute. Two hose bibbs × 5 gpm demand = 10 gpm. Total gpm rating = 48.0 gpm + 10 gpm = 58.0 gpm demand.
Step 2 Line A: Enter the minimum pressure available at the main source of supply in Column 2. This is 55 psi (379.2 kPa). The local water authorities generally keep records of pressures at different times of day and year. The available pressure can also be checked from nearby buildings or from fire department hydrant checks.
Line B: Determine from Table 604.3 the highest pressure required for the fixtures on the system, which is 15 psi (103.4 kPa), to operate a flushometer valve. The most remote fixture outlet is necessary to compute the pressure loss caused by pipe and fittings, and represents the most downstream fixture along the circuit of piping requiring the available pressure to operate properly as indicated by Table 604.3.
Line C: Determine the pressure loss for the meter size given or assumed. The total water flow from the main through the service as determined in Step 1 will serve to aid in the meter selected. There are three common types of water meters; the pressure losses are determined by the American Water Works Association Standards for displacement type, compound type and turbine type. The maximum pressure loss of such devices takes into consideration the meter size, safe operating capacity (gpm) and maximum rates for continuous operations (gpm). Typically, equipment imparts greater pressure losses than piping.
Line D: Select from Table E103.3(4) and enter the pressure loss for the tap size given or assumed. The loss of pressure through taps and tees in pounds per square inch (psi) are based on the total gallon-per-minute flow rate and size of the tap.
Line E: Determine the difference in elevation between the main and source of supply and the highest fixture on the system. Multiply this figure, expressed in feet, by 0.43 psi (2.9 kPa). Enter the resulting psi loss on Line E. The difference in elevation between the water supply source and the highest water supply outlet has a significant impact on the sizing of the water supply system. The difference in elevation usually results in a loss in the available pressure because the water supply outlet is generally located above the water supply source. The loss is caused by the pressure required to lift the water to the outlet. The pressure loss is subtracted from the pressure at the water source. Where the highest water supply outlet is located below the water source, there will be an increase in pressure that is added to the available pressure of the water source.
Lines F, G and H: The pressure losses through filters, backflow prevention devices or other special fixtures must be obtained from the manufacturer or estimated and entered on these lines. Equipment such as backflow prevention devices, check valves, water softeners, instantaneous or tankless water heaters, filters and strainers can impart a much greater pressure loss than the piping. The pressure losses can range from 8 psi to 30 psi.
Step 3 Line I: The sum of the pressure requirements and losses that affect the overall system (Lines B through H) is entered on this line. Summarizing the steps, all of the system losses are subtracted from the minimum water pressure. The remainder is the pressure available for friction, defined as the energy available to push the water through the pipes to each fixture. This force can be used as an average pressure loss, as long as the pressure available for friction is not exceeded. Saving a certain amount for available water supply pressures as an area incurs growth, or because of aging of the pipe or equipment added to the system is recommended.
Step 4 Line J: Subtract Line I from Line A. This gives the pressure that remains available from overcoming friction losses in the system. This figure is a guide to the pipe size that is chosen for each section, incorporating the total friction losses to the most remote outlet (measured length is called developed length).
Exception: When the main is above the highest fixture, the resulting psi must be considered a pressure gain (static head gain) and omitted from the sums of Lines B through H and added to Line J. The maximum friction head loss that can be tolerated in the system during peak demand is the difference between the static pressure at the highest and most remote outlet at no-flow conditions and the minimum flow pressure required at that outlet. If the losses are within the required limits, then every run of pipe will also be within the required friction head loss. Static pressure loss is the most remote outlet in feet × 0.433 = loss in psi caused by elevation differences.
Step 5 Column 4: Enter the length of each section from the main to the most remote outlet (at Point E). Divide the water supply system into sections breaking at major changes in elevation or where branches lead to fixture groups.
Step 6 Column 5: When selecting a trial pipe size, the length from the water service or meter to the most remote fixture outlet must be measured to determine the developed length. However, in systems having a flushometer valve or temperature controlled shower at the topmost floors the developed length would be from the water meter to the most remote flushometer valve on the system. A rule of thumb is that size will become progressively smaller as the system extends farther from the main source of supply. Trial pipe size may be arrived at by the following formula:
Line J (Pressure available to overcome pipe friction) × 100/equivalent length of run total developed length to most remote fixture × percentage factor of 1.5 (note: a percentage factor is used only as an estimate for friction losses imposed for fittings for initial trial pipe size) = psi (average pressure drops per 100 feet of pipe).
For trial pipe size, see Figure E103.3(3) (Type L copper) based on 2.77 psi and a 108 gpm = 2 1/2 inches. To determine the equivalent length of run to the most remote outlet, the developed length is determined and added to the friction losses for fittings and valves. The developed lengths of the designated pipe sections are as follows:
A-B 54 Feet
B-C 8 feet
C-D 13 feet
D-E 150 feet
Total developed length = 225 feet
The equivalent length of the friction loss in fittings and valves must be added to the developed length (most remote outlet). Where the size of fittings and valves is not known, the added friction loss should be approximated. A general rule that has been used is to add 50 percent of the developed length to allow for fittings and valves. For example, the equivalent length of run equals the developed length of run (225 ft × 1.5 = 338 ft). The total equivalent length of run for determining a trial pipe size is 338 feet.
Example: 9.36 (pressure available to overcome pipe friction) x 100/338 (Equivalent length of run = 225 × 1.5) = 2.77 psi (average pressure drop per 100 feet of pipe).
Step 7 Column 6: Select from Table E103.3(6) the equivalent lengths for the trial pipe size of fittings and valves on each pipe section. Enter the sum for each section in Column 6. (The number of fittings to be used in this example must be an estimate.) The equivalent length of piping is the developed length plus the equivalent lengths of pipe corresponding to friction head losses for fittings and valves. Where the size of fittings and valves is not known, the added friction head losses must be approximated. An estimate for this example is found in Table E.1.
Table E.1
Cold Water Pipe Section Fittings / Valves Pressure Loss Expressed as Equivalent Length of Tube (Feet) Hot Water Pipe Section Fittings / Valves Pressure Loss Expressed as Equivalent Length of Tube (Feet) A-B 3 - 2 1/2" Gate valves 3 A-B 3 - 2 1/2" Gate valves 3 1 - 2 1/2" Side branch tee 12 1 - 2 1/2" Side branch tee 12 B-C 1 - 2 1/2" Straight run tee 0.5 B-C 1 - 2" Straight run tee 7 1 - 2" 90-degree ell 0.5 C-F 1 - 2 1/2" Side branch tee 12 C-F 1 - 1 1/2" Side branch tee 7 C-D 1 - 2 1/2" 90-degree ell 7 C-D 1 - 1/2" 90-degree ell 4 D-E 1 - 2 1/2" Side branch tee 12 D-E 1 - 1 1/2" Side branch tee 7
Step 8 Column 7: Add the figures from Column 4 and Column 6, and enter in Column 7. Express the sum in hundreds of feet.
Step 9 Column 8: Select from Figure E103.3(3) the friction loss per 100 feet (30 480 mm) of pipe for the gallon-per-minute flow in a section (Column 3) and trial pipe size (Column 5). Maximum friction head loss per 100 feet is determined on the basis of total pressure available for friction head loss and the longest equivalent length of run. The selection is based on the gallon-per-minute demand, the uniform friction head loss and the maximum design velocity. Where the size indicated by hydraulic table indicates a velocity in excess of the selected velocity, a size must be selected that produces the required velocity.
Step 10 Column 9: Multiply the figures in Columns 7 and 8 for each section and enter in Column 9.
Step 10 Column 9: Multiply the figures in Columns 7 and 8 for each section and enter in Column 9.
Total friction loss is determined by multiplying the friction loss per 100 feet (30 480 mm) for each pipe section in the total developed length by the pressure loss in fittings expressed as equivalent length in feet. Note: Section C-F should be considered in the total pipe friction losses only if greater loss occurs in Section C-F than in pipe Section D-E. Section C-F is not considered in the total developed length. Total friction loss in equivalent length is determined in Table E.2 .
Table E.2
Pipe Sections Friction Loss Equivalent Length (feet) Cold Water Hot Water A-B 0.69 × 3.2 = 2.21 0.69 × 3.2 = 2.21 B-C 0.085 × 3.1 = 0.26 0.16 × 1.4 = 0.22 C-D 0.20 × 1.9 = 0.38 0.17 × 3.2 = 0.54 D-E 1.62 × 1.9 = 3.08 1.57 × 3.2 = 5.02 Total pipe friction losses (Line K) 5.93 7.99
For SI: 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.
Step 11 Line K: Enter the sum of the values in Column 9. The value is the total friction loss in equivalent length for each designated pipe section.
Step 12 Line L: Subtract Line J from Line K and enter in Column 10.
The result should always be a positive or plus figure. If it is not, repeat the operation using Columns 5, 6, 8 and 9 until a balance or near balance is obtained. If the difference between Lines J and K is a high positive number, it is an indication that the pipe sizes are too large and should be reduced, thus saving materials. In such a case, the operations using Columns 5, 6, 8 and 9 should again be repeated.
The total friction losses are determined and subtracted from the pressure available to overcome pipe friction for trial pipe size. This number is critical as it provides a guide to whether the pipe size selected is too large and the process should be repeated to obtain an economically designed system.
Answer: The final figures entered in Column 5 become the design pipe size for the respective sections. Repeating this operation a second time using the same sketch but considering the demand for hot water, it is possible to size the hot water distribution piping. This has been worked up as a part of the overall problem in the tabular arrangement used for sizing the service and water distribution piping. Note that consideration must be given to the pressure losses from the street main to the water heater (Section A-B) in determining the hot water pipe sizes.
Figure E103.3(1) Example - Sizing
For SI: 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.
Figure E103.3(2) Friction Loss in Smooth Pipe a (Type K, ASTM B 88 Copper Tubing)
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.
Figure E103.3(3) Friction Loss in Smooth Pipe a (Type L, ASTM B 88 Copper Tubing)
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.
Figure E103.3(5) Friction Loss in Fairly Smooth Pipe a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to smooth new steel (fairly smooth) pipe and to actual diameters of standard- weight pipe.
Figure E103.3(6) Friction Loss in Fairly Rough Pipe a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to fairly rough pipe and to actual diameters which in general will be less than the actual diameters of the new pipe of the same kind.
Figure E103.3(7) Friction Loss in Rough Pipe a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to very rough pipe and existing pipe and to their actual diameters.
Table E103.3(1) Recommended Tabular Arrangement for Use in Solving Pipe Sizing Problems
Column 1 2 3 4 5 6 7 8 9 10 Line Description Lb per square inch (psi) Gal. per min through section Length of section (feet) Trial pipe size (inches) Equivalent length of fittings and valves (feet) Total equivalent length col. 4 and col. 6 (100 feet) Friction loss per 100 feet of trial size pipe (psi) Friction loss in equivalent length col. 8 × col. 7 (psi) Excess pressure over friction losses (psi) A Service and cold water distribution piping a Minimum pressure available at main 55.00 B Highest pressures required at a fixture (Table 604.3) 15.00 C Meter loss 2" meter 11.00 D Tap in main loss 2" tap (Table E103.3(4)) 1.61 E Static head loss 21 × 43 psi 9.03 F Special fixture loss backflow preventer 9.00 G Special fixture loss – Filter 0.00 H Special fixture loss – Other 0.00 I Total overall losses and requirements (Sum of Lines B through H) 45.64 J Pressure available to overcome pipe friction (Line A minus Lines B to H) 9.36 Designation FU 264 Pipe section (from diagram) AB 288 108.0 54 2 1/2 15.00 0.69 3.2 2.21 – Cold water BC 264 104.5 8 2 1/2 0.5 0.85 3.1 0.26 – Distribution piping CD 132 77.0 13 2 1/2 7.00 0.20 1.9 0.38 – CF b 132 77.0 150 2 1/2 12.00 1.62 1.9 3.08 – DE b 132 77.0 150 2 1/2 12.00 1.62 1.9 3.08 – K Total pipe friction losses (cold) – – – – – – 5.93 – L Difference (Line J minus Line K) – – – – – – – 3.43 Pipe section (from diagram) A'B' 288 108.0 54 2 1/2 12.00 0.69 3.3 2.21 – Diagram B'C' 24 38.0 8 2 7.5 0.16 1.4 0.22 – Hot water C'D' 12 28.6 13 1 1/2 4.0 0.17 3.2 0.54 – Distribution C'F ' b 12 28.6 150 1 1/2 7.00 1.57 3.2 5.02 – Piping D'E ' b 12 28.6 150 1 1/2 7.00 1.57 3.2 5.02 – K Total pipe friction losses (hot) – – – – – – 7.99 – L Difference (line) minus Line K – – – – – – – 1.37
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 gpm = 3.785 L/m.
a. To be considered as pressure gain for fixtures below main (to consider separately, omit from "I" and add to "J").
b. To consider separately, in K use C-F only if greater loss than above.
Table E103.3(2) Load Values Assigned to Fixtures a
Fixture Occupancy Type of Supply Control Load Values, in Water Supply Fixture Units (wsfu) Cold Hot Total Bathroom group Private Flush tank 2.7 1.5 3.6 Bathroom group Private Flushometer valve 6.0 3.0 8.0 Bathtub Private Faucet 1.0 1.0 1.4 Bathtub Public Faucet 3.0 3.0 4.0 Bidet Private Faucet 1.5 1.5 2.0 Combination fixture Private Faucet 2.25 2.25 3.0 Dishwashing machine Private Automatic – 1.4 1.4 Drinking fountain Offices, etc. 3/8" valve 0.25 – 0.25 Kitchen sink Private Faucet 1.0 1.0 1.4 Kitchen sink Hotel, restaurant Faucet 3.0 3.0 4.0 Laundry trays (1 to 3) Private Faucet 1.0 1.0 1.4 Lavatory Private Faucet 0.5 0.5 0.7 Lavatory Public Faucet 1.5 1.5 2.0 Service sink Offices, etc. Faucet 2.25 2.25 3.0 Shower head Public Mixing valve 3.0 3.0 4.0 Shower head Private Mixing valve 1.0 1.0 1.4 Urinal Public 1" flushometer valve 10.0 – 10.0 Urinal Public 3/4" flushometer valve 5.0 – 5.0 Urinal Public Flush tank 3.0 – 3.0 Washing machine (8 lb) Private Automatic 1.0 1.0 1.4 Washing machine (8 lb) Public Automatic 2.25 2.25 3.0 Washing machine (15 lb) Public Automatic 3.0 3.0 4.0 Water closet Private Flushometer valve 6.0 – 6.0 Water closet Private Flush tank 2.2 – 2.2 Water closet Public Flushometer valve 10.0 – 10.0 Water closet Public Flush tank 5.0 – 5.0 Water closet Public or private Flushometer tank 2.0 – 2.0
For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg.
a. For fixtures not listed, loads should be assumed by comparing the fixture to one listed using water in similar quantities and at similar rates. The assigned loads for fixtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water loads being three-fourths of the total load for the fixture in each case.
Table E103.3(3) Table for Estimating Demand
Supply Systems Predominantly for Flush Tanks Supply Systems Predominantly for Flushometer Valves Load Demand Load Demand (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute) 1 3.0 0.04104 – – – 2 5.0 0.0684 – – – 3 6.5 0.86892 – – – 4 8.0 1.06944 – – – 5 9.4 1.256592 5 15.0 2.0052 6 10.7 1.430376 6 17.4 2.326032 7 11.8 1.577424 7 19.8 2.646364 8 12.8 1.711104 8 22.2 2.967696 9 13.7 1.831416 9 24.6 3.288528 10 14.6 1.951728 10 27.0 3.60936 11 15.4 2.058672 11 27.8 3.716304 12 16.0 2.13888 12 28.6 3.823248 13 16.5 2.20572 13 29.4 3.930192 14 17.0 2.27256 14 30.2 4.037136 15 17.5 2.3394 15 31.0 4.14408 16 18.0 2.90624 16 31.8 4.241024 17 18.4 2.459712 17 32.6 4.357968 18 18.8 2.513184 18 33.4 4.464912 19 19.2 2.566656 19 34.2 4.571856 20 19.6 2.620128 20 35.0 4.6788 25 21.5 2.87412 25 38.0 5.07984 30 23.3 3.114744 30 42.0 5.61356 35 24.9 3.328632 35 44.0 5.88192 40 26.3 3.515784 40 46.0 6.14928 45 27.7 3.702936 45 48.0 6.41664 50 29.1 3.890088 50 50.0 6.684 60 32.0 4.27776 60 54.0 7.21872 70 35.0 4.6788 70 58.0 7.75344 80 38.0 5.07984 80 61.2 8.181216 90 41.0 5.48088 90 64.3 8.595624 100 43.5 5.81508 100 67.5 9.0234 120 48.0 6.41664 120 73.0 9.75864 140 52.5 7.0182 140 77.0 10.29336 160 57.0 7.61976 160 81.0 10.82808 180 61.0 8.15448 180 85.5 11.42964 200 65.0 8.6892 200 90.0 12.0312 225 70.0 9.3576 225 95.5 12.76644 250 75.0 10.026 250 101.0 13.50168 275 80.0 10.6944 275 104.5 13.96956 300 85.0 11.3628 300 108.0 14.43744 400 105.0 14.0364 400 127.0 16.97736 500 124.0 16.57632 500 143.0 19.11624 750 170.0 22.7256 750 177.0 23.66136 1,000 208.0 27.80544 1,000 208.0 27.80544 1,250 239.0 31.94952 1,250 239.0 31.94952 1,500 269.0 35.95992 1,500 269.0 35.95992 1,750 297.0 39.70296 1,750 297.0 39.70296 2,000 325.0 43.446 2,000 325.0 43.446 2,500 380.0 50.7984 2,500 380.0 50.7984 3,000 433.0 57.88344 3,000 433.0 57.88344 4,000 535.0 70.182 4,000 525.0 70.182 5,000 593.0 79.27224 5,000 593.0 79.27224
Table E103.3(4) Loss of Pressure Through Taps and Tees in Pounds per Square Inch (psi)
Gallons per Minute Size of Tap or Tee (inches) 5/8 3/4 1 1 1/4 1 1/2 2 3 10 1.35 0.64 0.18 0.08 – – – 20 5.38 2.54 0.77 0.31 0.14 – – 30 12.10 5.72 1.62 0.69 0.33 0.10 – 40 – 10.20 3.07 1.23 0.58 0.18 – 50 – 15.90 4.49 1.92 0.91 0.28 – 60 – – 6.46 2.76 1.31 0.40 – 70 – – 8.79 3.76 1.78 0.55 0.10 80 – – 11.50 4.90 2.32 0.72 0.13 90 – – 14.50 6.21 2.94 0.91 0.16 100 – – 17.94 7.67 3.63 1.12 0.21 120 – – 25.80 11.00 5.23 1.61 0.30 140 – – 35.20 15.00 7.12 2.20 0.41 150 – – – 17.20 8.16 2.52 0.47 160 – – – 19.60 9.30 2.92 0.54 180 – – – 24.80 11.80 3.62 0.68 200 – – – 30.70 14.50 4.48 0.84 225 – – – 38.80 18.40 5.60 1.06 250 – – – 47.90 22.70 7.00 1.31 275 – – – – 27.40 7.70 1.59 300 – – – – 32.60 10.10 1.88
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kpa, 1 gallon per minute = 3.785 L/m.
Table E103.3(5) Allowance in Equivalent Lengths of Pipe for Friction Loss in Valves and Threaded Fittings (feet)
Fitting or Valve Pipe Size (inches) 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 45-degree elbow 1.2 1.5 1.8 2.4 3.0 4.0 5.0 6.0 90-degree elbow 2.0 2.5 3.0 4.0 5.0 7.0 8.0 10.0 Tee, run 0.6 0.8 0.9 1.2 1.5 2.0 2.5 3.0 Tee, branch 3.0 4.0 5.0 6.0 7.0 10.0 12.0 15.0 Gate valve 0.4 0.5 0.6 0.8 1.0 1.3 1.6 2.0 Balancing valve 0.8 1.1 1.5 1.9 2.2 3.0 3.7 4.5 Plug-type cock 0.8 1.1 1.5 1.9 2.2 3.0 3.7 4.5 Check valve, swing 5.6 8.4 11.2 14.0 16.8 22.4 28.0 33.6 Globe valve 15.0 20.0 25.0 35.0 45.0 55.0 65.0 80.0 Angle valve 8.0 12.0 15.0 18.0 22.0 28.0 34.0 40.0
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
Table E103.3(6) Pressure Loss in Fittings and Valves Expressed as Equivalent Length of Tube a (feet)
Nominal or Standard Size (inches) Fittings Coupling Valves Standard EII 90-Degree Tee Ball Gate Butterfly Check 90 Degree 45 Degree Side Branch Straight Run 3/8 0.5 – 1.5 – – – – – 1.5 1/2 1 0.5 2 – – – – – 2 5/8 1.5 0.5 2 – – – – – 2.5 3/4 2 0.5 3 – – – – – 3 1 2.5 1 4.5 – – 0.5 – – 4.5 1 1/4 3 1 5.5 0.5 0.5 0.5 – – 5.5 1 /2 4 1.5 7 0.5 0.5 0.5 – – 6.5 2 5.5 2 9 0.5 0.5 0.5 0.5 7.5 9 2 1/2 7 2.5 12 0.5 0.5 – 1 10 11.5 3 9 3.5 15 1 1 – 1.5 15.5 14.5 3 1/2 9 3.5 14 1 1 – 2 – 12.5 4 12.5 5 21 1 1 – 2 16 18.5 5 16 6 27 1.5 1.5 – 3 11.5 23.5 6 19 7 34 2 2 – 3.5 13.5 26.5 8 29 11 50 3 3 – 5 12.5 39
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0 1745 rad.
a. Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings, double the allowances shown in the table. The equivalent lengths presented above are based on a C factor of 150 in the Hazen-Williams friction loss formula. The lengths shown are rounded to the nearest half-foot.
Section PC E201. Reserved
BetaNYC's copy has no text for this section. Read Section PC E201 at American Legal Publishing.
Section PC E202. Determination of Pipe Volumes
E202.1 Determining volume of piping systems.
Where required for engineering design purposes, Table E202.1 shall be used to determine the approximate internal volume of water distribution piping.
Table E202.1 Internal Volume of Various Water Distribution Tubing
Ounces of Water Per Foot of Tube Size Nominal, Inch Copper Type L Copper Type K 3/8 0.97 0.84 1/2 1.55 1.45 3/4 3.22 2.90 1 5.49 5.17 1 1/4 8.36 8.09 1 1/2 11.83 11.45 2 20.58 20.04
For SI: 1 ounce = 0.030 liter.