§ 27-440. Gasoline and diesel oil motor vehicle fuel storage
All volatile flammable liquids and diesel oil motor vehicle fuel storage tanks shall be installed below ground and vented to the open air except for such aboveground installation as may be authorized by the rules of the fire commissioner. The installation and venting of storage tanks shall be in accordance with applications and plans approved by the commissioner and shall also meet the requirements of chapter four of this title and the rules of the fire commissioner. Except as otherwise provided for in chapter four of this title or the rules of the fire commissioner, underground tank installations shall comply with the following:
(a) The tops of the tanks shall be at least two feet below finished grade and at least two feet below the level of any cellar or basement floor within ten feet of the tanks.
(b) Tanks shall be supported on foundations complying with subchapter eleven of this chapter.
(c) Tanks shall be located so that the forces from any building foundation and support loads are not transmitted to the tanks. The distance from any part of a tank to the nearest wall of any basement, pit or cellar, or from any property line that may be built upon, shall not be less than three feet.
(d) Tanks shall be covered with a structurally supported reinforced concrete slab at least eight inches thick extending at least twelve inches beyond the horizontal outlines of the tanks and placed over a coverage of suitable clean backfill material.
(e) All concrete shall have a minimum compressive strength of twenty-five hundred pounds per square inch at twenty-eight days.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/068.
§ 27-441. Location of pumps
No gasoline pumps or other mechanical equipment shall be installed so as to permit servicing of motor vehicles standing on a public street. Canopies and supports over pumps and service equipment shall be noncombustible, except that they may be of construction having a one hour fire resistance rating or of heavy timber construction meeting the requirements of section 27-623 of article seven of subchapter ten of this chapter when located more than twenty feet from interior lot lines and from any building or structure.
§ 27-442. Heating equipment
Heat generating equipment for automotive service stations shall be enclosed in accordance with the requirements of section 27-419 of article five of this subchapter.
§ 27-443. Application
This section shall apply to the construction, alteration, and use of buildings or spaces as automotive repair shops.
§ 27-444. Classification
Automotive repair shops shall be classified in industrial occupancy group D-1.
§ 27-445. Volatile flammables
All volatile flammables shall be stored and handled in accordance with the provisions of chapter four of this title.
§ 27-446. Ventilation
All spaces used for the repair of motor vehicles shall be provided with mechanical ventilation adequate to provide four air changes per hour.
(a) Exhaust gases. Where engines are to be run for test purposes or adjustments, provisions shall be made to collect the exhaust gases from each vehicle and to discharge such gases to the outer air by means of a positively induced draft. The discharge opening from such system shall be located as required by subchapter thirteen of this chapter.
(b) Pits. All pits for inspection or repair shall have mechanical exhaust ventilation taken from near the bottom of the pits. Pit exhaust systems shall be adequate to provide at least four air changes per hour.
§ 27-447. Sprinklers
Automatic sprinkler protection complying with the construction provisions of subchapter seventeen of this chapter shall be provided as required by occupancy group D-1.
§ 27-448. Heating equipment
Heat generating equipment for automotive repair shops shall be enclosed in accordance with the requirements of section 27-419 of article five of this subchapter.
§ 27-450. Application
This section shall apply to the construction, alteration, and use of buildings or spaces as public garages. Any areas of such buildings in which gasoline, oil, and similar products are dispensed shall meet the requirements of article eight of this subchapter; any areas in which motor vehicles are repaired shall meet the requirements of article nine of this subchapter; and any areas in which any paint spraying is done shall meet the requirements of article three of this subchapter.
§ 27-451. Classification
Public garages shall be classified according to their specific uses as follows:
(a) Group 1. Buildings or spaces used for the parking of vehicles having fuel storage tanks in excess of twenty-six gallon capacity; or used for the parking of vehicles of any size, and in which mechanical repair, body work, or painting of vehicles is conducted, or in which gasoline, oil, or similar products are dispensed. Group 1 public garages shall be classified in storage occupancy group B-1.
(b) Group 2. Buildings or spaces used exclusively for the parking of vehicles having fuel storage tanks of twenty-six gallon capacity or less, and in which no repair, body work or painting of vehicles is conducted, and in which no gasoline, oil, or similar products are dispensed. Group 2 public garages shall be classified in storage occupancy group B-2.
§ 27-452. Construction
The street floor construction of group 1 public garages shall have at least a two hour fire-resistance rating. Where openings are provided in the floor of any public garage, they shall be protected by railings complying with the requirements of subchapters nine and ten of this chapter, with a curb or ramp at least six inches high above the floor. All floors shall be concrete or equivalent noncombustible material. Columns in parking areas shall comply with the provisions of section 27-559 of article three of subchapter nine of this chapter.
§ 27-453. Group 1 public garages in buildings of other occupancy classification
No group 1 public garage shall be located within, or attached to, a building occupied for any other use, unless separated from such other use by construction meeting the requirements of table 52 for fire divisions. Elevators, stairways, and exit passageways connecting group 1 garages to other occupancies shall be accessible only through vestibules constructed of materials having a two hour fire-resistance rating. The floor area of such vestibules shall be at least fifty square feet but not more than seventy-five square feet. Ventilation shall be provided by a louver permanently-open to the outdoor air having a net free area of one hundred forty-four square inches, located near the floor. Vestibule doors shall be one and one-half hour self-closing fire doors, with a six inch high sill provided at the door between the vestibule and the garage. Both doors shall swing in the direction of the elevators, stairways or exit passageways.
§ 27-454. Roof storage of motor vehicles
Roofs of buildings shall not be used for the parking or storage of motor vehicles unless the building is of class I-A, I-B, or I-C construction, or is an open parking structure. When the roof of a building is used for parking of motor vehicles, it shall be provided with a parapet wall or guard rail at least three feet six inches high, and with curbs or wheel guards of noncombustible materials of a least eight inches high. Such guards shall be substantially anchored to prevent any vehicle from striking the parapet wall or guard rail. Guard rails shall comply with the requirements for railings in subchapter nine of this chapter.
§ 27-455. Sprinklers
(a) Automatic sprinkler protection complying with the construction provisions of article four of subchapter seventeen shall be provided as required for occupancy group B-1 or B-2 respectively, except that in existing buildings lawfully occupied as garages prior to December sixth, nineteen hundred sixty-eight, storage of forty-five thousand gallons or less of product having a flash point over one hundred degrees° F (tag open cup) in the cargo space of tank truck or other vehicles approved for such storage by the fire commissioner, pending delivery, shall not be deemed to require sprinkler protection.
(b) Smoke detection or thermostatic alarm with central office connection. A thermostatic alarm system or smoke detection system equipped with a central office connection complying with subchapter seventeen of this code, and reference standard RS-17-3 of the appendix to this code may be provided in lieu of the sprinkler system required under the preceding subdivision in existing buildings lawfully occupied as garages prior to December sixth, nineteen hundred sixty-eight, when the storage of fuel oils or other products having a flash point over one hundred degrees F (tag open cup) is twenty-two thousand five hundred gallons or more but not exceeding forty-five thousand gallons in the cargo space of tank trucks or other vehicles approved for such storage by the fire commissioner, pending delivery.
(c) Portable fire fighting appliances, as the fire commissioner may direct, shall be provided in existing buildings lawfully occupied as garages prior to December sixth, nineteen hundred sixty-eight, when the storage of fuel oils or other products, having a flash point over one hundred degrees F (tag open cup), in the cargo space of tank trucks or other vehicles approved for such storage by the fire commissioner, pending delivery, is less than twenty-two thousand five hundred gallons.
§ 27-456. Ventilation
Public garages shall be ventilated in accordance with provisions of section 27-766 of article eight of subchapter twelve of this chapter and the following:
(a) Garage spaces above or below grade except as provided in subdivision (e) of this section shall be provided with mechanical ventilation according to one of or a combination of the following methods:
(1) Air exhaust at the rate of not less than one cfm per square foot of total floor area with properly designed means for air inflow.
(2) Air supply at the rate of not less than one cfm per square foot of total floor area with properly designed means for air outflow.
(3) Air exhaust or air supply at a rate sufficient to maintain an average concentration of carbon monoxide not to exceed one hundred parts per one million parts of air for periods longer than one hour and with a maximum concentration at any time not to exceed four hundred parts of carbon monoxide per one million parts of air. The concentration of carbon monoxide shall be determined by periodic tests taken between three and four feet from the floor by means of approved carbon monoxide detector tubes or other equivalent means. This method of mechanical ventilation may be used only if the overall design includes automatic ventilating fan control by means of approved carbon monoxide monitoring devices or by other approved means located so as to provide full protection for the occupancy.
(b) The provisions of section 27-766 of article eight of subchapter twelve of this chapter shall apply.
(c) Air supply shall be taken from an uncontaminated source. Exhaust outlets shall be located in accordance with the requirements of subchapter thirteen with one-half of them located six inches above floor level. In public garages where motor vehicles are parked by mechanical means, the ventilation requirements shall be one-half of those required above.
(d) No automotive service pits shall be installed in floors below the street floor. Pits shall have mechanical exhaust ventilation taken from near the bottom.
(e) Garage spaces above grade provided with natural ventilation having a free openable area of at least five per cent of the total floor area of the space and having adjustable openings measuring at least six inches by four inches located within six inches of the floor and at most sixteen feet apart on all outside and court walls need not be provided with mechanical ventilation.
§ 27-457. Exits
Public garages shall be provided with at least two exits from each tier of parking. One of the exits may be a ramp used by motor vehicles, when serving not more than one level below grade. All vertical exits shall have a minimum width of thirty-six inches and shall be enclosed in two hour fire-resistive construction, except as permitted by section 27-458 of article ten of subchapter seven of this chapter. No exit in a group 1 public garage shall have a path of travel through a fuel dispensing area. In group 2 public garages occurring in occupancy group J-2 buildings, overhead doors shall be of the automatic self-closing type.
(a) Travel distance. No point in any public garage shall be more than one hundred feet from an exit, except that such distance may be increased to one hundred fifty feet when the garage is fully sprinklered.
(b) Repair and fuel spaces. Spaces in group 1 public garages used for the repair of motor vehicles or the dispensing of fuel shall be provided with at least two exits, within the travel distance limitations of subdivision (a) of this section.
(c) Roof parking. When the roof of a building is used for parking, interior vertical exits shall be enclosed in a bulkhead constructed as required by subchapter five of this chapter.
§ 27-458. Ramps
Vehicular ramps in public garages shall not exceed a gradient of one in seven, and their surfaces shall be nonslip. A landing having a minimum length of twenty feet shall be provided at the discharge point at the street level, within the street line. Ramps serving as required exits shall be enclosed in construction having a two hour fire-resistance rating except that openings for motor vehicles at each parking tier may be protected by a water curtain consisting of deluge-type sprinkler heads supplying at least three gallons of water per minute per linear foot of opening.
§ 27-459. Heating equipment
Heat generating equipment for public garages shall be enclosed in accordance with the requirements of section 27-419 of article five of subchapter seven of this chapter.
§ 27-459.1. Parking spaces for people having physical disabilities
Parking spaces for people having physical disabilities shall comply with the requirements of section 27-292.19 and reference standard RS 4-6.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058.
§ 27-460. Application
This section shall apply to the construction, alteration, and use of open parking structures. Open parking structures in buildings of other occupancy group classification shall not be permitted unless separated from other occupancies by construction having at least a two hour fire resistance rating.
§ 27-461. Height and area limitations
The height of the top parking surface, and the area per parking tier, shall not exceed the limitations listed in table 7-1.
TABLE 7-1 Height and Area Limitation of Open Parking Structures
Construction Classification Maximum Allowable Height (ft.) Allowable Area Per Parking Tier (sq.ft.) 1A unlimited unlimited 1B unlimited unlimited 1C 100 50,000 1D 100 50,000 1E 75 30,000
a. The area of an open parking structure having not more than two tiers above grade shall not be limited.
b. Open parking structures of construction class 1C or 1D exceeding three parking levels may be sixty thousand square feet on any parking level provided they shall have at least fifty per cent of their perimeter, fifty per cent open.
c. Open parking structures of construction class 1C or 1D, exceeding three parking levels, may be one hundred thousand square feet on any parking level when fifty per cent of the perimeter is fifty per cent open, and may be one hundred twenty-five thousand square feet on any parking level when seventy-five per cent of the perimeter is fifty per cent open and may be one hundred fifty thousand square feet on any parking level when one hundred per cent of the perimeter is fifty per cent open in all aforementioned cases and shall have frontage space on at least two sides, and the horizontal distance on any level to an open exterior wall shall not exceed two hundred feet.
d. Open parking structures of construction class 1E exceeding three parking levels may be fifty thousand square feet on any parking level when fifty per cent of the perimeter is fifty per cent open and may be sixty-two thousand five hundred square feet on any parking level when seventy-five per cent of the perimeter is fifty per cent open and may be seventy-five thousand square feet on any parking level when one hundred per cent of the perimeter is fifty per cent open in all aforementioned cases and shall have frontage space on at least two sides, and the horizontal distance on any level to an open exterior wall shall not exceed two hundred feet.
e. The allowable areas specified in notes b, c and d above shall apply only to open parking structures used exclusively for the parking and storage of passenger vehicles accommodating not more than nine passengers but not including trailers, campers or similar vehicles.
§ 27-462. Construction
All materials used in the construction of open parking structures shall be noncombustible. Columns in parking areas shall comply with the provisions of section 27-559 of article three of subchapter nine of this chapter. Interior finishes shall be class A. The minimum clear height of any parking tier shall be at least six feet six inches.
(a) Below grade. Any portion of an open parking structure extending below grade shall comply with all of the requirements for public garages as provided in article ten of this subchapter.
§ 27-463. Exterior walls
An exterior enclosure wall shall be required on any side of an open parking structure located within fifteen feet of an interior lot line. Such walls shall be noncombustible construction having at least a two hour fire-resistance rating.
§ 27-464. Curbs and bumpers
Curbs or bumpers of noncombustible materials shall be provided at the perimeter of each parking tier. Such curbs or bumpers shall be at least eight inches high, substantially anchored, and so located that no part of any motor vehicle will contact a wall, partition, or railing.
§ 27-465. Railings
Substantial railings or protective guards of noncombustible materials shall be provided at the perimeter of all parking tiers, except where exterior walls are provided, and around all interior floor openings. Such railings or guards shall be at least three feet six inches high, and shall be designed in accordance with the requirements of subchapter nine of this chapter.
§ 27-466. Floor openings
A curb or ramp at least six inches high shall also be provided at all interior floor openings. All floors shall be pitched to provide adequate drainage.
§ 27-467. Motor fuel pumps
Motor fuel pumps and facilities may be provided within an open parking structure as an accessory use. Such facilities shall comply with the requirements for the storage and handling of volatile flammables as provided in chapter four of this title. The area used for such purpose shall be located on the street floor. No pedestrian exit from any parking area shall have a path of travel through any fuel dispensing area.
§ 27-468. Mechanical parking
Open parking structures in which motor vehicles are parked by mechanical means shall comply with the requirements for open parking structures, except that the requirements for means of egress may be modified as provided in section 27-469 of this article.
§ 27-469. Exits
(a) Driver parking. Open parking structures with driver parking shall be provided with at least two exits from each tier. One of the exits may be a ramp used by motor vehicles, when serving not more than one level below grade. Exit stairs shall have a minimum width of thirty-six inches and may be unenclosed, except that they shall be enclosed in noncombustible construction having at least a two hour fire-resistance rating if the first riser of the stair is more than thirty feet from one of the open exterior walls of the structure. No point on any tier of parking shall be more than one hundred feet from an exit.
(b) Mechanical parking. Open parking structures with mechanical parking equipment shall be provided with at least one exit from each tier of parking. Such exit may be unenclosed, but shall have a minimum width of thirty-six inches. No point on any tier of parking shall be more than two hundred feet from an exit.
§ 27-470. Ramps
Ramps used for the movement of motor vehicles and as required exits need not be enclosed when serving tiers above grade. Such ramps shall have a gradient not exceeding one in seven, with nonslip surfaces. A landing having a minimum dimension of twenty feet shall be provided at the discharge point of all ramps at the street level, within the street line. Where a ramp is also used for the parking of motor vehicles, it shall be considered as a parking tier and may not serve as an exit for the occupants of the structure.
§ 27-471. Elevators
Passenger elevators in open parking structures shall comply with the requirements of subchapter eighteen of this chapter, except that hoistways may be enclosed with noncombustible construction.
§ 27-472. Standpipes
Open parking structures shall be provided with standpipe in accordance with the requirements of subchapter seventeen of this chapter.
§ 27-472.1. Parking spaces for people having physical disabilities
Parking spaces for people having physical disabilities shall comply with the requirements of section 27-292.19 and reference standard RS 4-6.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058.
§ 27-473. Application
This section shall apply to the construction, alteration, and use of buildings or spaces as private garages.
§ 27-474. Classification
Private garages shall be classified in storage occupancy group B-2.
§ 27-475. Attached garages
Private garages attached to, or located above or below, a dwelling shall have walls, partitions, floors, and ceilings separating the garage from the dwelling, having a fire-resistance rating of at least one hour, except that such fire-resistive construction shall not be required between a dwelling and a carport when such carport is open on at least two sides. Any openings to the dwelling in required walls or partitions shall be protected with one and three-quarter inch solid core wood doors or equivalent.
§ 27-476. Connection by breezeway
When a breezeway connects a garage with a dwelling, such a breezeway shall be firestopped at all points of connection to the garage.
§ 27-477. Floors
Garage floors shall be of concrete or equivalent noncombustible material that will not absorb flammable liquids. The sills of all door openings connecting a garage with a dwelling shall be raised at least four inches above the garage floor.
§ 27-478. Ventilation
No air used for heating, cooling, or ventilation shall be circulated through garages to dwellings.
§ 27-479. Application
This section shall apply to the construction, alteration, and use of open parking lots. Open parking lots shall be unobstructed and free of other uses. All driveways and open spaces used for the parking or storage of motor vehicles shall be surfaced with concrete asphalt, or equivalent durable, dustless material.
§ 27-480. Curb cuts
For the purpose of this section, a curb cut shall be defined as the total length of cut curb, including splays.
(a) For street frontages of one hundred feet or less, the amount of cut curb shall not exceed sixty per cent of the frontage of the lot. No single curb cut shall exceed thirty feet in length, and there shall not be more than two curb cuts on any street frontage of one hundred feet or less. The minimum distance between two curb cuts shall be five feet.
(b) For additional street frontage over one hundred feet there may be an additional curb cut for each fifty feet of frontage.
(c) No curb cut shall commence within eight feet of a side lot line, except that on lots with street frontages of fifty feet or less, or on corner lots, the curb cut may commence two feet six inches from the side lot line.
(d) The distance of curb cuts from the intersection of street lines shall comply with the zoning resolution.
(e) Notwithstanding any of the above computations, no curb cut shall be less than ten feet.
§ 27-481. Protection of adjoining property
(a) Curbs and bumpers. Open parking lots shall be completely separated from adjoining land by curbs or bumpers of concrete, masonry, steel, heavy timber, or other similar and equally substantial materials, securely anchored so as to stop motor vehicles. Curbs and bumpers shall be at least eight inches high and eight inches wide. The only openings permitted in required curbs and bumpers shall be for drainage and for motor vehicle entrances and exits, and at pedestrian entrances.
(b) Drainage. Where the surface paving of an open parking lot is non-porous, such lot shall be drained as required by subdivisions (b), (c) or (d) of section P110.2 of reference standard RS-16, as applicable. An asphaltic concrete surface, not to exceed one and one-half inches in thickness after compaction, shall be considered a porous surface provided such surface will pass an amount of water equivalent to one-half inch of rainfall per hour and provided such surface is underlaid by permeable soil, except that whenever an off-street parking facility is constructed in connection with the construction of a new building, or whenever such parking facility falls within the definition of a substantial horizontal enlargement as set forth in subdivision (a) of section P110.2 of reference standard RS-16, all storm water falling or coming to rest on such parking facility shall be disposed of as provided in section P110.2 of reference standard RS-16.
§ 27-482. Accessory uses and occupancies
Parking lot offices, attendant shelters, storage facilities, and similar structures used in conjunction with open parking lots may be provided for accessory use, but shall comply with all of the provisions of this code applicable to the specific use or occupancy. Motor vehicle fuel pumps. Fuel pumps for the servicing of motor vehicles may be provided for accessory use in conjunction with open parking lots when complying with the requirements for the storage and handling of volatile flammables as provided in chapter four of this title. Fuel pumps shall be at least thirty feet from any parking space or interior lot line.
§ 27-483. Parking spaces for people having physical disabilities
Parking spaces for people having physical disabilities shall comply with the requirements of section 27-292.19 and reference standard RS 4-6.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058.
§ 27-488. Application
This section shall apply to the construction, alteration and use of all indoor and outdoor pools intended for swimming or bathing purposes, except for pools that have less than eighteen inches in depth of water at every point. Pools above grade having a maximum water depth of forty-eight inches above grade and an area not exceeding five hundred square feet that are accessory to J-3 occupancies and that are privately used for noncommercial purposes shall be exempt from the provisions of this subchapter except that such pools shall comply with the requirements of section 27-493 of this article. All pools not exempt from the provisions of this subchapter shall comply with the applicable provisions of subchapter sixteen of this chapter. No building permit shall be required for pools exempted by this section. Regardless of any contrary provision, any pool existing on January first, nineteen hundred sixty-nine, which is accessory to J-3 occupancies, and that is privately used for noncommercial purposes shall be exempt from the provisions of this subchapter except that such pools shall comply with the requirements of section 27-493 of this article.
§ 27-489. Construction
Pools shall be constructed so as to be water tight and easily cleaned. They shall be built of nonabsorbent materials with smooth surfaces and shall be free of open cracks and open joints.
(a) Walls. The walls of pools shall be vertical for at least the top two feet six inches below the normal water level. The junctions between the side walls and the bottom shall be coved. A pool overflow shall be provided meeting the requirements of reference standard RS-16.
(b) Bottom slopes. The bottom of any portion of a pool where the water is less than five feet six inches deep shall have a maximum slope of one foot vertically for every fifteen feet horizontally.
(c) Ladders. There shall be a ladder or steps with handrails at the deep end and at the shallow end of every pool. Ladders and steps shall have nonslip treads.
(d) Walkways. Every pool shall have a walkway at least five feet wide around its entire perimeter. The walkway shall have a nonslip surface and be so constructed that it does not drain into the pool.
(e) Hand-holds. Every pool shall be constructed so that either the overflow gutter, if provided, or the top of the side walls afford a continuous hand-hold for bathers.
(f) Markings. Permanent markings showing the depth of the shallow end, break points, diving depth, and deep end shall be provided so as to be visible from both inside and outside the pool.
(g) Spectator area. Areas exclusively intended for spectators shall meet the applicable requirements of subchapter eight of this chapter for places of assembly.
(h) Diving boards and towers. Diving towers shall be rigidly constructed and permanently anchored. The depth of the water below a diving board shall be at least eight feet six inches for boards one meter (3.28 ft.) or less above the water. For diving boards more than one meter and not more than three meters (9 ft. 10 in.) above the water, the depth below the board shall be at least twelve feet. For diving boards or platforms more than three meters above the water, the depth below the board shall be at least sixteen feet. Indoor pools shall provide at least twelve feet overhead clearance above all diving boards.
§ 27-490. Dressing facilities
Toilet rooms, shower rooms, and indoor dressing areas shall be constructed of nonabsorbent materials with smooth-finish walls and partitions. Floors shall have a nonslip surface impervious to moisture, free of cracks or open joints, and sloped to drains. The junctions between the side walls and floors shall be coved. Individual dressing rooms or cubicles within indoor dressing areas shall be excluded from the above requirements. Cabanas and dressing rooms that are not a part of any other occupancy shall also be excluded. Toilets and showers. Toilets, lavatories, and showers, including piping, shall be provided in accordance with the requirements of subchapter sixteen of this chapter.
§ 27-491. Ventilation and heating
Indoor pools, dressing rooms, toilets, and shower rooms shall be ventilated in accordance with the requirements of subchapter twelve of this chapter. Unless used only between May first and October thirty-first, such spaces shall be heated in accordance with the requirements of subchapter twelve of this chapter.
§ 27-492. Water circulation, water treatment, and drainage
The supply, circulation, treatment, and drainage of water for pools shall meet the requirements of subchapter sixteen of this chapter and the health code.
§ 27-493. Safety precautions
(a) No overhead electrical conductors shall be installed within fifteen feet of any swimming pool. All metal fences, enclosures, or railings that might become electrically charged as a result of contact with broken overhead conductors or from any other cause near, or adjacent to, a swimming pool shall be grounded in accordance with the provisions of lightning protection in the electrical code of the city of New York.
(b) Every outdoor swimming pool, fish pond, or other pool greater than eighteen inches deep at any point shall be protected by an enclosure, barrier or other means adequate to make such pool inaccessible to small children which including gates thereto shall be at least four feet high above the adjacent ground. All gates shall be self-latching with latches located at least four feet high above the ground or otherwise made inaccessible to small children from the outside.
§ 27-493.1. Facilities for people having physical disabilities
Facilities for people having physical disabilities shall comply with the requirements of subarticle two of article two of subchapter four and of subchapter sixteen.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058.
§ 27-494. Application
This section shall apply to the construction, alteration, and use of radio and television towers on buildings. Radio and television receiving antennas more than twenty feet high above a roof shall be deemed to be such towers and shall be subject to the requirements of this section.
§ 27-495. Location and access
Towers shall be so located, and equipped with ladders or other devices, as to be readily accessible for inspection purposes. No guy wire or other accessories shall cross or encroach upon any street or pass over any electric power line.
§ 27-496. Construction
Towers located on the roofs of buildings shall be constructed of noncombustible materials. Isolated towers less than one hundred feet high and supported directly from the ground may, when located outside of the fire districts, be constructed of timber meeting the requirements of construction class II-A. All towers shall be grounded for lightning protection in accordance with the provisions of the electrical code of the city of New York.
§ 27-497. Loads
Towers shall be designed in accordance with the load requirements of subchapter nine of this chapter.
§ 27-498. Application
This section shall apply to the construction, alteration, and use of all outdoor signs and display structures, together with their appurtenant and auxiliary devices.
(a) No sign may be hung or attached upon or on the outside of any building unless such work is performed by or under the supervision of a licensed sign hanger.
(b) No sign shall be erected until a permit therefor has been obtained from the commissioner in accordance with the provisions of article two of subchapter eleven of this chapter.
§ 27-499. Obstructions
No sign shall be erected so as to obstruct free ingress to, or egress from, a required door, window, stairs, or other required exits, or be placed so as to prevent free passage from one part of a roof to any other part. No sign shall be attached in any manner to a fire escape or exterior stair, or placed so as to interfere with any opening for light or ventilation required under the provisions of subchapter twelve of this chapter.
§ 27-500. Ground signs
(a) Location. No part of a ground sign shall be erected so as to project beyond the street line, except as specifically permitted by the provisions of subchapter four of this chapter.
(b) Materials. Inside the fire districts, ground signs shall be constructed entirely of noncombustible materials, except as permitted in sections 27-506 and 27-507 of this article. Outside the fire districts, the structure of ground signs exceeding twenty-five hundred square feet in facing or display area shall be constructed of noncombustible materials, and the facing of such signs shall be noncombustible, except as permitted in sections 27-506 and 27-507 of this article. The bottom of the facing of all ground signs shall be at least thirty inches above the ground, which space may be filled with open lattice work or decorative trim.
(c) Supports. Ground signs shall be constructed and anchored to resist loads acting in any direction on the sign, in accordance with the provisions of subchapter nine of this chapter.
(1) Anchors and supports shall be designed for safe bearing loads on the soil and for an effective resistance to pullout amounting to a force twenty-five per cent greater than the required resistance to overturning. Anchors and supports shall penetrate to a depth of at least four feet.
(2) Whenever anchors or supports consist of wood embedded in the soil, the wood shall be treated under pressure as specified in subchapter eleven of this chapter before erection. This requirement shall not apply to signs which are not to remain in place for more than six months.
(3) Members furnishing structural support for signs shall be designed in accordance with the requirements of subchapter ten of this chapter, and shall be of adequate thickness to meet the corrosion conditions.
§ 27-501. Wall signs
(a) Limitations. Wall signs shall not extend beyond the top or ends of the wall surface on which they are placed unless meeting all the requirements of this code regulating roof signs, projecting signs, or ground signs as the case may be. Wall signs shall not project beyond street lines except as permitted in subchapter four of this chapter.
(b) Materials. Inside the fire districts, wall signs shall be constructed entirely of noncombustible materials except as permitted in sections 27-506 and 27-507 of this article. Outside the fire districts, the framework of wall signs exceeding five hundred square feet. in facing or display area shall be constructed of noncombustible materials, and the facing of such signs shall be noncombustible except as permitted in sections 27-506 and 27-507 of this article.
(c) Supports. Wall signs shall be constructed and supported to resist loads acting in any direction on the sign in accordance with the provisions of subchapter nine of this chapter. Attachment shall be by means of metal anchors, bolts, or similar devices. Wooden blocks or anchorage with wood used in connection with screws or nails shall not be used, except in the case of wall signs attached to buildings having walls of wood.
(d) Fire department access. Wall signs that are, or have been, erected to cover doors or windows required by this code for fire department access to existing buildings shall be provided with access panels as required by section 27-292 of article two of subchapter four of this chapter. Existing wall signs shall be altered or otherwise arranged to comply with this requirement on or before December sixth, nineteen hundred seventy.
§ 27-502. Projecting signs
(a) Location. Projecting signs, other than temporary signs, shall not be constructed on those streets and avenues listed in reference standard RS 7-2, and shall not be constructed to project beyond the street line except as permitted in subchapter four of this chapter.
(b) Limitations. Projecting signs whose width when measured at a plane parallel to the building wall, does not exceed two feet may extend not more than five feet above the main roof level of the building to which they are attached; except that for buildings thirty-five feet high or less, such projecting signs may be erected to a maximum height of forty feet above grade but in no case to a height of more than fifteen feet above the main roof level.
(c) Materials. All projecting signs shall be constructed of noncombustible materials except as permitted in sections 27-506 and 27-507 of this article.
(d) Supports. Projecting signs shall be constructed and supported to resist loads acting in any direction on the sign in accordance with the provisions of subchapter nine of this chapter. Attachment shall be by means of metal anchors, bolts, supports, chains, wire ropes, rods, or other similar devices. No staples or nails shall be used to secure any projecting sign to any building. Turnbuckles or other equivalent means of adjustment shall be placed in all chains, wire ropes, or rods supporting or bracing projecting signs. All chains, wire ropes, or rods, and their attachments, shall be galvanized or of corrosion-resistant material, and no such supports shall be attached to an unbraced parapet wall.
§ 27-503. Roof signs
(a) Location. Roof signs shall be set back a minimum of six feet from the face of the walls of the building on which they are erected.
(b) Materials. Inside the fire districts, roof signs shall be constructed entirely of noncombustible materials except as permitted in sections 27-506 and 27-507 of this article. Outside the fire districts, the framework of roof signs exceeding fifteen hundred square feet in facing or display area or having any part more than sixty-five feet above grade shall be constructed of noncombustible materials, and the facing of such signs shall be noncombustible, except as permitted in sections 27-506 and 27-507 of this article.
(c) Supports. Roof signs shall be constructed and anchored to resist loads acting in any direction on the sign in accordance with the provisions of subchapter nine of this chapter. Such signs shall be so constructed as to leave a clear space of at least seven feet between the roof and the lowest part of the sign, and at least five feet between the vertical supports thereof.
§ 27-504. Marquee signs
(a) Limitations. No part of a marquee sign shall project above or below the marquee fascia, except that in the case of theaters licensed under the provisions of subchapters one and three of chapter two of title twenty of the administrative code, marquee signs may project not more than eight feet above nor more than one foot below the fascia, provided that the total height of such signs does not exceed nine feet and the lowest part of such signs is at least ten feet above the ground or sidewalk level. Marquee signs may extend the full length of the marquee on all sides, but in no case shall they project beyond the ends of the marquee.
(b) Materials. All marquee signs shall be constructed of noncombustible materials except as permitted in sections 27-506 and 27-507 of this article.
(c) Supports. Construction and anchorage of marquee signs shall conform to the requirements for projecting signs under subdivision (d) of section 27-502 of this article.
§ 27-505. Illuminated signs
General. All ground signs, wall signs, roof signs, projecting signs, and marquee signs may be lighted by internal or external sources when complying with the following requirements:
(1) ILLUMINATION. No sign shall be illuminated by other than electrical means. All wiring and accessory electrical equipment shall conform to the provisions of the electrical code of the city of New York.
(2) MATERIALS. Every illuminated sign shall be constructed of noncombustible materials except as permitted in section 27-507 of this article.
(3) PERMISSIBLE PROJECTIONS. Lighting reflectors may project beyond the top or face of all signs, provided that every part of such reflector is at least ten feet above the ground or sidewalk level. In no case shall such reflectors project beyond a vertical plane two feet inside the curb line. Reflectors shall be constructed, attached, and maintained so that they shall not be, or become, a hazard to the public.
§ 27-506. Temporary signs
(a) Materials. Temporary signs not more than five hundred square feet in area may be constructed of combustible materials. Temporary signs more than one hundred square feet in area shall be made of rigid materials with rigid frames. Temporary signs shall be securely attached to their supports, and shall be removed as soon as they are torn or damaged, but in no case later than thirty days after their erection.
(b) Limitations. Temporary signs of combustible materials shall not extend more than one foot over, or into, a street, except that when permitted by the department of transportation, temporary banners or signs of combustible materials may be suspended from buildings or poles to extend across streets, and except that temporary signs of combustible materials constructed without a frame may be attached flat against, or suspended from the fascia of a canopy or marquee, provided that the lowest part of any such sign is at least nine feet above the ground or sidewalk level.
§ 27-507. Use of combustible materials
(a) General. In all signs required to be constructed of noncombustible materials under the provisions of this code, wood or other materials of combustible characteristics similar to wood may be used for moldings, cappings, trim, nailing blocks, letters, latticing, and other purely ornamental features.
(b) Slow-burning plastics. Slow-burning plastics may be used in sign construction subject to the following conditions and requirements.
(1) If all parts of the sign other than the letters and decorations are made from noncombustible materials, the display surface or sign facing may be made of slow-burning plastic, or may be occupied or covered by letters and decorations made from, or faced with, slow-burning plastics not exceeding a total area calculated from the values given in tables 7-2 and 7-3.
TABLE 7-2 Ground Signs and Wall Signs (Noncombustible Materials)
Area of Facing or Display Surface Area Occupied or Covered by Plastics 150 sq. ft. or less 100 per cent of display surface area Over 150 sq. ft., but not over 2,000 sq. ft. 150 sq. ft. plus 50 per cent of the difference between 150 sq. ft. and the area of the display surface Over 2,000 sq. ft. Not over 1,050 sq. ft. without permission of the commissioner
TABLE 7-3 Roof Signs, Projecting Signs, and Marquee Signs (Noncombustible Materials)
Area of Facing or Display Surface Area Occupied or Covered by Plastics 150 sq. ft. or less 100 per cent of display surface area Over 150 sq. ft. but not over 2,000 sq. ft. 150 sq. ft. plus 25 per cent of the difference between 150 sq. ft. and the area of the display surface. Over 2,000 sq. ft. Not more than 575 sq. ft. without permission of the commissioner
(2) If combustible materials are permitted in the framework, moldings, cappings, trim, nailing blocks, latticing or other parts of the sign, the display surface or sign facing may be occupied or covered by letters and decorations made from or faced with slow-burning plastics not exceeding a total area calculated from the values given in tables 7-4 and 7-5.
TABLE 7-4 Ground Signs and Wall Signs (Combustible Materials)
Area of Facing or Display Surface Area Occupied or Covered by Plastics 300 sq. ft. or less 50 per cent of display surface area Over 300 sq. ft. but not over 2,000 sq. ft. 150 sq. ft. plus 25 per cent of the difference between 150 sq. ft. and the total area of the display surface Over 2,000 sq. ft. Not over 575 sq. ft. without permission of the commissioner
TABLE 7-5 Roof Signs (Combustible Materials)
Area of Facing or Display Surface Area Occupied or Covered by Plastics 1,000 sq. ft. or less 25 per cent of display surface area Over 1,000 sq. ft. but not over 2,000 sq. ft. 250 sq. ft. plus 10 per cent of the difference between 1,000 sq. ft. and the total area of the display surface Over 2,000 sq. ft. Not more than 350 sq. ft. without special permission of the commissioner
§ 27-508. Maintenance and inspection
(a) Maintenance. All signs, together with all supports, braces, guys, and anchors, shall be kept in good repair at all times, and when not adequately galvanized or constructed of corrosion-resistant materials, shall be painted periodically to prevent corrosion. It shall be the duty and responsibility of the owner or lessee of every sign to maintain the immediate premises occupied by the sign in a safe, clean, sanitary, and inoffensive condition and free and clear of all obnoxious substances.
(b) Annual inspection. Every sign for which a permit is required shall be inspected at least once in every calendar year.
Title 27, Chapter 1, Subchapter 7, Article 17-A. Youth Protection Against Tobacco Advertising and Promotion Act
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.1. Short title
This article shall be known and may be cited as the "Youth Protection Against Tobacco Advertising and Promotion Act."
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.2. Definitions
For the purposes of this article, the following terms shall be defined as follows:
a. "Amusement arcade" means any enclosed business establishment, open to the public, whose primary purpose is the operation of coin-operated amusement devices within the meaning of subchapter three of chapter two of title 20 of this code.
b. "Child day care center" means (i) any child care arrangement, public, private or parochial child care center, school-age child care program, day nursery school, kindergarten, play school or other similar school or service operating pursuant to authorization, license or permit of the city or state, (ii) any facility that provides child care services as defined in section four hundred ten-p of the New York state social services law, or (iii) any child day care center as defined in section three hundred ninety of the New York state social services law. The definition of "child day care center" applies whether or not care is given for compensation but does not include child day care centers located in private dwellings and multiple dwelling units.
c. "Cigarette" means any product which consists of (i) any roll of tobacco wrapped in paper or in any substance not containing tobacco or (ii) any roll of tobacco wrapped in any substance containing tobacco which, because of its appearance, the type of tobacco used in the filler, or its packaging and labeling is offered for use or purchase by consumers as a cigarette described in (i) of this subdivision.
d. "Cigarette tobacco" means any product that consists of loose tobacco and is intended for use by consumers in a cigarette.
e. "Multiple dwelling" means any building or structure that may lawfully be occupied as the residence or home of three or more families living independently of each other.
f. "Multiple dwelling unit" means any unit of residential accommodation in a multiple dwelling.
g. "Person" means any natural person, partnership, co-partnership, firm, company, corporation, limited liability corporation, agency as defined in section eleven hundred fifty of the New York city charter, association, joint stock association or other legal entity.
h. "Playground" means any outdoor premises or grounds owned or lawfully operated by or on behalf of, the board of education, the department of parks and recreation, or any public, private or parochial school, any child day care center or any youth center, which contains any device, structure or implement, fixed or portable, used or intended to be used by persons under the age of eighteen for recreational or athletic purposes including, but not limited to, play equipment such as a sliding board, swing, jungle gym, sandbox, climbing bar, wading pool, obstacle course, swimming pool, seesaw, baseball diamond, athletic field, or basketball court.
i. "Private dwelling" means any building or structure or portion thereof that may lawfully be occupied for residential purposes by not more than two families, including the grounds of such building or structure.
j. "School building" means any building or structure or any portion thereof, owned, occupied by, or under the custody or control of any public, private or parochial institution and lawfully used for the primary purpose of providing educational instruction to students at or below the twelfth grade level.
k. "Smokeless tobacco" means any product that consists of cut, ground, powdered, or leaf tobacco that is intended to be placed by the consumer in an oral cavity.
l. "Tobacco product" means a cigarette, smokeless tobacco or cigarette tobacco.
m. "Tobacco product advertisement" means any written word, picture, logo, symbol, motto, selling message, poster, placard, sign, photograph, device, graphic display or visual image of any kind, recognizable color or pattern of colors, or any other indicia of product identification identical or similar to, or identifiable with, those used for any brand of tobacco product, or any combination thereof, the purpose or effect of which is to promote the use or sale of a tobacco product through such means as, but not limited to, the identification of a brand of a tobacco product, a trademark of a tobacco product or a trade name associated exclusively with a tobacco product.
n. "Tobacco product promotion" means (i) any item or service marketed, licensed, sold or distributed, whether indoors or outdoors, which is not a tobacco product but which bears the brand of a tobacco product, a trademark of a tobacco product or a trade name associated exclusively with a tobacco product, alone or in conjunction with any written word, picture, logo, symbol, motto, selling message, poster, placard, sign, photograph, device, graphic display or visual image of any kind, recognizable color or pattern of colors, or any other indicia of product identification identical or similar to, or identifiable with those used for any brand of a tobacco product, or (ii) any gift or item other than a tobacco product offered or caused to be offered to any person purchasing a tobacco product in consideration of the purchase thereof, or to any person in consideration of furnishing evidence, such as credits, proofs-of-purchase, or coupons, of such purchase; provided, however, that a tobacco product promotion shall not include any gift or item provided through the exchange or redemption through the mail of any such credits, proofs-of-purchase, coupons or other evidence of the purchase of a tobacco product.
o. "Youth center" means any building or structure or portion thereof, lawfully occupied by any person for the primary purpose of operating a trade school (including those conducting after-school, vocational, remedial, tutorial, educational assistance programs) or an indoor recreational center (including recreational, cultural, physical fitness, or sports programs) for persons under the age of eighteen years, and which has been certified as such to the department in accordance with the procedure to be set by the department. Such certification shall be accepted by the department but nothing in this subdivision shall prevent the commissioner from removing a certified youth center from consideration as a youth center if she or he determines it does not meet the criteria of a youth center.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.3. Tobacco product advertisement restriction
a. It shall be unlawful for any person to place, cause to be placed, to maintain or to cause to be maintained, a tobacco product advertisement within one thousand feet, in any direction, of any school building, playground, child day care center, amusement arcade or youth center, in any outdoor area including, but not limited to, billboards, roofs and sides of buildings, rolling shutters or gates, any enclosures into which rolling shutters or gates retract, water tanks and towers and free-standing signboards; provided, however, that any tobacco product advertisement on an awning projecting from the outside of a premises as of July 1, 1997 where tobacco products are sold or offered for sale may be retained until two years from the effective date of this law.
b. It shall be unlawful for any person to place, cause to be placed, to maintain, or cause to be maintained, a tobacco product advertisement in the interior of a building or structure which is within one thousand feet, in any direction, of any school building, playground, child day care center, amusement arcade or youth center, when such advertisement is within five feet of any exterior window or any door which is used for entry or egress by the public to the building or structure; provided, however, that tobacco product advertisements may be placed or maintained in the interior of any such premises where such advertisements are (i) parallel to the street and face inward, or (ii) affixed to a wall panel or similar fixture that is perpendicular to the street regardless of whether such advertisements are illuminated or not illuminated.
c. Nothing in this section shall prevent a person from placing, causing to be placed, maintaining, or causing to be maintained, a single sign, poster, placard or label no larger than six square feet and containing only black text, in any language, not exceeding eight inches in height on a white background stating "TOBACCO PRODUCTS SOLD HERE" or such words translated into any language, within ten feet of an entrance to the premises where tobacco products are sold or offered for sale.
d. Nothing in this section shall prevent a tobacco product manufacturer, distributor or retailer from placing, causing to be placed, maintaining or causing to be maintained, its corporate or other business name on a building or structure, in any location, where such building or structure or a portion thereof is owned, operated or leased by such manufacturer, distributor or retailer and that building or structure is the principal place of business of such manufacturer, distributor or retailer in the city of New York; provided, however, that the corporate or other business name of such manufacturer, distributor or retailer is registered or filed in the United States or such manufacturer, distributor or retailer is authorized to do business in any state, and the corporate or business name of such manufacturer, distributor or retailer does not include any brand name or trademark of a tobacco product, alone or in conjunction with any written word, picture, logo, symbol, motto, selling message, poster, placard, sign, photograph, device, graphic display or visual image of any kind, recognizable color or pattern of colors, or any other indicia of product identification identical or similar to, or identifiable with, those used for any brand of a tobacco product.
e. This section shall not apply to any tobacco product advertisement on a motor vehicle. Nothing in this subdivision shall be construed to authorize the placement of a tobacco product advertisement in a location where such placement is otherwise prohibited by the rules of the department of transportation or other applicable law.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.4. Non-compliant advertisements to be removed
The owner, operator or lessee of any location or premises where a tobacco product advertisement is prohibited or restricted pursuant to the requirements of section 27-508.3 of this article shall have thirty days from the effective date of the local law that added this section to remove any non-compliant tobacco product advertisements.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.5. Sponsorship of and at events
Nothing in this article shall prevent a tobacco products manufacturer, distributor, or retailer who sponsors, in whole or in part, any athletic, musical, artistic, or cultural event, or team or entry in a competition or exhibition in any location from displaying or causing to be displayed the corporate or other business name of such sponsor; provided, however, that the corporate or other business name of such sponsor is registered or filed in the United States or such sponsor is authorized to do business in any state, and the corporate or other business name of such sponsor does not include any brand name or trademark of a tobacco product, alone or in conjunction with any written word, picture, logo, symbol, motto, selling message, poster, placard, sign, photograph, device, graphic display or visual image of any kind, recognizable color or pattern of colors, or any other indicia of product identification identical or similar to, or identifiable with, those used for any brand of a tobacco product.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003.
§ 27-508.6. Injunctive relief
Whenever any person has engaged in any act or practice which constitutes a violation of any provision of this article or of chapter thirteen of title eleven of this code, or of subchapter one of chapter two of title twenty of this code, or of any rule promulgated thereunder, the city may make application to a court of competent jurisdiction for an order enjoining such act or practice.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/003 and L.L. 2000/002.
§ 27-508.7. Penalties
Notwithstanding the provisions of sections 26-122, 26-125 and 26-248 of this code, a violation of this article shall not subject any person to liability for a criminal offense.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1998/010.
§ 27-509. Permitted heights
In other than residence districts as established by the zoning resolution, fences may be erected throughout the city to a maximum height of ten feet. In residence districts, no fences, whether of masonry, steel, wood, or any other materials shall be erected to a height of more than six feet above the ground, except that fences used in conjunction with nonresidence buildings and public playgrounds, excluding buildings accessory to dwellings, may be erected to a height of fifteen feet Higher fences may be permitted by the commissioner where required for the enclosure of public playgrounds, school yards, parks, and similar public facilities.
§ 27-510. Location and height
Tents or air-supported structures may be erected inside or outside of the fire districts provided they are not more than one story high above the ground, or above a roof that meets the requirements of subchapter five of this chapter for fire divisions.
§ 27-511. Separation
No tent or air-supported structure shall be erected closer than twenty feet to any interior lot line nor closer than thirty feet in any direction to an unprotected opening, required exterior stairway or corridor, or required exit door, on the same level or above the level of the tent or air-supported structure. A tent or air-supported structure may abut another building on the same lot if there are no unprotected openings or exits above or within thirty feet as above stipulated, if there is no door between them that is a required exit, and if the exterior wall separating them meets the requirements of subchapter five of this chapter for fire divisions. Exceptions. Requirements for separation from other buildings on the site shall be waived where a tent or air-supported structure is used for on-site temporary shelter for construction work, or incidental fabrication of construction elements to be used on the site of construction.
§ 27-512. Fire protection
The ground enclosed by a tent or air-supported structure, and the ground for a distance of at least ten feet. outside of same, shall be cleared and maintained clear of all combustible material or vegetation. No open flame of any kind shall be employed within the structure, or closer than twenty feet to any part of the enclosure fabric. Fire extinguishing facilities shall be provided in accordance with the requirements of chapter four of this title.
§ 27-513. Exits
Notwithstanding any other requirements of subchapters six and eight of this chapter, travel distance to an exit from any point within a tent or air-supported structure shall not exceed seventy-five feet. Exit doors in air-supported structures shall close automatically against normal operational pressures. Opening force at the edge of such doors shall not exceed fifteen pounds, with the structure at operational pressure. Exit doors shall be located in frames so constructed that they will remain operative and support the weight of the structure in a state of total collapse.
§ 27-514. Structural requirements
(a) Tents. Tents shall be guyed, supported, and braced to withstand a wind pressure of ten pounds per square foot of projected area of the tent. The poles and their supporting guys, stays, stakes, fastenings, etc. shall be of sufficient strength and attached so as to resist wind pressure of twenty psf of projected area of the tent.
(b) Air-supported structures.
(1) Air-supported structures shall be anchored to the ground or supporting structure by either ballast or positive anchorage, sufficiently and evenly distributed, and adequate to resist the inflation lift load, the aerodynamic lift load, and the drag (shear) load due to wind impact. The latter factors shall be based on a wind velocity of at least seventy miles per hour, and an estimated stagnation of not less than 0.5q for structures on grade whose height is equal to, or less than, the width of the structure. For greater heights, or for elevated structures, increased anchorage shall be provided, justified by analytical and/or experimental data.
(2) The skin of the structure shall be of such strength, and the joints so constructed, as to provide a minimum dead load strip tensile strength at seventy degrees F of four times the seventy mph design load (inflation and aerodynamic loading). The joints shall provide a dead load strip tensile strength of one hundred sixty degrees F of twice the seventy mph design load (i.e., a factor of safety of four and two respectively). In addition, the material shall provide a trapezoidal tear strength of at least fifteen per cent of the maximum design tensile load. Material and joint strengths shall be so certified by the manufacturer, justified by analytical and/or experimental data.
§ 27-515. Flame resistance
(a) Tents. All materials used for tents shall be treated to be flameproofed and shall remain flameproofed in accordance with chapter four of this title.
(b) Air-supported structures. All fabrics that have a base fabric weight of 6.4 oz. per square yard or less or that are used to enclose spaces classified in occupancy group C, E, F, G, H or J shall have an extinction time of not more than two seconds when tested under the small scale test method of reference standard RS 7-3. All other fabrics shall have a flame extinction time of not over one minute and/or a flame spread of not over one inch per minute when tested in accordance with the provisions of reference standard RS 7-4.
§ 27-516. Pressurization system
Air-supported structures shall be inflated and shall remain inflated during all periods of occupancy to a minimum differential pressure of 0.88 in. and a maximum differential pressure of 1.50 in. of water. Ventilation flow per occupant, either through vents or anticipated leakage, shall comply with the requirements of subchapter twelve of this chapter. Occupied spaces. Where the net floor area per occupant is one hundred fifty square feet or less, the structure shall be provided with at least two blowers, each of which shall have adequate capacity to maintain the required inflation pressure. Also, an auxiliary engine-generator set capable of powering one blower, or a supplementary blower powered by an internal combustion engine, either of which shall have the capacity to run continuously for four hours, shall be located outside the structure, shall be weather protected, and shall be arranged to automatically operate the blower within twenty seconds upon failure of the normal source. Heat shall be provided from a source outside the structure so arranged as to prevent the spread of fire to the structure. The temperature within the air-supported structure shall be maintained at the temperature required by subchapter twelve of this chapter, but not less than fifty degrees Fahrenheit during periods of snowfall.
§ 27-517. Certificate of occupancy
Certificates of occupancy for tents or air-supported structures shall be issued for a period not exceeding one year, and such certificates may be renewed for one year periods thereafter if the tent or air-supported structure complies with all laws, rules and regulations in effect at the time of request for renewal.
§ 27-518. Application
This article shall apply to the construction, alteration and use of buildings or spaces wherein nitric acid is stored.
§ 27-519. Location
Carboys containing nitric acid shall be stored in storage vaults.
§ 27-520. Construction requirements
(a) Vaults shall be constructed of incombustible acid-resistant material with a fire resistance of at least one hour.
(b) Doors opening into such storage vaults shall be self-closing, noncombustible fire doors with a fire-protection rating of at least three quarters of an hour.
(c) Vault floors shall be constructed of acid-resistant brick, concrete treated with sodium silicate or other acid-proof material and shall incorporate a dike constructed of the same material, whose height shall be adequate to contain the acid plus the neutralizing substance that would be necessary to neutralize said acid plus six inches.
(d) The floor shall be provided with a valved drain which shall be connected to the drainage system in accordance with the requirements of subchapter sixteen of this chapter.
§ 27-521. Ventilation
Mechanical ventilation systems for storage vaults shall be adequate to effect ten complete air changes per hr. Exhaust shall be taken from within twelve inches above the level of the top of the dike. The exhaust system shall be independent of exhaust systems serving other parts of the building and the openings to the outdoors shall be located in accordance with the provisions of subchapter thirteen of this chapter for system conveying vapors.
§ 27-521.1. Applicability
This article shall apply to the construction, alteration and use of atriums.
§ 27-521.3. Construction
(a) Atriums may be constructed only in buildings in noncombustible construction groups 1-A, 1-B and 1-C.
(b) An atrium shall be fully enclosed except that openings of any size into the two lowest levels of an atrium shall be permitted if such openings are provided with opening protectives having a fire-resistance rating of at least one and one-half hours or are provided with sprinklers no more than six feet apart.
(c) The minimum horizontal clear dimension of an atrium shall be forty feet, provided, however that this dimension can be reduced to twenty feet where sprinkler spacing on the occupied side adjacent to glass panels authorized by subdivision (d) of this section is no more than four feet or the minimum atrium area is twelve hundred square feet.
(d) Atrium enclosing walls shall be of at least two hour fire-resistant construction or of glass that is wired, laminated, or tempered and is provided with sprinklers on the occupied side spaced no more than six feet apart, except as otherwise permitted by subdivision (c) of this section.
§ 27-521.4. Fire protection equipment
(a) Smoke detectors. In all spaces opening onto an atrium, a smoke detecting system shall be installed in accordance with the requirements of reference standard RS 17-5E.
(b) Standpipes. At least one standpipe outlet in addition to a riser or risers within required stairways, shall be installed in every atrium.
(c) Sprinklers.
(1) Every story or mezzanine within an atrium that overhangs another story or mezzanine within fifty feet shall have the overhang sprinklered in accordance with section 27-956 of article four of subchapter seventeen of this chapter, except that atrium ceilings less than fifty feet above the atrium floor but more than thirty feet above the floor may alternatively be provided with smoke detectors, which shall be of the central supervisory type connected to an approved central station. Every room or space opening onto the atrium shall be sprinklered, no matter where located.
(2) Except as otherwise permitted by subdivision (c) of section 27-521.3 of this article, at glass panels permitted by subdivision (d) of such section, sprinklers on the occupied side at all levels shall be spaced six feet apart parallel to the glass and that distance away from the glass panels so as to insure complete glass wetting upon activation. No obstructions to such wetting capability shall be permitted.
(3) Every sprinkler system for an atrium shall be provided with sources of water supply in accordance with article four of subchapter seventeen of this chapter.
§ 27-521.5. Means of egress
(a) No vertical exits shall discharge into an atrium at any level.
(b) Atrium corridors shall have a width equal to or greater than one hundred fifty per cent of that required by either table 6-1 of subchapter six or table 8-1 of subchapter eight, as applicable.
(c) An unenclosed path of travel to a required exit shall be permitted, except that access to one of the required vertical exits shall be only through an enclosed passageway or corridor conforming to the requirements for exits of subchapter six.
§ 27-521.6. Fire alarm and communication system
An interior fire alarm and communication system shall be installed in accordance with the requirements of reference standard RS 17-3.
§ 27-521.7. Signs
Atriums shall be provided with all signs required by articles seven and nine of subchapter six of this chapter, regardless of the occupant load of the atrium.
§ 27-521.8. Smoke control
(a) In all atriums there shall be provided a system of mechanical ventilation of sufficient capacity to exhaust at least six air changes per hour of the combined volumes of the atrium and all spaces with an open connection to the atrium, or 1 cfm/sq. ft. from all such spaces, whichever is greater, using either dedicated fan equipment or the building ventilation system arranged to shut down automatically, with manual override capability. Make-up air shall be supplied at the lowest level of an atrium at a rate equal to seventy-five percent of exhaust.
(b) All atriums shall have a gravity ventilation system equipped with remote manual controls to remove smoke if the mechanical exhaust system fails.
(c) A ventilation system serving an atrium shall not be interconnected with any other system serving another space.
(d) Ventilation systems supplying occupied spaces shall not be interconnected with the general atrium supply.
§ 27-521.9. Emergency power
All atriums shall be provided with an emergency power system meeting the requirements of article eleven of subchapter six of this chapter.
§ 27-521.10. Applicability
This article shall apply to the construction, alteration and use of malls.