1 RCNY Chapter 7000 Mechanical Code

§ 7000-01. National Fire Protection Association, Flammable Combustible Code Edition Amendment. [Repealed]

Open this section

(Repealed City Record 1/22/2018, eff. 2/21/2018)

§ 7011-01. A2L Refrigerating Systems

Open this section

(a) Scope. Pursuant to footnote c of Table 1103.1 of the New York City Mechanical Code (MC), all refrigerating systems utilizing refrigerants classified into safety group “A2L” by the 2022 edition of American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 34 installed after the effective date of this rule must comply with the requirements of this section.

(b) References. See MC Sections 102.4, 1101.6, 1101.8, 1101.11, 1102.2, 1104.2, 1105.3, 1105.7, 1105.8, 1105.9, 1105.11 and 1108.1

(c) General.

(1) Applicability. Group A2L refrigerating systems must conform to the specific provisions of the 2022 edition of ASHRAE 15 as adopted and modified by 1 RCNY § 7015-02. ASHRAE 15 provisions apply pursuant to Section MC 102.8. Except otherwise stated, ASHRAE 15 does not apply to residential refrigeration systems complying with ASHRAE 15.2 as modified by 1 RCNY § 7015-03.

(2) Changing refrigerant. Refer to ASHRAE 15 Section 5.3.

(3) Signs, nameplates, and operation and emergency shut-down instructions. Signs and identification for Group A2L refrigerant must comply with ASHRAE 15 Section 10.1. Emergency shutdown procedures, including instructions, must comply with ASHRAE 15 Section 10.6. Nameplates must comply with ASHRAE 15 Section 9.17.

(d) System requirements.

(1) Refrigerants. Refrigerants having a Safety Group Classification of A2L not identified in MC Table 1103.1, but listed in ASHRAE 34 Table 4-1 and 4-2, are not required to be approved by the department before use.

(2) Refrigerant Detection System Requirements. When required by Section 7.6.2.3 of ASHRAE 15 for refrigeration systems for human comfort applications or Section 7.7.3.3 of ASHRAE 15 for refrigeration systems other than human comfort applications, refrigeration systems having refrigerants in Safety Group Classification A2L must have an integral refrigerant detection system. Such refrigerant detection systems must comply with Section 7.6.2.4 of ASHRAE 15.

(3) Mitigation Action Requirements. Mitigation actions must be provided in accordance with section 7.6.2.5 of ASHRAE 15.

(4) Release Mitigation Controls. Release mitigation controls may be used to reduce the releasable charge in accordance with 7.3.4 and 7.6 of ASHRAE 15 such that the Mitigation Releasable Refrigerant Charge (Mrel) as calculated in 7.3.4.3 is less than or equal to the Effective Dispersal Volume Charge (EDVC) calculated in 7.6.

(e) Refrigeration system classification. Refrigerants in safety group “A2L” must be classified in ASHRAE 34, Table 4-1 and 4-2.

(f) System application requirements.

(1) Refrigerant restrictions. The use of the term “natural ventilation” in Section 7 of ASHRAE 15 is not construed to require outside air.

(2) Allowable refrigerant charges for human comfort. Allowable refrigerant charge volumes for high-probability direct systems utilizing A2L refrigerants must be calculated in accordance with ASHRAE 15, Section 7.6. For a space having only recirculating air conditioning unit(s), with no adjoining spaces and with no outside air introduced by ductwork, ASHRAE 15 section 7.6.1.2 must be used to calculate the maximum refrigerant charge of such unit’s independent circuit in conjunction with the definition of “Air Circulation” in 1 RCNY § 7015-02.

(3) Allowable refrigerant charges for other than human comfort. Allowable refrigerant charge volumes for high-probability direct systems utilizing A2L refrigerants must be calculated in accordance with ASHRAE 15 Section 7.7.

(g) Machinery room.

(1) Machinery room. Where refrigerants in safety group A2L are used in machinery rooms, such machinery rooms must be designed to comply with the applicable requirements of Section 8.9 and 8.11 of ASHRAE 15.

(2) Emergency pressure control system. Permanently installed refrigeration systems containing more than 6.6 pounds (3 kg) of A2L refrigerant are not required to be provided with an emergency pressure control system.

(3) Refrigerant detector. When refrigerants in safety group A2L are used, the machinery room must be provided with a refrigerant detection system in accordance with Section 8.11 of ASHRAE 15 and the following:

(i) An emergency alarm “FDNY Alarm” must generate an output signal in no more than 30 seconds when exposed to a refrigerant concentration exceeding 25% of the lower flammability limit (LFL) or when it reaches the upper detection limit of the refrigerant detector, whichever is lower, start level 2 ventilation in accordance with ASHRAE 15, and automatically de-energize the following equipment in the machinery room:

(A) Refrigerant compressors,

(B) Refrigerant pumps,

(C) Normally closed automatic refrigerant valves,

(D) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating.

(ii) A trouble Alarm “FDNY Fault” must generate an output signal when the detection of refrigerant concentration reaches a concentration equal to the occupational exposure limit (OEL) value for such refrigerant as published in ASHRAE 34 and start level 1 ventilation in accordance with ASHRAE 15.

(iii) A supervisory alarm “FDNY Supervisory” must generate an output signal when the detector identifies a malfunctioning component within the system that needs immediate attention.

(iv) The set points for “trouble alarm” and “emergency alarm” must be in accordance with Table 8-1 of ASHRAE 15.

(v) All alarms must annunciate at both a refrigerant detection panel inside the machinery room and at an annunciator panel located outside the machinery room. The annunciator panel located outside the machinery room must display the same information in the panel located inside the machinery room and be installed within 10 feet of the machinery room entrance door, on the premises.

(vi) When refrigerant detectors are installed in buildings without fire alarm systems, such refrigerant detection system must be monitored at a continuously attended location, on the premises, by a person holding a Certificate of Fitness issued by the New York City Fire Department (“FDNY”) or by an FDNY approved central supervising station with refrigerant detection alarm, supervisory, and trouble signals being transmitted as separate and distinct signals to such FDNY approved central station.

(vii) When refrigerant detectors are installed in buildings with fire alarm systems, such refrigerant detector system may be used in multi-hazard applications.

(viii) When refrigerant detectors are installed in buildings with a building-wide fire alarm system, the refrigerant detector control panel must be monitored by such building-wide fire alarm system and the following signals must be transmitted to the building-wide fire alarm control panel (fire command center or station):

(A) Emergency Alarm “FDNY Alarm”

(B) Supervisory signal “FDNY Supervisory”

(C) Trouble Alarm “FDNY Fault”

Each alarm input to the control unit, whether emergency, supervisory or trouble alarm, must be transmitted to the building-wide fire alarm control panel (fire command center or station) at a discrete point, if the building-wide fire alarm system is capable, and the location of an operated initiating device must be visibly indicated by floor, fire zone, or other approved subdivision.

(ix) Where a building is provided with emergency power, refrigerant detection systems must be connected to such emergency power. Where a building is not otherwise provided with emergency power, the power source for emergency power to a refrigerant detection system must be served by an uninterruptable power source (UPS).

(h) Refrigerant piping safety for all group A2L refrigerating systems. Where refrigerant piping penetrates floors, ceilings, or roofs pursuant to Section 1107.2.3 of the NYC Mechanical Code, it must comply with the requirements of paragraphs (1) through (5) of this subdivision.

(1) Refrigerant piping systems, including but not limited to stop valve, and piping identification must comply with the requirements of ASHRAE 15 section 9.12.

(2) Refrigerant quantity limits must comply with the requirements of ASHRAE 15 section 7.6 or 7.7.

(3) Effective dispersal volume (EDV) calculations for rooms not connected to other spaces must comply with section 7.2.3.1 of ASHRAE 15 and must be performed for all spaces other than shafts through which refrigerant piping passes, regardless of whether such space is served by the system.

Exception: Rooms not connected to other spaces are exempt from EDV calculation in accordance with section 7.2.3.1 if such refrigerant piping and fittings are enclosed in an outer sleeve consisting of piping of the same material. The outer sleeve must be able to hold the design working pressure of the system. Press-fit couplings may be used. In addition to the outer containment piping, refrigerant piping must be further enclosed in construction having a 2-hour fire-resistance rating.

(4) EDVC calculation in connected spaces.

(i) Where spaces are connected via natural ventilation, the size of the opening and EDVC must be calculated in accordance with ASHRAE 15 section 7.2.3.2

(ii) Where spaces are connected via ducted air distribution system, the EDVC must be calculated in accordance with ASHRAE 15 section 7.2.3.3

(iii) Where spaces are connected via mechanical ventilation, the EDVC must be calculated in accordance with ASHRAE 15 section 7.2.3.4

(5) Location. Refrigerant piping for Group A2L refrigerants must comply with the location requirements of Section 9.12 of ASHRAE 15.

Exception: Refrigerant piping for Group A2L refrigerant may be installed in public corridors if such refrigerant piping and fittings are enclosed in an outer sleeve consisting of piping of the same material. The outer sleeve must be able to hold the design working pressure of the system. Press-fit couplings may be used. In addition to the outer containment piping, refrigerant piping must be further enclosed in construction having a 2-hour fire-resistance rating.

(i) Testing and inspection.

(1) Testing of refrigerating system and its components must be performed in accordance with ASHRAE 15 section 9.13 and 9.14. Such test must be witnessed by a special inspector.

(2) Special inspections must be conducted in accordance with 2022 NYC Building Code 1705.21.

(Added City Record 4/15/2026, eff. 5/15/2026)

§ 7015-01. Referenced Standards

Open this section

Pursuant to § 28-103.19 of the New York City Administrative Code, delete and replace the following reference standards as follows:

Reference standard ACCA Manual D as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new ACCA Manual D is added to read as follows:

ACCA Air Conditioning Contractors of America 2800 Shirlington Road, Suite 300 Arlington, VA 22206 Standard Reference Number Title Referenced in code section number ANSI/ACCA 1 Manual D -2016 Residential Duct Systems 603.2

Reference standard AHRI 700 as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new AHRI 700 is added to read as follows:

AHRI Air-Conditioning, Heating and Refrigeration Institute 4100 North Fairfax Drive, Suite 200 Arlington, VA 22203 Standard Reference Number Title Referenced in code section number 700 -2019 Standard for Specifications for Refrigerants 1102.2.2.3

Reference standard ASME CSD-1 as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new ASME CSD-1 is added to read as follows:

ASME American Society of Mechanical Engineers Three Park Avenue New York, NY 10016-5990 Standard Reference Number Title Referenced in code section number CSD-1 -2012 Controls and Safety Devices for Automatically Fired Boilers 1004.1, 1004.1.1, 1004.8, 1006.1, 1006.2, 1006.3, 1006.4, 1007.1, 1007.2, 1007.3, 1010.2.1, 1011.1

Reference standard NFPA 54 as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new NFPA 54 is added to read as follows:

NFPA National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 Standard Reference Number Title Referenced in code section number 54 -2018 National Fuel Gas Code 504.9, 901.2, 910.7

Reference standard NSF 358-1 as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new NSF 358-1 is added to read as follows:

NSF NSF International 789 Dixboro Road, P.O. Box 130140 Ann Arbor, MI 48113-0140 Standard Reference Number Title Referenced in code section number NSF 358-1 -2014 Polyethylene Pipe and Fittings for Water-Based Ground-Source “Geothermal” Heat Pump Systems Table 1210.4, Table 1210.5

Reference standard SMACNA as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new SMACNA is added to read as follows:

SMACNA Sheet Metal & Air-Conditioning Contractors National Association, Inc. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 Standard Reference Number Title Referenced in code section number SMACNA -2021 Fibrous Glass Duct Construction Standards 603.5

Reference standard UL 2158A as added by Section MC 1502 of the New York City Mechanical Code is hereby deleted and a new UL 2158A is added to read as follows:

UL UL LLC 333 Pfingsten Road Northbrook, IL 60062-2096 Standard Reference Number Title Referenced in code section number 2158A -2017 Standard for Clothes Dryer Transition Duct 504.8.3

(Added City Record 11/15/2023, eff. 12/15/2023)

§ 7015-02. American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 15 Amendment Relating to the Installation of Refrigerating Systems Utilizing Refrigerants Classified into Safety Group “A2L"

Open this section

Pursuant to Section 28-103.19 of the New York City Administrative Code, the Department of Buildings adopts the 2022 edition of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 15 Safety Standard for Refrigeration Systems as it pertains to the installation of refrigerating systems utilizing refrigerants classified into safety group “A2L” in residential applications and amends it to read as follows:

Delete and replace the definitions in Section 3.1 of air circulation and safety shutoff valve, as follows:

Air circulation: mechanically inducing airflow within spaces connected by air ducts.

Safety shutoff valve: an automatically controlled refrigerant valve for the purpose of limiting the amount of refrigerant released into a space when a refrigerant leak is detected. Valves must be designed to close in an event of an electric power failure.

Revise Section 7.2.3.4 to read as follows:

7.2.3.4 Connected Spaces via Mechanical Ventilation. Where two or more spaces are connected by a mechanical ventilation system complying with the requirements of section 7.6.4, the volume of all such connected spaces must be included in the effective dispersal volume used to calculate the EDVC.

Revise Section 7.6.2.4 (g) to read as follows:

g. Generate an output signal in not more than 30 seconds when exposed to a refrigerant concentration at or exceeding 25% of the LFL (+0%, –1%).

(Added City Record 4/15/2026, eff. 5/15/2026)

§ 7015-03. American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 15.2 Amendment Relating to the Installation of Refrigerating Systems Utilizing Refrigerants Classified into Safety Group “A2L” in Residential Applications

Open this section

Pursuant to Section 28-103.19 of the New York City Administrative Code, the Department of Buildings adopts the 2022 edition of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 15.2 Standard and Addenda a, b, c, d, f, g and h of the 2022 edition of ASHRAE 15.2 Safety Standard for Refrigeration Systems in Residential Applications as it pertains to the installation of refrigerating systems utilizing refrigerants classified into safety group “A2L” in residential applications and amends it as follows:

Revise Section 2.1 to read as follows:

2.1 This standard applies to listed refrigeration systems in one- and two-family dwellings in group R3 buildings that are limited to serving only a single dwelling unit or sleeping unit. Where a residential refrigeration system utilizing A2L refrigerants exceeds the charge limits or other applicability criteria of ASHRAE 15.2, the system must comply with ASHRAE 15.

Delete paragraphs a, b, and c and replace with the following: DELETED.

(Added City Record 4/15/2026, eff. 5/15/2026)

§ 7015-04. American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 34 Addenda Amendment Relating to the Designation and Safety Classification of Refrigerants

Open this section

Pursuant to Section 28-103.19 of the New York City Administrative Code, the Department of Buildings adopts the 2022 edition of Addenda a, d, e, f, i, n, o, r, s, v, w and al of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (“ASHRAE”) 34 as it pertains to the Designation and Safety Classification of refrigerants.

(Added City Record 4/15/2026, eff. 5/15/2026)