NYC Administrative Code Title 28, Chapter 12 The New York City Existing Building Code (effective July 17, 2027), part 3 of 5
Section EBC 806 to Section EBC A102: 57 sections.
Section EBC 806. Accessibility
806.1 General.
A building, facility, or element that is altered shall comply with Chapter 11 of the New York City Building Code, Section 306 of this code and this section.
806.1.1 Extent of application.
An alteration of an existing element, space, or area of a facility shall not be required to provide a greater level of accessibility than that which would be required for new construction. Alterations shall not reduce or have the effect of reducing accessibility of a facility or portion of a facility.
806.2 Compliance.
A facility that is altered shall comply with the applicable provisions in Sections 806.2.1 through 806.2.14 of this code and Chapter 11 of the New York City Building Code to the extent of the alteration, unless it is technically infeasible. Where compliance with this section is technically infeasible, the applicant of record shall seek a commissioner’s waiver in accordance with Section 306.3 of this code.
A facility that is constructed or altered to be accessible shall be maintained accessible during occupancy.
Exceptions:
1. Where Chapter 11 of the New York City Building Code would exempt the altered element or space from compliance, if it were new construction.
2. Accessible means of egress required by Chapter 10 of the New York City Building Code are not required to be provided in existing facilities.
806.2.1 Entrances and accessible routes.
Where an alteration includes alterations to an entrance or a route that would be required to be accessible by this code, such entrance and route shall be made accessible in accordance with Chapter 11 of the New York City Building Code.
806.2.2 Elevators.
Altered elements of existing elevators shall comply with ASME A17.1/CSA B44 as amended by Appendix K of the New York City Building Code and ICC A117.1. Where such altered elevator is part of a bank of elevators that are programmed to respond to the same hall call control panel, similar elements of the other elevators shall also be altered to comply.
806.2.3 Platform lifts in existing buildings.
In existing buildings, platform (wheelchair) lifts installed pursuant to Section 306.2.5 shall be permitted to be a part of the required accessible route.
806.2.4 Limited Use / Limited-Application (LULA) Elevators in existing buildings.
In existing buildings, a LULA installed pursuant to Section 306.2.4 shall be permitted to be a part of the required accessible route.
806.2.5 Stairways and escalators in existing buildings.
Where an escalator or stairway is added where none existed previously, an accessible route shall be provided between the levels served by the escalator or stairways in accordance with Section 1104.4 of the New York City Building Code.
Exception: Where the levels to be connected by an escalator or stairway are already provided with an accessible route.
806.2.6 Ramps.
Where steeper slopes than allowed by Section 1012.2 of the New York City Building Code are necessitated by space limitations, the slope of ramps in or providing access to existing facilities shall comply with Table 806.2.6 of this code.
Table 806.2.6 Ramps
SLOPE MAXIMUM RISE Steeper than 1:10 but not steeper than 1:8 3 inches Steeper than 1:12 but not steeper than 1:10 6 inches
For SI: 1 inch = 25.4 mm.
806.2.7 Dining areas.
An accessible route to raised or sunken dining areas or to all parts of outdoor seating areas is not required provided that the same services and decor are provided in an accessible space usable by any occupant and not restricted to use by people with a disability. The raised, sunken, or outdoor seating areas not provided with an accessible route shall not exceed 25 percent of the total combined area for accessible dining areas.
806.2.8 Dwelling and sleeping units.
Where dwelling or sleeping units are altered, they shall comply with Sections 806.2.8.1 through 806.2.8.2.
806.2.8.1 Alterations to dwelling or sleeping units in occupancy Group I-1, I-2, I-3 or R-1.
Where dwelling or sleeping units are altered in occupancy Group I-1, I-2, I-3 or R-1, the requirements of Section 1107 of the New York City Building Code shall apply only to the spaces being altered.
Exception: Where the dwelling or sleeping units included in the work area exceeds more than 50 percent of the dwelling or sleeping units in the building and under single ownership, the requirements of Section 1107 of the New York City Building Code shall apply to all the dwelling or sleeping units under that single ownership.
806.2.8.2 Alterations to dwelling or sleeping units in Occupancy Group R-2.
Where dwelling or sleeping units are altered in Occupancy Group R-2, the requirements of Section 1107 of the New York City Building Code shall apply only to the spaces being altered.
806.2.9 Toilet and bathing rooms.
Where it is technically infeasible to alter existing toilet and bathing rooms to be accessible, an accessible family or assisted-use toilet or bathing room constructed in accordance with the requirements of Sections 1109.2.1 through 1109.2.1.6 of the New York City Building Code is permitted; however, the family or assisted-use toilet or bathing room shall be located on an accessible route, on the same floor and in the same area as the existing toilet or bathing rooms. At the inaccessible toilet and bathing rooms, directional signs indicating the location of the nearest family or assisted-use toilet room or bathing room shall be provided. These directional signs shall include the dynamic accessibility symbol and sign characters shall meet the visual character requirements in accordance with ICC A117.1.
806.2.10 Dressing, fitting and locker rooms.
Where it is technically infeasible to provide accessible dressing, fitting or locker rooms at the same location as similar types of rooms, 1 accessible room on the same level shall be provided. At the dressing, fitting or locker rooms, directional signs indicating the location of the nearest accessible dressing, fitting and locker room shall be provided. These directional signs shall include the dynamic accessibility symbol and sign characters shall meet the visual character requirements in accordance with ICC A117.1. Where separate sex facilities are provided, accessible rooms for each sex shall be provided. Separate sex facilities are not required where only unisex rooms are provided.
806.2.11 Fuel dispensers.
Operable parts of replacement fuel dispensers shall comply with the applicable requirements of Chapter 11 of the New York City Building Code.
Exception: Where existing curbs make compliance technically infeasible, operable parts may be permitted to be 54 inches (1372 mm) maximum measured from the surface of the vehicular way where fuel dispensers are installed on existing curbs.
806.2.12 Thresholds.
The maximum height of thresholds at doorways shall be in accordance with ICC A117.1.
806.2.13 Amusement rides.
Where the structural or operational characteristics of an amusement ride are altered to the extent that the amusement ride’s performance differs from that specified by the manufacturer or the original design, the amusement ride shall comply with requirements for new construction in accordance with Section 1110.4.8 of the New York City Building Code.
806.2.14 Electric vehicle charging stations.
In an alteration where electric vehicle charging stations are added or altered, the charging station shall be located along an accessible route and comply with Section 1106.8 of the New York City Building Code.
Exception: In existing facilities with no accessible route, electrical vehicle charging stations are not required to be located along an accessible route.
806.3 Alterations affecting an area containing a primary function.
Where an alteration affects the accessibility to or contains an area of primary function, the route to the primary function area, including entrances, shall be accessible in accordance with this section and Section 806.3.1. The accessible route to the primary function area shall include toilet facilities and drinking fountains serving the area of primary function. The costs of providing the accessible route are not required to exceed 25 percent of the costs of the alterations affecting the area of primary function.
Exceptions:
1. This provision does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets and signs.
2. This provision does not apply to alterations limited solely to mechanical systems, electrical systems, installation or alteration of fire protection systems and abatement of hazardous materials.
3. This provision does not apply to alterations undertaken for the primary purpose of increasing the accessibility of a facility.
4. This provision does not apply to altered areas limited to Type B or Type B+NYC dwelling and sleeping units.
806.3.1 Path of travel prioritization.
The cost of improvements along the path of travel shall be prioritized in accordance with the following:
1. Accessible entrances.
2. Accessible route to the altered area.
3. Accessible toilet facilities.
4. Accessible drinking fountains and bottle-filling stations.
5. Accessible telephones.
6. Additional items such as parking, storage and alarms.
Section EBC 807. Structural
807.1 General.
Structural elements and systems within buildings undergoing Level 1 alterations shall comply with Chapter 7.
Section EBC 808. Electrical
808.1 New installations.
All newly installed electrical equipment and wiring relating to work done in any work area shall comply with all applicable requirements of the New York City Electrical Code and as provided for in Sections 808.3 through 808.5 of this code.
808.2 Existing installations.
Existing wiring and equipment supplying the work area that is found to be defective shall be upgraded in Group A-1, A-2, A-5, H and I occupancies to meet the requirements of the New York City Electrical Code. For purposes of this section, the term “defective wiring” means wiring methods and materials that do not conform to the requirements of Article 110 of the New York City Electrical Code and present an imminent danger to occupants. Examples of defective wiring include unprotected conductors or oversized overcurrent protection devices that are unsuitable for the environment they are installed in, and obsolete wiring methods such as knob and tube. For purposes of this section, the term “defective equipment” means any electrical equipment or its installations that are found to be dangerous to human life or property. Examples of defective equipment include ungrounded and unbonded equipment; equipment that is overloaded and inadequate to serve the connected loads; unapproved or unlisted equipment; deteriorating equipment; and equipment that is corroded or shows signs of water damage.
808.3 Residential occupancies.
Any work within a dwelling unit in Group R-2 and R-3 occupancies that involves the removal of wall coverings (such as gypsum-board and plaster) or relocation / addition of walls and partitions in the work area must conform to the requirements of Sections 210.52 and 210.70 of the New York City Electrical Code with respect to the required receptacle outlets and lighting outlets in the dwelling unit. Any work within a dwelling unit in Group R-2 and R-3 occupancies that does not involve the removal of wall coverings (such as gypsum-board and plaster) or relocation / addition of walls and partitions in the work area shall require the installation of new receptacle outlets and lighting outlets in any work area in accordance with the requirements of Sections 808.3.1 through 808.3.6.
808.3.1 Enclosed areas.
All enclosed areas, other than closets, kitchens, basements, garages, hallways, laundry areas, utility areas, storage areas and bathrooms shall have a minimum of 2 duplex receptacle outlets or 1 duplex receptacle outlet and 1 ceiling or wall-type lighting outlet.
808.3.2 Kitchens.
Kitchen areas shall have a minimum of 2 duplex receptacle outlets.
808.3.3 Laundry areas.
Laundry areas shall have a minimum of 1 duplex receptacle outlet located near the laundry equipment and installed on an independent circuit.
808.3.4 Ground fault circuit interruption.
Newly installed receptacles shall be provided with ground fault circuit interruption as required by the New York City Electrical Code.
808.3.5 Minimum lighting outlets.
At least 1 lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage, and detached garage with electric power, and to illuminate outdoor entrances and exits. Such lighting outlets, and associated controls, shall comply with any applicable requirements of the New York City Electrical Code.
808.3.6 Utility rooms and basements.
At least 1 lighting outlet shall be provided in utility rooms and basements where such spaces are used for storage or contain equipment requiring service.
808.4 Space for equipment.
In Group R-2 and R-3 occupancies, working space and dedicated space for electrical equipment including, but not limited to, panelboards, control panels and equipment disconnecting means in which there are exposed live parts when covers are opened or removed for troubleshooting, maintenance or similar activities, shall be provided in accordance with Article 110 of the New York City Electrical Code.
808.5 Smoke and carbon monoxide alarms in dwelling or sleeping units.
Installation of smoke and carbon monoxide alarms in dwelling and sleeping units pursuant to Section 804.4.3.1 of this code shall comply with the applicable provisions of NFPA 72 as modified by Appendix Q of the New York City Building Code and New York City Electrical Code.
Section EBC 809. Mechanical
809.1 General.
Mechanical elements and systems within the work area undergoing alteration Level 1 or within rooms or spaces where work on a stand-alone system as described in section 601.2.3.3 occurs shall comply with this section and Section 309.
809.1.1 Compliance of an entire mechanical system as new construction.
An entire mechanical system shall be required to comply with the New York City Mechanical Code for new construction when either:
1. The work area exceeds 50 percent of the area served by that system; or
2. 50 percent of the capacity of terminal distribution elements connected to that system is altered or replaced.
Exception: Mechanical system components that serve only an occupied space under separate tenancy that is entirely outside the work area.
809.2 Applicability of New York City Mechanical Code.
Alteration of mechanical systems including new components, equipment and appliances shall comply with the New York City Mechanical Code and Sections 309 and 809.2.1 through 809.15 of this code.
809.2.1 Work on mechanical systems not addressed in Chapter 1 .
Work on mechanical systems and elements not addressed in Chapter 1 of this code shall be governed by Chapter 1 of the New York City Mechanical Code .
809.2.2 Work on mechanical systems not addressed in Chapter 3.
Work on mechanical systems and elements not addressed in Chapter 3 of this code shall be governed by Chapter 3 of the New York City Mechanical Code.
Exceptions: The following shall apply to any work on mechanical systems and elements:
1. Equipment, appliances and supports that are exposed to wind shall be designed to resist wind pressure determined in accordance with Section 307.2.
2. The determination as to whether seismic supports apply to an alteration shall be made in accordance with Section 307.2.
3. The guard provisions and access to roofs and elevated equipment shall comply with Section 309.2.2.
809.3 Ventilation.
Ventilation shall comply with Chapter 4 of the New York City Mechanical Code.
Exception: Connection to existing outdoor air intake openings that are to remain unmodified in size and that are not considered in compliance with Section 401.4 of the New York City Mechanical Code shall be permitted to remain provided that they continue to function as required for the existing approved use and comply with the separation requirements between intake and exhaust openings.
809.4 Exhaust systems.
Exhaust systems shall comply with Chapter 5 of the New York City Mechanical Code and this section.
Exceptions:
1. Connection to existing exhaust openings that are to remain unmodified in size and that are not considered in compliance with Section 501.3 of the New York City Mechanical Code shall be permitted to remain provided that they continue to function as required for the existing approved use. Such openings shall comply with the separation requirements between intake and exhaust openings.
2. Replacement of existing fans of the same capacity and motor horsepower.
3. In kind replacement of fans or manual controls as part of an existing manual post fire smoke exhaust system in prior code buildings.
4. Modification of toilet exhaust branch ductwork and risers where the fan systems serving this duct distribution remain as existing.
5. Connection to existing commercial kitchen exhaust ductwork that is to be reused provided that the duct system has been in continuous service and not dormant or abandoned for more than 1 year. The existing ductwork system shall be tested in accordance with Section 506.3.2.5 of the New York City Mechanical Code.
809.5 Duct systems.
Duct systems shall comply with Chapter 6 of the New York City Mechanical Code and this section.
Exception: Replacement of existing fans of the same capacity and motor horsepower.
809.5.1 Ducts and air transfer openings.
All new and existing duct penetrations and air transfer openings within the work area shall comply with Chapter 6 of the New York City Mechanical Code. The work area boundary shall not be altered so as to exclude these penetrations and openings. All new and existing duct penetrations and air transfer openings that are part of the same duct or fan system and within the same room or space as a duct system altered as part of work on a stand-alone system shall comply with Chapter 6 of the New York City Mechanical Code.
809.5.1.1 Shaft and wall penetrations.
Connections of new or altered ducts to a duct system which penetrates an existing shaft located on the same floor shall require such nearby shaft penetrations to comply with Chapter 6 of the New York City Mechanical Code when any of the following occurs:
1. The penetrations in shafts and walls are located within or enclosing the work area, within or enclosing a space adjacent to the work area, or within or enclosing the room or space in which work on a stand-alone system alters or adds ducts.
2. The shaft and wall penetrations are located within 10 feet (3.05 m) of the work area where the intervening space is a common or public use area. Such distance shall be measured from the inside face of the wall or ceiling comprising the work area boundary.
3. The shaft and wall penetrations are located within 10 feet (3.05 m) of the room or space in which work on a stand-alone system alters or adds ducts and where the intervening space is a common or public use area. Such distance shall be measured from the furthest edge of the system component being altered or installed.
4. The shaft riser design airflow capacity delivered to the floor is increased by more than 10 percent.
5. The work area exceeds 50 percent of the floor area. Compliance shall be required for all penetrations located on the floor where the work area is located, including penetrations located within common or public use areas, except that compliance shall not be required for penetrations in spaces under separate tenancy.
6. The room or space in which work on a stand-alone system alters or adds duct exceeds 50 percent of the floor area. Compliance shall be required for all penetrations located on that floor, including penetrations located within common or public use areas, except that compliance shall not be required for penetrations in spaces under separate tenancy.
809.6 Fire dampers.
New and existing fire dampers in the work area, or in the room or space in which work on a stand-alone system which includes duct alterations occurs, shall be operationally tested in accordance with the procedures outlined in NFPA 80.
809.7 Smoke dampers.
New and existing smoke dampers in the work area, or in the room or space in which work on a stand-alone system which includes duct alterations occurs, shall be operationally tested in accordance with the procedures outlined in NFPA 105.
809.8 Combustion, ventilation, and dilution air.
Combustion, ventilation, and dilution air shall comply with Chapter 7 of the New York City Mechanical Code and this section.
Exception: Existing combustion, ventilation and dilution air intakes less than 30 inches (762 mm) above grade may be reused provided they comply with all of the following:
1. An areaway shall be provided, or an existing areaway shall be extended a minimum of 30 inches (762 mm) above adjacent grade where grade is measured from the top of the areaway.
2. A grating with equivalent free area equal to the boiler room wall intake opening shall be provided at the top of the areaway or a guard complying with Section 1015 of the New York City Building Code shall be provided around the perimeter of the areaway.
3. The bottom of the boiler room wall intake opening shall be a minimum of 30 inches (762 mm) above the bottom of the areaway, or mechanical ventilation in compliance with Section 706 of the New York City Mechanical Code shall be provided.
4. Carbon monoxide alarms and detectors shall be installed within the mechanical or boiler room to shut down the appliances upon carbon monoxide detection in accordance with Section 915 of the New York City Building Code.
5. Manual restart of the appliance shall be required after shutdown by carbon monoxide detection.
809.9 Chimneys and vents.
Chimney and vent systems shall comply with Chapter 8 of the New York City Mechanical Code and this section.
Exceptions:
1. Existing connectors that are below the boiler outlet or below the boiler floor to connect to the vertical chimney shall be permitted to be replaced in kind notwithstanding the pitch requirements of Section 803.10.5 of the New York City Mechanical Code provided the existing connector is replaced to comply with the remaining requirements of Section 803 of the New York City Mechanical Code and the connector is tested in accordance with Section 810 of the New York City Mechanical Code .
2. Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent that is to remain in service or where an appliance is connected to an existing chimney or vent during the process of a new appliance installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4 of the New York City Mechanical Code.
809.10 Specific appliances.
Specific appliances shall comply with Chapter 9 of the New York City Mechanical Code and this section.
Exceptions:
1. Vibration isolators for replacement cooling towers may be omitted in accordance with Section 309.2.3.
2. Combustible fill shall be permitted in replacement cooling towers in accordance with Section 309.2.4.
809.11 Boilers, water heaters and pressure vessels.
Boilers, water heaters and pressure vessels shall comply with Chapter 10 of the New York City Mechanical Code, 12 NYCRR Parts 4 and 14 as amended, and this section.
Exceptions:
1. The required clearances around equipment shall be permitted to be modified or reduced for in-kind replacement of boilers or appliances, in an existing boiler room, that do not comply with the required clearances, provided that plans shall demonstrate that the clearances are technically infeasible and that, at a minimum, the manufacturer’s required clearances shall be provided.
2. In-kind replacement of boilers shall not require the installation of a floor drain where a floor drain did not already exist and where there is a means of liquid disposal.
809.11.1 Chimney test.
Where new or altered equipment or appliances are connected to an existing chimney, the chimney shall be tested in accordance with Chapter 8 of the New York City Mechanical Code, Chapter 5 of the New York City Fuel Gas Code or Chapter 21 of the New York City Building Code, as applicable.
809.11.2 Fuel burning appliances in dwelling units.
When fuel burning appliances providing heat or hot water are replaced or installed within a dwelling unit in buildings of Occupancy Group R-2, interlocked carbon monoxide detection with a manual reset shall be installed in accordance with the New York City Building Code.
809.12 Refrigeration.
Refrigeration shall comply with Chapter 11 of the New York City Mechanical Code.
809.13 Hydronic piping.
Hydronic piping shall comply with Chapter 12 of the New York City Mechanical Code and this section.
809.13.1 Existing high-pressure steam and high temperature hot water piping systems.
Existing high-pressure steam and high temperature hot water piping systems shall be maintained, inspected, repaired, relocated and altered in compliance with Section 1211.3 of the New York City Mechanical Code.
809.14 Fuel oil piping and storage.
Fuel oil piping and storage shall comply with Chapter 13 of the New York City Mechanical Code and this code.
Exceptions:
1. Minor repairs, including but not limited to the replacement of a gasket, valve, pump or pump set, repair of a valve packing gland or tightening of flange bolts shall not require hydrostatic testing.
2. In-kind replacements of the same capacity of existing boilers and/or generators with no fuel oil system alteration or modification shall not require the entire existing fuel oil system to comply with Chapter 13 of the New York City Mechanical Code. The existing fuel oil system can continue to be used if it is in compliance with applicable codes and laws in effect when the system was installed.
3. Manual fuel oil fill operations for generators in prior code buildings shall comply with the following requirements when lawfully constructed prior to December 6, 1968, provided that all of the following conditions are satisfied:
3.1. The emergency generator and diesel fuel storage tanks must be authorized for use by a valid Fire Department fuel oil permit.
3.2. The combined total quantity of diesel fuel stored in the emergency generator storage tank(s) and any diesel fuel stored in reserve portable drums or containers shall not exceed 330 gallons (1249.2 L) on any given story.
3.3. The maximum diesel fuel reserve storage in portable drums or containers shall not exceed 60 gallons (227.1 L) any given story and shall be stored in spaces conforming to Section 1305.13.3, Items 1 through 5, and 7 of the New York City Mechanical Code. Any empty drums or containers shall be removed immediately and disposed of in a legal manner.
3.4. Diesel fuel shall be transferred in sealed portable drums or containers satisfying Sections 5003.10.2 and 5003.10.3 of the New York City Fire Code. The transfer of diesel fuel and the manual filling of the generator storage tanks shall be conducted by, or supervised by, a person holding a FDNY Certificate of Fitness C-98 for storage and use of combustible liquids. The transfer of diesel fuel from lower to upper stories or roof shall only be via the building freight elevator utilizing hand trucks. Transfer via any passenger elevator shall be prohibited.
3.5. The transfer of diesel fuel from the sealed portable container to the emergency generator fuel storage tank shall be performed using a hand crank pump satisfying the provisions of Section 5705.2.5 of the New York City Fire Code.
3.6. The DOB Boiler Division shall, upon satisfactory inspection, issue to the owner DOB form 16A “Certificate of Approval for Oil Burning Installation” indicating that the application involves the manual transfer and filling of the emergency generator diesel fuel storage tank(s) from portable drums or containers and that an FDNY Certificate of Fitness is required when such manual transfer is performed. A copy of the completed form shall be transmitted by the DOB Boiler Division to the Fire Department district office of the Bureau of Fire Prevention.
4. In-kind replacements of fuel oil storage tanks of the same capacity and not exceeding 1375 gallons (5205 L) in rooms without ventilation shall be permitted without requiring such replacement to comply with the ventilation requirements of Chapter 13 of the New York City Mechanical Code.
5. Existing oversized fuel oil headers exceeding the limits of Section 1305.9 of the New York City Mechanical Code shall be permitted to remain provided all of the following conditions are satisfied:
5.1 The existing fuel oil header is in compliance with prior applicable codes and laws.
5.2 The original header installation contains future valved, capped outlets for the connection of an additional generator.
5.3 The new work shall be connected to an existing valve.
5.4 The existing oversized fuel oil header is not being modified or altered.
5.5 The Fire Department shall be notified, in writing, of fuel oil header capacities exceeding the limits of Section 1305.9 of the New York City Mechanical Code.
6. In prior code buildings, where a dedicated, fire-rated room enclosure is technically infeasible, the replacement of existing indoor concrete encased fuel oil tanks with protected fuel oil tanks of the same capacity listed in accordance with UL 2085 shall be permitted.
809.14.1 Existing fuel oil piping system to comply with current code.
An existing fuel oil piping system shall be made to comply with the New York City Mechanical Code if any of the following apply:
1. The addition of a generator is not provided for by future valved, capped outlets on a header.
2. The addition or replacement of fuel oil piping exceeds 50% of the existing system piping lengths.
3. The addition of fuel oil pumping exceeds 50% of existing pumping capacity.
809.14.2 Outdoor fuel oil piping in existing buildings.
Outdoor fuel oil piping supplying existing buildings, including both horizontal and vertical piping, utilizing pumps to transfer fuel oil to appliances at levels above the lowest floor or to storage tanks at levels above the lowest floor in buildings shall comply with the following:
1. Vertical piping shall be located a minimum of 10 feet (3048 mm) from lot lines or a 2-hour fire-rated-enclosure shall be provided.
2. Vertical piping shall be located a minimum of 3 feet (914 mm) from building openings and combustible construction.
3. Vertical outdoor fuel oil piping shall be enclosed in a fully welded outer containment of at least No. 10 standard Gage steel sized in accordance with Section 1305.9.3.2 of the New York City Mechanical Code.
4. Horizontal outdoor fuel oil piping shall comply with Section 1305.9.3 of the New York City Mechanical Code.
5. In addition to the requirement of Section 1305.9.4 of the New York City Mechanical Code, a drain pipe shall also be provided from the lowest point in the vertical outdoor containment enclosure to a minimum 55-gallon (208 L) container with a leak detection alarm, arranged so as to sound an alarm and stop the transfer pump. The container may be located immediately inside the building.
6. Materials and supports directly exposed to the weather shall be stainless steel or other corrosion resistive material.
7. Details shall be provided for piping supports and connections to building structure.
8. Penetrations of building walls shall be encased in a protective pipe sleeve. The annular space between the piping and the sleeve shall be sealed with an approved noncombustible material in accordance with the New York City Building Code.
9. Piping shall be grounded in accordance with Section 250.104(B) of the New York City Electrical Code.
10. Piping shall be protected from vehicle impact and physical damage.
11. Flexible fuel oil piping systems shall not be utilized unless such systems are provided with continuous leak detection and are listed and labeled in accordance with UL 1369.
12. Piping shall not encroach into the minimum width or height of means of egress.
13. Roof access shall comply with Section 306.5 of the New York City Mechanical Code.
14. Piping shall be identified by a permanent label or tag at intervals not more than 40 feet (12 192 mm) in length and at all changes of direction. The label or tag shall be located outside of the enclosure.
15. Fuel oil piping on building roofs shall comply with the requirements of the New York City Mechanical Code.
809.14.3 Ventilation of fuel oil storage tank rooms.
Replacement of tanks in prior code buildings may utilize an existing gravity ventilation system complying with the following:
1. Independent supply and exhaust openings or ducts discharging to the outside shall be provided; and
2. The total net free area of supply and exhaust openings shall be equal to at least 1 percent of the floor area of the room equally divided between the supply and exhaust.
809.15 Solar systems.
Solar systems shall comply with Chapter 14 of the New York City Mechanical Code.
Section EBC 810. Plumbing
810.1 General.
Plumbing systems including elements and system components, piping and fixtures within the work area in buildings undergoing alteration Level 1 or within rooms or spaces where work on stand-alone systems as described in Section 601.2.3.3 occurs shall comply with the New York City Plumbing Code, Section 310 of this code and this section, as applicable.
810.2 Insulation of concealed piping.
To the extent required by the New York City Energy Conservation Code, where concealed existing piping is exposed during a Level 1 alteration, such piping shall be insulated as required by Section 302.9.4 of this code.
Section EBC 811. Fuel Gas Systems
811.1 General.
Alterations made to fuel gas systems including piping, appliances and components shall be in compliance with Section 311 and this section, as applicable.
811.2 Fuel burning appliances in dwelling units.
Installation of fuel burning appliances in dwelling units shall require the installation of carbon monoxide detection in accordance with Section 915.1 of the New York City Building Code.
Section EBC 812. Elevators and Conveying Systems
812.1 General.
Alterations made to existing elevators and conveying systems shall comply with Chapter 30 and ASME A17.1 as modified by Appendix K of the New York City Building Code, as applicable, and this section. Work listed in Table 812.1 shall be considered a Level 1 Alteration.
Table 812.1 – Level 1 Alteration Work a
A17.1 Section Name of A17.1 Section A17.1 Sub-section Name of A17.1 Sub-section 8.6.3 Replacements 8.6.3.10 Replacement of Hydraulic Jack, Plunger, Cylinder, Tanks, and Anticreep Leveling Device 8.6.3 Replacements 8.6.3.11 Replacement of Valves and Piping 8.7.2 Alterations to Electric Elevators 8.7.2.1 Hoistway Enclosures 8.7.2 Alterations to Electric Elevators 8.7.2.7 Machinery Spaces, Machine Rooms, Control Spaces, and Control Rooms 8.7.2 Alterations to Electric Elevators 8.7.2.8 Electrical Equipment, Wiring, Pipes, and Ducts in Hoistways and Machine Rooms 8.7.2 Alterations to Electric Elevators 8.7.2.9 Machinery and Sheave Beams, Supports, and Foundations 8.7.2 Alterations to Electric Elevators 8.7.2.10 Entrances and Hoistway Openings 8.7.2 Alterations to Electric Elevators 8.7.2.11 Hoistway Door Locking Devices, Access Switches, and Parking Devices (Including replacing door operators) 8.7.2 Alterations to Electric Elevators 8.7.2.14 New Car Enclosures (Including replacing cab panels when deadweight of the car is increased or decreased by more than 5%. See ASME Section 8.7.2.15.2) 8.7.2 Alterations to Electric Elevators 8.7.2.15 Car Frame and Platforms 8.7.2 Alterations to Electric Elevators 8.7.2.16 Capacity, Loading, and Classification 8.7.2 Alterations to Electric Elevators 8.7.2.17 Change in Rise or Rated Speed 8.7.2 Alterations to Electric Elevators 8.7.2.18 Car and Counterweight Safeties 8.7.2 Alterations to Electric Elevators 8.7.2.19 Speed Governors and Governor Ropes 8.7.2 Alterations to Electric Elevators 8.7.2.20 Ascending Car Overspeed and Unintended Car Movement Protection 8.7.2 Alterations to Electric Elevators 8.7.2.22 Counterweights 8.7.2 Alterations to Electric Elevators 8.7.2.25 Driving Machines and Sheaves (Except regrooving of sheaves, which can be considered as an LAA. See Table 510.2) 8.7.2 Alterations to Electric Elevators 8.7.2.26 Terminal Stopping Devices 8.7.2 Alterations to Electric Elevators 8.7.2.27 Operating Devices and Control Equipment (Including adding Phase I or Phase II recall, replacing car operating panels or hall buttons) 8.7.2 Alterations to Electric Elevators 8.7.2.28 Emergency Operations and Signaling Devices 8.7.3 Alterations to Hydraulic Elevators 8.7.3.7 Machine Rooms, Machinery Spaces, Control Spaces, and Control Rooms 8.7.3 Alterations to Hydraulic Elevators 8.7.3.8 Electrical Wiring, Pipes, and Ducts in Hoistways and Machine Rooms 8.7.3 Alterations to Hydraulic Elevators 8.7.3.9 Machinery and Sheave Beams, Supports, and Foundations 8.7.3 Alterations to Hydraulic Elevators 8.7.3.10 Hoistway Entrances and Openings 8.7.3 Alterations to Hydraulic Elevators 8.7.3.11 Hoistway Door Locking Devices (Including replacing door operators) 8.7.3 Alterations to Hydraulic Elevators 8.7.3.14 Car Frames and Platforms 8.7.3 Alterations to Hydraulic Elevators 8.7.3.15 Safeties 8.7.3 Alterations to Hydraulic Elevators 8.7.3.16 Governors and Governor Ropes 8.7.3 Alterations to Hydraulic Elevators 8.7.3.17 Change in Type of Service 8.7.3 Alterations to Hydraulic Elevators 8.7.3.18 Change in Class of Loading 8.7.3 Alterations to Hydraulic Elevators 8.7.3.19 Carrying of Passengers on Freight Elevators 8.7.3 Alterations to Hydraulic Elevators 8.7.3.20 Increase in Rated Load 8.7.3 Alterations to Hydraulic Elevators 8.7.3.21 Increase in Deadweight of Car (More than 5%) 8.7.3 Alterations to Hydraulic Elevators 8.7.3.22 Change in Rise or Rated Speed 8.7.3 Alterations to Hydraulic Elevators 8.7.3.23 Hydraulic Equipment 8.7.3 Alterations to Hydraulic Elevators 8.7.3.24 Valves, Pressure Piping, and Fittings 8.7.3 Alterations to Hydraulic Elevators 8.7.3.26 Counterweights 8.7.3 Alterations to Hydraulic Elevators 8.7.3.29 Tanks 8.7.3 Alterations to Hydraulic Elevators 8.7.3.30 Terminal Stopping Devices 8.7.3 Alterations to Hydraulic Elevators 8.7.3.31 Operating Devices and Control Equipment (Including adding Phase I or Phase II Recall, replacing car operating panels or hall buttons) 8.7.4 Alterations to Elevators with Other Types of Driving Machines 8.7.4 Alterations to Elevators with Other Types of Driving Machines 8.7.5 Alterations to Special Application Elevators 8.7.5 Alterations to Special Application Elevators 8.7.6 Alterations to Escalators and Moving Walks 8.7.6 Alterations to Escalators and Moving Walks 8.7.7 Alterations to Dumbwaiters and Material Lifts 8.7.7 Alterations to Dumbwaiters and Material Lifts 8.11.1.4 Installations Placed Out of Service 8.11.1.4 Installations Placed Out of Service
a. All references to A17.1 refer to ASME A17.1, as amended by Appendix K of the New York City Building Code .
Section EBC 813. Energy Conservation
813.1 Minimum requirements.
Level 1 alterations made to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the New York City Energy Conservation Code. Level 1 alterations shall conform to the energy requirements of Chapters R5 or C5, Existing Buildings, of the New York City Energy Conservation Code, as applicable.
Section EBC 814. Interior Environment
814.1 Ventilation requirements for enlarged bathrooms, toilet rooms, kitchens, and kitchenettes.
For bathrooms, toilet rooms, kitchens and kitchenettes undergoing enlargement, natural or mechanical ventilation sized in accordance with the New York City Mechanical Code shall be provided for the proposed floor area.
Exceptions:
1. Bathrooms and toilet rooms enlarged to meet the accessibility requirements of the New York City Building Code and that increase the room size by less than 50 percent of the existing floor area shall be permitted to maintain the existing means of ventilation without an increase provided no additional plumbing fixture is being proposed.
2. Kitchens and kitchenettes enlarged to meet the accessibility requirements of the New York City Building Code shall be permitted to maintain the existing means of ventilation without an increase in ventilation size provided no additional cooking appliance load is being proposed.
Section EBC 901. General
901.1 Scope.
Level 2 alterations as described in Section 603 shall comply with the requirements of this chapter and Chapter 3.
901.2 Compliance.
In addition to the provisions of this chapter, level 2 alteration work shall comply with all of the requirements of Chapter 8. The requirements of Sections 803, 804 and 805 shall apply to Level 2 alteration work within all work areas whether or not they include exits and corridors shared by more than 1 tenant and regardless of the occupant load, except as otherwise provided in Sections 903, 904, and 905.
901.2.1 Building safety performance and scoring method.
The design professional of record may elect to comply with Chapter 13 as an alternative to compliance with any of the requirements of Sections 903, 904 and 905 , including Sections 803, 804 and 805, in accordance with Section 301.1.4.
901.2.2 Work that increases floor surface area of an existing building by more than 110 percent.
Where a Level 2 alteration made to an existing building causes the existing floor surface area to be increased by more than 110 percent pursuant to Section 302.7, such building shall comply with the New York City Building Code as if hereafter erected.
Section EBC 902. Special Use and Occupancy
902.1 Uses and occupancies subject to Chapter 4 of the New York City Building Code.
Except as stated in Section 901.2.2 of this code, where an existing building occupied by a use or occupancy that is identified in Chapter 4 of the New York City Building Code is undergoing a level 2 alteration, such alteration work within the work area shall comply with the applicable requirements of Chapter 4 of the New York City Building Code and this section.
902.1.1 High-rise buildings.
Within work areas in buildings having occupied floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, alteration work shall comply with applicable provisions of Section 403 of the New York City Building Code and Sections 902.1.1.1 through 902.1.1.7 of this code.
902.1.1.1 Smoke detection systems control and ducts and air transfer openings.
All duct and air transfer openings within the work area and all fan systems serving the work area shall be newly installed or made to comply with Sections 606 and 607 of the New York City Mechanical Code.
Exception: The standby power requirements of Sections 606 and 607 of the New York City Mechanical Code shall not apply if both of the following conditions are met:
1. Standby power systems do not exist or existing standby power systems have insufficient capacity to serve this load.
2. New standby or emergency power is not required by Section 902.1.1.7 of this code.
902.1.1.2 Elevators.
Where there is an elevator or elevators for public use, at least 1 elevator serving the work area shall comply with this section. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3 as amended by Appendix K of the New York City Building Code . New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1/CSAB44.1 as amended by Appendix K of the New York City Building Code .
902.1.1.3 Additional exit stairway.
In existing buildings erected pursuant to the laws in effect prior to December 31, 2014, with a height exceeding 420 feet (128 m), where the work area exceeds 75 percent of the building area, the requirements for additional exit stairway of Section 403.5.2 of the New York City Building Code shall apply.
Exceptions:
1. In buildings where at least 50 percent of passenger elevators intended for general public use, including other elevators serving all floors, are used for occupant self-evacuation in compliance with Sections 3008.1 through 3008.11 of the New York City Building Code.
2. Existing fully sprinklered buildings shall be considered in compliance with Section 3008.3.2 of the New York City Building Code.
902.1.1.4 Structural integrity of exit enclosures and elevator hoistway enclosures.
Where the work area includes stairs or elevator hoistway enclosures, the design professional of record shall determine compliance of the enclosures with the structural integrity provisions of Section 403.2.3 of the New York City Building Code. Where the existing wall assembly of such enclosures do not meet the requirements of Section 403.2.3 of the New York City Building Code, the occupied side of such wall assembly within the work area shall comply with 1 of the methods provided in Section 403.2.3.2. In prior code buildings, existing concrete, masonry or masonry equivalent exit and elevator hoistway enclosures shall be deemed to comply with the structural integrity requirements of Section 403.2.3 of the New York City Building Code.
Exception: New, relocated or altered exit and elevator hoistway enclosures shall comply with all of the requirements of Section 403.2.3 of the New York City Building Code.
902.1.1.5 Smokeproof exit enclosures.
In prior code buildings, where the work area exceeds 75 percent of the building area, smokeproof exit enclosures shall be provided for all exit stairways throughout the building in accordance with Sections 403.5.4, 909.20 and 1023.11 of the New York City Building Code.
902.1.1.6 Elevator lobbies in prior code buildings.
Elevator lobbies required by Section 403.6.3 shall be constructed in accordance with Section 3006.1.1 or Section 3006.1.2 of the New York City Building Code, as applicable, on each floor being altered where the work area exceeds 50 percent of that floor.
Exceptions.
1. Elevator lobbies shall not be required for elevators that are located within other occupied tenant spaces that are not subject to alteration work.
2. Notwithstanding Exception 1, where the work area exceeds 75 percent of the building area, elevator lobbies shall be constructed in accordance with Section 3006.1.1 or Section 3006.1.2 of the New York City Building Code, as applicable, on all floors served by elevators.
902.1.1.6.1 Access to an exit stair not available.
Except as permitted by Section 902.1.1.6.2, where the elevator lobby cannot provide access to an exit, a red telephone shall be installed in the vestibule near the elevator doors in the elevator lobby to communicate with the main lobby fire command station or building manager’s office or to a central service station when the building is not attended. The phone shall provide two-way communication in accordance with Section 907.2.13.3 of the New York City Building Code and shall comply with the requirements of NFPA 72 as modified by Appendix Q of the New York City Building Code. A sign shall be posted near the phone. The sign shall read “In Case of Fire or Other Emergency, Use This Phone to Contact Lobby or Building Manager or Central Service Station”.
902.1.1.6.2 Locking of lobby doors.
Where locking devices are proposed on elevator lobby doors for security reasons to prevent access that leads to an exit, such locking devices shall be installed in accordance with Appendix K of the New York City Building Code .
902.1.1.7 Emergency and standby systems.
Where an existing building is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building area, the building shall comply with Chapter 27 of the New York City Building Code.
902.1.2 Boiler and furnace equipment rooms.
Boiler and furnace equipment rooms located within single occupancy or mixed occupancy existing buildings of Occupancy Groups I-1, I-2, I-4, R-1 or R-2 shall be enclosed by fire-resistance-rated construction in accordance with Section 509 of the New York City Building Code.
Section EBC 903. Building Elements and Materials
903.1 Existing shafts and vertical openings.
Existing shafts and vertical openings, including stairways, shall be enclosed and protected in accordance with the New York City Building Code from the highest level within the work area, including the level of exit discharge and all floors below the level of exit discharge. Where the proposed alteration results in a reduction in the existing fire-resistive rating, the registered design professional of record shall demonstrate compliance with Section 303.2 of this code.
903.1.1 Prior code buildings.
In prior code buildings, existing shafts and vertical openings, including stairways, shall be enclosed and protected in accordance with Section 803.2.1 from the highest level within the work area including the level of exit discharge and all floors below.
903.2 Fire separations in Group R-3.
Fire separation in Group R-3 occupancies shall be in accordance with Section 903.2.1.
903.2.1 Separation required in R-3 occupancy.
Where the work area in any attached one- or two-family dwellings results in the removal of wall or ceiling finishes exposing the existing fire separation that was constructed in accordance with Appendix M of the New York City Building Code or department issued memorandum on the same subject matter, special inspection shall be performed in accordance with Section 1705.17 of the New York City Building Code on the side of the dwelling unit wall that is part of the work area to determine whether the assembly is in compliance with Chapter 7 of the New York City Building Code. Any wall or portions thereof separating the dwelling units that are identified as not continuous from the foundation to the underside of the roof sheathing shall be constructed to provide a continuous fire separation using construction materials consistent with the existing wall or complying with the requirements for new structures. Such work shall be limited to the side of the dwelling unit wall that is part of the work area.
903.3 Interior finish.
The interior finish of walls and ceilings in exits and corridors in any work area or exit serving the work area, between the highest floor on which there is a work area and the floor of exit discharge, shall comply with the requirements of Section 803.4.
Exception: Interior finish of walls and ceilings in corridors and exits within tenant spaces that are entirely outside the work area.
903.4 Protection of window openings on lot line air shafts in Group R-2 buildings.
Where a prior code building is undergoing a Level 2 alteration and the building contains windows that open onto a lot line air shaft as defined in Chapter 2, and any part of such window is less than 3 feet (914 mm) from the lot line or less than 6 feet (1829 mm) from another window on the adjacent building, all such windows shall be protected in accordance with Section 803.8. For the purpose of this section, separation distance to adjacent buildings shall be measured in any direction to the nearest edges of window openings.
Exception. Windows located in occupied tenant spaces outside the work area.
903.4.1 Work areas exceeding 75 percent of the building area.
Where the work area exceeds 75 percent of building area, all windows opening on lot line air shafts shall be protected in accordance with Section 803.8 throughout the building.
903.5 Existing buildings in fire districts.
Alterations made to existing buildings shall comply with Sections 302.6 and 803.9.
Section EBC 904. Fire Protection
904.1 General.
Existing buildings undergoing a Level 2 alteration shall be provided with fire protection systems in accordance with this section, Section 304 and Section 804, as applicable.
904.1.1 Compliance within the work area.
See Sections 904.2 and 904.4.
904.1.2 Compliance throughout the building.
The entire building shall comply with Chapter 9 of the New York City Building Code as if hereafter erected where:
1. The Level 2 alteration work is covered by Section 901.2.2 of this code; or
2. The Level 2 alteration work area exceeds 75 percent of the building area.
904.2 Automatic sprinkler systems.
Except as stated in Sections 904.2.1 through 904.2.3, an automatic sprinkler system shall be provided in the work area in accordance with Section 804.2 regardless of the occupant load, the percentage of the work area per floor, and whether or not the work area includes exits or corridors serving more than 1 tenant. The design and installation of the system shall be in accordance with Chapter 9 of the New York City Building Code, except as permitted for prior code buildings in Section 804.2.8 of this code.
904.2.1 High-rise buildings.
Where a prior code high-rise building is undergoing a Level 2 alteration, an automatic sprinkler system shall be provided in work areas as required by Chapter 9 of the New York City Building Code. Prior code buildings with existing sprinkler systems may use the provisions of Section 804.2.8 of this code.
904.2.2 Rubbish and linen chutes.
Rubbish and linen chutes located in the work area shall be provided with an automatic sprinkler system where protection of the rubbish and linen chute would be required under the provisions of the New York City Building Code for new construction.
904.2.3 Upholstered furniture or mattresses.
Work areas shall be provided with an automatic sprinkler system in accordance with the New York City Building Code where any of the following conditions exist within the work area:
1. A Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceeds 2,500 square feet (232 m 2 ).
2. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m 2 ).
3. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m 2 ).
904.3 Reserved.
904.4 Fire alarm and detection systems.
Fire alarm and detection systems shall be provided throughout the work area in accordance with Section 907 of the New York City Building Code as required for new construction.
Section EBC 905. Means of Egress
905.1 General.
Except as stated in Section 901.2.2, the means of egress shall comply with the requirements of Sections 305 and 805 within the work area that includes exits and corridors regardless of the number of tenants served by such exits and corridors. The means of egress shall also comply with Sections 905.1.1 and 905.1.2.
905.1.1 Means-of-egress lighting.
All interior exit stairways and ramps from the highest work area floor to the exit discharge shall be provided with artificial lighting in accordance with the requirements of Chapter 10 of the New York City Building Code.
905.1.2 Exit signs.
Means of egress from the highest work area floor to the exit discharge shall be provided with exit signs in accordance with the requirements of Chapter 10 of the New York City Building Code.
905.2 Existing combustible stairs in prior code buildings.
Where a prior code building of Occupancy Group R-1 or R-2 is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building area, existing exit stairs constructed of combustible materials shall be replaced in their entirety with non-combustible construction, including stairs, landings, handrails and guards. The replacement stair shall meet the requirements of Chapter 10 of the New York City Building Code. Where the size of the existing shaft does not allow for full compliance with Chapter 10 of the New York City Building Code in regards to required dimensions, the replacement stair may comply with Section 805.12.1 of this code.
Exception: Prior code buildings that are fully sprinklered and comply with the fire protection requirements of Chapter 9 of the New York City Building Code.
Section EBC 906. Accessibility
906.1 General.
Within the work area, a building, facility or element that is altered shall comply with Chapter 11 of the New York City Building Code, this section and Sections 306 and 806 of this code.
Exception: Where the commissioner grants a waiver from certain requirements of Chapter 11 of the New York City Building Code pursuant to Section 306 of this code.
906.1.1 Applicability of Chapter 11 of the New York City Building Code to the entire building.
Where a building is undergoing a Level 2 alteration, the entire building shall comply with the provisions of Chapter 11 of the New York City Building Code as if hereafter erected.
Exception: In a building of Occupancy Group R-2, where the dwelling or sleeping units included in the work area exceed more than 50 percent of the dwelling or sleeping units in the building and are under a single ownership, all common use facilities serving those dwelling or sleeping units shall comply with the requirements of Chapter 11 of the New York City Building Code .
Section EBC 907. Structural
907.1 General.
Where existing buildings are undergoing Level 2 alterations including structural alterations, the provisions of Chapter 7 shall apply.
907.2. Structural condition assessment.
Level 2 alterations shall require an initial structural condition assessment pursuant to Section 704.3. Where the Level 2 alteration includes a structural alteration, a detailed structural condition assessment pursuant to Section 704.4 is also required.
Section EBC 908. Electrical
908.1 General.
All electrical equipment and wiring within work areas shall comply with all applicable requirements of the New York City Electrical Code, this section and Sections 308 and 808 of this code.
908.1.1 Compliance of the entire electrical system as new construction.
Where the building is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building area, the entire electrical system shall comply with the provisions of the New York City Electrical Code for new construction.
Section EBC 909. Mechanical
909.1 General.
Mechanical elements and systems within work areas in buildings undergoing a Level 2 alteration shall comply with Section 309, Section 809 and this section.
909.2 Applicability of New York City Mechanical Code.
Where an existing building is undergoing a Level 2 alteration, all existing mechanical systems within the work area, including components, equipment and appliances, shall comply with the New York City Mechanical Code, this section and Section 809.2 of this code.
909.2.1 Ventilation.
Ventilation systems serving work areas of a Level 2 alteration shall be newly installed or altered to comply with requirements of Chapter 4 of the New York City Mechanical Code for new construction.
909.2.2 Exhaust systems.
Exhaust systems serving work areas of a Level 2 alteration shall be newly installed or altered to comply with requirements of Chapter 5 of the New York City Mechanical Code for new construction.
909.2.3 Compliance of ventilation, exhaust, and duct systems as new construction.
Where the building is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building floor area, all ventilation, exhaust and duct systems shall be newly installed or altered to comply with the provisions of Chapters 4, 5 and 6 of the New York City Mechanical Code for new construction.
Section EBC 910. Plumbing
910.1 General.
Plumbing elements and systems within work areas in buildings undergoing a Level 2 alteration shall comply with Section 310, Section 810 and this section.
910.1.1 Compliance of the entire plumbing system as new construction.
Where the building is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building area, the entire plumbing system shall comply with the provisions of the New York City Plumbing Code for new construction.
Exception. Plumbing system components that are found to be in code-compliant condition upon inspection and certification by a licensed master plumber shall be permitted to remain.
Section EBC 911. Fuel Gas
911.1 General.
Fuel gas elements and systems within work areas in buildings undergoing a Level 2 alteration shall comply with Section 311, Section 811, and this section.
911.1.1 Compliance of entire fuel gas system as new construction.
Where the building is undergoing a Level 2 alteration and the work area exceeds 75 percent of the building floor area, the entire fuel gas system shall comply with the provisions of the New York City Fuel Gas Code for new construction.
Exception . Fuel gas system components that are found to be in code-compliant condition upon inspection and certification by a licensed master plumber shall be permitted to remain.
Section EBC 912. Energy Conservation
912.1 Minimum requirements.
Level 2 alterations to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the New York City Energy Conservation Code. Level 2 alterations shall conform to the energy requirements of Chapters R5 or C5 of the New York City Energy Conservation Code , as applicable.
Section EBC 1001. General
1001.1 Scope.
The provisions of this chapter shall apply where a change of occupancy occurs, as defined in Section 202, and as described in this chapter.
1001.2 Certificate of occupancy.
A change of occupancy of a building or space shall not be made without the approval of the department. A certificate of occupancy shall be issued for a change of occupancy when required by Section 28-118 of the Administrative Code.
1001.3 Change of occupancy.
As used in this chapter, the term “Change of Occupancy” shall include:
1. A change of occupancy classification. This includes a change from 1 Group to another Group (for example: B to E, A-2 to B, R-1 to R-2, or A-3 to A-1)
2. A change of use within the same Occupancy Group, which shall mean:
1.1. A change that requires compliance with different code requirements.
1.2. A change that triggers more restrictive fire protection requirements.
1.3. A change of how a space is being used within a facility.
1001.4 Compliance.
Where a building or portion thereof is subject to a change of occupancy as described in Section 1001.3, such building or portion thereof shall comply with Sections 1001.4.1 and 1001.4.2.
1001.4.1 Change of occupancy classification.
Where the occupancy classification of a building or portion thereof is changed, the provisions of Sections 1002 through 1012 shall apply to such change.
1001.4.2 A change of use within the same Occupancy Group.
Where the use of a building or space is changed to a different use within the same Occupancy Group that requires compliance with different code requirements, such building or space shall comply with the applicable provisions of Sections 1002 to 1012 and Chapters 8 or 9 as applicable. For the purposes of complying with Chapters 8 or 9, work area shall be considered that portion of the building subject to change.
1001.5 Existing buildings within the fire districts.
A change of occupancy of an existing building within the fire district shall not be made unless such change is permitted in the fire district for the building construction type. A change of occupancy to Group H-1 is prohibited within fire districts.
Section EBC 1002. Special Use and Occupancy
1002.1 Compliance with Chapter 4 of the New York City Building Code.
Where the character or use of an existing building or part of an existing building is changed to a special use or occupancy category subject to Chapter 4 of the New York City Building Code, such building, or part thereof, shall comply with all of the applicable requirements of Chapter 4 of the New York City Building Code.
1002.2 Incidental use areas.
Where the use of a space is changed to 1 of the incidental uses listed in Table 509 of the New York City Building Code, such change shall be subject to Section 509 of the New York City Building Code.
Section EBC 1003. Building Elements and Materials
1003.1 General.
Building elements and materials in portions of buildings undergoing a change of occupancy classification shall comply with this section.
1003.2 Heights and areas.
Hazard categories with regard to height and area shall be in accordance with Table 1003.2.
Table 1003.2 Heights and Areas Hazard Categories
RELATIVE HAZARD OCCUPANCY CLASSIFICATIONS 1 (Highest Hazard) H 2 A-1, A-2, A-3, A-4, I, R-1, R-2 3 E, F-1, S-1, M 4 (Lowest Hazard) B, F-2, S-2, A-5, R-3, U
1003.2.1 Height and area for change to higher hazard category.
When a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1003.2, heights and areas of buildings and structures shall comply with the requirements of Chapter 5 of the New York City Building Code for the new occupancy classification.
Exception: For high-rise buildings constructed pursuant to building codes in existence prior to the effective date of the 2014 New York City Construction Codes, and are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code, the fire-resistance rating of the existing building elements that were allowed to be reduced in accordance with Table 601 of the New York City Building Code may be maintained. However, any proposed change to the construction classification of the building or fire-resistance rating of the building elements shall be made to comply with Section 403.2.1 of the New York City Building Code.
1003.2.1.1 Fire wall alternative.
In groups other than Groups H, F-1, and S-1, fire barriers and horizontal assemblies constructed in accordance with Sections 707 and 711 of the New York City Building Code shall be permitted to be used in lieu of fire walls to subdivide the building into separate buildings for the purpose of complying with the area limitations required for the new occupancy where all of the following conditions are met:
1. The buildings are protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 of the New York City Building Code;
2. The maximum allowable area between fire barriers, horizontal assemblies, or any combination thereof shall not exceed the maximum allowable area determined in accordance with Chapter 5 of the New York City Building Code without an increase allowed for an automatic sprinkler system in accordance with Section 506 of the New York City Building Code; and
3. The fire-resistance rating of the fire barriers and horizontal assemblies shall be not less than that specified for fire walls in Table 706.4 of the New York City Building Code.
Exception: Where horizontal assemblies are used to limit the maximum allowable area, the required fire-resistance rating of the horizontal assemblies shall be permitted to be reduced by 1 hour provided the height and number of stories increases allowed for an automatic sprinkler system by Section 504 of the New York City Building Code are not used for the buildings.
1003.2.2 Fire barriers.
Where a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1003.2, fire barriers in separated mixed use buildings shall comply with the fire-resistance requirements of the New York City Building Code.
Exception: In prior code buildings subject to verification by the registered design professional of record, where the fire barriers are required to have a 1-hour fire-resistance rating, existing wood lath and plaster in good condition, existing one-half-inch-thick (12.7 mm) gypsum wallboard or other materials acceptable to the department shall be permitted.
1003.2.3 Height and area for change to equal or lesser hazard category.
Where a change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 1003.2, the height and area of the existing building shall be deemed acceptable.
1003.3 Exterior wall fire-resistance ratings.
Hazard categories with regard to fire-resistance ratings of exterior walls shall be in accordance with Table 1003.3.
Table 1003.3 Exposure of Exterior Walls Hazard Categories
RELATIVE HAZARD OCCUPANCY CLASSIFICATION 1 (Highest Hazard) H 2 F-1, M, S-1 3 A, B, E, I, R 4 (Lowest Hazard) F-2, S-2, U
1003.3.1 Exterior wall rating for change of occupancy classification to a higher hazard category.
Where a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1003.3, exterior walls shall have fire resistance and exterior opening protectives as required by the New York City Building Code.
Exception: A 2-hour fire-resistance rating shall be allowed where the building does not exceed 3 stories in height and is classified as 1 of the following Occupancy Groups: A-2 and A-3 with an occupant load of less than 300, B, F, M, or S.
1003.3.2 Exterior wall rating for change of occupancy classification to an equal or lesser hazard category.
When a change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 1003.3, existing exterior walls, including openings, shall be accepted.
1003.3.3 Opening protectives.
Openings in exterior walls shall be protected as required by the New York City Building Code. Where openings in the exterior walls are required to be protected because of their distance from the lot line, the sum of the area of such openings shall comply with the allowable area of Table 705.8 of the New York City Building Code.
Exceptions. The following exceptions shall apply to existing openings:
1. Existing openings that are not in compliance with the area limitations of Section 705.8 of the New York City Building Code can be maintained provided that they are protected in accordance with Sections 715.4 and 715.5 of the New York City Building Code.
2. Protected openings shall not be required in buildings of Group R-2 and R-3 occupancies that are located not less than 3 feet (914 mm) from the lot line. The allowable area of openings per story shall be in accordance with the fire separation distance as indicated in Table 705.8 of the New York City Building Code.
3. Exterior opening protectives are not required where an automatic sprinkler system has been installed throughout provided the area limitations of Section 705.8 of the New York City Building Code are not exceeded.
4. Exterior opening protectives are not required where the change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 1003.3 provided the area limitations of Section 705.8 of the New York City Building Code are not exceeded.
1003.4 Enclosure of vertical shafts.
Enclosure of vertical shafts shall be in accordance with Sections 1003.4.1 through 1003.4.4.
1003.4.1 Minimum requirements.
Vertical shafts shall be designed to meet the New York City Building Code requirements or the requirements of this section.
1003.4.2 Stairways.
When a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1005.2, interior stairways shall be enclosed as required by the New York City Building Code.
Exception: In prior code buildings, where the New York City Building Code allows for reduction in fire rating of stair enclosures below the existing fire rating of such stair enclosure, such reduction shall not be permitted unless the building or portion thereof subject to the change is protected with an automatic sprinkler system from the highest floor undergoing the change of occupancy to and including the level of exit discharge.
1003.4.3 Other vertical shafts.
Interior vertical shafts other than stairways, including but not limited to elevator hoistways and service and utility shafts, shall be enclosed as required by the New York City Building Code when there is a change of occupancy classification to a higher hazard category (lower number) as specified in Table 1005.2.
Exception. In prior code buildings, existing 1-hour interior shaft enclosures shall be accepted where a higher rating is required and the building or portion thereof subject to the change in occupancy classification is protected with an automatic sprinkler system from the highest floor undergoing the change to and including the level of exit discharge.
1003.4.4 Openings.
When there is a change of occupancy classification to a higher hazard category (lower number) as shown in Table 1005.2, all openings into existing vertical shaft enclosures shall be protected by fire assemblies having a fire protection rating corresponding to the vertical shaft rating, but not less than 1 hour, and shall be maintained self-closing or be automatic-closing by actuation of a smoke detector. All other openings, including duct and air transfer openings, shall be fire protected in an approved manner. Existing fusible link-type automatic door-closing devices shall be permitted in all shafts except stairways if the fusible link rating does not exceed 135°F (57°C).
1003.4.4.1 Window openings on lot line air shafts.
Where an existing building or portion thereof, classified in Occupancy Group R-1 or R-2, is undergoing a change in occupancy classification, all window openings on a lot line air shaft, as described in Section 803.8, shall be protected in accordance with Section 803.8.
1003.5 Interior finish.
Where work is being done in areas of the building undergoing the change of occupancy classification, the interior finish of walls, floors, and ceilings shall comply with the requirements of the New York City Building Code for the new occupancy classification.
Section EBC 1004. Fire Protection
1004.1 Change of occupancy classification or change of use within the same Occupancy Group.
Fire protection systems governed by Chapter 9 of the New York City Building Code shall be provided in accordance with Sections 1004.1.1 and 1004.1.2.
1004.1.1 Change in the main use or dominant occupancy of the building.
Where there is a change to the main use or dominant occupancy of the building, the entire building shall comply with the requirements of Chapter 9 of the New York City Building Code as if hereafter erected.
1004.1.2 Partial change of occupancy classification or a change in use that triggers more restrictive fire protection requirements in Chapter 9 of the New York City Building Code.
Where a portion of an existing building is changed to a new occupancy classification or to a use that requires compliance with a more restrictive fire protection requirement as per Chapter 9 of the New York City Building Code, such portion of the building shall comply with the requirements of Chapter 9 subject to the separation conditions as indicated in Sections 1004.1.2.1 and 1004.1.2.2.
1004.1.2.1 Change without separation.
Where the portion of the existing building subject to the change is not separated from the remainder of the building with fire barriers or horizontal assemblies having a fire-resistance rating as required in the New York City Building Code for the separate occupancy or use, the entire nonseparated area shall comply with all of the requirements of Chapter 9 applied throughout the nonseparated area for the most restrictive occupancy classification or use in the nonseparated area and with the requirements of this chapter.
1004.1.2.2 Change with separation.
Where the portion of the existing building subject to the change is separated from the remainder of the building with fire barriers or horizontal assemblies having a fire-resistance rating as required in the New York City Building Code for the separate occupancy, that portion shall comply with all of the requirements of Chapter 9 for the new occupancy classification or use and with the requirements of this chapter.
Section EBC 1005. Means of Egress
1005.1 General.
Means of egress in portions of buildings undergoing a change of occupancy classification shall comply with Sections 1005.2 through 1005.6.
1005.2 Hazard categories.
Hazard categories with regard to life safety and means of egress shall be in accordance with Table 1005.2.
Table 1005.2 Means of Egress Hazard Categories
RELATIVE HAZARD OCCUPANCY CLASSIFICATIONS 1 (Highest Hazard) H 2 I-2, I-3, I-4 3 A, B, E, I-1, M, R-1, R-2 4 F-1, R-3, S-1 5 (Lowest Hazard) F-2, S-2, U
1005.2.1 Means of egress for change to higher hazard category.
When a change of occupancy classification is made to a higher hazard category (lower number) as shown in Table 1005.2, the means of egress shall comply with the requirements of Chapter 10 of the New York City Building Code.
Exceptions: Prior code buildings shall be permitted to comply with the provisions of Section 305.5 and the following, as applicable:
1. Stairways shall be enclosed in compliance with the applicable provisions of Section 903.1.
2. Existing corridor doorways, transoms and other corridor openings shall comply with the requirements of Section 805.
3. Existing dead-end corridors shall comply with the requirements of Section 805.
4. For the purpose of complying with Section 1029 of the New York City Building Code, an existing operable window with clear opening area no less than 4 square feet (0.38 m 2 ) and minimum opening height and width of 22 inches (559 mm) and 20 inches (508 mm), respectively, shall be accepted as an emergency escape and rescue opening provided other requirements of Section 1029 of the New York City Building Code are complied with.
1005.2.2 Means of egress for change to equal or lower hazard category.
Where a change of occupancy classification is made to an equal or lesser hazard category (higher number) as shown in Table 1005.2, existing elements of the means of egress shall comply with the requirements of Section 905 for the new occupancy classification. Newly constructed or configured means of egress shall comply with the requirements of Chapter 10 of the New York City Building Code.
Exception: Prior code buildings shall be permitted to comply with Section 305.5 and buildings with existing scissors stairs may be changed to Group B or R occupancies without the requirement for an additional exit stair, where the building is equipped with an automatic sprinkler system in accordance with Chapter 9 of the New York City Building Code and where the height of the building does not exceed 75 feet (22 860 mm) from the lowest level of fire department vehicle access to highest occupied floor or 6 stories, whichever is less.
1005.3 Egress capacity.
Egress capacity shall be no less than as specified in Chapter 10 of the New York City Building Code for the new occupancy.
1005.4 Handrails.
Existing stairways shall comply with the handrail requirements of Section 805.9 from the area subject to the change of occupancy classification to the exit discharge level.
1005.5 Guards.
Existing guards shall comply with the requirements of Section 805.11 in the area subject to the change of occupancy classification including those along the egress path from the work area to the level of exit discharge.
1005.6 Additional requirements for prior code buildings.
Prior code buildings shall also comply with Sections 1005.6.1 and 1005.6.2.
1005.6.1 Replacement of combustible stairs.
In prior code buildings of Occupancy Groups R-1 and R-2, where the floor area subject to the change of occupancy is more than 50 percent of the building area, existing stairs constructed of combustible materials shall be replaced in their entirety with non-combustible construction, including stairs, landings, handrails, and guards.
Exception: Buildings that are fully sprinklered and comply with the fire protection requirements of Chapter 9 of the New York City Building Code.
1005.6.2 Means of egress from cellar level used in connection with small establishments classified as occupancy Groups B, M, or A-2 in prior code buildings.
Where a cellar space is undergoing a change of occupancy to be used in connection with a Group B, M, or A-2 establishment occupying the grade story above and such establishment does not exceed 2000 square feet (185.8 m 2 ) in area, the means of egress and protection of such cellar space may comply with Sections 1005.6.2.1 through 1005.6.2.3, as applicable.
Exception: The cellar level meets the requirements of the New York City Building Code for new construction.
1005.6.2.1 Cellar space is used by employees of the establishment.
Where the cellar space is to be used only by employees of the establishment above, all the following conditions shall be complied with:
1. The cellar space does not exceed 50 percent of the floor area of the establishment above and not to be occupied by more than 10 employees;
2. The entire cellar is protected by an automatic sprinkler system in accordance with Chapter 9 of the New York City Building Code; and
3. The means of egress from the cellar space shall consist of:
3.1. A door opening onto either a public corridor leading to the enclosed egress stairway that maintains enclosure to discharge at the street, or opening directly to an enclosed stair or exit passageway leading to the street; and
3.2. A door to an enclosed stair not less than 30 inches (762 mm) wide leading to the establishment above.
1005.6.2.2 Cellar level is used by patrons or customers of the establishment.
Where the cellar is to be used by patrons or customers of the establishment above, all the following conditions shall be complied with:
1. The cellar level and the floor above are protected by an automatic sprinkler system and the cellar space has an occupant load of not more than 50 persons;
2. The means of egress from the cellar shall consist of:
2.1. An exit door opening onto a public corridor leading to the enclosed egress stairway that maintains enclosure to discharge at the street or an opening directly to an enclosed stair or exit passageway leading to the street; and
2.2. A door to an enclosed connecting stair not less than 44 inches (1118 mm) wide leading to the establishment above.
1005.6.2.3 Cellar level is occupied by customers or patrons in excess of the limits of Sections 1005.6.2.1 and 1005.6.2.2.
Where the cellar level is occupied by more than 50 people, 2 enclosed means of egress leading directly to the street, in compliance with Chapter 10 of the New York City Building Code, shall be provided. In addition, such level shall be protected with automatic sprinkler system in accordance with Chapter 9 of the New York City Building Code.
Section EBC 1006. Accessibility
1006.1 General.
Accessibility in buildings or portions of buildings undergoing a change of occupancy, as described in Section 1001.3, shall comply with Chapter 11 of the New York City Building Code, in accordance with Section 1006.1.1.
1006.1.1 Requirements based on change of occupancy classification or a change of use.
Where a building or portion thereof is undergoing a change of occupancy classification or a change of use as described in Section 1001.3, requirements of New York City Building Code Chapter 11 shall apply as follows:
1. To the entire building, as if the building were hereafter erected, where the change is made in the main use or dominant occupancy of such building.
2. Throughout a space, including the immediate entrance(s) thereto, where an alteration is made that is considered either (i) a change in occupancy classification of such space in accordance with Chapter 3 of the New York City Building Code, or (ii) a change in how a space is being used, or (iii) a change in the zoning use group of such space in accordance with the New York City Zoning Resolution.
2.1. Where the immediate entrance(s) to such space provides direct access to the sidewalk, such immediate entrance(s) shall be provided with an accessible route to the sidewalk. Where the immediate entrance(s) to such space are only through an adjacent space, such as a building lobby, such space shall be provided with an accessible route, through the adjacent space, to the sidewalk.
2.2. Where elevator service is provided in the building and the rooftop is undergoing a change of use or occupancy that is intended for use by general public or building occupants served by such elevator service, an accessible route shall be provided to access such rooftop.
Section EBC 1007. Structural
1007.1 Compliance with Chapter 7 .
Buildings or portions thereof subject to a change of occupancy as described in Section 1001.3 shall be subject to Chapter 7.
1007.2. Structural condition assessment.
Buildings or portions thereof subject to a change of occupancy shall require an initial structural condition assessment per Section 704.2.2. Where the change of occupancy includes a structural alteration, a detailed structural condition assessment per Section 704.3 is also required.
Section EBC 1008. Electrical
1008.1 Special occupancies.
Where the occupancy or use of an existing building or part of an existing building is changed to 1 of the following special occupancies as described in the New York City Electrical Code, the electrical wiring and equipment of the building or portion thereof that contains the proposed occupancy shall comply with the applicable requirements of the New York City Electrical Code whether or not a change of Occupancy Group is involved:
1. Hazardous locations.
2. Commercial garages, repair, and storage.
3. Aircraft hangars.
4. Gasoline dispensing and service stations.
5. Bulk storage plants.
6. Spray application, dipping, and coating processes.
7. Health care facilities.
8. Places of assembly.
9. Theaters, audience areas of motion picture and television studios, and similar locations.
10. Motion picture and television studios and similar locations.
11. Motion picture projectors.
12. Agricultural buildings.
13. Marinas.
1008.2 Unsafe conditions.
Where the occupancy of an existing building or part of an existing building is changed, all unsafe conditions shall be corrected without requiring that all parts of the electrical system comply with the New York City Electrical Code.
1008.3 Service upgrade.
Where the occupancy of an existing building or part of an existing building is changed, the electrical service shall comply with the requirements of the New York City Electrical Code for the new occupancy.
1008.4 Quantity and location of required electrical outlets.
Where the occupancy of an existing building or part of an existing building is changed, the quantity and location of required electrical outlets shall comply with the New York City Electrical Code for the new occupancy.
Section EBC 1009. Mechanical
1009.1 Mechanical requirements.
Where the existing building or part of an existing building is subject to a change of occupancy, mechanical systems serving the new occupancy or use shall comply with Sections 1009.1.1 and 1009.1.2.
1009.1.1 Change in occupancy classification.
Where there is a change in the occupancy classification of the building or portion thereof, the building area subject to change shall comply with all the requirements of the New York City Mechanical Code for the new occupancy classification.
1009.1.2 A change of use within the same Occupancy Group.
Where a building or space is changed to a use with higher mechanical ventilation demand, the mechanical system serving such building or space shall comply with the requirements of Section 809 or 909 as applicable.
Section EBC 1010. Plumbing
1010.1 Plumbing requirements.
Where the existing building or part of an existing building is subject to a change of occupancy, the plumbing system serving the new occupancy or use shall comply with Sections 1010.1.1 through 1010.1.8.
1010.1.1 Change in occupancy classification.
Where there is a change in the occupancy classification of the building or portion thereof, the area of the building subject to change shall comply with all the requirements of the New York City Plumbing Code for the new occupancy classification.
1010.1.2 A change of use within the same Occupancy Group.
Where a building or space is changed to a use with different plumbing requirements, the plumbing system serving such building or space shall comply with the requirements of Sections 1010.1.3 through 1010.1.8 as applicable. Alteration work associated with such change shall comply with Sections 810 or 910 as applicable to the level of alteration made to the building or space.
1010.1.3 Increased demand.
Where the occupancy or use of an existing building or part of an existing building is changed, such that the new occupancy or use is subject to increased or different plumbing fixture requirements or to increased water supply requirements in accordance with the New York City Plumbing Code, the new occupancy or use shall comply with the New York City Plumbing Code provisions.
Exception: Where the change affects less than 10 percent of the building floor area and does not require more than 1 additional plumbing fixture.
1010.1.4 Food-handling occupancies.
If the new occupancy or use is a food-handling establishment, all existing sanitary waste lines located above the food or drink preparation or storage areas shall be protected to prevent leaking pipes or condensation on pipes from contaminating food or drink through the installation of drip pans. New drainage lines shall not be installed above such areas and shall be protected in accordance with the New York City Plumbing Code.
1010.1.5 Interceptor required.
If the new occupancy or use will produce grease-laden wastes, interceptors shall be provided as required in the New York City Plumbing Code. Grease-laden waste shall not discharge to a public sewer system without the approval of the New York City department of environmental protection.
1010.1.6 Oil separator.
If the new occupancy or use will produce oil-laden wastes, an oil separator shall be provided as required in the New York City Plumbing Code . Oil-laden waste shall not discharge to a public sewer system without the approval of the New York City department of environmental protection.
1010.1.7 Chemical wastes.
If the new occupancy or use will produce chemical wastes, the following shall apply:
1. If the existing piping is not compatible with the chemical waste, the waste shall be neutralized prior to entering the drainage system, or the piping shall be changed to a compatible material.
2. Chemical waste shall not discharge to a public sewer system without the approval of the New York city department of environmental protection.
1010.1.8 Group I-2.
If the Occupancy Group is changed to Group I-2, the plumbing system shall comply with the applicable requirements of the New York City Plumbing Code for new construction.
Section EBC 1011. Energy Conservation
1011.1 Minimum requirements.
Where an existing building or portion thereof is undergoing a change of occupancy, such change shall be subject to Chapter C5 or R5 of the New York City Energy Conservation Code, as applicable.
Section EBC 1012. Other Requirements
1012.1 Light and ventilation.
Light and ventilation shall comply with the requirements of Chapter 12 of the New York City Building Code for the new occupancy or use.
1012.1.1 Group R-1, R-2, and I-1 occupancies.
Where the occupancy classification of an existing building or part thereof is changed to Occupancy Group R-1, R-2, or I-1, such change shall also be subject to the requirements of Appendix D and the New York City Housing Maintenance Code.
1012.1.2 Group R-3 occupancy.
Where the occupancy classification of a building or part thereof is changed to Occupancy Group R-3, such change shall also be subject to the requirements of the New York City Housing Maintenance Code.
Section EBC 1101. General
1101.1 Scope.
An addition to an existing building or structure shall comply with the New York City Building Code as required for new construction without requiring the existing building or structure to be altered to meet such new construction requirements, except as required by this chapter. Where an addition impacts the existing building or structure, that portion shall comply with this code.
1101.2 Creation or extension of noncompliance.
An addition shall not create or extend any noncompliance in the existing building to which the addition is being made with regard to accessibility, structural strength, fire safety, height and area limitations, means of egress, or the capacity of mechanical, plumbing, or electrical systems, except as may be permitted by this chapter.
1101.3 Other work.
Any alteration work within an existing building to which an addition is being made shall comply with the applicable requirements for the work as classified in Chapter 6.
1101.4 Work that increases floor surface area of an existing building by more than 110 percent.
Where an addition including alteration made to an existing building causes the existing floor surface area to be increased by more than 110 percent pursuant to Section 302.7, the entire building shall be made to comply with the provisions of the New York City Building Code as if it were a new construction hereafter erected.
Section EBC 1102. Heights and Areas
1102.1 Height limitations.
No addition shall increase the height of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the New York City Building Code for new construction.
1102.2 Area limitations.
No addition shall increase the area of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the New York City Building Code for new construction unless fire separation, as required by the New York City Building Code, is provided.
Exception: In-filling of floor openings and non-occupiable appendages, such as elevator and exit stairway shafts, shall not be included in determining the floor area as set forth in Chapter 5 of the New York City Building Code.
1102.3 Fire areas.
Existing fire areas increased by the addition shall comply with Chapter 9 of the New York City Building Code.
1102.4 Additions made to certain multiple dwellings.
Vertical and horizontal additions made to multiple dwellings erected in accordance with the law in effect before December 6, 1968, shall also comply with the applicable provisions of Chapters D5, D6, and D7 of Appendix D.
1102.5 Existing buildings within the fire district.
In accordance with Section 302.6 and Appendix D of the New York City Building Code, an existing building shall not hereafter be increased in height or area unless it is of a type of construction permitted for new buildings within the fire district or altered to comply with the requirements for such type of construction. Nor shall any existing building be hereafter extended on any side, nor square footage or floors added within the existing building, unless such modifications are of a type of construction permitted for new buildings within the fire district.
Exceptions:
1. Existing one- and two-family dwellings of a type of construction not permitted in the fire district can be extended by 25 percent of the floor area existing at the time the building was included in the fire district. Such extension shall be of any type of construction permitted by the New York City Building Code.
2. Prior code one- and two-family dwellings of construction class VA may be enlarged to a maximum height of 50 feet (15.2 m) or 4 stories, whichever is less, and a maximum area of 5,000 square feet (465 m 2 ) per floor, where such building is protected with a sprinkler system and smoke alarm system in compliance with Chapter 9 of the New York City Building Code.
Section EBC 1103. Structural
1103.1 Compliance with Chapter 7 of the New York City Existing Building Code.
Additions to existing buildings or structures are new construction and shall comply with the New York City Building Code and Chapter 7
1103.2 Flood hazard areas.
Additions and foundations in flood hazard areas shall comply with Appendix G of the New York City Building Code and Chapter 7.
1103.3 Structural condition assessment.
Additions to existing buildings or structures shall require an initial structural condition assessment in accordance with Section 704.2. Where the addition to the existing building or structure includes a structural alteration or an increase in loads applied to the existing building or structure, a detailed structural condition assessment in accordance with Section 704.3 is also required.
Section EBC 1104. Fire Protection
1104.1 Requirements.
Fire protection systems shall be provided in additions to existing buildings in accordance with Chapter 9 of the New York City Building Code where such systems would be required in new construction for a space or building or where required by the New York City Fire Code.
1104.2 Sprinkler system.
Sprinkler systems shall be provided in additions to a building as required by Section 1104.1.
Exception: Sprinklers shall not be required to be installed in additions to unsprinklered buildings to be occupied exclusively as one- or two-family dwellings. This exception shall not apply where sprinkler protection is otherwise required due to a change of occupancy or alterations made to the existing building pursuant to Chapters 9 or 10, or where sprinkler protection is required by the New York City Fire Code.
1104.3 Standpipe systems.
Standpipe systems shall be provided in additions to existing buildings as required by Section 1104.1, and Sections 1104.3.1 and 1104.3.2 for prior code buildings.
1104.3.1 Additions made to prior code buildings with existing standpipe systems.
Where the alteration involves the addition of stories to a building with an existing standpipe system, and 1 or more stair shafts are not currently equipped with standpipes, standpipes shall be provided in all required stairways in accordance with Chapter 9 of the New York City Building Code.
Exception: Additional standpipes are not required where all of the following conditions are met:
1. The alteration involves the addition of only 1 story;
2. Existing standpipes in existing stair shafts are extended in accordance with Chapter 9 of the New York City Building Code;
3. Standpipe hose connections are provided in compliance with Item 6 of Section 905.4 of the New York City Building Code; and
4. The demand on the standpipe system, including any additional demand, with respect to flow and pressure does not exceed the capacity of the existing approved system.
1104.3.2 Additions made to prior code buildings with no existing standpipe systems.
Where the alteration involves the addition of stories to a building with no existing standpipe system, standpipes shall be provided in all required stairways in accordance with Chapter 9 of the New York City Building Code.
Exception: Standpipes are not required where all of the following conditions are met:
1. The alteration involves the addition of only 1 story;
2. The completed building does not exceed 6 stories; and
3. The completed building does not exceed 85 feet (22.86 m) in height.
1104.4 Fire alarm requirements for additions made to buildings.
Fire alarm systems shall be provided in additions as required by Section 1104.1, and the existing building shall comply with Sections 1104.4.1 through 1104.4.3 as applicable. The fire alarm components for additions shall be connected to the fire alarm system serving the main use or dominant occupancy of the existing building.
1104.4.1 Large-area buildings.
Additions resulting in a large-area building shall comply with Sections 1104.4.1.1 and 1104.4.1.2.
1104.4.1.1 Fire alarm in large-area building.
Where the addition results in the building being classified as a large-area building pursuant to Section 907.2.2.2, 907.2.7.1, 907.2.10.1, or 907.2.8.5 of the New York City Building Code , the fire alarm requirements of those sections shall apply to the entire building.
1104.4.1.2 Auxiliary radio communications systems in large-area buildings.
Where the addition results in the total building area exceeding 250,000 square feet (23 226 m 2 ), an auxiliary radio communication system in accordance with Section 916 of the New York City Building Code shall be provided.
Exception: Auxiliary radio communications systems shall not be required in buildings constructed pursuant to building codes in effect prior to November 7, 2022, where the addition does not exceed 10 percent of the building area in existence or indicated on filed plans on or before such date.
1104.4.2 High-rise buildings.
Where the vertical addition to the existing building results in the building being classified as a high-rise building subject to Section 403 of the New York City Building Code, the fire alarm requirements of Section 907.2.13 of the New York City Building Code shall apply to the entire building.
Exception: In prior code buildings, compliance with Section 907.2.13 of the New York City Building Code shall not be required where the vertical addition is limited to a penthouse level that does not exceed 33 and one-third percent of the roof area including other rooftop structures in accordance with Section 504.3 of the New York City Building Code.
1104.4.3 Smoke and carbon monoxide alarm detection in existing portions of a building.
Where an addition is made to a building or structure of a Group R-2 occupancy that constitutes a portion of a dwelling unit, the entire remaining portion of the dwelling unit shall be provided with smoke and carbon monoxide alarms as required by Chapter 9 of the New York City Building Code.
1104.5 Other alteration work.
Any alteration work within an existing building to which an addition is being made shall comply with the fire protection requirements of Chapters 8 or 9 of this code, as applicable.
Section EBC 1105. Means of Egress
1105.1 General.
Means of egress from an addition to an existing building or structure shall comply with Chapter 10 of the New York City Building Code and with this section. Means of egress from additions shall be permitted to utilize existing exit facilities of the building or structure in accordance with sections 1105.2 through 1105.3. Compliance with Chapter 10 of the New York City Building Code for the new addition’s means of egress shall not conflict with the safe use of the existing egress facilities.
1105.2 The addition does not increase the existing floor surface area by more than 110 percent.
Where the addition including alteration made to the building does not exceed the existing floor surface area by more than 110 percent pursuant to Section 302.7, the existing exit facilities shall be permitted to be utilized by the new addition to discharge onto the outside, subject to Sections 1105.2.1 and 1005.2.2. Such existing exit facilities shall be in compliance with the terms of their approval prior to the proposed addition.
1105.2.1. Prior code buildings.
Means of egress components serving the addition shall comply with Chapter 10 of the New York City Building Code or as permitted by Section 305.5.
1105.2.1.1 Vertical exits.
In prior code buildings, existing vertical exits may be extended to serve the addition, maintaining its width, in compliance with Section 305.5 provided the occupant load of the new addition shall not exceed the capacity of the existing stairs.
1105.2.2 Horizontal additions.
Where the horizontal addition contains a new egress stair, such stair shall comply with Chapter 10 of the New York City Building Code. The new addition shall be permitted to utilize the additional exit facilities provided in the existing portion of the building. Where such existing building is a prior code building, use of existing means of egress shall be permitted to comply with Section 305.5.
1105.3 Work that increases existing floor surface area of an existing building by more than 110 percent.
Where the addition including alteration made to the building involves an increase in the floor surface area by more than 110 percent, as per Section 1101.4, the entire means of egress system for the building including the addition shall comply with Chapter 10 of the New York City Building Code as if hereafter erected.
Exception: The existing means of egress need not be altered to meet the requirements of Chapter 10 of the New York City Building Code as hereafter erected where the horizontal addition made to the existing building acts as an independent building section meeting all the following conditions:
1. The horizontal addition is provided with means of egress independent of the existing building;
2. The horizontal addition is separated from the existing building by a minimum of two-hour rated fire barrier; and
3. The horizontal addition complies with all applicable fire protection requirements of Chapter 9 of the New York City Building Code.
Section EBC 1106. Accessibility
1106.1 Minimum requirements.
Accessibility provisions of Chapter 11 of the New York City Building Code for new construction shall apply to additions. An addition that affects the accessibility to, or contains an area of, primary function shall also comply with the requirements of Sections 806 and 906, as applicable.
1106.2 Additions requiring accessibility throughout a building.
In accordance with Section 1101.4, where an addition, including any alteration made to the building, increases the existing floor surface area of the existing building by more than 110 percent, the entire building shall be made to comply with Chapter 11 of the New York City Building Code as if it were new construction hereafter erected.
Section EBC 1107. Energy Conservation
1107.1 Minimum requirements.
Additions to existing buildings shall conform to the energy requirements of the New York City Energy Conservation Code as they relate to new construction.
Section EBC 1108. Other Building Systems
1108.1 General.
Additions to building systems, elements, and components in existing buildings shall be subject to Sections 1108.2 through 1108.6.
1108.2 Plumbing.
Where additions are made to existing buildings, the alterations and additions to plumbing systems, equipment, and appliances shall be in accordance with the New York City Plumbing Code and this code, as required by Section 310.
1108.3 Fuel gas.
Where additions are made to existing buildings, the alterations and additions to fuel gas piping systems, equipment, and appliances shall be in accordance with the New York City Fuel Gas Code and this code, as required by Section 311.
1108.4 Mechanical.
Where additions are made to existing buildings, the alterations and additions to mechanical systems, equipment, or appliances shall be in accordance with the New York City Mechanical Code and this code, as required by Section 309.
1108.5 Electrical.
Where additions are made to existing buildings, the alterations and additions to electrical systems, equipment, and appliances shall be in accordance with the New York City Electrical Code and this code, as required by Section 308.
1108.6 Elevators.
Where additions are made to existing buildings, the alterations and additions to existing elevators shall be in accordance with Chapter 30 and Appendix K of the New York City Building Code.
Exception: Extensions of existing elevators are not required to serve penthouse structures comprising the upper level of a multi-story R-2 occupancy dwelling unit located upon the roof of a sixth story of a building erected in accordance with the laws in effect before December 6, 1968 and provided that the building is deemed to be 6 stories or less pursuant to Section 504.3 of the New York City Building Code.
1108.6.1 Existing non-elevator buildings.
Where vertical additions are made to existing non-elevator buildings such that the number of stories exceeds the limits specified by Chapter 30 of the New York City Building Code, such buildings shall be provided with at least 1 elevator that accesses all floors.
Exceptions:
1. The addition of a penthouse level above an existing 4-story non-elevator building in Group R-2, where such building is constructed in accordance with the laws in effect on December 6, 1968 or later, provided the penthouse addition meets both of the following conditions:
a. The area of the penthouse addition and other roof structures do not constitute a new story as described in Chapter 15 of the New York City Building Code; and
b. The addition is directly connected to the existing dwelling unit below.
2. Vertical additions to multiple dwellings constructed pursuant to laws in effect before December 6, 1968, as provided for in Section D306.1 of Appendix D of the New York City Building Code.
1108.7 Other alteration work within the existing building.
Any alteration work within an existing building to which an addition is being made shall comply with the plumbing, fuel gas, mechanical, electrical, or elevator requirements of Chapters 8 and 9, as applicable.
Section EBC 1301. General
1301.1 Scope.
The provisions of this chapter shall apply to the alterations, additions and changes of occupancy of existing buildings built prior to July 1, 2008, including moved structures, as referenced in Section 301.1.4 when elected by the design professional of record, as an alternative to the life safety requirements of Chapters 8 through 11 and Chapter 14. The provisions of this chapter are intended to maintain or increase the current degree of public safety in existing buildings while permitting alterations, additions, and changes of occupancy of these buildings.
1301.1.1 Compliance with other provisions of this code.
When this chapter is elected as an alternative to compliance with the life safety provisions of Chapters 8 through 11 as referenced by Section 301.1.3, alterations, additions, and changes of occupancy to existing structures shall comply with all other applicable provisions of Chapters 8 through 11 and Chapter 3 related to use of material, accessibility, structural, plumbing, mechanical, electrical, fuel gas, and energy conservation, including all other requirements of this code not covered by this chapter.
1301.1.1.1 Increase in floor surface area by more than 110 percent.
Where the proposed addition and/or alteration made to an existing building causes an increase in the building floor surface area, over the amount of existing floor surface area, by more than 110 percent, such building shall comply with the New York City Building Code as hereafter erected and this chapter shall not apply, pursuant to Section 302.7.
Section EBC 1302. Applicability
1302.1 Applicability.
Buildings existing prior to July 1, 2008, in which there is work involving additions, alterations, or changes of occupancy shall be made to conform to the requirements of this chapter, when elected by the design professional of record as an alternative to the fire and life safety provisions of Chapters 8 through 11. The provisions of Sections 1302.1.1 through 1302.1.3 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B, E, F, I-2, M, R, and S. These provisions shall not apply to buildings with occupancies in Groups H, I-1, I-3, or I-4. Registered design professionals evaluating buildings classified in Groups R-1 and R-2 shall not violate the requirements of Appendix D in their application of this chapter.
1302.1.1 Change in use or occupancy.
Where an existing building or portion thereof is changed to a new use or occupancy classification, the requirements of Chapters 3 or 10, as applicable, shall apply except as indicated in this chapter and Table 301.1.4.
1302.1.2 Additions.
Additions to existing buildings shall comply with the requirements of Chapters 3 or 11 as applicable, except as indicated in this chapter and Table 301.1.4.
1302.1.3 Alterations.
Alterations to existing buildings or portions thereof shall comply with the requirements of Chapters 3, 8, or 9, as applicable, except as indicated in this chapter and Table 301.1.4.
Section EBC 1303. Acceptance
1303.1 Acceptance.
For alterations, additions, and changes of occupancy to existing buildings that are evaluated in accordance with this chapter as permitted by Section 301.1.4, compliance with this chapter shall be reviewed and accepted by the department.
1303.1.1 Compliance with other codes.
Buildings that are evaluated in accordance with this chapter shall comply with the New York City Construction Codes as applicable.
Section EBC 1304. Investigation and Evaluation
1304.1 Investigation and evaluation.
For proposed work covered by this chapter, the building owner shall cause the existing building to be investigated and evaluated by a registered design professional in accordance with the provisions of Section 1304.
1304.1.1 Submittal.
The results of the investigation and evaluation as required in Sections 1304.2 and 1304.3 along with proposed compliance alternatives, shall be submitted to the department for review and consideration.
1304.1.2 Determination of compliance.
The department shall determine whether the existing building, with the proposed addition, alteration, or change of occupancy, complies with the provisions of this chapter in accordance with the evaluation process in Section 1304.3.
1304.2 Evaluation.
The evaluation shall be comprised of 3 categories: fire safety, means of egress, and general safety, as described in this section and Section 1304.3.
1304.2.1 Fire safety.
Included within the fire safety category are passive fire protection and active fire protection features of the building.
1304.2.2 Means of egress.
Included within the means of egress category are the configuration, characteristics, and support features for means of egress in the building.
1304.2.3 General safety.
Included within the general safety category are the fire safety parameters and the means of egress parameters.
1304.3 Evaluation and scoring process.
The department shall promulgate rules to determine the building elements and systems within the 3 categories of Sections 1304.2.1 through 1304.2.3 subject to the investigation and evaluation process. The rules shall also determine the value of each element or system contributing to the overall building score.
Section EBC 1401. General
1401.1 Scope.
This chapter provides requirements for relocated, moved, or raised buildings including relocatable buildings, as defined in Chapter 2.
1401.1.1 Multiple dwellings.
The relocation, moving, or raising of multiple dwellings shall also comply with Appendix D.
1401.2 Conformance.
The relocation, moving or raising of a building shall not create any new noncompliance with the applicable provisions of the New York City Building Code . Any repair, alteration, or change of occupancy undertaken within the relocated, moved, or raised building shall comply with the requirements of this code applicable to the work being performed, as indicated in Chapter 6 . Any field-fabricated elements shall comply with the requirements of the New York City Building Code .
Exception: Frame structures designated as historic structures may be relocated into fire districts subject to the approval of the commissioner.
1401.2.1 Exterior walls and openings.
Exterior walls and openings of relocated or moved buildings shall comply with Chapter 7 of the New York City Building Code.
Section EBC 1402. Requirements
1402.1 Location on the lot.
Relocated, moved, or raised buildings shall be located on the lot in accordance with the requirements of the New York City Building Code , the New York City Fire Code , the New York City Zoning Resolution , applicable federal, state, and local laws, rules, and regulations.
1402.1.1 Relocating or moving buildings into the fire district.
Buildings shall not hereafter be relocated or moved into the fire district or to another lot in the fire district unless the building is of a type of construction permitted in the fire district. The prohibitions set forth in this section shall not apply to historic frame buildings where approved by the commissioner in accordance with Section 1401.2.
1402.1.1.1 Group R-1 and R-2 occupancies.
No building or space classified in Occupancy Group R-1 or R-2 may be relocated to a lot containing a building classified in construction Type IIB, VA, or VB.
1402.2 Compliance with Chapter 7.
Relocated, moved, or raised buildings shall comply with Chapter 7.
1402.3 Flood hazard areas.
If buildings are to be relocated or moved into a flood hazard area, or are raised within a flood hazard area, such buildings shall comply with Section 1612 and Appendix G of the New York City Building Code.
1402.4 Required inspection.
The department may inspect or require an approved agency to inspect, at the expense of the owner, the various structural parts of a relocated, moved, or raised building to verify that structural components and connections have not sustained structural damage.
1402.4.1 Special inspection of relocating, raising, and moving of a building.
Where an existing building is being relocated, moved, or the lowest above-grade floor or lowest subgrade floor of a building is to be raised, lifted, or elevated, periodic special inspection of such work is required. The permit holder shall notify the department in writing at least 48 hours before the commencement of such work. All new structural work shall be inspected in accordance with Chapter 17 of the New York City Building Code.
1402.5 Exit discharge.
Relocated or moved buildings shall provide access to a public way in accordance with the exit discharge provisions of Chapter 10 of the New York City Building Code.
1402.6 Accessibility.
Relocated, moved, or raised buildings shall be located on the lot so as to be accessible at each entrance in accordance with Chapter 11 of the New York City Building Code .
1402.7 Fire protection.
Where new utility connections are required for a relocated building, subject to the approval of the New York City Department of Environmental Protection, water service lines used exclusively for supplying fire protection systems shall be provided where a building of similar use, occupancy, construction, and height is required to be protected in accordance with Chapter 9 of the New York City Building Code. Such connection shall be ready for future installations, when required by this code.
Exception: One- or two-family dwellings, where space is reserved for future installation of a pressurized tank sized to provide the anticipated water flow demands of a sprinkler system designed in accordance with Chapter 9 of the New York City Building Code.
Section EBC 1501. General
1501.1 Scope.
The requirements of this chapter shall apply to construction or demolition operations performed in existing buildings, as well as buildings that will be occupied during work, including newly constructed buildings that are partially occupied while work is ongoing.
1501.2 Compliance with the New York City Building Code.
In addition to the provisions of this chapter, Chapter 33 of the New York City Building Code shall also govern the conduct of all construction or demolition operations with regard to the safety of the public and property.
1501.3 Responsibility for safety.
Nothing in this chapter shall be construed to relieve persons engaged in construction or demolition operations from complying with other applicable provisions of law, nor is it intended to alter or diminish any obligation otherwise imposed by law on any party engaged in a construction or demolition operation, including but not limited to the owner, construction manager, general contractor, subcontractors, material men, registered design professionals, or other party to engage in sound design and engineering, safe construction or demolition practices, including but not limited to debris removal, and to act in a reasonable and responsible manner to maintain a safe construction or demolition site.
Section EBC 1502. Safeguards for Occupants
1502.1 Occupant protection required.
When construction or demolition activity occurs in an occupied building, barricades, signs, drop cloths, and other protective means shall be installed and maintained as necessary to provide reasonable protection for the occupants against hazard and nuisance. Such protective means shall be indicated on an occupant protection plan, or on a tenant protection plan, as applicable. Protective means shall also be installed as required by this code, the New York City Building Code, and any other applicable provisions of law.
1502.2 Common areas.
Common areas open to the public shall be left clean and free from hazards at the end of the workday.
1502.3 Notification of disruption of utility services, egress, and accessibility features.
In a building, including newly constructed buildings, in which any dwelling unit will be occupied during construction or demolition work, and where heat, hot water, cold water, gas, electricity, or other utility services are to be disrupted by such work, or where required means of egress or accessibility features are to be impacted by such work, occupants of the dwelling units shall be provided a minimum of 48-hours’ notice prior to the disruption or impact, unless the disruption or impact is due to an emergency condition. When due to an emergency condition, notice of the disruption or impact shall be made as soon as practicable.
Exception: Notification of disruption of elevator service shall comply with the requirements of Section 1502.4.
1502.4 Notification of disruption of elevator service.
Notification of disruption of elevator service shall be provided in accordance with Section 28-304.10 of the Administrative Code.
1502.5 Tenant and occupant protection plans.
A tenant protection plan shall be prepared when required by Section 1503. An occupant protection plan shall be prepared when required by Section 1504.
1502.6 Egress.
The requirements of Section 1505 shall apply.
1502.7 Tenant and occupant safety notes for limited alteration applications.
When required by rules promulgated by the department, work performed under a limited alteration application shall be conducted in accordance with tenant and occupant safety notes, with such notes posted at the worksite in a location readily visible to the public. The content of the tenant and occupant safety notes shall summarize existing code and legal requirements.
Section EBC 1503. Tenant Protection Plan
1503.1 Where required.
Alteration, construction, or partial demolition work performed in a building in which any dwelling unit will be occupied during the work, including newly constructed buildings with 1 or more occupied dwelling units, shall be conducted in accordance with a tenant protection plan.
Exceptions: A tenant protection plan is not required for the following types of work. This exception shall not alleviate the owner, contractor, or any other entity engaged in the work from their obligation to comply with applicable tenant protection laws and regulations.
1. Work that does not require a permit.
2. Work whose scope is limited to that authorized by a Limited Alteration Application.
3. Work limited to the alteration of an existing elevator.
4. Electrical work that does not require the submittal of plans to the department.
1503.2 Applicant.
The tenant protection plan shall be prepared by a registered design professional and filed with the department. Such registered design professional shall be retained by the general contractor performing the alteration, construction, or partial demolition work.
Exceptions: In the following instances, the tenant protection plan may be prepared and filed by the registered design professional of record retained by the owner as part of the underlying application for alteration, construction, or partial demolition work:
1. Work in occupied one- and two-family homes.
2. Work limited to the interior of a single, owner-occupied dwelling unit of an occupied multiple dwelling with no disruption to the essential services of other units. For a dwelling unit within a property that is owned by a condominium or held by a shareholder of a cooperative corporation under a proprietary lease, the unit must be occupied by the owners of record for such unit.
1503.3 Permit issuance.
No permit shall be issued for work that requires a tenant protection plan unless such plan is approved by the department.
1503.4 The plan.
Tenant protection plans shall, at a minimum, contain the items required by Sections 1503.4.1 and 1503.4.2.
1503.4.1 Plan statement.
The tenant protection plan shall contain a statement signed by the owner and signed by the applicant affirming that the building contains dwelling units that will be occupied during construction. In addition, such statement shall indicate, in sufficient detail, the specific units that are or may be occupied during construction, and the means and methods to be employed to safeguard the safety and health of the occupants throughout the construction, including, where applicable, details such as temporary fire-rated assemblies, opening protectives, or dust containment procedures. Such means and methods shall be described with particularity and in no case shall terms such as "code compliant," "approved," "legal," "protected in accordance with law," or similar terms be used as a substitute for such description.
1503.4.2 Plan content.
The tenant protection plan must be site specific. The elements of the tenant protection plan may vary depending on the nature and scope of the work but, at a minimum, must comply with all applicable laws and regulations, including the New York City Construction Codes , the New York City Fire Code , the New York City Housing Maintenance Code , the New York City Noise Control Code and the New York City Health Code , and shall make detailed and specific provisions for:
1. Egress. The tenant protection plan shall identify the egress that will be provided. At all times in the course of construction, provision shall be made for code compliant means of egress, as required by the New York City Construction Codes. Required egress shall not be obstructed at any time except where approved by the commissioner.
2. Fire safety. All necessary laws and controls, including those with respect to occupied dwellings, as well as additional safety measures necessitated by the construction, shall be strictly observed.
3. Health requirements. Specification of means and methods to be used for control of dust, disposal of construction debris, pest control, and maintenance of sanitary facilities shall be included.
3.1. Lead and asbestos. There shall be included a statement of compliance with applicable provisions of law relating to lead and asbestos, and such statement shall describe with particularity what means and methods are being undertaken to meet such compliance.
4. Compliance with housing standards. The requirements of the New York City Housing Maintenance Code and the New York State Multiple Dwelling Law, where applicable, shall be strictly observed.
5. Structural safety. No structural work shall be done that may endanger the tenants.
6. Noise restrictions. Specification of means and methods to be used for the limitation of noise to acceptable levels in accordance with the New York City Noise Control Code shall be included. Where hours of the day or the days of the week in which construction work may be undertaken are limited pursuant to the New York City Noise Control Code, such limitations shall be stated.
7. Maintaining essential services. Where heat, hot water, cold water, gas, electricity, or other utility services are provided in such building or in any dwelling unit located therein, the tenant protection plan shall specify the means and methods to be used for maintaining such services during such work in accordance with the requirements of the New York City Housing Maintenance Code.
7.1. Disruptions. If a disruption of any such service is anticipated during the work, the plan shall specify the anticipated duration of such disruption and the means and methods to be employed to minimize such disruption, including the provision of sufficient alternatives for such service during such disruption.
7.2. Coordinating work to minimize disruptions. Where disruptions are anticipated, the plan shall specify coordination efforts to be employed to minimize disruption to tenants, including but not limited to staging or phasing of work.
8. Maintaining accessibility. The tenant protection plan shall specify the means and methods to be used to maintain existing levels of accessibility for building tenants.
8.1. Disruptions. If accessibility is anticipated to be disrupted by the work, then the plan shall specify the anticipated duration of such disruption and the means and methods to be employed to minimize disruption to tenants, including the provision of sufficient alternatives.
9. Notifications. The tenant protection plan shall indicate the means and methods to provide required notifications to the tenants, including but not limited to notifications required by Sections 1502.3 and 1502.4.
1503.5 Public availability of tenant protection plan.
Upon issuance of a permit for work containing a tenant protection plan, the department shall make the tenant protection plan publicly available on its website.
1503.6 Provision of copy of tenant protection plan to tenants upon request.
The owner of a building undergoing work for which a tenant protection plan is required by Section 1503.1 shall, upon request from a tenant of a dwelling unit within such building, provide such tenant with a paper copy of the tenant protection plan approved by the department.
1503.7 Notice to tenants.
Upon issuance of a permit for work containing a tenant protection plan, the owner shall (i) distribute a notice regarding such plan to each occupied dwelling unit and (ii) post a notice regarding such plan in a conspicuous manner in the building lobby, as well as on each floor within 10 feet of the elevator, or in a building where there is no elevator, within 10 feet of or in the main stairwell on such floor. The notice shall be in a form created or approved by the department and shall include:
1. A statement that tenants of the building may obtain a paper copy of such plan from the owner and may access such plan on the department website;
2. The name and contact information of the site safety manager, site safety coordinator, or superintendent of construction required by Section 3301.3 of the New York City Building Code, as applicable, or, if there is no site safety manager, site safety coordinator, or superintendent of construction, the name and contact information of the owner of the building or such owner’s designee; and
3. A statement that tenants of the building may call 311 to make complaints about the work.
4. Where the work involves the disturbance of lead-based paint, as defined in Section 27-2056.2, or paint of unknown lead content, occupants of the building shall be directed to information regarding the hazards associated with lead-contaminated dust in a form established by the department in collaboration with the Department of Health and Mental Hygiene.
1503.8 Phased tenant protection plans.
Multiple layouts of the tenant protection features enumerated in Section 1503.4 may be submitted at any time during construction operations to show phased tenant protection plan designs consistent with the phase of anticipated work. Layouts submitted subsequent to a previously approved tenant protection plan shall constitute an amendment to such plan. Such amended plan shall be approved by the department prior to the commencement of the work requiring such amended plan.
1503.9 Contractor statement.
The permit holder for the underlying alteration, construction, or partial demolition shall sign a statement certifying that the tenant protection plan submitted by the registered design professional aligns with the scope of work intended.
Exception: This statement shall not be required where a tenant protection plan is filed as part of the underlying application, as permitted under the exception to Section 1503.2.
1503.10 Special inspection.
Tenant protection plans shall be subject to special inspection in accordance with Section 1705.26 of the New York City Building Code. The special inspector shall be employed by a special inspection agency and shall possess the qualifications set forth in rules promulgated by the commissioner.
1503.11 Department inspection of tenant protection plan.
The owner shall notify the department in writing at least 72 hours prior to the commencement of any work requiring a tenant protection plan. The department shall conduct an inspection of at least 10 percent of such sites within 7 days after the commencement of such work to verify compliance with the tenant protection plan. The department shall conduct follow-up inspections of such sites every 180 days until the work is completed to verify compliance with the New York City Construction Codes and tenant protection plan. Additionally, the department shall conduct an inspection within 10 days of receipt of a complaint concerning such work. Where the department receives a complaint alleging that dust is not being contained or controlled in accordance with a tenant protection plan, it shall conduct an inspection within 24 hours. The department shall, in collaboration with the department of health and mental hygiene, develop a procedure to complete a lead-contaminated dust test upon a determination that dust is not being contained or controlled during such tenant protection plan inspections or an inspection conducted in response to a complaint, and take any appropriate enforcement action, including the issuance of an order pursuant to section 28-207.2 of the Administrative Code. The department of health and mental hygiene shall assist the department to implement such procedure, including submitting dust samples collected by the department to a laboratory for analysis. The department shall refer the result of any such inspection to the department of health and mental hygiene for review and further inspection in accordance with the New York City Health Code.
1503.12 Enforcement of tenant protection plan.
If work is not being performed in accordance with the tenant protection plan, the commissioner may issue a stop work order pursuant to Section 28-207.2 of the Administrative Code.
Section EBC 1504. Occupant Protection Plan
1504.1 Where required.
Alteration, construction, or partial demolition work performed in a building that will be occupied during the work, including newly constructed buildings that are partially occupied while work is ongoing, shall be conducted in accordance with an occupant protection plan.
Exceptions: An occupant protection plan is not required for the following types of work. This exception shall not alleviate the owner, contractor, or any other entity engaged in the work from their obligation to comply with applicable occupant protection laws and regulations.
1. Work subject to a tenant protection plan in accordance with Section 1503.
2. Work that does not require a permit.
3. Work whose scope is limited to that authorized by a Limited Alteration Application.
4. Work limited to the alteration of an existing elevator.
5. Electrical work that does not require the submittal of plans to the department.
1504.2 Preparing the plan.
The occupant protection plan shall be prepared by or on behalf of the general contractor performing the alteration, construction, or partial demolition work. Where the work will result in a change to building use or occupancy, a permanent change to egress, a temporary reduction to egress during work, or a disruption to fire alarm, standpipe, or sprinkler or similar fire suppression systems during work, such individual preparing the occupant protection plan shall be a registered design professional.
1504.3 The plan.
The occupant protection plan shall provide the same level of detail and clarity, and include the same content and statements, as a tenant protection plan required under Section 1503.4. The term “tenant” in such sections shall, for the purpose of the occupant protection plan, mean “occupant,” and the terms “dwelling,” “dwelling unit,” or “unit” shall mean “occupied space.”
1504.4 Available upon request.
The occupant protection plan shall be kept at the site by the general contractor performing the alteration, construction, or partial demolition work, and shall be made available to the department upon request.
1504.5 Provision of copy of occupant protection plan to occupants upon request.
The owner of a building undergoing work for which an occupant protection plan is required shall, upon request from an occupant of such building, provide such occupant with a paper copy of the occupant protection plan.
1504.6 Notice to occupants.
Upon issuance of a permit for work requiring an occupant protection plan, the owner shall post a notice regarding such plan in a conspicuous manner in the building lobby, as well as within 10 feet of the elevator on each floor open to the public where such work is occurring, or in a building where there is no elevator, within 10 feet of or in the main stairwell on such floor. The notice shall be in a form created or approved by the department and shall include:
1. A statement that occupants of the building may obtain a paper copy of such plan from the owner;
2. The name and contact information of the site safety manager, site safety coordinator, or superintendent of construction required by Section 3301.3 of the New York City Building Code , as applicable, or, if there is no site safety manager, site safety coordinator, or superintendent of construction, the name and contact information of the owner of the building or such owner’s designee, or, if the site is owned or leased by a government entity, the name and contact information of the project officer, building manager, or similar designated official; and
3. A statement that occupants of the building may call 311 to make complaints about the work.
1504.7 Phased occupant protection plans.
The occupant protection plan may be developed in phases to show the occupant protection plan layouts consistent with the anticipated work for such phase. The occupant protection plan maintained at the site must be a complete and self-contained document that fully accords with the ongoing work.
Section EBC 1505. Maintaining Means of Egress
1505.1 Maintenance of means of egress.
Existing required means of egress shall be maintained at all times during construction or demolition operations in an occupied building and shall not be removed, obstructed, or altered in any manner that would diminish the full effectiveness of such means of egress.
Exceptions:
1. Where a new permanent or temporary means of egress that complies with all applicable egress requirements of Chapter 10 of the New York City Building Code is provided in substitution, and the new permanent or temporary means of egress has satisfactorily passed an inspection by the department or another party designated by the department prior to the diminishment of any existing required means of egress in the building.
2. A variance approved in accordance with Section 28-103.3 of the Administrative Code.
Section EBC 1506. Automatic Sprinkler System
1506.1 Sprinkler systems during alteration or demolition.
Existing sprinkler systems in buildings undergoing an alteration or demolition shall comply with the requirements of Section 3303.7.4 of the New York City Building Code and Section 1506.2.
1506.2 Sprinkler protection during construction in fully sprinklered buildings.
Where alterations are proposed to a floor on which the sprinkler system is to be temporarily disconnected in the work area, Temporary Core Sprinkler Protection (TCSP) shall be provided in accordance with Sections 1506.2.1 through 1506.2.5. Alterations shall also comply with the New York City Fire Code , including referenced standards therein.
1506.2.1 Temporary Core Sprinkler Protection (TCSP).
As a temporary fire protection measure, TCSP shall be provided on occupied floors on which an existing sprinkler system is to be temporarily disconnected during alterations. When provided, TCSP shall be connected to the fire alarm system in the building. In buildings without a fire alarm system, TCSP shall be connected to a local annunciation and notification system. TCSP shall comply with and shall be placed in accordance with applicable requirements of NFPA 13 as modified by Appendix Q of the New York City Building Code. TCSP shall provide the same responses as the existing sprinkler system monitoring in the building. TCSP shall be provided at the following locations:
1. At the elevator hoistway openings.
2. At exit doors to required exit stairways.
3. Along the egress paths, including corridors, connecting all required exits and elevator lobbies.
1506.2.2 Sprinkler protection on partially occupied floors.
When a floor is partially occupied during an alteration, the sprinkler heads in the work area may be temporarily removed and the TCSP that complies with Section 1506.2.1 shall not be required provided all the following conditions are met:
1. The work area does not exceed 52,000 square feet (4831 m 2 ) and is fully compartmented in at least 1- hour fire-rated barriers or horizontal assemblies;
2. The entire floor’s sprinkler system remains intact outside of the work area;
3. Sprinkler head(s) are placed on both sides of all entrances to and exits from the work area;
Exceptions:
1. Spaces located outside of the first floor entrances and exits.
2. Openings to exit enclosures.
4. Heat detectors are placed on the construction side of the entrance doors to the temporary compartmented work area. Heat detectors shall be installed in compliance with NFPA 72 as modified by Appendix Q of the New York City Building Code for the occupancy in which they are placed and shall be connected to the fire alarm system in the building. Where there is no fire alarm system, heat detectors shall be connected to a local annunciation and notification system;
5. Sprinkler heads are not placed inside the stairwell when the work area is near the stairwell;
6. All required exits are maintained for the duration of the construction, including those from the work area; and
7. Application for a permanent replacement sprinkler system is made within 60 days of application filed for the temporary removal of sprinklers.
1506.2.3 Sprinkler protection on unoccupied floors.
TCSP, as described in Section 1506.2.1, shall be provided when an entire floor is unoccupied during an alteration in a fully sprinklered existing building. The sprinklers shall be located at an appropriate height above the floor to clear any future ductwork and sprinklers and shall comply with and be placed in accordance with Section 903 of the New York City Building Code.
1506.2.4 Scope of work with duration of 1 year or more.
Where the alteration work is expected to take a year or longer, temporary protection measures described in Sections 1506.2.2 and 1506.2.3 shall not be permitted and the entire floor(s) undergoing alterations shall be sprinklered in accordance with Section 903 of the New York City Building Code.
1506.2.5 Compliance with the New York City Fire Code.
Where temporary removal or disconnection of sprinkler system is permitted in accordance with Sections 1506.2.2 or 1506.2.3, the building owner shall comply with the New York City Fire Code out-of-service requirements.
Section EBC 1601. General
1601.1 General.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard.
1601.2 Subsequent additions, modifications, or deletions.
Refer to the rules of the department for any subsequent additions, modifications, or deletions that may have been made to these standards in accordance with Section 28-103.19 of the Administrative Code.
1601.3 Applicability.
The application of the referenced standards shall be as specified in Section 102.4.3.
Section EBC 1602. Standards
ASCE/SEI American Society of Civil Engineers Structural Engineering Institute 1801 Alexander Bell Drive Reston, VA 20191-4400 Standard reference number Title Referenced in code section number 7—16* *As modified in Chapter 16 of the New York City Building Code Minimum Design Loads and Associated Criteria for Buildings and Other Structures with Supplement No. 1 307.2.1, 705.4 41—17 Seismic Evaluation and Retrofit of Existing Buildings 202 (BSE-1N, BSE-2N), 703.5.3.3, 705.6, Table 705.6
ASME American Society of Mechanical Engineers 3 Park Avenue New York, NY 10016 Standard reference number Title Referenced in code section number A17.1—13* CSA B44—2013 *As modified in Appendix K of the New York City Building Code Safety Code for Elevators and Escalators 306.2.4, 312.6.6, 403.2.5.1, Table 403.2.5.1, 510.2, Table 510.2, 510.3, 806.2.2, 812.1, Table 812.1, 902.1.1.2 A17.3—2015* *As modified in Appendix K of the New York City Building Code Safety Code for Existing Elevators and Escalators 118.2.4, 312.2, 902.1.1.2 A18.1—2014 Safety Standard for Platform Lifts and Stairway Chairlifts 306.2.5
ASTM ASTM International 100 Barr Harbor Drive West Conshohocken, PA 19428-2959 Standard reference number Title Referenced in code section number E136—2012 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C 202 (NON- COMBUSTIBLE MATERIAL) E814—2013 Test Method of Fire Tests of Through-penetration Firestops 502.7.3
ICC International Code Council, Inc. 500 New Jersey Ave, NW, 6th Floor Washington, DC 20001 Standard reference number Title Referenced in code section number A117.1—09 Accessible and Usable Buildings and Facilities 306.2.3, 306.2.4, 306.2.5, 806.2.2, 806.2.9, 806.2.10, 806.2.12
NFPA National Fire Protection Agency 1 Batterymarch Park Quincy, MA 02269-9101 Standard reference number Title Referenced in code section number 13—16* *As modified in Appendix Q of the New York City Building Code Installation of Sprinkler Systems 504.2.2, 505.2.2, 803.2.1, 804.2.8.2, 804.2.8.2.1, 1506.2.1 72—16* *As modified in Appendix Q of the New York City Building Code National Fire Alarm Code 312.6.6, 804.4, 804.4.2, 808.5, 902.1.1.6.1, 1506.2.2 80—13 Fire Dampers 809.2.6.2 105—13 Smoke dampers 809.2.6.3
TMS The Masonry Society 105 South Sunset Street, Suite Q Longmont, CO 80501 Standard reference number Title Referenced in code section number 402—2016* *As modified in Chapter 21 of the New York City Building Code Building Code Requirements and Specifications for Masonry Structures 703.5.3.4
UL UL LLC 333 Pfingsten Road Northbrook, IL 60062 Standard reference number Title Referenced in code section number 1369-18 Aboveground Piping for Flammable and Combustible Liquids 809.14.2 1479—03 Fire Tests of Through-penetration Firestops—with Revisions through October 2012 502.7.3 2085—97 (R2010) Standard for Protected Aboveground Tanks for Flammable and Combustible Liquids (with Revisions through 2010) 809.14
Section EBC A101. Scope
A101.1 General.
This Appendix gives requirements for connecting walls to floors and parapets and chimneys to roofs for existing unreinforced masonry buildings with wood framed floors or roofs, where required by Chapter 7.
The provisions of this Appendix are intended as minimum standards for incrementally improving structural seismic resistance and are established primarily to reduce the risk of loss, damage to property, or injury to persons. Compliance with these provisions will not necessarily prevent loss of life or injury or prevent earthquake damage to retrofitted buildings.
This Appendix is based on a seismic design criteria limit of Sd1 £ .133, and wind conditions of Exposure D. This Appendix does not apply to essential or hazardous facilities.
A101.2 Definitions.
UNREINFORCED MASONRY (URM). Includes burned clay, concrete, or sand-lime brick; hollow clay or concrete block; plain concrete; and hollow clay tile.
UNREINFORCED MASONRY WALL. A masonry wall that:
1. Relies solely on the tensile strength of masonry units, mortar, and grout in resisting design loads. Any area of reinforcement that may be present is neglected in determining resistance to loads; and
2. Carries a minimum service load of 100 pounds per lineal foot (1459 N/m) of roof and/or floor loads.
Section EBC A102. Masonry Wall Connections
A102.1 Connection locations.
Unreinforced masonry walls shall be connected at the roof and floor levels.
A102.1.1 Connection requirements.
Connections shall consist of existing connections and/or new connections. New connections shall be as shown in Figures A1-1, A1-2, or A1-3 where applicable, and provided at a maximum plan spacing of 5 feet and 4 inches (1625 mm) on center. A registered design professional can provide alternative anchor spacings and details for loads conforming to the New York City Building Code. All wall connections shall be secured to the framing members parallel or perpendicular to the wall. Cross-grain bending in wood members used for wall connections is prohibited.
A102.2 Minimum wall connection capacity.
Connection of walls to each floor or roof shall be able to resist a minimum service load of 200 pounds per linear foot (2919 N/m), acting normal to the wall at the level of the floor or roof. Existing wall connections, if used, must meet the requirements of this chapter, or must be supplemented with new connections to comply with requirements.
A102.2.1 Existing wall connections capacity.
Existing connections used as all or part of the required wall connections shall be considered to have a service tension capacity of 100 pounds (445 N), unless tested or evaluated by a registered design professional. Friction shall be neglected in determining existing connection capacity.
A102.2.2 Wall connections per Chapter 33 of the New York City Building Code.
Wall connections installed as required by Section 3309 and attached to joists in a manner similar to Figure A1-1 may be deemed to comply with the requirements of this Appendix.
A102.3 Wall connection testing and inspection.
New wall connections shall be tested and inspected in accordance with the requirements of Chapter 17 of the New York City Building Code, and as required by the connection manufacturer. Testing of existing wall connections, if required, shall be specified and evaluated by a registered design professional.
A102.4 Existing wall wythe bonding and pattern.
A registered design professional shall confirm that the existing exterior wall wythes that are being anchored are properly bonded together. If wythes are not properly bonded together, or the bonding pattern of wythes is different from header courses every sixth course, a registered design professional shall evaluate the conditions and design repairs if required.