§ 27-521.12. Construction; general
(a) A mall may be constructed only in buildings in noncombustible construction groups 1-A, 1-B and 1-C.
(b) The minimum horizontal clear dimension at any level in a mall shall be twenty feet.
(c) Where different tenancies have openings to a mall the tenancies shall be separated in accordance with section 27-341 of article five of subchapter five of this chapter.
(d) All openings between a mall and other spaces shall be provided with a noncombustible draft curtain that shall extend downward a minimum of twenty-four inches below the lowest ceiling adjacent to such draft curtain or shall meet the requirements of clause three of subparagraph d of paragraph three of subdivision (h) of section 27-370 of article five of subchapter six of this chapter relating to show windows.
§ 27-521.13. Fire protection equipment
(a) Smoke detectors. Smoke detectors meeting the specifications of section 27-981 of article six of subchapter seventeen shall be located at the ceiling and adjacent to each return air intake.
(b) Standpipes. At least one standpipe outlet shall be installed in every mall.
(c) Sprinklers. An automatic wet sprinkler system shall be installed in every mall.
(1) All spaces with openings between such spaces and a mall shall be fully sprinklered in accordance with subchapter seventeen of this chapter and reference standard RS 17-2 regardless of floor area or occupancy classification.
§ 27-521.14. Egress
The exits for a mall shall be of sufficient capacity to accommodate the aggregate occupant load of the mall and all spaces opening onto the mall.
§ 27-521.15. Smoke control
(a) In all malls there shall be provided a system of mechanical ventilation of sufficient capacity to exhaust at least six air changes per hour of the combined volumes of the mall and all spaces with an open connection to the mall, or 1 cfm/sq. ft. from all such spaces, whichever is greater, using either dedicated fan equipment or the building ventilation system arranged to shut down automatically, with manual override capability. Make-up air shall be supplied at the lowest level of a mall at a rate equal to seventy-five per cent of exhaust.
(b) All malls shall have a gravity ventilation system equipped with remote manual controls to remove smoke if the mechanical exhaust system fails.
(c) A ventilation system serving a mall shall not be interconnected with any other system serving another space.
(d) Ventilation systems supplying occupied spaces shall not be interconnected with the general mall supply.
§ 27-521.16. Signs
Malls shall be provided with all signs required by articles seven and nine of subchapter six of this chapter, regardless of occupant load of the mall.
§ 27-522. Scope
The provisions of this subchapter shall control the design and construction of places of assembly as defined in subchapter two of this chapter. For specific classification of assembly occupancies, see article eight of subchapter three of this chapter. For place of assembly permit requirements, see section 27-525.1 of article two of this subchapter.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1990/023.
§ 27-523. Definitions
For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.
§ 27-524. Tents and air supported structures
Places of assembly enclosed by tents or air supported structures shall comply with the provisions of this subchapter regulating indoor places of assembly, and with the provisions of article nineteen of subchapter seven of this chapter.
§ 27-525. General
The provisions of this article shall apply to all places of assembly, in addition to the specific requirements of articles three through five of this subchapter for the several categories of places of assembly.
§ 27-525.1. Place of assembly permit
a. It shall be unlawful to use or occupy any building or premises or part thereof as a place of assembly unless and until a permit therefor shall have been issued by the department. The permit shall be for a term of one year.
b. The application for such permit and such permit shall be in a form prescribed by the commissioner.
c. The annual fee for a permit issued pursuant to this section shall be the amount provided for in paragraph seven of subdivision a of section 26-214 of the code. An application for such permit or renewal thereof shall be accompanied by the annual fee, except as otherwise provided in section 26-210 of the code.
d. The permit issued pursuant to this section shall be posted in a conspicuous place in the place of assembly which is covered by such permit.
e. In the case of a permittee that is an establishment that offers for sale food and/or beverages for on-premises consumption, but not including establishments operated by a not-for-profit corporation, and employs or uses the services of a security guard, as that term is defined in subdivision six of section eighty nine-f of the general business law, such permittee shall comply with the provisions of article 7-A of the general business law, shall obtain proof that such security guard is registered pursuant to article 7-A of the general business law, shall maintain such proof in a readily available location, in accordance with rules promulgated by the commissioner during all hours in which such place of assembly is open to the public, shall maintain a roster of all security guards working at any given time when such place of assembly is open to the public, and shall require each security guard to maintain on his or her person proof of registration at all times when on the premises.
f. For purposes of this section, there shall be a rebuttable presumption that a person employed or whose services are retained at a place of assembly whose job functions include (1) the monitoring or guarding of the entrance or exit of such place of assembly to manage ingress and egress to such place of assembly for security purposes during the hours of operation of such establishment and/or (2) protection of such place of assembly from disorderly or other unlawful conduct by such patrons is a security guard provided, however, that such rebuttable presumption shall not apply to the owner of such establishment as described in subdivision e of this section that has received a place of assembly permit.
g. Notwithstanding any provision of this chapter, only the permittee shall be liable for violations of this section that relate to a permittee's obligations regarding security guards.
h. In addition to employees of the department, employees of the police department and the department of consumer and worker protection shall have the authority to enforce the provisions of this section regarding security guards.
i. The enforcement agency shall report any violation of the provisions of this section relating to security guards to the state liquor authority if the permittee holds a license pursuant to the alcoholic beverage control law.
(Am. L.L. 2020/080, 8/28/2020, eff. 8/28/2020)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1990/023 and L.L. 2020/080.
§ 27-526. Location
No place of assembly shall be located within two hundred fifty feet of any occupancy containing explosive contents.
§ 27-527. Posted capacity
Signs shall be posted in all assembly spaces, indicating the number of persons who may legally occupy the space. Signs shall not be required where seating is fixed in place in accordance with an approved seating plan and no provision is made for standee spaces. Such signs, where required, shall read as follows:
OCCUPANCY BY MORE THAN________ PERSONS IS DANGEROUS AND UNLAWFUL Public Assembly License No. ______________________________________ (where applicable) Commissioner, Dept. of Buildings, City of New York
When a space is occupied for multiple purposes involving different occupant loads, the sign shall read as follows:
OCCUPANCY BY MORE THAN (number) PERSONS AS (type of occupancy) OR BY (number) PERSONS AS (type of occupancy) OR BY (number) PERSONS AS (type of occupancy) IS DANGEROUS AND UNLAWFUL Public Assembly License No. ______________________________________ (where applicable) Commissioner, Dept. of Buildings, City of New York
Signs shall be at least twelve inches wide and sixteen inches high. The lettering shall be red on a white background. The letters shall be at least one inch high and the numerals at least one and one-quarter inches high. Signs shall be framed under a transparent protective cover, and permanently mounted in a location that is conspicuously visible to a person entering the space. Signs shall be lighted by artificial illumination at all times during occupancy to maintain at least five foot candles on the surface of the sign.
§ 27-528. Approved seating plans
In every place of assembly providing seating, copies of approved seating plans and approved alternate seating plans shall be kept on the premises. The plans shall be readily available for inspection, and shall provide the following information:
(a) For assembly spaces:
(1) The location of each seat of each tier of seating, along with the number of occupants of each seating section.
(2) The location and number of standees for each standee area.
(3) The total number of occupants of each tier and of the assembly space.
(4) The location and classification of all exits.
(b) For safe areas:
(1) The furniture and equipment arrangement and location.
(2) The number of occupants to be accommodated.
(c) For stage areas:
(1) The maximum number of occupants, including audience seating on the stage.
(2) Any conditions limiting the use of the stage area.
(3) The location of all exits. These plans shall not be smaller in size than required for one-eighth inch scale plans.
§ 27-529. Enclosure and interior finish
Places of assembly shall be separated from adjoining occupancies by construction meeting the requirements of table 5-1 or table 5-2, whichever may apply. The interior finish of places of assembly shall meet the requirements of table 5-4.
§ 27-530. Means of egress
Places of assembly shall be provided with exit facilities meeting all of the requirements of this subchapter and all of the requirements of subchapter six of this chapter. A place of assembly located in a building classified in another occupancy group shall comply with the exit requirements of this subchapter, but may use the exit facilities of the building of which it is a part as a means of egress from the building.
§ 27-531. Seating in assembly spaces
All seating in assembly spaces shall conform to the following:
(a) Seating arrangements. Except as otherwise provided in this subchapter, all seating shall be arranged in rows to provide for orderly egress.
(1) CHAIR SEATING. Seating patterns employing individual chairs shall comply with the following:
a. Assembly spaces in which the net floor area, exclusive of stage area, is less than eight square feet per person shall be provided with chairs that are rigidly anchored to the construction or fixed in place by devices that prevent movement in any direction, except that not more than twelve movable chairs may be provided in a box or loge if such box or loge is separated from the main seating pattern by railings or other permanent construction and has an area of at least five square feet per chair.
b. In assembly spaces where the net floor area, exclusive of stage area, is between eight and twelve square feet per person, movable chairs may be used provided all chairs in a row between aisles are fastened or ganged together to preserve the integrity of the row. Not more than twelve chairs shall be used in any row between aisles.
c. In assembly spaces where net floor area, exclusive of stage area, is more than twelve square feet per person, individual movable chairs may be used. Not more than twelve chairs shall be used in any row between aisles.
d. All chairs placed on stepped platforms less than four feet wide shall be anchored or fixed in place.
e. The minimum distance between centerlines of chairs in the same row shall be nineteen inches.
f. The spacing between the back of one chair in any row and any part of the chair in the row behind it, including arm blocks, when the seat is in the lift-up position for automatic operation or in the horizontal position for nonlift-up or nonautomatic operation, when measured horizontally between plumb lines, shall be at least twelve inches, and this spacing shall be increased for any of the following reasons:
1. Where a difference in floor level occurs between any two rows, the spacing shall be increased as follows:
Difference in Level (in.) Increase in Space (in.) 6-10, plus any fraction of an inch 1 11-16, plus any fraction of an inch 2 17-22, plus any fraction of an inch 3 23 and over 4
2. Where it is necessary from any location to pass more than seven chairs to reach the nearest aisle, spacing shall be increased one-quarter of an inch for each chair in excess of seven.
g. Not more than eight chairs shall be provided in any row of seating having access to only one aisle except as provided below for bleacher and platform seating.
h. Performance viewing positions shall be provided for persons who use wheelchairs in accordance with the following schedule.
Capacity of Assembly Space Number of Viewing Positions 75 to 100 minimum 4 101 to 150 minimum 5 151 to 200 minimum 6 201 to 300 7 301 to 400 8 401 to 500 9 501 to 1,000 2 percent of total Over 1,000 20 plus 1 for each 100 over 1,000
These positions shall be located so as not to interfere with egress from any row of seats and shall be reachable by means of ramps and/or elevators. Steps shall not be allowed in line of travel from the main approach entry to the designated locations. Size and placement of wheelchair locations, surfaces, access to performing area and listening systems where required, shall comply with the provisions of reference standard RS 4-6. These positions may be utilized by persons who do not use wheelchairs provided that the positions are delineated on the approved seating plans, the seating is readily removable and the positions are unsold one full working day before the performance.
(2) BLEACHER SEATING. Fixed or folding bleachers shall comply with the following:
a. For the purpose of determining occupant load, individual seat space width shall be assumed to be eighteen inches. There shall be a space of at least fourteen and one-half inches between the back edge of each seat and the front edge of the seat immediately behind it when measured between plumb lines.
b. The width of footboards and seat boards shall be at least nine and one-half inches. Where wider seat boards are provided, the space between seats may be reduced by an amount equivalent to the increase in width.
c. Sections having not more than ten consecutive rows of seating shall not require aisles. Where there are more than ten consecutive rows, aisles shall be provided at the ends of seat rows, the minimum spacing between seat rows shall be increased to sixteen inches and the required space between seat rows shall be increased by one-quarter of an inch for each seat in excess of seven that it is necessary to pass to reach an aisle. Cross aisles shall be provided at the bottom of each section of seating.
d. Bleacher seating shall be constructed to comply with the requirements of subchapters nine and ten of this chapter.
(3) PLATFORM SEATING. Stepped platforms used for seating without chairs shall comply with the following:
a. For the purpose of determining occupant load, individual seat space width shall be assumed to be eighteen inches.
b. Platforms shall be at least twenty-eight inches deep from front to back.
c. Platform depth shall be increased one-quarter of an inch for each seat in excess of seven that it is necessary to pass to reach an aisle.
d. Aisles complying with section 27-532 of this article shall be provided when the height between levels of platform seating exceeds eight inches.
(4) BENCH SEATING. Bench or pew seating, with or without backs, may be used when complying with the applicable requirements for chair seating in of paragraph one of this subdivision. For the purpose of determining occupant load, individual seat space width shall be assumed to be eighteen inches.
(5) TABLE AND CHAIR SEATING. Tables and chairs shall be so arranged that the distance from any chair at any table by way of a path between tables and chairs is not greater than eighteen feet to an aisle leading to an exit. The width of the path shall be at least eighteen inches, except that it may be reduced by one inch for each one foot that the distance to the aisle is less than eighteen feet but may not be reduced to less than twelve inches. Chairs, when placed with the front edge of the seat on a line with the edge of the table, shall not protrude into the path. Booths containing up to eight seats may be used, provided they open directly on an aisle.
(6) COUNTER SEATING. Counters at which food or beverages are consumed shall be attached to the floor. Fixed or movable chairs or stools may be provided. The number of occupants shall be determined on the basis of one occupant for each eighteen inches of counter length. The width of aisles bordering counters shall be measured excluding a depth of eighteen inches for chair or stool spaces.
(7) STANDEE AREAS. Standee areas may be permitted within assembly spaces provided each standee space has a minimum width of twenty-two inches and a minimum depth of twenty-one inches. Standee areas shall not encroach on the required exit facilities and shall be separated from the space to be left clear for passage by tape, ribbon or other easily broken material, supported by lightweight posts fixed in stationary sockets, so constructed and placed as to not constitute an obstruction in case of panic or emergency.
(8) PROTECTIVE GUARDS. Protective guards shall be provided for seating and standee areas as follows:
a. A protective guard at least thirty inches high above the floor shall be provided along the fascia of all balconies, loges, and boxes, except that the guard shall be at least thirty-six inches high at the bottom of stepped aisles. When rails or other parts of such guards are designed with ledges more than two and one-half inches wide, the top surface of the ledges shall slope down toward the seating area at an angle of at least thirty degrees from the horizontal. The guards shall provide an unperforated curb or toeguard at least twelve inches high above the level of the floor of the balcony, loge, or box.
b. A protective guard at least thirty inches high above the floor shall be provided at cross aisles where fixed seat backs of any adjacent lower level do not project at least twenty-four inches above the cross aisle level.
c. A protective guard at least eighteen inches high above the floor shall be provided along the front edge of any stepped platform where fixed seat backs of the adjacent lower level do not project at least eighteen inches above the stepped platform level.
d. A protective guard at least twenty-six inches high above seat level shall be provided at the open ends of bleacher seating, extending from the front of the third row of seats to the back of the highest row of seats, and continuously along the rear of the seating, except where the seating is adjacent to a wall.
e. Guards shall be designed to meet the load requirements for railings in subchapter nine of this chapter.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058.
§ 27-532. Aisles and cross aisles
Assembly spaces shall be served by aisles, cross aisles, or other unobstructed floor areas providing access to exits, except as permitted for bleacher seating in paragraph two of subdivision (a) of section 27-531 of this article.
(a) The capacity of aisles and cross aisles shall be adequate to serve all persons for whom they provide a primary path of travel to an exit. (See section 27-533 of this article.)
(1) CAPACITY. The capacity of aisles and cross aisles shall be as listed in table 8-1. The unit of exit width shall be twenty-two inches. Seats or other facilities shall not project into an aisle or cross aisle so as to reduce the width of the aisle or cross aisle more than one inch per unit of exit width.
(2) MINIMUM WIDTH. Aisles and cross aisles shall have a minimum width of forty-four inches except that the width may be at least thirty-six inches under any one or more of the following conditions:
a. In any assembly space having a total of not more than three hundred occupants.
b. When not more than the number of persons permitted for one unit of exit width is served.
c. At the narrowest point when a tapered aisle is permitted under paragraph three of this subdivision.
d. When an aisle parallels and is alongside an enclosure wall or partition that is provided with exit doors spaced not more than sixteen feet on centers, provided such aisle serves only the rows of seats adjacent to it.
(3) TAPERED AISLES. Tapered aisles shall be used where egress is provided only at one end of the aisle, except that uniform aisles may be used when their width for the entire length will accommodate eighty per cent of the total occupant load served by the aisle. Tapered aisles shall be widened gradually so that their width at the point of discharge provides for the entire occupant load of the aisle.
(4) UNIFORM AISLES. Aisles of uniform width shall be used where egress is provided at both ends of an aisle by either cross aisles or exit doors. The width of uniform aisles shall not be less than required for sixty per cent of the total occupant load served by the aisles.
(5) AISLE WIDTH AT OPENINGS. When an aisle or cross aisle discharges directly into exit openings, a space shall be provided in front of such openings that is at least as wide as such openings and at least as deep as the width of the aisle or cross aisle.
(6) CROSS AISLES. Cross aisles, at any point shall not be closer than twelve feet to a stage area using scenery or scenic elements. Steppings shall not be permitted in cross aisles.
(7) AISLE GRADIENTS AND STEPPINGS. The floors of aisles shall have a gradient of not more than one in eight. Where differences in levels require a greater gradient, steps shall be used, complying with the following:
a. When one riser only is used between levels of platforms, its height shall not exceed eight inches, and where more than one riser is used, none shall exceed seven and three-quarter inches.
b. No riser shall be less than four inches high.
c. No riser shall vary from the height of the riser immediately above or below except that risers that are separated by a tread of seventeen inches or more may vary up to one-quarter inch.
d. The width of treads of intermediate steps between platform levels shall be at least nine and one-half inches, but not more than ten and one-half inches, exclusive of nosings.
e. Treads at the level of platforms and seventeen inches or more in width may slope not more than one-quarter inch in twelve inches.
f. No steps shall be used to enter a row of seats from an aisle unless an unobstructed floor space of at least seven square feet is provided at the level of the aisle, between the aisle and the steps.
g. Each step in an aisle shall be marked along its nosing with a permanent contrasting color stripe, and shall be provided with a step light.
h. The line of risers of aisle steppings shall deviate no more than twenty degrees from a line perpendicular to the centerline of the aisle.
(8) STEPPED AISLE LANDINGS. Stepped aisles shall be provided with landings at exit openings, and shall have a length equal to at least the width of the aisle and a slope of not more than one in twelve.
(9) LIGHTING. Aisles and cross aisles shall be provided at all times with at least one-half foot candle of artificial illumination by electrical means.
(10) VOMITORIES. Vomitories within assembly spaces shall comply with all of the requirements for aisles, and shall have a clear ceiling height of at least seven feet.
§ 27-533. Travel distance
At least one exit opening shall be available from every attached seat or standee space in an assembly space, or from the most remote point in the space when movable seats are provided or, when no seats are provided, within the primary travel distance limitation listed in table 8-1. In addition, an alternate exit opening shall be available from every attached seat or standee space, or from the most remote point when attached seats are not provided within the secondary travel distance limitation listed in table 8-1. Such alternate exit openings may serve to satisfy the requirements for primary travel distance for other seats or locations. Exit openings satisfying the primary and secondary travel distance requirements for any one seat or location shall be separated from each other by a distance of at least twenty-five feet.
(a) Travel distance shall be the measured distance along centerlines of paths of travel to the centerline of the exit opening, as adjusted by penalties for multi-directional or stepped travel as provided below.
(1) No path of travel shall be permitted through rows of seating other than the first leg of travel from a seat to an aisle.
(2) The first thirty-five feet of a primary path of travel and a secondary path of travel may be common to each other except that this distance may be increased to fifty feet in F-2 places of assembly.
(3) Not more than three changes in direction of travel shall be permitted in the path of travel to an exit opening. A change in direction shall be deemed to occur when it is necessary to change direction by a forty-five degrees or greater angle, measured from the preceding line of travel, except that it shall not be considered as a change in direction when it is necessary in an aisle or cross aisle to travel in another direction not more than seven feet.
(4) Travel distance shall be the sum of the distances of all segments of travel to the exit, computed as follows:
Segment Length First leg of travel Measured distance Second leg of travel after first change in direction Measured distance Third leg of travel after second change in direction 1.25 times measured distance Fourth leg of travel after third change in direction 1.40 times measured distance Any leg of travel with four or more steps 1.25 times length of segment as computed above
§ 27-534. Exit openings
Exit openings from assembly spaces shall comply with the following:
(a) Capacity. The capacity of exit openings shall be listed as in table 8-1, based on the number of occupants for whom the opening satisfies the primary travel distance requirement.
(b) Width. Exit openings shall be at least thirty-six inches wide for single doors and at least sixty-six inches but not more than eighty-eight inches wide for doors swinging in pairs, except that in assembly spaces having an occupant load of over three hundred persons, single door openings shall be at least forty-four inches wide.
(c) Classification. Exit openings from assembly spaces shall be classified as follows:
Class 1. Exit openings that are used for normal entry to the assembly space, and that open directly to a safe area or to an open exterior space.
Class 2. Exit openings that are not used for normal entry to the assembly space, and that open directly to a safe area or to an open exterior space.
Class 3. Exit openings that open from the assembly space into corridors, exit passageways, or vertical exits.
(d) Distribution of classes. The required exit capacity from F-2 places of assembly, and from all other assembly spaces in which the net floor area, exclusive of stage area, is twelve square feet or more per person may be provided by exit openings of any class. The required exit capacity from assembly spaces in which the net floor area, exclusive of stage area, is less than twelve square feet per person shall be distributed so that exit openings of each class are provided to comply with the following requirements:
1. For assembly spaces in which the mean floor level is not more than fifteen feet above or below the adjoining grade elevation, the exit capacity shall be distributed as follows:
Class 1 – not less than forty per cent
Class 2 – not more than sixty per cent
Class 3 – not more than forty per cent
2. For assembly spaces in which the mean floor level is more than fifteen feet, but not more than thirty feet, above or below the adjoining grade elevation, the exit capacity shall be distributed as follows:
Class 1 – not less than sixty per cent
Class 3 – not more than forty per cent
3. For assembly spaces in which the mean floor level is more than thirty feet above or below the adjoining grade elevation, the exit capacity shall be distributed as follows:
Class 1 – not less than one hundred per cent
(e) Location. No exit opening shall be closer than twelve feet to any part of a stage using scenery or scenic elements. All exit openings shall be clearly identifiable and shall not be disguised as part of a wall or covered in any way to obscure them from view. Where, because of the configuration of the assembly space enclosure an exit opening is not visible from all seats using it as a means of egress, directional exit signs shall be placed on the enclosure alongside the exit opening to indicate its location. These signs shall be in addition to those required over the exit opening.
(f) Locking. No exit door shall be locked so as to prevent egress from an assembly space while it is occupied.
§ 27-535. Safe areas
Safe areas shall comply with the following: When provided to serve class one or class two exit openings safe areas shall be separated from assembly spaces by noncombustible construction having a two hour fire-resistance rating, and shall serve as transition areas in the line and direction of exit travel. They shall serve for normal entry to the assembly space and may be used as corridors, lobbies, or lounges. No room or space classified in occupancy group A, B1, D-1, or D-2 shall open upon a safe area. Safe areas shall be at a level not more than six feet above or below the level at which egress is made from the assembly space, except that a separate safe area shall not be required for any assembly space having an occupant load of less than one hundred fifty persons and which is served by a safe area of another assembly space, when such safe area is in the direction of egress. Ventilating systems for safe areas shall not be connected to systems serving any other spaces, unless separated from such systems by fire dampers actuated by smoke detectors meeting the construction requirements of subchapter thirteen of this chapter.
(1) COLLECTING SAFE AREAS. Places of assembly having more than one assembly space may have a collecting safe area that receives the occupant load discharged into it by other safe areas. Collecting safe areas shall be located within six feet above or below the assembly space nearest to grade.
(2) OCCUPANT LOAD. The occupant load of a safe area shall be the aggregate occupant load of all exit openings discharging directly into it. The occupant load of a collecting safe area shall be the aggregate occupant load of all exit openings discharging directly into it, plus fifty per cent of the occupant load of other safe areas discharging into it.
(3) DIMENSIONS. Except as provided in subdivision four of this section, the clear unobstructed floor area of each safe area shall be sufficient to accommodate the total occupant load of the safe area on the basis of two square feet per person, not including space occupied by furniture or equipment. The minimum dimension of such unobstructed space shall be eight feet. The width of the unobstructed space shall be measured at right angles to the direction of travel to an exit and shall not be less than required for the occupant load, on the basis of the exit capacity listed in table 8-1. The height of safe areas shall be at least eight feet at all points.
(4) SAFE AREAS NEAR GRADE. When a safe area provides egress to an open exterior space, either directly or through a vestibule, the safe area need not provide the floor area required by subdivision three of this section when the level of discharge from the safe area to the open exterior space is not more than four feet above or below the grade of the open exterior space.
(5) RAMPS AND STEPS. Ramps in safe areas shall have a gradient of not more than one in twelve, except that when not exceeding six feet in length, the gradient may be not greater than one in ten. Steps in safe areas shall comply with the following requirements:
a. No riser shall be less than six inches nor more than seven and one-half inches high.
b. No riser shall vary in height from the riser immediately above or below it.
c. Treads in flights of steps shall be at least ten and one-half inches wide exclusive of nosing, and, except as provided in paragraph d of this subdivision, the sum of two risers plus the width of one tread shall be at least twenty-four inches but not more than twenty-five and one-half inches.
d. No change in levels shall have less than three risers, except that where the intervening tread is between twenty-eight inches and thirty-six inches, two risers may be used when the edge of each tread is marked by a contrasting color stripe.
e. Where exit openings from an assembly space are above or below the level of the safe area, a platform shall be provided at the same level as that of the exit opening. The platform shall be at least one foot wider on each side than the exit opening, and shall extend a minimum of six feet in the direction of exit travel. The sides of such platforms, and of steps or ramps leading from them, shall be protected by guards at least three feet high.
(6) EXITS FROM SAFE AREAS. The capacity of exits from safe areas shall be as listed in table 8-1. Exit openings from safe areas shall discharge into exit types as provided in subchapter six of this chapter.
(7) DOOR HARDWARE. Doors from safe areas or from exits from safe areas opening directly to the outdoors and furnished with locks shall be equipped with fire exit bolts complying with the requirements of paragraph two of subdivision (k) of section 27-371 of subchapter six of this chapter.
§ 27-536. Corridors
Corridors shall comply with all of the requirements of subchapter six of this chapter, except as modified below:
(a) Capacity. The capacity of corridors shall be as listed in table 8-1.
(b) Changes in level. Changes in level requiring less than three risers in a corridor shall be by a ramp having a slope not greater than one in ten.
§ 27-537. Exit passageways
Exit passageways shall comply with all of the requirements of subchapter six of this chapter, except as modified below:
(a) Capacity. The capacity of exit passageways shall be as listed in table 8-1.
(b) Changes in level. Changes in level requiring less than three risers in an exit passageway shall be by a ramp having a slope not greater than one in ten.
§ 27-538. Vertical exits
Stairs, escalators and ramps shall comply with all of the requirements of subchapter six of this chapter, except as modified below:
(a) Capacity. The capacity of stairs, escalators or ramps shall be as listed in table 8-1.
(b) Width. The minimum width of stairs shall be at least forty-four inches, except that where the total occupant load is not more than permitted for one unit of exit width, the minimum width may be thirty-six inches.
(c) Unenclosed vertical exits. Vertical exits leading directly from one safe area to another, or leading from a safe area directly to an open exterior space, need not be enclosed.
(d) Ramp slope. Ramps serving as vertical exits shall not have a slope greater than one in ten.
§ 27-539. Open exterior spaces
(a) Capacity. Open exterior spaces shall be adequate in width and area to accommodate the accumulated occupant load of all exits discharging into them on the basis of two square feet per person.
(b) Minimum dimensions. The minimum dimensions of open exterior spaces shall be twenty feet, except that when the principal entrance to the place of assembly is from an open exterior space, the minimum dimension of this space shall be thirty feet. No open exterior space shall have less than four hundred square feet of floor area, and floor area shall be measured exclusive of the following:
1. The area immediately outside any exit door from the place of assembly for a distance perpendicular to the exit doors of ten feet for the full width of the exit opening.
2. The area of steps, platforms, stairs, or ramps within or leading to or from the space.
3. The area of obstructions such as shrubs, trees, fixed furniture, signs, sculptures, pools, and similar obstructions to occupancy or exit travel.
(c) Above or below grade. When an open exterior space is more than fifteen feet above or below the grade of the street or public space to which it discharges, its required area shall be increased by one-third.
(d) Egress from open exterior spaces. Exterior exit passageways, ramps, or steps leading from open exterior spaces shall be not less in width than required for the occupant load of all exits discharging into the open exterior space. The width of such exit passageways shall be based on the capacities listed in table 8-1, but in no case less than ten feet. Ramps and steps shall comply with the requirements of paragraph e of subdivision five of section 27-535 of this article.
§ 27-540. Exit lighting
In addition to the requirements of subchapter six of this chapter, lighting shall be provided in the following areas:
(a) Safe areas. Safe areas shall be artificially lighted by electrical means at all times during occupancy of a place of assembly so as to provide illumination of at least five foot candles at the level of the floor and on the surface of all stairs, steps, ramps, and escalators within the safe area.
(b) Open exterior spaces. Yards or courts which serve as open exterior spaces shall be artificially lighted by electrical means at all times between sunset and sunrise during occupancy of a place of assembly so as to provide illumination of at least five foot candles at the level of the floor over at least the required area.
§ 27-541. Exit signs
Signs meeting the requirements of subchapter six of this chapter and subdivision (e) of section 27-534 of this article shall be provided in all assembly spaces to indicate the location of exits and, where necessary, the direction to the exits. All exit or directional signs shall be placed so that they are clearly visible from all parts of the assembly spaces, and the bottom of all signs shall be at least seven feet above floor level. Signs shall be of the internally lighted type in all assembly spaces where the general illumination is reduced to less than five foot candles during a performance or during occupancy. Signs shall be lighted at all times during occupancy.
TABLE 8-1 Determination of Exit and Access Requirements
Occupancy Group Classification Maximum Travel Distance Within Assembly Space (ft.) a Capacity (number of persons per unit of width) Ramps Corridors, Safe Areas, Exit Passageways Primary Secondary Aisle and Cross Aisle e Doors or Openings Stairs and Escalators From Assembly Space From Safe Area F-1a b 85 125 80 50 100 60 80 F-1b c 100 125 90 80 125 80 100 F-2 175 250 400 400 500 320 425 F-3 100 d 125 d 90 80 125 80 100 F-4 85 d 125 d 80 50 100 60 80
Notes for Table 8-1:
a See section 27-533. When an exit opening from an assembly space discharges into corridor that does not meet the requirements of this code for a safe area, the travel distance shall include the distance within the corridor to an exit.
b See paragraph four of subdivision (b) of section 27-546 for stages.
c See paragraph three of subdivision (b) of section 27-547 for stages.
d In places of assembly completely equipped with automatic sprinklers, this distance may be increased fifty percent.
e See section 27-532.
§ 27-542. Emergency lighting
All assembly spaces shall be provided with emergency lighting facilities sufficient to provide at least five foot candles of illumination at the floor level. Such lighting shall be on circuits that are separate from the general lighting and power circuits, either taken off ahead of the main switch or connected to a separate emergency lighting power source, and be arranged to operate automatically in the event of failure of the normal lighting system. The provisions of this section shall apply retroactively to all existing places of assembly that are or would be classified in occupancy groups F-3 and F-4 or are changed to such classification under this code, in accordance with the following schedule and specifications:
1. Cabarets, dance halls, night clubs, and taverns having an occupant load exceeding one hundred fifty persons shall complete the installation required by this section on or before April twelfth, nineteen hundred seventy-nine.
2. Cabarets, dance halls, night clubs, and taverns having an occupant load of one hundred fifty persons or less shall complete such installation on or before July twelfth, nineteen hundred seventy-nine.
3. Spaces occupied exclusively as restaurants shall complete such installation on or before October twelfth, nineteen hundred seventy-nine.
4. All other spaces in occupancy groups F-3 and F-4 shall complete such installation on or before January twelfth, nineteen hundred eighty.
5. The wiring shall conform with the electrical code of the city of New York, and have the same protection as specified for wiring in reference standard RS17-3, RS17-3A or 17-3B.
6. Storage battery equipment may be used as the sole source of energy provided it conforms with the provisions of section four of reference standard RS 17-3 or consists of two battery packs listed by an acceptable testing laboratory or conforms with nationally accepted standards for such source of emergency energy.
§ 27-543. Light projection sources
Motion picture projection and other light projection sources shall comply with the following:
(a) Film. The projection, use or storage of film having a nitrocellulose base (commonly known as nitrate film) shall not be permitted except under conditions specified in special permits when issued by the fire department. Safety film meeting the specifications and test standards of reference standard RS 8-1 may be projected, used or stored.
(b) Projection machines. Projection machines shall meet the requirements of the electrical code of the city of New York. The lamp housing of projection machines using carbon-arc or other light sources that emit gaseous discharge shall be equipped with, or connected to a mechanical ventilation system of adequate capacity to exhaust the products of combustion through ducts directly to the outdoors. Such duct systems shall comply with the requirements of subchapter thirteen of this chapter. When more than one projection machine or other facility employing a carbon-arc or similar light source is used, all may be vented by the same duct system if the capacity is adequate for all facilities so connected.
(c) Other light source facilities. All devices, such as spotlights, that employ a carbon-arc or other light source that emits gaseous discharge shall be vented directly as required in subdivision (b) of this section, unless the space in which such devices are located is mechanically ventilated and provides at least two thousand cubic feet of room volume for each device.
(d) Light or projection rooms or booths. When enclosed, rooms or booths used for the projection of motion picture film or the manipulating of lights shall be built of noncombustible materials, and shall provide a clear working space of at least two feet around the projection apparatus. Such rooms or booths shall be provided with vents opening to a mechanically ventilated area or the outdoors, adequate in size to supply the make-up air required. The rooms or booths shall be provided with at least one noncombustible or metal clad door at least two feet by six feet opening in the direction of exit travel, and no point within the room, booth, or gallery shall be more than fifty feet from a door opening into a corridor or space that provides access to an exit at a distance not greater than seventy-five feet.
§ 27-544. Motion picture screens
Motion picture screens shall be noncombustible, or have a flame spread rating not over twenty-five, or be of materials that have been rendered flameproof in accordance with the provisions of chapter four of this title. The construction supporting screens shall be noncombustible, and shall comply with the stage rigging requirements of subchapter nine and with the provisions of subchapter ten of this chapter.
§ 27-545. General
The provisions of this section shall apply to all places of assembly classified in occupancy group F-1 under the provisions of subchapter three of this chapter.
§ 27-546. F-1a places of assembly
F-1a places of assembly shall comply with all of the requirements of article two of subchapter eight of this chapter, and with the following:
(a) Construction in seating areas.
(1) Scenery or scenic elements may be placed in seating sections of F1a assembly spaces if such elements:
a. Are noncombustible, or of materials that have been rendered flameproof in accordance with the provisions of chapter four of this title, or have a flame spread rating of twenty-five or less.
b. Are adequately braced or secured.
c. Do not obstruct the required visibility of, or paths of travel to, exit openings.
(2) Platforms or runways for performances, to accommodate the operation of cameras, electronic equipment, or motion picture projection machines not using carbon-arc or other light source that emits a gaseous discharge may be constructed in seating sections, provided such platforms or runways comply with the requirements of paragraph one of subdivision (a) of this section.
(b) Stage requirements.
(1) DEFINITION. For the purposes of this section the stage in an F-1a place of assembly shall include the performing area and all other nonaudience areas that are used in the presentation of a performance and that are open to the performing area. The performing area shall be that area between the outer edge of the stage apron and the furthermost up-stage acting boundary, the width being the maximum stage opening to the audience.
(2) STAGE FLOOR CONSTRUCTION. The floor construction of stages shall provide fire-resistance ratings complying with the requirements of section 27-240 of article two of subchapter three of this chapter and table 3-4 except as follows:
a. Any portion of the stage floor used for passing scenery and scenic elements to a lower level may consist of heavy timber construction supporting tight fitting traps of at least three inch nominal solid wood or of equivalent materials in terms of fire-resistance, strength, and stiffness properties.
b. Stage lifts shall comply with the provisions of subchapter eighteen of this chapter. Any portion of the stage floor that is equipped with stage lifts shall be of noncombustible construction. Joints between lift platforms and adjacent floors shall be tightly fitted.
c. Finish flooring shall comply with the provisions of section 27-351 of article five of subchapter five of this chapter.
(3) AREAS BELOW THE STAGE. When the stage floor is equipped with traps or stage lifts, the room or space below the stage into which the traps or lifts open shall be completely enclosed by construction having at least the fire-resistance rating required for the stage floor, and such room or space shall not be used as a workshop or storage area. Storage shall not be deemed to include the location in this area of scenery or scenic elements used during a performance. However, no combustible material that has a flamespread rating greater than twenty-five or that has not been rendered flameproof in accordance with chapter four of this title may be stored in this location at any time. Under-stage areas shall comply with the requirements of paragraph eleven of this subdivision.
(4) EXITS FROM THE STAGE. At least two exits, remote from each other, shall be available from every point on a stage, each within a travel distance limitation of one hundred twenty-five feet. The occupant load of the stage shall be based upon one person per fifteen square feet for the performing area and on one person per fifty square feet for the remaining area. When any portion of a stage is used for audience seating at any time, exits of adequate capacity shall be provided for that portion, within the travel distance limitations for assembly space seating. Exit openings serving a stage directly shall have a capacity of seventy-five persons per unit of exit width.
(5) SCENERY AND SCENIC ELEMENTS. All scenery or scenic elements shall be of noncombustible materials, or of materials having a flame-spread rating not exceeding twenty-five, or of materials that have been rendered flameproof in compliance with the provisions of chapter four of this title. Scenery and scenic elements not complying with the above requirements may be used only when expressly permitted by the fire department.
(6) RIGGING LOFTS, FLY GALLERIES, AND GRIDIRONS. Girders, beams, or slats of galleries or gridirons over the stage floor or in the rigging loft need not be fire protected but shall be of noncombustible materials designed in accordance with the provisions of subchapters nine and ten of this chapter.
(7) AUTOMATIC SPRINKLER PROTECTION. Stages in F-1a places of assembly shall be provided with automatic sprinkler protection complying with the construction provisions of subchapter seventeen of this chapter, as follows:
a. Automatic sprinklers shall be placed above all rigging lofts; and above all stage areas, other than those portions of stage areas specifically designated on approved plans as performing areas which do not have rigging lofts above and that are not at any time used for storage purposes. Sprinklers above rigging lofts shall be located so that no gridiron or other obstruction intervenes between the sprinkler heads and the scenery or scenic elements.
b. When any part of a stage is sprinklered in accordance with the provisions of subparagraph a of this paragraph, or when rigging lofts are provided, such stage areas and rigging lofts shall be completely separated from audience areas by a deluge sprinkler system designed to form a vertical water curtain, with heads spaced to provide a water density of at least three gpm per linear foot. The water curtain system shall be controlled by a deluge valve actuated by a "rate of rise system" and " fixed temperature system." The heat actuating devices shall be located on not more than ten foot centers around the perimeter of the sprinklered area or as otherwise required for the type of device used to assure operation of the system. In addition to the automatic controls, manual operating devices shall be located at the emergency control station as required by paragraph ten of this subdivision, and adjacent to at least one exit from the stage. Such exit shall be remote from the emergency control panel.
c. When openings are provided in the stage floor for stage lifts, trap doors or stairs, sprinklers spaced five feet on centers shall be provided around the opening at the ceiling below the stage, and baffles at least twelve inches in depth shall be installed around the perimeter of the opening.
d. All valves controlling sprinkler supplies shall be provided with tamper switches wired to an annunciator panel located at the emergency control panel.
e. The operation of any section of the sprinkler system and the deluge system shall activate the emergency ventilating equipment required in paragraph eight of this subdivision.
f. The water flow alarm, tamper switches and deluge system equipment shall be provided with central station supervision in addition to the required local alarm.
g. Existing premises shall be required to conform with this requirement on or before January twelfth, nineteen hundred eighty. However, existing sprinkler systems which have been previously accepted by the department or by the fire department shall be deemed in compliance with this requirement.
(8) EMERGENCY VENTILATION. Emergency ventilation shall be provided for all stages in F-1a places of assembly to provide a means of removing smoke and combustion gases to the outdoors in the event of a fire, as follows:
a. A mechanical exhaust system shall be provided of sufficient capacity to exhaust an amount of air at least equal to the sum of the following:
(1) two cfm per square foot of the performing area.
(2) four cfm per square foot of that portion of stage area that is not designated as performing area.
(3) four cfm per square foot of rigging loft area.
b. The exhaust system shall be designated to be activated both manually and automatically, manual operation shall be by means of a manually operated switch located at the emergency control panel as required by paragraph ten of this subdivision and adjacent to at least one exit from the stage. Such exit shall be remote from the emergency control panel. Automatic activation shall be by means of the sensing devices that start the operation of the sprinklers. Exhaust air openings of ducts shall be located so as to provide the most effective removal of smoke and combustion gases.
c. The exhaust system shall be provided with an automatic emergency by-pass damper in the exhaust duct on the suction side of the fan. Such damper shall close to the fan in the event of a power failure to the fan motor and shall open directly to the outdoors if the fan is located outside the building, or shall open to a duct leading directly to the outdoors if the fan is located inside the building. When located inside the building, the fan shall be insulated with a minimum of one inch magnesia block or the equivalent in insulating and fire-resistive qualities. Exhaust fans shall have drive and bearings located outside of the fan impeller housing. The exhaust system shall not be connected to exhaust openings in any space other than the stage and rigging loft, and shall be constructed to comply with the provisions of subchapter thirteen of this chapter switches shall be clearly labelled "emergency stage ventilation" and shall be painted red.
d. The emergency ventilation system shall be connected to both the normal and emergency light and power circuits.
(9) CURTAINS. No curtain shall be located between the audience area and the stage unless it is designated to permit the air movement required for emergency ventilation in paragraph eight of this subdivision to bypass or pass through the curtain without excessive billowing, and be made of noncombustible fabrics, as specified in the appendix of reference standard RS 7-3.
(10) EMERGENCY CONTROL PANEL. An emergency control panel shall be provided, as follows:
a. It shall be located on or adjoining the stage, except that where the stage is surrounded by seating, it shall be located so as to permit a view of the audience and stage areas. It shall be manned in accordance with the requirements of the fire department at all times during the presentation of a performance to an audience.
b. It shall be equipped with tell-tale lights to indicate when feeders and sub-feeders of emergency light and power circuits are in operation in assembly spaces and all exits, including safe areas.
c. It shall, when a deluge type sprinkler system is provided, be equipped with manual operating devices to activate the sprinkler system. It shall also be provided with a signal system to show when any portion of the sprinkler system has been deactivated.
d. It shall be provided with switches to provide for operation of the emergency ventilating system. Controls for the ventilating system shall be electrically supervised. The supervisory circuit shall be provided with a trouble bell and light, both of which shall be activated in the event of a failure in the ventilation system. A silencing switch may be provided, and where provided, shall have either an automatic reset or shall ring again when the trouble is corrected.
e. It shall be equipped with a public address system serving loudspeakers in the assembly space. The public address system shall be connected to both the normal and emergency light and power circuits.
f. It shall be equipped with an alarm system and intercom connected to the manager's office, the dressing rooms, and to a supervisory central fire station.
(11) AUXILIARY STAGE SPACES. Auxiliary stage spaces such as understage areas, dressing rooms, green rooms, storage rooms, work shops, and similar spaces associated with the use of the stage shall comply with the following:
a. No point within any auxiliary stage space shall be more than fifty feet from a door providing access to an exit.
b. There shall be at least two exits available from every auxiliary space, one of which shall be available within a travel distance of seventy-five feet. A common path of travel of twenty feet to the two exits shall be permitted.
c. The occupant load of dressing rooms shall be based on one person per fifty square feet of area.
d. Auxiliary stage spaces shall be equipped with automatic sprinklers when required by the provisions of subchapter seventeen of this chapter.
e. No workshop involving the use of combustible or inflammable paint, liquids, or gases or their storage shall open directly upon a stage.
f. The interior finish of auxiliary stage spaces shall comply with the requirements of table 5-4.
(12) STAGE LIGHTING. No stage lights shall be placed so that they will develop temperatures on the surface of any material that will cause that material to ignite, or smoke, or cause its flameproofing to deteriorate.
§ 27-547. F-1b places of assembly
F-1b places of assembly shall comply with all of the requirements of article two of this subchapter, and with the following:
(a) Certificate of occupancy. The certificate of occupancy for F-1b places of assembly shall specifically note the prohibition against the use or placement of scenery or scenic elements on or above the stage.
(b) Stage requirements.
(1) DEFINITION. For the purposes of this section, the stage in an F-1b place of assembly shall be the area where the principal activity viewed by the audience takes place.
(2) CONSTRUCTION. Raised platforms may be built as stages in F-1b places of assembly when they are supported on floors having the fire-resistance ratings required by table 3-4, in accordance with the following:
a. The area below the platform shall be enclosed on all sides with solid construction.
b. The horizontal area of stage construction shall not exceed the following: Wood frame: maximum area-four hundred square feet. Fire retardant treated wood: maximum area-twelve hundred square feet. Noncombustible frame: maximum area – unlimited.
c. The floor of the stage, when wood is used, shall be at least one inch nominal thickness, and shall be laid on a solid, noncombustible backing, or all spaces between supporting members shall be fire-stopped with noncombustible material.
d. In all F-lb places of assembly providing live entertainment, at anytime, the stage, dressing rooms and property rooms shall be provided with automatic sprinkler and fire alarm protection in conformance with the provisions of subchapter seventeen of this chapter. Existing premises shall be required to conform with this requirement on or before January twelfth, nineteen hundred eighty. However, existing sprinkler systems which have been previously accepted by the department or by the fire department shall be deemed in compliance with this requirement.
(3) EXITS FROM THE STAGE. At least two exits, remote from each other, shall be available from every point on a stage, each within a travel distance limitation of one hundred fifty feet The occupant load of the stage shall be based upon one person per twenty-five square feet of area. When any portion of a stage is used for audience seating at any time, exits of adequate capacity shall be provided for that portion, within the travel distance limitations for assembly space seating. Exit openings serving a stage directly shall have a capacity of one hundred persons per unit of exit width.
(4) EMERGENCY CONTROL PANEL. In F-1b places of assembly having an occupant load over six hundred persons, an emergency control panel shall be provided, as follows:
a. It shall be located so as to have a view of the audience and stage areas, and shall be manned during the presentation of a performance to an audience, by a competent person instructed in its use.
b. It shall be equipped with tell-tale lights to indicate when feeders and sub-feeders of emergency light and power circuits are in operation in assembly spaces and all exits, including safe areas.
c. It shall be equipped with a public address system serving loudspeakers in the assembly space. The public address system shall be connected to both the normal and emergency light and power circuits.
§ 27-548. General
The provisions of this section shall apply to all places of assembly classified in occupancy group F-2 under the provisions of subchapter three. F-2 places of assembly shall comply with all of the requirements of article two of this subchapter, and with the following:
(a) Enclosure. To qualify as an F-2 outdoor place of assembly, a place of assembly shall have at least forty per cent of the combined surface area of all exterior wall and roof planes open to the outdoors. When a portion of an outdoor place of assembly is enclosed to a greater extent, that portion shall comply with all of the requirements of this code applicable to indoor places of assembly.
(b) Grandstands. Grandstands shall comply with the following:
(1) CONSTRUCTION. Grandstands shall be designed in accordance with the requirements of subchapters nine and ten of this chapter.
(2) HEIGHT AND AREA. Grandstands, when built entirely of noncombustible materials, may be of unlimited height and area, and when built of combustible materials, shall be subject to the following limitations:
a. No section of seating shall exceed twenty feet in height, or exceed ten thousand square feet in area.
b. When more than one section of seating is provided, and the separation between them is less than fifty feet, each section shall be separated from the other by construction having a fire-resistance rating of at least two hours and rising to a height of at least two feet six inches above the levels of seating at each row.
c. No outdoor grandstand of combustible materials shall be erected within less than two-thirds of its height, but in no case less than ten feet, of a building or an interior lot line unless separated therefrom by noncombustible construction having a one hour fire-resistance rating.
(3) SPACES UNDER SEATS. Spaces under grandstand seats shall be kept free of all combustible materials and shall not be occupied or used for other than egress, unless such spaces are completely enclosed by noncombustible construction having a two hour fire-resistance rating.
(4) PARKING. Motor vehicle parking spaces shall not be closer than twenty feet to any grandstand unless separated therefrom by noncombustible construction having a one hour fire-resistance rating.
(c) Stage requirements.
(1) DEFINITION. For the purposes of this section the stage in an F-2 place of assembly shall be the area where the principal activity viewed by the audience takes place.
(2) CONSTRUCTION. The horizontal area of stage construction shall not exceed the following: Wood frame: maximum area-five thousand square feet. Fire retardant treated wood: maximum area-ten thousand square feet. Noncombustible frame: maximum area – unlimited.
(3) EXITS FROM THE STAGE. At least two exits, remote from each other, shall be available from every point on a stage, each within a travel distance limitation of three hundred feet. The occupant load of the stage shall be based upon one person per fifty square feet of area. When any portion of a stage is used for audience seating at any time, exits of adequate capacity shall be provided for that portion, within the travel distance limitations for assembly space seating. Exit openings serving a stage directly shall have a capacity of four hundred persons per unit of exit width.
(4) EMERGENCY CONTROL PANEL. In F-2 places of assembly having an occupant load over one thousand persons, an emergency control panel shall be provided as follows:
a. It shall be located so as to have a view of the audience and stage areas, and shall be readily accessible at all times during the presentation of a performance to an audience, to a competent person instructed in its use.
b. It shall be equipped with tell-tale lights to indicate when feeders and sub-feeders of emergency light and power circuits are in operation in assembly spaces and all exits.
c. It shall be equipped with a public address system serving loudspeakers in the assembly space. The public address system shall be connected to both the normal and emergency light and power circuits.
(d) Drive-in theaters. Drive-in theaters shall comply with the following:
(1) Projection booths and projection machines shall comply with the requirements of section 27-543 of article two of this subchapter. Motor vehicle parking spaces shall not be closer than twenty feet to any projection booth or machine.
(2) Projection screens and supporting structures shall comply with the requirements of section 27-544 of article two of this subchapter and shall be designed in accordance with the requirements of subchapters nine and ten of this chapter as applied to signs. Motor vehicle parking spaces shall not be closer than twenty feet to any projection screen.
(e) Amusement parks. Buildings and structures within amusement parks shall be constructed to conform with all of the requirements of this code governing the specific use and occupancy. Amusement devices shall not be placed in operation until they have been made to comply with the provisions of subchapter eighteen of this chapter.
§ 27-549. General
The provisions of this section shall apply to all places of assembly classified in occupancy group F-3 or F-4 under the provisions of subchapter three of this chapter. F-3 or F-4 places of assembly shall comply with all the requirements of article two of this subchapter and the following:
(a) Stage requirements.
(1) With scenery and scenic elements. Where an F-3 or F-4 place of assembly provides a stage using scenery and scenic elements, the space shall comply with all of the requirements of this code applicable to F1a places of assembly.
(2) Without scenery and scenic elements. Where an F-3 or F-4 place of assembly provides a stage not using scenery or scenic elements, the space shall comply with all of the requirements of this code applicable to F-1b places of assembly.
(3) Cabarets. In all F-4 places of assembly used as a cabaret, the stage dressing rooms and property rooms shall be provided with automatic sprinkler and fire alarm protection in compliance with the provisions of subchapter seventeen of this chapter. Existing premises shall be required to conform with this requirement on or before January twelfth, nineteen hundred eighty.
(b) Retroactive provisions. On or before January twelfth, nineteen hundred eighty, all places of assembly providing entertainment or used as a cabaret within F-3 or F-4 occupancies shall be provided with automatic sprinkler and fire alarm protection to comply with the provisions of subchapter seventeen of this chapter.
§ 27-550. Scope
Buildings and parts thereof, shall be capable of resisting all levels actually imposed thereon without exceeding the allowable stresses prescribed in subchapters ten and eleven of this chapter. In no cases shall the assumed loads be less than the minimum values described herein. In addition, within special flood hazard areas, and below the regulatory flood datum, as described in article ten of subchapter four of this chapter, applicable load requirements of reference standard RS 4-5 shall be applied.
§ 27-551. Standards
The provisions of reference standard RS-9 shall be a part of this subchapter.
§ 27-552. Definitions
For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.
§ 27-553. Construction materials and assembled elements of construction
Except as provided in section 27-555 of this article, the dead load shall be the actual weight of the building materials or construction assemblies to be supported, computed from the unit weights given in reference standard RS 9-1. Where unit weights are not established in reference standard RS 9-1, the actual weights may be determined by analysis or from data in manufacturers' drawings or catalogs. Unit weights less than those given in reference standard RS 9-1 may be used only with approval of the commissioner.
§ 27-554. Service equipment
Provision shall be made for the weights of all building service equipment including plumbing stacks, piping, heating and air conditioning equipment, electrical equipment, elevators, elevator machinery, flues, and similar fixed equipment. The weights of such equipment (or the allowances therefor) shall be included in the dead load. The weight of equipment that is part of the occupancy of a given area shall be considered as live load. See also paragraph two of subdivision (b) and subdivision (d) of section 27-557 of article three of this subchapter.
§ 27-555. Partition loads
Weights of all partitions shall be considered, using either actual weights at locations shown on the plans or the equivalent uniform load given in subdivision (b) of this section.
(a) Actual loads. Where actual partition weights are used, the uniform design live load may be omitted from the strip of floor area under each partition.
(b) Equivalent uniform load. The equivalent uniform partition loads in reference standard RS 9-1 may be used in lieu of actual partition weights except for bearing partitions or partitions in toilet room areas (other than in one- and two-family dwellings), at stairs and elevators, and similar areas where partitions are concentrated. In such cases, actual partition weights shall be used in design. Except as otherwise exempted, equivalent uniform loads shall be used in areas where partitions are not definitely located on the plans, or in areas where partitions are subject to rearrangement or location.
§ 27-556. General
In addition to the applicable dead, wind, and other loads, the building shall be designed for uniform live loads, for concentrated live loads, or for concurrent combinations of uniform and concentrated live loads, whichever produce the greatest stress.
§ 27-557. Floor live loads
(a) Uniformly distributed live loads. The minimum design values established in reference standard RS 9-2 for various occupancies or uses shall be used subject to the provisions of subdivision (d) of this section. Where the occupancy or use of a space does not conform to any of those listed, the design load shall be determined by the architect or engineer subject to approval by the commissioner.
(b) Concentrated live loads.
(1) The building framing shall be capable of supporting the concentrated live loads established in reference standard RS 9-2, placed so as to produce maximum stress.
(2) Floors that support any items of machinery, electrical or mechanical equipment, or other concentrated live load in excess of one thousand pounds (including the weights of pads or bases) shall be designed to support such weight as a concentrated load or group of concentrated loads.
(c) Nonconcurrence.
(1) When a concentrated live load is present, the uniformly distributed load may be considered to be omitted in the area occupied by the concentrated load.
(2) Where reference standard RS 9-2 indicates that the concentrated live load is nonconcurrent with the uniform live load, it may be assumed that the total concentrated load is to be omitted when the uniform load is present and that the total uniform load is to be omitted when the concentrated load is present.
(d) Conformance. For purposes of determining that the magnitude of the actual live load conforms to or is less than the minimum design live load established in this section, the actual uniform live load shall be approximated by averaging the total load actually applied over a rectangular area of one hundred fifty square feet having no side less than eight feet.
§ 27-558. Live loads for sidewalks, driveways, and railings
(a) Sidewalks and driveways.
(1) When supported on grade, all sidewalks for new buildings and alterations shall be subject to inspection and acceptance by the commissioner. Portions of such sidewalks that are located between the curb line and the street line shall be constructed in compliance with the specifications for concrete sidewalks of the department of transportation.
(2) All sidewalks and driveways or portions thereof that are structurally supported shall be designed for a live load of one hundred psf uniformly distributed and in accordance with the provisions of subchapter ten of this chapter. Where subject to intentionally or accidentally imposed wheel loads of vehicles, such portions of sidewalks and driveways shall be designed for a uniformly distributed load of six hundred psf or for the maximum vehicular wheel load that could be imposed thereon, whichever develops the greater stresses.
(3) Appurtenant components of sidewalks and driveways, including manholes, manhole covers, vault covers, gratings, etc., shall be designed for the loads prescribed in paragraph two of this subdivision, or shall conform to the standards of the city agency having jurisdiction.
(b) Railings and parapets.
(1) Railings and parapets around stairwells, balconies, areaways, and roofs, and other railings in similar locations other than those for places of assembly, shall be designed to resist the simultaneous application of a lateral force of forty plf and a vertical load of fifty plf, both applied to the top of the railing. For railings and parapets at the front of theater balconies and in similar locations in places of assembly, the lateral force shall be increased to fifty plf and the vertical load to one hundred plf. An exception is made for railings in oneand two-family dwellings, which shall be designed for a lateral force of twenty plf plus a vertical load of twenty plf, both applied at the top of the railing. The total lateral force and total vertical load shall be at least two hundred pounds each.
(2) Intermediate and bottom rails, if provided, shall be designed for the simultaneous application of forty plf applied horizontally and fifty plf applied vertically; however, lateral and vertical design loads on intermediate and bottom rails need not be considered in the design of posts and anchorages. For railings having solid panels, the panels shall be designed for a uniform lateral load of twenty psf.
(3) Where railings or parapets support fixtures, allowance shall be made for the additional loads imposed thereby.
(4) Railings, bumpers, or similar devices used in parking areas to resist the impact of moving vehicles shall be designed to resist a lateral load of three hundred plf applied at least twenty-one inches above the roadway; but in no case shall the load be less than twentyfive hundred pounds per vehicle.
§ 27-559. Columns in parking areas
Unless specially protected, columns in parking areas subject to impact of moving vehicles shall be designed to resist the lateral load due to impact and this load shall be considered a load of infrequent occurrence. For passenger vehicles, this lateral load shall be taken as a minimum of twenty-five hundred pounds applied at least twenty-one inches above the roadway and acting simultaneously with other design loads.
§ 27-560. Stage areas using scenery or scenic elements
Scenery battens and suspension systems shall be designed for a load of thirty pounds per linear foot of batten length. Loft block and head block beams shall be designed to support vertical and horizontal loads corresponding to a four inch spacing of battens for the entire depth of the gridiron. Direction and magnitude of total forces shall be determined from the geometry of the rigging system including load concentrations from spot line rigging. Locking rails shall be designed for a uniform uplift of five hundred psf with a one thousand pound concentration. Impact factor for batten design shall be seventy-five per cent and for loft and head block beams shall be twenty-five per cent. A plan drawn to a scale not less than one-quarter inch equals one foot shall be displayed in the stage area indicating the framing plan of the rigging loft and the design loads for all members used to support scenery or rigging. Gridirons over stages shall be designed to support a uniformly distributed live load of fifty psf in addition to the rigging loads indicated.
§ 27-561. Roof loads
Roofs and marquees shall be designed for wind, live, and other loads as prescribed in subdivisions (a) through (d) of this section. It may be assumed that maximum wind load occurs with zero live load and that maximum live load occurs with zero wind load. For dwellings an exception is made for awnings, canopies, and patio covers, which may be designed for a live load of twenty psf of horizontal projection.
(a) Live load. Minimum design live loads shall be as follows:
(1) For roofs with slopes up to and including twenty degrees from the horizontal, thirty psf of horizontal projection.
(2) For roofs with slopes greater than twenty degrees from the horizontal, thirty psf of horizontal projection, reduced by one psf for each degree of slope in excess of twenty degrees.
(3) For valleys, live loadings shall be increased to provide for accumulations of snow. The loading intensity shall be assumed to vary from forty-five psf at the low point to fifteen psf at the ridge.
(4) For roofs having curved or pyramidal shapes, the proposed live load shall be established by the architect or engineer, subject to approval by the commissioner.
(b) Wind load. The provisions of section 27-569 of article five of this subchapter shall apply.
(c) Concentrated loads. The provisions of subdivision (b) of section 27-557 of this article shall apply.
(d) Special loads.
(1) When used for purposes such as promenades, assembly areas, or roof gardens, design shall be made for live loads corresponding to the particular usage, as indicated in reference standard RS 9-2. Such loads shall be considered as nonconcurrent with the wind load or with the live load specified in subdivision (a) of this section. The design live and wind loads for roofs, as specified elsewhere in this subchapter, shall be deemed to provide for incidental use of the roof of a building by the occupants thereof.
(2) Where roofs are intended for the ponding of water, the roof shall be designed for the maximum possible depth of water which may be ponded thereon as determined by the relative levels of roof deck and overflow weirs or scuppers. Such load need not be considered as occurring simultaneously with wind or live load.
(3) Girders and roof trusses (other than joists) over garage areas regularly utilized for the repair of vehicles and over manufacturing floors or storage floors used for commercial purposes shall be capable of supporting, in addition to the specified live and wind loads, a concentrated live load of two thousand pounds applied at any lower chord panel point for trusses, and at any point of the lower flange for girders.
(4) Where roofs are landscaped, the uniform design live load on the landscaped portions shall be thirty psf. The weight of the landscaping materials shall be considered as dead load and shall be computed on the basis of saturation of the earth. The areas adjacent to the landscaped portions shall be considered as assembly areas, unless specific provision is made to prevent such use.
(5) Where equipment is placed on roofs, the design shall provide for the support of such equipment.
§ 27-562. Moving loads
Where applicable to the use or occupancy of the building, the design shall consider the moving loads described below.
(a) General. The loads established in subdivisions (a) and (b) of section 27-557 of this article shall be assumed to include allowance for ordinary impact conditions.
(b) Passenger vehicles. Areas used for, and restricted by physical limitations of clearance to, the transit or parking of passenger vehicles shall be designed for the uniformly distributed and concentrated loads for parking areas for such vehicles as provided in reference standard RS 9-2, applied without impact. An exception is made for members or constructions which, because of physical limitations, cannot be subjected to direct load from the vehicle or from a jack or hoist used to raise or suspend the vehicle. Such members or constructions shall be designed for the loads corresponding to the actual usage.
(c) Truck loads. Minimum loads (including vertical, lateral, and longitudinal) and the distribution thereof shall meet the applicable requirements of reference standard RS 9-3, except that impact shall be taken as ten per cent of the vertical reaction.
(d) Railroad equipment. Minimum loads (including vertical, lateral, longitudinal, and impact) and the distribution thereof shall meet the applicable requirements of reference standard RS 9-4.
(e) Crane runways and supports.
(1) VERTICAL LOADS. Actual maximum wheel loads occurring when the crane is lifting its capacity load shall be used. To allow for impact, the lifted load shall be increased twenty-five per cent or the wheel loads increased fifteen per cent whichever produces greater stress condition.
(2) HORIZONTAL LOADS.
a. Lateral load (due to crane trolley travel) shall be twenty per cent of the sum of the capacity load and the trolley weight, applied one-half at the top of each rail and acting in either direction normal to the runway rail.
b. Longitudinal load (due to crane travel) shall be twenty per cent of the maximum total reaction (not including impact) on the rail being considered, applied at the top of the rail and acting parallel to the runway.
(f) Monorail beams and supports.
(1) Vertical loads shall be the sum of the capacity load and trolley weight. To allow for impact, the lifted load shall be increased ten per cent for hand-operated and twenty-five per cent electrically-operated trolleys.
(2) Longitudinal loads shall be twenty per cent of the sum of the capacity load and the weight of the trolley.
(3) Lateral load shall be twenty per cent of the sum of the capacity load and the weight of the trolley.
(4) Centrifugal forces shall be considered for curved tracks.
(g) Loads on supports for elevators, dumbwaiters, and escalators. The provisions of subchapter eighteen of this chapter shall apply.
(h) Loads on machinery supports. Unless machinery is isolated from the support framing, the reactions of reciprocating or heavy power-driven units shall be increased at least fifty per cent and reactions of light shaft- or motor-driven units shall be increased at least twenty-five per cent to provide for impact.
(i) Assembly structures. Seating areas in grandstands, stadiums, and similar assembly structures shall be designed to resist the simultaneous application of a horizontal swaying load of at least twenty-four plf of seats applied in a direction parallel to the row of the seats, and of at least ten plf of seats in a direction perpendicular to the row of the seats. When this load is used in combination with wind for outdoor structures, the wind load shall be one-half of the design wind load, and the provisions of subchapter ten of this chapter relating to infrequent stress conditions shall apply to this loading condition.
(j) Heliports and helistops.
(1) CONCENTRATED LOADS.
a. Landing area. Helicopter landing areas shall be designed for either of the following vertical loads acting at any location:
1. A single concentrated load equal to three quarters of the gross weight of the helicopter and acting on an area of one square foot.
2. Concentrated loads representing the gross wheel reactions of the helicopter acting simultaneously and increased one-third for impact.
b. Taxiing area Helicopter taxiing areas shall be designed for concentrated loads in accordance with clause two of this subparagraph.
(2) UNIFORM LIVE LOAD. The landing and taxiing areas shall be capable of supporting a uniformly distributed live load of forty psf acting nonconcurrently with the concentrated loads.
§ 27-563. Partial loading conditions
(a) Uniformly distributed loads. In continuous framing and cantilever construction, the design shall consider live load on all spans and arrangements of partial live load that will produce maximum stresses in the supporting members. The simplifications given in paragraphs one through three of this subdivision are permissible.
(1) FLOOR AND ROOF FRAMING.
a. For vertical live load applied to the level under consideration, the far ends of the columns above and below that level may be assured as fixed.
b. Combinations of live load may be limited to the following:
1. Live load placed on two adjacent spans.
2. Live load placed on alternate spans. The effects of live load on spans more than two spans away from the span under consideration may be neglected.
(2) ARCHES AND GABLED FRAMES.
a. Live load placed on 1/2 span adjacent to one support.
b. Live load placed on the center 1/4 span.
c. Live load placed on 3/8 the span adjacent to each support.
(3) COLUMNS. Moments due to vertical loads may be calculated from the live load on the largest single adjacent span of the floor under consideration. This moment shall be assumed to act concurrently with live load on all other floors.
(b) Moving concentrated loads. Structural members supporting moving concentrated loads shall be designed for only those loads that can physically occur simultaneously and are arranged to produce maximum stresses.
§ 27-564. Floor loads to be posted
(a) Posting required. Posting requirements shall conform to the requirements of section 27-225 of article twenty-three of subchapter one of this chapter.
(b) Data required. The following floor load data shall be shown:
(1) The uniformly distributed design live load for each floor or part thereof.
(2) The weight of any piece of machinery or equipment weighing more than one thousand pounds, and its identifying description and location.
(3) The maximum design wheel load and total maximum weight of any vehicle that may be brought into the building.
(4) The equivalent uniform partition loads or, in lieu of this, a statement to the effect that the design was predicated on actual partition loads.
§ 27-566. Floor live loads
The uniform live load to be used for design shall be the basic value established in reference standard RS 9-2 multiplied by the percentages given in subdivisions (a) through (d) of this section.
(a) Except as provided in subdivisions (b), (c), and (d), the percentages in table 9-1 shall apply. Contributory areas shall be computed in accordance with section 27-567 of this article.
(b) No live load reduction shall be permitted for the following: members and connections (other than columns, piers, and walls) supporting floor areas used for storage (including warehouses, library stacks, and record storage); areas used for parking of vehicles; and areas used as place of assembly, for manufacturing, and for retail or wholesale sales. For columns, piers, and walls supporting such floor areas the maximum live load reduction shall be twenty per cent.
(c) No live load reduction shall be permitted for calculating shear stresses at the heads of column in flat slab or flat plate construction.
(d) In lieu of the percentages given in table 9-1, the live load reductions for columns, piers and walls may be taken as fifteen per cent of the live load on the top floor, increased successively at the rate of five per cent on each successive lower floor, with a maximum reduction of fifty per cent; and for girders supporting two hundred square feet or more of floor area, the live load reduction may be taken as fifteen per cent. The limitations of subdivisions (b), (c) and (d) of this section shall apply.
TABLE 9-1 Percentage of Live Load*
Contributory Area Ratio of Live Load to Dead Load* 0.625 or less 1 2 or More 149 or less 100 100 100 150-299 80 85 85 300-449 60 70 75 450-599 50 60 70 600 or more 40 55 65
Note for Table 9-1: * For intermediate values of live load/dead load, the applicable percentages of live load may be interpolated.
§ 27-567. Contributory floor areas
For purposes of computing live load reduction, contributory floor areas shall be determined as follows:
(a) For the design of one-way and two-way slabs: the product of the shorter span length and a width equal to one-half the shorter span length. Ribbed slabs shall be considered as though the slabs were solid.
(b) For the design of slabs in flat plate or flat slab construction: one-half the area of the panel.
(c) For the design of columns and girders or trusses framing into columns: the loaded area directly supported by the column, girder, or truss. For columns supporting more than one floor, the loaded area shall be the cumulative total area of all the floors that are supported.
(d) For the design of joists and similar multiple members framing into girders or trusses, or minor framing around openings: twice the loaded area directly supported but not more than the area of the panel in which the framing occurs.
§ 27-568. Foundations and column supports
§ 27-569. Wind loads and earthquake loads
(a) Wind loads. The structural frame and exterior components of all buildings, signs, tanks, and other exposed constructions shall be designed to resist the pressures due to wind as prescribed in reference standard RS 9-5. Wind shall be assumed to act from any direction. For continuous framing, the effects of partial loading conditions shall be considered.
(b) Earthquake loads. Every building, structure and portion thereof shall, at a minimum, be designed and constructed to resist the effects of seismic ground motions as prescribed in reference standard RS 9-6.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1995/017.
§ 27-570. Earth pressures and foundation loads
The provisions of article three of subchapter eleven of this chapter shall apply.
§ 27-571. Bins and bunkers
Loads on component parts of bins and bunkers may be reduced for friction on sidewalls, provided that sidewalls and supports are proportioned for the increased vertical loads. Where stresses would be increased in any component by arching of the fill, the effect of such arching shall be considered.
§ 27-572. Prestressing forces
Prestressing forces shall be considered in the design of prestressed concrete structures, cable structures, guyed structures, and multiple intersecting truss webs utilizing tension members.
§ 27-573. Construction loads
The provisions of subchapter nineteen of this chapter shall apply.
§ 27-574. Fluid pressures
The design of building components shall consider pressures, both positive and negative, of confined fluids and gases.
§ 27-575. Ice
The weight of a one-half inch radial thickness of ice on all surfaces shall be considered as part of the live load in the design of open framed or guyed towers.
§ 27-576. Thermal forces
The design of enclosed buildings more than two hundred fifty feet in plan dimension shall provide for the forces and/or movements resulting from an assumed expansion corresponding to a change in temperature of forty degrees F. For exterior exposed frames, arches, or shells regardless of plan dimensions, the design shall provide for the forces and/or movements resulting from an assumed expansion and contraction corresponding to an increase or decrease in temperature of forty degrees F for concrete or masonry construction and sixty degrees F for metal construction. For determining required anchorage for piping, the forces shall be determined on the basis of temperature variations for the specific service conditions. Friction forces in expansion bearings shall be considered.
§ 27-577. Shrinkage
The design of reinforced concrete components shall provide for the forces and/or movements resulting from shrinkage of the concrete in the amount of 0.0002 times the length between contraction joints for standard weight concrete, and 0.0003 times the length between contraction joints for lightweight concrete. The design of arches and similar structures shall provide for effects of shrinkage, plus rib-shortening, plus plastic flow.
§ 27-578. Distribution of vertical loads
Distribution of vertical loads to supporting members shall be determined on the basis of a recognized method of elastic analysis or system of coefficients of approximation. Elastic or inelastic displacements of supports shall be considered and, for the distribution of dead loads, the modulus of elasticity of concrete or composition sections shall be reduced to consider plastic flow. Secondary effects, due to warping of the floors shall be considered.
§ 27-579. Distribution of horizontal loads
The following provisions shall apply to superstructure framing only, and shall not apply to structures wherein horizontal loads are transmitted to the foundation by stay-cables, arches, non-rectangular frames, or by frames, trusses, or shear walls not oriented in vertical planes.
(a) Distribution of horizontal loads to vertical frames, trusses and shear walls. Horizontal loads on the superstructure shall be assumed to be distributed to vertical frames, trusses, and shear walls by floor and roof systems acting as horizontal diaphragms. The proportion of the total horizontal load to be resisted by any given vertical frame, truss, or shear wall shall be determined on the basis of relative rigidity, considering the eccentricity of the applied load with respect to the center of resistance of the frames, trusses, or shear walls. For vertical trusses, web deformations shall be considered in evaluating the rigidity.
(b) Distribution of horizontal loads within rigid frames of tier buildings.
(1) ASSUMPTIONS. The distribution of horizontal loads within rigid frames of tier buildings may be determined on the basis of a recognized method of elastic analysis or, subject to limitations in paragraph two of this subdivision, may be predicated on one or more of the following simplifying assumptions:
a. Points of inflection in beams or columns are at their midspan and midheight, respectively. The story shear is distributed to the columns in proportion to their stiffnesses.
b. The change in length of columns due to axial effects of the horizontal loads may be neglected.
c. Vertical column loads due to horizontal forces are taken by the exterior columns only, or are resisted by the columns in proportion to the column distances from the neutral axis of the bent.
(2) LIMITATIONS.
a. For buildings over three hundred feet in height, the change in length of the columns, due to the effects of the horizontal loads, shall be evaluated or the framing proportioned to produce regular movements of the successive joints at each floor so that warping of the floor system may be neglected.
b. Simplifying assumptions used in design shall be subject to approval by the commissioner for any of the following conditions or circumstances:
1. For buildings over three hundred feet in height or for buildings with a height-width ratio greater than five.
2. At two-story entrances or intermediate floors.
3. Where offsets in the building occur.
4. Where transfer columns occur.
5. In any similar circumstances of irregularities or discontinuities in the framing.
(c) Distribution of load in self-relieving construction. The framing of self-relieving construction may be proportioned on the assumption that connections are fully rigid in resisting moments due to lateral load and that any larger moments due to the gravity loads or due to a combination of gravity and lateral loads will be relieved by deformation of the connection material, provided that:
(1) The fasteners shall be capable of developing the full moment capacity of the connection at the allowable unit stress established in subchapter ten of this chapter.
(2) The connection shall be capable of resisting the moment due to lateral load, and the shear due to lateral load plus vertical load, all at the allowable unit stresses established in subchapter ten of this chapter.
(3) The framing and the building are within the limitations established in subparagraph b of paragraph two of subdivision (b) of this section.
(4) The connections shall be detailed to permit the required deformations without fracture, and their capacity to so function shall be verified by test or other means.
(d) Structural walls and partitions. Walls and partitions, if specifically designed to resist the applied forces, may be considered as contributing to the resistance or rigidity of the structure with regard to horizontal loads.
§ 27-580. Scope
The provisions of this subchapter, supplemented by the additional requirements of subchapter eleven of this chapter, shall establish minimum requirements for materials, designs, and construction to be used for all structural elements in buildings. In addition, within special flood hazard areas and below the regulatory flood datum, as described in article ten of subchapter four of this chapter, materials, designs and construction required for structural elements by reference standard RS 4-5 shall be applicable.
§ 27-581. Standards
The provisions of reference standard RS-10 shall be a part of this subchapter.
§ 27-582. Definitions
For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.
§ 27-583. Plans
For the requirements governing the filing of plans and the work to be shown on the plans, see subchapter one of this chapter.
§ 27-584. Permits
For the requirements governing equipment work permits and equipment use permits, see subchapter one of this chapter.
§ 27-585. General requirements
For purposes of this code, the structural elements of a building shall normally include all floor, roof, and wall framing members and slabs (but not including slabs-on-grade); all piers, walls, footings, piles, and similar elements of the foundation; and all other elements of both foundation and superstructure which, in engineering practice, are proportioned on the basis of calculated stress. Where doubt exists as to the structural nature of an element, the provisions of this subchapter, and of subchapter eleven of this chapter, shall be deemed to apply only to an element in which the materials are stressed in excess of thirty-three and one-third per cent of the allowable stress values (without increase for infrequent stress conditions) for such material in its proposed use, or to an element wherein public safety would be involved in the event of excessive distortion under the applied loads.
§ 27-586. Materials and methods of construction
Materials and methods of construction used in the manufacture and/or placement of structural elements in a building shall be subject to the requirements of article seven of subchapter one of this chapter, the inspection provisions established in tables 10-1 and 10-2 and the detailed requirements of articles four through twelve of this subchapter and article thirteen of subchapter eleven of this chapter.
§ 27-587. Fire protection requirements to apply
Where a material or method of construction in a specific use is required to provide fire protection as well as structural adequacy, the material or method of construction shall meet both specified requirements.
§ 27-588. Use of used and unidentified materials
The utilization of used materials and unidentified or ungraded materials shall be limited to non-structural elements, except:
(a) Such materials (or elements) may be reused, or continued in use, at stress levels to which the materials or elements were subjected in the previous construction, or at load capacity as demonstrated by load test procedures as described in subdivision (a) of section 27-599 of article three of this subchapter.
(b) Unidentified materials may be graded by the recovery and test of representative samples, or by other means satisfactory to the commissioner.
(c) Used materials shall be considered to be graded where the grade is clearly indicated on the approved plans for the existing construction and may be used at the allowable stress levels for that grade of like material as established in the building code in force at the time the plans for the existing construction were approved.
TABLE 10-1 Inspection of Materials and Assemblies
Materials Elements That Shall Be Subject to Controlled Inspection a, b, d Elements That Are Not Subject to Controlled Inspection a, c, d Steel None All structural elements and connections Concrete Materials for all structural elements proportioned on the basis of calculated stresses seventy per cent or greater, of basic allowable values. See article five for specific requirements relating to "quality control of materials and batching." (1) All materials for structural elements proportioned on the basis of calculated stresses less than seventy per cent of basic allowable values.(2) Concrete materials for:(a) Short span floor and roof construction proportioned as per section 27-610.(b) Walls and footings for buildings in occupancy group J-3.(3) Metal reinforcement. Aluminum None All structural elements and connections. Wood None All structural elements and connections. Reinforced gypsum concrete None All structural elements. Masonry None All structural elements. Other Requirements as may be established in other subchapters of this code or by the commissioner.
Notes for Table 10-1:
a For general provisions relating to inspection see section 27-132.
b All structural materials and assemblies subject to controlled inspection shall be tested and/or inspected at their place of manufacture and evidence of compliance with the provisions of this subchapter shall be provided as stipulated in articles four through twelve.
c Mill, manufacturer's and supplier's inspection and test reports will be accepted as evidence of compliance with the provisions of this code for all structural materials and assemblies not subject to controlled inspection.
d Basic allowable stress values as referenced herein shall denote allowable stress value without increase for infrequent stress conditions as established in this code or in the applicable reference standard for the material or element in its proposed use.
TABLE 10-2 Inspection of Methods of Construction
Materials Operations on Structural Elements That Shall Be Subject to Controlled Inspection a, b, d Operations on Structural Elements That Are Not Subject to Controlled Inspection a, c, d Steel (1) Welding operations and the tensioning of high strength bolts in connections where the calculated stresses in the welds or bolts are fifty per cent or more of basic allowable values. (1) Welding operations and the tensioning of high strength bolts in connections where the calculated stresses in the welds or bolts are less than fifty per cent of basic allowable values. (2) Connection of fittings to wire cables for suspended structures, except where cables together with their attached fittings are proof-loaded to not less than fifty-five per cent of ultimate capacity. (2) All other fabrication and erection operations not designated for controlled inspection. Concrete Except for those operations specifically designated in this table are not subject to controlled inspection, for all concrete, the operations described in subdivision (a) of section 27-607 shall be subject to controlled inspection. (1) All operations relating to the construction of members and assemblies (other than pre-stressed members) which involve the placement of a total of less than fifty cubic yards of concrete and wherein said concrete is used at levels of calculated stress seventy per cent or less of basic allowable values. (2) Placing and curing of concrete for all:(a) Short span floor and roof construction as per section 27-610(b) Walls and footings for buildings in occupancy group J-3. (3) Size and location of reinforcement for walls and footings for buildings in occupancy group J-3.(4) All other operations not described in subdivision (a) of section 27-607. Aluminum Welding operations in connections where the calculated stresses in the welds are fifty per cent or more of the basic allowable values. (1) Welding operations in connections where the calculated stresses in the welds are less than fifty per cent of basic allowable values. (2) All other fabrication and erection operations not designated for controlled inspection. Wood Fabrication of glued-laminated assemblies and of plywood components. All other operations not designated for controlled inspection. Reinforced Gypsum Concrete None All operations incident to the fabrication and placement of structural elements. Reinforced Masonry (1) Fabrication of prefabricated units. (1) All masonry work for buildings in occupancy group J-3. (2) Placement and bedding of units; sizes of members, including thickness of walls and wythes; sizes of columns; the size and position of reinforcement, in place, and provisions for curing and protection against freezing for all reinforced masonry construction unless such operations are specifically not designated for controlled inspection. (2) All mixing of mortar. (3) All other operations not designated for controlled inspection. Unreinforced Masonry Placement and bedding of units and sizes of members including thickness of walls and wythes; sizes of columns; cleanouts; and provisions for curing and protection against freezing for all masonry construction proportioned on the basis of structural analysis as described in section four of reference standard RS 10-1B, unless such operations are specifically not designated for controlled inspection. (1) All masonry work for buildings in occupancy group J-3. (2) All mixing of mortar. (3) All other operations not designated for controlled inspection.
Notes for Table 10-2:
a For general provisions relating to inspection see section 27-132.
b All construction operations designated for controlled inspection shall be inspected by the architect or engineer designated for controlled inspection during the performance of such operation.
c Certification by the fabricator or erector, as applicable, will be accepted as evidence of compliance with the provisions of this code for all construction operations not subject to controlled inspection.
d Basic allowable stress values as referenced herein shall denote allowable stress value without increase for infrequent stress conditions as established in this code or in the applicable reference standard for the material or element in its proposed use.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1995/017.
§ 27-589. Equivalent systems of design
Nothing in this subchapter shall be construed to prohibit the use of any system of design, alternate to those indicated, provided that it can be demonstrated to the satisfaction of the commissioner that such system of design will provide a factor of safety against structural failure consistent with the requirements of articles four through twelve of this subchapter, fire safety in consonance with the requirements of subchapters three through eight of this chapter, and such other characteristics pertinent to the safety of life, health, and property as prescribed in this subchapter or as may be required by the commissioner. Alternate or equivalent materials or methods of construction shall be subject to the provisions of section 27-133 of article seven of subchapter one of this chapter.
§ 27-590. Deferred detailing
Where structural elements are normally detailed on shop or working drawings, the application for the permit shall so state, and issuance of the permit shall be conditioned upon future submission of such shop or working drawings showing the approval of an architect or engineer with regard to such elements, or of a signed statement by an architect or engineer to the effect that such drawings were prepared to his or her satisfaction. In cases where the detailing of structural elements has been made on the basis of fire-resistance ratings, load tables, or similar data as given in manufacturer's catalogues, the application for approval of the plans shall so state and issuance of such acceptance shall be conditional upon submission of a statement by the manufacturer, or of other supporting documentary evidence of accreditation furnished by the manufacturer, attesting to the accuracy of the data and stating that such data were derived in conformance with the provisions of this code. Where the detailing of structural elements has been made on the basis of data published in technical documents of recognized authority issued by, or accredited by, the agency or association promulgating the applicable reference standard cited in this code, such statements will not be required.
§ 27-591. Stability
Except as provided in article twelve of subchapter eleven of this chapter with regard to foundation elements, a building, or any element thereof shall be proportioned to provide a minimum factor of safety of 1.50 against failure by sliding or overturning. The required stability shall be provided solely by the dead load plus any permanent anchorages which may be provided.
§ 27-592. Bracing
Unless otherwise specified in the reference standards, members used to brace compression members shall be proportioned to resist an axial load of at least two per cent of the total compressive design stress in the member braced, plus any transverse shear therein.
§ 27-593. Secondary stresses
Secondary stresses in trusses shall be considered and where of significant magnitude, their effects shall be provided for in the design.
§ 27-594. Combination of loads
Dead loads, live loads (including impact) and reduced live loads, where applicable, shall be considered as basic loads. Wind, earthquake, thermal forces, shrinkage, and unreduced live loads (where live load reduction is permitted by subchapter nine of this chapter) shall be considered as loads of infrequent occurrence. Members shall have adequate capacity to resist all applicable combinations of the loads listed in subchapter nine of this chapter, in accordance with the following:
(a) Where design is based on allowable working stresses, the loads as described in subchapter nine of this chapter shall be multiplied by the following factors and the design shall be based on the resulting load values:
(1) For combinations of basic loads, only, the factor shall be 1.0, except that for the design of temporary structures (defined as a structure which will be in place six months or less) the factor shall be 0.75.
(2) For any combination of one or more basic loads with any one load of infrequent occurrence, the factor shall be 0.75, except that for the design of temporary structures the factor shall be 0.67.
(3) For any combination of one or more basic loads with two or more loads of infrequent occurrence, the factor shall be 0.67. Exception. The provisions of reference standards RS 10-8 and RS 10-9 relating to increases of allowable unit stresses for short-time loading shall apply.
(b) Where design is based on ultimate strength criteria (including plastic design of steel structures and proportioning of suspended structures), the loads, as described in subchapter nine of this chapter shall be multiplied by the factors indicated in subdivision (e) of section 27-639 of article eleven of this subchapter and in the applicable reference standards. The design shall be based on the resulting load values. Exceptions.
1. Where combinations of load for which factors are given in the reference standard include the load of wind (or earthquake) the design additionally shall consider combinations of load wherein each other of the loads of frequent occurrence as listed in this paragraph are substituted for the load of wind.
2. The design also shall consider combinations of load wherein two most critical of the loads of infrequent occurrence are combined with the basic loads. For such combination, however, the factors indicated in the reference standards and in subdivision (e) of section 27-639 of article eleven of this subchapter for suspended structures, for the combination of basic loads plus one load of infrequent occurrence may be reduced fifteen per cent.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1995/017.
§ 27-595. Deflection limitations
The applicable provisions of the several reference standards cited in this subchapter shall apply. In addition, the total of the dead plus live load vertical deflections (including effects of creep and shrinkage) of members, supporting walls, veneered walls, or partitions constructed of or containing panels of masonry, glass, or other frangible materials shall not exceed 1/360 of the span.
§ 27-596. General
The structural design of a member or assembly shall be deemed to be adequate if the design computations demonstrate conformance with the applicable standards noted in articles four through twelve of this subchapter. Where, because of practical difficulties, such computations cannot be executed, the structural design may be deemed adequate if the member or assembly is subjected to, and satisfactorily performs under, load tests in accordance with the provisions of subdivision (a) of section 27-599 of this article. Where there is a question as to the adequacy of a completed or partly completed construction, the provisions of sections 27-597, 27-598, and subdivision (b) of section 27-599 of this article shall apply.
§ 27-597. Questionable construction
If, upon inspection, it is found that a construction or any part thereof, as built, shows open cracks, spallings, or other signs of distress; or should inspection records show more significant deficiency of construction; or should laboratory tests on concrete or other materials that have been incorporated into the work indicate deficiency of strength; or should there be a reasonable doubt as to the strength, stability, or adequacy of the construction or any part thereof, such construction may be checked to verify the adequacy thereof either by computation, or by core or load tests conducted in accordance with the provisions of section 27-598 or subdivision (b) of section 27-599 of this article or by any combination of these means. Should the adequacy of construction not be verified within a reasonable time, such construction shall be rejected and shall be demolished or reinforced or rebuilt to be made safe in conformance with the requirements of this code. In the event of a disagreement, the final decision as to the acceptance of the work shall be made by the commissioner. All such tests shall be made without expense to the city.
§ 27-598. Core tests of concrete construction
The adequacy of the concrete in a building may be ascertained by the recovery and testing of cores. Cores shall be taken and tested in accordance with the procedure described in reference standard RS 10-16. In lieu thereof, cores cast-in-place and originally cured with the parent concrete, or other device acceptable to the architect or engineer designated for controlled inspection and which will produce test specimens simulating the condition of the concrete in place including the size and proportions specified for core specimens may be utilized to demonstrate the adequacy of the concrete in place. The compressive strength so determined shall meet the requirements for strength tests as described in reference standard RS 10-3.
§ 27-599. Load tests
(a) Prequalifying load tests. The provisions of this section shall apply only to load tests made for the purpose of establishing the structural adequacy of members or assemblies before such members or assemblies are incorporated into the work. Load tests for the purpose of establishing the strength of an element or assembly, in place, after construction, shall conform to the requirements of subdivision (b) of this section.
(1) TEST SPECIMENS. The test specimens shall be a true representation of the units or assemblies to be used in the work and, unless sufficient tests are conducted on differing specimens to interpolate the performance of members of varying characteristics, test specimens shall be substantially identical with the units or assemblies to be used in service. Particular attention shall be given to matching the type and grade of material and, in the case of concrete, the mix, age, curing, and other pertinent variables.
(2) SUPPORT CONDITIONS AND INTERACTION. Load tests shall be performed in such a manner that the supports for the members or assemblies being tested will simulate the conditions of support in the building, except that conditions of partial fixity may be approximated by condition of full or zero restraint, whichever produces a more severe stress condition in the member being tested. The test conditions shall be such as to obviate all interaction of fills, finishes, partitions, supports, or members whose interaction normally would be neglected in design. Where continuous, multiple, intersecting, or connected members are used in the test, all interacting members shall be simultaneously and fully loaded and additional tests shall be performed under the partial loading conditions specified in subchapter nine of this chapter. Test specimens shall not be unloaded and reloaded or subjected to cyclical loading, except as specifically required by the provisions of this code and except that the adding of increments of additional load to a member already under load and the application of the test load as described in subparagraph b of paragraph three of this subdivision following removal of the test load described in subparagraph a of paragraph three of this subdivision will be permitted.
(3) STRENGTH REQUIREMENTS. The member or assembly, supported as described in paragraph two of this subdivision, shall be capable of supporting:
a. Without visible damage (other than hairline cracks) its own weight plus a test load equal to one hundred fifty per cent of the design live load plus one hundred fifty per cent of any dead load that will be added at the site; and
b. Without collapse, its own weight plus a test load equal to fifty per cent of its own weight plus two hundred fifty per cent of the design live load plus two hundred fifty per cent of any dead load that will be added at the site. The latter loading shall remain in place for a minimum period of one week. All loading conditions described in subchapter nine of this chapter shall be considered. The design live load shall be the nominal value reduced for contributory area as described in subchapter nine. Except as permitted under paragraph five of this subdivision, units to be tested shall be full size. Load bearing wall and partition assemblies shall be tested both with and without window and door framing where such framing will be included in the final assemblies. Exception. If the load tests are conducted and the results promulgated in a manner that will permit clear differentiation between the dead and live load components added at the site, then the capacity of the member or assembly without visible damage other than hairline cracks as determined under load test condition in subparagraph a of paragraph three of this subdivision, may be reduced to the weight of the member, plus any dead load that will be added at the site, plus one hundred fifty per cent of the design live load; and the capacity of the member or assembly to resist collapse as determined under load test condition in subparagraph b of paragraph three of this subdivision may be reduced to one hundred fifty per cent of the weight of the member, plus one hundred fifty per cent of any dead load that will be added at the site, plus two hundred fifty per cent of the design live load.
(4) DEFLECTION REQUIREMENT. With the member or assembly supported as described in paragraph two of this subdivision, and after loading as required by the provisions of subparagraph a of paragraph three of this subdivision and the removal of said load, the percentage of recovery of the deflection caused by the superimposed load shall be at least seventy-five per cent. The deflection under the design live load shall not exceed that permitted in this subchapter.
(5) MODEL TESTS. Tests on models less than full size may be used to determine the relative intensity, direction, and distribution of stresses and applied loads, but shall not be considered as a proper method for evaluating stresses in, nor the strength of, individual members unless approved by the commissioner for this purpose. Where model analysis is proposed as a means of establishing the structural design, the following conditions shall be met:
a. Analysis shall be made by a firm or a corporation satisfactory to the commissioner.
b. The similitude, scaling, and validity of the analysis shall be attested to by an officer or principal of the firm or corporation making the analysis.
c. A report on the analysis shall be submitted showing test set-ups, equipment, and readings.
(b) Load tests of completed construction. The provisions of this subdivision shall apply to any type of construction where the appropriate reference standard does not provide for load test of completed construction and the construction is questionable. When the appropriate reference standard provides for such load testing, the provisions of reference standard shall be used.
(1) Strength. The construction shall be loaded in two stages:
(a) With all dead load to which it will be subjected in service plus a superimposed load equal to the design live load reduced as described in subchapter nine of this chapter; and
(b) With a total load, including its own weight, equal to one hundred fifty per cent of the total dead load to be supported in service plus one hundred eighty per cent of the design live load, reduced for contributory area as described in subchapter nine of this chapter, which load shall remain in place for a minimum period of twenty-four hours.
(2) Deflection requirement. Under the first stage loading, the deflection shall not exceed that permitted in the applicable reference standard. The residual deflection after removal of the second stage loading shall not exceed twenty-five per cent of the calculated elastic deflection under the superimposed test load. The structure, after recovery of the deflection shall not show any evidence of serious distress.
(3) Interaction. The load area shall extend to include the loading of all framing and elements that contribute to the strength of the element or elements under test, by way of interaction.
(4) Lateral loads. Where the elements in question must resist lateral loads in service, such loads shall be simulated in the tests. In such case, the magnitude of the applied live load and lateral load components of the test load may be adjusted as described in section 27-594 of article two of this subchapter, provided that the stress condition under the load increments described in paragraph one of this subdivision is not more critical.
(5) Reloading. Unloading and reloading or cyclical loading of test areas will not be permitted, except for the addition of increments of additional load to a member already under load.
§ 27-600. General requirements
§ 27-601. Identification
(a) Masonry units. Masonry units shall be clearly identified to show the grade of the unit and the compressive strength where called for on the plans.
(b) Metal reinforcement. Reinforcing bars shall be rolled so as to identify the grade of steel and the size. Bundles and rolls of cold-drawn steel wire or welded wire fabric shall be tagged so as to identify the type and grade of steel and the size.
§ 27-602. Inspection
The inspection of masonry and masonry construction shall conform to the requirements of tables 10-1 and 10-2.
§ 27-603. General requirements
Concrete materials, design, construction, quality, inspection and testing shall meet the requirements of reference standard RS 10-3. Precast concrete construction utilizing a thin skin or slab stiffened or supported by a system of ribs shall conform to the requirements of reference standard RS 10-4.
§ 27-604. Identification of metal reinforcement
Reinforcing bars shall be rolled so as to identify type and grade of steel, and size. Bundles and rolls of wire, strands, or welded wire fabric shall be tagged so as to identify the type and grade of steel and the size.
§ 27-605. Mixes
Concrete may be proportioned, batched, and mixed by any of the following methods:
(a) Method I. Mixes with minimum cement content.
(1) MINIMUM CEMENT CONTENT. The cement content used in the work shall not be less than the content given in table 10-3 for the corresponding strength of concrete.
TABLE 10-3 Minimum Cement Content
Specified Compressive Strength in 28 Days (f'c) - psi Minimum Pounds of Cement Per Cubic Yard of Concrete (all aggregates) 3,000 540 3,500 610 4,000 660 5,000 800 Over 5,000 Permitted only by reference standard RS 10-3 6,000 and over Permitted only by reference standard RS 10-3, "Special Requirements for High Strength Concrete."
Note: Minimum pounds of cement may be reduced up to 8 percent by the addition of an accepted admixture.
(2) WATER-CEMENT OR STRENGTH-CEMENT RATIO. Normal weight concrete proportioned on the basis of preliminary tests shall be produced by using a water-cement ratio corresponding to a point on a strength-cement or water-cement ratio curve. Proportioning of lightweight and heavyweight concrete, and concrete using an aggregate other than natural sand, gravel or stone shall be by using a strength-cement content curve. The point on the respective curves shall represent a strength of concrete at the slump and age called for on the plans at least twenty-five percent higher than the specified strength, f'c. The cement content shall not be less than the content shown in table 10-3.
(3) PRELIMINARY TESTS. Preliminary tests of concrete shall be made in advance of any concreting operation by a licensed concrete testing laboratory acceptable to the architect or engineer of record. Preliminary tests shall consist of compression strength tests of molded concrete cylinders made in accordance with reference standards RS 10-17 and RS 10-21. A curve representing the relation between the average strength of the concrete at twenty-eight days, or at any other specified age filed with the department, and the strength-cement ratio or the water-cement ratio shall be established for the range of strength values at the slump required for the work. The tests shall include at least four mixes with different strength-cement ratios or four mixes with different water-cement ratios and at least four cylinder specimens for each mix. The cylinder strength tests shall be supplemented by tests to confirm that the cement and aggregates conform to the provisions of reference standard RS 10-3.
(4) PREVIOUSLY ACCEPTED MIXES. In lieu of the requirements of paragraph three of this subdivision, the architect or engineer designated for controlled inspection may permit the use of mix proportions of aggregates having the same specific gravity, size and gradation; cements of the same type and batch weight; admixtures of the same type and quantity; and other ingredients the same as or equal to those that have been previously submitted with applicable preliminary tests which complied with paragraphs one and two of this subdivision, and which have been accepted by the commissioner within the past year. If any of the mix proportions or ingredients are changed, a separate submission for acceptance shall be required.
(5) QUALITY CONTROL AND INSPECTION OF MATERIALS AND OF BATCHING. Where concrete materials are used for structural elements defined in section 27-585 of article one of this subchapter, quality control and inspection shall be provided at the batch plant by a licensed concrete testing laboratory under the supervision of the architect or engineer designated for controlled inspection, in accordance with the requirements of table 10-1 and in sufficient scope to:
a. Determine and record the actual batched weights of the ingredients and the volume of water charged into the mixer;
b. Verify that such weights conform to the weights and proportions required by the preliminary test mix, adjusted for moisture content, fineness modulus and gradation of aggregates;
c. Verify conformance of the quality and condition of the materials to reference standard RS 10-3.
d. Verify that the aggregates have the same specific gravity, size and gradation; the cement is the same type and batch weight, the admixtures are the same type and quantity; and that any other ingredients are the same as or equal to those used for the preparation of the preliminary test mixes;
e. For all concrete, whether or not designated for controlled inspection, attestation of the results of quality control and inspection at the batch plant shall appear on a ticket accompanying each load of concrete. The attestation for subparagraphs a, b, c and d of this paragraph shall be executed by the licensed concrete testing laboratory.
f. The licensed concrete testing laboratory shall also attest that the slump entrained air content and unit weight of the fresh concrete, as discharged from the mixer at the job site, were tested in accordance with reference standards RS 10-49, RS 10-51, RS 10-52, RS 10-61, RS 10-62, RS 10-63 and RS 10-64, and that all were in compliance with the accepted mix design.
(b) Method II. Proportioning on the basis of field experience.
(1) PROPORTIONING. For the computation of the standard deviation in accordance with reference standard RS 10-14, mixes with test data from previous projects, similarly proportioned in accordance with the provisions of subdivision (a) of this section, and having materials of similar density and admixtures and having a slump equal to or greater than that at which the concrete is to be placed shall be used. Such mixes may be accepted subject to the approval of the architect or engineer designated for controlled inspection.
(2) STRENGTH. The required average strength, fcr, to be used as the basis for the selection of mix proportions, shall in no case be less than fifteen percent higher than the specified strength called for on the plans.
(3) BATCHING. The concrete shall be produced either in the concrete production facility used to produce the concrete from which the tests were made to develop the field experience data referred to in paragraph one of this subdivision or, subject to the approval of the architect or engineer designated for controlled inspection, in any concrete production facility that has data showing a record of standard deviation equal to or less than that of the original facility. All concrete proportioned according to field experience shall be produced in a plant with automatic recording equipment for all ingredients.
(4) QUALITY CONTROL AND INSPECTION OF MATERIALS AND OF BATCHING. When the concrete is batched in a plant where automatic recording equipment documents the batched weights or volumes of cement, aggregates, admixtures and water, no inspection of the materials or of the batching, nor any attestation by a licensed concrete testing laboratory responsible to the architect or engineer designated for controlled inspection, shall be required. A concrete producer shall:
a. Verify that such weights conform to the required weights and proportions, and to the strength-cement ratio or water-cement ratio required by the proportioning established pursuant to paragraph one of this subdivision, adjusted for moisture content, fineness modules and gradation of aggregates.
b. Verify conformance of the quality and condition of the materials to reference standard RS 10-3.
c. Attest, on a ticket accompanying each load, to the specified strength of the concrete, the actual weights or volume of the ingredients, and the weight or volume of water charged into the mixer at the batch plant or to be added at the job site. A statement that subparagraph b of this paragraph has been complied with shall also be included.
d. If at any time the automatic recording equipment becomes inoperative, the concrete production facility may be permitted, but only with the approval of the architect or engineer designated for controlled inspection, to batch and mix concrete for a period not to exceed three consecutive working days. During such a period, the concrete production facility shall engage a concrete batch plant inspector from a licensed concrete testing laboratory to observe and record the actual weights of the cement, aggregates, admixtures and other ingredients, and the weight or volume of water charged into the mixers. If the automatic recording equipment is inoperative for a period longer than three consecutive working days the concrete production facility shall not batch or mix concrete and the architect or engineer designated for controlled inspection shall notify the commissioner in writing that such equipment is inoperative.
(c) Method III. Average Concrete.
(1) in lieu of making preliminary tests, average concrete limited to the concrete strengths shown in table 10-3A below may be used, and the cement content shall not be less than the value given in table 10-3A for the corresponding specified compressive strengths, nor shall the total volume of water (moisture plus added water) exceed that specified therein, provided that the total yardage placed does not exceed fifty cubic yards and the levels of calculated stress do not exceed seventy percent of the basic allowable stresses.
TABLE 10-3A
Specified compressive strength in twenty-eight days (f'c) pounds per square inch Minimum pounds of cement per cubic yard of concrete Maximum permissible total volume of water U.S. gallons per cubic yard of concrete 2,000 520 40 2,500 560 41 3,000 610 42
(2) Each load of concrete shall be certified by the producer to the owner, whether produced at a ready mixed plant or site mixed, as to the total quantity of concrete, concrete strength and actual quantities per cubic yard of each material, including water, contained therein. A copy of such certificate shall be available to the department during the progress of the work and for two years thereafter.
§ 27-606. Documentation
All mix proportions and supporting data shall be submitted for acceptance to the commissioner or to the architect or engineer designated for controlled inspection, as required, prior to the start of any work. All required attestations shall become a part of the documentation to be filed with the commissioner, and shall be subject to verification by strength tests, as hereinafter described, by check sampling of ingredients, or by such other inspections as the commissioner or the architect or engineer designated for controlled inspection may elect. Copies of all documentation filed with the commissioner, all the licensed concrete testing laboratory test data and required attestations, together with the tapes recording the batch weight where automatic recording equipment is used shall be available for inspection for a period of two years after the completion of the project. Such records shall be maintained by the architect or engineer designated for controlled inspection.
§ 27-607. Inspections
Inspection of concrete and concrete construction shall conform to the requirements of tables 10-1 and 10-2 and the provisions of this subchapter.
(a) Controlled inspection. Controlled inspection of concrete construction shall include:
(1) STRENGTH TESTS. Strength tests shall be performed on all structural concrete. The provisions of reference standard RS 10-3 shall apply. A licensed concrete testing laboratory shall, in compliance with reference standards RS 10-17, RS 10-51 and RS 10-52, sample the concrete, make and cure the test specimens at the job site, transport the specimens to the laboratory and test the specimens for compressive strength. Written reports of the results shall be furnished to the architect or engineer designated for controlled inspection and to the concrete producer immediately, but not more than five days following the conclusion of the compression strength tests. Test specimens shall be stored on the job site in an insulated curing box of sufficient size and strength to contain all the specimens made in any four consecutive working days and to protect the specimens from falling over, being jarred or otherwise disturbed during the period of initial curing. The box shall be erected, furnished and maintained by the concrete contractor. Such box shall be equipped to provide the moisture and to regulate the temperature necessary to maintain the proper curing conditions required by reference standard RS 10-52. Such box shall be located in an area free from vibration such as pile driving and traffic of all kinds. No concrete requiring inspection shall be delivered to the site until such storage curing box has been provided. Specimens shall remain undisturbed in the curing box until ready for delivery to the testing laboratory but not less than sixteen hours. Specimens delivered to the laboratory prior to an age of forty-eight hours shall not be demolded prior to delivery. All specimens shall be carefully removed from the box and transported to the laboratory by the licensed concrete testing laboratory in accordance with the provisions of reference standard RS 10-52. All specimens shall be delivered to the laboratory before the laboratory closes at the end of the second working day following the day the specimens were molded. The date of arrival at the laboratory shall be recorded on the specimen test reports. All concrete failing to meet the specified minimum strength requirements shall be rejected by the architect or engineer designated for controlled inspection pending verification of the adequacy of the construction as described in section 27-598 of article three of this subchapter.
(2) ADDITIONAL TESTS. Each sample of fresh concrete made in accordance with reference standard RS 10-51 for the purpose of molding strength test specimens shall be made under the supervision of the architect or engineer designated for controlled inspection. Each sample shall be tested by the licensed concrete testing laboratory to determine its slump in accordance with reference standard RS 10-49, its entrained air content in accordance with reference standards RS 10-61 and RS 10-62, its unit weight in accordance with reference standards RS 10-63 and RS 10-64 and its temperature. If any of the tests fail to meet the specified requirements, the concrete shall be sampled again and the particular test that failed shall be repeated. If the second test fails to meet the specified requirements, then, with the approval of the architect or engineer designated for controlled inspection, adjustments shall be made to the concrete in the mixer to correct the deficiency. Test specimens shall not be molded from any sample that did not meet the specified requirements nor shall the concrete from which the sample was taken be placed in the structure, provided, however, that such concrete may be used elsewhere in the work where it meets or exceeds the specified requirements, but only with the approval of the architect or engineer designated for controlled inspection. In such case, test specimens shall be molded by the licensed concrete testing laboratory which shall also record the precise location where the concrete was placed in the structure.
(3) CONTROLLED INSPECTION LOG BOOK. A controlled inspection log book, limited solely to the concrete construction work, readily available to inspectors and representatives of the department, concrete suppliers and the architect and/or engineer of record, shall be maintained at the job site by the architect or engineer designated for controlled inspection, who shall make therein daily entries pertaining to the progress of the work. The entries shall describe, but not be limited to, the location, size and dimensions of the concrete members for which forms were constructed that day; the reinforcement installed in, and the specific locations and time spans of, every concrete placement; the air temperature, wind velocity and direction and other weather conditions during the twenty-four hours after concrete has been placed, specifically at eight a.m., noon and four p.m., the protections taken against excessive temperatures and adverse weather conditions at each placement made that day; the methods used, to cure the concrete and the period during which such methods were maintained; the actual hour when forms were stripped and shores were reinstalled and tensioning was applied to all prestressed members. The log shall become a part of the documentation to be filed with the commissioner as provided in section 27-606 and shall include the attestation of the architect or engineer designated for controlled inspection that the concrete construction work complies with the approved plans and the provisions of this code.
(b) Other required inspection. Quality control or inspection shall be provided with respect to all operations of mixing and placing concrete and reinforcement that are not designated for controlled inspection. In the case of sidewalks, curbs, paving, slabs-on-grade and any work designated in table 10-1 under the caption "Elements That Are Not Subject to Controlled Inspection" or in table 10-2 under the caption "Operations on Structural Elements That Are Not Subject to Controlled Inspection," all inspections shall be subject to and in accordance with the requirements of subdivision (b) of section 27-132. If any test to determine the quality or compressive strength of the concrete is required, the fresh concrete shall be sampled and tested for slump, entrained air content, unit weight and temperature. Compression strength test specimens shall be molded only by a licensed concrete testing laboratory or by a person certified by the American Concrete Institute as qualified to perform such function. Attestation shall be executed by the person superintending the use of the material in accordance with the requirements of subdivision (b) of section 27-132 of article seven of subchapter one of this chapter.
§ 27-608. Admixtures
Admixtures may be used in the concrete only where included in the preliminary test mixes made in accordance with paragraph three of subdivision (a) of section 27-605 or mixes proportioned in accordance with the provisions of reference standard RS 10-3. In the case of mixes proportioned in accordance with subdivision (c) of section 27-605, there shall be no reduction of the cement content called for in table 10-3A because admixtures are used in the mix. Where admixtures are used, the provisions of reference standards RS 10-3 and RS 10-44 shall apply. In addition, no anti-freeze agents shall be used. Admixtures shall be added in measured quantities in conformance with the accepted mix design.
§ 27-609. Licensed concrete testing laboratories
All strength tests of concrete and testing of concrete materials required by the provisions of this section shall be performed by concrete testing laboratories licensed in accordance with the requirements of article nine of subchapter two of chapter one of title twenty-six of the administrative code and rules promulgated by the commissioner. The licensed concrete testing laboratory shall, among other things, analyze, evaluate and test concrete materials; determine whether the materials comply with specifications and pertinent referenced national standards in reference standard RS 10-3; select mix proportions for preliminary tests; recommend the mix proportions to be used on the project for which the tests were made; analyze data from previous projects and compute the standard deviation; and recommend the mix proportions to be used based on such field experience data. At the batch plant or at the job site, the licensed concrete testing laboratory shall, among other things, sample concrete and test for slump, entrained air content, unit weight and temperature, mold compression test specimens; store and cure such specimens on the job site; remove, transport and deliver such specimens to the laboratory; demold, store, cure, cap and test such specimens at the laboratory and furnish written reports of the results of all tests of the materials and concrete to the architect or engineer designated for controlled inspection and to the concrete producer. When tests of the hardened concrete are required, they shall be made by the licensed concrete testing laboratory in accordance with reference standard RS 10-3 and the national standards for making tests for penetration resistance, rebound number, pullout strength and of drilled cores. The architect or engineer designated for controlled inspection is authorized either to dismiss or to employ a particular licensed concrete testing laboratory at any time during the progress of the work.
§ 27-610. Short-span concrete floor and roof construction supported on steel beams
In lieu of analysis, the following empirical procedures may be used for the design of short-span concrete floor and roof slabs containing draped reinforcement and supported on steel beams. The empirical equations described in subdivisions (c) and (d) of this section shall apply only where the steel beams are placed, or are encased, in a manner that will provide section for the transfer of shear from slabs to beams equivalent to, or in excess of, the slab thickness required by said equations.
(a) Concrete. The concrete shall have a minimum compressive strength at twenty-eight days of seven hundred psi.
(b) Reinforcement. Reinforcement shall consist of steel fabric, rods, or other suitable shapes that shall be continuous or successively lapped to function as a continuous sheet. The main reinforcement shall be at least 0.15% of the gross cross section where continuous steel fabric is used and at least 0.25% of the gross cross section where other forms of steel reinforcement are used. All reinforcing shall be draped, with the center of the reinforcement at the center of the span one inch above the bottom of the slab and the center of reinforcement over the support one inch below the top of the slab.
(c) Minimum slab thickness. The minimum total thickness of concrete floor and roof construction shall be determined by the following formula, but shall not be less than four inches:
t = L + w-75 2 200
where:
t = total thickness (in.)
L = clear span between steel flanges (ft.)
w = gross uniform load (dead load plus reduced live load) (psf).
(d) Allowable Load. The allowable load shall be determined by the following formula:
w = 3CA s L2
where:
w = gross uniform load (psf)
As = cross-sectional area of main reinforcement (sq. in. per ft. of slab width)
L = clear span between steel flanges in feet. (L shall not exceed ten feet in any case, and when the gross floor load exceeds two hundred psi shall not exceed eight feet.)
C = the following coefficient for steel having an ultimate strength of at least fifty-five thousand psi;
1. For lightweight aggregate concrete:
a. twenty thousand when reinforcement is continuous.
b. fourteen thousand when reinforcement is hooked or attached to one or both supports.
2. For stone concrete:
a. twenty-three thousand when reinforcement is continuous.
b. fifteen thousand when reinforcement is hooked or attached to one or both supports.
(1) When the above formula is used the reinforcement shall be hooked or attached to one or both supports or be continuous.
(2) If steel of an ultimate strength in excess of fifty-five thousand psi is used, the above coefficient may be increased in the ratio of the ultimate strength to fifty-five thousand but at most by thirty percent.
(e) Openings in floors and roofs. Openings more than one foot six inches on a side shall be framed. All areas encompassing multiple openings aggregating more than one foot six inches in any ten foot width or span of floor or roof slab shall be framed.
§ 27-611. Pneumatically placed concrete
Construction methods shall conform to the applicable provisions and recommendations of reference standard RS 10-15.
§ 27-611.1. Conveying concrete by pumping methods
All classes and strengths of concrete may be conveyed by pumping methods. All materials and methods used shall conform to the rules promulgated by the commissioner for conveying concrete by pumping methods.
§ 27-612. Formwork, slip form construction, lift method construction, precast and prestressed construction
The provisions of subchapter nineteen of this chapter shall apply.
§ 27-613. Concrete utilizing preplaced aggregate
The use of concrete formed by the injection of grout into a mass of preplaced coarse aggregate will be permitted where it can be demonstrated by successful prototype installation that the proposed mix, materials, and method of placement will produce a concrete of the specified strength and free of areas or inclusions of uncemented aggregate.
(a) Prototypes. At least two prototypes, from either previous work or samples prepared for the proposed project shall be prepared. The forms shall be stripped, and a minimum of six cores recovered and tested to demonstrate the strength of the concrete produced by the proposed materials and methods of installation. In addition, the homogeneity of the prototypes shall be demonstrated by demolishing the prototypes.
(b) In-place concrete. The concrete, as finally placed in the work, shall be prepared using the same materials, mix, equipment, and procedures utilized to prepare the successful prototype installations.
(c) Inspection. All preparation and placement of structural concrete utilizing preplaced aggregates shall be subject to controlled inspection. Compression test specimens shall be prepared and tested as required for premixed concrete, except that the specimens shall be prepared under conditions that will simulate the conditions under which the concrete in the work is installed.
§ 27-613.1. Precast and prestressed concrete
The provisions of reference standard RS 10-3 shall apply.