NYC Administrative Code Title 27, Chapter 1 Building Code, part 9 of 17
§ 27-881 to § 27-971: 97 sections.
§ 27-881. Draft hoods
(a) All vented equipment, except dual oven type combination ranges, equipment with sealed combustion chambers, and units designed for power burners or forced venting, shall be installed with a draft hood or with a barometric damper.
(b) The draft hood supplied with, or forming a part of, vented equipment shall be installed in accordance with the requirements of the applicable standard in reference standard 15-2. The draft hood shall be located in the same room as the combustion air opening of the equipment.
§ 27-882. Chimneys for venting gas-fired equipment
When venting of gas-fired equipment is provided for by the use of chimneys, such chimneys shall be constructed in accordance with the requirements of this subchapter.
§ 27-883. Gas equipment connected to chimneys
Automatically controlled gas-fired equipment connected to a chimney that also serves equipment for the combustion of solid or liquid fuel shall be equipped with an automatic pilot. A gas-fired equipment vent connector and a chimney connector from equipment burning another fuel, located on the same floor, may be connected into the same chimney through separate openings, or may be connected through a single opening if joined by a suitable fitting located as close as practicable to the chimney. If two or more openings are provided into one chimney, they shall be at different levels.
§ 27-884. Types of gas vents
(a) Type B gas vents. Type B gas vents conforming to the requirements of section 27-855 of article one of this subchapter may be used to vent gas-fired equipment. Type B gas vents may be used for single-story or multi-story installations when they conform to the requirements of section 27-855 of article one of this subchapter and the gas equipment used in multi-story installations shall be accepted for such use. Type B gas vents shall be used to vent only listed gas appliances with draft hoods and other gas appliances listed for use with Type B gas vents. However, Type B gas vents shall not be used for venting:
(1) vented wall furnaces listed for use with Type BW gas vents only;
(2) incinerators;
(3) appliances which may be converted readily to the use of solid or liquid fuels;
(4) combination gas-oil burning appliances;
(5) appliances listed for use with chimneys only.
(b) Type B-W gas vents. Type B-W gas vents conforming to the requirements of section 27-855 of article one of this subchapter shall be used to vent gas-fired vented recessed heaters. Type B-W gas vents may be used with single-story or multi-story installations when they conform to the requirements of section 27-855 of article one of this subchapter and the gas equipment used in multi-story installations shall be accepted for such use. Type BW vents shall be used with listed vented gas wall furnaces having a capacity not greater than that of the listed Type BW gas vent.
(c) Single-wall metal vents. Single-wall metal vents may be used to vent gas-fired equipment and shall be constructed of not less than 16 oz. sheet copper, or No. 20 galvanized sheet gauge steel, or of other equivalent noncombustible corrosion-resistive material. Single-wall metal gas vents may pass through the roof or exterior wall to the outdoor air, but shall not pass through any attic or other concealed space nor through any intermediate floor construction.
(d) Connection to a common vent. Connection of gas-fired equipment on more than one floor level to a common vent, except as provided for in subdivisions (a) and (b) of this section, shall be prohibited.
(e) Ventilating hoods. Ventilating hoods and exhaust systems may be used to vent kitchen, laboratory, and commercial equipment.
§ 27-885. Labeling gas vents
Gas vents for use with gas-fired equipment, and which are not designed for use with solid or liquid fuel-fired equipment, shall be plainly and permanently identified by a metal label etched or embossed to read: "This gas vent is for equipment which burns gas only. Do not connect to incinerator or solid or liquid fuel-burning equipment." This label shall be attached to the vent at a point near where the gas vent system enters the wall, ceiling, or chimney.
§ 27-886. Special venting arrangements
(a) Equipment with sealed combustion chambers. The vent requirements contained in this subchapter do not apply to equipment having sealed combustion chambers and which are so constructed and installed that all air for combustion is derived from outside the space being heated and all flue gases are discharged by integral vent to the outdoors. Such equipment, having integral venting, shall be installed in accordance with the conditions of the applicable standard governing their use.
(b) Gas-vent exhausters and chimney exhausters. Gas-vent exhausters and chimney exhausters may be used with gas appliances in lieu of natural draft vents. Where an exhauster is used with gas-burning equipment requiring venting, provisions shall be made to prevent the flow of gas to the main burner in the event of failure of the exhaust system. A vent connector serving gas equipment vented by natural draft shall not be connected into the discharge side of a power exhauster.
(c) Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems may be used to vent gas equipment installed in commercial applications. When automatically operated equipment, such as water heaters, are vented through natural-draft ventilating hoods, dampers shall not be installed in the ventilating system. When the ventilating hood or exhaust system is equipped with a power-driven exhaust fan, the equipment control system shall be so interlocked as to permit equipment operation only when the power exhaust is in operation. When used, ventilating hoods shall be built and installed in accordance with the provisions of subchapter thirteen of this chapter.
§ 27-887. Installation requirements
(a) The gas vent connected to equipment with a single vent shall not be less than the size of the draft hood outlet, and in no case less than two inches in diameter.
(b) When more than one piece of equipment is connected to a gas vent, the area shall be not less than the area of the largest vent connector plus fifty percent of the areas of additional vent connectors or in accordance with the provisions of reference standard RS 15-1.
(c) Where two or more vent connectors enter a common vertical gas vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. Two or more items of gas equipment may be vented through a common vent connector or manifold located at the highest level consistent with available headroom or clearance to combustible material. The manifold, all junction fittings, and the common vent connector shall be of a size adequate for the combined volume of the vent gases.
(d) Gas vents shall be enclosed as provided in subdivision (c) of section 27-861 of article two of this subchapter.
§ 27-888. Gas vent height and locations
Gas vents shall extend at least two feet above the highest construction, such as a roof ridge, parapet wall, or penthouse, within ten feet of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond ten feet from the vent and up to and including the distance determined by the following formula:
D = 2 Ö A
where: D = Distance in ft., measured from the center of the vent outlet to the nearest edge of the construction.
A = Free area, in sq. in., of vent flue space.
Vents shall be subject to the following additional requirements:
(a) No gas vent shall terminate less than five feet in vertical height above the highest connected equipment draft hood outlet or flue collar.
(b) No type B-W gas vent serving a vented recessed heater shall terminate less than twelve feet in vertical height above the bottom of the heater.
(c) All gas vents shall terminate in an approved vent or cowl, which shall prevent down drafts and prevent rain and debris from entering the vent.
§ 27-889. Adjoining gas vents
(a) Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends above the top of a previously constructed gas vent within fifty feet, the owner of the new or altered building shall have the responsibility of altering such gas vents that have their outlets within fifty feet measured horizontally, of any part of the newly erected building. Such alterations shall be at the expense of the owner of the new or altered building and shall be accomplished by one of the following means or a combination thereof:
(1) Carry up such previously constructed vents from gas-fired equipment to the height required in section 27-888 of this article.
(2) Offset such gas vents to a distance of more than fifty feet from the new or altered building, provided that the new location of the outlet of the offset gas vent shall comply with the requirements of this subchapter.
(b) Protection of draft. After the alteration of a gas vent as described in subdivision (a) of this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical devices or equipment necessary to maintain the proper draft in the equipment.
(c) Written notification. The owner of the new or altered building shall notify the owner of the building affected in writing at least forty-five days before starting the work and request written consent to do such work. Such notice shall be accompanied by a written description or a plan showing how the proposed alterations are to be made.
(d) Approval. The method of correction shall be subject to the approval of the commissioner.
(e) Refusal of consent. If consent is not granted by the owner of the previously constructed or altered building to do the alteration work required by paragraph one of subdivision (a) of this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner, and the owner of the new or altered building has submitted plans that conform to the requirements of this section, he or she shall thereupon be released from any responsibility for the operation of his or her equipment and for any health hazard or nuisance that may occur as a result of the newly erected or modified building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Likewise, should such owner neglect to grant consent within forty-five days from the date of written request or fail to signify his or her refusal, he or she shall then assume all responsibilities as prescribed above.
(f) Procedures. It shall be the obligation of the owner of the new or altered building to:
(1) Schedule this work so as to create a minimum of disturbance to the occupants of the affected building.
(2) Provide such essential services as are normally supplied by the equipment while it is out of service.
(3) Where necessary, support such extended gas vents from his or her building or carry up such vents within his or her building.
(4) Provide for the maintenance, repair, and/or replacement of such alterations.
(5) Make such alterations of the same material as the original gas vent except where the owner of the vent affected shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural esthetics of the existing building.
(g) Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building.
(h) The commissioner may grant a variance in accordance with the provisions of section 27-107 of article one of subchapter one of this chapter.
§ 27-890. Support of gas vents
All portions of gas vents shall be adequately supported for the weight of the material used and for the applied loads on the vent.
§ 27-891. Prohibited termination
Gas vents extending through outside walls shall not terminate below eaves or parapets.
§ 27-892. Construction
Vent connectors for conversion burners without draft hoods, or other gas-fired equipment without draft hoods, shall be constructed of materials having resistance to corrosion and temperature not less than that of no. 24 galvanized sheet gauge steel.
(a) Vent connectors used for gas-fired equipment having draft hoods and for conversion burners having draft hoods, shall be constructed of type B gas vent material or materials having resistance to corrosion and temperature not less than that of no. 26 galvanized sheet gauge steel.
(b) The vent connector between the equipment and the vertical gas vent or chimney shall have the greatest possible initial rise consistent with the headroom available in the equipment area and with the required clearance to combustible material. The horizontal run of the vent connector shall be as short as possible and the equipment shall be located as near the gas vent or chimney as practicable. The maximum length of an uninsulated horizontal run of vent connector shall not exceed seventy-five percent of the height of the gas vent or chimney.
(c) No vent connector shall pass through floor or ceiling construction.
§ 27-893. Clearances
(a) Minimum clearance. Minimum clearances at vent connectors to combustible materials shall not be less than those listed in table 15-10.
(b) Reduced clearances. These clearances may be reduced when the combustible construction is protected as provided in table 15-11.
TABLE 15-10 Vent Connector Clearance for Gas-Fired Equipment
Equipment Minimum Distances from Combustible Materials (in.) Type B Gas Vent Material Other Than Type B Materials Boiler As required by Std. 6 Warm air furnace As required by Std. 6 Water heater As required by Std. 6 Room heater As required by Std. 6 Floor furnace As required by Std. 6 Conversion burner (with draft hood) 6 9 Equipment with draft hoods 6 9 Equipment without draft hoods Not Permitted 18
TABLE 15-11 Reduced Clearances for Vent Connectors with Specified Forms of Protection a
Specified Form of Protection b Reduced Clearances Where the Required Clearance with No Protection is: 18 in. 9 in. 6 in. (a) 1/4 in. asbestos millboard spaced out 1 in.c 12 6 3 (b) 28 gauge sheet metal on 1/4 in. asbestos millboard 12 4 2 (c) 28 gauge sheet metal spaced out 1 in.c 9 4 2 (d) 28 gauge sheet metal on 1/8 in. asbestos millboard spaced out 1 in.c 9 4 2 (e) 1 1/2 in. asbestos cement covering on heating appliance 18 9 6 (f) 1/4 in. asbestos millboard on 1 in. mineral fiber bats reinforced with wire mesh or equivalent 6 4 2 (g) 22 gauge sheet metal on 1 in. mineral fiber bats reinforced with wire or equivalent 3 2 2 (h) 1/4 in. asbestos cement board or 1/4 in. asbestos millboard 18 9 4 (i) 1/4 in. cellular asbestos 18 9 3
Notes for Table 15-11:
a Except for the protection described in (e) above, all clearances should be measured from the outer surface of the appliance to the combustible material disregarding any intervening protection applied to the combustible material.
b Applied to the combustible material unless otherwise specified and covering all surfaces within the distance specified as the required clearance with no protection. Thicknesses are minimum.
c Spacers shall be on noncombustible material.
§ 27-894. Thimbles
(a) When passing through combustible constructions, bent connectors constructed of type B gas vent material shall be installed so that the clearances required by the standard are maintained.
(b) Vent connections made of single-wall metal pipe shall not pass through any combustible walls or partitions unless they are guarded at the point of passage by ventilated metal thimbles not smaller than the following:
(1) For equipment conforming to standards – four inches larger in diameter than the vent connector.
(2) For equipment having draft hoods – six inches larger in diameter than the vent connector.
(3) For equipment without draft hoods – twelve inches larger in diameter than the vent connector.
§ 27-895. Size of connectors
The vent connector shall not be smaller than the size of the flue collar or the draft hood outlet of the gas-fired equipment. Where a single item of equipment has more than one draft hood outlet, the vent connector shall equal the combined area of the draft hood outlets for which it acts as a common connector to the gas vent or chimney.
§ 27-896. Scope
The provisions of this subchapter shall establish and control the minimum requirements for the design, installation, alteration, repair, and maintenance of plumbing systems, including gas piping, sanitary and storm drainage, industrial and special wastes, sanitary facilities, water supplies and storm water and sewage disposal, except where specific exemptions are made in the code. All installation, alteration, repair, and maintenance work shall be performed by or under the direct supervision of a licensed master plumber, except as follows:
(a) Minor alterations and ordinary repairs as defined and delimited in article five of subchapter one of this chapter.
(b) Installation of gas service piping and gas meter piping may be performed by a utility corporation that is subject to the jurisdiction of the public service commission, provided that the corporation maintains and services such piping.
(c) Emergency repairs to alleviate hazardous conditions in gas distribution piping may be performed by a utility corporation which is subject to the jurisdiction of the public service commission, subject to the requirements of section 27-176 of article fifteen of subchapter one of this chapter.
§ 27-897. Standards
The provisions of reference standard RS-16 shall be a part of this subchapter.
§ 27-898. Definitions
For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.
§ 27-899. Plans
For the requirements governing the filing of plans and the work to be shown on plans, see subchapter one of this chapter.
§ 27-900. Permits
For the requirements governing application for building permits and plumbing permits, see subchapter one of this chapter.
§ 27-901. General requirements
Plumbing and gas piping shall be designed and installed so as to satisfy the following conditions and the requirements of reference standard RS-16: (a) All occupied premises shall have potable water. Every building intended for human habitation, occupancy, or use shall be provided with a supply of potable water.
(b) Sufficient water required. Plumbing fixtures, devices, and appurtenances shall be supplied with water in sufficient volume and at pressures adequate to enable them to function properly. The pipes conveying the water shall be of sufficient size to provide the water required without undue pressure reduction and without undue noise under all normal conditions of use.
(c) Water conservation. Plumbing shall be designed and adjusted to use the minimum quantity of water consistent with proper performance and cleansing of the fixture of plumbing appurtenance.
(d) Safeguarding against explosion. Devices for heating and storing water shall be designed, installed, and maintained to guard against rupture of the containing vessel through overheating.
(e) Connection to public water supply systems and to sanitary or combined sewer systems.
(1) GENERAL.
a. The water distribution system and system for conveying sewage from any building in which plumbing fixtures are installed shall be connected, respectively, to a public water main and a sanitary or combined sewer if either or both are available and, regarding the sewer, if the department determines that connection thereto is feasible. The department shall determine that connection is feasible if:
1. the sewer is of adequate capacity to receive all sewage flowing from the building;
2. the sewer is in adequate physical condition to receive such sewage;
3. no physical obstacles exist, between the boundaries of the lot or tract of land on which the building is located and the sewer, which would make connection to the sewer impracticable;
4. the elevation of the sewer in relation to the lot or tract of land on which the building is located is such that conveyance of the sewage from the building to the sewer is not impracticable;
5. the sewer is located in the same drainage area as all or most of the lot or tract of land on which the building is located; and
6. no other factor reasonably related to the conveyance of sewage from the building to the sewer would make such connection impracticable or undesirable as a proper means of sewage disposal.
b. Where a public water main is not available, an individual potable water supply shall be provided, and where neither a sanitary nor a combined sewer is available to which the department determines that connection is feasible, a private sewer or private sewage disposal system shall be provided. All such private systems shall be provided subject to the approval of the commissioner and of any other agency or agencies having jurisdiction, and constructed in accordance with the requirements of reference standard RS-16 and, with respect to the construction of individual on site private sewage disposal systems, in accordance with the specifications and standards prescribed by the commissioner, in consultation with the commissioner of environmental protection, pursuant to section six hundred forty three of the charter.
c. Extensions of public sewers and water mains shall be made in accordance with the regulations of the department of environmental protection.
(2) SYSTEMS AVAILABLE.
a. A public water main, and a sanitary or combined sewer for the purpose of conveying sewage, shall be deemed available to a building in which plumbing fixtures are installed, except to a one-or two-family dwelling, if a property line of such building is within five hundred feet (measured along a street, alley, or right-of-way) of the public water supply system or the sewer. The connection shall be made in accordance with the applicable standards of the department of environmental protection.
b. A public water supply system, and a sanitary or combined sewer for the purpose of conveying sewage, shall be deemed available to a one- and two-family dwelling if a property line of such dwelling is within one hundred feet (measured along a street, alley, or right-of-way) of the public water supply system or the sewer. The connection shall be made in accordance with the applicable standards of the department of environmental protection, provided, however, that such one- and two-family dwelling need not connect directly to the sewer if the common elements of an internal private drain are located in a dedicated, unobstructed right-of-way that extends to the sewer with a minimum width of ten feet located entirely outside of the building footprint and outside of all overhangs and projections that are less than fourteen feet in height above grade.
c. Where two or more one-or two-family dwellings are to be constructed on a tract of land, or where a substantial improvement of any other type of building or buildings is contemplated on a tract of land, the public water supply system and/or the sanitary or combined sewer may be declared available thereto by the agencies having jurisdiction thereon even though the distances specified in subparagraphs a and b of this paragraph are exceeded.
(f) Well water systems. No well or individual water supply may be installed for any purpose without the approval of the commissioner and of the department of health and mental hygiene and the department of environmental protection.
(g) Design and maintenance of system for conveying sewage from building. The system for conveying sewage from the building shall be designed, constructed and maintained to guard against fouling, deposit of solids, and clogging, and shall be provided with adequate cleanouts so arranged that the pipes may be readily cleaned.
(h) Exclusion of certain substances from the plumbing system.
(1) DETRIMENTAL OR DANGEROUS MATERIAL. No person shall deposit, by any means, any of the following into the building drainage system or sewer: ashes, cinders, rags, flammable, poisonous, or explosive liquids, gases, oils, grease, or any other material that could obstruct, damage, or overload such system, or that could interfere with the normal operation of the sewage treatment processes.
(2) INDUSTRIAL WASTES. Wastes from hospitals, chemical plants, laundries, abattoirs, or any other industrial wastes that could be detrimental to the public sewer or public health, shall be treated before such wastes are discharged into the public sewer. At the time of the filing of plumbing plans for any hospital, chemical plant, laundry, abattoir, or any other industrial structure, a statement shall be filed with the commissioner indicating the substances, ingredients, or matter, that will be discharged into the sewer, together with written approval of the department of environmental protection for the method of treatment of said substance, ingredient or matter, before it is discharged into the public sewer.
(i) Prevention of contamination. Plumbing fixtures, devices, and appliances shall be provided with adequate protection to prevent contamination of food, water, sterile goods, and similar materials by backflow of sewage. The fixture, device, or appliance shall be connected indirectly with the building drainage system when necessary.
(j) Drainage below street level. The drainage of all sanitary and storm water below the crown level of the street sewer, or below a level where backflow from the street sewer is possible, shall be conveyed to a sewage ejector and/or sump through a system of subhouse drains, and lifted into the street sewer or disposal system.
(k) Disposal of storm water. Storm water falling or coming to rest on property on which new buildings or substantial horizontal enlargements are to be constructed, and on all streets and other paved areas constructed or altered in connection with the construction of such new buildings or substantial horizontal enlargements, shall be disposed of in accordance with the requirements of reference standard RS-16 and the rules and regulations of the department of environmental protection. No person providing a system for disposing of storm water, as required by this subdivision, shall in any way alter, relocate or affect any existing drainage system on the property, except in accordance with the provisions of section 19-137 of title nineteen of the administrative code. Except as otherwise permitted by this code, no person shall perform land contour work, as defined in section 19-137 of this code, which work causes storm water to flow across sidewalks or onto an adjacent property. For purposes of this subdivision, the term "substantial horizontal enlargement" shall have the meaning given such term in subdivision (a) of section P110.2 of reference standard RS-16.
(l) Required plumbing fixtures. Every dwelling unit in buildings classified in occupancy groups J-2 and J-3 shall have at least one water closet, one lavatory, one kitchen-type sink, and one bathtub or shower. All other buildings shall be equipped with the number and types of plumbing fixtures required by reference standard RS-16; provided, however, that the minimum required number of water closets in any arena, bar, concert hall, convention hall, motion picture theatre, public dance hall, stadium, or theatre shall be in accordance with article eight of this subchapter.
(m) Smooth surfaces required. Plumbing fixtures shall be made of smooth, nonabsorbent material and shall be free from fouling surfaces.
(n) Location of fixtures.
(1) LIGHT AND VENTILATION. For light and ventilation requirements of rooms or spaces containing plumbing fixtures, see subchapter twelve of this chapter.
(2) LOCATION. Piping, fixtures, or equipment shall be located so as not to interfere with the normal operation of windows, or doors and other exit openings.
(3) ACCESSIBILITY. Plumbing fixtures shall be located so that they are readily accessible to the users.
(o) Liquid-seal traps required. Each fixture directly connected to the drainage system shall be equipped with a liquid-seal trap, except as otherwise provided in this subchapter. The drainage system shall be designed to provide adequate air circulation in all pipes with no danger of siphonage, aspiration, or forcing of trap seals under conditions of ordinary use.
(p) Exhausting of foul air to outside. Each vent terminal shall extend to the outdoor air and be located and installed so as to minimize the possibility of clogging and the return of foul air to the building.
(q) Materials and workmanship. All materials and equipment used in the plumbing and gas systems shall be free from defects, and shall be designed, constructed, and installed so as to give satisfactory service for their expected life.
(r) Condemned equipment. Any plumbing materials or equipment condemned by the commissioner because of wear, damage, defects, or sanitary hazards shall not be used or re-used for plumbing purposes.
(s) Prevention of sewer flooding. Where a plumbing drainage system is subject to backflow of sewage from the public sewer, suitable provision shall be made to prevent its overflow in the building.
(t) Test of plumbing system. The plumbing system shall be subjected to such tests as will readily disclose all leaks and defects in the work or in the material used.
(u) Proper maintenance. Plumbing systems shall be maintained in a safe and serviceable condition from the standpoint of both operation and health.
(v) Protection of ground and surface water. Sewage or other waste shall not be discharged into surface or subsurface water unless it has been discharged by a method subject to the approval of the commissioner and of the department of health and mental hygiene and the department of environmental protection.
(w) Weather protection. Water service piping shall be installed at least four feet below exterior grade, and building house sewers shall be installed at least three feet below exterior grade. Plumbing piping in exterior building walls shall be adequately protected against freezing by insulation or heat, or by both.
(x) Structural safety. The structural safety of a building shall not be affected or impaired in any way as a result of the installation, alteration, renovation, or replacement of a plumbing system or any part thereof. See subchapters nine, ten, eleven and nineteen of this chapter.
(y) Strains and stresses in pipes. Piping shall be installed so as to prevent strains and stresses that would exceed the structural limitations of the pipe and so as to prevent deflection or deformation that would cause the system to malfunction. Provision shall be made for expansion and contraction and for structural settlement that might affect the piping.
(z) Installation limitations.
(1) ELEVATOR SHAFTS. No piping shall be installed in any elevator or counterweight hoistway.
(2) FIRE RATED CONSTRUCTION. No plumbing or gas piping shall be installed in any construction required to have a fire resistance rating except in accordance with the provisions of subchapter five of this chapter.
(3) STAIR ENCLOSURES. No piping of any kind, with the exception of piping required or permitted under subchapter seventeen of this chapter, shall be permitted within a stair enclosure.
(aa) Special flood hazard restrictions. Within special flood areas and below the regulatory flood datum as described in article ten of subchapter four of this chapter, plumbing installations shall comply with the applicable provisions of reference standard RS 4-5.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1993/104, L.L. 1996/065, and L.L. 2005/057.
§ 27-902. Use of nonconforming material or equipment
(a) No person shall use or install any new or used plumbing material or equipment, unless it complies with the requirements set forth in this subchapter and reference standard RS-16.
(b) No person shall use any portable equipment that utilizes mercury to test the pressure of gas piping, drainage or vent systems.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2001/017.
§ 27-903. Fire protection
Where pipes pass through construction required to have a fire-resistance rating, they shall comply with the requirement of section 27-343 of article five of subchapter five of this chapter.
§ 27-904. Establishing gas supply
It shall be unlawful for any utility company to supply gas to a building, place or premises in which new meters other than replacement are required until a certificate of approval of gas installation from the department of buildings is filed with such utility company. When new gas service piping has been installed it shall be locked-off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility owned) and gas distribution piping has been inspected and certified as required by the department of buildings as being ready for service.
§ 27-905. Alterations to gas piping systems
When alterations, extensions or repairs to existing gas meter piping or gas distribution piping requires the shut-off of gas flow to a building, the utility shall be notified by the owner or his or her authorized representative.
§ 27-906. Public water supply
(a) Required capacity. Where the required capacity of potable water supply is available from street water mains at the site, every building shall be supplied from such mains.
(b) Power pumps. When power pumps are required in the water supply system of a building, they shall take their supply from the street water mains in the manner prescribed in reference standard RS-16.
§ 27-907. Private water supply
Every private source of potable water supply, other than a water supply company franchised by the city of New York shall be subject to the approval of the commissioner; and every private source of nonpotable water supply shall be submitted to the commissioner for approval and recording.
§ 27-908. Cross-connection of supplies and identification
(a) Cross-connection. No person shall connect water piping supplied directly from street water mains to other sources; and no cross-connection shall be made between the potable water distribution system and any portion of waste or soil systems, or between the potable water distribution system and fixtures or devices that may contaminate, pollute, or otherwise render the water nonpotable.
(b) Identification. Water supply systems not approved as potable shall be identified at each outlet with a warning sign stating that the water is unfit, and its use prohibited, for drinking purposes. Piping carrying potable water shall be identified and distinguished from water piping carrying nonpotable water by distinctive painting or markings as prescribed in reference standard RS-16.
(c) Construction. The construction of water supply systems shall be in accordance with the requirements of reference standard RS-16.
§ 27-909. Permits
In addition to the permits required under provisions of subchapter one of this chapter, the following permits shall also be required.
(a) Permits for the installation of the building house sewer from the street line to, and including, the spur connection at the street sewer shall be obtained from the department of environmental protection, except that, in conjunction with the issuance of a permit for the construction or alteration of a structure within the curbline, the commissioner may issue a permit for connection with a sewer or drain.
(b) Permits for sidewalk and street openings shall be obtained from the department of transportation.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1996/065.
§ 27-910. Individual sewage systems
Where public sewers are deemed not available according to subdivision (e) of section 27-901 of article one of this subchapter, an individual on site private sewage disposal system shall be installed in accordance with the requirements of this subchapter. When public sewers are made available, the individual on site private sewage disposal system shall be abandoned in a manner prescribed by the commissioner, and the building house sewer shall be connected to the available public sewer within six months of the date of notification that the sewer has been accepted to receive flow by the agency or agencies having jurisdiction.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1996/065.
§ 27-911. Construction
The construction of drainage systems shall be in accordance with the requirements of reference standard RS-16.
§ 27-912. Requirements
Hospital and institutional plumbing shall be installed in accordance with all of the applicable requirements for plumbing and gas piping of this subchapter and in accordance with the specific modifications of reference standard RS-16.
§ 27-913. Requirements
All plumbing for swimming pools, including display pools and fountains, shall be installed in accordance with the requirements of this subchapter, the requirements of reference standard RS-16, and the requirements of the New York city health code.
§ 27-914. Construction
For requirements covering the general construction of swimming pools, the provisions of article sixteen of subchapter seven of this chapter shall apply.
§ 27-915. Operation
No swimming pool regulated by the provisions of this code shall be operated without a permit from the department of health and mental hygiene.
§ 27-916. General
When alterations are made requiring the addition of two or more plumbing fixtures in an existing building, or when a building is remodeled for an extension in size or change in use in which plumbing, drainage, or gas piping work is involved, all the new work shall be made to conform to all the applicable sanitary requirements of this code and the affected portions of the system made adequate for the added load.
§ 27-917. Existing soil and vent stacks
(a) When a new building is erected higher than an existing building, no operable windows or other wall openings shall be located closer than ten feet to an existing stack vent or vent stack on the lower building. Wherever necessary, the owner of the new building shall at his or her own expense and with the approval of the adjoining owner, offset the stack vent or vent stack to a distance ten feet or more from such windows or wall opening, or shall extend such stack vents or vent stacks to a height of at least three feet above the topmost opening.
(b) When the existing adjoining building is higher than the new building, all new soil, waste, or vent stacks of the new building shall be located at least ten feet from the common lot line, or shall be carried to a level above the higher existing roof, adequately supported and with the consent of the owners of both the new and existing structures.
§ 27-918. Existing gas meter rooms
Existing gas meter rooms shall comply with the provisions of section P-115.5(c) of the reference standard RS-16 no later than December first, nineteen hundred seventy-two.
§ 27-919. Inspection
Every new plumbing and gas piping system and every part of an existing system that has been altered, except for ordinary repairs, shall be inspected and tested to determine compliance with code requirements except that the commissioner may promulgate rules authorizing a certification from a master plumber for minor work that was performed in accordance with applicable codes in lieu of the two day inspection notification requirement of section 27-920 of this article and the inspection reporting requirements of subdivision a of section 27-922 of this article. In no event shall such certification be allowed for any new installation, or any alteration to an existing as piping system.
§ 27-920. Notification
The holder of the plumbing permit shall give at least two days prior written notice to the commissioner that the plumbing work covered by the permit is ready for inspections and test.
§ 27-921. Testing of plumbing and gas piping systems
(a) New, altered, extended, or repaired systems. Every new plumbing and gas piping system and every part of an existing system that has been altered or repaired except for minor alterations and ordinary repairs, shall be tested as hereinafter prescribed to disclose leaks and defects. However, testing may be waived in the following cases:
(1) In any case that does not involve replacement, alteration, or relocation of any water supply, drainage, or vent piping.
(2) In any case where plumbing equipment may be set up temporarily for exhibition purposes.
(b) Representation at test.
(1) Tests required by section 27-922 of this article shall be conducted in the presence of the commissioner or an authorized plumbing inspector of the department.
(2) The commissioner may also authorize such test to be witnessed by architects, engineers, master plumbers or representatives of utility companies, each of whom must be acceptable to the commissioner. Persons performing this function shall have had at least five (5) years experience in inspection and testing of gas piping systems, or hold a current master plumbers license. Such tests may be conducted without any verifying inspection or tests by members of the department, provided that verified statements and supporting inspectional and test reports are filed with the department within one working day of such tests.
(c) Exposure of work. If any plumbing system or part thereof is enclosed before it has been inspected, tested, and accepted as prescribed in this subchapter, such system or part thereof shall be uncovered upon the direction of the commissioner.
(d) Retesting. If, upon inspection and tests, any of the work fails to meet the test requirements, the necessary corrections shall be made before any reinspections or retests are conducted.
§ 27-922. Requirements
(a) Drainage and vent systems.
(1) Rough Plumbing. Except for outside leaders and perforated or open jointed drain tile (subsoil drains), the piping of plumbing drainage and venting systems shall be verified as to materials and shall be tested upon completion of the rough piping installation and proven to be watertight. The commissioner may require the removal of any cleanout plugs to ascertain that the prescribed pressure has been reached in all parts of the system.
a. Water test. A water test shall be applied to the drainage system either in its entirety or in sections after rough piping has been installed. If applied to the entire system, all openings in the piping, except the highest opening, shall be tightly closed and the system filled with water to the point of overflow. If the system is tested in sections, each opening, except the highest opening of the section under test, shall be tightly plugged and each section filled with water. No section shall be tested with less than a ten foot head of water. In testing successive sections, at least the upper ten feet of the following section shall be tested, so that no joint or pipe in the building (except the uppermost ten feet of the system) shall have been submitted to a test of less than a ten foot head of water. The water shall be kept in the system or in the portion under test for at least fifteen minutes before inspection starts; the system shall then be tight at all points.
b. Air test. An air test may be used only when permission for this type of test is obtained from the commissioner. The air test shall be made by attaching an air compressor testing apparatus to any suitable opening and, after closing all other inlets and outlets of the system, forcing air into the system until there is a uniform gauge pressure of five psi. This pressure shall be held, without introducing additional air, for a period of at least fifteen minutes.
(2) Finished Plumbing. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be verified as to materials, and shall be tested and proven gastight by either a smoke test or a peppermint test.
a. Smoke test. The smoke test shall be made by filling all traps with water and then introducing into the entire system a pungent, thick smoke produced by one or more smoke machines. When the smoke appears at stack openings on the roof, these openings shall be closed and a pressure equivalent to a one inch water column shall be maintained for the period of the inspection.
b. Peppermint test. The peppermint test shall be made by introducing two ounces of oil of peppermint into the roof vent terminal of every line or stack to be tested. The oil of peppermint shall be followed at once by ten quarts of hot water (one hundred sixty degrees Fahrenheit or higher), whereupon all roof vent terminals shall be sealed. The detection of the odor of peppermint at any trap or other point in the system shall determine the location of any leaks. Persons who have come in contact with the oil of peppermint shall be excluded from the test area.
(b) Building house sewer. The building house sewer shall be tested by inserting a test plug at the point of connection with the street sewer before such connection is made. The building house sewer shall then be filled with water under a head of at least ten feet. The water level at the top of the test head of water shall not drop for at least fifteen minutes.
(c) Water systems. Upon completion of a section of a water system or of the entire water system, the completed section or system shall be verified as to materials, and shall be tested and proven tight under a water pressure at least twenty-five percent greater than the working pressure under which it is to be used. The water used for tests shall be obtained from a potable source of supply.
(d) Gas piping systems. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to materials, and tested and proven tight as follows:
(1) Gas distribution piping:
a. Distribution pressures up to and including one-half psig. The completed piping is to be tested with a non-mercury gauge at a pressure of three pounds per square inch gauge (psig) for a minimum of thirty minutes.
b. Distribution pressures over one-half psig through three psig. The completed piping is to be tested at fifty psig for a minimum of thirty minutes.
c. Distribution pressures over three psig through fifteen psig. The completed piping is to be tested at one hundred psig for a minimum of one hour.
d. Distribution pressures above fifteen psig. The completed piping is to be tested to twice the maximum allowable operating pressure, but not less than one hundred psig, for a minimum of one hour.
(2) Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in paragraph one of this subdivision, or if different, the piping shall be certified by the local utility as being tested in compliance with their requirements.
(3) Notwithstanding the above, all coded or wrapped pipe shall be pressure tested at a minimum of ninety psig. For testing, the piping shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. Fresh water may be used as the test medium only where the required test pressure exceeds one hundred psig.
(4) The commissioner shall publish a list of non-mercury gauges certified by a nationally recognized testing lab or promulgate rules with standards for non-mercury gauges within one hundred and twenty days of the effective date of this paragraph.
(e) Other piping systems. All other piping systems shall be tested in accordance with the requirements prescribed in reference standard RS-16.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2001/017.
Title 27, Chapter 1, Subchapter 16, Article 8. Minimum Water Closets In Places of Public Assembly
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2005/057.
§ 27-922.1. Definitions
For the purposes of this article only, the following definitions shall apply in conjunction with the definitions found in sections 27-232:
a. "Convention hall" shall mean any building or space utilized, during the major period of occupancy, for the holding of exhibitions or conventions.
b. "Specified place of public assembly" shall mean any arena, bar, as such term is defined in section 17-502 of this code, concert hall, convention hall, motion picture theatre, public dance hall, stadium, or theatre open to the general public.
c. "Public dance hall" shall mean any building or space utilized, during the major period of occupancy, for dancing, and where alcoholic beverages are permitted to be served.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2005/057.
§ 27-922.2. Applicability
a. Notwithstanding any other provision of this code, the provisions of this article shall apply to any bathroom open to the general public in the following:
(1) Any specified place of public assembly in a new building or space;
(2) Any specified place of public assembly in an existing building or space that has been altered where the alteration of the building or space results in a change in the occupancy group classification of the building or space under the provisions of subchapter three of this chapter;
(3) Any specified place of public assembly that is altered where the cost of making alterations in any twelve-month period shall exceed thirty percent of the value of such building or space, provided such bathroom is part of the work area of such alterations; and
(4) Any specified place of public assembly that is altered where the cost of making alterations in any twelve-month period shall exceed fifty percent of the value of such building or space.
b. The cost of making alterations and the value of the building or space shall be determined in accordance with section 27-119 of this chapter.
c. This article shall not apply to any building or space classified in occupancy group G or H, or any space within any building classified in occupancy group G or H, or any building or space owned by any school or hospital and used for any educational or health purpose.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2005/057.
§ 27-922.3. Minimum requirements
a. The number of water closets required for any specified place of public assembly shall be as listed in Table 16-1.
TABLE 16-1
Number of Persons Number of Water Closets for Men Number of Water Closets for Women 1-150a 1 2 151-300 2 4 301-450 3 6
Note for Table 16-1:
a The requirements for the number of water closets for occupancy by 150 persons or less shall not apply to bars except that there shall be at least one water closet for men and at least one water closet for women or an equivalent number of unisex bathrooms. For occupancy by more than 450 persons, there shall be one water closet for men and two water closets for women for each additional 300 persons. The population used to determine the number of water closets required shall be based on the number of people to occupy the space; provided, however, that in no case shall the population be deemed less than that determined by allowing one hundred and twenty-five square feet of floor area per person.
b. Urinals may be provided in bathrooms in lieu of water closets but the number shall not exceed fifty percent of the required number of water closets.
c. Unisex bathrooms may be provided in lieu of separate bathrooms for men and women.
d. This section is only intended to change the ratio of men's and women's water closets required under title 27 of this code as provided herein, and is not intended to require more than one water closet per fifty persons for occupancy by 450 persons or less, or more than one water closet per one hundred persons for occupancy by more than 450 persons.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2005/057.
§ 27-922.4. Waivers
a. The commissioner may waive the requirements of this article for the alteration of existing buildings; provided, however, that such waiver is based upon a specific finding that strict compliance with these requirements:
(1) would create an undue economic burden; or
(2) would not achieve its intended objective; or
(3) would be physically or legally impossible; or
(4) would be unnecessary in light of alternatives which insure the achievement of the intended objective or which achieve the intended objective more efficiently, effectively or economically; or
(5) would entail a change so slight as to produce a negligible additional benefit consonant with the purposes of this article.
b. Each application for a waiver under subdivision a of this section shall be made to the commissioner in writing, setting forth each requirement sought to be waived and the specific reason or reasons therefor. The commissioner shall determine, under all of the circumstances presented by such application, which of such requirements may appropriately be waived. The commissioner shall render such determination in a writing which shall set forth in detail the commissioner's findings and conclusions with respect to each requirement sought to be waived. A copy of such written determination shall be forwarded to the applicant. Such written determination shall be filed with the department and shall be available for public inspection.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2005/057.
§ 27-923. Scope
The provisions of this subchapter shall establish and control the minimum requirements for the design and installation of standpipe, sprinkler, fire alarm, and fire detection systems except for fire alarm systems in factory and mercantile buildings and where specific exemption is made in this code. Alterations or additions to existing systems shall comply with the requirements of this subchapter regardless of magnitude or cost.
§ 27-924. Standards
The provisions of reference standard RS-17 shall be part of this subchapter.
§ 27-925. Definitions
For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.
§ 27-926. Plans
For the requirements governing the filing of plans and the work to be shown on plans, see subchapter one of this chapter.
§ 27-927. Permits
For the requirements governing equipment work permits, equipment use permits, see subchapter one of this chapter.
§ 27-928. General requirements
All systems of standpipes, sprinklers, fire alarms, and fire detectors and all component devices thereof, as required by this subchapter specifically and by subchapters four, five, seven and eight of this chapter shall be installed in accordance with the provisions of this subchapter.
§ 27-929. Retroactive requirements
The provisions of this subchapter shall apply retroactively for the specific occupancies indicated in subdivisions (j) and (s) of section 27-954 and paragraph ten of subdivision (a) of section 27-968 of this subchapter. An application noting compliance shall be required to be filed on or before April thirteenth, nineteen hundred seventy-nine; and installation shall be required on or before January thirteenth, nineteen hundred eighty, except as otherwise provided in this code.
(a) The provisions of this article shall apply retroactively for the specific occupancies and spaces indicated in subdivisions (v), (w) and (y) of section 27-954 and subdivision (j) of section 27-972. Installation of all systems required by these sections shall be completed on or before April first, nineteen hundred eighty-seven.
(b) Notwithstanding the provisions in subdivision a of this section, an application for a permit and approval of plans for the installation of fire alarm and signal systems as required under the provisions of article five of this subchapter in buildings classified in occupancy group J-1 shall be filed with the department on or before June thirtieth, nineteen hundred eighty-seven and such installation shall be completed on or before December thirty-first, nineteen hundred eighty-seven.
(c) Notwithstanding any other provision of this subchapter, the requirement to install a system of automatic sprinklers shall apply retroactively to any space in a basement, cellar or other location below grade subject to the provisions of subdivision aa of section 27-954 of this code. Installation of such system of automatic sprinklers shall be completed on or before April thirtieth, two thousand four.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2002/026.
§ 27-929.1. Retroactive requirements for office buildings one hundred feet or more in height
(a) General requirements.
(1) Notwithstanding any other provision of this subchapter, all office buildings one hundred feet or more in height and buildings classified in occupancy group E one hundred feet or more in height in existence on the effective date of this subdivision shall have a full system of automatic sprinklers installed in accordance with this subchapter. Reports relating to the installation of such sprinkler systems shall be filed in accordance with subdivision (b) of section 27-228.5 of this code and installation of such sprinkler systems shall be completed on or before July 1, 2019 or, if applicable, on or before a date specified by the commissioner pursuant to paragraph (2) of subdivision (b) of section 27-228.5 of this code.
(2) Exception. Where an owner of a building or portion thereof subject to such retroactive requirement demonstrates to the satisfaction of the commissioner that the installation of sprinklers in a particular, limited portion of such building is not practicable, either due to structural conditions or because of designation as an interior landmark by the New York city landmarks preservation commission, the commissioner may waive such limited portions from the requirements of this section but may require additional fire safety measures to protect the health, safety and welfare of the public.
(3) Application to buildings with a full system of automatic sprinklers. The provisions of this subdivision shall not apply to buildings in existence on the effective date of this subdivision in which a full system of automatic sprinklers was installed or required to be installed pursuant to any other provision of law. Nothing in this subdivision shall be construed to limit the applicability of any other provision of this code requiring sprinklers in the buildings referred to herein.
(b) Converted buildings. Notwithstanding the foregoing provisions, on and after the effective date of this subdivision, no building one hundred feet or more in height shall be converted to an office building or to a building classified in occupancy group E, whether or not application for such conversion is required to be filed with the department, unless a full system of automatic sprinklers is installed in such building in accordance with this subchapter prior to such conversion.
§ 27-930. Existing standpipes
Standpipe systems existing on December sixth, nineteen hundred sixty-eight shall not be required to be altered to conform to the provisions of this subchapter, except as follows:
(a) The existing installation shall meet the following minimum requirements:
(1) WATER SUPPLIES. There shall be a reserve of at least twenty-five hundred gallons of water in a gravity or pressure tank for exclusive use of the standpipe; or there shall be a direct connection to a city main meeting the requirements of section 27-945 of article three of this subchapter.
(2) GRAVITY TANKS. The gravity tank or tanks shall be filled by direct city water connection or by an automatic fill pump at a rate of at least forty-five gpm; and the bottom of the tank shall be located at least eleven feet six inches above the highest hose outlet under the main roof.
(3) HOSE AND HOSE VALVES. Hose and hose valves shall be in good serviceable condition. Hose valve wheel handles shall be within six feet six inches of the floors or stair landings or the wheel handle may be within two feet horizontally from a stair tread and no more than six feet six inches vertically above the tread. Such hose may be omitted from hose racks in existing buildings in occupancy group J-2 provided that the provisions of paragraph five of subdivision (c) of section 27-942 of article three of this subchapter are complied with.
(4) FIRE DEPARTMENT CONNECTIONS. There shall be a three inch by three inch siamese hose connection with approved caps, painted red. The word "Standpipe" shall be cast in the body of the siamese connection or on metal plates that are secured to the riser or to the face of the building behind the siamese connection.
(5) NOZZLES. A five-eighths inch smooth bore nozzle with two and one-half inch hose shall be provided where the hydrostatic pressure at the hose valve is less than ten psig.
(6) PROTECTION FROM FREEZING. All parts of the standpipe system that are exposed to freezing shall be protected in accordance with the requirements of subdivision (a) of section 27-949 of article three of this subchapter.
(7) PRESSURE REDUCING VALVES. Pressure reducing valves shall be provided as required by section 27-944 of article three of this subchapter.
(8) DRIP VALVES. Drip valves shall be provided between the siamese connection and the check valve.
(b) When the building requires additional standpipe protection because of extension in height or in area, or the occupancy is changed to a use requiring additional protection, the new or altered part of the system shall comply with this subchapter.
§ 27-931. Existing sprinklers
(a) Required sprinklers. Sprinkler systems and devices existing on December sixth, nineteen hundred sixty-eight shall not be required to be altered to conform to the provisions of this subchapter, except that when additional protection is required for a change in occupancy or for a building addition, the new or altered part of the system shall comply with this subchapter. Sprinklers in any extension or alteration shall be connected to, or extended from, the existing system or a separate water supply as provided in section 27-962 of article four of this subchapter. Additional heads shall not be connected to existing undersized piping.
(b) Voluntary sprinklers. Sprinkler systems and devices existing on December sixth, nineteen hundred sixty-eight, but which are not required by this code, need not conform to the provisions of this subchapter, except that when a siamese hose connection is installed in the system, the siamese connection shall be installed and the entire system pressure tested as required by this subchapter.
§ 27-932. When required
(a) Wet standpipe systems shall be installed:
(1) In all buildings or portions thereof exceeding six stories or seventy-five feet in height, except that open parking structures shall not require installation of a wet standpipe system unless they exceed ten parking levels or seventy-five feet in height.
(2) In all portions of buildings two or more stories in height that have a floor area of ten thousand square feet or more on any floor.
(b) Where standpipes are required by the height and area limitations of subdivision (a) of this section, a non-automatic or automatic dry standpipe system may be installed in lieu of the wet standpipe in all buildings classified in occupancy group G not over six stories or seventy-five feet in height. A dry standpipe system shall be installed in all open parking structures which exceed three parking levels and contain not more than ten parking levels.
(c) A standpipe system shall be installed in all buildings exceeding three stories in height that have an area exceeding seven thousand five hundred square feet on any floor and where a standpipe system is not otherwise required by the provisions of this subchapter. A nonautomatic or automatic dry system may be used in lieu of the wet standpipe.
(d) The following buildings shall be exempt from the provisions of subdivisions (a), (b) and (c) of this section:
(1) Buildings classified in occupancy groups F, G, H, and J that do not exceed two stories or thirty feet in height and an area of twenty thousand square feet on any floor and are provided with hand or portable fire extinguishers as required by the fire department.
(2) Buildings classified in occupancy groups E, F, G, H, and J that require a wet standpipe as provided in paragraph two of subdivision (a) and subdivision (c) of this section but not exceeding six stories or seventy-five feet in height and that are equipped throughout with an automatic wet or dry sprinkler system connected to a central supervisory station, and such system complies with the provision of this subchapter.
§ 27-933. Yard hydrant systems required
Outdoor amusement and exhibition places, oil storage plants, lumber yards, trailer camps, industrial parks, and similar occupancies shall have yard hydrants installed so that the entire area may be reached by two hundred fifty feet of hose from a yard hydrant or a street hydrant. Single hydrant connection shall be at least in six inch I.P.S. Such hydrants shall be directly connected with city water main or private water main, or supplied from gravity tanks or pressure tanks, as provided in this subchapter.
(a) Where the area of such enclosure is more than forty thousand square feet and where the available city water service is less than that specified in paragraph one of subdivision (b) of section 27-945 of this article, the yard hydrant system shall be supplied as follows:
(1) A gravity tank of at least fifty thousand gallon capacity shall be provided and elevated so that the bottom of the tank is at least seventy-five feet above the highest grade elevation and at least twenty-five feet above the highest building in the area supplied by this tank.
(2) In lieu of paragraph one of this subdivision, there shall be provided a manual fire pump with a capacity of at least one thousand gpm, and a suction tank of at least fifty thousand gallon capacity. The suction tank shall be supplied through a six inch connection to the city water main controlled by an automatic ball float valve in the suction tank. A bypass shall be provided so that the pump may be fed directly from the city water main.
(3) The pump shall be located in a pump house at the street main side of the area or enclosure.
(4) Suction from a river or well may be permitted by the commissioner if the required quantity of reasonably clean fresh water may be obtained thereby, subject to the approvals of such other authorities as may have jurisdiction over the primary source of supply.
(b) The maximum distance between hydrants shall be two hundred fifty feet. At each yard hydrant, two hundred fifty feet of rubber lined hose, with a smooth bore one and one-eighth inch approved play-pipe, shall be placed in a hose house painted red, and the words "Fire Hose" in six inch white letters shall be painted on the door.
(c) The approval of the fire department shall be obtained for location of any monitor nozzles that may be required in addition to yard hydrants. Not more than one monitor nozzle with remote control will be required for each forty thousand square feet of area or fraction thereof unless, in the fire department's opinion, an unusual hazard exists.
(d) Standpipes and sprinkler systems may be connected to a yard hydrant system in accordance with the requirements of this subchapter.
(e) Yard hydrant systems connected to city water mains shall be provided with post indicator valves located in an accessible position. Post indicator valves shall be locked open and be painted red.
(f) Fire extinguishing equipment, in addition to that prescribed by this section, shall be provided in accordance with requirements of chapter four of this title for oil storage plants, oil refineries, and other plants deemed by the fire commissioner to present unusual fire hazards, and also in rooms or spaces housing electrical equipment when such fire extinguishing equipment is deemed necessary.
§ 27-934. Standpipe systems in structures being erected or demolished
(a) During construction or demolition of any structure for which a standpipe system is required, provision shall be made for the use of such standpipe by the fire department in accordance with the provisions of section 27-1014 of article one of subchapter nineteen and this subchapter.
(b) Temporary risers shall be at least four inches in diameter for structures less than four hundred fifty feet high and at least six inches in diameter for structures four hundred fifty feet high or more. There shall be as many risers as will be, or were, required for the permanent system. Each such riser shall be connected to a cross connection that is supplied through siamese hose connections at the street level, and shall be equipped on each floor with a two and one-half inch hose outlet valve. The installations shall be made so that each riser, cross-connection, and branch line can be plugged or capped when work is not being done on the system. The location of the siamese hose connection shall be placarded, kept free from obstruction, and identified by a red light.
§ 27-935. Number of standpipe risers required
The number of standpipe risers shall be such that every point of every floor can be reached by a twenty foot stream from a nozzle attached to not more than one hundred twenty-five feet of hose connected to a riser outlet valve.
§ 27-936. Location of standpipe risers
(a) Standpipe risers and two and one-half inch angle hose valves shall be located within stairway enclosures. For additional requirements see section 27-343 of article five of subchapter five and subdivision (j) of section 27-375 of article five of subchapter six of this chapter. When stairway enclosures are not available within the distance limitations of section 27-935 of this article, the standpipe risers and two and one-half inch angle hose valves shall be located as near to the enclosure as practicable, subject to the approval of the commissioner. A metal sign with one inch lettering indicating the location of the outlet shall be provided in the stair enclosure on each floor where the riser is not located in the enclosure.
(b) No standpipe riser shall be placed in any shaft containing a gas or fuel pipeline.
§ 27-937. Omission of standpipe service
(a) Standpipe outlets may be omitted in portions of first floors or basements that are completely separated from the entrance hall or enclosed stairways leading to the upper floors, provided portable fire extinguishers are installed, subject to the approval of the commissioner.
(b) Standpipe protection shall be omitted from transformer vaults, high-tension switchboard rooms, and other locations where the use of hose streams would be hazardous. Any space or room that houses equipment of such nature that the use of water would be ineffective in fighting the fire, or would be hazardous, shall have a conspicuous metal sign on each door opening on such space or room stating the nature of the use and the warning: "Use No Water".
§ 27-938. Size of standpipe risers
The size of standpipe risers shall be in accordance with Table 17-1.
TABLE 17-1 Size of Standpipe Risers
Height1 Minimum Riser Size Required (I.P.S.) 150 ft. or less 4 in. Greater than 150 ft 6 in.
Note for Table 17-1: 1 The height shall be that of the individual riser to the highest hose outlet (not including manifold outlets) from the level of the entrance floor at street level at which the riser begins.
§ 27-939. Devices used in system
No device, valve, pipe, or fitting may be used in a standpipe system unless such device, valve, pipe or fitting has been accepted or approved in accordance with the provisions of section 27-135 of article eight of subchapter one of this chapter.
§ 27-940. Siamese connections required
Siamese connections shall be provided as follows:
(a) One siamese connection shall be provided for each three hundred feet of exterior building wall or fraction thereof facing upon each street or public space.
(b) Where buildings face upon two parallel streets or public spaces without an intersecting street or public space, one siamese shall be provided for each three hundred feet of exterior building wall or fraction thereof facing upon each such parallel street or public space.
(c) Where a building faces upon two intersecting streets or public spaces and the total length of the exterior building walls facing upon such streets or public spaces does not exceed three hundred feet only one siamese connection need be installed provided the siamese connection is located within fifteen feet of the corner and on the longer street.
(d) Where a building faces on three streets or public spaces, one siamese connection shall be provided for each three hundred feet of building wall or fraction thereof facing upon such streets or public spaces, provided that at least one siamese connection is installed on each of the parallel streets or public spaces, and further provided that the siamese connections shall be located so that the distance between them does not exceed three hundred feet.
(e) Where a building faces upon four streets or public spaces, at least one siamese connection shall be provided on each street front or public space; however, only one siamese connection need be provided at the corner of two intersecting streets or public spaces if the siamese connection is located within fifteen feet of the corner and on the longer street or public space, and if the distances between siamese connections, in all cases, does not exceed three hundred feet.
(f) In any case where the exterior building walls of a building facing a street or public space is obstructed in part by another building, one siamese connection shall be provided for each clear three hundred feet of exterior building wall or fraction thereof facing upon such street or public space.
§ 27-941. Cross connections
(a) Standpipe systems that include more than one riser shall have all risers cross-connected at, or below, the street entrance floor level, except as otherwise provided in this section.
(b) Standpipe systems in buildings required by the provisions of section 27-943 of this article to have one or more zones shall be so designed and installed that the risers supplied from each zone will be cross-connected below, or in, the story of the lowest hose outlets from the water source in each zone. Horizontal intermediate check valves shall be installed in the run of each riser continuing into a higher zone in such manner as to permit all upper zones of the system to be fed through one riser from the zone below and to prevent any lower zone of the system from being supplied from a zone above.
(c) Risers supplied by an upper level cross connection shall be provided with manual control valves or remote control valves, so arranged that risers supplied by the upper level cross connections may independently be shut off from the tank supplies.
(d) Cross connections shall be at least as large as the largest riser supplied by the cross connection. However, when supplying two, but not more than four four-inch risers, the cross connection shall not be less than five inches. The cross connection shall not be less than six inches for all other riser combinations.
(e) Where there is no cellar, cross connections may be hung from the ceiling of the lowest story.
(f) Each siamese connection shall be connected to a riser or to a cross connection connecting other siamese hose connections or risers. The pipe from the siamese connection to the riser or cross connection shall be five inch i.p.s., except that a four inch pipe shall be sufficient when such pipe supplies a single four inch riser system. The pipe from the siamese connection shall be run as directly as practicable to the riser or cross connection.
§ 27-942. Hose stations
(a) Hose outlet valves.
(1) At the riser on each floor served by the riser and on the entrance floor above the riser control valve, a two and one-half inch hose outlet valve shall be provided for fire department use. Such hose outlet valve shall be readily accessible from a stairway landing or from a floor, and shall be located between five feet and six feet above the landing or floor.
(2) At the top of the highest riser, there shall be provided above the main roof level, a three-way manifold equipped with three two and one-half inch hose valves with hose valve caps. Where the manifold is located other than within a heated stair enclosure or bulkhead, the control valve shall be located in a horizontal run of piping below the roof.
(b) Location. Hose stations shall be located at the standpipe risers located either within a stair enclosure or adjacent to the entrance to such enclosure as provided in section 27-936 of this article. When the hose station is located outside the stair enclosure and the riser is within the stair enclosure, it shall be known as and referred to as "Auxiliary Hose Station".
(1) Hose stations shall be located so that every point in the floor area served by the hose station is within twenty feet of the end of the hose nozzle with the hose in its extended position. The maximum length of hose that shall be permitted at any hose station is one hundred twenty-five feet.
(c) Size, type and quality of hose. Hose shall be provided on hose racks at each hose station as follows:
(1) Hose shall be one and one-half inch "flax-line" unlined linen hose or equivalent, factory coupled, in occupancy groups C, E, F, G, H, and J.
(2) Hose shall be two and one-half inch cotton, rubber-line, or rubber hose or equivalent, factory coupled, in occupancy group A.
(3) Hose shall be two and one-half inch "flax-line" unlined linen hose or equivalent, factory coupled, for occupancy groups other than those in paragraphs one and two of this subdivision.
(4) Hose for auxiliary hose stations shall be one and one-half inch "flax-line" unlined hose or equivalent.
(5) Hose lines shall be made up of fifty foot factory coupled hose except that required hose lengths of less than fifty feet shall be in one section of the required length. Only one length less than fifty feet will be permitted where hose length is not of equal fifty foot increments, and no length shall be less than twenty-five feet.
(6) Hose may be omitted from hose racks in occupancy groups J-1 and J-2 whenever at least three open nozzles, two one and one-half inch, and two two and one-half inch spanner wrenches, two two and one-half by one and one-half inch non-swivel reducing couplings and three hundred seventy-five feet of one and one-half inch hose are stored and maintained in a locked cabinet located on the main entrance floor in a location near the standpipe riser enclosure subject to the approval of the commissioner, and hose valves are capped with a hose valve cap fastened to the valve with a chain. The person responsible for the maintenance of the standpipe system shall maintain on the premises a key for unlocking the storage cabinet. The key shall be kept in a location where it is readily available to authorized persons, but not available to the general public. A sign shall be placed on the storage cabinet indicating the location of the key. An additional labelled key shall be kept in a locked receptacle near the storage cabinet openable by a fire department standard key. Such receptacle shall be marked "For Fire Department Use Only." A metal sign shall be placed in each stair enclosure on the main entrance floor stating clearly where the storage cabinet is located.
(7) Hose may be omitted from hose racks for nonautomatic dry standpipe systems provided that the hose outlet valves are capped with hose valve caps which are chained to the valves.
(d) Auxiliary hose stations.
(1) Auxiliary hose stations may be installed in those occupancies where one and one-half inch hose is permitted as specified in subdivision (c) of this section.
(2) When auxiliary hose stations are installed, the required two and one-half inch hose valve at the riser shall be installed and the valve shall be equipped with a cap fastened to the valve with a chain.
§ 27-943. Maximum pressures
The standpipe system shall be zoned by the use of gravity tanks, automatic fire pumps, pressure tanks, and street pressure so that the maximum pressure at the inlet of any hose valve in the zone does not exceed one hundred sixty psig.
§ 27-944. Pressure reducing valves
(a) When the normal hydrostatic pressure at a two and one-half inch hose outlet valve exceeds fifty-five psig, each valve shall be equipped with an adjustable type pressure reducer so that the pressure on the downstream side will not exceed fifty psig when the discharge is at the rate of two hundred gpm from a one inch orifice nozzle attached to one hundred feet of two and one-half inch unlined hose.
(b) At one and one-half inch hose stations, an adjustable type of pressure reducer shall be provided on each hose outlet valve where the hydrostatic pressure exceeds eighty-five psig and shall be so adjusted that the pressure on the downstream side will not exceed eighty psig when seventy gpm is discharged from a one-half inch orifice nozzle attached to the length of hose to be provided at the hose station.
(c) The pressure reducing valve shall be permanently marked with the address of the premises in which it is installed and with the floor location and the setting for the location at which it is to be used.
§ 27-945. Water supply for standpipe systems
(a) Primary water supply for standpipe systems. Every standpipe system except nonautomatic dry standpipe systems shall have a primary water supply available at all times at every hose outlet, or made available automatically when the hose valve at any outlet is opened. Such primary water supply may be from one or more gravity tanks from a pressure tank or tanks, from a direct connection to a city water main, from a connection to a private water main, or from an automatic fire pump.
(b) Method of providing water supply for standpipe systems. Combinations of two or more of the following methods shall be used; in using such combinations, the siamese connections shall be considered as a source of supply.
(1) Direct connections of standpipes to the city water system provided one of the following conditions is met:
a. A statement furnished by the bureau of water supply of the department of environmental protection indicates a pressure in the street main that is capable of maintaining a static pressure of at least fifteen psig. at the highest hose outlet between the hours of eight a.m. and five p.m. on a normal working day when a street level fire hydrant within two hundred fifty feet of the building is supplied from the same street main and is discharging at least five hundred gpm through a two and one-half inch hydrant butt.
b. For buildings forty feet or less in height with an area of not more than twenty thousand square feet per floor, there is a four inch direct connection to the street main that is fed two ways or there is a four inch direct connection to each of two street mains on two street fronts so installed that shutting off one service will not interfere with the supply of the other, and there is sufficient pressure in the street main to maintain a minimum static pressure of twenty-five psig. at the highest required hose outlet and the department of environmental protection states that the required street pressure is available.
(2) A private yard main when meeting the conditions of a direct water connection to the city water system.
(3) Gravity tanks provided:
a. The minimum quantity of water reserved for standpipe service is thirty-five hundred gallons in each standpipe zone.
b. The bottom of the tank shall be at least twenty-five feet above the highest hose outlet that such tank supplies, (except the roof manifold) and those hose outlets in a penthouse enclosing mechanical equipment, except as otherwise provided in subparagraph e of this paragraph.
c. Each zone of the standpipe system having three risers or more shall have a total fire reserve capacity of five thousand gallons or more from one or more gravity tanks for each zone.
d. Where a group of two or more buildings, connected or separated, is operated under a single control, a single gravity tank having a fire reserve capacity of at least five thousand gallons may be accepted as the primary water supply for the several standpipe systems of such group, provided a dead riser is carried from the bottom of the tank to an underground header or cross connection system and provided each building unit has a post indicator type control valve outside or an o.s. and y. control valve inside the building at a readily accessible location. The underground cross connection may not cross any public street without the approval of the city departments having jurisdiction.
e. Useable storage or office space on penthouse floors shall be provided with a riser outlet valve within the distances stated in section 27-935 of this article. In lieu of elevating the bottom of the gravity tank twenty-five feet above these outlets, an automatic fire pump with local supervisory alarms may be installed. The pump shall be capable of delivering two hundred fifty gpm. at a pressure of twenty-five psig. above the normal static pressure at the highest outlet supplied by the pump. The pump shall take suction from the gravity tank and be so arranged as to permit the siamese connection and any required manual fire pump to supply these outlets. No more than three stories of any penthouse or of penthouse and building stories combined, may be supplied by this method.
(4) Pressure tanks shall be acceptable as the primary supply to the system provided all of the following conditions are met:
a. A pressure tank, or tanks, so proportioned and located that a pressure of at least fifteen psig will be available at the nozzle of the highest required hose station, exclusive of roof outlets, when all the water has been discharged from the pressure tank.
b. The storage quantities stated for gravity tanks in subparagraphs a, c and d of paragraph three of this subdivision are met and an additional volume equivalent to one-half of the required water storage space is provided for the required air.
c. An air compressor is provided with suitable automatic control and of sufficient capacity to build up air pressure of at least seventy-five psig. in the tank within three hours and to maintain thereafter an air pressure between seventy and eighty psig. The automatic control shall also maintain the proper air-to-water ratio in the pressure tank.
d. Pressure tanks shall be supplied with water through a fixed pipe, independent of the standpipe riser, and at least two inches in size. The water supply and connection shall be capable of supplying the tank at a rate of at least sixty-five gpm without reducing the pressure in the tank. The tank shall have a fixed water level plate on the end opposite the gauge glass, or other equivalent indicating device.
(5) An automatic fire pump shall be acceptable as the primary supply to the system provided:
a. The building is three hundred feet high or less, or if the building is higher than three hundred feet, the automatic fire pump is used only for the lower three hundred feet. The zones above three hundred feet shall be supplied by either a gravity tank conforming to paragraph three of subdivision (b) of this section or a pressure tank conforming to paragraph four of subdivision (b) of this section and in addition shall be supplied by the manual fire pump required by section 27-946 of this article.
b. The automatic fire pump supplying the system or section has a capacity of at least five hundred gpm with a discharge pressure of at least twenty-five but not exceeding seventy psig (above the normal) static pressure at the highest hose outlet within the zone supplied by the pump plus the frictional resistance from the pump to the outlet at a flow of five hundred gpm.
c. The electrical power to the pump is connected to the street side of the building service switch.
(c) High and low risers and cross connections in standpipe systems. When tanks are used for the primary water supply, the standpipe systems may use separate riser systems serving, respectively, low and high parts of the building. Separate gravity tanks or pressure tanks may supply each zone, but in every case the standpipe system shall be so designed that every hose outlet of the entire system can be supplied through the required cross connections from every siamese connection and from every manually operated fire pump located at or below the street level.
(d) Use of standpipe riser for sprinkler system water supply. Standpipe risers may be used to supply water to sprinklers in buildings classified in occupancy group E, one hundred feet or more in height, and in existing office buildings, one hundred feet or more in height, in accordance with applicable provisions of this subchapter and reference standards RS17-1 and RS17-2.
§ 27-946. Fire pumps
(a) Additional water supply. Additional water supply shall be provided for standpipes in buildings over three hundred feet high. The primary water supply to the standpipe system shall be supplemented by one or more manually operated fire pumps as follows:
(1) Standpipe systems in buildings more than three hundred feet high shall have at least one seven hundred fifty gpm pump or two five hundred gpm pumps. Pumps shall be capable of delivering their rated capacity at a pressure of fifty psig above the normal static pressure determined from the highest hose outlet (except the roof manifold) in the building plus the frictional resistance through the pipe from the pump to the outlet.
(2) Where a group of two or more buildings, whether connected or separated, are operated under a single ownership and one or more buildings exceed three hundred feet in height, one fire pump shall be accepted as the supplemental supply for the group. The pump shall be installed in the building where the maintenance personnel are located, and a metal sign with one inch lettering shall be installed in each building at all of the hose outlets on the entrance floor indicating the location of the fire pump.
(b) Standpipe pump rooms and location.
(1) Fire pumps shall be installed at the entrance floor level or below, in rooms enclosed by noncombustible construction having a two hour fire-resistance rating and that are adequately heated, ventilated, lighted, and drained. The pump room shall have access to the street level by a direct opening to a street or a court, or by a passageway or stairway having a fire-resistance rating of at least two hours.
(2) No person shall install other machinery or mechanical equipment in a fire pump room, unless the building is of construction class IA, IB, or IC.
(3) No person shall place or install any equipment containing a refrigerant classified in groups A1, A2, A3, B1, B2 or B3 in subchapter thirteen of this chapter, or place or install gas piping or gas consuming devices or any other equipment within any space housing a fire pump that would create a hazardous condition.
(c) Power supply for standpipe fire pumps. The type of fire pump and prime mover used in a standpipe system shall be suitable for the required service in a standpipe system provided for fire department use. If the prime mover employs any form of power other than an electric current supplied by a public utility, the use thereof shall be subject to the approval of the commissioner. Electrical power to the motor shall be taken from the street side of the house service switch.
(d) Combined use of fire pumps for standpipe and automatic sprinkler systems. A fire pump that furnishes the required auxiliary water supply either to a standpipe system or to an automatic sprinkler system shall be accepted as furnishing the corresponding water supply to the other system if such pump is in the same premises, provided that in every such case of combined use, suitable relief and shutoff valves shall be installed so as to prevent the water pressure on the automatic sprinkler system resulting from any required operation of the pump for the standpipe system from becoming greater than one hundred seventy-five psig.
§ 27-947. Direct connections of standpipes to the public water system
(a) Control valve. Each service directly supplying a standpipe system or a fire pump shall be equipped with a control valve located under the sidewalk in a flush sidewalk box located within two feet of the street line, or in such other locations as may be approved by the department of environmental protection. The purpose of each such control valve shall be clearly indicated by the words "Standpipe Supply Control," cast in the cover of such flush sidewalk box or, in lieu thereof, a metal sign with one inch lettering shall be located on the exterior building wall indicating the use and location of the valve.
(b) Water supply to standpipe fire pumps.
(1) Any required manual or automatic fire pump shall draw from two independent street water mains in different streets, except that: (i) any manual or automatic fire pump serving a building classified in occupancy group J-2 that is fully protected by a system of automatic sprinklers may draw from a single water main; and (ii) an automatic fire pump may draw from a single water main if augmented by a suction tank or tanks, and if the valves at the meter and pump are provided with tamper switches that are wired to an approved central station of an operating fire alarm company. Where two services are installed, one service from the street water main shall be run directly to the pump, and the other service may be used for domestic water supply. The connection from water mains to the pumps shall be at least six inch pipe size and shall be flushed before connection is made to the system. Connections shall be in accordance with subchapter sixteen of this chapter.
(2) In the event that two separate and distinct water mains are not available as a supply or the street mains cannot produce the required supply, there shall be provided a suction tank, or tanks, suitably located and of sufficient capacity to furnish the fire pump with at least a one-half hour supply at the rated capacity of such pump. Suction tanks shall be filled by a six inch connection to the water main, controlled by an automatic ball float valve in the suction tank. A six inch bypass shall be provided so that pumps may be fed directly from the street water main.
(3) When a water service supplies both the domestic service and the manual fire pump, a remote control valve shall be placed on the domestic service connection at the point where such connection is taken from the city supply or service main. Such remote control valve shall be controlled from a point near the pump control panel. In lieu of a remote control valve, a manually operated valve may be installed to shut off the entire domestic water supply to the building, provided such valve is located in the fire pump room and is properly tagged for identification.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-948. Installation of private fire hydrants
(a) When buildings are not required to be provided with a standpipe system, at least one entrance to the building shall be located within two hundred fifty feet of a street hydrant; or, a private hydrant of the same type as the city hydrant connected to the street water main shall be provided within two hundred fifty feet of entrance. The private hydrant shall be supplied by at least an eight inch pipe, and the domestic water supply may be connected to this private supply provided a shutoff valve is installed in a curb box in the domestic supply within six feet of the hydrant shutoff valve.
§ 27-949. Protection of standpipe system
(a) All parts of the standpipe systems that may be exposed to frost shall be protected from freezing by any one of the following methods:
(1) The piping shall be frostproofed with insulation having a thermal conductance of 0.1 Btu/hr. per square foot of surface per degree F at a mean temperature of seventy to seventy-five degrees F. Insulation shall be protected to prevent water infiltration, and when exposed to the weather the insulation shall be covered with a forty-five pound roofing felt jacket or equivalent.
(2) Steam or electric tracers may be used in conjunction with the insulation.
(b) Tanks subject to freezing temperatures shall be protected.
§ 27-950. Standards for installation
Details for installation, components, sizing, valves, fittings, protection against freezing, etc., for standpipe systems and related equipment shall be in accordance with reference standard RS 17-1.
§ 27-951. Inspections and tests
(a) Inspections. Every new system and every part of an existing system that is altered, extended, renovated, or repaired, except for ordinary repairs, shall comply with the applicable requirements of this subchapter.
(b) Notification. Advance notification of tests and inspections required by this section shall be given to the commissioner.
(c) Representation at test. Tests required by this section shall be conducted in the presence of the commissioner or his or her authorized representative, or in lieu thereof, the commissioner may accept a signed statement of an architect or engineer, whose name is submitted with the notification in subdivision (b) of this section, declaring that he or she has witnessed the tests and that the standpipe system meets the requirements of this code. If a representative of the commissioner does not appear within two days after receipt of such report by the commissioner, the report shall be deemed to be accepted by the commissioner.
(d) Testing equipment required. All equipment, material, and labor required for testing a system or part thereof shall be furnished by, and at the expense of, the person responsible for installing the work.
(e) Testing of system. Systems may be tested in sections, or parts, in accordance with the requirements of this subchapter.
(f) Acceptance. Before the acceptance of such system, each system shall be subjected to the tests required by this section.
(g) Standpipe system tests.
(1) PRESSURE TESTS.
a. The test shall demonstrate that the system will sustain a hydrostatic pressure of at least one hundred psig, and at least three hundred psig at the siamese connection, for a period of at least one hour at the topmost hose outlet and at the lowest fire pump supply connection to the system. In buildings not exceeding three stories or forty feet in height, the test pressures need not be more than fifty psig. in excess of the normal hydrostatic pressures at the topmost hose outlet, and this pressure must be maintained for a period of at least one hour.
b. Pressure tanks shall be tested to demonstrate that they will sustain a hydrostatic pressure of at least one hundred fifty per cent of the normal maximum required operating pressure for a period of at least one hour.
(2) FLOW TEST. The system shall be flow tested to determine that water is available at the top outlet of each riser, the lowest outlet in each riser, and through each siamese connection. The system shall be flushed to remove all foreign matter from the system. Flow shall be through at least a two and one-half inch hose without nozzle at each one of the above mentioned locations at separate times.
(3) ALTERATION TESTS. When alterations, additions, or repairs are made to a standpipe system, the entire system shall be subjected to a hydrostatic test pressure of at least fifty psig at the highest hose outlet, and in addition, a flow test shall be made as stated in paragraph two of this subdivision through the new or altered portion of the system.
(h) Pump tests.
(1) Fire pumps shall be tested at the factory, and a certified test curve shall be furnished with each pump.
(2) Pumps shall be tested after installation to ascertain that the pump is supplying its rated capacity at the highest required hose outlet or through the roof manifold. The test shall be performed as follows:
a. At least fifty feet of approved two and one-half inch rubber lined hose equipped with a one and one-eighth inch nozzle shall be connected to the highest two and one-half inch hose outlet valve. One of these assemblies shall be connected in parallel for each two hundred fifty gpm of rated pump capacity.
b. The nozzle or nozzles of the hose assembly shall discharge at, or above, the highest required hose outlet or through a manifold.
c. Pitot tube gauge readings shall be taken at each nozzle to determine that the required pump capacity is being discharged.
d. For manually operated fire pumps, the suction and discharge pressures shall be recorded for each step or pump speed. The pump rpm electrical current, and voltage readings shall be recorded with the specific discharge pressure for each supply condition.
e. Automatic fire pumps shall be tested to ascertain that all of the automatic controls are in good working order.
f. All of the above readings shall be noted on the required standpipe diagram or a framed chart, which shall be mounted in a visible location near the pump control panel.
g. When pumps are supplied by two independent services, the test shall be conducted from each service independent of the other and, in addition, with both services supplying the pump.
(i) Test equipment for fire pumps.
(1) For every fire pump installation, there shall be provided for test purposes at least three fifty foot lengths of approved two and one-half inch rubber lined fire hose. Hose shall be hung in the pump room or other convenient location.
(2) Three two and one-half inch by one and one-eighth inch nozzles, three spanner wrenches, and twelve washers shall be stored with the required hose.
§ 27-952. Standpipe signal systems
Standpipe signal systems shall be provided in accordance with section 27-974 of article five of this subchapter.
§ 27-953. Elevators for fire department use
Elevators for fire department use shall be provided as required by section 27-989 of article one of subchapter eighteen.
§ 27-954. Required sprinklers
A system of automatic sprinklers shall be provided in the areas listed in this section and as required in subchapters four through eight of this chapter. A summary of sprinkler requirements is given in table 17-2.
TABLE 17-2 SUMMARY OF SPRINKLER REQUIREMENTS
Where Required Type of System Automatic Sources Required Partial System Permitted Connection to Domestic Permitted Alternate Permitted (§ 27-955) Siamese Required (§ 27-959) Central a Station Required (§ 27-955) (§ 27-967) Water b Flow Alarm Required (§ 27-957) (§ 3721 of RS 17-2) Automatic Dry Sprinkler Permitted (§ 5212 of RS-17) Dry Non-automatic Sprinkler Permitted c High Hazard Bldg. – Group A (§ 27-954(a)) 2 No No § 27-961(c) No Yes None a Yes Yes No High Hazard Spaces – Group A (§ 27-954(b)) 1 Yes No § 27-961(c) No § 27-959(a)(3) If over 36 heads in a fire section None a Yes If over 36 heads in a fire section Yes No Storage Occupancy Bldg. – Group B1 (§ 27-954(c)) 1 No No § 27-961(c) No Yes None a Yes Yes No Storage Occupancy Spaces Bldg. – Group B1 (§ 27-954(d)) 1 Yes Yes § 27-961(c) No § 27-959(a)(3) If over 36 heads in a fire section None a Yes b If over 36 heads in a fire section Yes No Storage Occupancy Spaces – Group B2 (§ 27-954(e)) 1 Yes No No § 27-959(a)(3) If over 36 heads in a fire section None a Yes b If over 36 heads in a fire section Yes No Mercantile Occupancy Spaces – Group C Exceeding 7,500 ft. (§ 27-954(f)) 2 sources if exceeding 20,000 sq. ft. 1 source if not more than 20,000 sq. ft. No No No Yes None a Yes Yes No Industrial Occupancy Bldg. – Group D-1, When required by Labor Law (§ 27-954(g)) 1 source if not hazardous occupancy No No No Yes None a Yes Yes No Industrial Occupancy Spaces – Group D-1 exceeding 7,500 sq. ft. (§ 27-954(h)) 1 No No No Yes None a Yes Yes No Business Occupancy Spaces – Group E Showrooms when Required by (§ 27-954(i)) 1 Yes Yes and/or standpipe riser No Yes None a Yes Yes No Assembly Occupancy Spaces – Group F-1 a (§ 27-954(j)) 1 Yes Yes No § 27-959(a)(3) If over 36 heads in a fire section None a Yes b No No Institutional Occupancy Group H – Corridors and Exit Passageway (§ 27-954(k)) 1 Yes Yes No § 27-959(a)(3) If over 36 heads in a fire section None a Yes No No Unventilated Areas Above or below grade (§ 27-954(l)) d 1 Yes Yes No § 27-959(a)(3) If over 36 heads in a fire section None a § 27-962(e)(8) Yes No Rubbish – Laundry and Similar Chutes (§ 27-954(m)) d 1 Yes Yes No No None a None Yes No Soiled Linen – Collection and Sorting Area (§ 27-954(n)) 1 Yes Yes No § 27-959(a)(3) If over 36 heads in a fire section None a Yes § 27-962(e)(8) Yes No Workshops (§ 27-954(o)) d 1 Yes Yes Yes § 27-959(a)(3) If over 36 heads in a fire section Yes If smoke detector is used in lieu of sprinkler Yes § 27-962(e)(8) Yes No Refuse Collection and Disposal Areas (§ 27-954(p)) d 1 Yes Yes In Occupancy Groups E, G No § 27-959(a)(3) If over 36 heads in a fire section None a Yes § 27-962(e)(8) Yes No Drying Areas – Laundries or Similar Spaces (§ 27-954(q)) d 1 Yes Yes In Occupancy Groups E, G Yes § 27-959(a)(3) If over 36 heads in a fire section Yes If smoke detector is used in lieu of sprinkler Yes § 27-962(e)(8) No No Cooling Towers (§ 27-954(r)) 1 No Yes No No None a Yes Yes No
Notes:
a Central station supervision required only when booster pump is provided under § 27-964 or when nonautomatic sprinkler is permitted by the commissioner.
b Water flow alarms required when more than 36 heads are installed in a fire section or fire area.
c Only when permitted by the commissioner (§ 27-967(c)).
d see § 27-954(w) for requirements pertaining to these spaces located in a building classified in occupancy group J-1.
(a) Buildings classified in high hazard occupancy group A.
(b) Spaces classified in high hazard occupancy group A.
(c) Buildings classified in storage occupancy group B-1 exceeding one thousand square feet in floor area, or seventy-five feet or more in height, except as modified under subdivisions a, b and c of section 27-455 of article ten of subchapter seven of this code.
(d) Spaces classified in storage occupancy group B-1 exceeding five hundred square feet in floor area, except as modified under subdivisions a, b and c of section 27-455 of article ten of subchapter seven of this code.
(1) Such storage spaces less than five hundred square feet in area shall install a system of automatic sprinklers, when required by the commissioner or the fire commissioner.
(e) Buildings and spaces classified in storage occupancy group B-2 exceeding five thousand square feet in floor area, or seventy-five feet or more in height, except as modified under subdivisions a, b and c of section 27-455 of article ten of subchapter seven of this code.
(f) Spaces in high rise buildings classified in mercantile occupancy group C, spaces classified in mercantile occupancy group C exceeding seventy-five hundred square feet in floor area or with an unenclosed stair or escalator between any two or more floors.
(g) Buildings classified in industrial occupancy group D when required by section two hundred eighty of the labor law or when seventy-five feet or more in height.
(h) Spaces classified in industrial occupancy group D-1 exceeding seventy-five hundred square feet, in floor area excluding heliports.
(i) Buildings classified in occupancy group E, one hundred feet or more in height having air-conditioning and/or mechanical ventilation systems that serve more than the floor in which the equipment is located, and on or before January eighteenth, nineteen hundred seventy-six, in existing office buildings one hundred feet or more in height having such systems, showroom spaces exceeding seventy-five hundred square feet in area located more than forty feet above curb level. The sprinkler system may be connected to the domestic water supply and/or the standpipe risers. Where connected to a standpipe riser, provision shall be made to prevent excessive pressure on the sprinkler heads. If such work is not completed on or before July eighteenth, nineteen hundred seventy-four, the owner shall submit a statement to the commissioner, with a copy to the fire commissioner, setting forth a plan and time schedule for the performance of the work and completion within the prescribed time. Such plan and schedule shall be subject to the approval of the commissioner. Failure to comply with the provisions of this subdivision, or to perform the work in accordance with the time schedule, as approved by the commissioner, shall constitute a violation.
(j) Dressing rooms and property rooms used in conjunction with all places of assembly, except for F-1B places of assembly not providing live entertainment.
(k) Corridors and exit passageways of buildings classified in institutional occupancy group H where the building or building section is not otherwise required to be fully sprinklered as provided in subchapter four. Patient rooms in H-2 occupancies shall be protected with smoke detectors complying with provisions of section 27-955 of this article when not required to be sprinklered by the provisions of subchapters four through seven.
(l) Regardless of occupancy group classification, any story above grade that cannot be ventilated by at least twenty square feet of free openable area and the first story below grade when it cannot be ventilated by at least thirty-five square feet of openable area per ten thousand cubic feet of volume. Such ventilation shall be provided by operable windows or other natural ventilation sources complying with section 27-749 of article six of subchapter twelve of this chapter. All other stories below grade shall be sprinklered. Sprinklers may be omitted in toilets, shower rooms, stairs, and mechanical and electrical equipment rooms. For purposes of this subdivision fixed windows may be considered as "openable" (may be broken inward) if they are not more than one hundred feet above grade, or fifteen feet below grade; or if they are located within six feet of an accessible roof or setback; or if they are located within six feet of an operable window having at least three foot by three foot openings.
(1) Buildings classified in occupancy group J-2 with not more than three dwelling units and buildings classified in occupancy group J-3 shall be exempt from this provision provided all spaces classified in storage occupancy group B-2 exceeding one thousand square feet have been sprinklered in accordance with the requirements of this subchapter.
(m) Rubbish chutes, laundry chutes, and chutes for similar uses. Sprinklers, protected from damage, shall be provided in accordance with reference standard RS 17-2, RS 17-2A, or RS 17-2B, as applicable.
(n) Soiled linen collection and sorting areas.
(o) Workshops exceeding one hundred square feet except in one- and two-family dwellings.
(p) Refuse collection and disposal areas.
(q) Drying area of laundries or similar spaces in which two or more clothes drying machines are installed. Sprinklers to be spaced to cover area five feet in front, rear, and sides of machines.
(r) Sprinklers for cooling towers, where required by subchapter five of this chapter, shall be either a dry pipe or deluge system designed in accordance with the provisions of reference standard RS 17-4.
(s) (1) F-4 places of assembly used as cabarets.
(2) Stages within F-1a, F-1b, F-3 or F-4 occupancies providing live entertainment at anytime as set forth in subchapter eight of this chapter.
(t) Buildings classified in occupancy group J-1, buildings classified in occupancy group J-2 with four or more dwelling units, spaces classified in occupancy group J-1, and spaces classified in occupancy group J-2 with four or more dwelling units.
(u) Places of assembly located within a building classified in occupancy group J-1.
(v) Catering establishments and banquet halls with an occupant load of three hundred or more persons.
(w) In all existing buildings classified in occupancy group J-1 (except for "residential hotels," as that term is defined by the commissioner pursuant to rules,) all spaces listed in subdivisions (c), (d), (l), (m), (n), (o), (p) and (q) of this section, except that an approved smoke detection alarm system may be installed in those locations described under subdivisions (o) and (q) in lieu of sprinklers other than in those locations where sprinklers are required pursuant to section 27-123.2 of this chapter. Such smoke detection system shall be of the supervisory type connected to an approved central station.
(x) High rise buildings classified in occupancy group F-1, F-3, F-4, or G, or any spaces classified in such occupancy groups located within a high rise building or building section more than seventy-five feet above curb level.
(y) Spaces in existing high rise buildings classified in occupancy group C and any space in an existing building classified in occupancy group C with an unenclosed stair or escalator between any two or more floors.
(z) Notwithstanding the provisions of subdivision i of this section, high rise buildings classified in occupancy group E and low rise buildings classified in occupancy group E with a total gross floor area of one hundred thousand square feet or more.
(aa) Regardless of occupancy group classification, in each basement, cellar or other location below grade, regardless of the floor area of such space, in any mercantile establishment in which the fire commissioner permits the storage of flammable or combustible mixtures pursuant to sections 27-4066, 27-4070 or 27-4094 of this code, except that, where such flammable or combustible mixtures are stored in such basement, cellar or other location below grade, in a room or other area that is segregated, vertically and horizontally, from surrounding spaces by a fire separation of not less than a two-hour fire-resistance rating, such system of automatic sprinklers shall be required only within such room or other area. Such system of automatic sprinklers shall conform to the requirements for automatic sprinklers for spaces classified in storage occupancy group B-1 pursuant to subdivision d of this section.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010 and L.L. 2002/026.
§ 27-955. Smoke detector alternate
An approved smoke detection alarm system may be used in lieu of sprinklers in those locations described in subdivisions (o) and (q) of section 27-954 of this article, except in buildings or spaces classified in occupancy group J-1 or J-2. Such smoke detection system shall be of the supervisory type connected to an approved central station.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-956. Standard for installation of sprinklers
(a) Except as herein provided in subdivision (b) of this section, the installation, components, sizing, spacing, location, clearances, position, and type of systems shall be in accordance with reference standard RS 17-2, except that sprinkler systems in one and two family dwellings may in the alternative be in accordance with reference standard RS 17-2B, and sprinkler systems in other residential buildings not exceeding six stories or seventy-five feet in height and in other residential spaces in buildings not exceeding six stories or seventy-five feet in height may in the alternative be in accordance with reference standard RS 17-2A.
(b) Notwithstanding any provision to the contrary contained in reference standards RS 17-2, RS 17-2A or RS 17-2B sprinklers may be omitted from clothes closets, linen closets, pantries, water closets, water closet compartments, bathrooms, general toilet rooms and shower rooms in buildings and spaces classified in occupancy group J-2 and J-3.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-957. Sprinkler alarm system
(a) A sprinkler alarm system shall be provided in accordance with the applicable provisions of reference standards RS 17-2, RS 17-2A, RS 17-2B and RS 17-3. Where the building is provided with a class E or modified class E fire alarm signal system, compliance with the applicable provisions of reference standard RS 17-3A or RS 17-3B shall be acceptable in lieu of compliance with provisions of reference standard RS 17-3.
(b) A sprinkler alarm system shall be required when more than thirty-six heads are installed in any fire area or section. See table 17-2 for general requirements.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-958. Approved devices
No device, valve, pipe, or fitting may be used in a sprinkler system unless such device, valve, pipe, or fitting is of a type approved for such use.
§ 27-959. Siamese connections required
(a) Where required.
(1) Siamese connections shall be provided in accordance with section 27-940 of article three of this subchapter, except as modified hereinafter.
(2) In below grade sprinkler systems for garage occupancies involving the storage or repair of motor vehicles, a siamese connection shall be provided within fifty feet of every exit or entrance used by motor vehicles.
(3) Where partial sprinkler protection is required for storage spaces, one siamese connection shall be provided when more than thirty-six heads are installed in one fire section. Areas subdivided, when the subdivisions are totally enclosed by noncombustible construction having at least a two hour fire-resistance rating, shall be considered separate fire sections and the number of heads in the largest section shall determine the necessity for siamese connections. When partial sprinkler systems are installed to protect entire floor areas, siamese connections shall be provided in accordance with section 27-940 of article three of this subchapter. In all cases where partial sprinkler protection is provided and siamese connections installed, metal signs shall be securely fastened to, or above, the siamese connection indicating the area protected. Where the building has two or more frontages, additional metal signs shall be installed indicating the location of the siamese connection.
(4) When a sprinkler system supplies a group of buildings, siamese connections shall be provided for each building as required by paragraphs one, two and three of this subdivision.
(5) A single three-inch (seventy-six millimeter) inlet fire department connection acceptable to the fire commissioner may be provided for the sprinkler system in lieu of each required siamese connection in buildings classified in occupancy group J-2 not exceeding six stories or seventy-five feet in height and in spaces classified in occupancy group J-2 in buildings not exceeding six stories or seventy-five feet in height.
(b) Installation and construction. The installation and construction of siamese connections shall be the same as required for fire standpipe systems, except that the caps of each automatic sprinkler siamese connection shall be painted green and the entire siamese connection of a nonautomatic sprinkler system shall be painted with aluminum paint, and except that caps of each siamese connection used for combination standpipe and sprinkler systems shall be painted yellow and signs provided as required in subdivision (b) of section two of reference standard RS17-1.
(c) A siamese connection need not be provided for a sprinkler system in one and two family dwellings.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-960. Piping from siamese connection
Piping from the siamese connection shall be the same size as the riser or trunk main to which it is connected, except that it need not be more than five inches in diameter when supplying larger riser or feed mains. When more than one siamese connection is required, the piping from each siamese connection need not exceed four inches in diameter.
§ 27-961. Classification of water supplies
(a) Automatic sources of water supply for sprinkler systems. Automatic sources of water supply for sprinkler systems shall include a gravity tank, pressure tank, automatic fire pump, or direct connection to the public water systems. Automatic fire pumps where used for sprinkler supply shall comply with the applicable provisions of sections 27-946 and 27-947 except that no enclosures shall be required, and provided that when an emergency power system is provided, the electric power to the motor shall be connected to the emergency power source.
(b) Auxiliary sources of water supply for sprinkler systems. Auxiliary sources of water supply for sprinkler systems shall include a manually actuated fire pump or siamese connection.
(c) Combination sprinkler and standpipe tank sources of water supply. Tanks used to provide the required primary water supply to a standpipe system may also be used as a supply for an automatic sprinkler system.
(d) Nonautomatic sources of water supply for sprinkler systems. Nonautomatic sources of supply for sprinkler systems shall include siamese connections.
§ 27-962. Sources of water supply for sprinkler systems
Sprinkler systems shall be provided with water from the following sources.
(a) Two automatic sources of water supply shall be provided for sprinklers in:
(1) Buildings classified in occupancy group A.
(2) Buildings classified in occupancy group C when the area on one floor exceeds twenty thousand square feet.
(3) Buildings classified in occupancy group F-1a when open heads are required for stages of unlimited size.
(b) At least one automatic source of water supply shall be provided for sprinklers installed in all occupancy groups, except those listed in subdivision (a) and except as provided in subdivision (c) of this section.
(c) The domestic water supply may be used to supply any sprinklers required under section 27-954 of this article when installed in buildings classified in occupancy groups E, G, H and J, or to supply any sprinklers required under subdivision (aa) of said section, regardless of occupancy group classification, provided that all the requirements stated in subdivision e of section 27-962 of this article are met.
(d) The domestic water supply may be used to supply water to sprinklers in cooling towers if provision is made to automatically stop the use of water through the domestic supply lines and provided that all of the requirements stated in subdivision (e) of this section are met.
(e) When the domestic water is used to supply sprinklers as permitted in subdivisions (c) and (d) of this section, all of the following conditions shall be met:
(1) The domestic water supply line from the tank or street supply is at least the size of the sprinkler line and that the capacity available is at least equal to the capacity required for the sprinklers.
(2) The domestic water supply line from the tank or street has the required pressure as provided in section 27-963 of this article.
(3) The domestic water supply line is of nonferrous material except when the domestic water supply is four inches or over.
(4) An o.s. and y. valve or an approved valve having visual indication, sealed open, is installed in the sprinkler supply branch, or such other valve arrangement as may be provided for in reference standard RS 17-2A or RS 17-2B, as applicable.
(5) The pipe connecting the domestic water supply and the sprinkler control valve is of nonferrous material and not less than twelve inches long.
(6) The number of heads in each fire section does not exceed twenty, except that the number of heads in each fire section may exceed twenty in buildings classified in occupancy group J-2 or J-3 not exceeding six stories or seventy-five feet in height and in spaces classified in occupancy group J-2 or J-3 in buildings not exceeding six stories or seventy-five feet in height, and no more than ten heads are supplied from any one domestic water riser.
(7) The connection is made at the supply or riser side of any domestic branch control valves.
(8) In connection with the above conditions, the number of fire sections having twenty or less heads may be unlimited; and the installation of alarms in branches supplying fire sections shall be at the option of the owner, except that such alarms shall be provided where required by reference standard RS 17-2A or RS 17-2B.
(9) A check valve is installed on the sprinkler supply branch.
(f) Nonautomatic sprinkler systems shall be provided with:
(1) Siamese connections in accordance with section 27-940 of article three of this subchapter.
(2) Malleable iron fittings approved for sprinkler installations.
(3) An approved automatic fire alarm with direct connection to a central station of an approved operating fire alarm company shall be installed in the area protected by the sprinkler system.
(g) There shall be no more than ten sprinkler heads connected to a plumbing riser supplying anything other than sprinkler heads, and no more than twenty sprinkler heads connected to a riser supplying only sprinkler heads in any fire section separated by two hour enclosures from adjoining fire sections. The number of sprinkler heads connected to a riser supplying only sprinkler heads may exceed twenty in buildings classified in occupancy group J-2 or J-3 that do not exceed six stories or seventy-five feet in height and in residential spaces classified in occupancy group J-2 or J-3 in buildings not exceeding six stories or seventy-five feet in height.
(h) Standpipe risers may be used to supply water to sprinklers in high rise buildings classified in occupancy groups E, G, H and J and in existing office buildings, one hundred feet or more in height, in accordance with applicable provisions of this subchapter and reference standards RS 17-1 and RS 17-2.
(i) The domestic water supply in buildings classified in occupancy group J-1 or J-2 may be used for sprinklers in corridors, in refuse chutes and in other similar areas, as approved by the commissioner. The domestic water may be supplied by direct public water connection or equipment and pumps approved for water supply in accordance with reference standard RS-16.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010 and L.L. 2002/026.
§ 27-963. Direct connection of sprinklers to the public water system
Direct connection of sprinklers to a city water main shall be acceptable as an automatic water supply, provided the main is capable of maintaining a pressure of at least fifteen psig at the top of the highest sprinkler riser, with five hundred gpm of water flowing from a two and one-half inch hydrant outlet located at the street level within two hundred fifty feet of the building. The hydrant test shall be made between the hours of eight a.m. and five p.m. on a working day. If the pressure found in this test is insufficient to comply with the above requirement, a minimum of twelve psig at the top of the highest sprinkler riser shall be acceptable, provided that all piping in the affected area and supply piping thereto that is four inches and under is increased one pipe size above those sizes required by reference standard RS 17-2, RS 17-2A or RS 17-2B, as applicable. In addition to the fifteen psig or twelve psig requirements, the following requirements shall be met.
(a) The size of each connection shall be as large as that of the main riser and, except in sprinkler systems in multiple dwellings, shall be at least three inches and shall be controlled by an accessible shutoff valve.
(b) The service pipe shall be flushed out thoroughly before connecting to the sprinkler system. A flow sufficient to produce a water velocity of at least five fps shall be used.
(c) Each service shall be equipped, under the sidewalk, with a control valve in a flush sidewalk box located within two feet of the front wall of the building or street line as required by the department of environmental protection. The location of the control valve shall be indicated by a sign placed on the structure directly opposite the sidewalk flush box, and such sign shall have a white background with one inch red letters reading: "Automatic Sprinkler Shutoff Valve . . . Feet Opposite This Sign." Alternatively, brass, bronze, or other metal sign with one inch letters, raised or counter-sunk one-eighth of an inch may be used.
(d) The plans submitted in connection with the permit application shall be accompanied by a statement from the bureau of water supply of the department of environmental protection, stating the size of street main or mains, distance to and size of mains from which it or they are fed, the location of control valves, the static pressure on the hydrant nearest the premises, and the residual pressure in the street main taken on a hydrant near the premises when the flow from the nearest hydrant is equal to the flow required to meet the requirements of this section. A letter from the bureau of water supply of the department of environmental protection estimating available flow and residual pressure shall be acceptable to the borough superintendent when a hydrant test cannot be conducted.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-964. Sprinkler booster pumps
Where the pressure from the city water main is insufficient to comply with the requirements of section 27-963 of this article but is sufficient to give at least five psig at the highest line of sprinklers as determined by test, an automatic, electrically driven pump installed for the purpose of boosting or increasing the city water pressure in the sprinkler system may be accepted subject to the following requirements:
(a) Pumps shall be of approved centrifugal type, capable of delivering at least two hundred gpm, and shall be capable of supplying twenty-five per cent of the heads, in the largest area supplied, at twenty gpm, at a pressure of at least twenty-five psig at the top of the highest sprinkler riser.
(b) Pumps shall be maintained under approved automatic control with closed circuit supervisory attachment. The supervisory attachments shall be directly connected to an office where maintenance personnel are in attendance twenty-four hours a day; or, in lieu thereof, the supervisory attachment may be directly connected to the central station of an approved operating fire alarm company. The supervisory alarm services shall be arranged so as to provide positive indication at an approved central office or sprinkler alarm panel board that the pump has operated or that the source of electrical supply has failed.
(c) Such pumps shall also comply with the applicable provisions of sections 27-946 and 27-947 of article three of this subchapter, except that only one supply shall be required and no enclosure shall be required.
§ 27-965. Gravity and pressure tanks
When the requirements of sections 27-963 and 27-964 of this article are not met, a pressure or gravity tank or other device shall be used, complying with the applicable provisions of subchapter sixteen of this chapter and reference standard RS 17-2, RS 17-2A or RS 17-2B.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-966. Protection of sprinkler system
(a) All parts of an automatic system exposed to freezing temperatures shall be protected from freezing in accordance with the provisions of section 27-949 of article three of this subchapter, or in lieu thereof, an automatic drypipe system or a system filled with a nonfreezing, noncombustible solution shall be used, and when a system filled with nonfreezing solution is used and the system is connected to a potable water supply, it shall be subject to the requirements of the health department and the bureau of water supply of the department of environmental protection.
(b) Sprinkler heads subject to damage shall be protected in accordance with the applicable provisions of reference standard RS 17-2, RS 17-2A, or RS 17-2B.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1999/010.
§ 27-967. Inspection and tests
All inspections and tests of sprinkler systems shall be conducted in accordance with the provisions of subdivisions a through f of section 27-951 of article three of this subchapter and the requirements of this article.
(a) Automatic wet and dry systems. Automatic wet and dry sprinkler systems shall be subjected to a hydrostatic pressure test for a period of one hour at a pressure of at least one hundred psig at the topmost sprinkler head and at least two hundred psig at the lowest cross connection to the siamese connections.
(b) Automatic dry pipe systems. In addition to the hydrostatic test in subdivision (a) of this section, the automatic dry pipe systems shall also be tested to forty psig air pressure for a twenty-four hour period with the pressure loss not to exceed one and one-half psig.
(c) Nonautomatic sprinkler systems. Nonautomatic sprinkler systems shall be subjected to a hydrostatic pressure test of fifty psig at the topmost sprinkler head, with the test pressure maintained for a period of at least one hour.
(d) Pressure tanks. Pressure tanks shall be hydrostatically tested to a pressure of at least one and one-half times the working pressure for a period of one hour.
(e) Sprinkler branches and heads supplied from domestic water. Sprinkler branches and heads shall be tested at the pressure required by this section or at the pressure of the domestic water supply as required by subchapter sixteen of this chapter, whichever is greater.
(f) System performance. A performance or operation test shall be made on each completed system to determine that all alarms, valves, indicators, pumps, deluge valves, dry pipe valves, and other appurtenances are in good working order.
(g) Supervisory service. All components connected to a central station of an approved operating fire alarm company shall be tested to determine that they are in good working order. The test report shall be accompanied by a statement from the central supervisory agency stating that the agency has been retained to provide the required supervision; and when the services of the agency have been terminated it shall notify the commissioner in writing.
(h) Altered systems. When additions, alterations, or repairs are made to a sprinkler system, the entire system shall be tested as stated in subdivisions (a), (b), (c), (e), and (g) of this section, except that the pressure at the top of the system need not exceed one hundred psig. In addition, a flow test of at least twenty gpm shall be made from a test connection at the end of the sprinkler header or the section altered or repaired.
(i) Pump tests. Pumps shall be tested in accordance with the applicable provisions of subdivisions (h) and (i) of section 27-951 of article three of this subchapter.
§ 27-968. Where required
(a) A closed circuit electrically supervised fire alarm signal system shall be installed in the following types of buildings:
(1) Hotels, motels, lodging houses, dormitories, and single room occupancies having more than fifteen sleeping rooms or accommodating more than fifteen lodgers above the first or ground story.
(2) Buildings classified in occupancy group H-1 or H-2. Systems installed in buildings where persons are restrained under the jurisdiction of an agency of the city or the state of New York may be modified to comply with the regulations of such agency, when such modification is approved by the commissioner.
(3) Day care agencies having a board of health permit for the accommodation of more than thirty children. If such day care agency is located at the grade level of the building, the fire alarm system is required only in the premises of the day care agency. If the day care agency is located at other than grade level of the building, an approved fire alarm system shall be provided throughout the building.
(4) Health clubs and turkish or other special treatment bath houses where there are sleeping accommodations for more than fifteen persons on the premises.
(5) Department stores or retail sales establishments having one or more floors above the street floor to which the public is admitted or with a total floor area of twenty thousand or more gross square feet.
(6) All public schools; also all private schools and university teaching buildings more than one story in height. If a school premise is located at other than a grade level of a building, an approved fire alarm system shall be provided throughout the building.
(7) Single and multi-tenant factory buildings more than two stories in height in which more than twenty-five persons are employed above the ground floor, as provided by section two hundred seventy-nine of the labor law. In buildings where more than ten per cent of the building occupancy is engaged in manufacturing, the building shall have an approved fire alarm system throughout.
(8) Buildings housing a motion picture studio.
(9) Buildings classified in occupancy group E, seventy-five feet or more in height and buildings classified in such occupancy group occupied or arranged to be occupied by an occupant load of more than one hundred persons above or below the street level or more than a total of five hundred persons in the entire building.
(10) a. Stages, dressing rooms and property rooms used in conjunction with all places of assembly used as cabarets.
b. Places of assembly used as a cabaret.
(b) Areas containing gas distribution piping operating at levels above fifteen psig shall have a combustible gas detection-alarm system, and a suitable fire protection system as approved by the commissioner with the concurrence of the fire commissioner.
§ 27-969. Approvals
(a) Equipment and systems shall be made of approved materials, and shall be free from defective workmanship. The requirements of reference standard RS17-5 shall apply except as specifically qualified herein.
(b) Before any fire alarm system is installed or extended, approval shall be obtained from the commissioner.
(c) All devices and equipment that have been approved shall have securely fastened thereon a manufacturer's label indicating compliance with the requirements of section 27-135 of article eight of subchapter one of this chapter.
§ 27-970. Existing installations
Except as provided in subdivisions (g) and (j) of section 27-972 of this article, fire alarm systems heretofore installed in buildings in accordance with rules then in force shall be accepted for use as long as they are maintained in good working order.
§ 27-971. Classification and general requirements of fire alarm systems
Fire alarms shall be classified as follows and shall meet the following general requirements:
(a) Uncoded closed circuit fire alarm system. Consisting of manually operated sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound continuously the signaling devices throughout all portions of the building.
(b) Master coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices giving a common code of signals throughout all portions of the building. The code shall consist of four rounds of a series of single strokes of the signaling devices, each round consisting of "3-3-3-3".
(c) Individually coded closed circuit general fire alarm systems. Consisting of manually operated pull-lever type sending stations and audible signaling devices, so arranged that the operation of any station will automatically sound the signaling devices, throughout all portions of the building, for a minimum of four rounds of a distinctive code of signals particular to the station at which the signal has been initiated. The code numbers that are used shall be subject to the approval of the fire commissioner.
(d) Individually coded closed circuit presignal fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause the sound of only the signal devices located in the engine room and basement and other places in the building where the members of a fire brigade work or assemble. The signaling device shall give four rounds of the particular code signal of the station at which the signal has been initiated. Approved equipment shall be provided at each station so that the operation of any station performed with the aid of a key or plug will sound all of the signal devices located in the building with four rounds of the particular coded signal of the station initiated. The code numbers used shall be subject to the approval of the fire commissioner. The presignal key or plug shall be so designed that it can be readily identified. Presignal type systems will not generally be approved; however, approval may be obtained from the fire commissioner where special type occupancies may warrant such a system.
(e) Combination unit or zone, and general alarm coded closed circuit fire alarm systems. Consisting of manually operated pull-lever type sending stations and signal devices so arranged that the operation of any station will cause all of the signaling devices in that unit or zone to sound four rounds of the particular coded signal of the station initiated, and simultaneously will cause all of the signaling devices on the general alarm circuit to sound four rounds of the coded signal designating the unit or zone in which the station is located. An approved register and time stamp may be used in connection with this system when approved by the fire commissioner. The register, if of the closed circuit type, shall be operated from a separate closed circuit control board or panel isolated by a barrier from the main control panel in the main fire alarm control cabinet. An approved closed circuit unit annunciator with trouble alarm circuit shall be installed as part of this system when required by the fire commissioner.
(f) Special systems. Consisting of the above systems as required, supplemented by special circuits for the operation of other fire alarm or detection devices in the systems, or electric control systems for stopping machinery, closing doors or ventilators, or shutting down fans as may be required by the commissioner or the code, or to call the central station of a private operating company of the fire department. Automatic fire detecting systems may be connected to operate an interior fire alarm system when connected thereto by an approved coded transmitter. In no case shall the transmitter be considered to replace the standard approved interior fire alarm station, except where a transmitter has been approved for both purposes. The special control circuits and devices shall be separate and distinct from the fire alarm system but shall be brought into action whenever the fire alarm system is set in operation.
(g) Class E system. Consisting of a class E fire alarm signal system as described in subdivision (f) of section 27-972 of article five of this subchapter and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(h) Modified class E system. Consisting of a modified class E fire alarm signal system as described in subdivision (g) of section 27-972 of article five of this subchapter and reference standard RS17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(i) Class C system. Consisting of a class C fire alarm signal system as described in subdivision (k) of section 27-972 and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(j) Class J system. Consisting of a class J fire alarm signal system as described in subdivision (l) of section 27-972 of article five of this subchapter and reference standard RS 17-3A. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(k) Modified class J system. Consisting of a modified class J fire alarm signal system as described in subdivision (m) of section 27-972 of article five of this subchapter and reference standard RS 17-3B. Such systems shall be exempt from the provisions of section 27-973 of article five of this subchapter, except that compliance with paragraph two of subdivision (a) and subdivision (e) of such section shall be required.
(l) Modified class J-1 system. Consisting of a modified class J-1 fire alarm signal system as described in paragraph two of subdivision (j) of section 27-972 of article five of this subchapter.