1 RCNY § 3007-02 Fire Service Access Elevator (FSAE) Hoistway Lighting
Where hoistway lighting is required to be provided in accordance with Building Code section 3007.5.2, the following lighting control requirements shall apply:
(a) A two-position ON-AUTO switch shall be provided for FSAE hoistway lighting controls.
(b) One switch for each hoistway containing FSAE shall be provided.
(c) Each switch's label descriptor shall include a reference to the FSAE car designation (e.g. A-1).
(Added City Record 1/20/2023, eff. 2/19/2023)