NYC Administrative Code Title 28, Chapter 12 The New York City Existing Building Code (effective July 17, 2027), part 2 of 5
Section EBC 502 to Section EBC 805: 31 sections.
Section EBC 502. Compliance
502.1 General.
All limited alteration work shall comply with this code and other codes as applicable.
502.2 Applicants for permits.
Applicants for limited alteration permits shall meet the minimum qualifications appropriate for the work filed in accordance with Articles 408, 410, 412, 418, and 421 of Title 28 of the Administrative Code and this code.
502.3 New and replacement materials, assemblies and details.
New and replacement materials, assemblies and details permitted by the applicable code for new construction shall be used in accordance with Section 302.4.
Exception: Provided no unsafe condition is created, like materials, assemblies and details shall be permitted for limited alterations.
502.4 Inspections.
All work associated with limited alterations shall be tested and inspected in accordance with the applicable provisions of this code, the Administrative Code, the New York City Building Code, the New York City Plumbing Code, the New York City Fuel Gas Code, the New York City Mechanical Code, the New York City Electrical Code, the New York City Fire Code and the New York City Energy Conservation Code, including their referenced standards, as applicable.
502.5 Emergency work.
Emergency work shall be in accordance with Section 28-105.4.1 of the Administrative Code.
502.6 Construction documents.
The department may promulgate rules to establish construction document submission requirements for limited alteration applications relating to demonstrating compliance with the applicable requirements.
502.7 Penetrations of floor/ceiling assemblies and fire-resistance-rated assemblies.
Where penetrations of floor/ceiling assemblies and assemblies required to have a fire-resistance rating are required as part of a limited alteration application scope of work, such penetrations shall be protected in accordance with the requirements of Sections 502.7.1 through 502.7.6. Where such penetrations cannot be protected in accordance with the requirements of Sections 502.7.1 through 502.7.6, the work shall not be permitted under a limited alteration application.
502.7.1 Stair enclosures.
Penetrations through a stair enclosure or a stair landing shall not be permitted as part of a limited alteration application.
Exceptions:
1. Limited standpipe alteration work pursuant to Section 506.
2. Limited sprinkler alteration work pursuant to Section 505.
502.7.2 Prescriptive methods.
Penetrations of floor/ceiling and wall assemblies required to have a fire-resistance rating by steel, ferrous or copper conduits, pipes, tubes, or vents no greater than 6 inches (152 mm) in diameter with a total cross-sectional area of opening of 144 square inches (92 903 mm 2 ) or less shall be permitted to be sealed by 1 of the following methods without certification by a manufacturer of those performing the installation:
1. Concrete or masonry walls or floors. The annular space around penetrations in a single concrete or masonry wall/floor by steel, ferrous or copper conduits, pipes, tubes or vents shall be sealed with concrete, grout or mortar installed through the full thickness of the floor or the thickness required to maintain the fire-resistance rating.
2. For walls and floors in prior code buildings. In prior code buildings, the annular space around penetrations through walls and floors shall be permitted to be of materials and thickness matching the adjacent existing construction in a manner in which they can be shaped, tightly fitted, and permanently secured in position, provided, however, that any firestopping sealant used in conjunction with such penetrations shall be noncombustible.
502.7.3 Fire-resistant penetrations and joints.
Penetration into or through fire-rated wall/horizontal assemblies shall be permitted to be installed in accordance with the requirements of this section. Such penetrations shall be protected by an approved through-penetration fire stop system installed and tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch (2.49 Pa) of water. The system shall have an F rating of 2 hours minimum for walls/horizontal penetrations. For horizontal penetration, the system shall have a T rating of 2 hours minimum where penetration is not contained and located inside rated wall cavities. The required ratings for both F and T rating shall not be less than the required rating of the floor/horizontal assemblies penetrated. Such installers shall be certified by the manufacturer of the firestopping assembly for the specific assembly.
502.7.3.1 Manufacturer certification.
The licensee responsible for the penetration shall obtain certification for the installation of the approved through-penetration fire stop system from the manufacturer of such fire stop system and provide proof of the certification in a form and manner acceptable to the department. The department may accept other certifications as specified by rules.
502.7.4 Electrical boxes.
Penetrations by listed electrical boxes of any material may be permitted provided such boxes have been tested for use in fire-resistance-rated assemblies and installed in accordance with the instructions included in the listing.
502.7.5 Additional methods and qualifications.
The department may approve additional methods of firestopping in conjunction with limited alteration applications, and/or qualifications for those installing firestopping as part of a limited alteration application by rule.
502.7.6 Certification by permit holder.
The permit holder shall certify to the department that the firestopping installation meets the requirements of Section 502.7, including proper restoration of any abandoned openings resulting from the work.
Section EBC 503. Limited Oil-Burning Appliance Alterations
503.1 Filing.
Limited oil-burning appliance alterations shall be filed and performed by a licensed oil-burning equipment installer meeting the requirements of Article 412 of Title 28 of the Administrative Code.
503.2 Categories of work.
Limited oil-burning appliance alterations shall be limited to the types of work set forth in Sections 503.2.1 and 503.2.2.
503.2.1 Category 1.
An addition to an existing oil-burning appliance meeting the following conditions:
1. The total cost of the proposed category 1 work in the building does not exceed $50,000 in any 12-month period; and
2. The proposed work is limited to the installation of:
1. Oil equipment;
2. Oil-fired appliances, located within the same enclosure or room as the existing oil-burning appliance;
3. Unit heaters; or
4. Oil piping including no more than 2 above-ground oil tanks each with a capacity of no more than 330 gallons (1249 L), provided such oil tanks also comply with the capacity limits established in Section 1305.11 of the New York City Mechanical Code. The newly installed tanks shall be listed and labeled in accordance with UL 80 or UL 142, or meet the alternative tank design and construction standards contained in Section 1305.14 of the New York City Mechanical Code.
503.2.2 Category 2.
An alteration, repair, replacement or removal of existing oil-burning appliances, piping, and equipment that is not subject to cost or duration limitations and that is limited to the following:
1. Replacement of oil burners, oil-burning appliances or water heaters in which the heat input per appliance does not exceed 3 million Btu/h (879 kW).
2. Relocation of an oil burner, oil-burning appliance or water heater within the same enclosure or room.
3. Placement of a temporary Department of Buildings registered oil-fired mobile boiler and corresponding fuel oil storage tank with associated piping at a site for emergency heating.
4. Placement of a temporary fuel oil storage tank with a capacity of 5,000 gallons (18 927 L) or less at a site for emergency use and connected to an existing oil-burning appliance.
5. Repair, replacement or relocation of oil equipment, appliances or oil piping including no more than 2 above-ground oil tanks, each with a capacity of no more than 330 gallons (1249 L) provided such oil tanks also comply with the capacity limitations of Section 1305.11 of the New York City Mechanical Code. The replacement tanks shall have a UL listing or labeling or meet the alternative tank design and construction standards contained in Section 1305.14 of the New York City Mechanical Code. Any such relocation shall be only within the same enclosure or room.
6. The change of grade of fuel oil.
Section EBC 504. Limited Plumbing Alterations
504.1 Filing.
Limited alterations made to a plumbing, fire suppression or fuel gas piping system or service shall be filed and performed by a licensed master plumber meeting the requirements of Article 408 of Title 28 of the Administrative Code.
504.2 Categories of work.
Limited plumbing alterations shall be limited to the types of work set forth in Sections 504.2.1 and 504.2.2.
504.2.1 Category 1.
An addition to an existing plumbing or fuel gas piping system or service where the total cost of the proposed Category 1 work in the building does not exceed $50,000 in any 12-month period and where the proposed work is limited to the following:
1. The addition of not more than 10 plumbing fixtures or fixture connections in a building within any 12-month period, including any associated plumbing necessary to serve such additional fixtures or fixture connections. The installation of the new fixtures shall be in compliance with Section 310.7 and not cause an existing system to become overloaded. If required, additional permits for construction shall be obtained in accordance with Section 105;
2. The installation of new fuel gas piping in conjunction with the addition of not more than 6 unit heaters or 6 infrared heaters;
3. The installation of new fuel gas piping in conjunction with the addition of gas appliances, when limited to:
3.1. Two Category 1 vented water heaters;
3.2. Gas pilots;
3.3. One gas barbecue in conjunction with an R-3 occupancy group; or
3.4. One pool heater in conjunction with an R-3 occupancy group;
4. The installation of new fuel gas piping to supply a lawfully existing appliance;
5. The installation of up to 5 new sprinkler heads supplied by an existing domestic water system within any 12-month period;
6. Installation of a new single domestic gas dryer that is vented directly through an exterior wall in a building occupied exclusively as a one- or two-family dwelling not more than 4 stories in height; as provided for in rules of the department. Clothes dryer exhaust shall be installed in accordance with Section 504 of the New York City Mechanical Code; and
7. The installation of piping serving electric water heaters. Electrical work shall be filed and performed in accordance with the New York City Electrical Code.
504.2.2 Category 2.
The repair, replacement of or alteration to an existing plumbing or fuel gas piping system that is not subject to cost or duration limitations and that is limited to the following:
1. The repair, replacement of or alteration of existing plumbing or fuel gas piping serving the same number of fixtures and appliances;
2. The in-kind replacement of plumbing fixtures and gas equipment. This shall not preclude plumbing work that is an ordinary repair or ordinary plumbing work from being filed as a limited alteration application;
3. The relocation of plumbing fixtures, and the replacement of plumbing fixtures that includes the installation and alteration of piping serving the fixture. This shall not preclude the relocation and replacement of plumbing fixtures that is an ordinary repair or ordinary plumbing work from being filed as a limited alteration application;
4. The installation or replacement of primary backflow preventers;
5. The installation of a fat, oil, and grease interceptor not exceeding a capacity of 200 lbs. (90 kg);
6. The replacement of a fat, oil, and grease interceptor with 1 having the same capacity and not exceeding a maximum of 1,000 lbs. (454 kg);
7. In-kind replacement of lawfully existing gas-fired appliances with a heat input of 3 million Btu/h (879 kW) or less;
8. Replacement of lawfully existing gas burners with a heat input of 3 million Btu/h (879 kW) or less;
9. Relocation of a lawfully existing gas burner/boiler within the same, unaltered fire-rated enclosure or room. Through-penetrations for piping shall be fire stopped in accordance with the requirements of Chapter 7 of the New York City Building Code. New through-penetrations for vents serving direct vent appliances shall be prohibited under category 2 work in buildings other than Occupancy Group R-3 not more than 4 stories in height;
10. Replacement of lawfully existing gas appliances with a heat input of 350,000 Btu/h (103 KW) or less with the following appliances that are vented directly through exterior walls serving buildings occupied exclusively as one- or two-family dwellings not more than 4 stories in height:
10.1 Boilers;
10.2 Water heaters;
10.3 Furnaces;
11. In-kind replacement of a lawfully existing direct-vent gas appliances with a heat input of 350,000 Btu/h (103 KW) or less with the following appliances that are vented directly through exterior walls:
11.1. Boilers;
11.2. Water heaters;
11.3. Furnaces;
12. Replacement of lawfully existing gas-fired domestic clothes dryers or pool heaters with a heat input of 350,000 Btu/h (103 KW) or less;
13. Installation of gas-fired salamanders for temporary heat during construction;
14. Placement of a registered gas-fired temporary boiler with associated gas piping at a site for emergency heating and/or hot water;
15. Replacement of up to 30 existing sprinkler heads providing that orifice sizes, type and deflector positions remain the same, and all such sprinkler heads are supplied by a domestic water system;
16. Rearrangement of not more than 20 sprinkler heads in areas classified in light hazard occupancy, as such term is defined in NFPA 13 as modified by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and supplied by a domestic water system and such areas will remain in such occupancy;
17. Rearrangement of not more than 20 sprinkler heads in restaurant service areas classified in Group 1 ordinary hazard occupancy, as such term is defined by NFPA 13 as amended by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and supplied by a domestic water system and such areas will remain in such occupancy; and
18. Rearrangement of not more than 20 sprinkler heads in mercantile areas classified in Group 2 ordinary hazard occupancy, as such term is defined by NFPA 13 as amended by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and supplied by a domestic water system and such areas will remain in such occupancy.
Section EBC 505. Limited Sprinkler Alterations
505.1 Filing.
Limited alterations made to sprinkler systems shall be filed and performed by a master fire suppression piping contractor, meeting the requirements of Article 410 of the Administrative Code.
505.2 Categories of work.
Limited sprinkler alterations shall be limited to the types of work set forth in Sections 505.2.1 through 505.2.3.
505.2.1 Category 1.
An alteration to an existing sprinkler system where the total cost of the proposed Category 1 work in the building does not exceed $50,000 in any 12-month period, the fire rating of the area where the new sprinkler heads are being installed is not being altered and the proposed work is limited to the installation of up to 5 new sprinkler heads off of an existing sprinkler system.
505.2.2 Category 2.
An alteration, repair or replacement of an existing sprinkler system or combined sprinkler standpipe system that is not subject to cost or duration limitations and that is limited to:
1. Replacement of sprinkler heads, provided that orifice sizes, type and deflector positions remain the same;
2. Replacement of parts required for the operation of a sprinkler system or combined sprinkler standpipe system;
3. Changes that do not alter the type of sprinkler system;
4. Repair, replacement or relocation of piping that does not affect the operation of the sprinkler system provided that orifice sizes, type and deflector positions remain the same;
5. Rearrangement of not more than 30 sprinkler heads in areas classified in light hazard occupancy, as such term is defined in NFPA 13 as modified by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and such areas will remain in such occupancy;
6. Rearrangement of not more than 30 sprinkler heads in restaurant service areas classified in Group 1 ordinary hazard occupancy, as such term is defined in NFPA 13 as amended by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and such areas will remain in such occupancy;
7. Rearrangement of not more than 30 sprinkler heads in mercantile areas classified in Group 2 ordinary hazard occupancy, as such term is defined by NFPA 13 as modified by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and such areas will remain in such occupancy;
8. Rearrangement of sprinkler heads in a storage area under 200 square feet classified as Group 1 ordinary hazard, as defined by NFPA 13 as modified by Appendix Q of the New York City Building Code, provided such areas are already sprinklered and such areas will remain in such occupancy;
9. Unlimited cut and cap of an existing sprinkler system associated with a permitted demolition or gut renovation;
10. Relocation of a fire department connection as part of a combined system; and
11. Relocation of class II auxiliary hose connections and cabinets within 10 feet (3048 mm) of their original location, provided that the existing covered area is not affected.
505.2.3 Category 3.
An alteration, repair or replacement of components of an existing sprinkler system that may be performed without the requirement of associated department inspections and that is limited to:
1. Direct replacement of drain piping;
2. Direct replacement of water flow, valve tamper, high-low pressure and similar switches, provided that any electrical wiring is performed in accordance with the provision of the New York City Electrical Code and this code;
3. Direct replacement of fire suppression related valves, gauges and controls; and
4. Repair or replacement of fire pump system components of same type and capacity including seals and repacking of pump shafts. This allowance does not include the full replacement of a fire pump.
Section EBC 506. Limited Standpipe Alterations
506.1 Filing.
Limited standpipe alterations shall be filed and performed by a licensed master fire suppression piping contractor or licensed master plumber meeting the requirements of Articles 410 or 408 of Title 28 of the Administrative Code, respectively.
506.2 Categories of work.
Limited standpipe alterations shall be limited to the types of work set forth in Section 506.2.1.
506.2.1 Category 2.
An alteration, replacement or repair to an existing standalone or combined standpipe system that is limited to the following:
1. Repair, replacement, rearrangement or relocation of components and piping required for the operation of a standalone or combined standpipe system;
2. Relocation of standalone or combined standpipe auxiliary hose sources and cabinets within 10 feet (3048 mm) of their original location, provided that the existing covered area is not affected and provided that such relocation complies with this code for a new installation;
3. Unlimited cut and cap of an existing standalone or combined standpipe system for a demolition or gut renovation; and
4. Relocation of a fire department connection as part of a standalone system.
Section EBC 507. Limited Home Improvement Alterations
507.1 Filing.
In a one- and two-family dwelling, the work specified in Section 507 shall be permitted to be filed as limited home improvement alterations and performed by a homeowner or home improvement contractor. The commissioner may promulgate rules to specify more types of work that can be filed as limited home improvement alterations.
Exceptions:
1. Buildings located in a special flood hazard area.
2. Where the scope of work includes any of the following:
2.1 Cutting away of gravity load bearing elements.
2.2 Removal of portions of fire walls or materials pertaining to them.
2.3 New flooring materials weighing more than 5 psf (24 kgf/m 2 ).
2.4 Installation of any element weighing more than 100 lbs. (45 kg) and supported on an area less than 1 square foot (0.09 m 2 ) or not more than 1 joist.
2.5 Partial removal of partition walls that exceed 6 feet (1.83 m), where work occurs in bearing brick masonry townhouses and where the distance between side walls is greater than 20 feet (6 m).
2.6 Removal without replacement of material pertaining to a fire separating wall or floor.
2.7 Removal of any portion of a nonload-bearing, nonfire-resistance-rated wall or partition exceeding 45 square feet (4.18 m 2 ).
2.8 Removal and in-kind replacement of more than 1 individual deteriorated framing member of loadbearing studs or joists, or 1 unit of masonry in a wall, floor, or ceiling in any 10 foot (3 m) by 10 foot (3 m) area.
2.9 The temporary removal and replacement of a beam or header in a nonload-bearing partition having a clear span greater than 3 feet 6 inches (1 m).
507.1.1 Performance of work.
When filed in accordance with Section 507.2, all work subject to Section 507 shall be performed by the homeowner or a home improvement contractor. Work filed by the homeowner shall by performed by the homeowner. Where any other work is to be performed by a contractor, such other work shall be performed pursuant to a separate work permit or limited alteration permit.
507.1.1.1 Electrical work.
Electrical work associated with the home improvement shall be filed and performed by a licensed electrician in accordance with this code and the New York City Electrical Code.
507.1.1.2 Plumbing work.
Plumbing work associated with the home improvement shall be filed and performed by a licensed plumber in accordance with this code and the New York City Plumbing Code.
507.1.2 Changes in scope of work.
During construction, where a change in the scope of work results in work that is subject to additional permit requirements, work must stop until an amended limited home improvement permit or other applicable permit is issued.
507.2 Covered work.
Limited home improvement alterations shall be limited to the types of work set forth in Sections 507.2.1 through 507.2.3.
507.2.1 Alterations filed by homeowners or home improvement contractors.
Alterations, repairs and replacement work made to one- and two-family dwellings that are limited to the following:
1. Constructing a storage closet. Such closet shall not:
1.1. block an existing window;
1.2. include a window;
1.3. exceed 20 square feet in area (1.85 m 2 );
1.4. block a sprinkler head or smoke/carbon monoxide detector; or
1.5. reduce the minimum clear dimension of the habitable room to less than 8 feet (2438 mm) or reduce the area of the habitable room to less than 80 square feet (7 m 2 ).
2. Adding insulation material to attics, provided the insulation R-values are in compliance with the New York City Energy Conservation Code.
507.2.2 Alterations filed by home improvement contractor.
Alterations, replacement and repairs made to one- and two-family dwellings filed and performed by home improvement contractors that are limited to the following work:
1. Construction of attached rear yard decks with a maximum projection of 8 feet (2438 mm) into rear yard from the rear face of the building wall and maximum height of 5 feet (1524 mm) above grade, complying with the New York City Zoning Resolution with regard to location and the New York City Building Code with regard to construction, including but not limited to structural strength, fire separation distance, stairs, handrails and guards.
2. Installation of a central air conditioning system in compliance with the New York City Energy Conservation Code with maximum capacity of 5 tons. The air conditioning equipment shall be located where permitted in accordance with the New York City Zoning Resolution. Separate electrical permits shall be obtained by a licensed electrician.
507.2.3 Alteration to existing kitchen, bathroom, or toilet room.
Limited home improvement alterations for the renovation or the replacement of a lawfully existing kitchen, bathroom, or toilet room shall be limited to one- and two-family dwellings in buildings not more than 3 stories, including a basement. The renovation or replacement of a lawfully existing kitchen, bathroom, or toilet room shall be limited to the following:
1. Removal and replacement of cabinets.
2. Removal and replacement of plumbing fixtures.
3. Removal and replacement of appliances.
4. Removal, replacement, and installation of wall, floor, and ceiling finishes and insulation materials.
Section EBC 508. Limited Window Replacement Alterations
508.1 Filing.
Limited window replacement alterations shall be filed and performed by a home improvement contractor qualified in accordance with requirements established by the commissioner or by a general contractor meeting the requirements of Article 418 of Title 28 of the Administrative Code. Replacements that are not filed by such contractors shall not qualify as limited window replacement alterations and must be filed as or part of a Level 1 or Level 2 alteration, as applicable.
508.1.1 Work exempt from permit.
See Section 105.3 for window replacements exempt from permit for one- and two-family dwellings.
508.2 Covered work.
Limited window replacement alterations shall be limited to the replacement of the sash and the covering where the existing openings are not to be modified in size. Where replacement window work does not comply with Section 508.2, such replacement shall be filed as or part of a Level 1 or Level 2 alteration, as applicable.
Exception: Replacement of windows required to be fire-rated pursuant to any provisions of law shall not be filed as a limited window replacement alteration.
508.3 Compliance.
Windows shall comply with all applicable requirements of the New York City Construction Codes for new construction, including the New York City Energy Conservation Code and Chapters 12, 16 and 33 of the New York City Building Code.
508.3.1 Residential light and air.
Replacement windows serving dwelling units in Group I-1, R-1, R-2 or R-3 occupancies shall not reduce the area of glazing or operable area below the standards established in Chapter 12 of the New York City Building Code, except where different requirements are provided in Appendix D of this code for certain multiple dwelling classifications, in which case such different requirements shall apply.
508.3.2 Emergency escape and rescue openings.
Replacement windows in Group R-2 and R-3 occupancies shall comply with Section 303.8.
508.3.3 Window guards.
Replacement of windows in Group R-2 occupancies shall comply with Section 303.7.
Section EBC 509. Limited Reroofing Alterations
509.1 Filing.
Limited reroofing alterations shall be filed and performed by a home improvement contractor qualified in accordance with requirements established by the commissioner or by a general contractor meeting the requirements of Article 418 of the Title 28 of the Administrative Code. Reroofings that are not filed by such contractors shall not qualify as limited reroofing alterations and must be filed as or part of a Level 1 or Level 2 alteration, as applicable.
509.1.1 Work exempt from permit.
See Section 105.3 for reroofing not required to be performed pursuant to a permit for one- and two-family dwellings.
509.2 Covered work.
Limited reroofing alterations shall be limited to the following:
1. Roof repair, as such term is defined in Chapter 2;
2. Reroofing of less than 1,000 square feet (92 m 2 );
3. Installation of coatings designed to increase reflectivity and/or prolong the service life of the existing roof covering;
4. Installation of insulation above the roof deck/sheathing, provided that, based on the scope of the work, the New York City Energy Conservation Code does not require additional thermal insulation for the roof; and
5. Replacement of existing deteriorated roof sheathing that is:
5.1. limited to not more than 10 percent of all existing roofs on the building for buildings with roof areas totaling less than 1,300 square feet (120 m 2 );
5.2. limited to 130 square feet (12 m 2 ) for buildings with roof areas totaling more than 1,300 square feet (120 m 2 ); or
5.3. limited to 65 contiguous square feet (6 m 2 ) in any location.
509.2.1 Increases in scope of work.
Where changes in the scope of work during the course of reroofing would result in exceeding the limitations of Section 509.2, Items 1 through 5, such work shall be refiled as part of a Level 1 or Level 2 alteration, as applicable.
509.3 Compliance.
Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of Section 1511 of the New York City Building Code.
Section EBC 510. Limited Elevator Alterations
510.1 Filing.
Limited elevator alterations shall be filed and performed by a licensed elevator agency director meeting the requirements of Article 421 of Title 28 of the Administrative Code.
510.1.1 Application.
Limited elevator alteration applications shall be filed with the department for repairs, replacements and modifications for damaged, broken or worn parts that are necessary for normal elevator maintenance as described in Section 510.2.
510.1.2 Other work.
Any elevator repair, replacement or modification work that requires an electrical/mechanical safety load test shall not be filed as limited elevator alteration. See Section 510.3 for additional work that must be filed as a Level 1 alteration.
510.2 Covered work.
Limited elevator alterations shall include the items of work covered by those provisions of ASME A17.1, as modified by Appendix K of the New York City Building Code, identified in Table 510.2 of this code.
Table 510.2 Limited Elevator Alterations
A17.1 Section Name of A17.1 Section A17.1 Sub-section Name of A17.1 Sub-section 8.6.2 Repairs 8.6.2.6 Repairs involving SIL rated device(s) 8.6.3 Replacements 8.6.3.14 Replacements involving SIL rated device(s) 8.7.2 Alterations to electric elevators 8.7.2.12 Power operation of hoistway doors 8.7.2 Alterations to electric elevators 8.7.2.13 Door reopening device 8.7.2 Alterations to electric elevators 8.7.2.14 When alterations to the car enclosure cause an increase or decrease of the deadweight of the car by less than 5%, see ASME section 8.7.2.15.2) 8.7.2 Alterations to electric elevators 8.7.2.21 Suspension means and their connections 8.7.2 Alterations to electric elevators 8.7.2.23 Car and counterweight buffers and bumpers 8.7.2 Alterations to electric elevators 8.7.2.24 Guide rails, supports, and fastenings 8.7.2 Alterations to electric elevators 8.7.2.25 Regrooving of machine sheaves 8.7.3 Alterations to hydraulic elevators 8.7.3.12 Power operation of hoistway doors 8.7.3 Alterations to hydraulic elevators 8.7.3.13 Door reopening device 8.7.3 Alterations to hydraulic elevators 8.7.3.25 Suspension ropes and their connections 8.7.3 Alterations to hydraulic elevators 8.7.3.27 Car buffers and bumpers 8.7.3 Alterations to hydraulic elevators 8.7.3.28 Guide rails, supports, and fastenings 8.7.6 Alterations to Escalators 8.7.6.1.5(c) Balustrades. Any alteration to the balustrades shall conform to 6.1.3.3 for the altered components. 8.7.6 Alterations to Escalators 8.7.6.1.5(d) Skirt Deflector Devices. Any alteration or addition of skirt deflector devices shall conform to 6.1.3.3.10 8.7.6 Alterations to Escalators 8.7.6.1.6 Any alteration to the handrails or handrail system shall require conformance with 6.1.3.2.2, 6.1.3.4.1 through 6.1.3.4.4, 6.1.3.4.6, 6.1.6.3.12, and 6.1.6.4. 8.7.6 Alterations to Escalators 8.7.6.1.7(a) Any alteration to the step system shall require conformance with 6.1.3.3.5, 6.1.3.5 (except as specified in 8.7.6.1.7(b)), 6.1.3.6, 6.1.3.8, 6.1.3.9.4, 6.1.3.10.4, 6.1.3.11, 6.1.6.3.3, 6.1.6.3.9, 6.1.6.3.11, 6.1.6.3.14, and 6.1.6.5. 8.7.6 Alterations to Escalators 8..7.6.1.7(b) Steps having a width less than 560 mm (22 in.) shall not be reduced in width by the alteration. 8.7.6 Alterations to Escalators 8.7.6.1.8 Any alteration of the comb plates shall require conformance with 6.1.6.3.13. 8.7.6 Alterations to Escalators 8.7.6.1.10 Any alteration to the tracks shall result in the escalator’s conforming with 6.1.3.8, 6.1.3.9.4, 6.1.3.10.1, and 8.7.1.4. 8.7.6 Alterations to Escalators 8.7.6.1.13 Any alteration to or addition of operating and or safety devices shall conform to 6.1.6 for that device. 8.7.6 Alterations to Escalators 8.7.6.1.14 An alteration to or addition of lighting, access, or electrical work shall conform with the specific requirements within 6.1.7 for that change. 8.7.6 Alterations to Moving Walk 8.7.6.2.5(c) Balustrades. Any alteration to the balustrades shall require conformance with 6.2.3.3. 8.7.6 Alterations to Moving Walk 8.7.6.2.6 An alteration to the handrails or handrail system shall require conformance with 6.2.3.2.3, 6.2.3.4, 6.2.6.3.10, and 6.2.6.4. 8.7.6 Alterations to Moving Walk 8.7.6.2.7(a) An alteration to the treadway system shall require conformance with 6.2.3.2.3, 6.2.3.3.5, 6.2.3.3.6, 6.2.3.5, 6.2.3.6 (except as specified in 8.7.6.2.7(b)), 6.2.3.8, 6.2.3.9, 6.2.3.10.4, 6.2.3.11.4, 6.2.3.11.5, 6.2.3.12, 6.2.6.3.3, 6.2.6.5, and 6.2.6.3.9. 8.7.6 Alterations to Moving Walk 8.7.6.2.7(b) The minimum width of the moving walk shall be permitted to be less than that required by 6.2.3.7. The existing width, if less than required by 6.2.3.7, shall not be decreased by the alteration. 8.7.6 Alterations to Moving Walk 8.7.6.2.8 An alteration of the comb plates shall require conformance with 6.2.3.8 and 6.2.6.3.11. 8.7.6 Alterations to Moving Walk 8.7.6.2.10 Any alteration to the tracks shall result in the moving walk’s conforming to 6.2.3.9, 6.2.3.10, 6.2.3.11.1, and 8.7.1.4. 8.7.6 Alterations to Moving Walk 8.7.6.2.13 An alteration to or addition of operating and/or safety devices shall conform with the specific requirements within 6.2.6 for that device. 8.7.6 Alterations to Moving Walk 8.7.6.2.14 An alteration to or addition of lighting, access, or electrical work shall conform with the specific requirements within 6.2.7 for that change.
a. All references to A17.1 refer to ASME A17.1, as amended by Appendix K of the New York City Building Code .
510.3 Level 1 alteration work.
Limited elevator alterations shall not include items of work covered by those provisions of ASME A17.1 as modified by Appendix K of the New York City Building Code, identified in Table 812.1 of this code. Such work shall be filed as a Level 1 Alteration.
Section EBC 601. General
601.1 Scope.
The provisions of this chapter shall be used in conjunction with Chapter 3 and Chapters 7 through 14 and shall apply to the alteration, addition and change of occupancy of existing structures, including relocated, moved or raised buildings, as referenced in Sections 301.1.3 and 301.1.5. Work performed on an existing building shall be classified in accordance with this chapter.
601.1.1 Compliance with other chapters.
Where elected by the registered design professional of record in accordance with Section 301.1.4, Chapter 13 may be used simultaneously with Chapters 8 through 11 and 14 for alterations, additions and changes of occupancy made to existing buildings.
601.2 Work area.
The work area, as defined in Chapter 2 , shall be identified on the construction documents by the registered design professional of record for the purpose of determining the applicability of the requirements of Chapters 8 and 9 . For the purpose of calculating work area as a percentage of building area, building area shall be calculated in accordance with the definition of such term in Chapter 2.
601.2.1 Permit applications that have not been signed off.
For the purpose of calculating the total work area, alteration applications that have not been signed off shall be cumulatively considered in accordance with Sections 601.2.1.1 and 601.2.1.2.
601.2.1.1 Cumulative work area.
For the purpose of determining the level of alteration for a newly filed application, the total work area shall include, on a cumulative basis, all applications filed after the effective date of the local law that added this section that have not been signed off.
601.2.1.2 Project specific work area.
For the purpose of determining total work area for Level 2 alterations exceeding 75 percent of building area, the total work area shall include related applications filed after the effective date of the local law that added this section that are associated with the project scope and are not yet signed off.
601.2.2 Minor alterations, ordinary repairs and limited alterations.
Where minor alterations, ordinary repairs and limited alterations, as described in Chapter 5, are included as part of the same scope of a Level 1 or Level 2 alteration, all such work shall be included for the purpose of determining the work area to the extent such work contributes to work area pursuant to Section 601.2.3.
601.2.3 Determination of work area.
Work areas shall be determined in accordance with Sections 601.2.3.1 through 601.2.3.3.
601.2.3.1 Interior work.
Work area shall be the entire horizontal area of the room or space being reconfigured. Reconfiguration shall include, but not be limited to, the items listed below, or as otherwise determined by the department to secure the beneficial purposes of this code:
1. Removal, relocation or installation of interior partitions, walls, doors, or ceilings.
2. Construction, removal, or relocation of stairs, ramps, or stair or ramp enclosures.
3. Construction, removal, reduction, or extension of a mezzanine level in compliance with Section 505 of the New York City Building Code.
4. Increase or decrease in the clear ceiling height of a space or a floor.
5. Creation of openings between levels, stories, or spaces. The work area shall include the opening and the area of the rooms or spaces impacted by the alteration.
6. Sealing or creation of operable skylights that are required for ventilation in roofs. The work area shall include the interior space impacted by such alteration to the roof. For the purposes of applying the requirements of Chapter 9 and requirements in Chapter 8 for work areas greater than 50 percent of the floor area, the work area shall be calculated as 10 times the area of the skylight where such skylight is 10 percent or less of the area of the room or space.
7. Sealing or creation of operable windows that are required for ventilation and doors in exterior walls. The work area shall include the interior space impacted by such alteration to the building exterior walls. For the purposes of applying the requirements of Chapter 9 and requirements in Chapter 8 for work areas greater than 50 percent of the floor area, the work area shall be calculated as 10 times the area of the exterior wall opening where such opening is 10 percent or less of the area of the room or space.
8. Creation or enclosure of vertical openings and shafts.
9. Construction or enlargement of elevator hoistways. The work area shall include the hoistway being constructed or enlarged and the rooms or spaces impacted by the alteration.
Exceptions:
1. Incidental work made to existing walls, shafts and ceilings associated with the installation of plumbing, mechanical, fuel gas, electrical and fire protection systems shall not be included in the determination of work area.
2. Where the space being reconfigured constitutes 10 percent or less of the total area of a room or floor that the reconfigured space is a part of, the work area shall be limited to the space being reconfigured. This exception does not apply to items 6 and 7 of this section.
601.2.3.2 Exterior work (Building envelope).
Alteration of the exterior walls and roof shall not be considered as work area in determining Level 1 and Level 2 alterations. However, where the alteration of the building exterior impacts the interior spaces of the building by creating or sealing of operable windows, skylights or doors, work area shall be determined in accordance with Section 601.2.3.1.
601.2.3.2.1 Changing the size of windows, skylights or doors that are required for natural light or ventilation.
Where the exterior work includes changing the size of windows, skylights or doors that are required for natural light or ventilation and no interior work occurs, the interior spaces impacted by such work shall not be considered as work area. Such work shall comply with Section 803.7.
601.2.3.3 Stand-alone systems.
Work area shall not include the installation of, alteration of or additions to plumbing, mechanical, electrical, vertical transportation systems, fuel gas, or fire protection systems.
Exception: The construction of or alterations made to create toilet rooms, mechanical equipment rooms and floors, boiler rooms and similar spaces, shall be counted as work areas in accordance with Section 601.2.3.1.
Section EBC 602. Alteration – Level 1
602.1 Scope.
Level 1 alteration is any alteration made to a building where the work area as determined in accordance with Section 601.2 does not exceed 50 percent of the building area.
602.1.1 Building systems.
Installation of new mechanical, plumbing, fuel gas, fire protection and vertical transportation systems in existing buildings or alterations to such systems, other than limited alterations subject to Chapter 5, shall be classified as a Level 1 alteration unless included as part of a Level 2 alteration.
602.2 Application.
Level 1 alterations shall comply with the provisions of Chapter 8 and, as applicable, with the provisions of Chapters 3 and 7 .
Section EBC 603. Alteration – Level 2
603.1 Scope.
Level 2 alteration is any alteration made to a building where the work area exceeds 50 percent of the building area.
603.1.1 Work area contributing to Level 2 alteration.
For the purpose of determining Level 2 alteration, work area shall be calculated pursuant to Section 601.2.
Exception. For categories of work established by rule.
603.2 Application.
Level 2 alterations shall comply with the provisions of Chapter 8 for Level 1 alterations as well as the provisions of Chapter 9 and, as applicable, with the provisions of Chapters 3 and 7.
Section EBC 604. Change of Occupancy
604.1 Scope.
Change of occupancy provisions apply where the activity is classified as a change of occupancy as defined in Chapter 2.
604.2 Application.
Changes of occupancy shall comply with the provisions of Chapter 10 and, as applicable, with the provisions of Chapters 3 and 7.
Section EBC 605. Additions
605.1 Scope.
Provisions for additions shall apply where work is classified as an addition as defined in Chapter 2.
605.2 Application.
Additions to existing buildings shall comply with the provisions of Chapter 11 and, as applicable, with the provisions of Chapters 3 and 7.
Section EBC 606. Relocated, Moved or Raised Buildings
606.1 Scope.
Provisions for relocated, moved or raised buildings shall apply to relocated, moved or raised buildings as defined in Chapter 2.
606.2 Application.
Relocated, moved or raised buildings shall comply with the provisions of Chapter 14 and, as applicable, with the provisions of Chapters 3 and 7.
Section EBC 607. Structural
Section EBC 701. General
701.1 Scope.
This chapter shall govern structural alterations of existing buildings, structures and parts thereof as a result of or in connection with repairs, alterations, partial demolition, change of occupancy, additions, removal, relocation, raising or moving of buildings and parts thereof and all other structures. Structural considerations related to alterations shall be performed according to this chapter.
Exceptions:
1. Where the structural alteration resulting from in-kind replacement of façade elements does not result in modifications to the load path, stiffness or strength of the existing buildings, structures and parts thereof, the provisions of Chapter 7 do not apply.
2. One- and two- family dwellings 3 stories or less in height where the existing building is of conventional light frame construction, excluding buildings with nogging walls, are not required to comply with the provisions of Sections 703.4, 703.5, 703.7, 704, and 705.6.
701.2 Conformance.
Structural alterations of existing buildings, structures, or parts thereof shall be made to comply with this code. Structural alterations of existing buildings, structures, or parts thereof shall not decrease the structural stability or the load carrying capacity of existing buildings, except as allowed by this code.
701.3 Applicability of the New York City Building Code.
Structural analysis, design and construction work in existing buildings shall be in accordance with the New York City Building Code requirements unless otherwise noted in this code. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations in the New York City Building Code. Where this code requires comparison of demand or capacity, all calculations will be in accordance with the current New York City Building Code, all loads applied to both existing and new portions of the structure shall be in accordance with Section 705 of this code and capacity evaluation in accordance with Section 707 of this code.
701.4 Relevant time period.
For purposes of this chapter, structural alterations not yet signed off, and structural alterations signed off within the previous 5 years, shall be considered as part of the current structural alteration.
Exception: Where the commissioner determines the physical construction work for such a signed-off structural alteration was completed more than 5 years prior to the approval of construction documents for the current structural alteration.
701.5 Responsibility to report.
Any dangerous condition observed shall be reported to the department as required by Section 28-301.1 of the Administrative Code. Such dangerous condition shall also be conveyed to the owner of the building and shall be immediately remedied.
Section EBC 702. Construction Documents
702.1 Requirements.
Construction documents shall be in conformance with Article 104 of Chapter 1 of Title 28 of the Administrative Code as well as Sections 107 and 1603 of the New York City Building Code and Chapter 7 of this code.
702.2 Additional drawing requirements.
For all structural elements within the area of structural work that are altered or that have their demand increased or stability decreased, drawings are required to include, where applicable to the scope of work, the information below. Where element sizes and any other required information is not known it shall be indicated as such and the requirements for field verification shall be stated. Notes on the drawing shall indicate the source of the information.
1. Existing structural element sizes and types where known.
2. The material properties used in design and analysis and the source of the values.
3. Foundation sizes and types.
4. Subsurface capacities.
5. Details for the repair of structural elements.
6. Existing detailing of the structural elements within the area of the structural scope.
7. Any assumptions made about the building permitted in accordance with Section 704.2 to be confirmed in accordance with Section 704.3.1.
Section EBC 703. General Design Requirements
703.1 General.
All structural alterations shall comply with this section and Sections 704 through 710, as applicable. All new structural elements and their connections shall comply with the New York City Building Code.
703.1.1 Underpinning and alternative methods of support of buildings and adjacent property.
Underpinning and alternative methods of support of buildings and adjacent property shall comply with the requirements of Chapters 18 and 33 of the New York City Building Code.
703.1.2 Separated buildings and structures.
Where the structural alteration is completely separated from an existing building or structure by a joint, only this isolated part shall be made to comply with the New York City Building Code as a new building. Unless determined by calculations, the joint shall be twice of that indicated in Section 1613.4 of the New York City Building Code.
703.1.3 Repairs due to accidental events.
Unless otherwise specified in this code, where damage to structural elements was the result of fire, vehicular impact, extreme environmental events or adjoining construction, structural repairs are permitted to only restore the structure to the condition prior to the event provided a registered design professional submits a report that such damage has not affected more than 20 percent of the structure.
703.2 Buildings required to comply as hereafter erected.
For buildings subject to structural alterations that increase existing floor surface area of an existing building by more than 110 percent as described in Section 302.7 of this code, the structure of such entire building shall be made to comply with the structural provisions of the New York City Building Code as if it were a new building hereafter erected.
703.3 Entire buildings required to comply with loading provisions.
For buildings subject to structural alterations that meet any of the criteria listed below, the structure of such entire building shall be made to comply with the structural loading provisions of the Section 705:
1. Structural alterations in which gravity load-carrying structural elements are affected by work that involves a change to the gravity load path that supports more than 55 percent of the total floor and roof area of the building or structure. The areas to be counted toward the 55 percent shall include mezzanines, penthouses, and in-filled courts and shafts tributary to the altered structural elements.
2. Where a building or portion greater than 10 percent thereof, or greater than 20,000 square feet, is subject to a change of occupancy that results in the building being assigned to a higher Risk Category, based on Table 1604.5 of the New York City Building Code. For buildings with an S DS less than 0.33, increased seismic loads due solely to an increase in Risk Category, where the change in Risk Category is to Risk Category II or III, need not be considered.
3. Where the total dead and live load of the entire building increases by more than 50 percent, unless the applicant demonstrates that the increased load is less than the original design load for the existing building or that the building demonstrates the existing capacity to withstand the new loads.
4. Where the wind base shear or overturning in either orthogonal direction increases by more than 50 percent, unless the applicant demonstrates that the increase in total wind load is less than the original design load for the existing building or that the building possesses the existing capacity to withstand the new loads.
5. Where the seismic base shear or overturning in either orthogonal direction increases by more than 50 percent, unless the applicant demonstrates that the increase in total seismic load is less than the original design load for the existing building or that the building possesses the existing capacity to withstand the new loads.
703.4 Increased demand on existing structural elements and foundations.
Alterations not meeting the criteria in Sections 703.2 or 703.3 shall comply with Sections 703.4.1 and 703.4.2.
703.4.1 Effects on structural elements.
Any existing structural element for which a structural alteration causes an increase in demand, or causes a decrease in capacity, including stability, shall be made to comply with the structural loading provisions of Section 705. The effect of the additional loads or decreasing capacity shall be considered through the load path until resolved in the subgrade.
Exceptions:
1. If the structural alteration does not increase the seismic mass of the building by more than 10 percent, nor decreases the lateral earthquake load resisting capacity of the building by more than 10 percent in either orthogonal direction, additional earthquake loads on the building’s lateral load resisting system due to the alteration need not be considered.
2. If the structural alteration does not increase the wind sail area of the building in each orthogonal direction by more than 10 percent, nor decrease the lateral wind load resisting capacity of the building by more than 10 percent in any direction, the additional wind loads need not be considered beyond the point that they have been delivered to the building structure’s main wind force resisting system.
3. Where a change in occupancy of less than 10 percent of a building area, or less than 20,000 square feet (1858 m 2 ), requires a building to design for an increased snow, wind or seismic load due solely to being assigned a higher Risk Category, other than Risk Category IV, based on Table 1604.5 of the New York City Building Code, such change to the loads need not be considered.
4. Increased seismic loads due solely to an increase in Risk Category, where the change in Risk Category is to Risk Category II or III need not be considered. This exception shall not apply to buildings with an S DS greater than 0.33.
5. An increase in demand on an element due to an increased dead load effect within the element due solely from the addition of a second layer of roof covering weighing 3 pounds per square foot (0.1437 kN/ m 2 ) or less over an existing single layer of roof covering need not be cause to alter the element.
703.4.2 Effects on foundations.
Effects on foundations shall comply with Sections 703.4.2.1 and 703.4.2.2 of this code. Bearing values shall be as required by Chapter 18 of the New York City Building Code.
703.4.2.1 New foundation elements.
New foundation elements shall comply with Chapter 18 of the New York City Building Code.
703.4.2.2 Existing foundation elements.
Any existing foundation element subjected to an increased load shall be made to comply with Chapter 18 of the New York City Building Code with the following exceptions.
Exceptions:
1. Where the existing foundation design capacity is not known, structural alterations which increase the gravity load by 5 percent or less need not be made to comply. Where the gravity load is increased between 5 and 10 percent the registered design professional of record shall consider the impact of potential additional building movement.
2. Structural alterations which increase the wind or seismic load by less than 20 percent need not be made to comply.
Exceptions 1 or 2 shall not be applicable a) where settlement or foundation movement is observed or has been documented, or b) where the proposed work reduces the bearing capacity of the soil strata providing support.
703.5 Stability.
Structural alterations shall comply with Sections 703.5.1, 703.5.2, and 703.5.3, as applicable.
703.5.1 Stability index.
Where a structural alteration reduces the lateral stiffness of a building by more than 10 percent, the building’s lateral system or the altered elements of its lateral system shall have a stability index less than 0.25. Where the stability index is between 0.1 and 0.25, structural analysis and design shall include second order effects.
The stability index shall be determined as follows:
Using factored loads or service loads Q = a (S P) D Vh
Where:
D = horizontal inter-story drift at a given story
S P = total vertical gravity loads at and above a given story
V = horizontal shear at a given story associated with D
h = story height
a where using factored loads and a = 1.5 where using service loads
Exception: Where a structural alteration is performed on an unreinforced masonry building with wood-framed floors constructed prior to 1903, apply Section 703.5.3.
703.5.1.1 Reduction of stiffness.
No structural alteration shall reduce or modify the lateral stiffness of a building, or story within a building, unless it is demonstrated that the altered building structure, or story as applicable, has a stability index less than 0.10 or the altered building structure is made to comply with the structural provisions of the New York City Building Code.
703.5.2 Buildings or stories initially out-of-plumb.
Where a structural alteration increases the lateral loads on a building or story, or reduces the lateral stiffness of a building or story, the analysis of the altered building or altered story shall include the effects of pre-existing horizontal out-of-plumbness in excess of 1 percent in the existing structural system. The initial out-of-plumbness shall be reported in accordance with Section 704 as appropriate and be evaluated to ensure the existing building is capable to sustain it prior to the alteration design. The pre-existing horizontal out-of-plumbness values shall be analyzed for their effect on the altered lateral system and their effects shall be additive to the drifts and forces due to wind and earthquake loading calculated in accordance with Section 705. Out of plumbness for each floor shall be measured from the floor elevations above and below to the most out-of-plumb location in the floor.
703.5.3 Structural alterations of unreinforced masonry buildings with wood-framed floors constructed prior to 1903.
Structural alterations of unreinforced masonry buildings with wood-framed floors constructed prior to 1903 shall comply with Sections 703.5.3.1 through 703.5.3.6:
703.5.3.1 Reduction to in-plane stiffness.
Where a perimeter wall of a building is altered such that its in-plane stiffness is reduced by more than 30 percent, the building’s lateral system shall be made to resist a load of 20 psf in any direction. This notional 20 psf load shall be used in allowable load combinations in lieu of the earthquake and wind with a multiplier of 1 and should not be considered applied simultaneously on parallel walls.
703.5.3.2 Walls.
Where the front or rear walls, or side walls fronting the public right of way, of a building are altered resulting in a final ratio of total horizontal length of opening area to total horizontal length of 50 percent or greater at any floor, the building’s lateral system shall be made to resist a load of 20 psf in any direction. This notional 20 psf load shall be used in allowable load combinations in lieu of the earthquake and wind with a multiplier of 1 and should not be considered applied simultaneously on parallel walls.
703.5.3.3 Calculations.
For purposes of calculating reduction of lateral strength or stiffness of an existing building only, all existing bearing and non-bearing, interior or exterior, partitions shall be considered as part of the structure of the building. Where an interior wood stud or masonry or terra cotta cross wall of a building is removed, the building’s lateral system shall be reinforced with a structural system equivalent in stiffness and strength capacity to that of the removed wall calculated using the methods indicated in ASCE 41.
703.5.3.4 Floor-to-floor heights.
Where the floor-to-floor heights of a building are increased as a result of an alteration such that the ratio of floor height to wall thickness exceeds 10, such walls shall be evaluated in accordance with TMS 402 including the effect of a 20 psf (LRFD) out-of-plane environmental load.
703.5.3.5 Verification of connections.
Where any of the provisions of Sections 703.5.3.1 through 703.5.3.4 are triggered, it shall be verified that there are connections of the floor and roof framing to the posts and surrounding walls, including to the unreinforced masonry walls parallel to joists. Where no connections are present, connections shall be installed to provide a tensile capacity of 200 plf.
703.5.3.6 Exposed walls.
The review of the structural stability of any exposed wall, including party walls after the neighboring structure has been removed, shall consider the engagement of perpendicular elements such as walls, floors and roofs. If the attachment of perpendicular elements is not anchored, connections shall be provided as required in Section 703.5.3.5.
703.6 Exceptions from detailing requirements.
Exceptions from detailing requirements are permitted as allowed by Sections 703.6.1 and 703.6.2. Drawings shall include a statement as to non-compliant elements.
703.6.1 Exception from continuity detailing requirements.
Notwithstanding the requirements of Sections 703.2 and 703.3, existing structural elements need not comply with the continuity detailing requirements of the New York City Building Code unless required by Section 708 of this code.
703.6.2 Exception from seismic detailing requirements.
Notwithstanding the requirements of Sections 703.2 and 703.3, existing structural elements need not comply with the seismic detailing requirements of the New York City Building Code unless required by Section 708 of this code.
703.7 Seismic separation requirements.
For altered buildings that must comply with Section 703.2 or 703.3 and are adjacent to or sharing unreinforced masonry walls, the structural requirements for seismic separation between the altered and existing structures shall be as follows:
1. For alterations erected adjacent to lot line unshared unreinforced masonry bearing walls, the structural separation shall comply with Section 1613.4.1 of the New York City Building Code, except that existing lot line unshared masonry walls that are otherwise allowed to remain need not be demolished to provide for seismic separation.
2. Where an existing building shares an unreinforced masonry party wall, there shall be no building separation between the altered and existing structure. The entire altered structure shall be designed to include an additional seismic load to account for the support of the party wall with connections capable of carrying a service (ASD) horizonal tension or compression load of 200 plf applied along each floor level, or a service (ASD) or 20 psf area load applied onto the party wall, whichever is larger. The connections shall be at the level of the floors of the adjoining building and shall not be set a distance larger than 8ft horizontally. Where floors do not exist, the distance between connections shall not exceed 15 ft vertically.
3. No structural separation is required where:
3.1. The neighboring structures are capable of transferring forces resulting from impact through diaphragms located at the same elevation.
3.2. The structures are capable of resisting all required vertical and lateral forces considering the loss of any elements or components damaged by impact of the structures.
3.3. An altered building, including its extension, is not required by this code to comply with seismic design.
3.4. A party wall is shared by buildings less than 3 stories regardless of whether the design is governed by seismic demands.
Section EBC 704. Condition Assessment
704.1 General.
Condition assessments shall be performed in accordance with Section 704 for all structural alterations.
704.1.1 Area of structural condition assessment.
The condition assessment shall include the area where structural work is being performed and all structural elements that may be affected by the alteration as required by Section 703.
704.1.2 Visual assessment.
For all buildings 7 stories or less, a visual assessment from the exterior of the building shall be performed. Such visual assessment may be performed from the adjacent ground and need not require the use of magnifying devices.
704.2 Structural alterations requiring data collection and an initial condition assessment.
An initial structural condition assessment shall be performed for all structural alterations, where an increase in the demand capacity ratio is introduced to an existing structure, or where required by Sections 907.2, 1007.2 or 1103.3, by the registered design professional of record prior to the submission of the application for construction document approval. During the initial structural condition assessment, the registered design professional of record shall collect and verify accessible data needed for performing the design.
704.2.1 Data collection and initial structural condition assessment.
The initial structural condition assessment shall cover the readily accessible and visible portions of the area of structural assessment specified in Section 704.1.1. The registered design professional of record shall identify the existing elements and verify if the available information sufficiently describes the existing structure and shall supplement such information with accessible observations. The initial structural condition assessment shall document any deteriorations, deficiencies, or potentially unsafe conditions that may have to be addressed during the development of the application for construction document approval. Where required information for the design is inaccessible, assumptions shall be included on the drawings required by Section 702.2. All assumptions are required to be confirmed during the detailed structural condition assessment required by Section 704.3.
704.2.2 Initial structural condition assessment.
The registered design professional of record shall produce a document that includes the following at a minimum, as applicable:
1. Material types of structural elements and strength.
2. Size, spacing and geometry of the structural elements within the area of the structural condition assessment.
3. Continuity of load paths with observations to the lowest level of the building.
4. The physical condition of the existing primary and secondary structural elements in the load path of the alteration where accessible and visibly observable.
5. Any deterioration of structural elements, including but not limited to rot, corrosion, loss of cohesion, displacement and cracking, plumbness, alignment and displacement.
6. Signs of moisture infiltration and related damage, or deformations due to possible overloading.
7. Presence of bowing; or building lean or deflections in excess of 1 percent.
8. Elements with significant unbraced lengths.
9. The remediation items enumerated in Section 708 that are potentially relevant to the building and work in question and a plan to investigate such conditions.
10. Indications of settlement in the building.
11. A list of documents consulted during the course of the condition assessment.
12. Notation of any assumption to be verified during performance of the detailed structural condition assessment in accordance with Section 704.3. Such assumptions shall also be noted on the drawings required by Section 702.2 and filed with the department.
13. Identification of the need for any further testing, surveying or monitoring.
The document shall be maintained at the site for the duration of the job and made available to the commissioner upon request.
704.3 Structural alterations requiring detailed structural condition assessment.
A detailed structural condition assessment shall be performed by the registered design professional of record for all structural alterations where existing structural elements are to be altered or an increase in the demand capacity ratio is introduced to an existing structure.
704.3.1 Detailed structural condition assessment.
The detailed structural condition assessment shall include the area of assessment specified in Section 704.1.1 or other elements as specified in Section 702.2 that are to be identified in the submittal to the department. The detailed condition assessment shall confirm all design assumptions including those of the initial structural condition assessment. The detailed structural condition assessment shall be performed and filed in accordance with Section 704.3.2 at a point before, and revised as needed during, the construction phase of the project, when structural elements or support systems are exposed such that they are accessible for detailed assessment. Structural elements shall be exposed where indicated on the drawings and as needed to satisfy the requirements of Section 703.
704.3.2 Investigation and detailed condition assessment.
The registered design professional of record shall submit a document containing the detailed structural condition assessment to the department after the relevant structural elements or support systems are exposed for detailed assessment but before the structural alterations are begun. The document shall be amended if required by the registered design professional of record after the completion of the construction phase. Where during the alteration process any immediate life/safety condition of concern is observed, such condition shall be communicated to the department as required by Section 28-301.1 of the Administrative Code. Such immediately hazardous condition shall also be conveyed to the owner of the building and shall be immediately remedied. The document shall include:
1. Description of structure and materials.
2. Identification of structural elements reviewed.
3. Description of physical condition of structural elements, including the location of deterioration.
4. Identification of methods used for the condition assessment, such as but not limited to visual observations, probing, borings, test pits, nondestructive testing and laboratory testing of materials.
4.1. Any documentation produced as a result of the investigation described in item 4 shall be included in the document.
5. Identification of deficiencies and causes of deficiencies.
6. Identification of elements and conditions different from the assumptions used in the design.
7. Life/safety conditions of concern should be addressed immediately. The timing of all other repairs should be discussed.
8. The remediation items enumerated in Section 708 that were investigated and the determinations of such investigation.
9. List of all design assumptions previously made from Sections 702.2 and 704.2 with confirmation or change to plans as required.
10. Any information from the initial condition assessment required by Section 704.2 not otherwise included.
704.3.2.1 Observed deficiencies outside the scope of work.
Where, in the course of the alteration, deficiencies not related to the scope of work are observed, the detailed document shall provide a discussion of the severity of any observed deficiencies.
704.4 Use of assessment.
The results of the condition assessments shall be used in the design of the work. Deterioration of structural elements shall be analyzed for conformance with this code and repaired as required. A revised document shall be filed with the department when structural changes or observations differ from the originally submitted documents.
Section EBC 705. Loads
705.1 General.
Loads shall comply with the New York City Building Code unless otherwise noted in Sections 705.2 through 705.6.
705.2 Dead loads.
The existing dead loads shall be confirmed by a rational approach relying upon accepted references, available information including design documents, in-situ and non-destructive testing, or design codes and standards of practice.
705.3 Live loads.
Uniform and concentrated live loads shall be in conformance with Section 1607 of the New York City Building Code.
Exception: For buildings or portions thereof designed to live load criteria in effect prior to July 1, 2008, that are not being modified or structurally altered, design uniform live loads shown in Table 705.3 shall be permitted.
Table 705.3 Minimum Design Live Loads for Buildings Constructed in Accordance with 1968building Code or Building Code Predating 1968 (Occupancy classifications are as defined by the New York City Building Code)
LIVE LOAD OCCUPANCY MINIMUM DESIGN LIVE LOAD (PSF) Commercial Space - Corridors (Above Ground Floor) 75 Manufacturing 100 Marquees 60 Storage (Light) 100 Storage (Heavy) 150 Wholesale Stores 100
705.4 Evaluation of snow, ice and rain loads.
Snow, rain on snow, ice loads including snow drift, sliding and unbalanced snow conditions shall be calculated according to the New York City Building Code and ASCE 7.
705.4.1 Snow sliding.
Where a vertical or horizontal alteration is performed, the altered building shall be designed to limit displacement of snow through sliding.
705.4.2 Special consideration.
Where existing buildings adjacent to a vertical or horizontal alteration have roofs with wood, steel truss or cold formed steel joists spanning 25 ft or less, a visual condition assessment of such adjacent building, as relevant to snow, ice or rain loading, shall be performed. Such visual assessment may be taken from the adjacent altered building’s roof and from the adjacent ground and need not require the use of magnifying devices. The owner of the building causing the vertical or horizontal alteration shall provide the results of the condition assessment to the owner of such adjacent building.
705.5 Wind loads.
Wind loads shall be determined in accordance with the New York City Building Code.
705.6 Seismic loads.
Seismic design shall be in accordance with either the New York City Building Code or ASCE 41, with each code followed in its entirety, as specified below:
1. Demand and capacity determined in accordance with the New York City Building Code.
2. Demand and capacity determined in accordance with ASCE 41, using a Tier 3 procedure and the two-level performance objective indicated in Table 705.6 for the applicable Risk Category. Site Class shall be determined in accordance with Chapter 16 of the New York City Building Code. Liquefaction evaluation shall be performed in accordance with Chapter 18 of the New York City Building Code.
Table 705.6 Performance Objectives for Use in ASCE 41 for Compliance with New York City Building Code-Level Seismic Forces
RISK CATEGORY (Based on New York City Building Code Table 1604.5) STRUCTURAL PERFORMANCE LEVEL FOR USE WITH BSE-1N EARTHQUAKE HAZARD LEVEL STRUCTURAL PERFORMANCE LEVEL FOR USE WITH BSE-2N EARTHQUAKE HAZARD LEVEL I Life Safety (S-3) Collapse Prevention (S-5) II Life Safety (S-3) Collapse Prevention (S-5) III Damage Control (S-2) Limited Safety (S-4) IV Immediate Occupancy (S-1) Life Safety (S-3)
Section EBC 706. Flood Hazard Areas
706.1 General.
Within areas of special flood hazard in accordance with Section 28-104.9.4 of the Administrative Code, all work for any activity regulated by Appendix G of the New York City Building Code shall be governed by such Appendix.
Section EBC 707. In-Place Material, Component Properties and Archaic Structural Systems
707.1 General.
Methods of design and properties of in-place structural materials, components, and assemblies, including archaic structural systems, shall be determined according to Appendix H or other requirements specified in this code.
Section EBC 708. Remediation Work
708.1 General.
Remediation work shall be performed within the work area as required by Section 708.1.1 and for conditions identified during the course of work independent of work area as required by Section 708.1.2.
708.1.1 Requirements within the work area.
Where during the project structural elements and systems within the work area are exposed by the removal of finishes from walls or floors and applicable structural elements, the following shall be verified and remedied within the work area:
1. Ceilings, flooring or sub-floor removals in unreinforced masonry structures. In structures with unreinforced masonry bearing walls and wood-framed or cold-formed joist floors, where ceilings or floorings are removed and the connection of the joist to the wall is exposed, or where anchors are added to party walls as required by Section 703.7, it shall be verified that there are connections of the wood framed or cold-formed joist floor to the wall including to the unreinforced masonry walls parallel to joists. Where no connections are present, connections shall be installed that comply with the requirements of the New York City Building Code, or Chapter A1 of Appendix A of this code.
2. Ceilings or sheathing removals in wood-framed structures. Where ceilings or sheathing are removed in wood-framed structures, it shall be verified that there is fastening of the wood-framed floor to the wall, including walls parallel to joists. Where no fastening is present, connections shall be made to comply with Chapter 23 of the New York City Building Code.
3. Sill plates in light-frame construction. Where a sill plate in light-frame construction is exposed, it shall be verified that the sill plate is connected to the foundation in conformance with the New York City Building Code. Where the condition does not conform to the New York City Building Code, connections shall be installed to provide 200 plf tension and shear capacity, or in accordance with Chapter A3 of Appendix A of this code.
4. Cripple walls in light-frame construction. Where the work on a light-frame building exposes the cripple wall, it shall be verified that the cripple wall is in conformance with Chapter 23 of the New York City Building Code. Where the condition does not conform to the New York City Building Code, it shall be made to conform, or a connection shall be installed in accordance with Chapter A3 of Appendix A of this code.
5. Headers and trimmers in stair openings. Where headers and trimmers around existing stair openings within the work area have deteriorated or have deflected 2 inches (50.8 mm), they shall be reviewed for compliance with the strength provisions of the New York City Building Code, and brought into compliance if required.
6. Soft stories in unreinforced masonry structures. Where a first floor exterior street or rear wall in an unreinforced masonry bearing wall structure is found to not be present, or if this street or rear masonry wall has been removed in the past, the structure shall be reinforced as required at the soft story to provide adequate gravity and lateral capacity. The altered structure shall be designed for wind loads of Section 705, or be made to conform with Chapter A4 of Appendix A of this code.
7. Existing openings in masonry bearing walls. Where existing openings in masonry bearing walls located at the lot line are exposed by architectural removals in the course of the work, the openings shall be checked for compliance with the structural provisions of the New York City Building Code. If found non-compliant, the conditions shall be addressed.
8. Areas with water piping. Where areas with existing water piping exist within the work area, and the structure is wood framed, the joists and deck beneath the area shall be reviewed for moisture-related or plumbing-related damage, and repaired as required.
9. Bearing of wood structural elements including beams, stair headers, joists and trusses. Where the wood structural element ends that are bearing in masonry pockets are exposed during the project, the condition of the structural elements that are bearing shall be verified, and repaired as required.
10. Sills at foundations. Where sills at foundations are exposed within the work area by removals during the project, the sill conditions shall be verified, and repaired, in accordance with the New York City Building Code, or Chapter A3 of Appendix A of this code.
11. Brick nogging walls. Where a brick nogging wall is exposed while opening the siding or interior finishes of a building and rot or other deterioration is found, that stud, or header as applicable, shall be replaced or sistered. Remedial work shall include all studs or headers placed within 2 feet of a deteriorated wood stud or header. The remediation shall continue until non-deteriorated studs or headers are found. All observed deteriorated mortar between nogging bricks or bricks and wood stud shall be pointed in a manner sufficient to prevent smoke or fire transmission. Facades of wood shingles shall not be covered with other materials without an examination of the condition of underlying studs.
708.1.2 Requirements independent of work area.
The following remediation work shall occur subject to the requirements and conditions of each item:
1. Roof sheathing removals in unreinforced masonry structures. In unreinforced masonry bearing wall and wood-framed floor structures where the sheathing of the roof is removed and the connection of the joist to the wall is exposed, or where anchors are added to party walls as required by Section 703.7, it shall be verified that there are connections of the roof to the wall including to the unreinforced masonry walls parallel to joists. Where no connections are present, connections shall be installed within the area of roof sheathing removal that comply with the requirements of the New York City Building Code, or are installed in accordance with Chapter A1 of Appendix A of this code.
2. Sheathing removals in wood-framed structures. Where sheathing is removed in wood-framed structures, it shall be verified that there is connection of the roof to the wall including walls parallel to joists. Where no connection is present, connections within the area of roof sheathing removal shall be made to comply with Chapter 23 of the New York City Building Code.
3. Bracing of unreinforced masonry parapets. Where a permit is issued for reroofing or roof replacement of more than 25 percent of the roof area, or the repair of a parapet, on a building that has parapets constructed of unreinforced masonry greater than 24” high above the roof plane, the remediation work shall include installation of parapet reinforcing on all such parapets to resist the lateral forces as specified in Sections 703.5 and 703.6 unless an evaluation demonstrates compliance with such requirements. The remediation shall be based on calculations using loads and methods indicated in Chapter 16 of the New York City Building Code, or prescriptive methods in Chapter A1 of Appendix A of this code.
Exceptions:
1. Parapets abutting an existing building wall.
2. The parapet abuts an adjacent roof not greater than 6 feet lower than the base of the parapet.
4. Bond-breaking flashing in masonry parapets. Where horizontal thru-wall flashing is exposed by removals in masonry parapets greater than 24” high above the roof plane, the bond-breaking effect of existing or new horizontal flashing within the parapet shall be structurally evaluated, and if found insufficient, the parapets within the area of removals shall be remediated.
5. Brick chimneys. Where reroofing includes more than 50 percent of area of the roof, the portions of all chimneys above the roof plane shall be examined and repaired or repointed as necessary in accordance with the New York City Building Code, or Chapter A1 of Appendix A of this code.
6. Cornices framed with wood. Where roofing is removed at wood-framed cornices with sheet metal or wood enclosure, it shall be verified that the wood or sheet metal enclosure has not decayed or deteriorated and fasteners are adequate and in good condition. If bracing for the portion above the top of the facade wall is found not present or adequate, it shall be installed within the area of roofing removal unless it can be demonstrated that it is not needed.
7. Bowstring wood trusses. Where a building with bowstring wood trusses is undergoing an alteration, the tension demand-capacity ratio of bottom chord and web members shall be confirmed for all bowstring trusses in the building using wood allowable values in accordance with Chapter 23 of the New York City Building Code, even when the loads are the same or decreased. It shall be confirmed that no damage exists at end bearing or other connections. It shall be confirmed that a continuous, structurally sound lateral bracing of trusses is secured and in place. The structure shall be repaired or strengthened as required.
Exception: Where bowstring trusses have already been previously evaluated and reports accepted by the department, the tension demand-capacity ratio of bottom chord and web members need not be re-evaluated as long as no new loads are added to the truss.
Section EBC 709. Peer Review
709.1. General.
When required, peer reviews shall be performed in accordance with the requirements of Section 1618 of the New York City Building Code for structural peer review, and Section 1818 of the New York City Building Code for geotechnical peer review.
709.2 Structural peer review – where required.
A structural peer review of the primary structure shall be performed for the following:
1. Where the alteration meets the requirements for peer review pursuant to Section 1618.2 of the New York City Building Code.
2. When the altered building is required to meet the structural requirements for a new building in accordance with Section 703.2 of this code, and the altered building meets the requirements of Section 1618.2 of the New York City Building Code.
3. Altered buildings taller than 7 stories where the work involves transferring a column or a column transfer removal that supports in aggregate more than 15 percent of the building area, or where the work involves transferring on 1 element a portion of a wall that portion of which supports more than 25 percent of the building area. In this case, only the design and sequence of the transfer and related load path, including the method of load transfer to the subgrade, shall be subject to peer review.
4. Buildings where a structural peer review is requested by the commissioner.
709.3 Geotechnical peer review - where required.
A geotechnical peer review shall be performed for the following:
1. Where a structural peer review is required pursuant to Section 709.2;
2. When the altered building is required to meet the structural requirements for a new building in accordance with Section 703.2, and the structure is of Risk Category III or IV where the Seismic site class is determined to be Site Class F.
3. Where performance-based foundation design is utilized in the design of the alteration.
4. Buildings where a geotechnical peer review is requested by the commissioner.
Section EBC 710. Structural Integrity
710.1 Prescriptive requirements.
Prescriptive structural integrity requirements of Section 1616 of the New York City Building Code shall be followed for all new structural elements.
710.2 Key Element Analysis.
A Key Element Analysis in accordance with Sections 1617 and 1618 of the New York City Building Code shall be performed for the following:
1. Where the alteration meets the requirements of Section 1617.1 of the New York City Building Code.
2. When the altered building is required to meet the requirements for a new building in accordance with Section 703.2 of this code, and the altered building meets the requirements of Section 1617.1 of the New York City Building Code.
3. Altered buildings taller than 7 stories where the work involves transferring a column or a column transfer removal that supports in aggregate more than 15 percent of the building area, or where the work involves transferring on 1 element a portion of a wall that portion of which supports more than 25 percent of the building area. In this case, only the design and sequence of the transfer and related load path, including the method of load transfer to the subgrade, shall be subject to key element analysis.
4. When specifically ordered by the commissioner.
Section EBC 801. General
801.1 Scope.
Level 1 alterations as described in Section 602 shall comply with the requirements of Chapter 3 and this chapter.
801.2 Compliance.
All new construction elements, components, systems, and spaces shall comply with the requirements of the New York City Building Code as new construction, except as specifically stated in this chapter and Chapter 3 as applicable.
801.2.1 Building safety performance and scoring method.
As an alternative to compliance with any provision of Sections 803, 804 or 805, the registered design professional of record shall be permitted to elect to comply with Chapter 13 and the rules of the department in accordance with Section 301.1.4.
801.3 New and replacement materials, assemblies and details.
Materials, assemblies and details for all new work shall comply with Section 302.4.
Section EBC 802. Reserved
BetaNYC's copy has no text for this section. Read Section EBC 802 at American Legal Publishing.
Section EBC 803. Building Elements and Materials
803.1 Scope.
The requirements of this section are limited to work areas in which Level 1 alterations are being performed, except that they shall apply beyond the work area where specified. The registered design professional of record shall be responsible to verify existing fire-resistive rating conditions of building elements. Use of prior codes to establish lawful existing conditions shall be permitted in accordance with Section 302.8.1.
803.2 Shafts and vertical openings.
Existing shafts and vertical openings shall comply with the provisions of Chapter 7 of the New York City Building Code except as stated in Sections 803.2.1 through 803.2.3 of this code for prior code buildings. Where Chapter 7 of the New York City Building Code allows for a reduction of the existing fire resistance rating, the registered design professional of record shall demonstrate compliance with Section 303.2 of this code.
803.2.1 Existing shafts and vertical openings in prior code buildings.
Existing interior vertical openings, including shafts connecting 2 or more floors, shall meet the requirements of Sections 803.2.1.1 through 803.2.1.12. Existing shafts and vertical openings that were lawfully enclosed in accordance with a prior code shall not be reduced in fire-resistance rating to meet the requirements of this section.
Exceptions:
1. Where vertical opening enclosure is not required by the New York City Building Code.
2. Interior vertical openings other than stairways may be sealed at the floor and ceiling of the work area by construction that is substantively similar to that of the existing floor-ceiling assembly of the work area.
3. An enclosure shall not be required where:
3.1. The opening connects the main floor and a mezzanine; or
3.2. All of the following conditions are met:
3.2.1. The communicating area has a light hazard occupancy or has an ordinary hazard occupancy in accordance with NFPA 13 as modified by Appendix Q of the New York City Building Code;
3.2.2. The communicating area is protected throughout by an automatic sprinkler system;
3.2.3. The communicating area is limited to 2 levels and the lowest or next to the lowest level is a street floor;
3.2.4. The entire area is open and unobstructed in a manner such that it may be assumed that a fire in any part of the interconnected spaces will be readily obvious to all of the occupants. Such open and unobstructed area shall be at least 80 percent of the floor area at each level without intervening partitions;
3.2.5. Exit capacity is sufficient to provide egress simultaneously for all occupants of all levels by considering all areas to be a single floor area for the determination of required exit capacity. The maximum travel distance for all occupants of all levels shall be 75 feet (22 860 mm) within the communicating areas;
3.2.6. Each floor level, considered separately, has at least one-half of its individual required exit capacity provided by an exit or exits leading directly out of that level without having to traverse another communicating floor level or be exposed to the smoke or fire spreading from another communicating floor level; and
3.2.7. The communicating areas are occupied by a single tenant.
803.2.1.1 Group A occupancies.
A minimum 1-hour rated enclosure shall be provided to protect all vertical openings not exceeding 3 stories where occupied by the same tenant and when the building is protected throughout by an approved automatic fire sprinkler system. Convenience stairs connecting such stories shall not be considered part of a required means of egress from each story.
803.2.1.2 Group B occupancies.
A minimum 1-hour rated enclosure shall be provided to protect all vertical openings not exceeding 3 stories. This enclosure shall not be required for buildings not exceeding 3,000 square feet (279 m 2 ) per floor where both of the following conditions are met:
1. The building is protected throughout by an approved automatic fire sprinkler system; and
2. Convenience stairs connecting such stories shall not be considered part of a required means of egress from each story.
803.2.1.3 Group E occupancies.
An enclosure shall not be required for vertical openings not exceeding 3 stories when the building is protected throughout by approved automatic fire sprinkler system and approved fire alarm system.
803.2.1.4 Group F occupancies.
An enclosure shall not be required for vertical openings not exceeding 3 stories where a vertical opening is necessary for manufacturing operations, direct access is provided to at least 1 enclosed stairway and the building is protected throughout by an approved automatic sprinkler system.
803.2.1.5 Group H occupancies.
An enclosure shall not be required for vertical openings not exceeding 3 stories where a vertical opening is necessary for manufacturing operations, every floor level has direct access to at least 2 remote enclosed stairways or other approved exits and the building is protected throughout by an approved automatic fire sprinkler system and approved fire alarm system.
803.2.1.6 Group M occupancies.
A minimum 1-hour rated enclosure shall be provided to protect all vertical openings not exceeding 3 stories. This enclosure shall not be required in buildings protected throughout by an approved automatic sprinkler system and any convenience stair connecting such stories shall not be considered part of a required means of egress from each story.
Exception: Malls designed and constructed under prior codes.
803.2.1.7 Group R-1 occupancies.
An enclosure shall not be required for vertical openings not exceeding 3 stories where such openings serve public areas and the building is protected throughout by an approved automatic sprinkler system and approved fire alarm system.
803.2.1.8 Group R-2 and I-1 occupancies.
A minimum 1-hour rated enclosure shall be provided to protect all vertical openings not exceeding 3 stories. However, vertical openings need not be enclosed within dwelling units in accordance with the following:
1. Vertical openings within dwelling units connecting 2 stories.
2. Vertical openings within dwelling units connecting 3 stories in:
2.1. Combustible buildings protected throughout by an automatic sprinkler system;
2.2. Noncombustible buildings where the dwelling unit containing the vertical opening is protected by an automatic sprinkler system.
803.2.1.9 Group R-3 occupancies.
An enclosure shall not be required for vertical openings or shafts in dwellings not exceeding 3 stories above a basement or where the building is protected throughout by an approved automatic sprinkler system.
803.2.1.10 Group S occupancies.
An enclosure shall not be required for vertical openings for:
1. Buildings connecting not more than 2 floor levels;
2. Buildings connecting not more than 3 floor levels and the structure is equipped throughout with an approved automatic sprinkler system; or
3. Open parking garages and ramps where vertical opening protection is not otherwise required.
803.2.1.11 Vertical openings exceeding 3 stories.
Where vertical openings exceed the limits of Sections 803.2.1.1 through 803.2.10 of this code for Occupancy Groups A, B, E, F, H, M, R-1, R-2, R-3 or S, such openings shall be permitted to be enclosed in accordance with Chapter 7 of the New York City Building Code where the building is protected throughout by an approved automatic sprinkler system. In Occupancy Groups R-1 and R-2 buildings, such enclosure shall not be less than what is required by Appendix D of this code. Buildings in Occupancy Groups E, H and R-1 shall also be provided with fire alarm systems.
803.2.1.12 Group I-2, I-3, and I-4 occupancies.
Vertical openings and shaft enclosures shall be permitted to comply with the New York City Building Code where the building is protected throughout by an approved automatic sprinkler system and approved fire alarm system. Existing shafts and vertical openings that are lawfully enclosed in accordance with prior codes shall be considered in compliance with this section.
803.2.2 Supplemental shaft and floor opening enclosure requirements.
Where the work area on any floor exceeds 50 percent of that floor area, the enclosure requirements of Section 803.2 shall apply to vertical openings other than stairways throughout the floor.
Exception: Vertical openings located in occupied spaces under separate tenancy that are entirely outside the work area.
803.2.3 Supplemental stairway enclosure requirements in prior code buildings.
Where the work area on any floor exceeds 50 percent of that floor area, stairways that are part of the means of egress serving the work area shall, at a minimum, be enclosed with 1-hour fire rated construction on the highest work area floor and all floors below.
Exception: Where stairway enclosure is not required by the New York City Building Code.
803.2.4 Requirements for non-egress convenience stairway or escalator opening.
In an existing building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code, a shaft enclosure is not required for an escalator opening or stairway which is not a portion of the means of egress and which is protected in accordance with the Section 712 of the New York City Building Code.
803.3 Smoke compartments.
In Group I-2 occupancies where the work area is on a story used for sleeping rooms for more than 30 persons sleeping or receiving care or treatment, the story shall be divided into not less than 2 compartments by smoke barrier walls in accordance with Section 407.5 of the New York City Building Code as required for new construction.
803.4 Interior finish.
The interior finish of walls and ceilings in exits and corridors in any work area shall comply with the requirements of the New York City Building Code.
Exception: In prior code buildings, existing interior finish materials that do not comply with the interior finish requirements of the New York City Building Code shall be permitted to be treated with an approved fire-retardant coating in accordance with the manufacturer’s instructions to achieve the required rating. The fire-retardant coating shall be listed by a Nationally Recognized Testing Laboratory.
803.4.1 Supplemental interior finish requirements.
Where the work area on any floor exceeds 50 percent of the floor area, Section 803.4 shall also apply to the interior finish in exits and corridors serving the work area throughout the floor.
Exception: Interior finish within occupied spaces under separate tenancy that are entirely outside the work area.
803.5 Guards.
Every portion of a floor or walking surface, such as a balcony or a loading dock, that is more than 30 inches (762 mm) above the floor or grade below and is not provided with guards, or those in which the existing guards are not adequate in strength and attachment in accordance with the applicable sections of Chapter 16 of the New York City Building Code, shall be provided with guards designed and installed in accordance with Chapter 10 of the New York City Building Code.
803.6 Vaults and reinforced spaces.
Where an alteration to an existing building or space involves the installation of a steel-plated or similarly reinforced or secured vault-like interior in a building or portion thereof, such alteration shall comply with the fire protection requirements of Chapter 9 of the New York City Building Code.
803.7 Windows in Occupancy Groups I-1, R-1, R-2 and R-3.
Where the alteration of an existing building in Occupancy Groups I-1, R-1, R-2 or R-3 includes the replacement of windows, the replacement windows shall be subject to the requirements of Sections 803.7.1 through 803.7.3.
803.7.1 Light and air requirements for replacement windows.
Replacement windows serving dwelling units in Group I-1, R-1, R-2 or R-3 occupancies shall not reduce the area of glazing or operable area below the requirements of Chapter 12 of the New York City Building Code, except where different requirements provided in Appendix D of this code for certain multiple dwelling classifications apply.
Exception. Where replacement windows installed within an existing window frame in R-3 occupancy are required to comply with the New York City Energy Conservation Code, the required window size may be reduced by the thickness of the existing frame. Where replacement of windows in R-3 occupancy requires replacement with a frame/mullions that are larger than the original frame/mullions and results in reduction in glazed area/daylight opening, the new window shall be allowed on condition the new window conforms with all other code requirements. Such reduction shall be minimized to the extent possible.
803.7.2 Window guards in Group R-2 occupancies.
Replacement windows shall be subject to the requirements of Section 303.7 of this code and Section 1015.9 of the New York City Building Code with regard to window guards.
803.7.3 Emergency escape and rescue openings.
Replacement windows in Group R-2 and R-3 occupancies shall comply with Section 303.8.
803.8 Protection of window openings on lot line air shafts in Group R-2 occupancies.
In prior code buildings, where there are windows that open onto a lot line air shaft as defined in Chapter 2 within the work area and any part of such window is less than 3 feet (914 mm) from the lot line or less than 6 feet (1829 mm) from another window on the adjacent building, such window shall be protected in the manner described by Sections 803.8.1 or 803.8.2. For the purpose of this section, separation distance to adjacent buildings shall be measured in any direction to the nearest edges of window openings.
803.8.1 Methods of protection.
Within the work area, windows opening on lot line air shafts shall be protected by 1 of the following methods:
1. The window shall be a fire window assembly meeting the requirements of Sections 705.8.2 and 716.6 of the New York City Building Code, and if the window is operable or is required to be operable by Chapter 12 of the New York City Building Code, the window shall be automatic-closing.
2. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code, the window shall be protected by a water curtain using automatic sprinklers approved for that use in accordance with Section 705.8.2 (Exception) of the New York City Building Code; or
3. The window is protected by a fire shutter complying with Sections 705.8.2 and 716.6 of the New York City Building Code.
803.8.2 A new sprinkler system is to be installed.
Where the installation of a new sprinkler system is proposed throughout a building containing air shaft windows, such windows shall be protected on the interior side, in accordance with Section 705.8.2 (Exception) of the New York City Building Code.
803.9 Existing buildings in fire districts.
Alterations made to existing buildings shall comply with Section 302.6 and Sections 803.9.1 through 803.9.3.
803.9.1 Construction type.
Every existing building, room, or space hereafter altered shall be of a construction type as indicated in Chapter 6 of the New York City Building Code including the required fire resistance rating of bearing walls, floors, roofs and their supporting structural members.
803.9.2 Roof covering.
Roof covering in the fire district shall conform to the requirements of Class A or B roof coverings as defined in Section 1505 of the New York City Building Code.
803.9.3 Existing one- or two-family dwellings.
Where an existing one- or two-family detached, zero lot line or semi-detached dwelling of 3 stories or less in height and 2,500 square feet (232 m 2 ) or less in area located within Zoning Districts R-1 through R-5 within Lower Density Growth Management Areas as defined by the New York City Zoning Resolution constructed of Type VA construction, is damaged, only the damaged portions shall be required to be reconstructed to conform to Type VA construction where such buildings are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code.
803.10 Architectural condition assessment.
Where a building is being altered and the work area exceeds 50 percent of the floor area, the registered design professional of record shall visually assess the condition of fire-resistant building elements and assemblies within the work area, and egress elements serving the work area on that same story. The results and findings of the assessment shall be incorporated in the scope of work as needed. Where the assessment reveals unsafe conditions or deteriorated building elements, such elements shall be remediated, and the unsafe conditions corrected. Such building elements and assemblies shall include:
1. Exit doors: fire rating, self-closing mechanism and as required by Section 805, as applicable.
2. Shafts and vertical openings enclosures.
3. Exit stair enclosure and material combustibility.
4. Fire walls and fire-rated partitions including penetrations and protection of windows and doors.
5. Protection of lot line windows.
6. Fire escape and access thereto, including attachment to exterior wall, stairs, balconies, fire protection of windows and railings.
Such condition assessment need not be repeated for the same work area unless required by the commissioner.
Exception: Alterations of one- and two-family dwellings in occupancy group R-3.
803.10.1 Hazardous conditions.
All conditions noted as hazardous to life, safety or health that are not immediately corrected shall be brought to the immediate attention of the commissioner.
803.11 Bearing of joists.
For non-fireproof buildings erected prior to December 6, 1968, the ends of floor and roof joists and beams shall not be supported on stud partitions, whether wood stud or metal stud. The ends of such joists and beams shall be supported on masonry, girders, trimmer or header beams. When supported on masonry walls, such joists and beams shall be cut to a bevel of 3 inches (914 mm) in their depth and shall have a bearing of at least 4 inches (102 mm) on the masonry. When supported on girders, such joists and beams shall have bearings of at least 4 inches (102 mm), and may be supported by metal stirrups, hangers or bolted hardwood cleats. Tail beams over eight feet (2438 mm) long and trimmer and header beams shall be hung in approved metal stirrups or hangers and shall be spiked unless supported on a wall or girder.
Exception: For buildings that are fully sprinklered and that comply with the height and area limitations of Chapter 5 of the New York City Building Code, connection details for joists and beams shall be permitted to comply with the New York City Building Code.
Section EBC 804. Fire Protection
804.1 Scope.
The requirements of this section shall be limited to work areas in which Level 1 alterations are being performed, except that, where specified, they shall apply throughout the floor on which the work areas are located or otherwise beyond the work area.
804.2 Automatic sprinkler systems.
Automatic sprinkler systems shall be provided in accordance with the requirements of Sections 804.2.1 through 804.2.8 of this code. Installation requirements, materials and methods shall be in accordance with Chapter 9 of the New York City Building Code.
804.2.1 High-rise buildings.
In high-rise buildings, work areas that have exits or corridors shared by more than 1 tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with automatic sprinkler protection in the entire work area where the work area is located on a floor that has a sufficient sprinkler water supply from an existing standpipe, combined standpipe or a sprinkler riser serving that floor.
Exception: If a building does not have sufficient water supply for design of a fire sprinkler system available to the floor without installation of a new fire pump or new water source connection, work areas shall be protected throughout all occupiable spaces not including those in sleeping units or individual dwelling units, and throughout common areas and work spaces such as corridors, lobbies, storage rooms, and equipment rooms, by a partial coverage smoke detection system that activates the occupant notification system in accordance with Sections 907.4, 907.5 and 907.6 of the New York City Building Code.
804.2.1.1 Supplemental automatic sprinkler system requirements.
Where the work area on any floor exceeds 50 percent of that floor area, Section 804.2.1 shall apply to the entire floor on which the work area is located.
Exception: Occupied spaces under separate tenancy that are entirely outside the work area.
804.2.2 Occupancy Groups A, B, E, F-1, H, I, M, R-1, R-2, S-1 and S-2.
In buildings with occupancies in Occupancy Groups A, B, E, F-1, H, I, M, R-1, R-2, S-1 and S-2, work areas that have exits or corridors shared by more than 1 tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with automatic sprinkler protection where both of the following conditions apply:
1. The work area is required to be provided with automatic sprinkler protection in accordance with the New York City Building Code as applicable to new construction; and
2. The work area exceeds 50 percent of the floor area and is located on a floor that has a sufficient sprinkler water supply from an existing standpipe, combined standpipe or a sprinkler riser serving that floor.
Exception: If a building does not have sufficient water supply for design of a fire sprinkler system available to the floor without installation of a new fire pump or new water source connection, work areas shall be protected throughout all occupiable spaces not including those in sleeping units or individual dwelling units, and throughout common areas and work spaces such as corridors, lobbies, storage rooms, and equipment rooms, by a partial coverage smoke detection system that activates the occupant notification system in accordance with Sections 907.4, 907.5 and 907.6 of the New York City Building Code.
804.2.2.1 Mixed uses.
In work areas containing mixed uses, 1 or more of which requires automatic sprinkler protection in accordance with Section 804.2.2, such protection shall not be required throughout the work area provided that the uses requiring such protection are separated from those not requiring protection by fire-resistance-rated construction having a minimum 2-hour rating for Occupancy Group H and a minimum 1-hour rating for all other occupancy groups.
804.2.3 Sprinkler protection required.
Work areas located in above or below grade stories where such stories are required to be sprinklered in accordance with Sections 903.2.11.1 through 903.2.11.3 of the New York City Building Code shall be sprinklered where the building has a sufficient water supply without installation of a new fire pump.
804.2.3.1 Supplemental automatic sprinkler system requirements.
Where the work area on any above or below grade story exceeds 50 percent of the area of that story, Section 804.2.3 shall apply to the entire story on which the work area is located.
Exception: Occupied spaces under separate tenancy that are entirely outside the work area.
804.2.4 Other required automatic sprinkler systems.
In buildings and areas listed in Table 903.2.11.10 of the New York City Building Code, work areas that have exits or corridors shared by more than 1 tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with an automatic sprinkler system where both of the following conditions apply:
1. The work area is required to be provided with an automatic sprinkler system in accordance with the New York City Building Code applicable to new construction; and
2. The building has sufficient water supply available to the floor for the design of an automatic sprinkler system without installation of a new fire pump or new water service connection.
804.2.5 Supervision.
Automatic sprinkler systems required by this section shall be supervised in accordance with Chapter 9 of the New York City Building Code.
804.2.6 Corridor ratings.
Where an approved automatic sprinkler system is installed throughout the story, and throughout the stories immediately above and below the work area, the required fire-resistance rating for any corridor located on the story of the work area shall be permitted to be reduced in accordance with the New York City Building Code.
Exception: Where the dead-end corridor length exceeds that permitted by the New York City Building Code, the required fire-resistance rating for the entire corridor shall not be permitted to be reduced.
804.2.7 Protection of lot line air shaft openings.
Where a sprinkler system is being installed in a building, lot line shaft openings shall be protected in the manner described by Section 803.8.
804.2.8 Special provisions for prior code buildings.
In addition to compliance with Sections 804.2.1 through 804.2.7, existing sprinkler system and components in prior code buildings may comply with Sections 804.2.8.1 and 804.2.8.2.
804.2.8.1 Existing single compartment fire reserve tanks.
Existing single compartment fire reserve tanks with a volume of 15,000 gallons (56781 L) or more that are to be replaced shall be compartmented and sized in conformance with the New York City Building Code.
Exception: Existing single compartment fire reserve tanks, with a volume of 15,000 gallons (56781 L) or more, constructed in accordance with the prior codes, shall be permitted to remain.
804.2.8.2 Automatic sprinkler existing water supply.
The water supply demand for a sprinkler system shall be calculated in accordance with the New York City Building Code and shall include the demand incurred by any new sprinkler heads installed and any existing sprinklers that shall remain. The existing water supply shall be permitted to remain provided that the newly calculated sprinkler system water supply demand does not exceed the existing system water supply capacity.
Exception: Where the existing sprinkler system water supply demand is calculated by taking the reduction in size of the calculated remote area of operation as permitted by NFPA 13 as modified by Appendix Q of the New York City Building Code, and such system is supplied by a fixed duration water supply of less than 5,000 gallons (18927 L), a supplemental water supply demand calculation shall be made without taking the area reduction.
804.2.8.2.1 Existing water supply insufficient to meet newly calculated demand.
Where the newly calculated water supply demand exceeds the existing system water supply capacity, the existing water supply shall be modified to provide the newly required sprinkler system demand. Where the addition or modification of water reserve tanks is impracticable, a reduction of storage to a 20-minute duration in light hazard occupancies shall be permitted, as approved by the department, provided that the reduction in size of the calculated remote area of operation as described in the exception to Section 804.2.8.2 is not taken, and that mechanical automatic means of makeup to the storage tank are installed in accordance with the following:
1. Automatic means of makeup for a tank fire reserve shall be capable of pumping water into the tank, for a period of 20 minutes, at a rate sufficient to equal the difference between the normal 30-minute demand and the alternate 20-minute demand. The demand required shall be calculated for the most demanding remote area from the riser without taking the reduction in size of the remote area otherwise permitted by NFPA 13 as modified by Appendix Q of the New York City Building Code;
2. Where the domestic water house pumps are used for makeup, at least 2 pumps, each of sufficient capacity to meet the makeup requirement, shall be provided; and
3. A low water alarm, listed for its use, shall be located at a point 500 gallons (1893 L) above the fire level reserve.
804.3 Standpipes.
Where the alteration work includes the addition or replacement of an entire exit stair shaft that is a required means of egress, the entire interior exit stair shaft shall be equipped with a standpipe in accordance with Section 905 of the New York City Building Code.
804.3.1 Connection of fire pumps to emergency power system.
The installation of new or replacement of existing fire pumps shall comply with Section 308.4 relating to connection to emergency power system in existing buildings.
804.4 Fire alarm and detection.
An approved fire alarm system shall be installed in accordance with Sections 804.4.1 through 804.4.7. An approved automatic fire detection system shall be installed in accordance with the provisions of this code and NFPA 72 as modified by Appendix Q of the New York City Building Code. Devices, combinations of devices, appliances and equipment shall be approved. The automatic fire detectors shall be smoke detectors, except that an approved alternative type of detector shall be installed in spaces such as boiler rooms, where products of combustion are present during normal operation in sufficient quantity to actuate a smoke detector.
804.4.1 Occupancy requirements.
A fire alarm system shall be installed in accordance with Sections 804.4.1.1 through 804.4.1.5. Existing alarm-notification appliances shall be automatically activated in accordance with the building’s existing approved fire alarm sequence of operations.
Exception: Occupancies with an existing, previously approved fire alarm system.
804.4.1.1 Occupancy Group E and Group I-4.
Where the work area exceeds 10 percent of the portion of the building occupied by occupancy Groups E or I-4 or 25 percent of the area of the floor in which the work area is located, a manual and automatic fire alarm system shall be installed throughout the floor. The installation shall be in accordance with the New York City Building Code and the fire alarm control unit shall be designed to accommodate expansion for the entire occupancy. Once the fire alarm coverage exceeds 50 percent of the entire occupancy, the fire alarm installation shall be extended throughout the occupancy.
Exception: Where a fire alarm system cannot be installed in accordance with the New York City Building Code, the system shall be approved by both the Commissioner and the Fire Commissioner.
804.4.1.2 Occupancy Group I-1.
Where the work area exceeds 10 percent of the portion of the building occupied by occupancy Group I-1 residential care/assisted living facilities or 25 percent of the area of the floor in which the work area is located, a manual and automatic fire alarm system shall be installed throughout the floor in accordance with the New York City Building Code and the fire alarm control unit shall be designed to accommodate expansion for the entire occupancy for existing Group I-1 occupancies. Once the fire alarm coverage exceeds 50 percent of the entire occupancy, the fire alarm installation shall be extended throughout.
Exception: Where a fire alarm system cannot be installed in accordance with the New York City Building Code, the system shall be approved by both the Commissioner and the Fire Commissioner.
804.4.1.3 Occupancy Group I-2.
A fire alarm system shall be installed throughout Group I-2 occupancies in accordance with the New York City Building Code.
804.4.1.4 Occupancy Group I-3.
Where the work area exceeds 10 percent of the portion of the building occupied by occupancy Group I-3 or 25 percent of the area of the floor in which the work area is located, a manual and automatic fire alarm system shall be installed throughout the floor. The installation shall be in accordance with the New York City Building Code and the fire alarm control unit shall be designed to accommodate expansion for the entire occupancy. Once the fire alarm coverage exceeds 50 percent of the entire occupancy, the fire alarm installation shall be extended throughout.
Exception: Where a fire alarm system cannot be installed in accordance with the New York City Building Code, the system shall be approved by both the Commissioner and the Fire Commissioner.
804.4.1.5 Occupancy Group R-1.
A fire alarm system shall be installed in Group R-1 occupancies in accordance with the requirements of the New York City Building Code for Group R-1 occupancies.
804.4.2 Control Units.
Where the capacity of the existing fire alarm system is not sufficient to support the alteration work in accordance with this section, and a new distributed control panel is added to the system, such new panel may be installed in a similar manner with installation and wiring comparable to the existing, approved fire alarm system. Such control panels shall comply with NFPA 72 as modified by Appendix Q of the New York City Building Code with respect to alarm reset capabilities, and any addressable initiating devices connected to the new distributed control panel shall report individually to the primary fire alarm control unit within the building.
804.4.3 Smoke detection.
Smoke detection shall be provided in work areas in accordance with Sections 804.4.3.1 and 804.4.3.3.
804.4.3.1 Smoke detection in individual sleeping and dwelling units.
Individual sleeping units and individual dwelling units in any work area in Group R and I-1 occupancies, where applicable, shall be provided with smoke detection in accordance with the New York City Building Code.
Exceptions:
1. Interconnection of smoke alarms outside of the work area to those installed inside the work area in accordance with this code shall not be required.
2. Existing I-1 occupancies that utilize smoke alarms for individual sleeping units or individual dwelling units are permitted to install smoke alarms in the work area in lieu of smoke detectors.
804.4.3.1.1 Smoke and carbon monoxide alarms in dwelling units during alterations involving removal of existing interior finishes in prior code buildings.
Smoke and carbon monoxide alarms complying with the location, interconnection and power source requirements of Chapter 9 of the New York City Building Code shall be provided throughout a dwelling unit when alteration work results in the removal of existing and/or installation of new interior wall or ceiling finishes permitting the installation of concealed wiring for all the required alarms throughout the dwelling unit.
804.4.3.2 Smoke detection in other spaces.
Where required by Chapter 9 of the New York City Building Code, in buildings that have an existing approved fire alarm system, smoke detection shall be provided in the following spaces when such spaces are included within the work area:
1. In each mechanical equipment, electrical, transformer, telephone equipment or similar room, in elevator machine rooms and in elevator lobbies.
2. In air distribution systems in accordance with Section 606 of the New York City Mechanical Code.
804.4.3.3 Smoke detectors in elevator lobbies and elevator landings of Group R-2 occupancies.
Where a new or upgraded fire alarm system is installed in a Group R-2 occupancy building in accordance with Chapter 9 of the New York City Building Code , the smoke detectors required to be installed at elevator lobbies, elevator landings, elevator machine rooms, or elevator hoistways shall be programmed to initiate Phase I emergency operations.
804.4.4 Location of fire alarm control equipment.
Fire alarm equipment and associated wiring shall be located in spaces within buildings in accordance with the New York City Building Code.
Exception. In prior code buildings, fire alarm control equipment and associated wiring may be installed in exit enclosures provided that such installations do not reduce the egress width below that required by code and a smoke detector need not be installed at the location of such fire alarm control unit.
804.4.5 Existing Mini class “E” and Advisory class “E” systems in prior code buildings.
Replacement of existing Mini class E and Advisory class E systems shall be made to comply with Chapter 9 of the New York City Building Code for that building or space.
804.4.6 Existing fire alarm systems in prior code places of assembly used as a cabaret.
Replacement of existing fire alarm systems in cabarets shall be made to comply with Chapter 9 of the New York City Building Code for that building or space.
804.4.7 Fire alarm system alterations and replacements in existing buildings.
Existing, approved fire alarm systems undergoing alterations or being replaced shall comply with the requirements of Section 804.4.7.1 through 804.4.7.5. For the purpose of applying the following sections, alteration applications that have not been signed off shall be cumulatively considered.
804.4.7.1 Replacement of the Fire Command Center (FCC), Fire Command Station (FCS) or Fire Alarm Control Panel (FACP).
Where the scope of work constitutes the replacement in kind of the FCC, FCS or FACP, full replacement of the fire alarm system shall not be required provided that the following conditions are met:
1. The sequence of operations shall match that of the existing system.
2. Where the existing power capacity is not adequate, a new connection that complies with the New York City Electrical Code shall be provided to the replacement equipment.
804.4.7.2 Relocation of the Fire Command Center (FCC), Fire Command Station (FCS) or Fire Alarm Control Panel (FACP).
Where the scope of work constitutes the relocation of the FCC, FCS, or FACP, the work shall comply with Section 804.4.7.1 and the following additional requirements:
1. The new proposed location shall be approved by the fire commissioner.
2. Existing power wiring and existing fire alarm system wiring may be utilized. Splicing of existing power wiring and existing fire alarm system wiring is prohibited.
3. Where an FCC, FCS or FACP is relocated, proximity requirements for related systems and controls shall be maintained including, but not limited to, elevator control panels and mechanical fan control panels.
804.4.7.3 System technology upgrade.
A system technology upgrade to an existing, approved fire alarm system shall comply with Sections 804.4.7.3.1 through 804.4.7.3.8. Where the scope of work includes upgrade or replacement of the Fire Command Center (FCC), Fire Command Station (FCS), or Fire Alarm Control Panel (FACP), and also includes the upgrade, replacement or addition of fire alarm control unit(s), a system replacement is not required provided that no more than 2 of the following thresholds are exceeded:
1. More than 75 percent of existing notification appliances are replaced in kind.
2. Power-limited fire alarm (PLFA) wiring between control unit(s) and initiating devices or notification appliances is replaced in more than 25 percent of the building's floor area.
3. More than 75 percent of the sum of existing initiating devices and existing emergency control function interface equipment are altered or replaced in kind. The percentage calculation shall not include any initiating devices being added to comply with selective coverage smoke detection requirements of Section 907.2 of the New York City Building Code.
4. More than 75 percent of the sum of existing warden telephone stations and firefighter telephones are replaced in kind.
804.4.7.3.1 Control units.
New or upgraded control units may be located in the same room or location as the existing control units.
804.4.7.3.2 Circuits.
Fire alarm system wiring used to interconnect control units shall meet the class and survivability requirements of the New York City Building Code applicable to new systems.
804.4.7.3.3 Smoke detection.
Selective coverage smoke detection as required by Section 907.2 of the New York City Building Code shall be installed.
804.4.7.3.4 Notification appliance circuits.
All notification appliance circuits shall be supervised upon completion of the system technology upgrade.
804.4.7.3.5 Operation sequence.
The system’s operation sequence shall be modified to comply with that required for a new building of the same characteristics.
804.4.7.3.6 Power connections.
Where the existing power capacity serving the existing fire alarm system is not adequate to power the upgraded fire alarm system, new AC power connections shall be provided for all upgraded fire alarm control equipment in accordance with the New York City Electrical Code.
804.4.7.3.7 Wiring.
Existing wiring not affected by the upgrade shall be permitted to remain.
804.4.7.3.8 Existing to remain.
Existing, functional initiating devices and notification appliances not affected by the upgrade shall be permitted to remain.
804.4.7.4 System replacement.
Where the scope of work includes a full replacement of the existing, approved fire alarm system, the system shall be installed in accordance with Section 907 of the New York City Building Code and in accordance with the applicable sections of the New York City Electrical Code.
804.4.7.5 Emergency and standby power for fire alarm upgrades and replacements in prior code buildings.
Where a fire alarm system is being altered or replaced in accordance with Section 804.4.7, and where the existing building does not have an on-site generator for emergency or standby power loads, installation of a generator to provide secondary power to the fire alarm system shall not be required. However, where the existing building does have an on-site generator for emergency or standby power loads, connection of the upgraded fire alarm system to the existing generator in accordance with Chapter 27 of the New York City Building Code shall be required.
Section EBC 805. Means of Egress
805.1 Scope.
The requirements of this section shall be limited to work areas that include exits or corridors shared by more than 1 tenant within the work area in which Level 1 alterations are being performed, except that, where specified for supplemental requirements, they shall apply throughout the floor on which the work areas are located or otherwise beyond the work area.
805.2 General.
The means of egress shall comply with the requirements of this section and Section 305.
805.3 Number of exits.
The number of exits shall be in accordance with Sections 805.3.1 through 805.3.3.
805.3.1 Minimum number.
Every story utilized for human occupancy on which there is a work area that includes exits or corridors shared by more than 1 tenant within the work area shall be provided with the minimum number of exits based on the occupancy and the occupant load in accordance with the New York City Building Code and Section 305.5.1 of this code. In addition, the exits shall comply with Sections 805.3.1.1 through 805.3.1.3.
805.3.1.1 Single-exit buildings.
Only 1 exit is required from buildings and spaces when permitted by Section 1006.3 of the New York City Building Code.
805.3.1.1.1 Prior code buildings.
In prior code buildings, 1 means of egress shall be permitted from floors in:
1. One- and two-family dwellings classified in Occupancy Group R-3.
2. Buildings classified in Occupancy Group B that are not more than 60 feet (18 288 mm) in height, have a gross area of 2,000 square feet (186 m 2 ) or less per floor, and have a maximum travel distance of 50 feet (15 240 mm) on any floor.
3. Buildings classified in Occupancy Group R-2 that are of noncombustible construction, have a gross area of 2,000 square feet (186 m 2 ) or less per floor, and have a maximum travel distance of 50 feet (15 240 mm) on any floor.
4. Buildings classified in Occupancy Group R-1 or R-2 that are not more than 2 stories and not more than 30 feet (9 144 mm) in height and have a maximum travel distance of 80 feet (24 384 mm), and the corridors and stair enclosure are provided with automatic sprinkler protection.
5. Buildings classified in Occupancy Group R-2 occupied exclusively by not more than one family on each story without boarders, roomers or lodgers and that are not more than 3 stories and not more than 40 feet (12 192 mm) in height, and the stair enclosure is provided with automatic sprinkler protection and without openings between any garage and the exit passageway.
6. Buildings classified in Occupancy Group R-2 that are not more than 3 stories and not more than 40 feet (12 192 mm) in height and occupied by not more than 4 families on each story, and the building is protected with an automatic sprinkler system.
7. Buildings constructed pursuant to codes prior to the 1968 Building Code with a floor area of 2,500 square feet (232.25 m 2 ) or less and 75 feet (22 860 mm) or less in height, only 1 required stairway need be provided when the occupancy on any floor above grade is 1 person for each 50 square feet (4.6 m 2 ) or more of floor area.
805.3.1.2 Multilevel dwelling units.
Multilevel dwelling units occupying a part of not more than 2 floors in buildings classified in Occupancy Group R-2 shall comply with Chapter 10 of the New York City Building Code.
Exception: In multilevel dwelling units occupying a part of not more than 2 floors in prior code buildings classified in Occupancy Group R-2, an exit shall not be required from every level of the dwelling unit provided that all of the following conditions are met:
1. The building is of noncombustible construction;
2. One level of the dwelling unit shall be the exit level with exit access doorway to 2 means of egress or as permitted by Section 805.3.1.1.1, and the other level is provided with a balcony connecting such level to an adjacent dwelling unit, in accordance with Section 305.5.19;
3. The maximum travel distance within the dwelling unit does not exceed 50 feet (15 240 mm) from any room within such dwelling unit measured to the centerline of the exit access door providing access to the 2 means of egress; and
4. The connecting stair shall be at least 2 feet 6 inches (762 mm) in width and terminate not more than 20 feet (6096 mm) from the exit access door on the exit level. However, a greater width may be required pursuant to Chapter 11 of the New York City Building Code.
805.3.1.3 Fire escapes required.
Where permitted by Section 305.5.16 in prior code buildings, an existing fire escape or newly constructed fire escape shall be accepted as providing 1 of the required means of egress.
805.3.2 Mezzanines.
Mezzanines in the work area and with an occupant load that exceeds that permitted by Table 805.4.1.1 or in which the travel distance to an exit exceeds 75 feet (22 860 mm) shall have access to at least 2 independent means of egress.
Exception: Travel distance may be extended to 100 feet (30 480 mm) including path of travel along connecting stair where the building is protected throughout with an automatic sprinkler system.
805.3.3 Main exit – Occupancy Group A.
All buildings classified in Occupancy Group A with an occupant load of 300 or more shall be provided with a main entrance capable of serving as the main exit with an egress capacity of at least one-half of the total occupant load. The remaining exits shall be capable of providing one-half of the total required exit capacity.
Exceptions:
1. Where there is no well-defined main exit or where multiple main exits are provided, exits shall be permitted to be distributed around the perimeter of the building provided that the total width of egress is not less than 100 percent of the required width.
2. Existing places of assembly with valid Place of Assembly Certificates of Operation in prior code buildings.
3. Existing special occupancy structures.
805.4 Egress doorways.
Egress doorways in any work area shall comply with Section 1006 of the New York City Building Code and Sections 805.4.1 through 805.4.5 of this code.
805.4.1 Required number of exits or exit access doorways.
Work areas shall be provided with exits or exit access doorways in accordance with the requirements of Section 1006.2 of the New York City Building Code except as stated in Sections 805.4.1.1 and 805.4.1.2 of this code.
805.4.1.1 Required number of exits and exit access doorways in prior code buildings.
In any work areas in prior code buildings, all rooms and spaces having an occupant load not greater than specified in Table 805.4.1.1 shall be permitted to have 1 exit access doorway. In work areas in prior code buildings, rooms and spaces having an occupant load greater than specified by Table 805.4.1.1 shall have a minimum of 2 exit access doorways.
Table 805.4.1.1 Maximum Occupant Load for Spaces with One Exit Access Door in Prior Code Buildings
OCCUPANCY GROUP CLASSIFICATION MAXIMUM OCCUPANT LOAD WITH 1 EXIT ACCESS DOOR H 10 S 50 M 74 F 50 B 74 A 74 E 74 I-1, I-2, I-3, I-4 15 R-1, R-2, R-3 20
805.4.1.2 Occupancy Group I-2.
In buildings classified as Group I-2 occupancy, any patient sleeping room or suite of patient rooms greater than 1,000 square feet (93 m 2 ) within the work area shall have a minimum of 2 egress doors.
805.4.2 Door swing.
In the work area, all means of egress doors serving rooms or spaces requiring more than 1 exit access door shall swing in the direction of exit travel. All means of egress doors from work areas that include an automatic teller machine (“ATM”) shall swing in the direction of exit travel.
805.4.2.1 Supplemental requirements for door swing.
Where the work area exceeds 50 percent of the floor area, door swing shall comply with Section 805.4.2 throughout the floor.
Exception: Means of egress within or serving only an occupied space under separate tenancy that is entirely outside the work area.
805.4.3 Door closing.
In any work area, all doors opening onto an exit passageway at grade or an exit stairway shall be self-closing or automatic-closing by listed closing devices.
Exception: Where exit enclosure is not required by the New York City Building Code.
805.4.3.1 Supplemental requirements for door closing.
Where the work area exceeds 50 percent of the floor area, door closing shall comply with the following requirements:
1. New or existing fire doors opening from the work area to exit stairways, exit passageways at grade or exit discharge shall comply with Section 805.4.3; and
2. The building owner shall certify, in a form acceptable to the department, that all other fire doors throughout the exit stairway from the level of the work area to the exit discharge, including fire doors to exit passageways and exit discharge, are self-closing or automatic-closing in accordance with Section 716.5.9 of the New York City Building Code.
805.4.4 Panic hardware.
In any work area, and in the egress path from any work area to the exit discharge, in buildings or portions thereof classified as Group H occupancies, Groups A and E occupancies with an occupant load greater than 74, and non-accessory tenant spaces or accessory rooms or spaces used for assembly purposes permitted to be classified as Group B occupancies, all required exit doors equipped with latching devices shall be equipped with approved panic hardware.
805.4.4.1 Supplemental requirements for panic hardware.
Where the work area exceeds 50 percent of the floor area, panic hardware shall comply with Section 805.4.4 throughout the floor.
Exception: Means of egress within an occupied space under separate tenancy that is entirely outside the work area.
805.4.5 Emergency power source in Occupancy Group I-3.
Power-operated sliding doors or power-operated locks for swinging doors shall be operable by a manual release mechanism at the door. Emergency power shall be provided for the doors and locks in accordance with Chapter 27 of the New York City Building Code.
Exceptions:
1. Emergency power is not required in facilities with 10 or fewer locks complying with the exception to Section 408.4.1 of the New York City Building Code.
2. Emergency power is not required where remote mechanical operating releases are provided.
805.5 Openings in corridor walls.
Openings in interior or public corridor walls in any work area shall comply with Sections 805.5.1 through 805.5.4.
Exception: Openings in corridors where such corridors are not required to be rated in accordance with the New York City Building Code.
805.5.1 Corridor doors.
Corridor doors in the work area shall be constructed to comply with Section 1010 of the New York City Building Code.
Exceptions:
1. Existing doors in buildings protected throughout with an approved automatic sprinkler system shall be required only to resist smoke, be reasonably tight fitting and shall not contain louvers.
2. In group homes with a maximum of 15 occupants that are protected with an approved automatic smoke detection system, closing devices may be omitted.
3. Door assemblies having a fire-resistance rating of at least 3/4 of an hour.
4. In prior code buildings classified in Occupancy Group E, in which an approved interior fire alarm system is installed and in which regular supervised fire drills are held, the doors to rooms or spaces devoted exclusively to nonhazardous uses in Occupancy Group E need not be fire rated, provided they are swinging, self-closing 1 3/4-inch solid core wood, and have a maximum area of 720 square inches (18 288 mm 2 ) of 1/4” thick laminated safety glass or fire-rated glass.
805.5.2 Transom openings.
Transom openings shall not be permitted in corridor walls. All existing transom openings in corridor walls within the work area shall be sealed with materials consistent with the corridor construction.
Exception: Existing transom openings in corridor walls that are not required to be rated in accordance with Chapter 10 of the New York City Building Code.
805.5.3 Other corridor openings.
Except as provided in Section 805.5.1 and 805.5.2, in any work area, any sash, grille, or opening in a corridor, and any window in a corridor not opening to the street, yard or court shall be sealed or replaced with materials or assemblies consistent with the corridor construction.
805.5.4 Supplemental requirements for corridor openings.
Where the work area on any floor exceeds 50 percent of the floor area, the requirements of Sections 805.5.1 through 805.5.3 shall apply throughout the floor.
Exception: Interior corridors in occupied spaces under separate tenancy that are entirely outside the work area.
805.6 Dead-end corridors.
Dead-end corridors in any work area shall not exceed 20 feet (6096 mm).
Exceptions:
1. Existing buildings that are protected throughout by sprinkler and fire alarm systems shall be permitted to comply with the requirements of Chapter 10 of the New York City Building Code.
2. Dead-end corridors in prior code buildings shall be permitted to comply with Table 805.6.
Table 805.6 Maximum Length of Dead-end Corridor (ft.)
Occupancy Group Max. Dead-End Length (ft) a Assembly A 30 Business B 50 Educational E 30 b Factory F 50 High Hazard H NP Institutional I-1, I-2, I-4 30 c I-3 40 Mercantile M 50 Residential R-1, R-2 40 R-3 NR Storage S1 50 S2 NR Utility U NR
For SI: 1 foot = 304.8 mm.
NP – Not Permitted NR – Not Required
Notes:
a. Except in occupancy group I, when a corridor is completely enclosed in construction having a two-hour fire resistance rating, with all corridor doors being self-closing and having a fire protection rating of 1 and one-half hours, the permissible length of dead ends may be increased 100 percent above the length listed in Table 805.6.
b. There shall not be more than 1 classroom on each side of a corridor between an exit and the end of the corridor (dead end).
c. There shall be no patient bedrooms between an exit and the end of the corridor (dead end).
805.7 Means-of-egress lighting.
Means-of-egress lighting shall be in accordance with this section, as applicable.
805.7.1 Artificial lighting required.
Means of egress in all work areas shall be provided with artificial lighting in accordance with the requirements of Chapter 10 of the New York City Building Code.
Exception: Modifications to existing places of assembly subject to the limitations of Section 305.5.18.1 of this code in prior code buildings and in existing motion picture theaters, theaters, concert halls, operas and similar places of assembly accommodating more than 300 persons that were established under Article 13 of the 1938 Building Code, including those constructed prior to 1938, shall be provided with lighting in compliance with the requirements applicable when the building was erected, or under the applicable requirements for the place of assembly when the place of assembly permit was issued, whichever is more restrictive. In addition, such existing places of assembly are permitted to comply with the requirements of Chapter 10 of the New York City Building Code.
805.7.2 Supplemental requirements for means-of-egress lighting.
Where the work area on any floor exceeds 50 percent of that floor area, means of egress lighting throughout the floor shall comply with Section 805.7.1.
Exceptions:
1. Means of egress within or serving only an occupied space under separate tenancy that is entirely outside the work area.
2. Existing means of egress lighting may be maintained where work is limited to change in seating arrangements, stages and platforms in existing places of assembly in prior code buildings pursuant to Section 305.5.18.1.1.
3. Existing means of egress lighting may be maintained in temporary places of assembly pursuant to Section 305.5.18.
805.8 Exit signs.
Exit signs shall be in accordance with this section, as applicable.
805.8.1 Work areas.
Means of egress in all work areas shall be provided with exit signs in accordance with the requirements of Chapter 10 of the New York City Building Code.
Exception: In existing motion picture theaters, theaters, concert halls, operas and similar places of assembly accommodating more than 300 persons that were established under Article 13 of the 1938 Building Code, including those constructed prior to 1938, requirements for exit sign graphics pursuant to Chapter 10 of the New York City Building Code shall not apply to existing exit signs installed under the 1938 Building Code or codes prior to the 1938 Building Code. Existing exit sign graphics may remain or be replaced with similar graphics.
805.8.2 Supplemental requirements for exit signs.
Where the work area on any floor exceeds 50 percent of that floor area, means of egress throughout the floor shall comply with Section 805.8.1.
Exceptions:
1. Means of egress within an occupied space under separate tenancy that is entirely outside the work area.
2. In existing motion picture theaters, theaters, concert halls, operas and similar places of assembly accommodating more than 300 persons that were established under Article 13 of the 1938 Building Code, including those constructed prior to 1938, requirements for exit sign graphics pursuant to Chapter 10 of the New York City Building Code shall not apply to existing exit signs installed under the 1938 Building Code or codes prior to the 1938 Building Code. Existing exit sign graphics may remain or be replaced with similar graphics.
805.9 Handrails.
The requirements of Sections 805.9.1 shall apply to handrails from the work area floor to, and including, the level of exit discharge.
805.9.1 Minimum requirement.
In prior code buildings, every required exit stairway that is part of the means of egress for any work area in which the existing handrails are not adequate in strength and attachment in accordance with the applicable sections of Chapter 16 of the New York City Building Code shall be provided with handrails designed and installed in accordance with Section 305.5.13 of this code.
805.10 Refuge areas.
Where alterations affect the configuration of an area utilized as a refuge area, the capacity of the refuge area shall not be reduced below that required in Sections 805.10.1 and 805.10.2.
805.10.1 Capacity.
The required capacity of refuge areas shall be in accordance with Sections 805.10.1.1 through 805.10.1.3.
805.10.1.1 Occupancy Group I-2.
In Group I-2 occupancies, the required capacity of the refuge areas for smoke compartments in accordance with Section 407.5.1 of the New York City Building Code shall be maintained.
805.10.1.2 Occupancy Group I-3.
In Group I-3 occupancies, the required capacity of the refuge areas for smoke compartments in accordance with Section 408.6.2 of the New York City Building Code shall be maintained.
805.10.1.3 Ambulatory care.
In ambulatory care facilities required to be separated by Section 422.2 of the New York City Building Code, the required capacity of the refuge areas for smoke compartments in accordance with Section 422.4 of the New York City Building Code shall be maintained.
805.10.2 Horizontal exits.
The required capacity of the refuge area for horizontal exits in accordance with Section 1026.4 of the New York City Building Code shall be maintained.
805.11 Guards.
The requirements of Section 805.11.1 shall apply to guards from the work area floor to, and including, the level of exit discharge but shall be confined to the egress path of any work area.
805.11.1 Minimum requirement.
Every open portion of a stairway, landing or balcony that is more than 30 inches (762 mm) above the floor or grade below and is not provided with guards, or those portions in which existing guards are judged to be in danger of collapsing, shall be provided with guards designed and installed in accordance with Chapter 10 of the New York City Building Code.
805.12 New egress stairs.
Where the work area includes the construction of a new egress stair in a new shaft, such new stair shall comply with all the requirements of Chapter 10 of the New York City Building Code.
805.12.1 Replacement of stair within an existing shaft.
Existing stairs may be replaced within the existing shaft provided that they comply with Sections 305.5.11, 305.5.13 and 305.5.15.
805.13 Escalators.
Replacement or alteration of existing escalators that were approved to be used as a second means of egress in prior code buildings shall be permitted to serve such purpose in compliance with Section 305.5.17. No new escalators shall be used as a component of a required means of egress.