NYC Administrative Code Title 28, Chapter 9 New York City Fuel Gas Code, part 1 of 4
§ 28-901.1 to Section FGC 401: 24 sections.
§ 28-901.1. Update
No later than the third year after the effective date of this section 28-901.1 and every third year thereafter, the commissioner shall submit to the city council proposed amendments that he or she determines should be made to this code to bring it up to date with the latest edition of the International Fuel Gas Code or otherwise modify the provisions thereof. In addition, prior to the submission of such proposal to the city council, such proposal shall be submitted to an advisory committee established by the commissioner pursuant to this title for review and comment.
§ 28-901.2. Enactment of the New York City Fuel Gas Code
The New York city fuel gas code based on the 2009 edition of the International Fuel Gas Code published by the International Code Council, with changes that reflect the unique character of the city and amendments that bring it up to date with the 2015 edition of such International Fuel Gas Code, is hereby adopted to read as follows:
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
Section FGC 101. General
101.1 Title.
This code shall be known and may be cited as the "New York City Fuel Gas Code," "NYCFGC" or "FGC". All section numbers in this code shall be deemed to be preceded by the designation "FGC".
101.2 Scope.
This code shall apply to the installation of fuel-gas piping systems, fuel-gas appliances and related accessories in accordance with Sections 101.2.2 through 101.2.5.
101.2.1 Reserved.
101.2.2 Piping systems.
These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig (103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of the appliance shutoff valves. Piping system requirements shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance.
101.2.3 Gas utilization appliances.
Requirements for gas appliances and related accessories shall include installation, combustion and ventilation air and venting and connections to piping systems.
101.2.4 Systems and equipment outside the scope.
This code shall not apply to the following:
1. Portable LP-gas appliances and equipment of all types that are not connected to a fixed fuel piping system.
2. Oxygen-fuel gas cutting and welding systems.
3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen and nitrogen.
4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants.
5. Integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by, or used in, chemical reactions.
6. LP-gas installations at utility gas plants.
7. Liquefied natural gas (LNG) installations.
8. Fuel gas piping in public utility power plants and atomic energy plants.
9. Components within proprietary items of equipment, apparatus or instruments such as gas-generating sets, compressors and calorimeters.
10. LP-gas equipment for vaporization, gas mixing and gas manufacturing.
11. Temporary LP-gas piping for buildings under construction or renovation that is not to become part of the permanent piping system.
12. Installation of LP-gas systems for railroad switch heating.
13. Installation of hydrogen gas, LP-gas and compressed natural gas (CNG) systems on vehicles.
14. Except as provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP-gas.
15. Building design and construction, except as specified herein.
16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig (68.9 kPa gauge).
17. Portable fuel cell appliances that are neither connected to a fixed piping system nor interconnected to a power grid.
101.2.5 Other fuels.
The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code.
101.3 Reserved.
101.4 Intent.
The purpose of this code is to provide minimum standards to safeguard life or limb, health, property, public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2010/049.
101.5 Severability.
If a section, subsection, sentence, clause or phrase of this code is, for any reason, held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this code.
Section FGC 102. Applicability
102.1 General.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.
102.2 Existing installations.
Except as otherwise provided for in this chapter or elsewhere in this code, a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existing installations lawfully in existence on the effective date of this code.
102.2.1 Existing buildings.
Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code, the New York City Building Code and the 1968 Building Code, as applicable.
102.3 Maintenance.
Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards that are required by this code shall be maintained in compliance with the applicable provisions under which they were installed.
102.3.1 Owner responsibility.
The owner or the owner's designated agent shall be responsible for maintenance of installations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected.
102.4 Additions, alterations or repairs.
Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded.
102.4.1 Minor additions, alterations, renovations and repairs.
Minor additions, alterations, renovations and repairs to existing installations shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.
102.4.2 Special provisions for prior code buildings.
In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings.
102.4.2.1 Fuel gas piping in prohibited locations.
For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner.
102.4.2.2 Guards and access to roofs and elevated structures.
The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location.
102.4.2.3 Seismic supports.
For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. Any applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9-6 of such code.
102.4.2.4 Wind resistance.
For prior code buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code.
102.5 Change in occupancy.
Refer to Chapter 1 of Title 28 of the Administrative Code.
102.6 Reserved.
102.7 Reserved.
102.8 Referenced standards.
The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards.
102.8.1 Editions of referenced standards.
References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule.
102.9 Requirements not covered by code.
Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner.
102.10 Application of references.
Reference to chapter section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
Section FGC 103. Department of Buildings
103.1 Enforcement agency.
Refer to the New York City Charter and Chapter 1 of Title 28 of the Administrative Code.
103.2 Reserved.
103.3 Reserved.
103.4 Reserved.
Section FGC 104. Duties and Powers of the Commissioner of Buildings
104.1 General.
The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies, procedures, and rules shall be in compliance with the intent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of the commissioner.
Section FGC 105. Approvals
105.1 Approvals.
Refer to Chapter 1 of Title 28 of the Administrative Code.
Section FGC 106. Permits
106.1 General.
Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code, and with requirements found elsewhere in this code.
106.2 Required.
Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, mechanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit.
106.3 Work exempt from permit.
Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or rules.
106.4 Validity of permit.
The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of errors in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other law.
106.5 Other permits.
In addition to any permits required by the provisions of this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation.
106.6 Permits with respect to limited alteration applications.
For permits with respect to limited alteration applications, refer to Sections 28-101.5 and 28-104.6, Exception 1, of the Administrative Code.
Section FGC 107. Construction Documents
107.1 General.
Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans.
107.2 Required documents.
The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrigeration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code.
107.2.1 Composite plans.
Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired.
107.3 Lot diagram.
The lot diagram shall be provided where applicable to the work proposed, including but not limited to the installation of exterior or rooftop equipment.
107.4 Building classification statement.
Where applicable to the proposed work, the statement shall identify:
1. The occupancy group or groups that apply to parts of the building in accordance with Section 302 of the New York City Building Code;
2. The occupancy group of the main use or dominant occupancy of the building;
3. The construction type of the building in accordance with Section 602 of the New York City Building Code;
4. The structural occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code;
5. The height of the building as defined in Section 202 of the New York City Building Code;
6. The applicable measurements to the highest and lowest level of Fire Department access;
7. Whether the building is inside or outside of the fire districts; and
8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapter 2 of the New York City Building Code.
107.5 Fuel-gas-burning appliance and fuel-gas piping plans.
Construction documents for fuel-gas-burning appliances and fuel-gas piping shall contain plans that include the following data and information:
1. Riser diagrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appliances.
2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances.
3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel-gas burning appliances, gas vents, and chimneys, with the riser numbers coordinated with other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut-off required by Appendix E, Section E.6. The plans shall also indicate the method or means of providing air to the appliance space, including duct and opening sizes, or means of direct venting.
4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire-extinguishing systems.
5. Seismic protection and restraint details for piping and appliances as required by Chapter 16 of the New York City Building Code.
6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and the clearances from combustible walls, partitions and ceiling; and the fire-resistive ratings of rooms and spaces containing the appliances.
7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and structures for chimneys and gas vents.
8. Details showing structural supports for fuel-gas-burning equipment where required.
9. In flood hazard areas, construction documents shall comply with Appendix G of the New York City Building Code.
107.6 Heating systems.
Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source.
107.7 Boilers.
Construction documents for boiler installations shall indicate the output capacity in BTU per hour (W), the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required by this code.
107.8 Energy efficiency.
Construction documents shall include compliance documentation as required by the New York City Energy Conservation Code.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
107.9 Retention of construction and submittal documents.
Refer to Section 28-104.12 of the Administrative Code.
Section FGC 108. Inspections and Testing
108.1 General.
Except as otherwise specified in Section 28-116.2.4.3 of the Administrative Code, inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such inspections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be required:
108.2 Required inspections and testing.
In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be required:
1. Progress inspections:
1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti-corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling.
1.2. Rough-in inspection shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be concealed are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections.
Exceptions:
1. A rough-in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve.
2. A rough-in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28-105.4.1 of the Administrative Code.
1.3 Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable.
1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspections shall include, but not be limited to, an inspection of components downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections.
2. Special inspections. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code.
3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code.
4. Final inspection. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code.
5. Issuance of certificate of compliance. Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign-off, the department shall issue a certificate of compliance as applicable for the following service equipment:
5.1. Fuel-gas-burning equipment,
5.2. Heating systems, and
5.3. Boilers.
The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure.
108.2.1 Approved inspection agencies.
Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code.
108.2.2 Inspection of prefabricated construction assemblies.
Prior to the approval of a prefabricated construction assembly having concealed work and the issuance of a permit, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basis upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code.
108.2.2.1 Test and inspection records.
Required test and inspection records shall be available to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed.
108.2.3 Exposure of work.
The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection.
108.3 Testing.
Installations shall be tested as required in this code and in accordance with Sections 108.3.1 through 108.3.3. Tests shall be made by the permit holder and witnessed by the department.
108.3.1 New, altered, extended or repaired installations.
New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects.
Exceptions:
1. A gas test shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve.
2. A gas test shall not be required when gas is reestablished by a utility company as permitted under section 28-105.4.1 of the Administrative Code.
108.3.2 Apparatus, instruments, material and labor for tests.
Apparatus, instruments, material and labor required for testing an installation or part thereof shall be furnished by the permit holder.
108.3.3 Reinspection and testing.
Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made to comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing.
108.3.4 Test validity.
A gas test that is accepted by the department shall be valid for a period of one year from the date of the test.
108.4 Sign-off of completed work.
Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code.
108.5 Temporary connection.
The commissioner shall have the authority to allow the temporary connection of an installation to the sources of energy for the purpose of testing the installation or for use under a temporary certificate of occupancy.
Section FGC 109. Violations
109.1 General.
Refer to Chapters 2 and 3 of Title 28 of the Administrative Code.
109.2 Authority to disconnect service utilities.
The commissioner shall have the authority to require disconnection of utility service to the building, structure or system regulated by the technical codes in case of emergency where necessary to eliminate an immediate hazard to life or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure or service system of the decision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as practicable thereafter.
109.3 Connection after order to disconnect.
A person shall not make energy source connections to installations regulated by this code that have been disconnected or ordered to be disconnected by the commissioner, or the use of which has been ordered to be discontinued by the commissioner until the commissioner authorizes the reconnection and use of such installations. When an installation is maintained in violation of this code, and in violation of a notice issued pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation.
Section FGC 201. General
201.1 Scope.
Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code and standard, have the meanings indicated in this chapter.
201.2 Interchangeability.
Words used in the present tense include the future; words in the masculine gender include the feminine and neuter; the singular number includes the plural and the plural, the singular.
201.3 Terms defined in other codes.
Where terms are not defined in this code and are defined in the New York City Electrical Code, New York City Building Code, New York City Fire Code, New York City Mechanical Code, New York City Plumbing Code, or the New York City Energy Conservation Code, such terms shall have meanings ascribed to them as in those codes.
201.3.1 Terms defined in the general administrative provisions.
The following terms are defined in Section 28-101.5 of the Administrative Code:
1968 BUILDING CODE.
1968 OR PRIOR CODE BUILDINGS OR STRUCTURES (PRIOR CODE BUILDINGS).
ACCEPTANCE OR ACCEPTED.
ADDITION.
ADMINISTRATIVE CODE.
ALTERATION.
APPROVAL OR APPROVED.
APPROVED AGENCY.
APPROVED FABRICATOR.
APPROVED INSPECTION AGENCY.
APPROVED TESTING AGENCY.
ARCHITECT.
BUILDING.
CERTIFICATE OF COMPLIANCE.
CHARTER.
CITY.
COMMISSIONER.
CONSTRUCTION DOCUMENTS.
DAY.
DEFERRED SUBMITTAL.
DEMOLITION.
DEMOLITION, FULL.
DEMOLITION, PARTIAL.
DEPARTMENT.
ENGINEER.
ENLARGEMENT.
ENVIRONMENTAL CONTROL BOARD or ECB.
EXISTING BUILDING OR STRUCTURE.
FABRICATED ITEM.
FIRE PROTECTION PLAN.
HEREAFTER.
HERETOFORE.
INSPECTION CERTIFICATE.
INTERIM CERTIFICATE OF OCCUPANCY.
LABEL.
LABELED.
LAND SURVEYOR.
LANDSCAPE ARCHITECT.
LETTER OF COMPLETION.
LIMITED ALTERATION APPLICATION.
LIMITED PLUMBING ALTERATIONS.
LIMITED SPRINKLER ALTERATIONS.
LIMITED STANDPIPE ALTERATIONS.
LISTED.
MAIN USE OR DOMINANT OCCUPANCY (OF A BUILDING).
MANUFACTURER'S DESIGNATION.
MARK.
MATERIALS.
OCCUPANCY.
OWNER.
PARTY WALL.
PERMIT.
PERSON.
PREMISES.
PRIOR CODE BUILDING.
PROFESSIONAL CERTIFICATION.
PROGRESS INSPECTION.
PROJECT.
REGISTERED DESIGN PROFESSIONAL.
REGISTERED DESIGN PROFESSIONAL OF RECORD.
REQUIRED.
RETAINING WALL.
SERVICE EQUIPMENT.
SIGN-OFF.
SINGLE ROOM OCCUPANCY MULTIPLE DWELLING.
SPECIAL INSPECTION.
SPECIAL INSPECTION AGENCY.
SPECIAL INSPECTOR.
STRUCTURE.
SUBMITTAL DOCUMENTS.
SUPERINTENDENT OF CONSTRUCTION (CONSTRUCTION SUPERINTENDENT).
USE (USED).
UTILITY COMPANY OR PUBLIC UTILITY COMPANY.
UTILITY CORPORATION OR PUBLIC UTILITY CORPORATION.
WORK NOT CONSTITUTING MINOR ALTERATIONS OR ORDINARY REPAIRS.
WRITING (WRITTEN).
WRITTEN NOTICE.
ZONING RESOLUTION.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
201.4 Terms not defined.
Where terms are not defined through the methods authorized by this section, such terms shall have ordinarily accepted meanings such as the context implies.
Section FGC 202. General Definitions
ABNORMAL OPERATING CONDITION. A condition that may indicate a malfunction or a noncompliant component of a piping system or appliance.
ACCESS (TO). That which enables a device, fixture, appliance or equipment to be reached by ready access or by a means that first requires the removal or movement of a panel, door or similar obstruction (see also "Ready access").
AIR CONDITIONER, GAS-FIRED. A gas-burning, automatically operated appliance for supplying cooled or dehumidified air or chilled liquid.
AIR CONDITIONING. The treatment of air so as to control simultaneously the temperature, humidity, cleanness and distribution of the air to meet the requirements of a conditioned space.
AIR, EXHAUST. See "Exhaust."
AIR-HANDLING UNIT. A blower or fan used for the purpose of distributing supply air to a room, space or area.
AIR, MAKEUP. Any combination of outdoor and transfer air intended to replace exhaust air and exfiltration.
APPLIANCE. Any apparatus or device that utilizes a fuel or raw material to produce light, heat, power, refrigeration or air conditioning.
APPLIANCE, AUTOMATICALLY CONTROLLED. Appliances equipped with an automatic burner ignition and safety shutoff device and other automatic devices which accomplish complete turn-on and shutoff of the gas to the main burner or burners, and graduate the gas supply to the burner or burners, but do not affect complete shutoff of the gas.
APPLIANCE TYPE.
Low-heat appliance (residential appliance). Any appliance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of 1,000°F (538°C) or less.
Medium-heat appliance. Any appliance in which the products of combustion at the point of entrance to the flue under normal operating conditions have a temperature of more than 1,000°F (538°C), but not greater than 2,000°F (1093.3°C).
APPLIANCE, UNVENTED. An appliance designed or installed in such a manner that the products of combustion are not conveyed by a vent or chimney directly to the outdoor atmosphere.
APPLIANCE, VENTED. An appliance designed and installed in such a manner that all of the products of combustion are conveyed directly from the appliance to the outdoor atmosphere through an approved chimney or vent system. See also "VENTED APPLIANCE CATEGORIES."
ATMOSPHERIC PRESSURE. The pressure of the weight of air and water vapor on the surface of the earth, approximately 14.7 pounds per square inch (psi) (101 kPa absolute) at sea level.
BAFFLE. An object placed in an appliance to change the direction of or retard the flow of air, air-gas mixtures or flue gases.
BAROMETRIC DRAFT REGULATOR. A balanced damper device attached to a chimney, vent connector, breeching or flue gas manifold to protect combustion appliances by controlling chimney draft. A double-acting barometric draft regulator is one in which the balancing damper is free to move in either direction to protect combustion appliances from both excessive draft and backdraft.
BOILER, HIGH-PRESSURE. An appliance for supplying steam or hot water that, for a steam boiler, operates at a pressure of more than 15 psig (103.4 kPa gauge), and for a hot water boiler, operates at a pressure exceeding 160 psig (1103 kPa gauge) or at a temperature exceeding 250°F (121.1°C).
BOILER, LOW-PRESSURE. A self-contained appliance for supplying steam or hot water as follows:
Hot water heating boiler. A boiler in which no steam is generated, from which hot water is circulated for heating purposes and then returned to the boiler, and that operates at water pressures not exceeding 160 pounds per square inch gauge (psig) (1103 kPa gauge) and at water temperatures not exceeding 250°F (121.1°C) at or near the boiler outlet.
Hot water supply boiler. A boiler, completely filled with water, which furnishes hot water to be used externally to itself, and that operates at water pressures not exceeding 160 psig (1103 kPa gauge) and at water temperatures not exceeding 250°F (121.1°C) at or near the boiler outlet.
Steam heating boiler. A boiler in which steam is generated and that operates at a steam pressure not exceeding 15 psig (103.4 kPa gauge).
BRANCH. A section of gas piping downstream from a riser, leading to appliances or equipment on no more than two consecutive floors.
BRAZING. A metal-joining process wherein coalescence is produced by the use of a nonferrous filler metal having a melting point above 1,000°F (537.8°C), but lower than that of the base metal being joined. The filler material is distributed between the closely fitted surfaces of the joint by capillary action.
BROILER. A general term including salamanders, barbecues and other appliances cooking primarily by radiated heat, excepting toasters.
BTU. Abbreviation for British Thermal Unit, which is the quantity of heat required to raise the temperature of 1 pound (454 g) of water 1°F (-17.2°C) (1 Btu = 1055 J).
BURNER. A device for the final conveyance of the gas, or a mixture of gas and air, to the combustion zone.
Induced draft. A burner that depends on draft induced by a fan that is an integral part of the appliance and is located downstream from the burner.
Power. A burner in which gas, air or both are supplied at pressures exceeding, for gas, the line pressure, and for air, atmospheric pressure, with this added pressure being applied at the burner.
CHIMNEY. A primarily vertical structure containing one or more flues used to remove hot gases from burning fuel, refuse, or industrial processes from a fuel-burning appliance to the outdoor atmosphere.
Factory-built chimney. A listed and labeled chimney composed of factory-made components, assembled in the field in accordance with manufacturer's instructions and the conditions of the listing.
Masonry chimney. A field-constructed chimney composed of solid masonry units, bricks, stones or concrete.
Metal chimney. A field-constructed chimney composed of metal.
CLEARANCE. The minimum distance through air measured between the heat-producing surface of the mechanical appliance, device or equipment and the surface of the combustible material or assembly.
CLOTHES DRYER. An appliance used to dry wet laundry by means of heated air. Dryer classifications are as follows:
Type 1. Factory-built package, multiple production. Primarily used in family living environment. Usually the smallest unit physically and in function output.
Type 2. Factory-built package, multiple production. Used in business with direct intercourse of the function with the public. Not designed for use in individual family living environment.
COMBUSTIBLE ASSEMBLY. Wall, floor, ceiling or other assembly constructed of one or more component materials that are not defined as noncombustible.
COMBUSTIBLE MATERIAL. Any material not defined as noncombustible.
COMBUSTION. In the context of this code, refers to the rapid oxidation of fuel accompanied by the production of heat or heat and light.
COMBUSTION AIR. Air necessary for complete combustion of a fuel, including theoretical air and excess air.
COMBUSTION CHAMBER. The portion of an appliance within which combustion occurs.
COMBUSTION PRODUCTS. Constituents resulting from the combustion of a fuel with the oxygen of the air, including inert gases, but excluding excess air.
CONCEALED LOCATION. A location that cannot be accessed without damaging permanent parts of the building structure or finished surface. Spaces above, below or behind readily removable panels or doors shall not be considered as concealed.
CONCEALED PIPING. Piping that is located in a concealed location (see "Concealed location").
CONDENSATE. The liquid that condenses from a gas (including flue gas) caused by a reduction in temperature or increase in pressure.
CONNECTOR, APPLIANCE (Fuel). Rigid metallic pipe and fittings or a listed and labeled device that connects an appliance to the gas piping system.
CONNECTOR, CHIMNEY OR VENT. The pipe that connects an appliance to a chimney or vent.
CONTROL. A manual or automatic device designed to regulate the gas, air, water or electrical supply to, or operation of, a mechanical system.
CONVERSION BURNER. A unit consisting of a burner and its controls for installation in an appliance originally utilizing another fuel.
COUNTER APPLIANCES. Appliances such as coffee brewers and coffee urns and any appurtenant water-heating appliance, food and dish warmers, hot plates, griddles, waffle bakers and other appliances designed for installation on or in a counter.
CUBIC FOOT. The amount of gas that occupies 1 cubic foot (0.02832 m 3 ) when at a temperature of 60°F (15.6°C), saturated with water vapor and under a pressure equivalent to that of 30 inches of mercury (101 kPa).
DAMPER. A manually or automatically controlled device to regulate draft or the rate of flow of air or combustion gases.
DECORATIVE APPLIANCE, VENTED. A vented appliance wherein the primary function lies in the aesthetic effect of the flames.
DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES. A vented appliance designed for installation within the fire chamber of a vented fireplace, wherein the primary function lies in the aesthetic effect of the flames.
DECORATIVE SHROUD. A listed, partial, non-combustible enclosure for aesthetic purposes that is installed at the termination of a venting system that surrounds or conceals a factory-built chimney system or vent cap.
DEMAND. The maximum amount of gas input required per unit of time, usually expressed in cubic feet per hour (1 ft 3 = 0.0283 m 3 ), or Btu/h (1 Btu/h = 0.293 1 W).
DILUTION AIR. Air that is introduced into a draft hood and is mixed with the flue gases.
DIRECT-VENT APPLIANCES. Appliances that are constructed and installed so that all air for combustion is derived directly from the outdoor atmosphere and all flue gases are discharged directly to the outdoor atmosphere.
DRAFT. The pressure difference existing between the appliance or any component part and the atmosphere, that causes a continuous flow of air and products of combustion through the gas passages of the appliance to the atmosphere.
Induced draft. The pressure difference created by the action of a fan, blower or ejector, that is located between the appliance and the chimney or vent termination.
Natural draft. The pressure difference created by a vent or chimney because of its height, and the temperature difference between the flue gases and the atmosphere.
DRAFT HOOD. A nonadjustable device built into an appliance, or made as part of the vent connector from an appliance, that is designed to (1) provide for ready escape of the flue gases from the appliance in the event of no draft, backdraft or stoppage beyond the draft hood, (2) prevent a backdraft from entering the appliance, and (3) neutralize the effect of stack action of the chimney or gas vent upon operation of the appliance.
DRAFT REGULATOR. A device that functions to maintain a desired draft in the appliance by automatically reducing the draft to the desired value.
DRIP. A nipple and cap placed at a lowpoint in a system of piping to collect condensate and from which the condensate is removable.
DRY GAS. A gas having a moisture and hydrocarbon dew point below any normal temperature to which the gas piping is exposed.
DUCT FURNACE. A warm-air furnace or heater normally installed in an air distribution duct to supply warm air for heating. This definition shall apply only to a warm-air heating appliance that, for air circulation, depends on a blower not furnished as part of the furnace.
DUCT SYSTEM. A continuous passageway for the transmission air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment and appliances.
DWELLING. A building or structure which is occupied in whole or in part as the home, residence or sleeping place of one or more families.
DWELLING UNIT. A single unit consisting of one or more habitable rooms and occupied or arranged to be occupied as a unit separate from all other units within a dwelling.
EQUIPMENT. Any apparatus or device that delivers gas as a fuel or raw material to an appliance or vents combustion products from an appliance, including but not limited to control devices, pressure regulators, valves, appliance appurtenances, gas connectors, or power exhausters used in connections to appliances.
EXCESS FLOW VALVE (EFV). A safety shut-off valve designed to activate to interrupt the flow of gas when the fuel gas passing through it exceeds a prescribed flow rate. Installed where specifically required by code or utility company.
EXHAUST. Air being removed from any space, appliance or piece of equipment conveyed directly to the atmosphere by means of openings or ducts.
EXTERIOR MASONRY CHIMNEYS. Masonry chimneys exposed to the outdoors on one or more sides below the roof line.
FIREPLACE. An assembly consisting of a hearth and fire chamber of noncombustible material and provided with a chimney, for use with solid fuels.
Factory-built fireplace. A listed and labeled fireplace and chimney system composed of factory-made components, and assembled in the field in accordance with manufacturer's instructions and the conditions of the listing.
Masonry fireplace. A hearth and fire chamber of solid masonry units such as bricks, stones, listed masonry units or reinforced concrete, provided with a suitable chimney.
FLAME SAFEGUARD. A device that will automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative, and when flame failure occurs on the burner or group of burners.
FLASHBACK ARRESTOR CHECK VALVE. A device that will prevent the backflow of one gas into the supply system of another gas and prevent the passage of flame into the gas supply system.
FLOOR FURNACE. A completely self-contained furnace suspended from the floor of the space being heated, taking air for combustion from outside such space and with means for observing flames and lighting the appliance from such space.
Fan type. A floor furnace equipped with a fan that provides the primary means for circulating air.
Gravity type. A floor furnace depending primarily upon circulation of air by gravity. This classification shall also include floor furnaces equipped with booster-type fans that do not materially restrict free circulation of air by gravity flow when such fans are not in operation.
FLUE. A passageway within a chimney or vent through which gaseous combustion products pass.
FLUE, APPLIANCE. The passage(s) within an appliance through which combustion products pass from the combustion chamber of the appliance to the draft hood inlet opening on an appliance equipped with a draft hood or to the outlet of the appliance on an appliance not equipped with a draft hood.
FLUE COLLAR. That portion of an appliance designed for the attachment of a draft hood, vent connector or venting system.
FLUE GASES. Products of combustion plus excess air in fireplace and appliance flues or heat exchangers.
FLUE LINER (LINING). A system or material used to form the inside surface of a flue in a chimney or vent, for the purpose of protecting the surrounding structure from the effects of combustion products and for conveying combustion products without leakage into the atmosphere.
FUEL GAS. A natural gas, manufactured gas, liquefied petroleum gas or mixtures of these gases.
FURNACE. A completely self-contained heating unit that is designed to supply heated air to spaces remote from or adjacent to the appliance location.
FURNACE, CENTRAL. A self-contained appliance for heating air by transfer of heat of combustion through metal to the air, and designed to supply heated air through ducts to spaces remote from or adjacent to the appliance location.
Forced-air type. A central furnace equipped with a fan or blower that provides the primary means for circulation of air.
FURNACE PLENUM. An air compartment or chamber to which one or more ducts are connected and that forms part of an air distribution system.
GAS CONVENIENCE OUTLET. A permanently mounted, manually operated device that provides the means for connecting an appliance to, and disconnecting an appliance from, the supply piping. The device includes an integral, manually operated valve with a nondisplaceable valve member and is designed so that disconnection of an appliance only occurs when the manually operated valve is in the closed position.
GAS PIPING. An installation of pipe, valves or fittings installed on a premises or in a building and utilized to convey fuel gas.
GAS UTILIZATION EQUIPMENT. An appliance that utilizes gas as a fuel or raw material or both.
HAZARDOUS LOCATION. Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances. The location is not necessarily categorized in the New York City Building Code as a high-hazard group classification.
HOUSE PIPING. See "Piping system."
HYDROGEN FUEL GAS ROOM. A separately ventilated, fully enclosed room designed to exclusively house the generation of gaseous hydrogen for immediate on-premises use in indoor fuel cells or other energy production process, and incidental indoor storage of gaseous hydrogen. A hydrogen fuel gas room is not intended to house the production or dispensing of hydrogen motor fuel.
IGNITION SOURCE. A flame, spark or hot surface capable of igniting flammable vapors or fumes. Such sources include appliance burners, burner ignitors, and electrical switching devices.
INCINERATOR. An appliance used to reduce combustible refuse material to ashes and that is manufactured, sold and installed as a complete unit.
INDUSTRIAL AIR HEATERS, NONRECIRCULATING DIRECT-FIRED. A heater in which all the products of combustion generated by the burners are released into the air stream being heated. The purpose of the heater is to offset building heat loss by heating only outdoor air.
INDUSTRIAL AIR HEATERS, RECIRCULATING DIRECT-FIRED. A heater in which all the products of combustion generated by the burners are released into the air stream being heated. The purpose of the heater is to offset building heat loss by heating outdoor air, and, if applicable, indoor air.
INFRARED RADIANT HEATER. A heater that directs a substantial amount of its energy output in the form of infrared radiant energy into the area to be heated. Such heaters are of either the vented or unvented type.
INTEGRAL VENT APPLIANCES. Appliances designed for outdoor installation that have built-in natural or mechanical venting means and are constructed and installed so that all air for combustion is derived from the outdoor atmosphere and all flue gases are discharged to the outdoor atmosphere through an integral vent termination.
INTERLOCK. A device actuated by another device with which it is directly associated, to govern succeeding operations of the same or allied devices. A circuit in which a given action cannot occur until after one or more other actions have taken place.
JOINT, FLANGED. A joint made by bolting together a pair of flanged ends.
JOINT, FLARED. A metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare.
JOINT, MECHANICAL. A general form of gas-tight joints obtained by the joining of metal parts through a positive-holding mechanical construction, such as press joint, flanged joint, threaded joint, flared joint or compression joint.
JOINT, PLASTIC ADHESIVE. A joint made in thermoset plastic piping by the use of an adhesive substance that forms a continuous bond between the mating surfaces without dissolving either one of them.
JOINT, PLASTIC HEAT FUSION. A joint made in thermoplastic piping by heating the parts sufficiently to permit fusion of the materials when the parts are pressed together.
JOINT, WELDED. A gas-tight joint obtained by the joining of metal parts in molten state.
LEAK CHECK. An operation performed on a gas piping system to verify that the system does not leak. Leakage checks are intended to discover open outlets, defective appliance connections and defects that have developed since the initial installation, normally performed after pressure testing.
LIMIT CONTROL. A device responsive to changes in pressure, temperature or level for turning on, shutting off or throttling the gas supply to an appliance.
LIQUEFIED PETROLEUM GAS or LPG (LP-GAS). Liquefied petroleum gas composed predominately of propane, propylene, butanes or butylenes, or mixtures thereof that is gaseous under normal atmospheric conditions, but is capable of being liquefied under moderate pressure at normal temperatures.
LIVING SPACE. Space within a dwelling unit utilized for living, sleeping, eating, cooking, bathing, washing and sanitation purposes.
LOG LIGHTER. A manually operated solid fuel ignition appliance for installation in a vented solid fuel-burning fireplace.
MAIN BURNER. A device or group of devices essentially forming an integral unit for the final conveyance of gas or a mixture of gas and air to the combustion zone, and in which combustion takes place to accomplish the function for which the appliance is designed.
METER. The instrument installed to measure the volume of gas delivered through it.
NPS. An abbreviation for "Nominal pipe size."
NONCOMBUSTIBLE MATERIALS. Materials that, when tested in accordance with ASTM E 136, have at least three of four specimens tested meeting all of the following criteria:
1. The recorded temperature of the surface and interior thermocouples shall not at any time during the test rise more than 54ºF (12.2ºC) above the furnace temperature at the beginning of the test.
2. There shall not be flaming from the specimen after the first 30 seconds.
3. If the weight loss of the specimen during testing exceeds 50 percent, the recorded temperature of the surface and interior thermocouples shall not at any time during the test rise above the furnace air temperature at the beginning of the test, and there shall not be flaming of the specimen.
OFFSET (VENT). A combination of approved bends that makes two changes in direction bringing one section of the vent out of line but into a line parallel with the other section.
ORIFICE. The opening in a cap, spud or other device whereby the flow of gas is limited and through which the gas is discharged to the burner.
OUTLET. The point at which a gas-fired appliance connects to the gas piping system.
OXYGEN DEPLETION SAFETY SHUTOFF SYSTEM (ODS). A system designed to act to shut off the gas supply to the main and pilot burners if the oxygen in the surrounding atmosphere is reduced below a predetermined level.
PILOT. A small flame that is utilized to ignite the gas at the main burner or burners.
PIPING. Where used in this code, "piping" refers to either pipe or tubing, or both.
Pipe. A rigid conduit of iron, steel, copper, brass or plastic.
Tubing. Semirigid conduit of copper, aluminum, plastic or steel.
PIPING SYSTEM. All fuel piping, valves and fittings from the outlet of the point of delivery to the outlets of the appliance shutoff valves.
PLASTIC, THERMOPLASTIC. A plastic that is capable of being repeatedly softened by increase of temperature and hardened by decrease of temperature.
POINT OF DELIVERY. For natural gas systems, the point of delivery is the outlet of the service meter assembly or the outlet of the service regulator or service shutoff valve where a meter is not provided. Where a valve is provided at the outlet of the service meter assembly, such valve shall be considered to be downstream of the point of delivery.
PORTABLE FUEL CELL APPLIANCE. A fuel cell generator of electricity, which is not fixed in place. A portable fuel cell appliance utilizes a cord and plug connection to a grid- isolated load and has an integral fuel supply.
PRESSURE DROP. The loss in pressure due to friction or obstruction in pipes, valves, fittings, regulators and burners.
PRESSURE TEST. An operation performed to verify the gas-tight integrity of gas piping following its installation or modification.
PURGE. To free a gas conduit of air or gas, or a mixture of gas and air.
QUICK-DISCONNECT DEVICE. A hand-operated device that provides a means for connecting and disconnecting an appliance or an appliance connector to a gas supply and that is equipped with an automatic means to shut off the gas supply when the device is disconnected.
READY ACCESS (TO). That which enables a device, fixture, appliance or equipment to be directly reached, without requiring the removal or movement of any panel, door or similar obstruction (see "Access (to)").
REGULATOR. A device for controlling and maintaining a uniform supply pressure, either pounds-to-inches water column (MP regulator) or inches-to-inches water column (appliance regulator).
REGULATOR, GAS APPLIANCE. A pressure regulator for controlling pressure to the manifold of the appliance. Types of appliance regulators are as follows:
Adjustable.
1. Spring type, limited adjustment. A regulator in which the regulating force acting upon the diaphragm is derived principally from a spring, the loading of which is adjustable over a range of not more than 15 percent of the outlet pressure at the midpoint of the adjustment range.
2. Spring type, standard adjustment. A regulator in which the regulating force acting upon the diaphragm is derived principally from a spring, the loading of which is adjustable. The adjustment means shall be concealed.
Multistage. A regulator for use with a single gas whose adjustment means is capable of being positioned manually or automatically to two or more predetermined outlet pressure settings. Each of these settings shall be adjustable or nonadjustable. The regulator may modulate outlet pressures automatically between its maximum and minimum predetermined outlet pressure settings.
Nonadjustable.
1. Spring type, nonadjustable. A regulator in which the regulating force acting upon the diaphragm is derived principally from a spring, the loading of which is not field adjustable.
2. Weight type. A regulator in which the regulating force acting upon the diaphragm is derived from a weight or combination of weights.
REGULATOR, LINE GAS PRESSURE. A device placed in a gas line between the service pressure regulator and the appliance for controlling, maintaining or reducing the pressure in that portion of the piping system downstream of the device.
REGULATOR, MEDIUM-PRESSURE (MP Regulator). A line pressure regulator that reduces gas pressure from the range of greater than 0.5 psig (3.4 kPa) and less than or equal to 5 psig (34.5 kPa) to a lower pressure.
REGULATOR, PRESSURE. A device placed in a gas line for reducing, controlling and maintaining the pressure in that portion of the piping system downstream of the device.
REGULATOR, SERVICE PRESSURE. A device installed by the serving gas supplier to reduce and limit the service line pressure to delivery pressure.
RELIEF OPENING. The opening provided in a draft hood to permit the ready escape to the atmosphere of the flue products from the draft hood in the event of no draft, back draft or stoppage beyond the draft hood, and to permit air into the draft hood in the event of a strong chimney updraft.
RELIEF VALVE (DEVICE). A safety valve designed to forestall the development of a dangerous condition by relieving either pressure, temperature or vacuum.
RELIEF VALVE, PRESSURE. An automatic valve that opens and closes a relief vent, depending on whether the pressure is above or below a predetermined value.
RELIEF VALVE, TEMPERATURE.
Manual reset type. A valve that automatically opens a relief vent at a predetermined temperature and that must be manually returned to the closed position.
Reseating or self-closing type. An automatic valve that opens and closes a relief vent, depending on whether the temperature is above or below a predetermined value.
RELIEF VALVE, VACUUM. A valve that automatically opens and closes a vent for relieving a vacuum within the hot water supply system, depending on whether the vacuum is above or below a predetermined value.
RISER, GAS. A vertical pipe supplying fuel gas that extends one full story or more.
ROOM HEATER, UNVENTED. See "Unvented room heater."
ROOM HEATER, VENTED. See "Vented room heater."
ROUGH-IN. Parts of the gas system that are installed prior to the installation of appliances or equipment. This includes gas piping, all the necessary supports and any appliances that are built into the structure.
SAFETY SHUTOFF DEVICE. See "Flame safeguard."
SERVICE PIPING. All fuel-gas piping, valves and fittings upstream of the point of delivery.
SHAFT. An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and the roof.
SLEEPING UNIT. A dwelling unit, which may contain either toilet or kitchen facilities but not both. Any sleeping unit housing more than one family shall also be classified as a congregate living unit. The creation of or conversion to sleeping units shall be limited by Section 27-2077 of the New York City Housing Maintenance Code .
SPECIFIC GRAVITY. As applied to gas, specific gravity is the ratio of the weight of a given volume to that of the same volume of air, both measured under the same condition.
STATIONARY FUEL CELL POWER PLANT. A self-contained package or factory-matched packages that constitute an automatically operated assembly of integrated systems for generating electrical energy and recoverable thermal energy that is permanently connected and fixed in place.
THERMOSTAT
Electric switch type. A device that senses changes in temperature and controls electrically, by means of separate components, the flow of gas to the burner(s) to maintain selected temperatures.
Integral gas valve type. An automatic device, actuated by temperature changes, designed to control the gas supply to the burner(s) in order to maintain temperatures between predetermined limits, and in which the thermal actuating element is an integral part of the device.
1. Graduating thermostat. A thermostat in which the motion of the valve is approximately in direct proportion to the effective motion of the thermal element induced by temperature change.
2. Snap-acting thermostat. A thermostat in which the thermostatic valve travels instantly from the closed to the open position, and vice versa.
THIRD-PARTY CERTIFICATION AGENCY. An approved agency operating a product or material certification system that incorporates initial product testing, assessment and surveillance of a manufacturer's quality control system.
THIRD-PARTY CERTIFIED. Certification obtained by the manufacturer indicating that the function and performance characteristics of a product or material have been determined by testing and ongoing surveillance by an approved third-party certification agency. Assertion of certification is in the form of identification in accordance with the requirements of the third-party certification agency.
THIRD-PARTY TESTED. Procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements.
TRANSITION FITTINGS, PLASTIC TO STEEL. An adapter for joining plastic pipe to steel pipe. The purpose of this fitting is to provide a permanent, pressure-tight connection between two materials that cannot be joined directly one to another.
UNIT HEATER
High-static pressure type. A self-contained, automatically controlled, vented appliance having integral means for circulation of air against 0.2 inch (15 mm H 2 O) or greater static pressure. Such appliance is equipped with provisions for attaching an outlet air duct and, where the appliance is for indoor installation remote from the space to be heated, is also equipped with provisions for attaching an inlet air duct.
Low-static pressure type. A self-contained, automatically controlled, vented appliance, intended for installation in the space to be heated without the use of ducts, having integral means for circulation of air. Such units are allowed to be equipped with louvers or face extensions made in accordance with the manufacturer's specifications.
UNLISTED BOILER. A boiler not listed by a nationally recognized testing agency.
UNVENTED ROOM HEATER. An unvented heating appliance designed for stationary installation and utilized to provide comfort heating. Such appliance provides radiant heat or convection heat by gravity or fan circulation directly from the heater and does not utilize ducts.
VALVE. A device used in piping to control the gas supply to any section of a system of piping or to an appliance.
Appliance shutoff. A valve located in the piping system, used to isolate individual appliances for purposes such as service or replacement.
Automatic. An automatic or semiautomatic device consisting essentially of a valve and operator that control the gas supply to the burner(s) during operation of an appliance. The operator shall be actuated by application of gas pressure on a flexible diaphragm, by electrical means, by mechanical means, or by other approved means.
Automatic gas shutoff. A valve used in conjunction with an automatic gas shutoff device to shut off the gas supply to a system. It shall be constructed integrally with the gas shutoff device or shall be a separate assembly.
Individual main burner. A valve that controls the gas supply to an individual main burner.
Main burner control. A valve that controls the gas supply to the main burner manifold.
Manual main gas-control. A manually operated valve in the gas line for the purpose of completely turning on or shutting off the gas supply to the appliance, except to pilot or pilots that are provided with independent shutoff.
Manual reset. An automatic shutoff valve installed in the gas supply piping and set to shut off when unsafe conditions occur. The device remains closed until manually reopened.
Service shutoff. A valve, installed by the serving gas supplier between the service meter or source of supply and the customer piping system, to shut off the entire piping system.
VENT. A pipe or other conduit composed of factory-made components, containing a passageway for conveying combustion products and air to the atmosphere, listed and labeled for use with a specific type or class of appliance.
Special gas vent. A vent listed and labeled for use with listed Category II, III and IV appliances.
Type B vent. A vent listed and labeled for use with appliances with draft hoods and other Category I appliances that are listed for use with Type B vents.
Type BW vent. A vent listed and labeled for use with wall furnaces.
Type L vent. A vent listed and labeled for use with appliances that are listed for use with Type L or Type B vents.
VENT CONNECTOR. See "Connector."
VENT GASES. Products of combustion from appliances plus excess air plus dilution air in the vent connector, gas vent or chimney above the draft hood or draft regulator.
VENT PIPING.
Breather. Piping run from a pressure-regulating device to the outdoors, designed to provide a reference to atmospheric pressure. If the device incorporates an integral pressure relief mechanism, a breather vent can also serve as a relief vent.
Relief. Piping run from a pressure-regulating or pressure-limiting device to the outdoors, designed to provide for the safe venting of gas in the event of excessive pressure in the gas piping system.
VENTED APPLIANCE CATEGORIES. Appliances that are categorized for the purpose of vent selection are classified into the following four categories:
Category I. An appliance that operates with a nonpositive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
Category II. An appliance that operates with a nonpositive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent.
Category III. An appliance that operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
Category IV. An appliance that operates with a positive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent.
VENTED ROOM HEATER. A vented self-contained, free-standing, nonrecessed appliance for furnishing warm air to the space in which it is installed, directly from the heater without duct connections.
VENTED WALL FURNACE. A self-contained vented appliance complete with grilles or equivalent, designed for incorporation in or permanent attachment to the structure of a building, mobile home or travel trailer, and furnishing heated air circulated by gravity or by a fan directly into the space to be heated through openings in the casing. This definition shall exclude floor furnaces, unit heaters and central furnaces as herein defined.
VENTING SYSTEM. A continuous open passageway from the flue collar or draft hood of an appliance to the outdoor atmosphere for the purpose of removing flue or vent gases. A venting system is usually composed of a vent or a chimney and vent connector, if used, assembled to form the open passageway.
Forced-draft venting system. A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under positive static vent pressure.
Induced draft venting system. A portion of a venting system using a fan or other mechanical means to cause the removal of flue or vent gases under nonpositive static vent pressure.
Mechanical draft venting system. A venting system designed to remove flue or vent gases by mechanical means, that consists of an induced draft portion under nonpositive static pressure or a forced draft portion under positive static pressure.
Natural draft venting system. A venting system designed to remove flue or vent gases under nonpositive static vent pressure entirely by natural draft.
WALL HEATER, UNVENTED-TYPE. A room heater of the type designed for insertion in or attachment to a wall or partition. Such heater does not incorporate concealed venting arrangements in its construction and discharges all products of combustion through the front into the room being heated.
WATER HEATER. Any heating appliance or equipment that heats potable water and supplies such water to the potable hot water distribution system.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051 and L.L. 2023/077.
Section FGC 301. General
301.1 Scope.
This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the installations regulated by this code in accordance with Section 101.2.
301.1.1 Other fuels.
The requirements for combustion and dilution air for gas-fired appliances shall be governed by Section 304. The requirements for combustion and dilution air for appliances operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code.
301.2 Energy utilization.
Heating, ventilating, air-conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2009/085.
301.3 Listed and labeled.
Appliances regulated by this code shall be listed and labeled.
301.4 Labeling.
Refer to Article 114 and Section 28-113.4 of the Administrative Code.
301.5 Label information.
A permanent factory-applied nameplate(s) shall be affixed to appliances on which shall appear in legible lettering: the manufacturer's name or trademark, the model number, serial number and, for listed appliances, the seal or mark of the testing agency. A label shall include the hourly rating in British thermal units per hour (Btu/h) (W), the type of fuel approved for use with the appliance, and the minimum clearance requirements.
301.6 Plumbing connections.
Potable water supply and building drainage system connections to appliances regulated by this code shall be in accordance with the New York City Plumbing Code.
301.7 Fuel types.
Appliances shall be designed for use with the type of fuel gas that will be supplied to them.
301.7.1 Appliance fuel conversion.
Appliances shall not be converted to utilize a different fuel gas except where complete instructions for such conversion are provided by the serving gas supplier, the appliance manufacturer, the burner manufacturer or the boiler manufacturer. If a specific listing and labeling is available for the burner and boiler combination it shall be submitted to the department. If a specific listing for the combination is not available the listing for the burner and a letter confirming compatibility shall be submitted by the burner manufacturer. The completed installation shall be inspected and tested in the field by a representative of the appliance manufacturer, the burner manufacturer or the boiler manufacturer, and certified by a registered design professional. A certification of compliance by a registered design professional developed in accordance with the requirements of the New York City Department of Environmental Protection may be used to satisfy this certification requirement. The registered design professional need not be the engineer of record for the design.
301.7.2 Liquid petroleum gas.
Storage or use of LPG for a stationary LPG installation shall comply with the New York City Fire Code.
301.8 Vibration isolation.
Where means for isolation of vibration of an appliance is installed, means for support and restraint of that appliance shall be provided as designed by a registered design professional.
301.9 Repair.
Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing.
301.10 Wind resistance.
Appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code.
301.11 Flood hazard.
For structures located in flood hazard areas, the appliance, equipment and system installations regulated by this code shall comply with the additional requirements of Appendix G of the New York City Building Code.
301.12 Seismic resistance.
When earthquake loads are applicable in accordance with the New York City Building Code, the supports shall be designed and installed for the seismic forces in accordance with that code.
301.13 Ducts.
Ducts required for the installation of systems regulated by this code shall be designed and installed in accordance with the New York City Mechanical Code.
301.14 Rodentproofing.
Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to protect against rodents in accordance with the New York City Building Code.
301.15 Prohibited location.
The appliances, equipment and systems regulated by this code shall not be located in an elevator shaft.
301.16 Mechanical systems.
Hydronic piping, ventilation and other mechanical systems not covered by this code shall be in accordance with the New York City Mechanical Code.
301.17 Electrical systems.
Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the New York City Electrical Code.
301.18 Noise control requirements.
Appliances and equipment regulated by this code must comply with Section 313 of the New York City Mechanical Code.
Section FGC 302. Structural Safety
302.1 Structural safety.
The building shall not be weakened by the installation of any gas piping. In the process of installing or repairing any gas piping, finished floors, walls, ceilings, tile work or any other part of the building or premises which is required to be changed or replaced shall be left in a safe structural condition in accordance with the requirements of the New York City Building Code.
302.1.1 Loading.
Alterations resulting in the addition of loads to any member, such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading.
302.2 Penetrations of floor/ceiling assemblies and fire-resistance-rated assemblies.
Penetrations of floor/ceiling assemblies and assemblies required to have a fire-resistance rating shall be protected in accordance with the New York City Building Code.
302.3 Cutting, notching and boring in wood members.
The cutting, notching and boring of wood members shall comply with Sections 302.3.1 through 302.3.5.
302.3.1 Solid non-engineered joist notches and holes.
Notches on the ends of the solid non-engineered joists shall not exceed one-fourth the joist depth. Notches in the top or bottom of joists shall not exceed one-sixth the depth, shall not be longer than one-third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bottom of the joist, and the diameter of any such hole shall not exceed one-third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code.
302.3.2 Stud cutting and notching.
In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5.8 of the New York City Building Code.
302.3.3 Bored holes in studs.
Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5/8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
302.3.4 Engineered wood products.
Cuts, notches and holes bored in trusses, structural composite lumber, structural glued-laminated members and I-joists are prohibited except where permitted by the manufacturer's recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional.
302.3.5 Drilling and notching of top plate.
When piping is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (No. 16 gage) and 1 1/2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1/2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code.
Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing, additional fastening is not required.
302.4 Trusses.
Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without the written concurrence and approval of a registered design professional.
302.5 Cutting, notching and boring in steel framing.
The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4.
302.5.1 Structural steel framing.
The cutting, notching and boring of holes in structural steel framing members shall be as prescribed by the registered design professional.
302.5.2 Cold-formed steel framing.
Flanges and lips of load-bearing, cold-formed steel framing members shall not be cut or notched. Holes in webs of load-bearing, cold-formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, penetration spacing or minimum hole edge distance as prescribed by the registered design professional.
302.5.3 Nonstructural cold-formed steel wall framing.
Flanges and lips of nonstructural cold-formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1/2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end.
302.5.4 Steel floor and roof decking.
Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional.
302.6 Cutting, notching and coring into concrete.
The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional.
302.7 Protection of footings.
Trenching installed parallel to footings and walls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall.
302.8 Piping materials exposed within plenums.
Piping materials exposed within plenums shall comply with the provisions of the New York City Mechanical Code.
Section FGC 303. Appliance Location
303.1 General.
Appliances shall be located as required by this section, specific requirements elsewhere in this code and the conditions of the equipment and appliance listing.
303.2 Hazardous locations.
Appliances shall not be located in a hazardous location unless listed and approved for the specific installation.
303.3 Prohibited locations.
Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces.
Exceptions:
1. In rooms other than those used for sleeping purposes, direct-vent appliances that obtain all combustion air directly from the outdoors and installed in accordance with the conditions of the listing and the manufacturer's instructions.
2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel-burning fireplaces that are installed in rooms that meet the required volume criteria of Section 304.5.
3. In rooms other than those used for sleeping purposes, appliances installed in an enclosure in which all combustion air is taken from the outdoors, in accordance with Section 304.6. Access to such enclosure shall be through a solid weather-stripped door, equipped with an approved self-closing device.
303.3.1 Gas-fired direct vent appliances.
Gas-fired direct vent space-heating appliances used for providing heat in rooms for sleeping purposes shall be deemed to be located outside of the sleeping room provided that the appliance and its installation comply with Sections 303.3.1.1 through 303.3.1.7.
303.3.1.1 General.
Such unit is factory assembled and manufactured with an integral, factory assembled and hard-wired carbon monoxide detector interlock and automatic main gas shut-off valve. The appliance shall be tested, designed and evaluated in accordance with Section 622 of this code. Acceptable gas-fired direct vent space-heating appliances shall be listed and labeled by an approved agency in accordance with Section 28-113.2.3 of the Administrative Code. Installation shall be in accordance with the manufacturer's instructions and the applicable listing.
303.3.1.2 Carbon monoxide detector.
The carbon monoxide detector shall be listed and labeled in accordance with UL 2034 and UL 2075 and installed in accordance with the carbon monoxide detector manufacturer's instructions. The carbon monoxide detector may be installed integral to the appliance, on the surface of the appliance or remotely, but hard-wired, no more than 5 feet (1.5 m) from the appliance.
303.3.1.3 Internal safety controls.
The appliance shall be hard-wired to the carbon monoxide detector in a supervisory signaling mode. If the carbon monoxide detector connection is not sensed, the appliance shall not initiate a startup sequence and shall alert the operator to the fault condition. The appliance shall be supplied with a carbon monoxide fault indicator easily visible and recognizable to the operator. The appliance shall be equipped with a manual restart control. Automatic reset is not permitted.
303.3.1.4 Gas piping.
The appliance shall be installed with natural gas only. All gas piping shall be hard-piped with no flexible connectors. Pursuant to Section 27-2034(f) of the New York City Housing Maintenance Code, each heater shall be equipped with an effective device to automatically shut off the gas supply to the heater if its pilot light or other constantly burning flame is extinguished, or in the event of an interruption of the gas supply to the heater, and will not permit the heater to be relighted unless such shut-off device is first reset manually.
303.3.1.5 Venting.
Such unit shall be of direct vent type, such that all air for combustion is derived from the outdoors and that all flue gases are discharged directly to the outdoors. Such unit shall be installed through a sleeve located in an exterior wall.
303.3.1.6 Installation.
Gas-fired direct vented appliances shall be installed in accordance with the following:
1. Carbon monoxide detectors installed with gas-fired direct vent space-heating appliance shall be provided in addition to code required carbon monoxide detector devices in dwelling units.
2. Carbon monoxide detectors installed with gas-fired direct vent space-heating appliance shall not be interconnected to other carbon monoxide detecting devices in the dwelling unit.
3. The appliance shall only be installed by a master licensed plumber.
303.3.1.7 Clearances.
Gas-fired direct vented appliances shall be installed with the following clearances:
1. Clearances from adjacent combustible surfaces shall meet the minimum clearances indicated by the manufacturer's instructions and the listing agency.
2. Clearances from adjacent openings or packaged terminal air conditioners (PTAC) and packaged terminal heat pumps (PTHP), the bottom of the vent terminal and the air intake shall be located at least 12 inches (304.8 mm) above finished ground level and in accordance with Table 303.3.1.7.
3. For all other equipment, all vent termination clearances from adjacent openings shall be in accordance with Section 503.8.
Table 303.3.1.7 PTAC and PTHP Vent Termination Clearance to Air Openings
Appliance Input Rating (BTU per hour) Vent Termination Clearance to Any Air Opening Into Same or Adjacent Building (inches) 10,000 or less 6 Over 10,000 but less than 50,000 9 50,000 or over 12
For SI: 1 inch = 25.4 mm, 1 British thermal unit per hour = 0.2931 W.
303.4 Protection from physical damage.
Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by approved barriers meeting the requirements of the New York City Fire Code.
303.5 Indoor locations.
Furnaces and boilers installed in closets and alcoves shall be listed for such installation.
303.5.1 Gas fired appliances.
Boilers, furnaces and other centrally installed space heating equipment, regardless of btu per hour input, shall be located in an enclosure in accordance with Section 509 of the New York City Building Code.
Exception: Gas fired direct vented appliances with a 350,000 btu per hour (102.6 kW) input or less may be installed in a non-fire rated enclosure.
303.5.2 Maximum temperature.
Maximum indoor temperature in spaces surrounding appliances shall not exceed the greater of the operational temperature of the installed equipment or 104°F (40°C).
303.6 Outdoor locations.
Appliances installed in outdoor locations shall be either listed for outdoor installation or provided with protection from outdoor environmental factors that influence the operability, durability and safety of the appliances.
303.7 Pit locations.
Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back a minimum of 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry, such concrete or masonry shall extend a minimum of 4 inches (101.6 mm) above adjoining grade and shall have sufficient lateral load-bearing capacity to resist collapse. The appliance shall be protected from flooding in a manner approved by the commissioner.
Section FGC 304. Combustion, Ventilation and Dilution Air
This section has 7 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section FGC 304 at American Legal Publishing.
304.1 General.
Air for combustion, ventilation and dilution of flue gases for appliances installed in buildings shall be provided by application of one of the methods prescribed in Sections 304.5 through 304.9. Where the requirements of Section 304.5 are not met, outdoor air shall be introduced in accordance with one of the methods prescribed in Sections 304.6 through 304.9. Direct-vent appliances, gas appliances of other than natural draft design, vented gas appliances not designated as Category I and appliances equipped with power burners shall be provided with combustion, and dilution air in accordance with the appliance manufacturer's instructions. Combustion and dilution air shall be obtained solely from the outdoors for fuel-burning appliances with an input greater than 350,000 Btu/h (102.6 kW). Ventilation air shall be provided by any suitable means. The mechanical room shall comply with the requirements of Section 1012 of the New York City Mechanical Code and Sections C402.5.3 and R402.4.4, as applicable, of the New York City Energy Conservation Code.
Exception: Type 1 clothes dryers that are provided with makeup air in accordance with Section 504 of the New York City Mechanical Code.
304.1.1 Crawl space and attic space.
For the purposes of this chapter, an opening to a naturally ventilated crawl space or attic space shall be considered equivalent to an opening to the outdoors.
304.1.1.1 Crawl space.
Where lower combustion air openings connect with crawl spaces, such spaces shall have unobstructed openings to the outdoors at least twice that required for the combustion air openings. The height of the crawl space shall comply with the requirements of the New York City Building Code and shall be without obstruction to the free flow of air.
304.1.1.2 Attic space.
Where combustion air is obtained from an attic area, the attic ventilating openings shall not be subject to ice or snow blockage, and the attic shall have not less than 30 inches (762 mm) vertical clear height at its maximum point. Attic ventilation openings shall be sufficient to provide the required volume of combustion air and the attic ventilation required by the New York City Building Code. The combustion air openings shall be provided with a sleeve of not less than 0.019 inch (0.48 mm) (No. 26 Gage) galvanized steel or other approved material extending from the appliance enclosure to at least 6 inches (152.4 mm) above the top of the ceiling joists and insulation.
304.2 Appliance location.
Appliances shall be located so as not to interfere with proper circulation of combustion, ventilation and dilution air.
304.3 Draft hood/regulator location.
Where used, a draft hood or a barometric draft regulator shall be installed in the same room or enclosure as the equipment served to prevent any difference in pressure between the hood or regulator and the combustion air supply. A barometric damper may be installed in an adjacent room provided that a louver is installed in the adjacent room to the outside air. The net free area of the louver shall be equal to or greater than the area of the barometric damper.
304.4 Circulation of air.
The equipment and appliances within every room containing fuel-burning appliances shall be installed so as to allow free circulation of air. Provisions shall be made to allow for the simultaneous operation of mechanical exhaust systems, fireplaces or other equipment and appliances operating in the same room or space from which combustion, ventilation, and dilution air is being drawn. Such provisions shall prevent the operation of such appliances, equipment and systems from affecting the supply of combustion, ventilation, and dilution air.
304.4.1 Makeup air for fuel-burning devices.
Where exhaust fans are installed, makeup air shall be provided to replace the exhausted air. Calculations shall be provided on the construction documents to validate the use of the exhaust fan(s) and compliance with this chapter.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2014/051 and L.L. 2023/077.
304.4.2 Ventilation air for fuel-burning devices.
Where ventilation air is brought in by mechanical means for heat generation mitigation, provisions must be made for proper air balance to prevent a negative or positive pressure in the boiler room and to discharge the ventilation directly to the outside.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.
304.4.3 Prohibited sources.
Openings and ducts shall not connect appliance enclosures with a space in which the operation of a fan will adversely affect the flow of the combustion, ventilation, and dilution air. Combustion, ventilation, and dilution air shall not be subject to ice or snow blockage. No combustion, ventilation, and dilution air inlet shall be less than 30 inches above grade. Combustion, ventilation, and dilution air shall not be obtained from a hazardous location, except where the fuel-fired appliances are located within the hazardous location and are installed in accordance with this code. Combustion, ventilation, and dilution air shall not be taken from a refrigeration machinery room, except where a refrigerant vapor detector system is installed to automatically shut off the combustion process in the event of refrigerant leakage. For structures in flood hazard areas, air shall be obtained from a location complying with the additional requirements of Appendix G of the New York City Building Code.
304.5 Indoor combustion air.
The required volume of indoor air shall be determined in accordance with Section 304.5.1 or 304.5.2, except that where the air infiltration rate is known to be less than 0.40 air changes per hour (ACH), Section 304.5.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with Section 304.5.3, are considered to be part of the required volume.
Exception: Combustion, ventilation, and dilution air shall be obtained solely from the outdoors for fuel-burning appliances with an input greater than 350,000 Btu/h (102.6 kW).
304.5.1 Standard method.
The minimum required volume shall be 50 cubic feet per 1,000 Btu/h (4.8 m 3 /kW) of the appliance input rating.
304.5.2 Known air-infiltration-rate method.
Where the air infiltration rate of a structure is known, the minimum required volume shall be determined as follows:
For appliances other than fan-assisted, calculate volume using Equation 3-1.
(Equation 3-1}
For fan-assisted appliances, calculate volume using Equation 3-2.
(Equation 3-2)
where:
I other = All appliances other than fan assisted (input in Btu/h).
I fan = Fan-assisted appliance (input in Btu/h).
ACH = Air change per hour (percent of volume of space exchanged per hour, expressed as a decimal).
For purposes of this calculation, an infiltration rate greater than 0.60 ACH shall not be used in Equations 3-1 and 3-2.
304.5.3 Indoor opening size and location.
Openings used to connect indoor spaces shall be sized and located in accordance with Sections 304.5.3.1 and 304.5.3.2 (see Figure 304.5.3).
Figure 304.5.3 All Air From Inside the Building (see Section 304.5.3)
304.5.3.1 Combining spaces on the same story.
Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/h (2200 mm 2 /kW) of the total input rating of all appliances in the space, but not less than 100 square inches (0.06 m 2 ). One opening shall commence within 12 inches (304.8 mm) of the top and one opening shall commence within 12 inches (304.8 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (76.2 mm).
304.5.3.2 Combining spaces in different stories.
The volumes of spaces in different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 square inches per 1,000 Btu/h (4402 mm 2 /kW) of total input rating of all appliances.
304.6 Outdoor combustion air.
Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with Section 304.6.1 or 304.6.2. The minimum dimension of air openings shall be not less than 3 inches (76.2 mm). The size of the openings connecting the room to the outdoor air supply shall also comply with any applicable rules of the New York City Department of Environmental Protection.
304.6.1 Two-permanent-openings method.
Two permanent openings, one commencing within 12 inches (304.8 mm) of the top and one commencing within 12 inches (304.8 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors.
Where directly communicating with the outdoors, or where communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/h (550 mm 2 /kW) of total input rating of all appliances in the enclosure (see Figures 304.6.1(1) and 304.6.1(2)).
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2,000 Btu/h (1100 mm 2 /kW) of total input rating of all appliances in the enclosure (see Figure 304.6.1(3)).
Figure 304.6.1(1) All Air from Outdoors – Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic (see Section 304.6.1)
Figure 304.6.1(2) All Air from Outdoors Through Ventilated Attic (see Section 304.6.1)
Figure 304.6.1(3) All Air from Outdoors (see Section 304.6.1)
304.6.2 One-permanent-opening method.
One permanent opening, commencing within 12 inches (304.8 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of not less than 1 inch (25.4 mm) from the sides and back and 6 inches (152.4 mm) from the front of the appliance. The opening shall directly communicate with the outdoors, or through a vertical or horizontal duct, to the outdoors or spaces that freely communicate with the outdoors (see Figure 304.6.2) and shall have a minimum free area of 1 square inch per 3,000 Btu/h (734 mm 2 /kW) of the total input rating of all appliances located in the enclosure and not less than the sum of the areas of all vent connectors in the space.
Figure 304.6.2 Single Combustion Air Opening, All Air from the Outdoors (see Section 304.6.2)
304.7 Combination indoor and outdoor combustion air.
The use of a combination of indoor and outdoor combustion air shall be in accordance with Sections 304.7.1 through 304.7.3.
304.7.1 Indoor openings.
Where used, openings connecting the interior spaces shall comply with Section 304.5.3.
304.7.2 Outdoor opening location.
Outdoor opening(s) shall be located in accordance with Section 304.6.
304.7.3 Outdoor opening(s) size.
The outdoor opening(s) size shall be calculated in accordance with the following:
1. The ratio of interior spaces shall be the available volume of all communicating spaces divided by the required volume.
2. The outdoor size reduction factor shall be one minus the ratio of interior spaces.
3. The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s) calculated in accordance with Section 304.6, multiplied by the reduction factor. The minimum dimension of air openings shall be not less than 3 inches (76.2 mm).
304.8 Reserved.
304.9 Mechanical combustion air supply.
Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from the outdoors at a rate not less than 0.35 cubic feet per minute per 1,000 Btu/h (0.034 m 3 /min per kW) of total input rating of all appliances located within the space. Combustion air rates shall also comply with any applicable rules of the New York City Department of Environmental Protection. The mechanical air supply shall be sufficient to accommodate combustion air, ventilation air, and dilution air requirements of the installation.
304.9.1 Makeup air.
Where exhaust fans are installed, makeup air shall be provided to replace the exhausted air.
304.9.2 Appliance interlock.
Each of the appliances served shall be interlocked with the mechanical air supply system to prevent main burner operation when the mechanical air supply system is not in operation. The air flow and the damper operation shall be proven prior to burner operation.
304.9.3 Reserved.
304.10 Opening obstructions locations, and protection.
The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. The net free area of an opening shall be that specified by the manufacturer of the opening covering. In the absence of such information, openings covered with metal louvers shall be deemed to have a net free area of 60 percent of the area of the opening, and openings covered with wood louvers shall be deemed to have a net free area of 10 percent of the area of the opening. Louvers and grilles shall be fixed in the open position.
Exception: Operable louvers shall be interlocked with the appliance so that they are proven to be in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the main burner from igniting if the louvers fail to open during burner startup and to shut down the main burner if the louvers close during operation.
304.10.1 Dampered openings.
Where the combustion air openings are provided with automatic, smoke or fire dampers, the dampers shall be electrically interlocked with the appliances served, so as to prevent operation of any appliance when any of the dampers are closed. Manually operated dampers shall not be installed in combustion air openings. The damper opening shall be proven prior to burner operation.
304.10.2 Caution sign.
A sign stating, "Louvers, dampers and/or ventilation openings must not be blocked or disabled." shall be permanently affixed, in clear view, adjacent to the opening(s) within the room containing the equipment. The letters used on the sign shall be at least 1 inch (25.4 mm) in height.
304.10.3 Opening location and protection.
Combustion air openings to the outdoors shall comply with the location and protection provisions applicable to outside air intake openings of Sections 401.5 and 401.6 of the New York City Mechanical Code.
304.11 Combustion air ducts.
Combustion air ducts shall comply with all of the following:
1. Be of galvanized steel complying with Chapter 6 of the New York City Mechanical Code or of equivalent corrosion-resistant material approved for this application.
Exception: Within dwelling units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one required fireblock is removed.
2. Have a minimum dimension of 3 inches (76.2 mm) in all directions.
3. Terminate in an unobstructed space allowing free movement of combustion air to the appliances.
4. Have the same cross-sectional areas as the free area of the openings to which they connect.
5. Serve a single appliance enclosure.
6. Not serve both upper and lower combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combustion air.
7. Not be screened where terminating in an attic space.
8. Not slope downward toward the source of combustion air, where serving the upper required combustion air opening.
9. Be constructed so that the remaining space surrounding a chimney or chimney liner, installed within a masonry, metal or factory-built chimney cannot be used to supply combustion, ventilation and dilution air, except for direct vent appliances designed and installed in accordance with the equipment manufacturer's instructions and listing.
304.12 Protection from fumes and gases.
Where corrosive or flammable process fumes or gases, other than products of combustion, are present, means for the disposal of such fumes or gases shall be provided. Such fumes or gases include carbon monoxide, hydrogen sulfide, ammonia, chlorine and halogenated hydrocarbons.
In barbershops, beauty shops and other facilities where chemicals that generate corrosive or flammable products, such as aerosol sprays, are routinely used, nondirect-vent-type appliances shall be located in a mechanical room separated or partitioned off from other areas with provisions for combustion air and dilution air from the outdoors. Direct-vent appliances shall be installed in accordance with the appliance manufacturer's instructions.
Section FGC 305. Installation
305.1 General.
Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of listing, the manufacturer's instructions and this code. Manufacturers' instructions shall be available on the job site at the time of inspection. Where a code provision is less restrictive than the conditions of the listing of the equipment or appliance or the manufacturer's instructions, the conditions of the listing and the manufacturer's instructions shall apply.
305.2 Hazardous area.
Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, handling or dispensing of combustible, flammable or explosive materials occurs.
305.3 Elevation of ignition source.
Equipment and appliances having an ignition source shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor in hazardous locations and public garages, private garages, repair garages, motor fuel-dispensing facilities and parking garages. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be considered to be part of the private garage.
Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant.
305.3.1 Installation in residential garages.
In residential garages where appliances are installed in a separate, enclosed space having access only from outside of the garage, such appliances shall be permitted to be installed at floor level, provided that the required combustion air is taken from the exterior of the garage.
305.3.2 Parking garages.
Connection of a parking garage with any room in which there is a fuel-fired appliance shall be by means of a vestibule providing a two-doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 305.3.
Exception: This section shall not apply to appliance installations complying with Section 305.4.
305.4 Public garages, motor fuel-dispensing facilities and repair garages.
Appliances located in public garages, motor fuel-dispensing facilities, repair garages or other areas frequented by motor vehicles shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicles are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening.
Exceptions:
1. The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 305.3 of this code and NFPA 30A.
2. Appliances installed in repair garages shall be separated from repair areas by walls or partitions, floors, or floor ceiling assemblies that are constructed so as to prohibit the transmission of vapors and having a fire-resistance rating of not less than 1 hour, and that have no openings in the wall separating the repair area within 8 feet (2438.4 mm) of the floor. Wall penetration shall be firestopped. Air for combustion purposes shall be obtained from the outdoors. The heating room shall not be used for the storage of combustible materials.
3. Heating appliances for vehicle repair areas where there is no dispensing or transferring of Class I or Class II flammable or combustible liquids or liquefied petroleum gas shall be installed in accordance with NFPA 30A.
305.5 Private garages.
Appliances located in private garages shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor.
Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 305.3.
305.6 Construction and protection.
Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code.
305.7 Clearances from grade.
Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending not less than 3-inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such supports shall be installed in accordance with the manufacturer's instructions.
305.8 Clearances to combustible construction.
Heat-producing equipment and appliances shall be installed to maintain the required clearances to combustible construction as specified in the listing and manufacturer's instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead projections or shelving and window swing. Devices, such as door stops or limits and closers, shall not be used to provide the required clearances.
305.9 Parking structures.
Appliances installed in enclosed, basement and underground parking structures shall be installed in accordance with NFPA 88A.
305.10 Repair garages.
Appliances installed in repair garages shall be installed in accordance with NFPA 30A.
305.11 Installation in aircraft hangars.
Heaters in aircraft hangars shall be installed in accordance with NFPA 409.
305.12 Avoid strain on gas piping.
Appliances shall be supported and connected to the piping so as not to exert undue strain on the connections.
Section FGC 306. Access and Service Space
306.1 Clearances for maintenance and replacement.
Appliances, control devices, heat exchangers and HVAC components shall be accessible for inspection, service, repair and replacement without disabling the function of a fire-resistance-rated assembly or removing permanent construction, other appliances, or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be provided in front of the control side to service an appliance.
306.2 Appliances in rooms.
Rooms containing appliances shall be provided with a door and an unobstructed passageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high.
Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be provided with access by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep and the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open.
306.3 Appliances in attics.
Attics containing appliances shall be provided with an opening and unobstructed passageway large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length when measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm) and large enough to allow removal of the largest component of the appliance.
Exceptions:
1. The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening.
2. Where the passageway is not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not greater than 50 feet (15 250 mm) in length.
306.3.1 Electrical requirements.
A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code.
306.4 Appliances under floors.
Under-floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest component of the appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 feet (6096 mm) in length when measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the appliance. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the passageway shall be lined with concrete or masonry extending 4 inches (101.6 mm) above the adjoining grade and having sufficient lateral-bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance.
Exceptions:
1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening.
2. Where the passageway is not less than 6 feet (1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length.
306.4.1 Electrical requirements.
A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code.
306.5 Equipment and appliances on roofs or elevated structures.
Where equipment or appliances requiring access are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade, roof, or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Such access to the roof or elevated structure and access from the roof or elevated structure to equipment requiring maintenance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall.
Permanent ladders installed to provide the required access shall comply with the following minimum design criteria:
1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm).
2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, as applicable.
3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep.
4. There shall be not less than 18 inches (457.2 mm) between rails.
5. Rungs shall have a diameter not less than 0.75-inch (19 mm) and be capable of withstanding a 300-pound (136.1 kg) load.
6. Where a cage, well or ladder safety device is provided, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 20 feet (6096 mm) in height. Landings shall be capable of withstanding a load of 100 pounds per square foot (488.2 kg/m 2 ). A guardrail and toeboard shall be provided on all open sides of the landing.
7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs, except where cages or wells are installed.
8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder.
9. Ladders shall be protected against corrosion by approved means.
10. Service personnel shall have access to ladders at all times.
11. Where ladder extensions are installed, the side rails of through or side-step ladder extensions shall extend 3 1/2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side-step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1/2 feet (1066.8 mm) minimum.
Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms.
Exception: This section shall not apply to Group R-3 occupancies.
306.5.1 Sloped roofs.
Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of 3 units vertical in 12 units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533.4 mm) sphere and shall comply with the loading requirements for guards specified in the New York City Building Code. Access shall not require walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with ladders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service.
306.5.2 Electrical requirements.
A receptacle outlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code.
306.6 Guards.
Guards shall be provided where various components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of components that require service. The top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch-diameter (533.4 mm) sphere and shall comply with the loading requirements for guards specified in the New York City Building Code.
306.7. Rooftop access and obstructions.
Equipment and appliances installed on rooftops of buildings shall be installed in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access.
Section FGC 307. Condensate Disposal
307.1 Evaporators and cooling coils.
Condensate drain systems shall be provided for equipment and appliances containing evaporators and cooling coils in accordance with the New York City Mechanical Code.
307.2 Fuel-burning appliances.
Liquid combustion by-products of condensing appliances shall be collected and discharged to an approved plumbing fixture, or disposal area in accordance with the manufacturer's instructions. Condensate piping shall conform to one of the standards listed in Section 803 of the New York City Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent slope).
307.2.1 Condensate disposal.
Condensate from all fuel-burning appliances and associated flues shall be neutralized to a pH of at least 6 and no more than 8 prior to disposal to a sanitary system.
307.3 Drain pipe materials and sizes.
Components of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polyethylene, ABS, CPVC or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relative to the material type. Condensate waste and drain line size shall be not less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized by a registered design professional.
307.4. Traps.
Condensate drains shall be trapped as required by the equipment or appliance manufacturer.
307.5 Auxiliary drain pan.
Category II or Category IV condensing appliances shall be provided with an auxiliary drain pan where damage to any building component will occur as a result of stoppage in the condensate drainage system. Such pan shall be installed in accordance with the applicable provisions of Section 307 of the New York City Mechanical Code and provided with a local alarm to indicate the collection of water.
Exceptions:
1. An auxiliary drain pan shall not be required for appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system.
2. An auxiliary drain pan shall not be required where a suitably sized and located floor drain is provided.
307.6 Condensate pumps.
Condensate pumps located in uninhabitable spaces, such as attics and crawl spaces, shall be connected to the appliance or equipment served such that when the pump fails, the appliance or equipment will be prevented from operating. Pumps shall be installed in accordance with the manufacturer's instructions.
Exceptions:
1. Equipment shutdown shall not be required when the condensate pump resides within the auxiliary drain pan provided under Section 307.5 and an alternate means for unit shutdown due to condensate overflow or leakage, such as a leak detector, is provided.
2. Equipment shutdown shall not be required when the potential for freezing of interior piping systems exists and the auxiliary drain pan provided under Section 307.5 is equipped with a secondary overflow drain that shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain.
307.7 Drain line maintenance.
Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut.
Section FGC 308. Clearance Reduction
This section has 3 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read Section FGC 308 at American Legal Publishing.
308.1 Scope.
This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, appliances, devices and equipment. Clearance requirements for air-conditioning equipment and central heating boilers and furnaces shall comply with Sections 308.3 and 308.4.
308.2 Reduction table.
The allowable clearance reduction shall be based on one of the methods specified in Table 308.2 or shall utilize a reduced clearance protective assembly listed and labeled in accordance with UL 1618. Where required clearances are not listed in Table 308.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrapolation below the range of the table. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance with the requirements of this section except that such clearances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing (see Figures 308.2(1) through 308.2(3)).
Table 308.2 a through k Reduction of Clearances With Specified Forms of Protection
Type of Protection Applied to and Covering All Surfaces of Combustible Material Within the Distance Specified as the Required Clearance With No Protection Where the Required Clearance With No Protection Appliance, Vent Connector, or Single-Wall Metal Pipe is: (inches) 36 18 12 9 6 Allowable clearances with specified protection (inches) Use Column 1 for clearances above appliance or horizontal connector. Use Column 2 for clearances from appliance, vertical connector, and single-wall metal pipe. Above Col. 1 Sides and rear Col. 2 Above Col. 1 Sides and rear Col. 2 Above Col. 1 Sides and rear Col. 2 Above Col. 1 Sides and rear Col. 2 Above Col. 1 Sides and rear Col. 2 1. 3 1/2-inch-thick masonry wall without ventilated airspace — 24 — 12 — 9 — 6 — 5 2. 1/2-inch insulation board over1-inch glass fiber or mineral wool batts 24 18 12 9 9 6 6 5 4 3 3. 0.0296 inch (No. 22 gauge) galvanized sheet metal over 1-inch glass fiber or mineral wool batts reinforced with wire on rear face with ventilated airspace 18 12 9 6 6 4 5 3 3 3 4. 3 1/2-inch-thick masonry wall with ventilated airspace — 12 — 6 — 6 — 6 — 6 5. 0.024-inch (nominal 24 gage) sheet metal with ventilated airspace 18 12 9 6 6 4 5 3 3 2 6. 1/2-inch thick insulation board with ventilated airspace 18 12 9 6 6 4 5 3 3 3 7. 0.024-inch (nominal 24 gage) sheet metal with ventilated airspace over 0.024-inch (nominal 24 gage) sheet metal with ventilated airspace 18 12 9 6 6 4 5 3 3 3 8. 1-inch glass fiber or mineral wool batts sandwiched between two sheets 0.024-inch (nominal 24 gage) sheet metal with ventilated airspace 18 12 9 6 6 4 5 3 3 3
For SI: 1 inch = 25.4 mm, °C = [(°F-32)/1.8], 1 pound per cubic foot = 16.02 kg/m 3 , 1 Btu per inch per square foot per hour per °F = 0.144 W/m 2 K.
a. Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing.
b. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding any intervening protection applied to the combustible material.
c. Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite an appliance or connector.
d. For all clearance reduction systems using a ventilated airspace, adequate provision for air circulation shall be provided as described.
e. There shall be not less than 1 inch between clearance reduction systems and combustible walls and ceilings for reduction systems using ventilated airspace.
f. Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum 1-inch air gap. To provide air circulation, the bottom and top edges, or only the side and top edges, or all edges shall be left open.
g. Mineral wool batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1,500°F.
h. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu per inch per square foot per hour per °F or less.
i. There shall be not less than 1 inch between the appliance and the protector. In no case shall the clearance between the appliance and the combustible surface be reduced below that allowed in this table.
j. All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable.
k. Listed single-wall connectors shall be installed in accordance with the manufacturer's instructions.
Notes:
"A" equals the clearance with no protection.
"B" equals the reduced clearance permitted in accordance with Table 308.2. The protection applied to the construction using combustible materials shall extend far enough in each direction to make "C" equal to "A".
Figure 308.2(1) Extent of Protection Necessary to Reduce Clearances from Appliance or Vent Connections
For SI: 1 Inch = 25.4 mm.
Figure 308.2(2) Wall Protector Clearance Reduction System
For SI: 1 Inch = 25.4 mm.
Figure 308.2(3) Masonry Clearance Reduction System
308.3 Clearances for indoor air-conditioning appliances.
Clearance requirements for indoor air-conditioning equipment shall comply with Sections 308.3.1 through 308.3.4.
308.3.1 Appliance clearances.
Air-conditioning appliances shall be installed with clearances in accordance with the terms of their listing and the manufacturer's instructions.
308.3.2 Clearance reduction.
Air-conditioning appliances shall be permitted to be installed with reduced clearances to combustible material, provided that the combustible material or appliance is protected as described in Table 308.2 and such reduction is allowed by the manufacturer's instructions.
308.3.3 Plenum clearances.
Where the furnace plenum is adjacent to plaster on metal lath or noncombustible material attached to combustible material, the clearance shall be measured to the surface of the plaster or other noncombustible finish where the clearance specified is 2 inches (50.8 mm) or less.
308.3.4 Clearance from supply ducts.
Supply air ducts connecting to listed central heating furnaces shall have the same minimum clearance to combustibles as required for the furnace supply plenum for a distance of not less than 3 feet (914.4 mm) from the supply plenum. Clearance is not required beyond the 3-foot (914.4 mm) distance.
308.4 Central-heating boilers and furnaces.
Clearance requirements for central-heating boilers and furnaces shall comply with Sections 308.4.1 through 308.4.5. The clearance to these appliances shall not interfere with combustion air; draft hood clearance and relief; and accessibility for servicing.
308.4.1 Appliance clearances.
Central-heating furnaces and low-pressure boilers shall be installed with clearances in accordance with the manufacturer's instructions.
308.4.2 Clearance reduction.
Central-heating furnaces and low-pressure boilers shall be permitted to be installed with reduced clearances to combustible material provided that such reduction is allowed by the manufacturer's instructions and the combustible material or appliance is protected as described in Table 308.2.
308.4.3 Clearance for servicing appliances.
Front clearance shall be sufficient for servicing the burner and the furnace or boiler.
308.4.4 Plenum clearances.
Where the furnace plenum is adjacent to plaster on metal lath or noncombustible material attached to combustible material, the clearance shall be measured to the surface of the plaster or other noncombustible finish where the clearance specified is 2 inches (50.8 mm) or less.
308.4.5 Clearance from supply ducts.
Supply air ducts connecting to listed central heating furnaces shall have the same minimum clearance to combustibles as required for the furnace supply plenum for a distance of not less than 3 feet (914.4 mm) from the supply plenum. Clearance is not required beyond the 3-foot (914.4 mm) distance.
Section FGC 309. Electrical
309.1 Grounding.
Gas piping shall not be used as a grounding electrode.
309.2 Connections.
Electrical connections between appliances and the building wiring, including the grounding of the appliances, shall conform to the New York City Electrical Code.
Section FGC 310. Electrical Bonding
310.1 Pipe and tubing.
Each above-ground portion of a gas piping system that is likely to become energized shall be continuously bonded electrically to an effective ground-fault current path. Gas piping shall be considered to be bonded where it is connected to appliances that are connected to the equipment grounding conductor of the circuit supplying that appliance.
Section FGC 401. General
401.1 Scope.
This chapter shall govern the design, installation, modification and maintenance of fuel-gas piping systems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems.
401.1.1 Meters and service piping.
Service piping includes the fuel-gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E. In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code.
401.1.2 Meters for gas consumption monitoring.
Approved gas meters shall be permitted to be installed for gas consumption monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer's instructions. A full size valve bypass shall be provided around gas meters for maintenance and repair.
401.2 Reserved.
401.3 Modifications to existing systems.
In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter.
401.4 Additional appliances.
Where an additional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be provided.
401.5 Identification.
All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked "Gas" in black letters. Where the installation requires a gas test such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served.
401.6 Interconnections.
Where two or more meters are installed on the same premises but supply separate consumers, the piping systems shall not be interconnected on the outlet side of the meters.
401.7 Piping meter identification.
Piping from multiple meter installations shall be marked with an approved permanent identification by the installer so that the piping system supplied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1.
401.8 Minimum sizes.
Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402.
401.9 Identification.
Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identification of the manufacturer.
401.10 Third-party testing and certification.
Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. Piping, tubing and fittings shall either be tested by an approved third-party testing agency or certified by an approved third-party certification agency.