Section MC 807. Changes In Appliance Fuels
807.1 Changes in appliance fuels.
Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per the New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if:
1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810.
2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel.
3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits.
Section MC 808. Reduction of Flue Size
808.1 Reduction of flue size.
Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood-burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter.
Section MC 809. Chimney Supported from Equipment
809.1 Chimney support.
Chimneys shall not be supported by the equipment they serve, unless such equipment has been specifically designed for such loads.
Section MC 810. Test Run and Smoke Test
810.1 Test run.
All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements.
Exception: A test run in accordance with this section may be conducted and certified to the department by the permit-holder when the work is performed as part of a limited alteration application, as defined in Section 28-101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
810.2 Requirement of a smoke test.
A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector responsible for the test that shall be submitted in writing to the department.
Exception: A smoke test may be performed by or under the supervision of a permit-holder when the work is performed as part of a limited alteration application, as defined in Section 28-101.5 of the Administrative Code. Such test shall not be required to be witnessed by the department, registered design professional or special inspector.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
810.3 Smoke test.
To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements:
1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit.
2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory.
3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1/2- inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney.
4. Refer to Section 1704.32 of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents.
Section MC 811. Exhaust Gases from Internal Combustion Engines and Turbines
811.1 Exhaust system construction.
The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following:
1. The exhaust system, if factory built, shall be installed in accordance with its listing and manufacturer's instructions.
1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa).
1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated for a pressure suitable for the operating conditions.
2. The exhaust system, if field fabricated, shall be constructed of at least 3/16-inch (4.8 mm) steel, or of other equivalent metal of similar strength and resistance to the temperature and corrosive action of the exhaust gases. No lining shall be required.
3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C).
4. Where the exhaust system runs inside a building outside of the room containing the equipment, it shall be enclosed in fire-rated construction with a fire rating equal to the fire rating of the construction of the room.
5. All joints shall be constructed so as to be gas tight under all operating conditions and tested in accordance with Section 810.
811.2 Emergency and standby generator discharge opening termination requirements.
The location of discharge outlets for emergency and standby generators shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people.
811.2.1 Interference.
No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard.
811.2.2 Chimneys.
The exhaust pipe may be connected to a chimney used for other equipment, provided that the operation of the engine does not adversely affect the operation of the other equipment so that it is in violation of the New York City Air Pollution Control Code.
811.3 All other engine and turbine discharge opening termination requirements.
The location of the discharge outlet from all other engines and turbines shall comply with the termination requirements of Section 801.21, Item 2 or Section 801.21, Item 3 based on the temperature of the flue gas entering the exhaust system.
811.4 Chimneys.
The exhaust system may be connected to a chimney used for other appliances, provided that the chimney complies with Section 811.1, Item 1 or Section 811.1, Item 2 and the operation of the engine does not adversely affect the operation of the other appliances and is in accordance with the New York City Air Pollution Control Code.
Section MC 901. General
901.1 Scope.
This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein and factory-built fireplaces. The approval, design, installation, construction, maintenance, alteration and repair of gas-fired appliances shall be regulated by the New York City Fuel Gas Code.
901.2 General.
The requirements of this chapter shall apply to the mechanical equipment and appliances regulated by this chapter, in addition to the other requirements of this code, and installed in accordance with the requirements of NFPA 31, NFPA 54 and NFPA 211.
901.3 Solid fuel-burning fireplaces and appliances.
All solid fuel-burning fireplaces and appliances shall be installed, altered and maintained in buildings in conformity with the applicable provisions of the New York City Air Pollution Control Code and no new solid fuel-burning fireplaces or appliances shall be permitted except those that burn the types of fuel allowed by such code.
(L.L. 2015/038, 5/6/2015, eff. 5/6/2016)
901.4 Hazardous locations.
Fireplaces and solid fuel-burning appliances shall not be installed in hazardous locations.
(Am. L.L. 2015/038, 5/6/2015, eff. 5/6/2016)
901.5 Inspection of solid fuel-burning heating appliances, chimneys and flues.
Inspections of solid fuel burning heating appliances, chimneys and flues shall be in accordance with the New York City Building Code.
(Am. L.L. 2015/038, 5/6/2015, eff. 5/6/2016)
901.6 Fireplaces.
Fireplaces (solid-fuel-type or ANSI Z21.50) shall be installed with tight-fitting noncombustible fireplace doors to control infiltration losses in construction types listed here:
1. Masonry or factory-built fireplaces designed to allow an open burn.
2. Decorative appliances (ANSI Z21.60 gas-log style unit) installed in a vented solid fuel fireplace.
3. Vented decorative gas fireplace appliances (ANSI Z21.50 unit). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code and Chapter 7 of this code.
(Am. L.L. 2015/038, 5/6/2015, eff. 5/6/2016)
Section MC 902. Masonry Fireplaces
902.1 General.
Masonry fireplaces shall be constructed in accordance with the New York City Building Code.
902.2 Fireplace accessories.
Listed and labeled fireplace accessories shall be installed in accordance with the conditions of the listing and the manufacturer's instructions. Fireplace accessories shall comply with UL 907.
Section MC 903. Factory-Built Fireplaces
903.1 General.
Factory-built fireplaces shall be listed and labeled and shall be installed in accordance with the conditions of the listing. Factory-built fireplaces shall be tested in accordance with UL 127.
903.2 Hearth extensions.
Hearth extensions of approved factory-built fireplaces shall be installed in accordance with the listing of the fireplace. The hearth extension shall be readily distinguishable from the surrounding floor area. Listed and labeled hearth extensions shall comply with UL 1618.
903.3 Unvented gas log heaters.
The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited.
903.4 Gasketed fireplace doors.
A gasketed fireplace door shall not be installed on a factory-built fireplace except where the fireplace system has been specifically tested, listed and labeled for such use in accordance with UL 127.
903.5 Flues.
Separate flues shall be provided for every fireplace and fireplace stove.
903.6 Combustion air supply.
All installations of factory-built fireplaces shall comply with the requirements of the New York City Energy Conservation Code concerning combustion air supply.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
Section MC 904. Pellet Fuel-Burning Appliances
904.1 General.
Pellet fuel-burning appliances shall be listed and labeled in accordance with ASTM E 1509 and shall be installed in accordance with the terms of the listing. If permitted, such appliances shall be operated in accordance with the New York City Air Pollution Control Code.
Section MC 905. Fireplace Stoves and Room Heaters
905.1 General.
Fireplace stoves and solid-fuel-type room heaters shall be listed and labeled and shall be installed in accordance with the conditions of the listing. Fireplace stoves shall be tested in accordance with UL 737. Solid-fuel-type room heaters shall be tested in accordance with UL 1482. Fireplace inserts intended for installation in fireplaces shall be listed and labeled in accordance with the requirements of UL 1482 and shall be installed in accordance with the manufacturer's instructions.
905.2 Connection to fireplace.
The connection of solid fuel appliances to chimney flues serving fireplaces shall comply with Sections 801.7 and 801.10.
905.3 Hearth extensions.
Hearth extensions for fireplace stoves shall be installed in accordance with the listing of the fireplace stove. The hearth extension shall be readily distinguishable from the surrounding floor area. Listed and labeled hearth extensions shall comply with UL 1618.
905.4 Air pollution.
All fireplace stoves and room heaters shall comply with the requirements of the New York City Air Pollution Control Code.
905.5 Combustion air supply.
All fireplace stoves and room heaters shall comply with the requirements of the New York City Energy Conservation Code concerning combustion air supply.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
905.6 Flues.
Separate flues and independent combustion air source shall be provided for every fireplace stove and room heater. Combustion air shall be provided in accordance with the manufacturer's recommendations and Chapter 7.
Section MC 906. Factory-Built Barbecue Appliances
906.1 General.
Factory-built barbecue appliances shall be listed and labeled for the use intended and shall be installed in accordance with the manufacturer's instructions, this chapter, the New York City Fuel Gas Code, and Chapters 3, 5, 7, 8 of this code. The construction and installation of chimneys serving barbeque appliances shall comply with all construction and installation requirements of fireplaces.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section MC 907. Incinerators and Crematories
907.1 General.
Incinerators and crematories shall be listed and labeled in accordance with UL 791 and NFPA 82 and shall be installed in accordance with the manufacturer's instructions.
907.2 Compliance.
All incinerators and crematories shall be installed, altered and maintained in buildings in conformity with the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code.
Section MC 908. Cooling Towers, Evaporative Condensers and Fluid Coolers
908.1 General.
A cooling tower used in conjunction with an air-conditioning appliance shall be installed in accordance with the manufacturer's instructions.
908.2 Access.
Cooling towers, evaporative condensers and fluid coolers shall be provided with ready access.
908.3 Location.
Cooling towers, evaporative condensers and fluid coolers shall be located to prevent the discharge vapor plumes from entering occupied spaces. Plume discharges shall be not less than 5 feet (1524 mm) above or 20 feet (6096 mm) away from any ventilation inlet to a building. Location on the property shall be as required for buildings in accordance with the New York City Building Code.
908.3.1 Indoor.
Cooling towers, evaporative condensers and fluid coolers located inside of buildings shall be constructed of noncombustible materials including fill and drift eliminators.
908.3.2 Outside.
Cooling towers shall be constructed of noncombustible materials.
Exceptions:
1. Fill and drift eliminators of limited combustible materials may be considered noncombustible if the cooling towers are provided with automatic sprinkler protection in compliance with Chapter 9 of the New York City Building Code.
2. Fill and drift eliminators for any individual cooling tower cell may be made of limited combustible materials provided all the following conditions are met:
2.1. The cooling tower is located on a building of construction Types IA or IB of the New York City Building Code.
2.2. The cooling tower cell is located at least 30 feet (9144 mm) away from windows or fresh air intakes which are at an elevation above the roof on which the cooling tower is located, whether in the same building or in an adjoining building.
2.3. The cooling tower cell is located not less than 15 feet (4572 mm) from the lot line.
2.4. The cooling tower cell is located not less than 10 feet (3048 mm) from any chimney, except that the distance shall not be less than 20 feet (6096 mm) from a chimney venting products of combustion other than from gas- or oil-fired appliances, whether on the same or an adjoining building.
908.4 Support and anchorage.
Supports for cooling towers, evaporative condensers and fluid coolers shall be designed in accordance with the New York City Building Code. Seismic restraints shall be as required by the New York City Building Code. Adequate vibration isolation shall be provided in accordance with the manufacturer's guidelines and as required for the supporting structure, and in accordance with Sections 313.3.7 and 313.3.8.
908.5 Water supply.
Cooling towers, evaporative condensers and fluid coolers shall be provided with an approved water supply, sized for peak demand. The quality of water shall be provided in accordance with the equipment manufacturer's recommendations. The piping system and protection of the potable water supply system shall be installed as required by the New York City Plumbing Code.
908.6 Drainage.
Drains, overflows and blowdown provisions shall be indirectly connected to an approved disposal location. Discharge of chemical waste shall be approved by the appropriate regulatory authority.
908.7 Refrigerants and hazardous fluids.
Heat exchange equipment that contains a refrigerant and that is part of a closed refrigeration system shall comply with Chapter 11. Heat exchange equipment containing heat transfer fluids which are combustible or hazardous shall comply with the New York City Fire Code. Flammable heat transfer fluids are prohibited.
908.8 Cooling towers.
Cooling towers, both open circuit and closed circuit type, and evaporative condensers shall comply with Sections 908.8.1 and 908.8.2.
908.8.1 Conductivity or flow-based control of cycles of concentration.
Cooling towers and evaporative condensers shall include controls that automate system bleed based on conductivity, fraction of metered makeup volume, metered bleed volume, recirculating pump run time or bleed time.
908.8.2 Drift eliminators.
Cooling towers and evaporative condensers shall be equipped with drift eliminators that have a maximum drift rate of 0.005 percent of the circulated water flow rate as established in the equipment's design specifications.
908.9 Additional requirements.
The installation and maintenance of all cooling towers, evaporative condensers, and fluid coolers shall comply with the requirements of Article 317 of Chapter 3 of Title 28 of the Administrative Code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section MC 909. Vented Wall Furnaces
909.1 General.
Vented wall furnaces shall be installed in accordance with their listing and the manufacturer's instructions. Oil-fired furnaces shall be tested in accordance with UL 730.
909.2 Location.
Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible furnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building.
909.3 Door swing.
Vented wall furnaces shall be located so that a door cannot swing within 12 inches (304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance.
909.4 Ducts prohibited.
Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance.
909.5 Manual shutoff valve.
A manual shutoff valve shall be installed ahead of all controls.
909.6 Access.
Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that must be removed for normal servicing operations shall not be attached to the building construction.
Section MC 910. Floor Furnaces
910.1 General.
Floor furnaces shall be installed in accordance with their listing and the manufacturer's instructions. Oil-fired furnaces shall be tested in accordance with UL 729. Unvented floor furnaces are prohibited.
910.2 Placement.
Floor furnaces shall not be installed in any corridor, in the floor of any aisle or passageway of any auditorium, public hall, place of assembly, or in any egress element from any such room or space.
With the exception of wall register models, a floor furnace shall not be placed closer than 6 inches (152.4 mm) to the nearest wall, and wall register models shall not be placed closer than 6 inches (152.4 mm) to a corner.
The furnace shall be placed such that a drapery or similar combustible object will not be nearer than 12 inches (304.8 mm) to any portion of the register of the furnace. Floor furnaces shall not be installed in concrete floor construction built on grade. The controlling thermostat for a floor furnace shall be located within the same room or space as the floor furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. Floor furnaces shall be located so as to be accessible. Floor furnaces shall be installed only in floors of noncombustible construction having at least a 2-hour fire rating, except as where required for one- and two-family dwellings.
910.3 Bracing.
The floor around the furnace shall be braced and headed with a support framework design in accordance with the New York City Building Code.
910.4 Clearance.
The lowest portion of the floor furnace shall have not less than a 6-inch (152.4 mm) clearance from the grade level; except where the lower 6-inch (152.4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be reduced to not less than 2 inches (50.8 mm). Where these clearances are not present, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12-inch (304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18-inch (457.2 mm) minimum clearance.
910.5 Enclosures.
Enclosures of floor furnaces shall be constructed entirely of noncombustible materials with a fire-resistance rating of at least 1 hour and shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace.
910.6 Duct temperature.
The outlet duct temperature of warm air heating furnaces shall not be greater than 250°F (121.1°C).
910.7 One- and two- family dwellings.
Floor furnace enclosures shall be constructed of noncombustible materials with a fire-resistance rating of at least 1 hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54.
Section MC 911. Duct Furnaces and Heaters
911.1 General.
Duct furnaces and heaters shall be installed in accordance with the manufacturer's instructions. Electric furnaces and duct heaters shall comply with UL 1995 or UL 1996, as applicable. Unvented fuel-fired duct furnaces are prohibited.
911.2 Access panels.
Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace.
911.3 Location of draft hood and controls.
The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken.
911.4 Circulating air.
Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall also be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circulating air blower.
911.5 Duct Temperature.
The outlet duct temperature of duct furnaces shall not be greater than 250°F (121.1°C).
Section MC 912. Infrared Radiant Heaters
912.1 General.
Electric infrared radiant heaters shall comply with UL 499.
912.2 Support.
Infrared radiant heaters shall be fixed in a position independent of fuel and electric supply lines. Hangers and brackets shall be noncombustible material.
912.3 Clearances.
Heaters shall be installed with clearances from combustible material in accordance with the manufacturer's instructions.
Section MC 913. Clothes Dryers
913.1 General.
Clothes dryers shall be installed in accordance with the manufacturer's instructions and shall comply with the following as applicable:
1. Electric commercial clothes dryers shall be tested in accordance with UL 1240.
2. Electric residential clothes dryers shall be tested in accordance with UL 2158.
3. Electric coin-, ticket-, or card-operated clothes dryers shall be tested in accordance with UL 2158.
913.2 Exhaust required.
Clothes dryers shall be exhausted in accordance with Section 504.
Exception: Electric clothes dryers provided with a condensate drain. Spaces containing such dryers shall be provided with transfer air openings or other approved means to provide adequate air exchanges with adjacent spaces.
913.3 Clearances.
Clothes dryers shall be installed with clearance to combustibles in accordance with the manufacturer's instructions.
Section MC 914. Sauna Heaters
914.1 Location and protection.
Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room.
914.1.1 Guards.
Sauna heaters shall be protected from accidental contact by an approved guard or barrier of material having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room.
914.2 Installation.
Sauna heaters shall be listed and labeled in accordance with UL 875 and shall be installed in accordance with their listing and the manufacturer's instructions.
914.3 Access.
Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building.
914.4 Heat and time controls.
Sauna heaters shall be equipped with a thermostat that will limit room temperature to 194°F (90°C). If the thermostat is not an integral part of the sauna heater, the heat-sensing element shall be located within 6 inches (152.4 mm) of the ceiling. If the heat-sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protected against physical damage.
914.4.1 Timers.
A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room.
914.5 Sauna room.
A ventilation opening into the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches (101.6 mm by 203.2 mm) located near the top of the door into the sauna room.
914.5.1 Warning notice.
The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside:
WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA.
The words shall contrast with the background and the wording shall be in letters not less than 1/4-inch (6.4 mm) high.
Exception: This section shall not apply to one- and two-family dwellings.
Section MC 915. Engine and Gas Turbine-Powered Equipment and Appliances
915.1 General.
The installation of liquid-fueled stationary internal combustion engines and gas turbines, including combustion air, exhaust, fuel storage and piping, shall meet the requirements of NFPA 37 and Chapters 7, 8, and 13 of this code. Stationary engine generator assemblies shall meet the requirements of UL 2200.
915.2 Powered equipment and appliances.
Permanently installed equipment and appliances powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer's instructions and NFPA 37.
Section MC 916. Pool and Spa Heaters
916.1 General.
Pool and spa heaters shall be installed in accordance with the manufacturer's instructions. Oil-fired pool and spa heaters shall be tested in accordance with UL 726. Electric pool and spa heaters shall be tested in accordance with UL 1261.
Section MC 917. Cooking Appliances
917.1 Cooking appliances.
Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers and griddles shall be listed, labeled and installed in accordance with the manufacturer's instructions. Oil-fired cooking appliances are prohibited. Commercial electric cooking appliances shall be listed and labeled in accordance with UL 197. Household electric ranges shall be listed and labeled in accordance with UL 858. Microwave cooking appliances shall be listed and labeled in accordance with UL 923. Oil-burning stoves shall be listed and labeled in accordance with UL 896. Solid-fuel-fired ovens shall be listed and labeled in accordance with UL 2162.
917.2 Prohibited location.
Cooking appliances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur.
917.3 Domestic appliances.
Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household-type appliances for domestic use.
917.4 Domestic range installation.
Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label.
917.5 Open-top broiler unit hoods.
A ventilating hood shall be provided above a domestic open-top broiler unit, unless otherwise listed for forced down draft ventilation.
917.5.1 Clearances.
A minimum clearance of 24 inches (609.6 mm) shall be maintained between the cooking top and combustible material above the hood. The hood shall be at least as wide as the open-top broiler unit and be centered over the unit.
917.6 Commercial cooking appliance venting.
Commercial cooking appliances, other than those exempted by Section 501.8 of the New York City Fuel Gas Code, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer's instructions or the appliance shall be vented in accordance with Section 505.1.1 of the New York City Fuel Gas Code.
917.7 Domestic ventilation.
When a hood is required for proper ventilation of a domestic cooking appliance, the exhaust and make-up air systems shall be properly engineered and designed in accordance with Chapter 5.
Section MC 918. Forced-Air Warm-Air Furnaces
918.1 Forced-air furnaces.
Oil-fired furnaces shall be tested in accordance with UL 727. Electric furnaces shall be tested in accordance with UL 1995. Solid fuel furnaces shall be tested in accordance with UL 391. Forced-air furnaces shall be installed in accordance with the listings and the manufacturer's instructions. Forced-air warm-air furnaces shall be installed in accordance with the requirements of NFPA 31 and the New York City Fuel Gas Code. Unvented fuel-fired furnaces are prohibited.
918.2 Heat pumps.
Electric heat pumps shall be tested in accordance with UL 1995 or UL 60335-2-40.
918.3 Dampers.
Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace.
918.4 Circulating air ducts for forced-air warm-air furnaces.
Circulating air for fuel-burning, forced-air-type, warm-air furnaces shall be conducted into the blower housing from outside the furnace enclosure by continuous air-tight ducts.
918.5 Outdoor and return air openings.
Outdoor intake openings shall be located in accordance with Section 401.4. Return air openings shall be located in accordance with Section 618.4 of the New York City Fuel Gas Code.
918.6 Outdoor opening protection.
Outdoor air intake openings shall be protected in accordance with Section 401.5.
Section MC 919. Conversion Burners
919.1 Conversion burners.
The installation of conversion burners shall conform to ANSI Z21.8 and the applicable requirements of Chapter 10 of this code.
Section MC 920. Unit Heaters
920.1 General.
Unit heaters shall be installed in accordance with the listing and the manufacturer's instructions. Oil-fired unit heaters shall be tested in accordance with UL 731.
920.2 Support.
Suspended-type unit heaters shall be supported by elements that are designed and constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. Suspended-type oil-fired unit heaters shall be installed in accordance with NFPA 31.
920.3 Ductwork.
A unit heater shall not be attached to a warm-air duct system unless listed for such installation.
Section MC 921. Vented Room Heaters
921.1 General.
Vented room heaters shall be listed and labeled and shall be installed in accordance with the conditions of the listing and the manufacturer's instructions.
Section MC 922. Kerosene and Oil-Fired Stoves
922.1 General.
The installation of kerosene and oil-fired stoves is prohibited.
Section MC 923. Ceramic Kilns
923.1 General.
Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1 Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on approved engineering evaluation.
923.1.1 Installation.
Kilns shall be installed in accordance with the manufacturer's instructions and the provisions of this code.
Section MC 924. Stationary Fuel Cell Power Plants
924.1 General.
Stationary fuel cell power plants having a power output not exceeding 10 MW, shall be tested in accordance with ANSI/CSA America FC1 and shall be installed in accordance with the manufacturer's instructions and NFPA 853. Such fuel cell plants shall be powered by hydrogen derived on-site from piped natural gas, except where the storage, handling and use of hydrogen or other flammable gas is authorized by the New York City Fire Code for such purposes and approved by the fire commissioner.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2008/026.
Section MC 925. Masonry Heaters
925.1 General.
Masonry heaters shall be constructed in accordance with the New York City Building Code.
Section MC 926. Gaseous Hydrogen Systems
926.1 Installation.
The installation of gaseous hydrogen systems shall be in accordance with the applicable requirements of this code, the New York City Fire Code, the New York City Fuel Gas Code and the New York City Building Code.
Section MC 927. Electric Radiant Heating Systems
927.1 General.
Electric radiant heating systems shall be installed in accordance with the manufacturer's instructions and shall be listed for the application.
927.2 Clearances.
Clearances for radiant heating panels or elements to any wiring, outlet boxes and junction boxes used for installing electrical devices or mounting luminaires shall be in accordance with the New York City Building Code and the New York City Electrical Code.
927.3 Installation on wood or steel framing.
Radiant panels installed on wood or steel framing shall conform to the following requirements:
1. Heating panels shall be installed parallel to framing members and secured to the surface of framing members or shall be mounted between framing members.
2. Mechanical fasteners shall penetrate only the unheated portions provided for this purpose. Panels shall not be fastened at any point closer than 1/4 inch (6.4 mm) to an element. Other methods of attachment of the panels shall be in accordance with the panel installation instructions.
3. Unless listed and labeled for field cutting, heating panels shall be installed as complete units.
927.4 Installation in concrete or masonry.
Radiant heating systems installed in concrete or masonry shall conform to the following requirements:
1. Radiant heating systems shall be identified as being suitable for the installation, and shall be secured in place as specified in the manufacturer's instructions.
2. Radiant heating panels and radiant heating panel sets shall not be installed where they bridge expansion joints unless they are protected from expansion and contraction.
927.5 Finish surfaces.
Finish materials installed over radiant heating panels and systems shall be installed in accordance with the manufacturer's instructions. Surfaces shall be secured so that fasteners do not pierce the radiant heating elements.
Section MC 928. Evaporative Coolers
928.1 General.
Evaporative cooling equipment shall:
1. Be installed in accordance with the manufacturer's instructions.
2. Be installed on level platforms and in accordance with Section 304.10.
3. Have openings in exterior walls or roofs flashed in accordance with the New York City Building Code.
4. Be provided with an approved water supply, sized for peak demand. The quality of water shall be provided in accordance with the equipment manufacturer's recommendations. The piping system and protection of the potable water supply system shall be installed as required by the New York City Plumbing Code.
5. Have ventilation air intake opening locations in accordance with Section 401.4.
Section MC 1001. General
1001.1 Scope.
This chapter shall establish the minimum safety requirements for and shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
Exceptions:
1. Pressure vessels used for unheated water supply.
2. Portable unfired pressure vessels and Interstate Commerce Commission containers.
3. Containers for bulk oxygen and medical gas.
4. Unfired pressure vessels having a volume of 5 cubic feet (0.14 m 3 ) or less operating at pressures not exceeding 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, S and U.
5. Pressure vessels used in refrigeration systems that are regulated by Chapter 11.
6. Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other similar humidity control systems.
7. Any boiler or pressure vessel subject to inspection by federal inspectors.
1001.2 Thermal safety (spill) switches.
Thermal safety (spill) switches shall be installed in accordance with Section 801.23.3.
1001.3 Clearances.
Minimum clearances at boilers, water heaters and pressure vessels shall be maintained in accordance with Chapter 3.
Section MC 1002. Water Heaters
1002.1 General.
Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accordance with the manufacturer's instructions, the New York City Plumbing Code and this code. All water heaters shall be capable of being removed without first removing a permanent portion of the building structure. The potable water connections and relief valves for all water heaters shall conform to the requirements of the New York City Plumbing Code. Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall comply with UL 1453. Oil-fired water heaters shall comply with UL 732. Approval for oil-fired water heaters 350,000 Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water heaters shall comply with UL 174 or UL 1995.
1002.2 Water heaters utilized for space heating.
Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space-heating applications shall be listed and labeled for such applications by the manufacturer and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an "H" code stamp. Water heaters shall be installed in accordance with the manufacturer's instructions, the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code. Oil-fired heaters shall comply with UL 732 and shall have an "HW" stamp.
1002.2.1 Sizing.
Water heaters utilized for both potable water heating and space-heating applications shall be sized to prevent the space-heating load from diminishing the required potable water-heating capacity.
1002.2.2 Temperature limitation.
Where a combination potable water-heating and space-heating system requires water for space heating, a temperature actuated mixing valve complying with ASSE 1017 shall be provided to temper the water supplied to the potable hot water distribution system in accordance with Section 607 of the New York City Plumbing Code.
1002.2.3 Cross-connection.
Water heaters utilized for both potable hot water and hot water for space-heating applications shall have separate heating sections and connections for distribution systems and shall not be cross-connected. The potability of the domestic water shall be maintained throughout the system in accordance with the New York City Plumbing Code.
1002.3 Supplemental water-heating devices.
Potable water-heating devices that utilize refrigerant-to-water heat exchangers shall be approved and installed in accordance with the New York City Plumbing Code, the applicable provisions of the New York City Energy Conservation Code and the manufacturer's instructions.
Section MC 1003. Pressure Vessels
1003.1 General.
All pressure vessels shall be constructed and certified in accordance with the ASME Boiler and Pressure Vessel Code, and shall bear the label of an approved agency. Pressure vessels shall be installed in accordance with the manufacturer's instructions and nationally recognized standards. Directly fired pressure vessels shall meet the requirements of Section 1004.
1003.2 Piping.
All piping materials, fittings, joints, connections and devices associated with systems utilized in conjunction with pressure vessels shall be designed for the specific application and shall comply with the ASME Boiler and Pressure Vessel Code and this code.
1003.3 Welding.
Welding on pressure vessels shall be performed by welders certified in compliance with nationally recognized standards, including the National Board Inspection Code and ASME Boiler and Pressure Vessel Code, Section IX. Such welders shall also comply with 12 NYCRR 4-6.2, and 12 NYCRR 14-3.3 through 14-3.18.
Section MC 1004. Boilers
1004.1 Standards.
Boilers shall be designed, constructed and certified in accordance with the ASME Boiler and Pressure Vessel Code, Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with fuel input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD-1. Controls and safety devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. Packaged oil-fired boilers shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be listed and labeled in accordance with UL 834. Approval for oil-fired boilers 350,000 Btu/h input (102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection.
1004.1.1 Field erected boilers requirements.
Field erected boiler installations shall comply with the following:
1. The vessel erector shall hold the appropriate ASME stamp for vessel construction.
2. The licensed installer is responsible for the installation of all controls and burners which shall be designed and constructed in accordance with the requirements of ASME CSD-1 and, as applicable, the ASME Boiler and Pressure Vessel Code, 12 NYCRR Parts 4 and 14, and NFPA 85.
3. The New York City Department of Environmental Protection shall approve the installation of the boiler and burner for compatibility, controls and safety devices.
4. Boiler vessels shall comply with one of the following listings:
4.1. UL 726 or UL 795 as applicable; or
4.2. UL 2106.
Exception: Unlisted equipment shall obtain approval from the department.
5. Controls and safety devices shall be tested and inspected in accordance with ASME CSD-1 and, as applicable, the ASME Boiler and Pressure Vessel Code, 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection shall be performed by the burner manufacturer's authorized representative in the presence of the licensed installer.
6. Inspection of the installed boiler assembly shall be performed by the department.
1004.2 Installation.
In addition to the requirements of this code, the installation of boilers shall conform to the manufacturer's instructions. Operating instructions of a permanent type shall be located in the boiler room and readily accessible. Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer's rating data and the nameplate shall be attached to the boiler.
1004.3 Working clearance.
Clearances shall be maintained around boilers, generators, heaters, tanks and related equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When boilers are installed or replaced, clearance shall be provided to allow access for maintenance and repair per the boiler's listing and manufacturer's instructions. Passageways for inspection around all sides of boilers shall have an unobstructed width of not less than 18 inches (457.2 mm) unless the boiler's listing or department approval or manufacturer's instructions state otherwise.
1004.3.1 Top clearance.
Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be in accordance with Table 1004.3.1.
Table 1004.3.1 Boiler Top Clearances
Boiler Type Minimum Clearances from Top of Boiler to Ceiling or Other Overhead Obstruction (feet) All boilers with manholes on top of the boiler except where a greater clearance is required in this table. 3 All boilers without manholes on top of the boiler except high-pressure steam boilers and where a greater clearance is required in this table. 2 High-pressure steam boilers with steam generating capacity not exceeding 5,000 pounds per hour. 3 High-pressure steam boilers with steam generating capacity exceeding 5,000 pounds per hour. 7 High-pressure steam boilers having heating surface not exceeding 1,000 square feet. 3 High-pressure steam boilers having heating surface in excess of 1,000 square feet. 7 High-pressure steam boilers with input not exceeding 5,000,000 Btu/h. 3 High-pressure steam boilers with input in excess of 5,000,000 Btu/h. 7 Steam-heating boilers and hot water-heating boilers with input exceeding 5,000,000 Btu/h. 3 Steam-heating boilers exceeding 5,000 pounds of steam per hour. 3 Steam-heating boilers and hot water-heating boilers having heating surface exceeding 1,000 square feet. 3
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 , 1 pound per hour = 0.4536 kg/h, 1 Btu/hr = 0.293 W.
1004.4 Mounting.
Equipment and appliances shall be set or mounted on a level base capable of supporting and distributing the weight contained thereon. Boilers, tanks and equipment shall be securely anchored to the structure. Equipment and appliances requiring vibration isolation shall be installed as designed by a registered design professional in accordance with the manufacturer's instructions.
1004.5 Floors.
Boilers shall be mounted on floors of noncombustible construction, unless listed for mounting on combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occupancies, boilers shall be installed in accordance with the requirements of Section 313.
1004.6 Boiler rooms and enclosures.
Boiler rooms and enclosures and access thereto shall comply with Chapters 5 and 10 of the New York City Building Code and Chapter 3 of this code. Boiler rooms shall be equipped with a floor drain or other approved means for disposing of liquid waste in accordance with the New York City Plumbing Code.
1004.7 Operating adjustments and instructions.
Hot water and steam boilers shall have all operating and safety controls set and operationally tested by the installing contractor. A complete control diagram and boiler operating instructions shall be furnished by the installer for each installation. A complete control diagram of a permanent type shall be located in the boiler room and shall be readily accessible.
1004.8 Burner controls.
Gas and oil modulating burners shall be provided with burner controls (oil and gas equivalent ratings) in accordance with ASME CSD-1 and NFPA 85.
1004.9 Conversion burners.
Conversion burners shall be installed in accordance with ANSI Z21.8.
Section MC 1005. Boiler Connections
1005.1 Valves.
Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping.
Exception: Shutoff valves are not required in a system having a single low-pressure steam boiler of 350,000 Btu/h (103 kW) output or less.
1005.2 Potable water supply.
The water supply to all boilers, including but not limited to backflow prevention, shall be connected in accordance with the New York City Plumbing Code.
Section MC 1006. Safety and Pressure Relief Valves And Controls
1006.1 Safety valves for steam boilers.
Steam boilers shall be protected with a safety valve in accordance with the ASME Boiler and Pressure Vessel Code or ASME CSD-1
1006.2 Safety relief valves for hot water boilers.
Hot water boilers shall be protected with a safety relief valve in accordance with the ASME Boiler and Pressure Vessel Code or ASME CSD-1.
1006.3 Pressure relief for pressure vessels.
Pressure vessels shall be protected with a pressure relief valve or pressure-limiting device as required by the manufacturer's instructions for the pressure vessel and in accordance with the ASME Boiler and Pressure Vessel Code or ASME CSD-1.
1006.4 Standards of safety and safety relief valves.
Safety and safety relief valves shall be listed and labeled, and shall have a minimum rated capacity for the equipment or appliances served. Safety and safety relief valves shall be set at not greater than the nameplate pressure rating of the boiler or pressure vessel and shall be in accordance with the ASME Boiler and Pressure Vessel Code or the ASME CSD-1.
1006.5 Installation.
Safety or relief valves shall be installed directly into the safety or relief valve opening on the boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief valve drain shall discharge by gravity to a nonhazardous point of discharge without obstruction.
1006.6 Safety and relief valve discharge.
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall, at a minimum, be the same diameter as the safety or relief valve outlet. Safety and relief valve discharge pipes shall be properly supported to prevent stress on the valve and vessel. Safety and relief valves shall not discharge so as to be a hazard, a potential cause of damage or otherwise a nuisance. Discharge of hazardous materials must be properly contained in a method approved by the department. High-pressure-steam safety valves shall be vented to the outside of the structure. Where a low-pressure safety valve or a relief valve discharges to the drainage system, the installation shall conform to the New York City Plumbing Code.
1006.7 Boiler safety devices.
Boilers shall be equipped with controls and limit devices as required by the manufacturer's instructions and the conditions of the listing.
1006.8 Electrical requirements.
The power supply to the electrical control system shall be from a two-wire branch circuit that has a grounded conductor, or from an isolation transformer with a two-wire secondary. Where an isolation transformer is provided, one conductor of the secondary winding shall be grounded. Control voltage shall not exceed 150 volts nominal, line to line. Control and limit devices shall interrupt the ungrounded side of the circuit. A means of manually disconnecting the control circuit shall be provided and controls shall be arranged so that when deenergized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position and shall be provided with ready access.
1006.8.1 Remote control (shutdown).
A remote control shall be provided to stop the flow of oil and/or gas and combustion air to any burner or fuel-burning internal combustion equipment. Such a control shall be provided along every means of egress from the room in which the burner or equipment is located. Each remote control shall be located outside of, but as close as practicable to the burner or equipment room itself and shall be labeled: "REMOTE CONTROL FOR BURNER."
Exception: Where an outside location is impracticable, the remote control shutdown may be provided immediately inside the room in which the burner or equipment is located. Such location must be accessible at all times.
1006.9 Carbon monoxide detectors.
Carbon monoxide detectors shall be provided in all fuel-fired appliance rooms to detect the level of carbon monoxide in the room and signal an alarm. Such detectors shall be listed and installed in accordance with Chapter 9 of the New York City Building Code.
Section MC 1007. Boiler Low-Water Cutoff
1007.1 General.
Steam and hot water boilers shall be protected with dual low-water cutoff control, with each control independently piped to the pressure vessel in accordance with ASME CSD-1. For hydronic boilers, the low-water cut out may be located in the supply piping above the boiler before any intervening valve. A flow-sensing control installed in accordance with ASME CSD-1 shall be considered a low-water cutoff for the purposes of this section.
Exception: Hot water boilers located within a dwelling unit supplying only that unit and having a total heat input of less than 400,000 Btu/h (117.2 kW) may be protected by only one low-water cutoff control.
1007.2 Operation.
Low-water cutoff controls and flow-sensing controls required by Section 1007.1 shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer and in accordance with ASME CSD-1, or when water circulation stops, respectively.
1007.3 Low-water cut out maintenance and testing.
Low-water cut outs shall be maintained in accordance with ASME CSD-1 and the manufacturer's specifications. An operator shall test low-water cut outs as follows: (1) high pressure steam boilers every shift, (2) low pressure steam boilers daily and (3) hot water boilers monthly. Slow drain tests shall be conducted for steam boilers every six months. Every year, low-water cut outs and associated piping for steam boilers shall be opened, cleaned and inspected. Records of all testing, cleaning, and inspection required by this section shall be maintained, and made available to the department upon request.
Section MC 1008. Boiler Blowoff / Blowdown Valves
1008.1 General.
Every boiler shall be equipped with blowoff / blowdown valve(s). The valve(s) shall be installed in the openings provided on the boiler. The minimum quantity and size of the valve(s) and associated piping shall be the quantity and size specified by the boiler manufacturer or the quantity and size of the boiler blowoff / blowdown valve opening. Where the maximum allowable working pressure of the boiler exceeds 15 psig (103.4 kPa), two bottom blowoff valves shall be provided consisting of either two slow-opening valves in series or one quick-opening valve and one slow-opening valve in series, with the quick-opening valve installed closest to the boiler.
1008.2 Discharge.
Blowoff / blowdown valves shall discharge to a safe place of disposal. Where discharging to the drainage system, the installation shall conform to the New York City Plumbing Code.
1008.3 Maintenance.
Blowdown lines shall be inspected annually to verify they are free of deposits and in good working condition.
Section MC 1009. Hot Water Boiler Expansion Tank
1009.1 Where required.
An expansion tank shall be installed in every hot water system. For multiple boiler installations, not less than one expansion tank is required. Expansion tanks shall be of the closed or open type. Tanks shall be rated for the pressure of the hot water system. Lockable shutoff valves shall be installed at connections to all expansion tanks. Valves shall remain locked in the open position.
1009.2 Closed-type expansion tanks.
Closed-type expansion tanks shall be installed in accordance with the manufacturer's instructions. Expansion tanks for systems designed to have an operating pressure in excess of 30 psi (205.8 kPa) shall be constructed and certified in accordance with the ASME Boiler and Pressure Vessel Code. The size of the tank shall be based on the capacity of the hot-water-heating system. The minimum size of the tank shall be determined in accordance with the following equation where all necessary information is known:
V t = (0.00041T - 0.0466)V s (Equation 10-1) (P a /P f ) - (P a /P o )
For SI:
V t = (0.000738T - 0.03348)V s (P a /P f ) - (P a /P o )
where:
V t = Minimum volume of tanks (gallons) (L). V s = Volume of system, not including expansion tanks (gallons) (L). T = Average operating temperature (°F) (°C). P a = Atmospheric pressure (psi) (kPa). P f = Fill pressure (psi) (kPa). P o = Maximum operating pressure (psi) (kPa).
Where all necessary information is not known, the minimum size of the tank shall be determined from Table 1009.2.
Table 1009.2 Closed-Type Expansion Tank Sizing
System Volume in Gallons Tank Capacities in Gallons Pressurized Diaphragm Type Nonpressurized Type 100 9 15 200 17 30 300 25 45 400 33 60 500 42 75 1,000 83 150 2,000 165 300
For SI: 1 gallon = 3.795 L
1009.3 Open-type expansion tanks.
Open-type expansion tanks shall be located not less than 4 feet (1219.2 mm) above the highest heating element. The tank shall be adequately sized for the hot water system. An overflow with a minimum diameter of 1 inch (25.4 mm) shall be installed at the top of the tank. The overflow shall discharge to the drainage system in accordance with the New York City Plumbing Code.
Section MC 1010. Gauges
1010.1 Hot water boiler gauges.
Every hot water boiler shall have a pressure gauge and a temperature gauge, or a combination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal range of the system's operation.
1010.2 Steam boiler gauges.
Every steam boiler shall have a water-gauge glass and a pressure gauge with a siphon. The pressure gauge shall indicate the pressure within the normal range of the system's operation.
1010.2.1 Water-gauge glass.
The gauge glass shall be installed in accordance with the ASME Boiler and Pressure Vessel Code or ASME CSD-1.
Section MC 1011. Tests
1011.1 Tests.
Upon completion of the assembly and installation of boilers and pressure vessels, acceptance tests shall be conducted in accordance with the requirements of the ASME Boiler and Pressure Vessel Code. Boilers shall not be placed in operation upon completion of construction until they have been inspected and tested and a certificate of compliance has been issued by the commissioner. All final inspections and tests for boilers shall be witnessed by a qualified boiler inspector in the employ of the department or a duly authorized insurance company as provided in Section 204 of the Labor Law of the State of New York. Equipment having an input of not more than 350,000 Btu/h (103 kW) shall be exempt from this requirement. Where field assembly of pressure vessels or boilers is required, a copy of the completed H-2, P-2 or U-1 Manufacturer's Data Report and the completed Appendix C of ASME CSD-1 required by the ASME Boiler and Pressure Vessel Code shall be submitted to the department.
1011.1.1 Fitness for service.
When a boiler or pressure vessel has exceeded its useful life or has been subjected to an event that may have impacted the integrity of the pressure vessel, the department may require that a fitness for service study be completed. The study shall be completed in accordance with the National Board Inspection Code Part 2, Section 4, and documented in accordance with the National Board 403 form.
1011.2 Test gauges.
An indicating test gauge shall be connected directly to the boiler or pressure vessel where it is visible to the operator throughout the duration of the test. The pressure gauge scale shall be graduated over a range of not less than one and one-half times and not greater than four times the maximum test pressure. Gauges utilized for testing shall be calibrated and certified annually in accordance with ASME B40.100 by the test operator.
1011.3 Periodic boiler inspections.
Periodic boiler inspections shall be performed in accordance with Article 303 of Chapter 3 of Title 28 of the Administrative Code and Section 1007.3 of this code. In addition, boiler inspections shall:
1. Be completed in accordance with the National Board Inspection Code.
2. Include the review of testing documentation for all controls and safety devices.
3. Verify that the flue connection from the boiler to the chimney is properly sealed and in good working condition.
4. Verify that the combustion air system as originally designed is operational.
5. Verify that the High Pressure Operators' licenses are current and that Low Pressure Operators are qualified per New York State requirements.
6. Include a permanent record of the visit.
7. Be subject to the quality control measures of the department.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1011.4 Pressurized systems containing hazardous materials.
Any pressurized system that contains hazardous materials or presents a physical hazard by release shall be pre-approved for installation, subject to testing, and subject to inspection by the department.
1011.5 Nondestructive examination.
When required by the department, the nondestructive examination (NDE) requirements, including technique, extent of coverage, procedures, personnel qualification, and acceptance criteria, shall be performed in accordance with the applicable provisions of the edition of the code of construction for the pressure-vessel in effect at the time of installation. Weld repairs and alterations shall be subject to the same nondestructive examination requirements. Where this is not possible or practicable, alternative NDE methods acceptable to the inspector and the department may be used.
Section MC 1012. Maximum Temperature
1012.1 Maximum temperature.
Maximum indoor temperature in spaces surrounding boilers, water heaters, and pressure vessels shall not exceed the operational temperature of the installed equipment or 104°F (40°C).
Section MC 1101. General
1101.1 Scope.
This chapter shall govern the design, installation, construction, alteration and repair of refrigeration systems that vaporize and liquefy a fluid during the refrigerating cycle. Refrigerant piping design and installation, including pressure vessels and pressure relief devices, shall conform to this code. Permanently installed refrigerant storage systems and other components shall be considered as part of the refrigeration system to which they are attached. This chapter shall also govern the change of refrigerants in existing refrigerating systems having a different safety group classification.
1101.2 Factory-built equipment and appliances.
Listed and labeled self-contained, factory-built equipment and appliances shall be tested in accordance with UL 207, 412, 471 or 1995. Such equipment and appliances are deemed to meet the design, manufacture and factory test requirements of this code if installed in accordance with their listing and the manufacturer's instructions.
1101.3 Protection.
Any portion of a refrigeration system that is subject to physical damage shall be protected in an approved manner.
1101.4 Water connection.
Water supply and discharge connections associated with refrigeration systems shall be made in accordance with this code and the New York City Plumbing Code.
1101.5 Fuel-oil and fuel-gas connection.
Refrigeration system devices, equipment and appliances utilizing fuel oil or fuel gas for combustion shall be installed in accordance with the applicable provisions of the New York City Fuel Gas Code and this code.
1101.6 General.
Refrigeration systems shall comply with the requirements of this code and, except as modified by this code, ASHRAE 15. Ammonia-refrigerating systems shall comply with this code and, except as modified by this code, ASHRAE 15 and IIAR 2. Such systems shall be maintained in accordance with the New York City Fire Code.
1101.7 Maintenance.
Mechanical refrigeration systems shall be maintained in proper operating condition, free from accumulations of oil, dirt, waste, excessive corrosion, other debris and leaks.
1101.8 Change in refrigerant type.
The type of refrigerant in refrigeration systems having a refrigerant circuit containing more than 220 pounds (99.8 kg) of Group A1 or 30 pounds (13.6 kg) of any other group refrigerant shall not be changed without prior notification to the commissioner and compliance with the applicable code provisions for the new refrigerant type. The refrigerant being considered shall be evaluated for suitability by an engineer. Whenever change in the type of refrigerant is to be done, consideration shall be given to the following:
1. The effects of the substitute refrigerant on materials in the system;
2. The possibility of overloading the liquid receiver, which shall not be more than 80 percent full of liquid;
3. The possibility of exceeding motor rating, design working pressure, or other requirements that would violate any of the provisions of this code;
4. The proper size of refrigerant controls;
5. The effect of the operation and setting of safety devices;
6. The possible hazards created by mixture of the original and the substituted refrigerant; and
7. The effect of the classification of the refrigerant as provided.
1101.9 Refrigerant discharge.
Notification of refrigerant discharge shall be provided in accordance with the New York City Fire Code.
1101.10 Gas and oil fired absorption systems.
Refrigeration systems utilizing fuel oil or fuel gas for combustion shall be installed in accordance with the applicable provisions of the New York City Fuel Gas Code and this code.
1101.11 Signs, nameplates, and operation and emergency shutdown instructions.
Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the following:
1. Sections 9.15, 11.2.1, 11.2.2, 11.2.4, and 11.7 of ASHRAE 15.
2. Each refrigeration unit or system shall be provided with a nameplate indicating the horsepower of the prime mover or compressor and the equivalent of such horsepower in kilowatts.
3. Section 1105.11 of this code.
1101.12 Locking access port caps.
Refrigerant circuit access ports located outdoors shall be fitted with locking-type tamper-resistant caps requiring a special tool or key to open.
Section MC 1102. System Requirements
1102.1 General.
The system classification, allowable refrigerants, maximum quantity, enclosure requirements, location limitations, and field pressure test requirements shall be determined as follows:
1. Determine the refrigeration system's classification, in accordance with Section 1103.3.
2. Determine the refrigerant classification in accordance with Section 1103.1.
3. Determine the maximum allowable quantity of refrigerant in accordance with Section 1104, based on type of refrigerant, system classification, and occupancy.
4. Determine the system enclosure requirements in accordance with Section 1104.
5. Refrigeration equipment and appliance location and installation shall be subject to the limitations of Chapter 3.
6. Nonfactory-tested, field-erected equipment and appliances shall be pressure tested in accordance with Section 1108.
1102.2 Refrigerants.
The refrigerant shall be that which the equipment or appliance was designed to utilize or converted to utilize. Refrigerants not identified in Table 1103.1 shall be approved by the department before use. Refrigerants not identified in Table 1103.1, other than those having a Safety Group Classification of A-1 or A2L, shall also be approved by the Fire Department before use.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1102.2.1 Mixing.
Refrigerants, including refrigerant blends, with different designations in ASHRAE 34 shall not be mixed in a system.
Exception: Addition of a second refrigerant is allowed where permitted by the equipment or appliance manufacturer to improve oil return at low temperatures. The refrigerant and amount added shall be in accordance with the manufacturer's instructions.
1102.2.2 Purity.
Refrigerants used in refrigeration systems shall be new, recovered or reclaimed refrigerants in accordance with Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3. Where required by the equipment or appliance owner, the installer shall furnish a signed declaration that the refrigerant used meets the requirements of Section 1102.2.2.1, 1102.2.2.2 or 1102.2.2.3.
Exception: The refrigerant used shall meet the purity specifications set by the manufacturer of the equipment or appliance in which such refrigerant is used where such specifications are different from that specified in Sections 1102.2.2.1, 1102.2.2.2 and 1102.2.2.3.
1102.2.2.1 New refrigerants.
Refrigerants shall be of a purity level specified by the equipment or appliance manufacturer.
1102.2.2.2 Recovered refrigerants.
Refrigerants that are recovered from refrigeration and air-conditioning systems shall not be reused in other than the system from which they were recovered and in other systems of the same owner. Recovered refrigerants shall be filtered and dried before reuse. Recovered refrigerants that show clear signs of contamination shall not be reused unless reclaimed in accordance with Section 1102.2.2.3.
1102.2.2.3 Reclaimed refrigerants.
Used refrigerants shall not be reused in a different owner's equipment or appliances unless tested and found to meet the purity requirements of AHRI 700. Contaminated refrigerants shall not be used unless reclaimed and found to meet the purity requirements of AHRI 700.
1102.3 Access port protection.
Refrigerant access ports shall be protected in accordance with Section 1101.12 whenever refrigerant is added to or recovered from refrigeration or air-conditioning systems.
Section MC 1103. Refrigeration System Classification
1103.1 Refrigerant classification.
Refrigerants shall be classified in accordance with ASHRAE 34 as listed in Table 1103.1.
Table 1103.1 Refrigerant Data and Safety Classifications a
Refrigerant Number Chemical Name Chemical Formula OEL d ppm v/v Safety c Group RCL (ppm v/v) (g/m 3 ) Ib/Mcf Methane Series 11 b trichlorofluoromethane CCl3F C1000 A1 1,100 6.2 .39 12 b dichlorodifluoromethane CCl2F2 1,000 A1 18,000 90 5.6 13 b chlorotrifluoromethane CClF3 1,000 A1 - - - 13B1 b bromotrifluoromethane CBrF3 1,000 A1 - - - 14 tetrafluoromethane (carbon tetrafluoride) CF4 1,000 A1 110,000 400 25 21 dichlorofluoromethane CHCl2F - B1 - - - 22 chlorodifluoromethane CHClF2 1,000 A1 59,000 210 13 23 trifluoromethane CHF3 1,000 A1 41,000 120 7.3 30 dichloromethane (methylene chloride) CH2Cl2 - B2 - - - 32 difluoromethane (methylene fluoride) CH2F2 1,000 A2L 36,000 77 4.8 40 chloromethane (methyl chloride) CH3Cl - B2 - - - 50 methane CH4 1,000 A3 - - - Ethane Series 113 b 1,1,2-trichloro-1,2,2-trifluoroethane CCl2FCClF2 1,000 A1 2,600 20 1.2 114 b 1,2-dichloro-1,1,2,2- tetrafluoroethane CClF2CClF2 1,000 A1 20,000 140 8.7 115 b chloropentafluoroethane CClF2CF3 1,000 A1 120,000 760 47 116 hexafluoroethane CF3CF3 1,000 A1 97,000 550 34 123 2,2-dichloro-1,1,1,-trifluoroethane CHCl2CF3 50 B1 9,100 57 3.5 124 2-chloro-1,1,1,2-tetrafluoroethane CHClFCF3 1,000 A1 10,000 56 3.5 125 pentafluoroethane CHF2CF3 1,000 A1 75,000 370 23 134 a 1,1,1,2-tetrafluoroethane CH2FCF3 1,000 A1 50,000 210 13 142 b 1-chloro-1, 1-difluoroethane CH3CClF2 1,000 A2 20,000 83 5.1 143 a 1,1,1-trifluoroethane CH3CF3 1,000 A2L 21,000 70 4.5 152 a 1,1-difluoroethane CH3CHF2 1,000 A2 12,000 32 2.0 170 ethane CH3CH3 1,000 A3 7,000 8.7 0.54 Ethers E170 methoxymethane (dimethyl ether) CH3OCH3 1,000 A3 8,500 16 1.0 Propane 218 octafluoropropane CF3,CF2CF3 1,000 A1 90,000 690 43 227 ea 1,1,1,2,3,3,3-heptafluoropropane CF3CHFCF3 1,000 A1 84,000 580 36 236 fa 1,1,1,3,3,3-hexafluoropropane CF3CH2CF3 1,000 A1 55,000 340 21 245 fa 1,1,1,3,3-pentafluoropropane CHF2CH2CF3 300 B1 34,000 190 12 290 propane CH3CH2CH3 1,000 A3 5,300 9.5 0.56 Cyclic Organic Compounds C318 octafluorocyclobutane -(CF2)4- 1,000 A1 80,000 660 41 Miscellaneous Organic Compounds Hydrocarbons 600 butane CH3CH2CH2CH3 1,000 A3 - - .51 600 a 2-methylpropane (isobutane) CH(CH3)2CH3 1,000 A3 4,000 9.6 .59 601 pentane CH3CH2CH2CH2CH3 600 A3 1,000 2.9 .18 601 a 2-methylbutane (isopentane) (CH3)2CHCH2CH3 600 A3 1,000 2.9 .18 611 methyl formate HCOOCH3 100 B2 - - - Inorganic Compounds 702 hydrogen H2 - A3 - - - 704 helium He - A1 - - - 717 ammonia NH3 25 B2L 320 0.22 .014 718 water H2O - A1 - - - 720 neon Ne - A1 - - - 728 nitrogen N2 - A1 - - - 740 argon Ar - A1 - - - 744 carbon dioxide CO2 5000 A1 40,000 72 4.5 764 sulfur dioxide SO2 - B1 - - - Unsaturated Organic Compounds 1150 ethene (ethylene) CH2=CH2 200 A3 - - - 1234yf 2,3,3,3-tetrafluoro-1-propene CF3CF=CH2 500 A2L 16,000 75 4.7 1234ze(E) trans-1,3,3,3-tetrafluoro-1-propene CF3CH=CHF 800 A2L 16,000 75 4.7 1270 propene (propylene) CH3CH=CH2 500 A3 1,000 1.7 .1 Zeotropes (Refrigerant Blends) 400 (50%/50%) b R-12/114 (50.0/50.0) 1,000 A1 28,000 160 10 400 (60%/40%) b R-12/114 (60.0/40.0) 1,000 A1 30,000 170 11 401A R-22/152a/124 (53.0/13.0/34.0) (±2.0/+0.5, -1.5;/±1.0) 1,000 A1 27,000 110 6.6 401B R-22,/152a/124 (61.0/11.0/28.0) (±2.0/+0.5, -1.5/±1.0) 1,000 A1 30,000 120 7.2 401C R-22,/152a/124 (33.0/15.0/52.0) (±2.0/+0.5, -1.5/±1.0) 1,000 A1 20,000 84 5.2 402A R-125/290/22 (60.0/2.0/38.0) (±2.0/+0.1, -1.0/±2.0) 1,000 A1 33,000 140 8.5 402B R-125/290/22 (38.0/2.0/60.0) (±2.0/+0.1, -1.0/±2.0) 1,000 A1 63,000 240 15 403A R-290/22/218 (5.0/75.0/20.0) (+.2, -2.0/±2.0/±2.0) 1,000 A2 33,000 120 7.6 403B R-290/22/218 (5.0/56.0/39.0) (+.2, -2.0/±2.0/±2.0) 1,000 A1 70,000 290 18 404A R-125/143a/134a (44.0/52.0/4.0) (±2.0/±1.0/±2.0) 1,000 A1 130,000 500 31 406A R-22/600a/142b (55.0/4.0/41.0) (±2.0/±1.0/±1.0) 1,000 A2 21,000 25 4.7 407A R-32/125/134a (20.0/40.0/40.0) (±2.0/±2.0/±2.0) 1,000 A1 83,000 300 19 407B R-32/125/134a (10.0/70.0/20.0) (±2.0/±2.0/±2.0) 1,000 A1 79,000 330 21 407C R-32/125/134a (23.0/25.0/52.0) (±2.0/±2.0/±2.0) 1,000 A1 81,000 290 18 407D R-32/125/134a (15.0/15.0/70.0) (±2.0/±2.0/±2.0) 1,000 A1 68,000 250 16 407E R-32/125/134a (25.0/15.0/60.0) (±2.0/±2.0/±2.0) 1,000 A1 80,000 280 17 407F R-32/125/134a (30.0/30.0/40.0) (±2.0/±2.0/±2.0) 1,000 A1 95,000 320 20 408A R-125/143a/22 (7.0/46.0/47.0) (±2.0/±1.0/±2.0) 1,000 A1 95,000 110 21 409A R-22/124/142b (60.0/25.0/15.0) (±2.0/±2.0/±1.0) 1,000 A1 29,000 120 7.1 409B R-22/124/142b (65.0/25.0/10.0) (±2.0/±2.0/±1.0) 1,000 A1 30,000 390 7.3 410A R-32/125 (50.0/50.0) (+0.5, -1.5/+1.5, -0.5) 1,000 A1 140,000 420 26 410B R-32/125 (45.0/55.0) (±1.0/±1.0) 1,000 A1 140,000 430 27 411A R-1270/22/152a(1.5/87.5/11.0) (+0.0, -1.0/+2.0,-0.0/+0.0, -1.0) 990 A2 14,000 46 2.9 411B R-1270/22/152a(3.0/94.0/3.0) (+0.0, -1.0/+2.0,-0.0/+0.0, -1.0) 980 A2 13,000 45 2.8 412A R-22/218/142b (70.0/5.0/25.0) (±2.0/±2.0/±1.0) 1,000 A2 22,000 82 5.1 413A R-218/134a/600a (9.0/88.0/3.0) ±1.0/±2.0/+0.0,-1.0) 1,000 A2 22,000 95 5.8 414A R-22/124/600a/142b(51.0/28.5/4.0/16.5) (±2.0/±2.0/±0.5 /+0.5, -1.0) 1,000 A1 26,000 100 6.4 414B R-22/124/600a/142b(50.0/39.0/1.5/9.5) (±2.0/±2.0/±0.5 /+0.5, -1.0) 1,000 A1 23,000 95 6.0 415A R-22/152a (82.0/18.0) (±1.0/±1.0) 1,000 A2 57,000 190 12 415B R-22/152a (25.0/75.0) (±1.0/±1.0) 1,000 A2 52,000 120 9.3 416A R-134a/124/600(59.0/39.5/1.5) (+0.5, -1.0/+1.0,-0.5/+1.0, -0.2) 1,000 A1 14,000 62 3.9 417A R-125/134a/600 (46.6/50.0/3.4) (±1.1/±1.0/+0.1,-0.4) 1,000 A1 13,000 56 3.5 417B R-125/134a/600 (79.0/18.3/2.7) (±1.0/±1.0/+0.1,-0.5) 1,000 A1 15,000 70 4.3 418A R-290/22/152a (1.5/96.0/2.5 (±0.5/±1.0/±0.5) 1,000 A2 59,000 200 13 419A R-125/134a/E170 (77.0/19.0/4.0) (1.0/1.0/1.0) 1,000 A2 70,000 310 19 420A R-134a/142b (88.0/12.0) (+1.0,-0.0/+0.0,-1.0) 1,000 A1 45,000 190 12 421A R-125/134a (58.0/42.0) (±1.0/±1.0) 1,000 A1 61,000 280 17 421B R-125/134a (85.0/15.0) (±1.0/±1.0) 1,000 A1 69,000 330 21 422A R-125/134a/600a (55.0/42.0/3.0) (±1.0/±1.0/+0.1,-0.4) 1,000 A1 63,000 290 18 422B R-125/134a/600a (82.0/15.0/3.0) (±1.0/±1.0/+0.1,-0.5) 1,000 A1 56,000 250 16 422C R-125/134a/600a (82.0/15.0/3.0) (±1.0/±1.0/+0.1,-0.5) 1,000 A1 62,000 290 18 422D R-125/134a/600a(65.1/31.5/3.4) (+0.9,-1.1/±1.0/+0.1,-0.4) 1,000 A1 58,000 260 16 423A R-134a/227ea (52.5/47.5) (±1.0/±1.0) 1,000 A1 59,000 310 19 424A R-125/134a/600a/600/601a(50.5/47.0/0.9/1.0/0.6) (±1.0/±1.0/+0.1,-0.2/+0.1, +0.2/+0.1,-0.2) 970 A1 23,000 100 6.2 425A R-32/134a/227ea (18.5/69.5/12.0) (±0.5/±0.5/±0.5) 1,000 A1 72,000 260 16 426A R-125/134a/600/601a(5.1/93.0/1.3/0.6) (±1.0/±1.0/+0.1,-0.2/+0.1, -0.2) 990 A1 20,000 83 5.2 427A R-32/125/143a/134a(15.0/25.0/10.0/50.0) (±2.0/±2.0/±2.0/;±2.0) 1,000 A1 79,000 290 18 428A R-125/143a/290/600a(77.5/20.0/0.6/1.9) (±1.0/±1.0/+0.1,-0.2/+0.1, -0.2) 1,000 A1 83,000 370 23 429A R-E170/152a/600a(60.0/10.0/30.0) (±1.0/±1.0/±1.0) 1,000 A3 6,300 13 .81 430A R-152a/600a (76.0/24.0) (±1.0/±1.0) 1,000 A3 8,000 21 1.3 431A R-290/152a (71.0/29.0) (±1.0/±1.0) 1,000 A3 5,500 11 .69 432A R-1270/E170 (80.0/20.0) (±1.0/±1.0) 710 A3 1,200 2.1 .13 433A R-1270/290 (30.0/70.0) (±1.0/±1.0) 880 A3 3,100 5.5 .34 433B R-1270/290 (5.0/95.0) (±1.0/±1.0) 950 A3 4,500 8.1 .51 433C R-1270/290 (25.0/75.0) (±1.0/±1.0) 790 A3 3,600 6.6 .41 434A R-125/143a/134a/600a(63.2/18.0/16.0/2.8) (±1.0/±1.0±1.0/+0.1,-0.2) 1,000 A1 73,000 320 20 435A R-E170/152a (80.0/20.0) (±1.0/±1.0) 1,000 A3 8,500 17 1.1 436A R-290/600a (56.0/44.0) (±1.0/±1.0) 1,000 A3 4,000 8.1 .5 436B R-290/600a (52.0/48.0) (±1.0/±1.0) 1,000 A3 4,000 8.1 .5 437A R-125/134a/600/601(19.5/78.5/1.4/0.6) (+0.5,-1.8/+1.5,-0.7/+0.1,-0.2/+0.1,-0.2) 990 A1 19,000 81 5.0 438A R-32/125/134a/600/601a(8.5/45.0/44.2/1.7/0.6) (+0.5,-1.5/±1.5/±1.5/+0.1,-0.2/+0.1,-0.2) 990 A1 20,000 79 4.9 439A R-32/125/600a(50.0/47.0/3.0) (±1.0/±1.0/±0.5) 990 A2 26,000 76 4.7 440A R-290/134a/152a(0.6/1.6/97.8) (±1.0/±0.6/±0.5) 1,000 A2 12,000 31 1.9 441A R-179/290/600a/600(3.1/54.8/6.0/36.1) (±0.3/±2.0/±0.6/±2.0) 1,000 A3 3,200 6.3 .39 Azeotropes (Refrigerant Blends) 500 b R-12/152a (73.8/26.2) - 1,000 A1 30,000 120 7.6 501 b R-22/12 (75.0/25.0) - 1,000 A1 54,000 210 13 502 b R-22/115 (48.8/51.2) - 1,000 A1 73,000 330 21 504 R-32/115 (48.2/51.8) - 1,000 - 140,000 450 28 507A R-125/143a (50.0/50.0) - 1,000 A1 130,000 520 32 508A R-23/116 (39.0/61.0) - 1,000 A1 55,000 220 14 508B R-23/116 (46.0/54.0) - 1,000 A1 52,000 200 13 509A R-22/218 (44.0/56.0) - 1,000 A1 75,000 390 24 510A R-E170/600a (88.0/12.0) (±0.5/±0.5) 1,000 A3 7,300 14 .87 511A R-290/E170 (95.0,5.0) (±1.0/±1.0) 1,000 A3 5,300 9.5 .59
For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.0283 m 3 .
a. Data based on ASHRAE 34 including Addenda a through o. For more complete data, see ASHRAE 34 and Addenda. Use of Addenda issued after Addendum o is subject to approval as set forth in Section 1102.2.
b. Class I ozone depleting refrigerant. Not permitted for new installations.
c. Refrigerants in Safety Group "A2L" shall comply with rules of the department. Refrigerants in Safety Group "B2L" shall comply with all applicable requirements for "B2" refrigerants.
d. OCCUPATIONAL EXPOSURE LIMIT (OEL). The time-weighted average (TWA) concentration for a normal 8-hour workday and a 40-hour workweek to which nearly all workers can be repeatedly exposed without adverse effect, based on the OSHA PEL, ACGIH TLV-TWA, AIHA WEEL, or consistent value.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1103.2 Occupancy classification.
Locations of refrigerating systems are described by occupancy classifications that consider the ability of people to respond to potential exposure to refrigerants. Where equipment or appliances, other than piping, are located outside a building and within 20 feet (6096 mm) of any building opening, such equipment or appliances shall be governed by the occupancy classification of the building. Occupancy classifications of buildings shall be in accordance with the building classifications in the New York City Building Code.
1. Institutional occupancy shall include Occupancy Groups I-1, I-2, I-3 and I-4.
2. Public assembly occupancy shall include Occupancy Groups A-1, A-2, A-3, A-4, A-5 and E.
3. Residential occupancy shall include Occupancy Groups R-1, R-2 and R-3.
4. Commercial occupancy shall include Occupancy Groups M and B, except Occupancy Group M with retail stores having an occupant load of more than 100 persons on any floor other than street level.
5. Large mercantile occupancy shall include Occupancy Group M with retail stores having an occupant load of more than 100 persons on any floor other than street level.
6. Industrial occupancy shall include Occupancy Groups F-1, F-2, H-1, H-2, H-3, H-4, H-5, S-1 and S-2.
7. Mixed occupancy occurs where two or more occupancies are located within the same building. Where each occupancy is isolated from the rest of the building by tight walls, floors and ceilings and by self-closing doors, the requirements for each occupancy shall apply to its portion of the building. Where the various occupancies are not so isolated, the occupancy having the most stringent requirements shall be the governing occupancy.
1103.3 System classification.
Refrigeration systems shall be classified according to the degree of probability that refrigerant leaked from a failed connection, seal or component could enter an occupied area. The distinction is based on the basic design or location of the components.
1103.3.1 Low-probability systems.
Double-indirect open-spray systems, indirect closed systems and indirect-vented closed systems shall be classified as low-probability systems, provided that all refrigerant-containing piping and fittings are isolated when the quantities in Table 1103.1 are exceeded.
1103.3.2 High-probability systems.
Direct systems and indirect open-spray systems shall be classified as high-probability systems.
Exception: An indirect open-spray system shall not be required to be classified as a high-probability system if the pressure of the secondary coolant is at all times (operating and standby) greater than the pressure of the refrigerant.
Section MC 1104. System Application Requirements
1104.1 General.
The refrigerant, occupancy and system classification cited in this section shall be determined in accordance with Sections 1103.1, 1103.2 and 1103.3, respectively. For refrigerant blends assigned dual classifications, as formulated and for the worst case of fractionation, the classifications for the worst case of fractionation shall be used. For blends assigned only a single safety group classification in Table 1103.1 or ASHRAE 34, that classification shall be used. Use of a Group A3 or Group B3 refrigerant is prohibited. In an industrial occupancy, a Group A3 or Group B3 refrigerant may be used in high- or low-probability systems only when approved by the commissioner and the Commissioner of the Fire Department. Such use will be approved only if the applicant can demonstrate to the satisfaction of the commissioner and the Commissioner of the Fire Department that the use of the refrigerant is a necessity and does not represent a substantial risk to life, limb, health or property.
1104.2 Machinery room.
Except as provided in Sections 1104.2.1 and 1104.2.2, all components containing the refrigerant shall be located either outdoors or in a machinery room where the quantity of refrigerant in an independent circuit of a system exceeds the amounts shown in Table 1103.1. For refrigerant names not listed in Table 1103.1, the same requirement shall apply when the amount for any named component exceeds that indicated in Table 1103.1 for that component. This requirement shall also apply when the combined amount of the named components exceeds a limit of 69,100 parts per million (ppm) by volume. Machinery rooms required by this section shall be constructed and maintained in accordance with Section 1105 for Group A1 and B1 refrigerants and in accordance with Sections 1105 and 1106 for Group A2, B2, A3 and B3 refrigerants. Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
Exceptions:
1. Machinery rooms are not required for listed equipment and appliances containing not more than 6.6 pounds (3 kg) of refrigerant, regardless of the refrigerant's safety classification, where installed in accordance with the equipment's or appliance's listing and the equipment or appliance manufacturer's installation instructions.
2. Piping in conformance with Section 1107 of this chapter and Section 8.10 of ASHRAE 15 is allowed in other locations to connect components installed in a machinery room with those installed outdoors.
1104.2.1 Institutional occupancies.
The amounts shown in Table 1103.1 shall be reduced by 50 percent for all areas of institutional occupancies except kitchens, laboratories and mortuaries. The total of all Group A2, B2, A3 and B3 refrigerants shall not exceed 550 pounds (249.4 kg) in occupied areas or machinery rooms. Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
1104.2.2 Industrial occupancies and refrigerated rooms.
This section applies only to industrial occupancies and refrigerated rooms for manufacturing, food and beverage preparation, meat cutting, other processes and storage. Machinery rooms are not required where all of the following conditions are met:
1. The space containing the machinery is separated from other occupancies by tight construction with tight-fitting doors.
2. Access is restricted to authorized personnel.
3. The floor area per occupant is not less than 100 square feet (9.3 m 2 ). Where provided with egress directly to the outdoors or into building exits meeting the requirements of the New York City Building Code, the minimum floor area shall not apply.
4. Refrigerant detectors are installed as required for machinery rooms in accordance with Section 1105.3.
5. Surfaces having temperatures exceeding 800°F (426.7°C) and open flames are not present where any Group A2, B2, A3 or B3 refrigerant is used (see Section 1104.3.3). Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
6. All electrical equipment and appliances conform to Class 1, Division 2, hazardous location classification requirements of the New York City Electrical Code where the quantity of any Group A2, B2, A3 or B3 refrigerant, other than ammonia, in a single independent circuit would exceed 25 percent of the lower flammability limit (LFL) upon release to the space based on the volume determined by Section 1104.4. Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
7. All refrigerant-containing parts in systems exceeding 100 hp (74.6 kW) drive power, except evaporators used for refrigeration or dehumidification; condensers used for heating; control and pressure relief valves for either; and connecting piping, shall be located either outdoors or in a machinery room.
1104.3 Refrigerant restrictions.
Refrigerant applications, maximum quantities and use shall be restricted in accordance with Sections 1104.3.1 through 1104.3.3.
1104.3.1 Air-conditioning for human comfort.
Group A3, B1, B2 and B3 refrigerants shall not be used in high-probability air conditioning systems for human comfort.
Exceptions:
1. Sealed absorption and unit air-conditioning systems having refrigerant quantities not exceeding those set forth in Table 1103.1.
2. Industrial occupancies.
Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
Table 1104.3.1 Special Quantity Limits for Sealed Ammonia/Water Absorption and Self-Contained Systems
Type of Refrigeration System Maximum Pounds for Various Occupancies Institutional Public Assembly / Large Mercantile Residential Commercial Sealed Ammonia / Water Absorption System In exit access or lobbies 0 0 3.3 3.3 In adjacent outdoor locations 0 0 22 22 In other than exit access lobbies 0 6.6 6.6 22 Unit Systems In other than exit access or lobbies 0 0 6.6 22
For SI: 1 pound = 0.454 kg.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1104.3.2 All occupancies.
The total of all Group A2, B2, A3 and B3 refrigerants other than R-717, ammonia, shall not exceed 1,100 pounds (499 kg) except where approved. Nothing in this section shall be construed to allow the use of Group A3 and B3 refrigerants if otherwise prohibited.
1104.3.3 Protection from refrigerant decomposition.
Where any device having an open flame or surface temperature greater than 800°F (426.7°C) is used in a room containing more than 6.6 pounds (3 kg) of refrigerant in a single independent circuit, a hood and exhaust system shall be provided in accordance with Section 510. Such exhaust system shall exhaust combustion products to the outdoors.
Exception: A hood and exhaust system shall not be required where any of the following apply:
1. The refrigerant is R-717, R-718 or R-744.
2. The combustion air is ducted from the outdoors in a manner that prevents leaked refrigerant from being combusted.
3. A refrigerant detector is used to stop the combustion in the event of a refrigerant leak (see Sections 1105.3 and 1105.5).
1104.4 Volume calculations.
Volume calculations shall be in accordance with Sections 1104.4.1 through 1104.4.3.
1104.4.1 Noncommunicating spaces.
Where the refrigerant-containing parts of a system are located in one or more spaces that do not communicate through permanent openings or HVAC ducts, the volume of the smallest, enclosed occupied space shall be used to determine the permissible quantity of refrigerant in the system.
1104.4.2 Communicating spaces.
Where an evaporator or condenser is located in an air duct system, the volume of the smallest, enclosed occupied space served by the duct system shall be used to determine the maximum allowable quantity of refrigerant in the system.
Exception: If airflow to any enclosed space cannot be reduced below one-quarter of its maximum, the entire space served by the air duct system shall be used to determine the maximum allowable quantity of refrigerant in the system.
1104.4.3 Plenums.
Where the space above a suspended ceiling is continuous and part of the supply or return air plenum system, this space shall be included in calculating the volume of the enclosed space.
Section MC 1105. Machinery Room, General Requirements
1105.1 Design and construction.
Machinery rooms shall be designed and constructed in accordance with the New York City Building Code and this section.
1105.2 Openings.
Ducts and air handlers in the machinery room that operate at a lower pressure than the room shall be sealed to prevent any refrigerant leakage from entering the airstream.
1105.3 Refrigerant detector.
Refrigerant detectors in machinery rooms shall be provided as required by ASHRAE 15.
1105.4 Tests.
Periodic tests of the mechanical ventilating system shall be performed in accordance with manufacturer's specifications and as required by the Commissioner of the Fire Department.
1105.5 Fuel-burning appliances.
Open flames that use combustion air from the machinery room shall not be installed in a machinery room.
Exceptions:
1. Where the refrigerant is carbon dioxide or water.
2. Fuel-burning appliances shall not be prohibited in the same machinery room with refrigerant-containing equipment or appliances where combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leakage from entering the combustion chamber, or where a refrigerant vapor detector is employed to automatically shut off the combustion process in the event of refrigerant leakage.
1105.6 Ventilation.
Machinery rooms shall be mechanically ventilated to the outdoors. Location of the mechanical ventilation openings within the machinery room shall be based on the relative density of the refrigerant to air. When compressors or self-contained unit system are housed in a machinery space, other than in a machinery room or plenum, the space shall be ventilated in accordance with the requirements of Section 1105.6.3.
Exception: Where a refrigerating system is located outdoors more than 20 feet (6096 mm) from any building opening and is enclosed by a penthouse, lean-to or other open structure, natural or mechanical ventilation shall be provided. Location of the openings shall be based on the relative density of the refrigerant to air. The free-aperture cross section for the ventilation of the machinery room shall be not less than:
F = ÖG (Equation 11-1)
For SI: F = 0.138ÖG
where:
F = The free opening area in square feet (m 2 ).
G = The mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room
1105.6.1 Discharge location.
The discharge of the air shall be to the outdoors in accordance with Chapter 5. Exhaust from mechanical ventilation systems shall be discharged not less than 20 feet (6096 mm) from outdoor air intake or openings into buildings and 10 feet (3048 mm) from a fire escape or exterior stair.
1105.6.2 Makeup air.
Provisions shall be made for makeup air to replace that being exhausted. Openings for makeup air shall be located to avoid intake of exhaust air. Supply and exhaust ducts serving the machinery room shall not serve any other area, shall be constructed in accordance with Chapter 5 and shall be covered with corrosion-resistant screen of not less than 1/4-inch (6.4 mm) mesh.
Exception: The requirement for supply and exhaust ducts to the machinery room to serve no other area shall not apply to a change in the type of refrigerant in a lawfully installed existing refrigerating system being maintained and operated in accordance with these approved installation requirements:
1. Where the replacement refrigerant has a safety classification of Group A1; or
2. Where the replacement refrigerant is R123 and the engineer or architect demonstrates to the satisfaction of the commissioner that providing such air supply and exhaust ducts represents a hardship and that the proposed alternative provides an equivalent level of safety.
1105.6.3 Ventilation rate.
For other than ammonia systems, the mechanical ventilation systems shall be capable of exhausting the minimum quantity of air both at normal operating and emergency conditions, as required by Sections 1105.6.3.1 and 1105.6.3.2. The minimum required ventilation rate for ammonia shall be 30 air changes per hour in accordance with IIAR2. Multiple fans or multispeed fans shall be allowed to produce the emergency ventilation rate and to obtain a reduced airflow for normal ventilation.
1105.6.3.1 Quantity-normal ventilation.
During occupied conditions, the mechanical ventilation system shall exhaust the larger of the following:
1. Not less than 0.5 cfm per square foot (0.0025 m 3 /s × m 2 ) of machinery room area or 20 cfm (0.009 m 3 /s) per person.
2. A volume required to limit the room temperature rise to18°F (-7.8°C) taking into account the ambient heating effect of all machinery in the room but not above a maximum temperature of 122°F (50°C).
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1105.6.3.2 Quantity-emergency conditions.
Upon actuation of the refrigerant detector required in Section 1105.3, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity:
Q = 100 x ÖG (Equation 11-2)
For SI: Q = 0.07 x ÖG
Where:
Q = The airflow in cubic feet per minute (m 3 /s).
G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room
1105.7 Termination of relief devices.
In addition to the requirements of Section 9.7.8 of ASHRAE 15, pressure relief devices, fusible plugs and purge systems located within the machinery room shall terminate outside of the structure at a location not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit.
1105.7.1 Discharge of Group A2, B2, A3 and B3 refrigerants.
Discharge of systems containing Group A2 or B2 refrigerants shall be acceptable to the commissioner. Discharge of systems containing Group A3 or B3 refrigerants shall be subject to the approval of the commissioner and the Commissioner of the Fire Department. Nothing in this section shall be construed to approve the use of Group A3 and B3 refrigerants if otherwise prohibited.
1105.7.2 Certificate of qualification.
Discharge of pressure relief devices, fusible plugs and purge systems for refrigerating systems containing flammable, toxic and highly toxic refrigerants and ammonia shall comply with Section 606 of the New York City Fire Code.
1105.8 Ammonia discharge.
Pressure relief valves for ammonia systems shall discharge in accordance with ASHRAE 15.
1105.9 Emergency pressure control system.
Permanently installed refrigeration systems containing more than 6.6 pounds (3 kg) of a refrigerant other than a Group A1 refrigerant shall be provided with an emergency pressure control system in accordance with Sections 1105.9.1 and 1105.9.2.
1105.9.1 Automatic crossover valves.
Each high- and intermediate-pressure zone in a refrigerating system shall be provided with a single automatic valve providing a crossover connection to a lower pressure zone. Such automatic crossover valves shall comply with Sections 1105.9.1.1 through 1105.9.1.3.
1105.9.1.1 Overpressure limit setpoint.
Automatic crossover valves shall be arranged to automatically relieve excess system pressure to a lower pressure zone if the pressure in a high- or intermediate-pressure zone rises to within 15 psi (108.4 kPa) of the setpoint for pressure-relief devices.
1105.9.1.2 Manual operation.
Automatic crossover valves shall be capable of manual operation for refrigerating systems containing more than 200 pounds (90.8 kg) of refrigerant.
1105.9.1.3 System design pressure.
Refrigerating system zones that are connected to a higher pressure zone by an automatic crossover valve shall be designed to safely contain the maximum pressure that can be achieved by interconnection of the two zones.
1105.9.2 Automatic emergency stop.
An automatic emergency stop feature shall be provided in accordance with Sections 1105.9.2.1 and 1105.9.2.2.
1105.9.2.1 Automatic crossover valves.
A refrigerating system equipped with an automatic crossover valve shall be designed, when such valve is activated, to cause all compressors on the affected system to immediately cease operating. Dedicated pressure-sensing devices located immediately adjacent to crossover valves may be used as a means for activating such crossover valve. To ensure that the automatic crossover valve system provides a redundant means of ceasing operation of the compressors in an overpressure condition, high-pressure cutout sensors associated with compressors shall not be used for purposes of activating such crossover valve.
1105.9.2.2 Overpressure in low-pressure zone.
The lowest pressure zone in a refrigerating system shall be provided with a dedicated means of determining a rise in system pressure to within 15 psi (103.4 kPa) of the zone pressure relief device setpoint. Activation of such overpressure sensing device shall cause all compressors on the effected system to immediately cease operation.
1105.10 Remote control.
A clearly identified switch of the break-glass type shall provide off-only control of the compressors in the machinery room. A second clearly identified switch of the break-glass type shall provide on-only control of the machinery room ventilation fans. Such switches shall be located outside each entrance to the machinery room and as close to the entrance as practicable, except that when an outside location is impracticable, such switches may be located immediately inside the machinery room provided such location is accessible at all times.
1105.11 Emergency signs.
Signs shall comply with the following:
1. Sections 8.11.8 and 11.2.4 of ASHRAE 15.
2. Refrigeration units or systems having a refrigerant circuit containing more than 220 pounds (99.8 kg) of Group A1 or 30 pounds (13.6 kg) of any other group refrigerant shall be provided with approved emergency signs, charts, and labels in accordance with NFPA 704.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1105.12 Storing refrigerant.
The total amount of refrigerant stored in a machinery room shall be the lesser of: (i) not more than twenty percent of the normal charge in the system; or (ii) not more than 330 pounds (149.7 kg) in addition to the charge in the system and the refrigerant contained in a permanently attached receiver. Refrigerant shall be stored in containers meeting the requirements of the New York City Fire Code.
Exception: Recovery service containers used for storing refrigerant during periods of system maintenance or replacement may exceed 330 pounds (149.7 kg) provided such containers are securely fixed in position and have pressure relief valves piped to the outside in conformance with this code.
Section MC 1106. Machinery Room, Special Requirements
1106.1 General.
Where required by Section 1104.2, the machinery room shall meet the requirements of this section in addition to the requirements of Section 1105.
1106.2 Elevated temperature.
There shall not be an open flame-producing device or continuously operating hot surface over 800°F (426.7°C) permanently installed in the room.
1106.3 Ammonia room ventilation.
Ventilation systems in ammonia machinery rooms shall be operated continuously at the ventilation rate specified in Section 1105.6.3.
Exceptions:
1. Machinery rooms equipped with a vapor detector that will automatically start the ventilation system at the ventilation rate specified in Section 1105.6.3 and that will actuate an alarm at a detection level not to exceed 1,000 ppm.
2. Machinery rooms conforming to the Class 1, Division 2, hazardous location classification requirements of the New York City Electrical Code.
1106.4 Flammable refrigerants.
Where refrigerants of Groups A2, A3, B2 or B3 are used, the machinery room shall conform to the Class 1, Division 2, hazardous location classification requirements of the New York City Electrical Code.
Exceptions:
1. Ammonia machinery rooms that are provided with ventilation in accordance with Section 1106.3. Nothing in this section shall be construed to approve the use of Group A3 and B3 refrigerants if otherwise prohibited.
2. Machinery rooms for systems containing Group A2L refrigerants that are in accordance with ASHRAE 15.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
1106.5 Remote controls.
Remote control of the mechanical equipment and appliances located in the machinery room shall be provided at an accessible location immediately outside the machinery room and adjacent to its principal entrance and shall comply with Sections 1106.5.1 and 1106.5.2.
1106.5.1 Refrigeration system emergency shutoff.
A clearly identified switch of the break-glass type or an approved tamper-resistant switch shall provide off-only control of refrigerant compressors, refrigerant pumps, and normally closed, automatic refrigerant valves located in the machinery room. Additionally, this equipment shall be automatically shut off whenever the refrigerant vapor concentration in the machinery room exceeds the vapor detector's upper detection limit or 25 percent of the LEL, whichever is lower.
1106.5.2 Ventilation system.
A clearly identified switch of the break-glass type or an approved tamper-resistant switch shall provide on-only control of the machinery room ventilation fans.
1106.6 Reserved.
Section MC 1107. Refrigerant Piping
1107.1 General.
The design of refrigerant piping shall be in accordance with ASME B31.5. Refrigerant piping shall be installed, tested and placed in operation in accordance with this chapter.
1107.1.1 Protection of refrigerant piping located inside buildings.
All refrigerant piping and fittings installed at a height less than 7 feet 3 inches (2209.8 mm) above the floor shall be concealed or otherwise protected from mechanical damage except at the point of connection to terminal equipment.
1107.2 Piping location.
Refrigerant piping that crosses an open space that affords passageway in any building shall be not less than 7 feet 3 inches (2209.8 mm) above the floor unless the piping is located against the ceiling of such space. Refrigerant piping shall not be placed in any elevator, dumbwaiter or other shaft containing a moving object or in any shaft that has openings to living quarters or to means of egress. Refrigerant piping shall not be installed in an enclosed public stairway, stairway landing or an exit.
1107.2.1 Piping in public corridors.
Refrigerant piping shall not be installed in public corridors.
Exception: Refrigerant piping in public corridors that complies with either of the following conditions:
1. Piping containing Group A1 refrigerant may be located in public corridors provided that the complete discharge of any one refrigerant system into the public corridor will not result in a refrigerant density equal to or greater than 50 percent of the allowable density set forth in Table 1103.1; and
1.1. There is not more than one refrigerant system's piping per tenant; and
1.2. Refrigerant piping and fittings are concealed or otherwise protected from mechanical damage; and either
1.3. Refrigerant piping and fittings are installed with brazed joints; or
1.4. The refrigerant equipment manufacturer provided pre-charged tubing systems installed in accordance with the refrigerant equipment manufacturer's instructions;
2. Piping containing Group A1 refrigerant may be located in public corridors provided that the complete discharge of any one refrigerant system into the public corridor will not result in a refrigerant density of 100 percent of the allowable refrigerant density set forth in Table 1103.1; and
2.1. Such system is provided with fast-acting shutoff valves on both high and low pressure refrigerant line sets, actuated by either local refrigerant monitors in the corridor, or on sensing a drop in pressure on either high or low pressure refrigerant line sets; and
2.2. Upon accidental discharge, actuation of installed refrigerant shutoff valves shall initiate locally installed alarm; and
2.3. Installation of fast-acting shutoff valves, refrigerant detectors, and alarms shall be in accordance with Appendix C; and
2.4. There is not more than one refrigerant system's piping per tenant; and
2.5. Refrigerant piping and fittings are concealed or otherwise protected from mechanical damage; and either
2.6. Refrigerant piping and fittings are installed with brazed joints; or
2.7. The refrigerant equipment manufacturer provided pre-charged tubing systems installed in accordance with the refrigerant equipment manufacturer's instructions.
1107.2.2 Piping in concrete floors.
Refrigerant piping installed in concrete floors shall be encased in pipe ducts. The piping shall be isolated and supported to prevent damaging vibration, stress and corrosion.
1107.2.3 Refrigerant piping penetrations.
Refrigerant piping shall not penetrate floors, ceilings or roofs.
Exceptions:
1. Penetrations connecting the basement and the first floor.
2. Penetrations connecting the top floor and a machinery penthouse or roof installation.
3. Penetrations connecting adjacent floors served by the refrigeration system.
4. Penetrations by piping in a direct system where the refrigerant quantity does not exceed Table 1103.1 for the smallest occupied space through which the piping passes.
5. Penetrations by piping in a direct system complying with Section 1107.2.3.1.
6. In other than industrial occupancies and where the refrigerant quantity exceeds Table 1103.1 for the smallest space, penetrations for piping that connects separate pieces of equipment that are either:
6.1. Enclosed by an approved gas-tight, fire- resistive duct or shaft with openings to those floors served by the refrigeration system or
6.2. Located on the exterior of the building where vented to the outdoors or to the space served by the system and not used as an air shaft, closed court or similar space.
1107.2.3.1 Direct systems.
Piping containing a quantity of Group A1 refrigerants in excess of Table 1103.1 for the smallest occupied space through which the piping passes, shall comply with Section 1107.9.
1107.3 Pipe enclosures.
Rigid or flexible metal enclosures or pipe ducts shall be provided for soft, annealed copper tubing used for refrigerant piping erected on the premises and containing other than Group A1 refrigerant. Enclosures shall not be required for connections between condensing units and the nearest riser box(es), provided such connections do not exceed 6 feet (1828.8 mm) in length.
1107.4 Condensation.
Refrigerating piping and fittings, brine piping and fittings that, during normal operation, will reach a surface temperature below the dew point of the surrounding air, and are located in spaces or areas where condensation will cause a safety hazard to the building occupants, structure, electrical equipment or any other equipment or appliances, shall be protected in an approved manner to prevent such damage.
1107.5 Materials for refrigerant pipe and tubing.
Piping materials shall be as set forth in Sections 1107.5.1 through 1107.5.7.
1107.5.1 Steel pipe.
Carbon steel pipe with a wall thickness not less than Schedule 80 shall be used for Group A2, A3, B2 or B3 refrigerant liquid lines for sizes 1.5 inches (38.1 mm) and smaller. Carbon steel pipe with a wall thickness not less than Schedule 40 shall be used for Group A1 or B 1 refrigerant liquid lines 6 inches (152.4 mm) and smaller, Group A2, A3, B2 or B3 refrigerant liquid lines sizes 2 inches (50.8 mm) through 6 inches (152.4 mm) and all refrigerant suction and discharge lines 6 inches (152.4 mm) and smaller. Type F steel pipe shall not be used for refrigerant lines having an operating temperature less than -20°F (-28.9°C).
1107.5.2 Copper and brass pipe.
Standard iron-pipe size, copper and red brass (not less than 80-percent copper) pipe shall conform to ASTM B 42 and ASTM B 43.
1107.5.3 Copper tube.
Copper tube used for refrigerant piping erected on the premises shall be seamless copper tube of Type ACR (hard or annealed) complying with ASTM B 280. Where approved, copper tube for refrigerant piping erected on the premises shall be seamless copper tube of Type K or L (drawn or annealed) in accordance with ASTM B 88. Annealed temper copper tube shall not be used in sizes larger than a 2-inch (50.8 mm) nominal size. Mechanical joints shall not be used on annealed temper copper tube in sizes larger than 7/8-inch (22.2 mm) OD size.
1107.5.4 Copper tubing joints.
Copper tubing joints used in refrigerating systems containing Group A2, A3, B1, B2 or B3 refrigerants shall be brazed. Soldered joints shall not be used in such refrigerating systems. Brazed joints shall be made in accordance with ASME Boiler and Pressure Vessel Code, Section IX Welding and Brazing Qualifications or in accordance with American Welding Society AWS B2.2 Standard for Brazing Procedure and Performance Qualification.
1107.5.5 Soldered joints.
Soldered joints shall be made as follows: soldered joint surfaces shall be cleaned, a flux conforming to ASTM B 813 shall be applied, and the joint shall be soldered with a solder conforming to ASTM B 32.
1107.5.6 Aluminum tube.
Type 3003-0 aluminum tubing with high-pressure fittings shall not be used with methyl chloride and other refrigerants known to deteriorate aluminum.
1107.5.7 Insulation.
Pipe and other refrigerant-containing components' insulation shall meet the requirements of Section 1204.1 of this code.
1107.6 Joints and refrigerant-containing parts in air ducts.
Joints and all refrigerant-containing parts of a refrigerating system located in an air duct of an air-conditioning system carrying conditioned air to and from human-occupied space shall be constructed to withstand, without leakage, a pressure of 150 percent of the higher of the design pressure or pressure relief device setting.
1107.7 Exposure of refrigerant pipe joints.
Refrigerant pipe joints erected on the premises shall be exposed for visual inspection prior to being covered or enclosed.
1107.8 Stop valves.
Systems containing more than 6.6 pounds (3 kg) of a refrigerant in systems using positive-displacement compressors shall have stop valves installed as follows:
1. At the inlet of each compressor, compressor unit or condensing unit.
2. At the discharge outlet of each compressor, compressor unit or condensing unit and of each liquid receiver.
Exceptions:
1. Systems that have a refrigerant pumpout function capable of storing the entire refrigerant charge in a receiver or heat exchanger.
2. Systems that are equipped with provisions for pumpout of the refrigerant using either portable or permanently installed recovery equipment.
3. Self-contained systems.
1107.8.1 Liquid receivers.
Systems containing 100 pounds (45.4 kg) or more of a refrigerant, other than systems utilizing nonpositive displacement compressors, shall have stop valves, in addition to those required by Section 1107.8, on each inlet of each liquid receiver. Stop valves shall not be required on the inlet of a receiver in a condensing unit, nor on the inlet of a receiver which is an integral part of the condenser.
1107.8.2 Copper tubing.
Stop valves used with soft annealed copper tubing or hard-drawn copper tubing 7/8-inch (22.2 mm) OD standard size or smaller shall be securely mounted, independent of tubing fastenings or supports.
1107.8.3 Identification.
Stop valves shall be identified where their intended purpose is not obvious. Numbers shall not be used to label the valves, unless a key to the numbers is located near the valves.
1107.9 Alternative refrigerant piping safety.
Where refrigerant piping penetrates floors, ceilings, or roofs pursuant to Section 1107.2.3, it shall comply with the alternative safety requirements of Sections 1107.9.1 through 1107.9.5.
1107.9.1 Nongas tight enclosures.
Where refrigerant piping and fittings pass through public corridors or occupied spaces in shafts or cavities that are not gas tight, such piping and fittings shall comply with the requirements of EN378 Part 1, Section 3.2.3.
1107.9.2 Occupied spaces.
Refrigerant piping systems in occupied spaces shall comply with the requirements of EN378 Part 1, Section C.3.2.1.
1107.9.2.1 Space volume calculations.
Space volume calculations shall comply with EN378 Part 1, Section 7.
1107.9.2.2 Dilution transfer openings.
Where required, dilution transfer openings shall be provided in accordance with EN378 Part 3, Section 6.3.2.
1107.9.3 Refrigerant shutoff valves.
Where required, refrigerant shutoff valves shall comply with the requirements of EN378 Part 3, Sections 6.4.1 through 6.4.3.
1107.9.4 Refrigerant safety alarms.
Where required, refrigerant safety alarms shall comply with the requirements of EN378 Part 3, Sections 8.1 through 8.2.
1107.9.5 Refrigerant detectors.
Where required, refrigerant detectors shall comply with the requirements of EN378 Part 3, Section 9.3.1.
Section MC 1108. Field Test
1108.1 General.
Every refrigerant-containing part of every system that is erected on the premises, except compressors, condensers, vessels, evaporators, safety devices, pressure gauges and control mechanisms that are listed and factory tested, shall be tested and proved tight after complete installation, and before operation. Tests shall include both the high- and low-pressure sides of each system at not less than the lower of the design pressures or the setting of the pressure relief device(s). The design pressures for testing shall be those listed on the condensing unit, compressor or compressor unit name-plate, as required by ASHRAE 15.
Exceptions:
1. Gas bulk storage tanks that are not permanently connected to a refrigeration system.
2. Systems using an A1 refrigerant erected on the premises with copper tubing not exceeding 5/8-inch (15.8 mm) OD, with wall thickness as required by ASHRAE 15, shall be tested in accordance with Section 1108.1, or by means of refrigerant charged into the system at the saturated vapor pressure of the refrigerant at 70°F (21.1°C) or higher.
3. Limited-charge systems equipped with a pressure relief device, erected on the premises, shall be tested at a pressure not less than one and one-half times the pressure setting of the relief device. If the equipment or appliance has been tested by the manufacturer at one and one-half times the design pressure, the test after erection on the premises shall be conducted at the design pressure.
1108.1.1 Booster compressor.
Where a compressor is used as a booster to obtain an intermediate pressure and discharges into the suction side of another compressor, the booster compressor shall be considered a part of the low side, provided that it is protected by a pressure relief device.
1108.1.2 Centrifugal / nonpositive displacement compressors.
In field-testing systems using centrifugal or other nonpositive displacement compressors, the entire system shall be considered as the low-side pressure for field test purposes.
1108.2 Test gases.
Tests shall be performed with an inert-dried gas including, but not limited to, nitrogen and carbon dioxide. Oxygen, air, flammable gases and mixtures containing such gases shall not be used.
Exceptions:
1. The use of air is allowed to test R-717, ammonia, systems provided that they are subsequently evacuated before charging with refrigerant.
2. Mixtures of dry nitrogen, inert gases, or a combination of them with nonflammable refrigerants in concentrations of a refrigerant weight fraction (mass fraction) not exceeding 5 are allowed for tests.
1108.3 Test apparatus.
The means used to build up the test pressure shall have either a pressure-limiting device or a pressure-reducing device and a gauge on the outlet side.
1108.4 Declaration.
A certificate of test shall be provided for all systems containing 55 pounds (24.9 kg) or more of refrigerant. The certificate shall give the name of the refrigerant and the field test pressure applied to the high side and the low side of the system. The certification of test shall be signed by the installer and shall be made part of the public record.
Section MC 1109. Periodic Testing
1109.1 Testing required.
The following emergency devices and systems shall be periodically tested and the results logged in accordance with the manufacturer's instructions and as required by the Commissioner of the Fire Department:
1. Treatment and flaring systems.
2. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes.
3. Fans and associated equipment intended to operate emergency purge ventilation systems.
4. Detection and alarm systems.
1109.2 Operation.
Operating permits and qualification of operators for refrigeration systems shall comply with the requirements of the New York City Fire Code.
Section MC 1201. General
1201.1 Scope.
The provisions of this chapter shall govern the construction, installation, alteration and repair of hydronic piping systems. This chapter shall apply to hydronic piping systems that are part of heating, ventilation and air-conditioning systems. Such piping systems shall include steam, hot water, chilled water, condenser water, cooling coil condensate drain, steam condensate and ground-source heat pump loop systems. Potable cold and hot water distribution systems shall be installed in accordance with the New York City Plumbing Code.
1201.2 Sizing.
Piping and piping system components for hydronic systems shall be sized for the design requirements of the system.
1201.3 Standards.
As an alternative to the provisions of Sections 1202 and 1203, piping shall be designed, installed, inspected and tested in accordance with ASME B31.1 and ASME B31.9, as applicable.
Section MC 1202. Material
1202.1 Piping.
Piping material, other than those contained within this section and conforming with the ASTM standards listed within this chapter, shall be of an approved type.
Exception: Embedded piping regulated by Section 1209, and ground-source heat pump loop systems regulated by Section 1210.
1202.2 Used existing materials.
Reused pipe, fittings, valves or other materials shall be clean and free of foreign materials.
1202.3 Material rating.
Materials shall be rated for the operating temperature and pressure of the hydronic system. Materials shall be suitable for the type of fluid in the hydronic system.
1202.4 Piping materials standards.
Hydronic pipe shall conform to the standards listed in Table 1202.4. The exterior of the pipe shall be protected from corrosion and degradation.
Table 1202.4 Hydronic Pipe
Material Standard (see Chapter 15) Acrylonitrile butadiene styrene (ABS) plastic pipe ASTM D 1527; ASTM F 2806 Chlorinated polyvinyl chloride (CPVC) plastic pipe ASTM D 2846; ASTM F 441; ASTM F 442 Copper, brass or copper-alloy pipe ASTM B 42; ASTM B 43; ASTM B 302 Copper, brass or copper-alloy tube (Type K, L or M) ASTM B 75; ASTM B 88; ASTM B 135; ASTM B 251 Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe ASTM F 1281;CSA B137.10 Cross-linked polyethylene (PEX) tubing ASTM F 876; ASTM F 877 Ductile iron pipe AWWA C115/A21.15; AWWA C151/A21.51 Polyethylene/aluminum/polyethylene (PE-AL-PE) pressure pipe ASTM F 1282; CSA B137.9 Polypropylene (PP) plastic pipe ASTM F 2389 Polyvinyl chloride (PVC) plastic pipe ASTM D 1785; ASTM D 2241 Raised temperature polyethylene (PE-RT) ASTM F 2623; ASTM F 2769 Steel pipe ASTM A 53 / A 53M; ASTM A 106 Steel tubing ASTM A 254
1202.5 Pipe fittings.
Hydronic pipe fittings shall conform to the respective pipe standards or to the standards listed in Table 1202.5.
Table 1202.5 Hydronic Pipe Fittings
Material Standard (see Chapter 15) Copper, brass, and copper alloys ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.24; ASME B16.26; ASME B16.51; ASTM F 1974 Ductile iron and gray iron ANSI/AWWA C110/A21.10; AWWA C153/A21.53; ASTM A 126; ASTM A 395; ASTM A 536; ASTM F 1476; ASTM F 1548 Malleable iron ASME B16.3 PE-RT fittings ASTM F 1807; ASTM F 2098; ASTM F 2159; ASTM F 2735; ASTM F 2769 PEX fittings ASTM F 877; ASTM F 1807; ASTM F 2159 Plastic ASTM D 2466; ASTM D 2467; ASTM F 438; ASTM F 439; ASTM F 877; ASTM F 2389; ASTM F 2735 Steel ASME B16.5; ASME B16.9; ASME B16.11; ASME B16.28; ASTM A 53/A 53M; ASTM A 106; ASTM A 234; ASTM A 420; ASTM A 536; ASTM A 395; ASTM F 1476; ASTM F 1548
1202.6 Valves.
Valves shall be constructed of materials that are compatible with the type of piping material and fluids in the system. Valves shall be rated for the temperatures and pressures of the systems in which the valves are installed.
1202.7 Flexible connectors, expansion and vibration compensators.
Flexible connectors, expansion and vibration control devices and fittings, when used, shall protect the components of the hydronic system from damage caused by expansion, contraction, transverse movement, angular deflection and vibration, shall be rated for the temperatures and pressures of the systems in which the devices are installed, and shall be compatible with the fluid and all materials provided.
Section MC 1203. Joints and Connections
1203.1 Approval.
Joints and connections, other than those contained in Section 1203 and conforming to the ASTM standards listed in Section 1203, shall be of an approved type. Joints and connections shall be tight for the pressure of the hydronic system.
1203.1.1 Joints between different piping materials.
Joints between different piping materials shall be rated for the temperatures and pressures of the systems in which the devices are installed and shall be compatible with the fluid and all materials provided.
1203.1.2 Joints between dissimilar metallic piping materials.
Joints between dissimilar metallic piping materials shall be provided to protect against galvanic corrosion. Such joints shall be made with dielectric fittings conforming to ANSI B16.39 or ASTM F 492, as applicable, shall be rated for the temperatures and pressures of the systems in which the devices are installed and shall be compatible with the fluid and all materials provided.
Exception: Dielectric fittings shall not be required for joints between dissimilar metal piping used within heat transfer appliances or equipment when such joints are provided by the appliance or equipment manufacturer, and such appliance or equipment is connected with isolation valves that are accessible.
1203.2 Preparation of pipe ends.
Pipe shall be cut square, reamed and chamfered, and shall be free of burrs and obstructions. Pipe ends shall have full-bore openings and shall not be undercut.
1203.3 Joint preparation and installation.
Where required by Sections 1203.4 through 1203.14, the preparation and installation of brazed, mechanical, soldered, solvent-cemented, threaded and welded joints shall comply with Sections 1203.3.1 through 1203.3.8.
1203.3.1 Brazed joints.
All joints shall be brazed with a brazing procedure developed and qualified in accordance with the ASME Boiler and Pressure Vessel Code, Section IX (Welding and Brazing Qualifications) or in accordance with AWS B2.2 standard for Brazing Procedure and Performance Qualification.
1203.3.2 Mechanical joints.
Mechanical joints shall be installed in accordance with the manufacturer's instructions.
1203.3.3 Soldered joints.
Joint surfaces shall be cleaned. A flux conforming to ASTM B 813 shall be applied. The joint shall be soldered with a solder conforming to ASTM B 32.
1203.3.4 Solvent-cemented joints.
Joint surfaces shall be clean and free of moisture. A primer, compatible with both the piping material and the cement shall be applied to pipe-joint surfaces, in accordance with the manufacturer's requirements. Joints shall be made while the cement is wet. Solvent cement conforming to the following standards shall be applied to all joint surfaces:
1. ASTM D 2235 for ABS joints.
2. ASTM F 493 for CPVC joints.
3. ASTM D 2564 for PVC joints.
1203.3.5 Threaded joints.
Threads shall conform to ASME B 1.20.1. Schedule 80 or heavier plastic pipe shall be threaded with dies specifically designed for plastic pipe. Thread lubricant, pipe-joint compound or tape shall be applied on the male threads only and shall be compatible for application on the piping material and fluid.
1203.3.6 Welded joints.
All joints shall be welded with a welding procedure developed and qualified in accordance with the ASME Boiler and Pressure Vessel Code, Section IX (Welding and Brazing Qualifications) or in accordance with AWS B2.1 Specifications for Welding Procedure and Performance Qualification.
1203.3.7 Grooved and shouldered mechanical joints.
Grooved and shouldered mechanical joints shall conform to the requirements of ASTM F 1476 and shall be installed in accordance with the manufacturer's instructions.
1203.3.8 Mechanically formed tee fittings.
Mechanically extracted outlets shall have a height not less than three times the thickness of the branch tube wall.
1203.3.8.1 Full flow assurance.
Branch tubes shall not restrict the flow in the run tube. A dimple/depth stop shall be formed in the branch tube to ensure that penetration into the outlet is of the correct depth. For inspection purposes, a second dimple shall be placed 1/4 inch (6.4 mm) above the first dimple. Dimples shall be aligned with the tube run.
1203.3.8.2 Brazed joints.
Mechanically formed tee fittings shall be brazed in accordance with Section 1203.3.1.
1203.4 ABS plastic pipe.
Joints between ABS plastic pipe or fittings shall be solvent-cemented or threaded joints conforming to Section 1203.3.
1203.5 Brass pipe.
Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints conforming to Section 1203.3.
1203.6 Brass tubing.
Joints between brass tubing or fittings shall be brazed, mechanical or soldered joints conforming to Section 1203.3.
1203.7 Copper or copper-alloy pipe.
Joints between copper or copper-alloy pipe or fittings shall be brazed, mechanical, soldered, threaded or welded joints conforming to Section 1203.3.
1203.8 Copper or copper-alloy tubing.
Joints between copper or copper-alloy tubing or fittings shall be brazed, mechanical or soldered joints conforming to Section 1203.3, flared joints conforming to Section 1203.8.1 or push-fit joints conforming to Section 1203.8.2.
1203.8.1 Flared joints.
Flared joints shall be made by a tool designed for that operation.
1203.8.2 Push-fit joints.
Push-fit joints shall be installed in accordance with the manufacturer's instructions.
1203.9 CPVC plastic pipe.
Joints between CPVC plastic pipe or fittings shall be solvent-cemented or threaded joints conforming to Section 1203.3.
1203.10 Reserved.
1203.11 Cross-linked polyethylene (PEX) plastic tubing.
Joints between cross-linked polyethylene plastic tubing and fittings shall conform to Sections 1203.11.1 and 1203.11.2. Mechanical joints shall conform to Section 1203.3.
1203.11.1 Compression-type fittings.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
1203.11.2 Plastic-to-metal connections.
Soldering on the metal portion of the system shall be performed not less than 18 inches (457.2 mm) from a plastic-to-metal adapter in the same water line.
1203.12 PVC plastic pipe.
Joints between PVC plastic pipe and fittings shall be solvent-cemented or threaded joints conforming to Section 1203.3.
1203.13 Steel pipe.
Joints between steel pipe or fittings shall be mechanical, threaded or welded joints conforming to Section 1203.3.
1203.14 Steel tubing.
Joints between steel tubing or fittings shall be mechanical or welded joints conforming to Section 1203.3.
1203.15 Polypropylene (PP) plastic.
Joints between PP plastic pipe and fittings shall comply with Sections 1203.15.1 and 1203.15.2.
1203.15.1 Heat-fusion joints.
Heat-fusion joints for polypropylene (PP) pipe and tubing joints shall be installed with socket-type heat-fused polypropylene fittings, electro-fusion polypropylene fittings or by butt fusion. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in accordance with ASTM F 2389.
1203.15.2 Mechanical and compression sleeve joints.
Mechanical and compression sleeve joints shall be installed in accordance with the manufacturer's instructions.
1203.16 Raised temperature polyethylene (PE-RT) plastic tubing.
Joints between raised temperature polyethylene tubing and fittings shall conform to Sections 1203.16.1 and 1203.16.2. Mechanical joints shall conform to Section 1203.3.
1203.16.1 Compression-type fittings.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
1203.16.2 PE-RT-to-metal connections.
Solder joints in a metal pipe shall not occur within 18 inches (457.2 mm) of a transition from such metal pipe to PE-RT pipe.
1203.17 Polyethylene/aluminum/polyethylene (PE-AL-PE) pressure pipe.
Joints between polyethylene/aluminum/polyethylene pressure pipe and fittings shall conform to Sections 1203.17.1 and 1203.17.2. Mechanical joints shall comply with Section 1203.3.
1203.17.1 Compression-type fittings.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
1203.17.2 PE-AL-PE-to-metal connections.
Solder joints in a metal pipe shall not occur within 18 inches (457.2 mm) of a transition from such metal pipe to PE-AL-PE pipe.
1203.18 Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe.
Joints between cross-linked polyethylene/aluminum/cross-linked polyethylene pressure pipe and fittings shall conform to Sections 1203.18.1 and 1203.18.2. Mechanical joints shall comply with Section 1203.3.
1203.18.1 Compression-type fittings.
Where compression-type fittings include inserts and ferrules or O-rings, the fittings shall be installed without omitting the inserts and ferrules or O-rings.
1203.18.2 PEX-AL-PEX-to-metal connections.
Solder joints in a metal pipe shall not occur within 18 inches (457.2 mm) of a transition from such metal pipe to PEX-AL-PEX pipe.
Section MC 1204. Pipe Insulation
1204.1 Insulation characteristics.
Pipe insulation installed in buildings shall conform to the requirements of the New York City Energy Conservation Code, shall be tested in accordance with ASTM E 84 or UL 723, using the specimen preparation and mounting procedures of ASTM E 2231; and shall have a maximum flame spread index of 25 and a smoke-developed index not exceeding 450. Insulation installed in an air plenum shall comply with Section 602.2.1.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
1204.2 Required thickness.
Hydronic piping shall be insulated to the thickness required by the New York City Energy Conservation Code.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
Section MC 1205. Valves
1205.1 Where required.
Shutoff valves shall be installed in hydronic piping systems in the locations indicated in Sections 1205.1.1 through 1205.1.6.
1205.1.1 Heat exchangers.
Shutoff valves shall be installed on the supply and return side of a heat exchanger.
Exception: Shutoff valves shall not be required where heat exchangers are integral with a boiler; or are a component of a manufacturer's boiler and heat exchanger packaged unit and are capable of being isolated from the hydronic system by the supply and return valves required by Section 1005.1.
1205.1.2 Central systems.
Shutoff valves shall be installed on the building supply and return of central utility systems, and district heating and cooling systems.
1205.1.3 Pressure vessels.
Shutoff valves shall be installed on the connection to any pressure vessel.
1205.1.4 Pressure-reducing valves.
Shutoff valves shall be installed on both sides of a pressure-reducing valve.
1205.1.5 Equipment and appliances.
Shutoff valves shall be installed on connections to mechanical equipment and appliances. This requirement does not apply to components of a hydronic system such as pumps, air separators, metering devices and similar equipment.
1205.1.6 Expansion tanks.
Lockable shutoff valves shall be installed at connections to all expansion tanks. Valves shall be locked in the open position.
1205.2 Reduced pressure.
A pressure relief valve shall be installed on the low-pressure side of a hydronic piping system that has been reduced in pressure. The relief valve shall be set at the maximum pressure of the system design. The valve shall be installed in accordance with Section 1006.
Section MC 1206. Piping Installation
1206.1 General.
Piping, valves, fittings and connections shall be installed in accordance with the conditions of approval.
1206.2 System drain down.
Hydronic piping systems shall be designed and installed to permit the system to be drained. Where the system drains to the plumbing drainage system, the installation shall conform to the requirements of the New York City Plumbing Code.
Exception: The buried portions of systems embedded underground.
1206.3 Protection of potable water.
The potable water system shall be protected from backflow in accordance with the New York City Plumbing Code.
1206.4 Pipe penetrations.
Openings for pipe penetrations in walls, floors or ceilings shall be larger than the penetrating pipe. Openings through concrete or masonry building elements shall be sleeved. The annular space surrounding pipe penetrations shall be protected in accordance with the New York City Building Code.
1206.5 Clearance to combustibles.
A pipe in a hydronic piping system in which the exterior temperature exceeds 250°F (121.1°C) shall have a minimum clearance of 1 inch (25.4 mm) to combustible materials.
1206.6 Contact with building material.
A hydronic piping system shall not be in direct contact with building materials that cause the piping material to degrade or corrode, or that interfere with the operation of the system.
1206.7 Water hammer.
The flow velocity of the hydronic piping system shall be controlled to reduce the possibility of water hammer. Where a quick-closing valve creates water hammer, an engineered water-hammer arrestor shall be installed. The arrestor shall be located within a range as specified by the manufacturer of the quick-closing valve.
1206.8 Steam piping pitch.
Steam piping shall be installed to drain to the boiler or the steam trap. Steam systems shall not have drip pockets that reduce the capacity of the steam piping.
1206.9 Strains and stresses.
Piping shall be installed so as to prevent detrimental strains and stresses in the pipe. Provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement. Piping shall be installed so as to avoid structural stresses or strains within building components.
1206.9.1 Flood hazard.
Piping located in flood hazard areas shall comply with Appendix G of the New York City Building Code.
1206.10 Pipe support.
Pipe shall be supported in accordance with Section 305. Seismic supports shall be provided where required by the New York City Building Code.
1206.11 Condensation.
Provisions shall be made to prevent the formation of condensation on the exterior of piping.
Section MC 1207. Transfer Fluid
1207.1 Flash point.
The flash point of transfer fluid in a hydronic piping system shall be not less than 50°F (10°C) above the maximum system operating temperature.
1207.2 Makeup water.
The transfer fluid shall be compatible with the makeup water supplied to the system.
Section MC 1208. Tests
1208.1 General.
Hydronic piping systems other than ground-source heat pump loop systems shall be tested hydrostatically at one and one half times the system design operating pressure, but not less than 100 psi (689 kPa). The duration of each test shall be not less than 2 hours. Ground-source heat pump loop systems shall be tested in accordance with Section 1210.10.
Section MC 1209. Embedded Piping
1209.1 Materials.
Embedded piping shall be plastic pipe or tubing, in accordance with Section 1202, rated at 100 psi (689.5 kPa) at 180°F (82.2°C).
1209.2 Pressurizing during installation.
Piping to be embedded in concrete shall be pressure tested prior to pouring concrete. During pouring, the pipe shall be maintained at the proposed operating pressure.
1209.3 Embedded joints.
Joints of pipe or tubing that are embedded in a portion of the building, such as concrete or plaster, shall be thermally-fused.
1209.4 Not embedded related piping.
Joints of other piping in cavities or running exposed shall be joined in accordance with manufacturer's instructions and related sections of this code.
1209.5 Thermal barrier required.
Radiant floor heating systems shall be provided with a thermal barrier in accordance with Sections 1209.5.1 through 1209.5.4.
Exception: Insulation shall not be required in engineered systems where it can be demonstrated that the insulation will decrease the efficiency or have a negative effect on the installation.
1209.5.1 Slab-on-grade installation.
Radiant piping utilized in slab-on-grade applications shall be provided with insulating materials installed beneath the piping having a minimum R-value of 5.
1209.5.2 Suspended floor installation.
In suspended floor applications, insulation shall be installed in the joist bay cavity serving the heating space above and shall consist of materials having a minimum R-value of 11.
1209.5.3 Thermal break required.
A thermal break shall be provided consisting of asphalt expansion joint materials or similar insulating materials at a point where a heated slab meets a foundation wall or other conductive slab.
1209.5.4 Thermal barrier material marking.
Insulating materials utilized in thermal barriers shall be installed such that the manufacturer's R-value mark is readily observable upon inspection.