NYC Administrative Code Title 28, Chapter 9 New York City Fuel Gas Code, part 4 of 4

Section FGC 612 to G.7: 70 sections.

Section FGC 612. Recirculating Direct-Fired Industrial Air Heaters

Open this section

612.1 General.

Recirculating direct-fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer's instructions.

612.2 Location.

Recirculating direct-fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct-fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct-fired industrial air heaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat.

612.3 Installation.

Direct-fired industrial air heaters shall be permitted to be installed in accordance with their listing and the manufacturer's instructions. Direct-fired industrial air heaters shall be installed only in industrial or commercial occupancies. Direct-fired industrial air heaters shall be permitted to provide fresh air ventilation.

612.4 Clearance from combustible materials.

Direct-fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer's instructions.

612.5 Air supply.

Air to direct-fired industrial air heaters shall be taken from the building, ducted directly from outdoors, or a combination of both. Direct-fired industrial air heaters shall incorporate a means to supply outside ventilation air to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the main burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation.

612.6 Atmospheric vents, gas reliefs or bleeds.

Direct-fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors.

Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter.

612.7 Relief opening.

The design of the installation shall include adequate provision to permit direct-fired industrial air heaters to operate at rated capacity by taking into account the structure's designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combination of these methods. The structure's designed infiltration rate and the size of relief openings shall be determined by a registered design professional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized dampers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation.

612.8 Controls.

Recirculating direct-fired air heaters shall be equipped with airflow-sensing devices, safety shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing.

Section FGC 613. Clothes Dryers

Open this section

613.1 General.

Clothes dryers shall be tested in accordance with ANSI Z21.5.1/CSA 7.1 or ANSI Z21.5.2/CSA 7.2 and shall be installed in accordance with the manufacturer's instructions.

Section FGC 614. Clothes Dryer Exhaust

Open this section

614.1 Clothes dryer exhaust.

Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code.

Section FGC 615. Sauna Heaters

Open this section

615.1 General.

Sauna heaters shall be installed in accordance with the manufacturer's instructions.

615.2 Location and protection.

Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room.

615.2.1 Guards.

Sauna heaters shall be protected from accidental contact by an approved guard or barrier of material having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room.

615.3 Access.

Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building.

615.4 Combustion and dilution air intakes.

Sauna heaters of other than the direct-vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1/4 inch (6.4 mm) high.

615.5 Combustion and ventilation air.

Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct-vent type shall be provided to the area in which the combustion air inlet and draft hood are located in accordance with Section 304.

615.6 Heat and time controls.

Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an integral part of the sauna heater, the heat-sensing element shall be located within 6 inches (152.4 mm) of the ceiling. If the heat-sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protected against physical damage.

615.6.1 Timers.

A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room.

615.7 Sauna room.

A ventilation opening into the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches (101.6 mm by 203.2 mm) located near the top of the door into the sauna room.

615.7.1 Warning notice.

The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside:

WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA.

The words shall contrast with the background and the wording shall be in letters not less than 1/4 inch (6.4 mm) high.

Exception: This section shall not apply to one- and two-family dwellings.

Section FGC 616. Engine and Gas Turbine-Powered Equipment and Appliances

Open this section

616.1 Powered equipment.

Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer's instructions and NFPA 37. Stationary engine generator assemblies shall meet the requirements of UL 2200.

616.2 Gas supply connection.

Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping.

Section FGC 617. Pool and Spa Heaters

Open this section

617.1 General.

Pool and spa heaters shall be tested in accordance with ANSI Z21.56/CSA 4.7 and shall be installed in accordance with the manufacturer's instructions.

Section FGC 618. Forced-Air Warm-Air Furnaces

Open this section

618.1 General.

Forced-air warm-air furnaces shall be tested in accordance with ANSI Z21.47/CSA 2.3 or UL 795 and shall be installed in accordance with the manufacturer's instructions.

618.2 Forced-air furnaces.

The minimum unobstructed total area of outdoor and return air ducts or openings to a forced-air warm-air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's instructions. The minimum unobstructed total area of supply ducts from a forced-air warm-air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's instructions.

Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer's instructions.

618.3 Dampers.

Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace.

618.4 Prohibited sources.

Outdoor or return air for forced-air heating or forced-air heating and cooling systems shall not be taken from the following locations:

1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet (914.4 mm) above the outside air inlet.

2. Where there is the presence of objectionable odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway.

3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code.

4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces.

Exception: The minimum volume requirement shall not apply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space.

5. A room or space containing an appliance where such a room or space serves as the sole source of return air.

Exception: This shall not apply where:

1. The appliance is a direct-vent appliance or an appliance not requiring a vent in accordance with Section 501.8.

2. The room or space complies with the following requirements:

2.1. The return air shall be taken from a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9.6 L/W) of combined input rating of all fuel-burning appliances therein.

2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volume of return air taken from the space.

2.3. Return-air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space.

3. Rooms or spaces containing solid fuel-burning appliances, provided that return-air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances.

6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned attic.

Exceptions:

1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited.

2. Dedicated forced-air systems serving only a garage shall not be prohibited from obtaining return air from the garage.

7. A crawl space by means of direct connection to the return side of a forced-air system. Transfer openings in the crawl space enclosure shall not be prohibited.

618.5 Screen.

Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1/4-inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1/4 inch (6.4 mm) and not larger than 1 inch (25.4 mm).

618.6 Return-air limitation.

Return air from one dwelling unit shall not be discharged into another dwelling unit.

618.7 Furnace plenums and air ducts.

Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace.

Section FGC 619. Conversion Burners

Open this section

619.1 Conversion burners.

The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD-1, including Appendix C.

Section FGC 620. Unit Heaters

Open this section

620.1 General.

Unit heaters shall be tested in accordance with ANSI Z83.8/CSA 2.6 and shall be installed in accordance with the manufacturer's instructions.

620.2 Support.

Suspended-type unit heaters shall be supported by elements that are designed and constructed to accommodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material.

620.3 Ductwork.

Ducts shall not be connected to a unit heater unless the heater is listed for such installation.

620.4 Clearance.

Suspended-type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches (457.2 mm) at the sides, 12 inches (304.8 mm) at the bottom and 6 inches (152.4 mm) above the top where the unit heater has an internal draft hood or 1 inch (25.4 mm) above the top of the sloping side of the vertical draft hood.

Floor-mounted-type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not less than 6 inches (152.4 mm). Where the flue gases are vented horizontally, the 6-inch (152.4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor-mounted-type unit heaters shall not be installed on combustible floors unless listed for such installation.

Clearances for servicing all unit heaters shall be in accordance with the manufacturer's instructions.

Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer's instructions and as approved by the department.

620.5 Installation in commercial garages and aircraft hangars.

Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11.

Section FGC 621. Unvented Room Heaters

Open this section

621.1 General.

The installation of unvented room heaters is prohibited.

621.2 Reserved.

621.3 Reserved.

621.4 Reserved.

621.5 Reserved.

621.6 Reserved.

621.7 Reserved.

Section FGC 622. Vented Room Heaters

Open this section

622.1 General.

Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accordance with the manufacturer's instructions, and shall be designed and equipped as specified in Section 602.2 of this code.

Section FGC 623. Cooking Appliances

Open this section

623.1 Cooking appliances.

Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1/CSA 6.5, ANSI Z21.58/CSA 1.6 or ANSI Z83.11/CSA 1.8 and shall be installed in accordance with the manufacturer's instructions.

623.1.1 LPG.

Except as may be permitted by the New York City Fire Code, cooking appliances using LPG are prohibited.

623.2 Prohibited location.

Cooking appliances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur.

Exception: Appliances that are also listed as domestic cooking appliances.

623.2.1 Barbecue grills.

Barbecue grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustible building surfaces, balconies and decks.

623.3 Domestic appliances.

Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household-type appliances for domestic use.

623.4 Domestic range installation.

Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label.

623.5 Open-top broiler unit hoods.

A ventilating hood shall be provided above a domestic open-top broiler unit, unless otherwise listed for forced down draft ventilation.

623.5.1 Clearances.

A minimum clearance of 24 inches (609.6 mm) shall be maintained between the cooking top and combustible material above the hood. The hood shall be at least as wide as the open-top broiler unit and be centered over the unit.

623.6 Commercial cooking appliance venting.

Commercial cooking appliances, other than those exempted by Section 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer's instructions or the appliance shall be vented in accordance with Section 505.1.1.

623.7 Domestic ventilation.

When a hood is provided for a domestic cooking appliance, the exhaust and make-up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code. Household cooking appliances shall have a vertical clearance above the cooking top of not less than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches (609.6 mm), measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed:

1. The underside of the combustible material or metal cabinet above the cooking top is protected with not less than 1/4-inch (6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick.

2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less than 1/4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance.

3. A listed cooking appliance or microwave oven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer's installation instructions for the upper appliance.

Section FGC 624. Water Heaters

Open this section

624.1 General.

Water heaters shall be tested in accordance with ANSI Z21.10.1/CSA 4.1 and ANSI Z21.10.3/CSA 4.3 and shall be installed in accordance with the manufacturer's instructions. Water heaters utilizing fuels other than fuel gas shall be regulated by the New York City Mechanical Code. Approval for water heaters 350,000Btu/h input (102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection.

624.1.1 Installation requirements.

The requirements for water heaters relative to sizing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following:

1. No person shall install or maintain in any dwelling unit a gas fuel fired water heater unless the heater obtains combustion air directly from the outside of the building.

2. No person shall install or maintain a gas fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas-fueled heater is installed.

3. Each heater shall be connected to a flue or outlet pipe.

624.2 Water heaters utilized for space heating.

Water heaters utilized both to supply potable hot water and provide hot water for space-heating applications shall be listed and labeled for such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an "H" code stamp. They shall be installed in accordance with the manufacturer's instructions, the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code.

Section FGC 625. Refrigerators

Open this section

625.1 General.

Refrigerators shall be tested in accordance with ANSI Z21.19/CSA 1.4 and shall be installed in accordance with the manufacturer's instructions.

Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer's instructions. If such instructions are not available, not less than 2 inches (50.8 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches (304.8 mm) above the top.

Section FGC 626. Gas-Fired Toilets

Open this section

626.1 General.

Gas-fired toilets are not approved for use in New York City.

626.2 Reserved.

Section FGC 627. Air Conditioning Appliances

Open this section

627.1 General.

Gas-fired air-conditioning appliances shall be tested in accordance with ANSI Z21.40.1/CGA 2.91 or ANSI Z21.40.2/CGA 2.92 and shall be installed in accordance with the manufacturer's instructions.

627.2 Independent piping.

Gas piping serving heating appliances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402).

627.3 Connection of gas engine-powered air conditioners.

To protect against the effects of normal vibration in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1.

627.4 Clearances for indoor installation.

Air-conditioning appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3.

Exceptions:

1. Air-conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer's instructions. Air-conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearances to combustible material, provided that the combustible material is protected in accordance with Table 308.2.

2. Air-conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accordance with such listing and the manufacturer's instructions.

627.5 Alcove and closet installation.

Air-conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air-conditioning appliances in alcoves and closets shall not be reduced by the protection methods described in Table 308.2.

627.6 Installation.

Air-conditioning appliances shall be installed in accordance with the manufacturer's instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of noncombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof.

627.7 Plenums and air ducts.

A plenum supplied as a part of the air-conditioning appliance shall be installed in accordance with the appliance manufacturer's instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The method of connecting supply and return ducts shall facilitate proper circulation of air.

Where the air-conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air.

627.8 Refrigeration coils.

A refrigeration coil shall not be installed in conjunction with a forced-air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duct system and cooling coil at the air throughput necessary for heating or cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace.

Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element.

627.9 Cooling units used with heating boilers.

Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent the chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air-handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.

627.10 Switches in electrical supply line.

Means for interrupting the electrical supply to the air-conditioning appliance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower.

Section FGC 628. Illuminating Appliances

Open this section

628.1 General.

Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer's instructions.

628.2 Mounting on buildings.

Illuminating appliances designed for wall or ceiling mounting shall be securely attached to substantial structures in such a manner that they are not dependent on the gas piping for support.

628.3 Mounting on posts.

Illuminating appliances designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code. Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them.

628.4 Appliance pressure regulators.

Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pressure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance.

Section FGC 629. Ceramic Kilns

Open this section

629.1 General.

Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation.

Section FGC 630. Infrared Radiant Heaters

Open this section

630.1 General.

Infrared radiant heaters shall be tested in accordance with ANSI Z83.19/CSA 2.35 or ANSI Z83.20/CSA 2.34 and shall be installed in accordance with the manufacturer's instructions.

630.2 Support.

Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hanger and brackets shall be of noncombustible material.

630.3 Combustion and ventilation air.

Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggregate input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters.

630.4 Installation in commercial garages and air-craft hangars.

Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11.

Section FGC 631. Boilers

Open this section

631.1 Standards.

Boilers shall be listed in accordance with the requirements of ANSI Z21.13/CSA 4.9 or UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD-1 and as applicable, the ASME Boiler and Pressure Vessel Code, Sections I, II, IV, V, VI and IX and NFPA 85. Low pressure boilers shall conform to the requirements of 12 NYCRR Part 4 and high pressure boilers shall conform to the requirements of 12 NYCRR Part 14.

631.2 Installation.

In addition to the requirements of this code, the installation of boilers shall be in accordance with the manufacturer's instructions and the New York City Mechanical Code. Operating instructions of a permanent type shall be attached to the boiler. Spill switches must be installed on all flue gas draft openings and interlocked with all vented appliances. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer's rating data and the nameplate shall be attached to the boiler.

631.3 Clearance to combustible materials.

Clearances to combustible materials shall be in accordance with Section 308.4.

Section FGC 632. Equipment Installed in Existing Unlisted Boilers

Open this section

632.1 General.

Gas equipment installed in existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer's instructions and the New York City Mechanical Code.

Section FGC 633. Stationary Fuel Cell Power Systems

Open this section

633.1 General.

Stationary fuel cell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI/CSA America FC 1 and shall be installed in accordance with the manufacturer's instructions, NFPA 853, the New York City Building Code, the New York City Fire Code and the New York City Electrical Code. Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706 of this code.

Section FGC 634. Chimney Damper Opening Area

Open this section

634.1 Free opening area of chimney dampers.

Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1.

Table 634.1 Free Opening Area of Chimney Damper for Venting Flue Gasses from Unlisted Decorative Appliances for Installation in Vented Fireplaces

Chimney Height (Feet) Minimum Permanent Free Opening (Square Inches) a 8 13 20 29 39 51 64 Appliance Input Rating (BTU Per Hour) 6 7,800 14,000 23,200 34,000 46,400 62,400 8,000 8 8,400 15,200 25,200 37,000 50,400 68,000 86,000 10 9,000 16,800 27,600 40,400 55,800 74,400 96,400 15 9,800 18,200 30,200 44,600 62,400 84,000 108,800 20 10,600 20,200 32,600 50,400 68,400 94,000 122,200 30 11,200 21,600 36,600 55,200 76,800 105,800 138,600

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645.16 m 2 , 1 British thermal unit per hour = 0.2931 W.

a. The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross-sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64-square-inch opening corresponds to the cross-sectional area of standard 8-inch by 8-inch chimney tile.

Section FGC 635. Gaseous Hydrogen Systems

Open this section

635.1 Installation.

The installation of gaseous hydrogen systems shall be in accordance with the applicable requirements of the New York City Fire Code, the New York City Building Code, and Chapter 7 of this code.

Section FGC 636. Outdoor Decorative Appliances

Open this section

636.1 General.

Permanently fixed-in-place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97/CSA 2.41 and shall be installed in accordance with the manufacturer's instructions.

Section FGC 701. General

Open this section

701.1 Scope.

The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 53 and 58 of the New York City Fire Code. Compressed gases shall also comply with Chapter 50 of the New York City Fire Code for general requirements.

701.2 Permits.

Permits shall be required as set forth in Section 106 and as required by the New York City Fire Code.

Section FGC 702. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FGC 702 at American Legal Publishing.

Section FGC 703. General Requirements

Open this section

703.1 Hydrogen generation.

The generation of gaseous hydrogen for immediate on-premises use in indoor fuel cells or other energy production process and incidental indoor storage of gaseous hydrogen shall be located in accordance with Section 706. Exhaust ventilation shall be required in rooms or spaces that house such generation of gaseous hydrogen in accordance with the applicable provisions of NFPA 2.

Section FGC 704. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FGC 704 at American Legal Publishing.

Section FGC 705. Reserved

Open this section

BetaNYC's copy has no text for this section. Read Section FGC 705 at American Legal Publishing.

Section FGC 706. Location of Gaseous Hydrogen Systems

Open this section

706.1 General.

The location and installation of gaseous hydrogen systems and appliances shall be in accordance with Sections 706.2 and 706.3.

Exception: Outdoor stationary fuel cell power plants in accordance with Section 633.

Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706.

706.2 Indoor gaseous hydrogen systems.

Gaseous hydrogen systems shall be located in hydrogen fuel gas rooms constructed in accordance with the New York City Building Code, the New York City Mechanical Code, the New York City Fire Code and NFPA 2.

706.3 Outdoor gaseous hydrogen systems.

Gaseous hydrogen systems located outdoors shall be in accordance with the New York City Fire Code.

Section FGC 801. General

Open this section

801.1 General.

This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title and the section or sections of this document that reference the standard.

801.2 Subsequent additions, modifications, or deletions.

Refer to the rules of the department for any subsequent additions, modifications or deletions that may have been made to these standards in accordance with Section 28-103.19 of the Administrative Code.

801.3 Applicability.

The application of the referenced standards shall be as specified in Section 102.8.

Section FGC 802. Standards

Open this section

ANSI American National Standards Institute 11 West 42nd Street New York, NY 10036 Standard reference number Title Referenced in code section number ANSI/CSA America FC1—2012 Stationery Fuel Cell Power Systems 633.1 NSF/ANSI 169—2016 Special Purpose Food Equipment and Devices 411.1.1 B109.1—19 Diaphragm-Type Gas Displacement Meters (Under 500 Cubic Feet Per Hour Capacity) 401.1.2 B109.2—00 (R2008) Diaphragm Type Gas Displacement Meters (500 Cubic Feet per Hour Capacity and over) 401.1.2 B109.3—19 Rotary-Type Gas Displacement Meters 401.1.2 Z21.1—2010 Household Cooking Gas Appliances 623.1 Z21.5.1/ CSA 7.1—2014 Gas Clothes Dryers – Volume I – Type 1 Clothes Dryers 613.1 Z21.5.2/ CSA 7.2—2014 Gas Clothes Dryers – Volume II – Type 2 Clothes Dryers 613.1, 614.3 Z21.8—94 (R2002) Installation of Domestic Gas Conversion Burners 619.1 Z21.10.1/CSA 4.1/—2012 Gas Water Heaters – Volume I – Storage, Water Heaters with Input Ratings of 75,000 Btu per Hour or Less 624.1 Z21.10.3/CSA 4.3—2011 Gas Water Heaters – Volume III – Storage, Water Heaters with Input Ratings Above 75,000 Btu per hour, Circulating and Instantaneous 624.1 Z21.13/CSA 4.9—2011 Gas-fired Low-pressure Steam and Hot Water Boilers 631.1 Z21.15/CGA 9.1—09 Manually Operated Gas Valves for Appliances, Appliance Connector Valves and Hose End Valves Table 409.1.1 Z21.18—2007 (R2017) Gas Appliance Pressure Regulators 410.3 Z21.19/CSA 1.4—02 (R2007) Refrigerators Using Gas (R1999) Fuel 625.1 Z21.21/CSA 6.5—05 Automatic Valves for Gas Appliances 603.2 Z21.24/CGA 6.10—06 Connectors for Gas Appliances 411.1, 411.3 Z21.40.1/CGA 2.91—96 (R2011) Gas-fired Heat Activated Air Conditioning and Heat Pump Appliances 627.1 Z21.40.2CGA 2.92—96 (R2011) Gas-fired Work Activated Air Conditioning and Heat Pump Appliances (Internal Combustion) 627.1 Z21.42—2014 Gas-Fired Illuminating Appliances 628.1 Z21.47/CSA 2.3—2012 Gas-fired Central Furnaces 618.1 Z21.50/CSA 2.22—2012 Vented Gas Fireplaces 601.2, 604.1 Z21.54—09 Gas Hose Connectors for Portable Outdoor Gas Fired Appliances 411.1 Z21.56/CSA 4.7—2013 Gas-fired Pool Heaters 617.1 Z21.58/CSA 1.6—2013 Outdoor Cooking Gas Appliances 623.1 Z21.60/CSA 2.26—2012 Decorative Gas Appliances for Installation in Solid-fuel Burning Fireplaces 601.2, 602.1 Z21.69/CSA 6.16—09 Connectors for Movable Gas Appliances 411.1.1, 411.1.4 Z21.75/CSA 6.27—07 Connectors for Outdoor Gas Appliances and Manufactured Homes 411.1, 411.2 Z21.80/CSA 6.22—11 Line Pressure Regulators 410.1 Z21.84—2012 Manually-lighted, Natural Gas Decorative Gas Appliances for Installation in Solid Fuel Burning Fireplaces 602.1, 602.2 Z21.86/CSA 2.32—08 Vented Gas-fired Space Heating Appliances 608.1, 622.1 Z21.88/CSA 2.33—2014 Vented Gas Fireplace Heaters 605.1 Z21.97/CSA 2.41—2012 Outdoor Decorative Appliances 636.1 Z83.4/CSA 3.7—2012 Nonrecirculating Direct-gas-fired Industrial Air Heaters 611.1 Z83.8/CSA 2.6—09 Gas Unit Heater, Gas Packaged Heater, Gas Utility Heaters and Gas-fired Duct Furnaces 610.1, 620.1 Z83.11/CSA 1.8—2013 Gas Food Service Equipment 623.1 Z83.18—00 Recirculating Direct Gas-fired Industrial Air Heaters 612.1 Z83.19/CSA 2.35—01 (R2009) Gas-fired High-intensity Infrared Heaters 630.1 Z83.20/CSA 2.34—08 Gas-fired Low-intensity Infrared Heaters 630.1

ASME American Society of Mechanical Engineers Three Park Avenue New York, NY 10016-5990 Standard reference number Title Referenced in code section number A13.1—2015 Scheme for the Identification of Piping Systems 401.5, 411.1, 411.2, G.5.3 B1.20.1—83 (Reaffirmed 2006) Pipe Threads, General Purpose (inch) 403.9 B16.5—R2009 Pipe Flanges and Flanged Fittings: NPS 1/2 through NFPS 24 Metric/Inch Standard 403.12.2 B16.20—2017 Metallic Gaskets for Pipe Flanges 403.13.1 B16.21—2016 Nonmetallic Flat Gaskets for Pipe Flanges 403.13.2 B16.33—2012 Manually Operated Metallic Gas Valves for Use in Gas Piping Systems up to 125 psig (Sizes 1/2 through 2) Table 409.1.1 B16.42—2011 Ductile Iron Pipe Flanges and Flanged Fittings, Classes 150 and 300 403.12.4 B16.44—2002 (Reaffirmed 2007) Manually Operated Metallic Gas Valves for Use in Aboveground Piping Systems Up to 5 psi Table 409.1.1 B16.47—2011 Large Diameter Steel Flanges: NPS 26 through NPS 60 Metric/Inch Standard 403.12.2 B31.1—12 Power Piping Code G.5.1 B36.10M—2004 Welded and Seamless Wrought-steel Pipe 403.4.2 B40.100—2013 Pressure Gauges and Gauge Attachments 406.4.3 BPVC—2010/2011 addenda ASME Boiler & Pressure Vessel Code 404.21.1, 406.1.1.1, 624.2, 631.1 CSD-1—2012 Controls and Safety Devices for Automatically Fired Boilers 619.1, 631.1

ASNT American Society for Nondestructive Testing PO Box 28518 1/11 Arlington Lane Columbus, OH 43228 Standard reference number Title Referenced in code section number SNT—TC—1A— 2016 Recommended Practice 404.21.1

ASTM ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428 Standard reference number Title Referenced in code section number A 53/A 53M—12 Specification for Pipe, Steel, Black and Hot Dipped Zinc-coated Welded and Seamless 403.4.2 A 106/A 106M—11 Specification for Seamless Carbon Steel Pipe for High-temperature Service 403.4.2 C 64—72 (1977) Withdrawn No Replacement (Specification for Fireclay Brick Refractories for Heavy Duty Stationary Boiler Service) 503.10.2.5 C 315—07 (2011) Specification for Clay Flue Liners and Chimney Pots 501.12 E 136—2012 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C 202 (Noncombustible materials)

CAN/ULC Standards Council of Canada 270 Albert Street, Suite 200 Ottawa ON KIP 6N7 Canada Standard reference number Title Referenced in code section number S635—16 Standard for Lining Systems for Existing Masonry or Factory-Built Chimneys and Vents 501.12, 501.15.4 S640—16 Standard for Lining Systems for New Masonry Chimneys 501.12

CSA CSA Group 8501 East Pleasant Valley Road Cleveland, OH 44131-5516 Standard reference number Title Referenced in code section number ANSI/CSA America FC1—2012 Stationary Fuel Cell Power Systems 633.1

MSS Manufacturers Standardization Society of the Valve & Fittings Industry, Inc. 127 Park Street, N.E. Vienna, VA 22180 Standard reference number Title Referenced in code section number ANSI/SP-58—2009 Pipe Hangers and Supports—Materials Design and Manufacture, Selection, Application and Installation 407.2

NFPA National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 Standard reference number Title Referenced in code section number 2—16 Hydrogen Technologies Code 703.1, 706.2 30A—15 Code for Motor Fuel Dispensing Facilities and Repair Garages 305.4, 305.10 37—15 Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines 616.1, G.3.1.1 54—16 National Fuel Gas Code 501.2.2, 609.9 56PS—12 Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems G.7 68—07 Standard for Explosion Protection by Deflagration Venting E.2.1, G.3.1 69—14 Standard on Explosion Prevention Systems E.2.1, G.2.5.1, G.3.2 72—16* * As modified by Appendix Q of the New York City Building Code National Fire Alarm and Signaling Code G.2.4.3 82—14 Incinerators, Waste and Linen Handling Systems and Equipment 503.2.5, Table 503.4, 607.1 85—15 Boiler and Combustion Systems Hazards Code 631.1 88A—15 Parking Structures 305.9 211—13 Standard for the Chimneys, Fireplaces, Vents and Solid Fuel-burning Appliances 502.1, 503.5.2, 503.5.3, 503.5.6.1, 503.5.6.3 409—11 Standard for the Aircraft Hangars 305.11 853—15 Installation of Stationary Fuel Cell Power Systems 633.1

UL UL LLC 333 Pfingsten Road Northbrook, IL 60062-2096 Standard reference number Title Referenced in code section number 103—2010 Factory-built Chimneys, Residential Type and Building Heating Appliances – with Revisions through July 2012 506.1 441—2010 Gas Vents 502.1 536—2014 Flexible Metallic Hose 405.5 641—2010 Type L Low-temperature Venting Systems – with Revisions through May 2013 502.1 795—2011 Commercial-industrial Gas Heating Equipment 610.1, 618.1, 631.1 959—2010 Medium Heat Appliance Factory-built Chimneys 506.3 1618—2009 Wall Protectors, Floor Protectors and Hearth Extensions – with Revisions through May 2013 308.2 1738—2010 Venting Systems for Gas Burning Appliances, Categories II, III and IV – with Revisions through May 2011 502.1 1777—2007 Standard for Chimney Liners – with revisions through October 2015 501.12, 501.15.4 2034—2008 Standard for Single- and Multiple-Station Carbon Monoxide Alarm – with Revisions through February 2009 303.3.1.2 2075—2013 Standard for Gas and Vapor Detectors and Sensors 303.3.1.3

E.1. General

Open this section

This appendix addresses the requirements for meters and service piping, underground or aboveground, as the piping enters the building. Service piping includes fuel gas piping, valves, and fittings upstream of the point of delivery. Service piping may include piping supplied by the gas service utility.

E.2. Gas regulator and gas regulator vent outlets

Open this section

Gas meter piping supplying gas to a building at a pressure in excess of 1/2 psig (3.4 kPa gauge) shall be provided with a regulator that will reduce the pressure of the gas to 1/2 psig (3.4 kPa gauge) or less prior to entering the gas distribution piping in the building, except where the use of higher pressure is permitted. Where gas distribution pressure in excess of 1/2 psig (3.4 kPa gauge) is permitted, it shall be regulated to not exceed the maximum pressure level as permitted by the code or the commissioner.

E.2.1 Inside gas meter piping operating at a pressure in excess of 15 psig (103.4 kPa gauge) shall comply with the following:

1. Where such piping is greater than 4 inches (101.6 mm) in diameter, the meter piping shall be installed in a properly ventilated meter room of 3-hour fire rated construction.

2. The maximum total developed length from the outlet of the service head valve to the inlet of the farthest regulator shall be limited as follows:

Service Line Valve Size Maximum Distance (Linear Feet of Pipe) Up to 2 inch (51 mm) pipe size 4 feet (1219 mm) Over 2 inch (51 mm) through 4 inch (102 mm) pipe size 8 feet (2438 mm) Over 4 inch (102 mm) through 8 inch (203 mm) pipe size 15 feet (4572 mm) 10 inch (254 mm) pipe size and larger 20 feet (6096 mm)

3. Where these maximum distances cannot be met, the following shall be required:

Footage (Linear Feet of Pipe) in Excess of Above Requirements Additional Requirements Up to 5 feet (1534 mm) The meter room shall have 3-hour fire-rating construction and adequate ventilation Over 5 feet (1524 mm) through 10 feet (3048 mm) Above requirements plus a combustible gas-detection alarm system Over 10 (3048 mm) feet through 15 feet (4572 mm) Above requirements plus special inspection by the customer or his representative as required by the New York City Building Code. Over 15 feet (4572 mm) through 20 feet (6096 mm) Above requirements plus (i) automatic gas shutoff devices; and (ii) explosion venting per NFPA 68 and NFPA 69 or alternative ventilation acceptable to the commissioner Over 20 feet (6096 mm) Above requirements plus suitable fire protection approved by the commissioner

For new gas installations made in existing structures, the above requirements shall be used to the extent feasible. Alternate designs may be considered by the commissioner.

E.2.2 When located inside the building, each regulator shall be provided with a vent pipe that leads directly to the outdoor air. The vent pipe shall be sized according to local utility requirements. The vent outlet shall not be located under a window or any opening leading back into the premises or located below any overhang or projection. No gas regulator vent outlet shall be covered over, plugged up, or otherwise obstructed, and all gas vents shall be identified by suitable marking on the outlet on the outside of the building. For buildings located in flood hazard areas, gas regulator vent outlets shall be installed in accordance with the additional requirements of Appendix G of the New York City Building Code.

E.3. Gas meter location

Open this section

Gas meter location shall comply with the following:

1. When located inside the building, meters shall be located as near as practicable to the point of entrance of the service and, where possible, the meters shall be located in the cellar or basement unless otherwise permitted by the commissioner. The meter location shall be clean, dry, and free of refuse, steam or chemical fumes and located not less than 3 feet (914.4 mm) from any source of ignition or any source of heat which might cause damage to the meter. Meters shall be adequately protected against extreme cold or heat and shall be readily accessible for reading and inspection. The area in which the meter is located shall be properly ventilated as per Section E.4. Notwithstanding the foregoing, outside meter installation shall be permitted in areas where the utility company certifies that dry gas is being distributed.

Exception: Gas meter locations in one- and two-family dwellings shall not require ventilation.

2. No gas meter, other than the replacement of an existing meter shall be located in any boiler room or other room or space containing a heating boiler, in any stair hall, nor in any public hall above the cellar or above the lowest story if there is no cellar.

3. Gas meter rooms, when provided, shall at all times be kept clear of all rubbish; and shall not be used in any way for storage purposes, including material or equipment of any kind. A legible sign reading "Gas meter room – No storage permitted" shall be permanently and conspicuously posted on the exterior of the meter room door, except that the sign may be posted on the interior of the meter room door in occupancy group R-3. The lettering of such signs shall be of bold type at least one inch (25.4 mm) in height and shall be properly spaced to provide good legibility. The lettering and background shall be of contrasting colors. Where gas meters and related equipment are not located in a separate room but are located in an open floor area, no combustible material shall be stored or kept within five feet of such equipment; nor shall the gas meter be within 3 feet (914.4 mm) of any heating boiler or sources of ignition and, except occupancy group R-3, there shall be a physical barrier required if the room is also used for storage purposes or the like.

4. The installation of gas meter piping shall be made in accordance with the requirements of this code and the local utility company.

5. Piping containing gas with a pressure exceeding 1/2 psig (3.4 kPa gauge) and the gas service pressure regulator which may be subjected to accidental vehicular impact shall be suitably protected.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

E.4. Gas meter room ventilation

Open this section

Any one of the following methods shall be considered sufficient to provide proper ventilation to a room or space in which a gas meter(s) is installed:

1. An opening to the outside air in the wall of such room or space, provided the free area of the opening is not less than 30 square inches (19 321 mm 2 ).

2. A duct or pipe having a cross-section area of at least 50 square inches (32 522 mm 2 ) of free area and a maximum length of 15 feet (4572 mm) leading to the outside air. However, under no circumstances shall the means of ventilation for the gas meter room or space be from an adjoining room or space within the building.

E.5. Gas service piping connections

Open this section

Gas service piping connections shall comply with the following:

1. Gas service piping shall be fitted with a gas service line valve, the valve located on the supply side of the meter and service regulator, if a service regulator is required. Where a plug type valve is used, it shall be constructed so as to prevent the core from being blown out by the pressure of the gas. In addition, it shall be of a type capable of being locked in the off position by the local gas utility. Where the gas service line valve is inside the building, it shall be in an accessible location within 2 feet (609.6 mm) of the point where the gas service connection enters the building or at such other location as may be permitted by the commissioner. Where the gas service connection is installed through a building wall below ground, it shall be protected with a wall sleeve extending at least 4 inches (101.6 mm) beyond the outer side of the wall and at least 1 inch (25.4 mm) beyond the inner side of the wall. The sleeve shall be sealed at both ends to prevent the entry of water and gas. Gas service connections, installed through ground slab construction, shall be protected with a floor sleeve sealed at both ends to prevent the entry of water and gas. The sleeve shall extend at least 4 inches (101.6 mm) above the floor, and shall be installed as specified by the utility company providing the service. It shall terminate at least 4 inches (101.6 mm) outside the building.

2. In all high-pressure areas, the utility company providing the service may inspect the gas service line valve and regulator in accordance with the provisions of 16 NYCRR Part 255 in addition to the department in accordance with Section 406 of this code.

3. No gas service shall enter a structure at a horizontal distance of less than 10 feet (3048 mm) from the cellar termination of a stairway, nor shall any gas meters or gas regulators be located less than 10 feet (3048 mm) from such stairway termination. Where such services, meters and regulators are separated from the stairway termination by a permanent partition or wall having a fire-resistance rating of at least 1 hour, the foregoing shall not apply. Unless forbidden by other provisions of this code, locations under a stairway are exempt from this requirement.

4. When the structure is erected on fill or on piles, provision shall be made to preclude possible damage to the gas service piping caused by settlement.

5. The installation of gas service piping shall be made in accordance with the requirements of the utility corporation providing the service as regulated by the provisions of 16 NYCRR Part 255. Further, such installation shall meet the requirements of the department.

6. Gas service piping outside a structure shall be installed not less than 24 inches (609.6 mm) below grade, except that a lesser distance of not less than 18 inches (457.2 mm) may be permitted, provided the piping is adequately protected in accordance with the requirements of this code and the utility corporation supplying service, and the piping is not located below a driveway. Any piping that is exposed to outdoor temperatures or installed underground with a cover of less than 2 feet (609.6 mm) shall be protected against frost, except that frost protection may be omitted in areas where the utility company certifies that dry gas is being distributed.

E.6. Outside gas cut-off

Open this section

Outside gas cut-off shall comply with the following:

1. An outside gas service line valve or other outside emergency shut-off device or other means acceptable to the commissioner and the Fire Commissioner shall be installed in every gas service pipe outside the building. If buried, such valve, device or method shall be readily accessible from grade. Every existing service which is being replaced or refurbished shall be provided with such valve, device or means, but in any event, all existing gas services shall be provided with such valve, device or method by January 1, 2010. However, in Group R-3 occupancy the completion date shall be January 1, 2020. The utility company shall provide the Fire Department with suitable tools for operation of such emergency shut-off valves, devices or means. The number of such tools required for supplying Fire Department units shall be determined by the Fire Department. On or before January 31, of each year, the utility company shall report to the department and the Fire Department the actual number of emergency shut-off valves installed for the preceding year.

2. If the outside gas service line valve, emergency shut-off device or means is located below ground, it shall be installed in a protective housing, and an easily identifiable cover shall be provided for the housing. The cover shall be flush with the surface of the ground and kept clear at all times so as to be accessible for immediate use.

3. The valve or emergency shut-off device shall be capable of being readily operated by removing the cover of the housing and inserting a portable key or other device over the operating end of the valve or emergency shut-off device.

4. If the outside gas service line valve is located above ground, it shall be suitably protected to prevent accidental vehicular impact and must be installed in accordance with provisions of 16 NYCRR Part 255.

5. Where a gas-fired generator provides required emergency power in accordance with the New York City Building Code, such generator shall have an outside gas cut-off valve that is separate from other gas services to the buildings. Such valves shall be identified by signage.

G.1. General

Open this section

This Appendix addresses natural gas distribution piping requirements for systems where the gas pressure is at or above 15 psig (103.4 kPa gauge). Installations of gas piping at pressures at or above 15 psig (103.4 kPa gauge) and equipment and appliances using gas with an inlet pressure at or above 15 psig (103.4 kPa gauge) shall be considered as high pressure natural gas installations.

G.1.1. Fire Department approval

Open this section

High pressure natural gas installations shall be approved by the Fire Department. All design documents associated with the installation shall be submitted to the Fire Department for approval. The Fire Department shall witness and approve final testing of the installation.

G.1.2. Certificate of fitness

Open this section

High pressure natural gas installations shall be operated under the supervision of a person holding a Certificate of Fitness issued by the Fire Department when required by the New York City Fire Code.

G.2. Construction requirements

Open this section

Buildings with high pressure natural gas installations shall meet the requirements of this section.

G.2.1. Structural requirements

Open this section

The structural integrity of the building shall meet the requirements of Section 1615.6 of the New York City Building Code for gas explosions. An explosion analysis shall be conducted where the gas pressure exceeds 125 psig (861.8 kPa gauge). Where an explosion analysis shows explosion pressure exceeding 430 psf (20.5 kPa gauge), the building's structural integrity shall be maintained at pressure levels determined by the explosion analysis. The explosion scenario and explosion analysis shall be approved by the Fire Department.

G.2.2. Fire-resistance-rated rooms and spaces

Open this section

Rooms and spaces containing high pressure natural gas piping shall be separated from all other areas of the building by fire barriers or horizontal assemblies, or both, having a fire-resistance rating of not less than 3 hours.

G.2.2.1. Shaft requirements

Open this section

Vertical runs of high pressure gas piping within a building shall be enclosed in masonry shafts constructed of walls not less than 4 inches (101.6 mm) in thickness and sealed to prevent any gas leakage from the shaft. Such shaft shall be vented to the outdoors at the top. Such shaft shall not be located adjacent to an exit stairway or exit passageway unless the shaft wall separating the exit stairway or exit passageway from the shaft is designed to resist a potential gas explosion in accordance with Section 1615.6 of the New York City Building Code.

G.2.3. Automatic sprinkler system

Open this section

Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code, except where an alternative fire-extinguishing system is approved in accordance with the New York City Fire Code and the New York City Building Code.

G.2.4. Gas detection

Open this section

Rooms and spaces containing high pressure gas piping must be equipped with an approved and listed gas detection alarm system.

G.2.4.1. Gas detection system

Open this section

A gas detection system including placement of gas detectors shall be installed in accordance with the manufacturer's recommendations, its listing and Section 908 of the New York City Building Code.

G.2.4.2. Supervision

Open this section

Gas detectors shall be supervised by a building fire alarm system in buildings where fire alarm systems are required or installed.

G.2.4.3. Power supply

Open this section

Power supply to the system, wiring of the system, its associated components and outputs shall be in accordance with NFPA 72 as modified by Appendix Q of the New York City Building Code and Section 907 of the New York City Building Code.

G.2.4.4. Alarm

Open this section

An audible and visual alarm shall be provided at the gas detection panel with an audible silence switch only.

G.2.4.5. Alarm transmission

Open this section

The gas detection system shall transmit a trouble signal and an alarm to the supervising station and to a 24-hour supervised location within the building.

G.2.4.6. Shutoff valves closure

Open this section

The gas detection system alarm activation shall trigger emergency gas shutoff valves serving the affected area to close and stop the gas flow.

G.2.5. Ventilation

Open this section

Rooms containing appliances or equipment operating with gas pressure at or above 15 psig (103.4 kPa gauge) shall be provided with ventilation in accordance with the requirements of Chapter 4 of the New York City Mechanical Code.

G.2.5.1. Explosion prevention

Open this section

For rooms or spaces containing appliances operating with gas pressure at or above 15 psig (103.4 kPa gauge) and less than 125 psig (861.8 kPa gauge), explosion prevention systems shall be provided in accordance with NFPA 69.

G.3. High hazard

Open this section

Rooms and areas containing appliances and equipment operating with gas pressure at or above 125 psig (861.8 kPa gauge) shall be classified as a Group H-2 occupancy and shall comply with the requirements of this section.

G.3.1. Explosion venting

Open this section

Appliances and equipment using gas at or above 125 psig (861.8 kPa gauge) shall be located in rooms provided with explosion venting in accordance with NFPA 68.

G.3.1.1. Gas turbines

Open this section

Gas turbine installations shall comply with the requirements of NFPA 37 and the requirements of Title 28 of the Administrative Code.

G.3.1.2. Gas turbine rooms

Open this section

For rooms containing gas turbines and fuel gas compressors, the design of the explosion venting system shall be based on the explosion resulting from the lower explosion limit being achieved within the room housing the turbine or fuel gas compressor, including its enclosure. All control valve stations, filters, and related accessories shall be placed in the gas turbine room or a separately protected room.

G.3.2. Emergency ventilation

Open this section

An emergency ventilation system shall be provided in accordance with NFPA 69 and shall be approved by the Fire Department. Ventilation calculations as listed in Annex D Ventilation Calculations of NFPA 69 shall be provided, and the gas release rate shall be approved.

G.3.3. Electrical equipment

Open this section

Electrical equipment within rooms and enclosures requiring emergency ventilation shall conform to the New York City Electrical Code for Class 1 Division 2 requirements.

G.4. Gas meter room

Open this section

A gas meter room served by gas at a pressure at or above 15 psig (103.4 kPa gauge) shall meet the requirements of the New York City Electrical Code for Class 1 Division 2 requirements, and shall comply with Appendix E of this code.

G.5. Piping requirements

Open this section

High pressure gas piping shall comply with the requirements of this section.

G.5.1. Piping material

Open this section

Installations of natural gas piping operating at pressures of 125 psig (861.8 kPa gauge) and above shall comply with the requirements of ASME B31.1.

(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.

G.5.2. Double wall piping

Open this section

Horizontal piping that traverses within a building from a protected room or shaft to a protected room or shaft shall be run in an outer pipe of the same pressure rating as the inner pipe. The outer pipe shall be welded and the annular space between the inner and outer pipe shall be equal to or greater than the inside diameter of the inner pipe. The annular space shall be monitored for natural gas with an approved gas detection alarm system and shall be vented to the exterior of the building. The outer pipe must open to the shaft and/or protected room or to the outside air.

G.5.3. Piping identification

Open this section

Piping shall be identified with markings in accordance with ASME A13.1.

G.5.4. Emergency gas shutoff

Open this section

An emergency gas shutoff valve shall be provided on the gas supply outside of any room containing an appliance utilizing gas at a pressure at or above 15 psig (103.4 kPa gauge). The emergency shutoff valve shall be controlled from a break glass station located outside the room served and from the gas detection system monitoring the room. The emergency shutoff valve shall automatically stop the gas flow to the room(s) containing the appliance(s) in the event of an unsafe condition. The emergency shutoff valve shall be manually operable. Emergency gas shutoff valve bypasses shall be prohibited.

G.6. Special inspection required

Open this section

The entire high pressure natural gas installation, including piping, equipment, appliances, gas detection and control systems, shall be subject to special inspection as set forth in Section 1705.24 of the New York City Building Code.

G.7. Cleaning and purging procedures

Open this section

Cleaning and purging procedures for high pressure natural gas piping, equipment and appliances shall be in accordance with NFPA 56.