NYC Administrative Code G.3.1.2 Gas turbine rooms

For rooms containing gas turbines and fuel gas compressors, the design of the explosion venting system shall be based on the explosion resulting from the lower explosion limit being achieved within the room housing the turbine or fuel gas compressor, including its enclosure. All control valve stations, filters, and related accessories shall be placed in the gas turbine room or a separately protected room.