RS 5-17. STANDARDS FOR THE INSTALLATION OF SMOKE SHAFTS
1. Smoke shafts shall be constructed as required for shafts in section 27-344.
2. Shafts may serve more than a single compartment on a given floor but in all cases shall have at least one wall common to or abutting the compartments served, or each added compartment shall be connected to the shaft by an individual duct with the same fire resistive rating as required for the smoke shaft.
3. The size of the shaft shall be uniform throughout and of such dimensions as to provide 60 air changes per hour in the largest compartment served and at a velocity of not less than 1,600 fpm nor more than 4,000 fpm.
4. Openings into the shaft shall be provided at each floor and shall be of a size to permit the number of air changes prescribed in 3 above at a maximum air velocity of 3,000 fpm. Such openings shall be located as high as possible and designed to vent the entire compartment. They shall be equipped with an opening protective or closure having a fire protective rating complying with table 5–3 (§ 27-342). Such closures shall be automatically openable individually upon the activation of a detector located at the return shaft of the compartment and upon the activation of any other detectors installed within the compartment.
5. An approved, automatically controlled, exhaust fan of such capacity as to exhaust 60 air changes per hour from the largest compartment served by the shaft and capable of maintaining not less than a 2-inch negative static pressure at its inlet under flow conditions shall be installed in the shaft.
a. The fan shall be located so that the bottom of the fan inlet is located not less than 3 feet above the top of the automatic protective closure in the highest fire floor served by the shaft.
b. The shaft shall terminate at least 3 feet above the roof level where it penetrates the roof and shall be provided with a protective weather closure which can be opened manually from the outside.
c. When the closure in the required opening on a floor opens, this shall automatically open the weather closure and start the fan.
d. The shaft exhaust fan shall also be controlled from a local start-stop station at the fan, and at either the mechanical control center or the fire command station.
e. The fan shall be operated from circuits that are separate from the general lighting and power circuits, either taken off ahead of the main switch or connected to an emergency power source when such source is provided.
RS 5-18. STANDARDS FOR THE PRESSURIZATION OF STAIRS
1. Each stair shall be provided with air in such amount as to satisfy the following requirements:
a. The air shall be mechanically supplied at one or more levels.
b. Each fan shall supply 100 per cent outdoor air.
c. Any opening shall be provided with an intake closure complying with the requirements for opening protectives of Title 27, Chapter 1 of the administrative code with an approved smoke detector located between the outside air intake and the supply fan. Upon the activation of this detector, only the system serviced by such detector shall shut down.
d. The maximum velocity of air supplied at the openings into the stair shall not exceed 3,000 fom at its point of discharge within the stair enclosure.
e. Intake closures shall open and the supply fan or fans shall start upon the activation of any detector in the building except that called for in paragraph c above. However, only the fan system associated with the activation of the detector shall shut down.
2. An approved, automatically controlled louver and weather closure open to the exterior at the highest floor served by the stair shall be installed in the case of a fan or fans producing an upward flow of air, or at the furthest point or points from the fan or fans when more than one fan is used, or at the lower end of the stair venting to outside if a single fan is located at the upper end of the shaft. The size shall be not less than 2 sq. in. per 100 cu. ft. of total shaft volume. Any existing fixed ventilating opening may be included in meeting this requirement. The louver shall be normally closed and shall open automatically by fusible link or other approved device when subjected to a temperature of 135°F. or to a rapid rise in temperature at a rate of 15 to 20°F. per minute, and the louver shall also be remotely operable from the fire command center. Such louver shall also satisfy the requirements of subdivision d of section 27-344.
3. The total supply of air introduced into each stair shall be equal to and not less than the algebraic sum of 24,000 cfm plus 200 cfm per story of stair.
4. Other operating requirements.
a. All weather closures may normally be in closed position.
b. The air supply fans shall provide positive pressure differential between the stair shaft and each floor at a maximum of 0.4 inches of water column whether doors are open or closed. Minimum positive pressure differentials between the stair shafts and each floor of 0.10 inches of water column when all doors are closed, and no less than 0.050 inches of water column when any three doors are open, shall be maintained. As an alternative to the maintenance of 0.050 inches of water column, a minimum average velocity of 400 feet per minute, measured in the plane of any open door, with any three doors open, shall be maintained.
c. Excess positive pressure within the stair closure may be relieved at one or more levels through protected openings in the stair enclosure in the following manner:
(1) Each opening shall be provided with an approved adjustable barometric back-draft damper so arranged as to permit air flow out of the stair enclosure only and shall be adjusted to close if the pressure differential is less than 0.05 inches of water column, and to remain open if the pressure differential is greater than 0.4 inches of water column.
(2) Each opening shall be protected with two 1 1/2-hour fire dampers arranged in series, each with fusible links rated to melt at 125°F.
(3) Acceptable alternative systems for the relief of excessive positive pressure other than through the protective openings in the stair enclosure may be installed, subject to the approval of the commissioner.
(4) Spill ducts located entirely within the stair enclosure and utilizing barometric dampers may be installed as an acceptable alternative system referred to in sub-paragraph 3 above.
d. Air supply fans shall also be controlled from a local start-stop station at the fans and from the fire command station. In addition, fan controls may also be located at the mechanical control center. These controls shall over-ride the automatic detection shut-down.
e. The fans shall be operated from circuits that are separate from the general lighting and power circuits taken off ahead of the main switch and connected to an emergency power source when such source is provided.
5. Full system testing shall be required for each installation and shall be subject to controlled inspection. Pressure or velocity measurements shall be taken for the purpose of determining whether the desired control of smoke will be established and reports of such measurements shall be made and copies thereof filed with the department as provided in Section 27-132 for controlled inspection. A full system test shall be performed after any construction and/or modifications to the stair enclosures altering the volume of such enclosures.
6. Operational tests of the stair pressurization systems shall be conducted every twelve months by building maintenance personnel and witnessed by the Fire Safety Director or by a Registered Architect or Professional Engineer to ensure that each system functions. The owner or his authorized representative shall retain at the premises a record of each test performed for Building and Fire Departments' use.
7. Operational tests shall determine that initiating devices such as fire alarms, sprinkler alarms, elevator recall, manual switches, and smoke detectors other than those designed to cause the shutdown of outside air intake systems, will cause the stair pressurization systems' intake dampers to open and fans to start.
RS 5-19
ASTM E 814—1983 Standard method of fire tests of through-penetration fire stops.
RS 5-20. STANDARDS FOR THE FLAMMABILITY OF CARPETS
DOC FF1—1970 Methanine pill test.
ASTM E 648—1988 Standard test method for critical radiant flux of floor covering systems using a radiant heat source.
ASTM E 662—1988 Standard test method for specific optical density of smoke generated by solid materials.
RS 5-21
UBC Std. 26-9–1997—Method of Test for the Evaluation of Flammability Characteristics of Exterior, Nonload-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate-Scale, Multistory Test Apparatus.
RS 6. PHOTOLUMINESCENT EXIT PATH MARKINGS
RS 6–1 Photoluminescent Exit Path Markings. RS 6–1A Additional Standards as Required by Reference Standard RS 6–1 for Photoluminescent Exit Path Markings.
RS 6-1. PHOTOLUMINESCENT EXIT PATH MARKINGS
This section has 10 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 6-1 at American Legal Publishing.
as required by Local Law 26 of 2004, New York City Building Code § 27-383(b)
Introduction
This standard is intended to provide minimum requirements for photoluminescent exit path markings that will aid in evacuation from buildings in the event of failure of both the power and back-up power to the lighting and illuminated exit signs. Photoluminescent material is charged by exposure to light and will emit luminance after the activating light source is unavailable. The markings covered by this standard are not designed to provide enough light to illuminate a dark egress path, but rather will provide luminescent signs and outlines of the egress path, stairs, handrails, and obstacles, so that occupants can discern these egress path elements in dark conditions. The markings are generally required to be located at a low location in case of smoke and to be readily seen, such as in a crowd situation. They are in addition to, and not as a substitute for, any other signage required under the Building Code, such as electrically illuminated exit signs with electrical back-up power required under § 27-383(a).
This standard covers: 1) the technical specifications for minimum performance of the materials; 2) the minimum requirements for placement of the signs and markings; 3) administrative filings to certify compliance; and 4) maintenance requirements.
1.0 Technical specifications for minimum performance
1.1 Mandatory certifications. All photoluminescent products covered by this standard shall be independently tested to certify compliance with the following characteristics in accordance with Reference Standard RS 6–1A:
1.1.1 Brightness Rating ("BR"): Minimum BR of 30-7-5, being the laboratory measurement of luminance at 10, 60, and 90 minutes, respectively
1.1.2 Washability
1.1.3 Toxicity
1.1.4 Radioactivity
1.1.5 Flame spread
1.2 Additional certification. For manufacturers seeking to represent their photoluminescent products in New York City as UV resistant (resistant to UV degradation and weather), such products shall be independently tested to certify compliance with Reference Standard RS 6–1A for UV degradation. Only products meeting this characteristic shall be installed in locations exposed to unfiltered sunlight or exterior weather conditions. UV-approved products may also be used in other locations where materials with proven long-term stability are desired by the owner.
1.3 Approval. Only those products approved by the Department of Buildings' Material and Equipment Acceptance Division ("MEA") shall be installed.
1.4 Labeling. All approved materials shall be labeled and identified with the model number as well as with "MEA #______ BR: ______" in a minimum of 6 point type with at least one such identification on each piece of material installed. However, labeling is not required for pieces of material less than 1 foot in length that are placed in immediate proximity of an identical model that is labeled. Those products certified for UV degradation shall be labeled with "UV" (e.g.: MEA 892-05-M BR: 39-8-6 UV). Products may include supplemental identifying information such as the manufacturer's name, trade name, or "NYC".
Note: A Brightness Rating of 30-7-5 means that the brightness (luminance) will be 30.0 mcd/m 2 (millicandelas per square meter) at 10 minutes, 7.0 mcd/m 2 at 60 minutes, and 5.0 mcd/m 2 at 90 minutes, under test conditions.
2.0 Minimum requirements for placement
2.1 Markings on 1) doors opening to "exits" or "exit passageways"; 2) doors opening to "corridors" where such "corridors" act as required "exit passageways" connecting two "vertical exits", and 3) doors serving as "horizontal exits". 1 All such doors, other than intermediate or final exit doors, shall be marked in compliance with 2.1. Intermediate and final exit doors shall comply with 2.2.9.
1 As such terms are defined in the Building Code of the City of New York.
2.1.1 Door signs. Doors shall be marked with a photoluminescent door sign designed in compliance with 2.3.1. The top of the signs shall be no higher than 18 inches (457 mm) above the finished floor. Signs shall be installed either on the door itself, or on the wall surface directly adjacent to the door, or both:
2.1.1.1 Door-mounted option (fig. 1).
The vertical centerline of the sign shall be centered with the door, or shall be in that half of the door, either the right or left, that contains the latch. In case of double-doors, both doors shall be marked and the signs shall be centered with the doors. For door-mounted signs, arrows may be omitted.
2.1.1.2 Wall-mounted option (fig. 2).
Signs shall be mounted on the wall surface directly adjacent to the latch-side of the door, as close as practicable to the door such that in no case shall there be more than 6" (152 mm) from the door to the edge of the sign. In case of double-doors, signs shall be placed on the wall surface directly adjacent to the hinge-sides of both doors. Where the wall surface directly adjacent to the latch side is too narrow to accommodate the sign, the sign may be placed on the adjacent perpendicular wall. For wall-mounted signs, arrows are mandatory.
EXCEPTION—Existing buildings: For buildings constructed pursuant to plans approved prior to July 1, 2006, the top of the signs may be as high as 26 inches (660 mm) above the finish floor where necessary because of molding, baseboards, or similar features.
2.2 Markings within "vertical exits," "horizontal extensions in "vertical exits," "horizontal exits," "supplemental vertical exits," and "exit passageways" 2
2 As such terms are defined in the Building Code of the City of New York.
EXCEPTION: Such markings are not required in "street level lobbies", "exterior stairs", or exterior balconies. 3
3 As such terms are defined in the Building Code of the City of New York.
2.2.1 (Steps (fig. 3). The entire horizontal leading edge of each step shall be marked with a solid and continuous stripe of photoluminescent material. The dimensions, distances and locations shall be consistent and uniform throughout the same exit.
2.2.1.1 Width. The width of the stripes, measured horizontally shall be:
Maximum: 2" (51 mm)
Minimum: 1" (25 mm).
2.2.1.2 Length. The stripes shall extend for the full length of the step.
2.2.1.3 Placement. The leading edge of the stripe shall be:
Maximum: (1/2" (13 mm) from the leading edge of the step
Minimum: 0" from the leading edge of the step.
2.2.1.4 Overlap. The stripe shall not overlap the leading edge of the step by more than 1/2" (13 mm) down the vertical face of the step.
EXCEPTION—Existing buildings. For buildings constructed pursuant to plans approved prior to July 1, 2006, in lieu of marking the full horizontal leading edge as per 2.2.1, one of the following marking options may be complied with:
1. Step markings (fig. 3). The entire horizontal leading edge of each step shall be marked with a solid and continuous stripe of photoluminescent material. The dimensions, distances and locations shall be consistent and uniform throughout the same exit.
1.1 Width. The width of the stripes, measured horizontally shall be:
Maximum: 2" (51 mm)
Minimum: 1" (25 mm).
1.2 Length. The stripes shall extend to within 2" (51 mm) of both the sides of the steps.
1.3 Placement. The leading edge of the stripe shall be:
Maximum: 1" (25 mm) from the leading edge of the step
Minimum: 0" from the leading edge of the step; or
1.4 Overlap. The stripe shall not overlap the leading edge of the step by more than 1/2" (13 mm) down the vertical face of the step.
2. Side edge markings (fig. 4). Side edge markings on both horizontal sides of each step that provide returns extending along the leading edge. The dimensions, distances and locations shall be consistent and uniform throughout the same exit. Such side edge markings shall be solid and continuous stripes of photoluminescent material:
2.1 Width of side edge markings. The width of the side edge marking shall comply with 2.2.1.1.
2.2 Placement of side edge markings. The side edge markings shall be placed no further than 2" (51 mm) from both sides of steps. Such stripes shall extend to within 2 1/4" (57 mm) of the back of each step and to within 1" (25 mm) of the leading edge of each step.
2.3 Width of returns. The returns shall also comply with 2.2.1.1 but are not required to be the same width as the side edge markings.
2.4 Placement of returns. The returns shall extend from the side edge marking, parallel with the leading edge of the step, for a minimum distance of 2" (51 mm). Such returns shall extend to within 1" (25 mm) of the leading edge of each step.
2.5 Overlap. The side edge markings including returns shall not overlap the face of the leading edge of the step by more than 1/2" (13 mm) down the vertical face of the step.
2.2.2 Leading edge of landings (fig. 5). The leading edge of all landings (for example the platforms at the top of stairs) shall be marked in a consistent and uniform manner throughout the same exit. Such markings shall comprise stripes following the same requirements as for steps in 2.2.1, except that: 1) the stripe shall be the same length as and consistent with the stripes on the steps, or may extend the full length of the leading edge of the landing; and 2) the leading edge of each landing shall be marked regardless of the age of the building.
2.2.3 Handrails (fig. 6). All handrails and handrail extensions shall be marked with a solid and continuous stripe of photoluminescent material. The dimensions, distances and locations shall be consistent and uniform throughout the same exit.
2.2.3.1 Width. The minimum width of the stripe shall be 1" (25 mm).
2.2.3.2 Placement. The stripe shall be placed at least on the top surface of the handrail for the entire length of any handrails including handrail extensions, and newel post caps.
2.2.3.3 Continuity. Where handrails or handrail extensions bend or turn corners, the stripe shall be as continuous as practicable with no more than a 4" (102 mm) gap without photoluminescent material permitted at such bends.
EXCEPTION—Existing buildings. For buildings constructed pursuant to plans approved prior to July 1, 2006, handrails are not required to be marked.
2.2.4 Floor perimeter demarcation lines. Floor perimeter demarcation lines are intended to outline the egress path by providing low location photoluminescent lines on both sides of the path. Stair landings and other parts of the egress path shall be provided with floor perimeter demarcation lines. The lines shall be a solid and continuous 1" to 2" (25 to 51 mm) wide stripe of photoluminescent material. The continuity of the demarcation lines may be interrupted to accommodate obstructions such as conduits, moldings, corners or bends, not to exceed 4" (102 mm). The dimensions, distances and locations shall be uniform and consistent throughout the same exit. Demarcation lines shall be located on the floor, or on the walls/vertical surface, or a combination of the two, as per the following:
2.2.4.1 Floor-mounted option (fig. 7). Perimeter demarcation lines may be located on the floor, and shall be placed as close as practicable to the wall, and shall extend to within 2" (51 mm) of the markings on the leading edge of landings. Where an obstruction (such as a standpipe) is located within the egress path, the demarcation line may, at the option of the owner, extend across the floor so that the obstruction is outside of the outlined area (see fig. 8). Demarcation lines on floors shall continue across the floor in front of all doors, except in front of those doors marked with door frame markings in accordance with 2.2.9.3 (see figs. 13, 14).
2.2.4.2 Wall-mounted option (fig. 9). Perimeter demarcation lines may be located on the wall, placed with the bottom edge no more than 4" (102 mm) above the finished floor. At the top or bottom of stairs, demarcation lines shall drop vertically to the floor within 2" (51 mm) of the step or landing edge. Demarcation lines on walls shall transition vertically to the floor and then extend across the floor where a line on the floor is the only practical method of outlining the path, for instance where obstructions or dead ends are to be outside of the outlined egress areas. Demarcation lines on walls shall continue across the face of all doors, or may transition to the floor and extend across the floor in front of such doors (see fig. 10), except in front of those doors marked with door frame markings in accordance with 2.2.9.3.
EXCEPTIONS. Perimeter demarcation lines are not required:
1. on the sides of steps; and
2. where an area is selected not to be outlined because it is not part of the egress path, for example an obstruction or dead end.
2.2.5 Obstacles. Obstacles at or below for 6'-6" (1981 mm) in height and projecting more than 4" (102 mm) into the egress path shall be outlined with markings no less than 1" (25 mm) in width comprised of a pattern of alternating equal bands, of photoluminescent material and black, with the alternating bands no more than 2" thick and angled at 45 degrees. Examples of such obstacles include standpipes, hose cabinets, wall projections, and restricted height areas (see fig. 8).
2.2.6 Directional signage upon entering an exit (fig. 11). Photoluminescent directional signs designed in compliance with 2.3.1 shall be placed in the stairwell or exit at every entrance thereto such that they are visible upon opening the door into the stairwell or exit (i.e., the opened door shall not obscure the sign). Such directional sign shall include an arrow indicating the direction of travel. The signs shall be located such that their top edge is within 18" (457 mm) above the finished floor.
EXCEPTION—Existing buildings. Buildings constructed pursuant to plans approved prior to July 1, 2006 are exempt from the requirements of 2.2.6. However, this exception shall not apply to below grade stories.
2.2.7 Directional signage at transfer levels and where egress direction is not clear (fig. 11). Photoluminescent directional signs designed in compliance with 2.3.1 and installed at heights indicated in 2.2.6 shall be placed on the wall: 1) at transfer levels; and 2) wherever egress direction is not clear. These directional signs shall include arrows indicating the direction of travel. Examples of placement include: at turns along horizontal extensions; at transitions from vertical to horizontal direction; at a "T" intersection; etc.
2.2.8 "Not An Exit" sign (fig. 12). Photoluminescent signs shall be placed on doors along the egress path that lead to dead ends (mechanical rooms, storage closets, etc.) Such signs shall contain sans serif lettering at least 1" (25 mm) high reading "NOT AN EXIT"
EXCEPTION—Existing buildings. Buildings constructed pursuant to plans approved prior to July 1, 2006 are exempt from this requirement.
2.2.9 Intermediate exit doors and final exit doors. For the purposes of this section and elsewhere in this standard, the following terms shall have the meanings set forth herein:
Intermediate exit door (fig. 13). When traveling in the egress direction, doors that lead from a vertical exit, horizontal extension in a vertical exit, horizontal exit, supplemental vertical exit, or exit passageway, but do not lead directly to the exterior or to a street level lobby are intermediate exit doors.
Final exit door (fig. 14). Doors leading directly to the exterior or a street level lobby are final exit doors.
2.2.9.1 Door signs. A photoluminescent wall-mounted door sign complying with 2.1.1.2 shall be mounted on the wall adjacent to all intermediate and final exit doors. At the final exit door, such sign shall contain supplemental directional text in sans serif letters one-half as high as the word EXIT. Examples of such texts are "FINAL EXIT", or "EXIT THROUGH LOBBY" or "EXIT TO STREET", or "EXIT TO CHAMBERS STREET", etc. (see fig. 15).
2.2.9.2 Door Hardware markings. Door hardware of all intermediate and final exit doors shall be marked with no less than 16 in 2 (406 mm 2 ) of photoluminescent material. This marking shall be located behind, immediately adjacent to, or on the door handle and/or escutcheon. Where a panic bar is installed, such material shall be no less than 1" (25 mm) wide for the entire length of the actuating bar or touchpad. All hardware markings covered by 2.2.9.2 may include ANSI Z535.1 safety green graphics such as arrows indicating door handle turning directions, E001 or E002 emergency egress symbols as per ISO 7010, the word "EXIT", the word "PUSH", and similar egress-related symbols provided the minimum 16 in 2 (406 mm 2 ) of photoluminescent material is maintained.
2.2.9.3 Door frame markings. The top and sides of the door frame of all intermediate and final exit doors shall be marked with a solid and continuous 1" to 2" (25 mm to 51 mm) wide stripe of photoluminescent material. Gaps are permitted in the continuity of door frame markings where a line is fitted into a corner or bend, but shall be as small as practicable and in no case greater than 1" (25 mm). Where the door molding does not provide enough flat surface on which to locate the stripe, the stripes may be located on the wall surrounding the frame. The dimensions, distances and locations of the required markings shall be consistent and uniform on all doors on the route to the exterior of the building.
2.3 General standards.
2.3.1 Design of door and directional signs. Unless otherwise specified, all photoluminescent door signs and directional signs referenced herein (see figs. 11, 15, 16, 17):
1. may be either positive or negative image;
2. shall be made with the non-photoluminescent portions of the signs in safety green as per ANSI Z535.1–2002, American National Standard for Safety Color Code;
3. shall include three components:
3.1 the word EXIT printed in sans serif letters at least 4" high (102 mm) with strokes no less than 1/2" (13 mm);
3.2 an emergency exit symbol at least 4" high (102 mm), complying with E001 or E002 as per ISO 7010 (2003-10-01), Graphical Symbols—Safety Colours and Safety Signs—Safety Signs Used in Workplaces and Public Areas; and
3.3 an arrow at least 2 3/4" (70 mm) high, complying with E005 or E006 as per ISO 7010.
Exceptions:
1. Arrows are not mandatory on door-mounted door signs required by 2.1.1.1.
2. The word EXIT is not mandatory on directional signs required by 2.2.6 and 2.2.7.
3. Additional descriptive text is permitted, provided such words are in sans serif letters and, where the word EXIT or emergency exit symbol is required on such sign, such descriptive text is no more than one-half as high as the word EXIT or the emergency exit symbol.
2.3.2 Solid and continuous. For the purposes of this standard, solid and continuous means without gaps or interruption, except as required for the control of expansion and contraction. A series of dashes, chevrons, dots, or other similar patterns is not solid and continuous. Nonetheless, photoluminescent materials shall be considered solid and continuous if they occasionally contain the following safety green (ANSI Z535.1) symbols or text: 1) the word EXIT, 2) egress symbol E001 or E002 as per ISO 7010; 3) direction arrows E005 or E006 as per ISO 7010, or other text or symbols as approved by the Commissioner.
2.3.3 Consistent and uniform. Where markings are required to be consistent and uniform throughout the same exit, those portions of an exit in which the egress travel direction is downward may be treated differently from those portions of the same exit in which the egress travel is upward.
2.3.4 Figures. The figures annexed are intended only for illustration, and where there is a conflict between the figures and the text, the text shall govern.
2.4 Good faith prior installations. The Commissioner may accept variations to the required dimensions, distances, returns (for side edge markings), locations, and MEA labeling for buildings where: 1) photoluminescent materials were installed prior to January 1, 2005; 2) such installations meet the intent of this standard. Applications for acceptance shall indicate all deviations from this standard. The commissioner shall require documentation that the photoluminescent materials installed achieve the equivalent brightness ratings as stated in 1.1.1 as well as proof showing that the installation was completed prior to January 1, 2005. The commissioner may require installation of additional photoluminescent signs or markings in order to conform to the intent of this standard. Any such acceptance by the commissioner shall be annexed to the affidavit or report filed with the Department of Buildings pursuant to 3.3, and a copy of such report or affidavit including attachments shall be available on the premises for inspection by the Department of Buildings and Fire Department.
2.5 Installation of additional signs and markings. Where photoluminescent signs or markings are installed in locations where they are not required by 2.1 and 2.2, such signs and markings shall be MEA-approved in accordance with 1.0 (technical specifications for minimum performance). Examples of such other signs could include floor numbering signs, elevator landing signs, elevator bank indicator signs, reentry signs, etc. Where door hardware or door frame markings in accordance with 2.2.9.2 or 2.2.9.3 are provided at reentry doors, the reentry signs required by the building code shall be photoluminescent and MEA-approved in accordance with 1.0.
2.6 Other occupancies. Where photoluminescent signs or markings are installed in the exit path in other than Class E high rise buildings, such signs or markings shall comply with this standard.
3.0 Administrative filings to certify compliance
3.1 Existing buildings; Affidavit. Owners of existing buildings shall submit an affidavit of completion certifying compliance with § 27-383(b) and RS 6-1, on or before July 1, 2006 for occupied buildings, or prior to issuance of a Certificate of Occupancy for new buildings under construction. In lieu of such affidavit, the owner may submit a report by an architect or engineer complying with 3.2. Such affidavit shall comply with the following:
3.1.1 Inspection. In such affidavit the owner shall certify that all components have been visually inspected, both with the normal lighting turned on, and with the normal and emergency lighting turned off.
3.1.2 Product identification. In such affidavit the owner shall identify the manufacturer and MEA approval number of each product installed, along with the manufacturer's product literature. The affidavit shall describe which particular products were installed in each part of the building.
3.1.3 Paints. Where in situ painting was utilized, the owner shall certify that he or she has inspected the installation and that the specified paint was utilized in accordance with the MEA-approved methods of application.
3.2 New buildings; Report. Owners of buildings filed pursuant to plans approved on or after July 1, 2006 shall submit a report of completion by an architect or engineer certifying compliance with § 27-383(b) and RS 6–1, prior to issuance of a certificate of occupancy. Such report shall comply with the following:
3.2.1 Inspection. Such report shall be submitted under controlled inspection as per Building Code § 27-132. The report shall certify that all components have been visually inspected, both with the normal lighting turned on and with the normal and emergency lighting turned off.
3.2.2 Product identification. Such report shall identify the manufacturer and MEA approval number of each product installed along with the manufacturer's product literature. The report shall describe which particular products were installed in which parts of the building.
3.2.3 Paints. Where in situ painting was utilized, the architect or engineer shall certify that he or she has inspected the installation and that the specified paint was utilized in accordance with the MEA-approved methods of application.
3.3 Submission of Affidavit or Report. Such affidavit or report shall be filed in duplicate with the Department of Buildings' Local Law Enforcement Unit for buildings constructed pursuant to plans approved prior to July 1, 2006, and with the respective Borough Office for new buildings. A third copy of the accepted affidavit or report shall be kept and maintained on the premises for inspection by the Department of Buildings and Fire Department. Failure to have such affidavit or report available for inspection shall constitute a violation of the code.
3.4 Fire protection plans. When construction of a new building or alteration of an existing building requires that a new or amended fire protection plan be filed in accordance with § 27-228, compliance with the photoluminescent sign and marking requirements of § 27-383(b) and RS 6–1 shall be indicated in such new or amended fire protection plan.
4.0 Maintenance program. Owners shall keep the required photoluminescent signs and markings in good repair. At a minimum, owners shall, every 12 months, perform a visual inspection of the signs and markings with the normal lighting turned on. Signs and markings that are missing, damaged, loose, or that show signs of wear or missing MEA labels shall be noted and promptly repaired. The log of such inspections, including the results and any corrective measures taken, shall be kept and maintained on the premises for inspection by the Department of Buildings and Fire Department. The log shall contain the date of inspection and the printed name and signature of the person performing the inspection. Deviations from any of the requirements of this standard shall be a violation of the code.
EXPLANATORY MATERIAL
The following are additional technical considerations for Reference Standard RS 6–1 and do not constitute a portion of the mandatory requirements.
A. Activating Illumination.
The products approved for use under Reference Standard 6–1 are tested in a laboratory with a fluorescent activating light source of 2 footcandles as measured on the surface of the test specimen. The measurement of 2 footcandles was derived from the minimum lighting levels as measured on the floor in exits as required by the New York City Building Code for buildings constructed after December 1, 1968. The Department of Buildings recognizes that many buildings are voluntarily providing more than 2 footcandles, and that many buildings erected before 1968 may properly be providing less. Additionally, some existing buildings are illuminated with incandescent lamps, which might not efficiently charge certain photoluminescent materials.
Reference Standard 6–1 does not permit the use of lower-performing photoluminescent products for brightly-lit environments, nor does it mandate the use of higher-performing photoluminescent products for grandfathered lighting environments. Therefore, prior to choosing a product, owners are encouraged to conduct a survey of existing lighting conditions to ensure adequate performance of the photoluminescent materials selected for the particular installation.
Reference Standard 6–1 relies on the current requirement of the New York City Building Code that continuous illumination be provided at all periods of building occupancy in corridors and exits 4 . Over the years, on a case-by-case basis, some buildings have been approved for the installation of motion-sensor activating switches allowing dark exit stairs, with the determination made that the resulting installation was equivalent to what was then required under the code. However, such determinations were made prior to the requirement of photoluminescent materials; motion-sensor devices that reduce continuous illumination to a level below the required 2 footcandles are no longer acceptable in exits where photoluminescent materials are required.
4 As such terms are defined in the Building Code of the City of New York.
B. Dissimilar Luminance Levels Within Same Environment
It is neither necessary nor possible to require that photoluminescent products in the same environment emit identical luminance levels; many factors, including the distance to the activating light source, the angle of incidence and shadows, will result in different luminance levels for identical photoluminescent products placed in the same stairway. Variations in actual luminance are expected in the same environment. However, grossly dissimilar brightness ratings within the same environment should be avoided.
C. Contrasting Colors
Photoluminescent materials are effective in completely dark conditions, and, conversely, are usually visible in normal lighting conditions. However, in dim or semi-lit conditions, such as when batteries for an emergency light are running low or when a stair is dark but a door is open to a lighted area, the photoluminescent materials forming the outlines of steps, landing, demarcation lines, and handrails might become hard to discern. Photoluminescent materials installed adjacent to a contrasting, dark color ameliorate this effect.
D. Abrasion Resistance
Reference Standard 6–1 does not mandate minimum standards for abrasion resistance. For products that are to be applied to walking surfaces, it is recommended that owners consider 1) the amount of traffic in the stairs by building occupants, and 2) the products' durability and resistance to abrasion. For instance, certain thin films and paints may be sufficient where the stairs are alarmed and only used in emergencies. However, where the occupants use the stairs on a daily basis, more durable products should be considered. Ultimately, the building owner is responsible for maintaining the photoluminescent materials in accordance with Reference Standard 6–1, Section 4.0.
E. Adhesives.
Reference Standard 6–1 does not specify the adhesives to be used. The choice of adhesive should be carefully considered for the longevity of the installation, particularly if the surface to which the product to be applied is porous, uneven, or subject to temperature or humidity variation. At a minimum owners should follow the manufacturers' instructions.
F. Slip-resistance.
Reference Standard 6–1 does not specify minimum slip-resistance requirements for photoluminescent products installed on walking surfaces. Whether or not a particular building's egress path is subject to any slip-resistance requirements may depend on the original date of construction. Any photoluminescent materials installed should be as slip-resistant as the minimum standard that is applicable to the building in which they are being installed. A stripe of photoluminescent material that is not slip-resistant may, depending on the design of the stair nosing product, be compensated for by the inclusion of an adjacent, slip-resistant strip.
G. Wall-mounted floor perimeter markings at doors.
In deciding whether to continue a wall-mounted demarcation line across a door or to transition to the floor (2.2.4.2), consideration should be given to how the door is used or secured so as to avoid the possibility that the demarcation line on the door, if left open, might lead evacuees into a non-egress space or area.
RS 6-1A. ADDITIONAL STANDARDS AS REQUIRED BY REFERENCE STANDARD RS 6–1 FOR PHOTOLUMINESCENT EXIT PATH MARKINGS
Specimens to be tested shall be finished products as they would be sold to purchasers. Each distinct product material shall be separately tested and receive its respective test results for its respective Materials, Equipment and Acceptance (MEA) Division approval number. However, variation in the size of the product and differences in the text or arrow directions, etc., shall not constitute a distinct product material, but shall constitute a different model number—provided that product literature describing with pictorial representations of all such model numbers associated with the test specimens is submitted to MEA.
Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick. In the case of paints, such painted test specimens shall be submitted along with the description of the procedures used to produce the test specimens (such as surface preparation, primer coats, number of photoluminescent coats, encapsulant coat if applicable, maximum/minimum temperature of humidity during painting if applicable, etc.). Such description shall be included in the laboratory's test report; and such description shall be included in the MEA resolution as the mandatory labeling on the paint cans as instructions to purchasers.
1.0 Brightness Rating
ISO 17398:2004, Safety Colours and Safety Signs–Classification, Performance and Durability of Safety Signs, Clause 7.11. Three specimens shall be tested (separately for each distinct product material). Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick. The testing shall be in accordance with ISO 17398, clause 7.11, with the following modifications:
1.1 Clause 7.11.5—Excitation Light Conditions. The test established in Clause 7.11.5.1 for classification of photoluminescent materials in accordance with Clause 5.5 is not required. The test in Clause 7.11.5.2 is required, however subclauses a), b), and c) are replaced with the following excitation standard: "Excitation of the phosphorescent test specimens shall be by a 4000K to 4500K fluorescent light providing a mean illuminance of 2 footcandles (21.6 lux) on the surface of the test specimen. The excitation duration shall be 2 hours."
1.2 Clause 7.11.6.1—Luminance Instrumentation. This Clause 7.11.6.1 describes two luminance instrumentation options. For this Reference Standard 6–1A, the contact luminance meter option shall be limited only to test specimens that are both smooth and flat.
1.3 Clause 7.11.6.4.2—Luminance recordings for classification purposes. This Clause 7.11.6.4.2 is not required.
1.4 Clause 7.11.6.4.3—Luminance recordings for product description purposes. The luminance performance shall be based on the mean values of the three test specimens measured at 10 minutes, the mean values of the three test specimens measured at 60 minutes, and the mean values of the three test specimens measured at 90 minutes. The resulting luminance performance shall constitute a "brightness rating", which shall be indicated in the test report. The minimum brightness rating shall be 30.0 mcd/m 2 at 10 minutes, 7.0 mcd/m 2 at 60 minutes, and 5.0 mcd/m 2 at 90 minutes. For example, a product that minimally meets the luminance levels would have a brightness rating of 30-7-5.
2.0 Washability
ASTM D 4828–1994 (2003), Standard Test Methods for Practical Washability of Organic Coatings.
2.1 Three specimens (of each distinct product material) shall be tested for each soil/staining medium in accordance with ASTM D 4828. Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick.
2.2 The laboratory shall prepare the soils and staining media that shall include: crayon, water-borne felt-tipped pen, lipstick, and a mineral-oil-bourne soilants as outlined in clause 6.2.
2.3 The cleaning media shall include liquid household cleansers available at supermarkets or laboratory-standardized liquid cleansers as outlined in clause 6.3.
2.4 After completion of the test, each specimen shall be rated at 5 or greater in accordance with clause 8.8.
3.0 Toxicity
Bombardier SMP 800-C (Rev. 4, 11/1/2000) Toxic Gas Generation Test. One test specimen (of each distinct product material) shall be tested in each of the flaming and non-flaming modes in accordance with SMP 800-C. Where the test specimen is narrower than the required 3" × 3" (76 mm × 76 mm), more than one test specimen shall be placed next to each other to provide 9 in 2 (229 mm 2 ) of surface area. Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick. The testing shall be in accordance with SMP 800-C, with the following modifications:
3.1 Clause 4.3—For determining the concentration of the toxic gases in accordance with the referenced Boeing BSS 7239 specification, the Commissioner may accept a procedure that uses gas detection tubes or other procedures, in lieu of the absorptive sampling procedure, provided that the testing laboratory outlines the procedures in its report and certifies that equivalent results are obtained.
3.2 Clause 5.0—In accordance with the Building Code and departmental rules, the Department of Buildings' Materials, Equipment and Acceptance Division may approve any testing laboratory it deems qualified to perform this test.
EXCEPTION: For photoluminescent products that, when installed, provide coverage exceeding the limits of interior trim, such products shall instead be tested for toxicity as interior finishes and/or interior floor coverings if and as required by Building Code § 27-348(e) and/or § 27-351. Tread nosings with a horizontal depth of 4" or less and that contain a photoluminescent stripe may be tested in accordance with RS 6–1A.
4.0 Radioactivity
ASTM D 3648–2004, Standard Practices for the Measurement of Radioactivity.
4.1 Three test specimens (of each distinct product material) shall be tested in accordance with ASTM D 3648. Thin gauge films and paints shall be tested when applied to a rigid cement board.
4.2 The activity of the test specimens shall be shown to be statistically indistinguishable from background.
4.3 Alpha and beta activity shall be measured on a test specimen of at least 1 in. × 1 in. (25.4 mm × 25.4 mm) and counted using a proportional counter for a minimum of 15 minutes.
4.4 Gamma activity shall be measured on the same test specimen using a gamma spectrometer counted for at least 1 hour.
5.0 Flame Spread—either one of the following two standards:
5.1 ASTM E 162–2002, Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source.
5.1.1 Four test specimens (of each distinct product material) shall be tested in accordance with ASTM E 162. Where the test specimen is narrower than required by the test, several pieces may be grouped together to provide the necessary surface area. Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick.
5.1.2 The specimens shall have a flame spread index (ls) not to exceed 35.
5.2 ASTM D 635–2003, Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position.
5.2.1 Ten test specimens shall be prepared for use in accordance with ASTM D 635.
5.2.2 The test specimens shall not burn beyond the 25 mm reference mark.
EXCEPTION: For photoluminescent products that, when installed, provide coverage exceeding the limits of interior trim, such products shall instead be tested for flame spread and smoke density as interior finishes and/or interior floor coverings if and as required by Building Code § 27-348(c) and (d) and/or § 27-351. Tread nosings with a horizontal depth of 4" or less and that contain a photoluminescent stripe may be tested in accordance with RS 6–1A.
6.0 UV Degradation ("UV") (only where a "UV" rating is requested for exterior weather conditions or unfiltered sunlight applications)
ASTM G 155–2004, Standard Practice for Operating Xenon Arc Light Apparatus for Exposure of Nonmetallic Materials.
6.1 Three specimens (of each distinct product material) shall be tested for a period of 1,000 hours in accordance with ASTM G 155. The specimens shall be subjected to Cycle 1 exposure condition noted in Table x3.1 of such standard. Thin gauge films and paints shall be tested when applied to a rigid cement board 1/4" thick.
6.2 The testing laboratory that conducted the weathering test shall certify that none of the following surface characteristics exist when viewed under a minimum of 5x magnification: cracking, checking, crazing, or erosion.
6.3 After conclusion of the testing, such laboratory shall directly send the specimens to the testing laboratory that conducted the brightness rating tests in 1.0.
6.4 The brightness rating testing laboratory shall perform luminance tests as per 1.0 on the weathered specimens and report the results. The specimens shall indicate at least 90% of the original brightness at 10 minutes, at least 90% of the original brightness at 60 minutes, and at least 90% of the original brightness at 90 minutes, as compared to the brightness ratings prior to the weathering test.
RS 7. SPECIAL USES AND OCCUPANCIES
List of Referenced National Standards RS 7–2 Restricted Locations for Projecting Signs. RS 7–3 Fire Tests for Flame-Resistant Textiles and Films.
LIST OF REFERENCED NATIONAL STANDARDS
NFiPA No.701—Standard Methods of Fire Tests for Flame-
Resistant Textiles and Films—1977.
RS 7-2. RESTRICTED LOCATIONS FOR PROJECTING SIGNS
Borough of Manhattan—
No permanent projecting sign shall be erected on any building on:
5th Avenue between Washington Square north and 110th Street;
34th Street between Park Avenue and 7th Avenue;
Madison Avenue between 23rd Street and 96th Street;
57th Street between Lexington Avenue and Broadway;
Vanderbilt Avenue between 42nd Street and 47th Street;
Park Avenue between 32nd Street and 40th Street;
Park Avenue between 45th Street and 96th Street;
33rd Street between Lexington Avenue and 5th Avenue;
35th through 41st Streets between Lexington Avenue and 5th Avenue;
43rd through 56th Streets between Lexington Avenue and 5th Avenue;
58th Street between Lexington Avenue and 5th Avenue;
60th Street between Lexington Avenue and 5th Avenue;
Nassau Street between Wall Street and Frankfort Street.
John Street between Broadway and William Street.
No permanent illuminated projecting sign shall be erected on any building on:
72nd Street between Central Park West and Riverside Drive.
Borough of Brooklyn—
No permanent projecting sign shall be erected on any building on:
Fulton Street between Flatbush Avenue and Joralemon Street and Willoughby Street
No permanent illuminated projecting sign shall be erected on any building on:
Fulton Street between Flatbush Avenue and Prospect Street and Henry Street;
Washington Street between Myrtle Avenue and Prospect Street;
Court Street between Fulton Street and Livingston Street;
Pierrepont Street between Fulton Street and Clinton Street;
Montague Street between Court Street and Clinton Street;
Remsen Street between Court Street and Clinton Street;
Joralemon Street between Court Street and Clinton Street.
RS 7-3
NFiPA No. 701 1977—Standard Methods of Fire Tests for Flame-Resistant Textile and Films.
RS 8. PLACES OF ASSEMBLY
List of Referenced National Standards RS 8–1 Specifications for Motion Picture Film-Safety Film.
LIST OF REFERENCED NATIONAL STANDARDS
ANSI/SMPTE 223M—Specifications for Motion-Picture Film-Safety Film—1985
ANSI PH 1.25—Specifications for Photography (Film-) Safety Photographic Film—1984
ANSI/NFiPA 40—Cellulose Nitrate Motion-Picture Film—1982
RS 8-1
ANSI/SMPTE 223M–1985—Specifications for Motion-Picture Film-Safety Film.
ANSI PH 1.25–1984—Specifications for Photography (Film-) Safety Photographic Film.
ANSI/NFiPA 40–1982—Cellulose Nitrate Motion-Picture Film.
RS 9. LOADS
List of Referenced National Standards RS 9–1 Minimum Unit Design Dead Loads for Structural Design Purposes. RS 9–2 Minimum Requirements for Uniformly Distributed and Concentrated Live Loads. RS 9–3 Highway Bridges. RS 9–4 Steel Railway Bridges RS 9–5 Minimum Design Wind Pressures. RS 9–6 Earthquake Loads.
LIST OF REFERENCED NATIONAL STANDARDS
AASHTO—Standard Specifications for Highway Bridges, Thirteenth Edition, and 1984, 1985 and 1986 Interim Specifications—1983
AREA—Specifications for Steel Railway Bridges, Chapter 15, Steel Structures, Manual for Railway Engineering—1987
UBC SECTION 2312—Earthquake Regulations with Accumulative Supplement—1990.
RS 9-1. MINIMUM UNIT DESIGN DEAD LOADS FOR STRUCTURAL DESIGN PURPOSES
Weight (psf) WALLS AND PARTITIONS (unplastered).— • Clay brick— High absorption (per 4 in. wythe) 33 • Low absorption (per 4 in. wythe) 45 • Concrete brick— 4 in. 46 • 4 in. lightweight aggregate 33 • 8 in. 89 • 8 in. lightweight aggregate 68 • 12 in. 130 • 12 in. lightweight aggregate 98 • Sand-lime brick— per 4 in. wythe 38 • Solid concrete brick— 4 in. 40 • 4 in. lightweight aggregate 27 • 8 in. 67 • 8 in. lightweight aggregate 48 • 12 in. 108 • 12 in. lightweight aggregate 72 • Hollow concrete block— 4 in. 30 • 4 in. lightweight aggregate 20 • 8 in. 53 • 8 in. lightweight aggregate 38 • 12 in. 85 • 12 in. lightweight aggregate 55 • Solid gypsum block— (per in. thickness) 6 • Hollow gypsum block— 2 in. 9.5 • 4 in. 12.5 • 6 in. 18.5 • Clay tile, load bearing— 4 in. 24 • 8 in. 42 • 12 in. 58 • Clay tile, non-load bearing— 2 in. 11 • 4 in. 18 • 8 in. 34 • 12 in. 46 • Facing tile— 2 in. 16 • 6 in. 29 • 8 in. 41 • Split terra cotta furring tile— 1 1/2 in. 8 • 2 in. 10 • 3 in. 12 • Glass block— 4 in. 20 • PLASTER PARTITIONS.— 2 in. thick, solid cement plaster on metal lath 25 • 2 in. thick, solid gypsum plaster on metal lath 18 • Metal studs, any lath, and 3/4 in. gypsum plaster, both sides 18 • Wood studs, any lath, and 3/4 in. gypsum plaster, both sides 19
Equivalent Uniform Partition Loads
Partition Weight (plf) Equivalent Uniform Load (psf) (To be added to floor dead and live loads) • 50 or less 0 • 51 to 100 6 • 101 to 200 12 • 201 to 350 20 • Greater than 350 20 plus a concentrated live load of the weight in excess of 350 plf.
Weight (psf) • PLASTER ON MASONRY SURFACES.— Gypsum, with sand aggregate, per in. 8.5 • Gypsum, with lightweight aggregate, per in. 4 • Gypsum, with wood fibers, per in. 6.5 • Cement, with sand aggregate, per in. 10 • Cement, with lightweight aggregate, per in. 5 • FLOOR FINISHES (Excluding fill or base).— Resilient flooring (asphalt tile, linoleum, etc.) 2 • Asphalt block, 2 in. 24 • Wood block, 3 in. 10 • Hardwood flooring, 7/8 in. 4 • Softwood sub-flooring, per in. 3 • Plywood sub-flooring, 1/2 in. 1.5 • Ceramic or quarry tile, 1 in. 12 • Terrazzo, 1 in. 12 • Slate, 1 in. 15 • Cement, 1 in. 12 • FLOOR FILL.— Cinders, no cement, per in. 5 • Cinders, with cement, per in. 9 • Sand, per in. 8
FLOORS—WOOD JOIST CONSTRUCTION (With double layer wood flooring—no ceiling).—
Joint Sizes (in.) Total Weight (psf) 12 in. Joist Spacing 16 in. Joist Spacing 2 × 6 6 5 2 × 8 6 6 2 × 10 7 6 2 × 12 8 7 3 × 6 7 6 3 × 8 8 7 3 × 10 9 8 3 × 12 11 9 3 × 14 12 10
Weight (psf) • CEILINGS (Including suspension system).— Plaster on tile or concrete—see "Plaster on Masonry Surfaces" Suspended metal lath and gypsum plaster, 3/4 in. 9 • Suspended metal lath and cement plaster, 3/4 in. 11 • Suspended acoustical tile 2 • ROOF AND WALL COVERINGS.— Clay roofing tiles 14 • Built-up roofing: 3-ply 1.5 • 5-ply 2.5 • Gravel, 1/4 to 5/8 in. 4 • Slag, 1/4 to 5/8 in. 3 • Crushed rock, 1/4 to 5/8 in. 4.5 • Aluminum sheet: 0.050 in. thick, flat 0.72 • 0.032 in. thick, corrugated 0.55 • 0.032 in. thick, V-Beam 0.58 • Steel, 20 gauge, protected V-beam 2.3 • Tin sheet, 28 gauge 1 • Asbestos-cement, corrugated roofing, 3/8 in. 4 • Fiberboard, 1/2 in. 0.8 • Gypsum sheathing, 1/2 in. 2 • Wood sheathing, per in. 3 • Wood shingles, in place 3 • Asphalt shingles, in place 6 • Asbestos-cement shingles, in place 4 • Cement tile, 3/8 in. in place 16 • Stucco (cement), per in. 10 • Slate, 3/16 in. in place 7 • Slate, 1/4 in. in place 10 • Skylight, metal frame, 3/8 in. wire glass 10 • MISCELLANEOUS MATERIALS—Glass— single strength 1.2 • double strength 1.6 • plate, wired or structured, 1/8 in. 1.6 • insulating, double 1/8 in. plates w/air space 3.5 • insulating, double 1/4 in. plates w/air space 7.1 • Insulation— fiber glass, per in. 1.5 • foam glass, per in. 0.8 • Urethane, 1 in. 1.0 • Urethane, 2 in. 1.2 • cork, per in. 1.0 • vegetable fiber boards, per in. 1.5 • bats and blankets, per in. 0.5 • vermiculite, loose fill—0.6 pcf • expanded polystyrene—1.0 pcf • Marble, interior, per in. 14.0 • Plastic, acrylic, 1/4 in. 1.5 • Slate, per in. 15.0 • Asphaltic concrete 144 • Cast-stone masonry (cement, stone, sand) 144 • Cinder fill 57 • Concrete, plain (other than expanded aggregates)— cinder 108 • slag 132 • stone (including gravel) 144 • Reinforced concrete— Add 6 pcf to unit weights shown for plain concrete Cork, compressed 14 • Earth 100 • Masonry, ashlar— granite 165 • limestone (crystalline) 165 • limestone (oolitic) 135 • marble 173 • sandstone (bluestone) 144 • Masonry, rubble w/mortar— granite 153 • limestone (crystalline) 147 • limestone (oolitic) 138 • marble 156 • sandstone (bluestone) 137 • Masonry, dry rubble— granite 130 • limestone (oolitic) 125 • marble 130 • sandstone (bluestone) 110 • Terra cotta, architectural— voids filled 120 • voids empty 72 • Timber, seasoned— pine, Douglas fir, and similar species 35 • oak, elm, and similar species 45
RS 9-2. MINIMUM REQUIREMENTS FOR UNIFORMLY DISTRIBUTED AND CONCENTRATED LIVE LOADS UNIFORMLY DISTRIBUTED LIVE LOADS
Occupancy or Use of Spaces Live load (psf) • Assembly spaces Drill rooms 150 • Assembly spaces having fixed seats, including auditorium areas in churches, schools, theaters, courthouses, lodges, lecture halls, and similar buildings 60a • Dance floors, restaurant serving and dining areas, mess halls, museums, gymnasiums, skating rinks, promenades, and roof gardens 100 • Private assembly spaces, including conference rooms and card rooms 50 • Stadium, grandstand, and reviewing stand seating areas 100 • Other assembly spaces See note d • Balconies Exterior See note b Interior (as required for occupancy or use) Mezzanines (as required for occupancy or use) • Catwalks 30 • Corridors (1) Corridors in schools 100 • (2) Corridors, elevators, and stairs in office buildings (other than first floor lobbies) 75 • (3) Corridors serving first floor elevator lobbies, auditoriums, and similar areas of public assembly 100 (4) Other (same as that required for the occupancy of the area being served) Elevator machine rooms (see Reference Standard RS-18) • Equipment rooms, including pump rooms, generator rooms, transformer vaults, and areas for switch gear, ventilating, air conditioning, and similar electrical and mechanical equipment 75 • Fire escapes Multiple dwellings 40 • Others 100 • Hospitals Operating rooms, laboratories, and service areas 60 • Rooms and wards 40 • Personnel areas 40 Other (as required for occupancy or use of the area) • Libraries Reading and study room areas 60 Stack areas (see Storage) Other (as required for occupancy or use of the area) • Lobbies and similar areas 100 • Manufacturing and repair areas 100 • Marquees 60 • Office areas (not including record storage areas) 50 • Parking areas For passenger cars, provided that the clear headroom at the entrance does not exceed 8 ft. 50 • Penal institutions Cell blocks 40 Other (as required for occupancy or use of the area) • Plaza areas (open) accessible to the public (including landscaped portions) 100 • Recreational areas Bowling alleys (alleys only) 40 • Poolrooms 75 • Other (see assembly areas) Residential areas Dormitories Non-partitioned 60 • Partitioned 40 • Dwellings Multi-family units Apartments 40 • Public rooms (as required for occupancy or use) One- and two-family units First floor 40 • Upper floors and habitable attics 30 • Uninhabitable attics 20c • Hotels Guest rooms 40 • Public rooms (as required for occupancy or use) Schools Classrooms 40 • Shops (automotive and press shops) 100 • Shops (others) 60 • Other (as required for occupancy or use of the area) Stairs and exit passages (same as Fire escapes) Storage Light 100 • Warehouse 150 • Stores Wholesale sales 100 • Retail sales Basement and first floor 100 • Upper floors 75 • Telephone equipment rooms 80 • Theaters Dressing rooms 40 • Projection room 100 • Stage floor 150 • Toilet areas 40
Notes:
a Uniform load shall be applied to the gross floor area.
b 150 per cent of live load on adjoining occupied area, but not more than 100 psf.
c Live load need be applied to joists or to bottom chords of trusses or trussed rafters only in those portions of attic space having a clear height of 42 in. or more between joist and rafter in conventional rafter construction; and between bottom chord and any other member in trussed or trussed rafter construction. However, joists or the bottom chords of trusses or trussed rafters shall be designed to sustain the imposed dead load or 10 psf, whichever is greater, uniformly distributed over the entire span.
d Live loads for assembly spaces other than those described in this reference standard shall be determined from the occupant load requirements as established by section 27-358 using the formula 100/net floor area per occupant but shall not be less than 50 psf nor more than 100 psf.
Concentrated Live Loads
Use or Location Load (lbs.) a Remarks Elevator machine room floor See Reference Standard RS-18 Gratings, checkered plates and similar metal decks 200 (on area of 1.0 sq. in.) Nonconcurrent with uniform live load. Floor registers and similar floor insets 250 (on area of 2 ft. × 2 ft.) Nonconcurrent with uniform live load. Parking areas—passenger vehicles accommodating nine passengers, or less 2,500 (on area of 20 sq. in.) For slab or deck design The concentrated load may be assumed to represent the reaction of a jack placed under one end of the vehicle. Omit uniform live load in area (6 ft. × 9 ft.) representing one half the vehicle, adjacent to the point of load concentration. 1,500 (each wheel) To be used in lieu of uniform live load in stalls of mechanized garages where there is no slab or deck. Parking areas—trucks, buses and passenger vehicles accommodating more than nine passengers 150 per cent of maximum wheel load with vehicle loaded (on area of 20 sq. in.) Same as for Parking areas—passenger vehicles accommodating nine passengers, or less. Floor of office areas 2,000 Nonconcurrent with uniform live load. Resident and multiple dwellings 200 (on area of 4.0 sq. in.) Nonconcurrent with uniform live load. Scuttles and skylight ribs 200 Nonconcurrent with uniform live load. Steel joists—for each individual joist 800 (for trussed joists apply at a panel point) Nonconcurrent with uniform live load. Roofs 250 (on area of 2 ft. × 2 ft.) Nonconcurrent with uniform live load. Not applicable for awnings, canopies, and similar constructions where access by persons is difficult and not intended. Stair and fire escape treads 300 (on area 1 ft. wide by depth of the tread and spaced at 3 ft. center-to-center) Nonconcurrent with uniform live load. Boiler rooms 3,000 The concentrated load of 3,000 lbs. may be assumed to represent the weight of minor items of equipment (pumps, etc.) in temporary locations during installation. In addition provision shall be made for supporting the weight of the empty boiler at pertinent locations on the floor to provide for replacement of the boiler
Note—
a Except when otherwise indicated loads are assumed to be applied over an area 2 1/2 ft. × 2 1/2 ft.
UNIFORMLY DISTRIBUTED AND CONCENTRATED LIVE LOADS FOR CONSTRUCTION ELEVATOR AND MATERIAL HOIST TOWER BACK STRUCTURES
DEFINITION:
Back Structure: A system of landing platforms and/or supports designed to transmit construction elevator or material hoist tower loads into the building structure.
WALKWAY PLATFORMS
{L} Live Load
1. Uniformly Distributed: 100 psf defined by the area enclosed by handrail, or by the gross area of the walkway if handrails are not provided.
2. Concentrated: 40% of the highest rated capacity of the hoist cars, non-concurrently with the uniform load, acting on a 4 square inch area anywhere within the boundary of handrail, or within the gross area of the walkway if handrails are not provided.
FRAME STRUCTURE
{L} Live load values determined by detailed analysis performed by the design professional acting on any combination of differing floor levels equal to the number of hoist cars plus one but not less than 50 psf or the carrying capacity of the elevator cars and hoist cars, whichever is greater.
SNOW LOAD
{S} 20 psf acting on the top two floors of gross plan area of the back structure.
ICE LOAD
{I} 40% of the dead load or a detailed analysis performed by the design professional based on the equivalent of one-quarter inch ice.
DYNAMIC LOADING
{d} Lateral force and moment resulting from the starting and stopping of the hoist cars. When more than one car is in operation, the dynamic loading shall reflect the most critical combination. The Dynamic loading is to be considered basic loading. Impact loading need not be considered.
DEAD LOADS {D}—REFER TO RS 9–1
WIND LOADS {W} & {w}—REFER TO RS 9–5
DESIGN LOAD COMBINATIONS
For Allowable Stress Design, factors used in loading combinations conform to 27-594 of the Building Code. The back structures shall be designed for the critical combination of:
1. {D} + {L} + {d}
2. 0.67 ({D} + {W})
3. 0.75 ({D} + {L} + {d} + {w})
4. 0.67 ({D} + {I} + {w} + {S})
Load factors for LRFD designs shall adhere to the LRFD recommendations and guidelines contained in the reference standard for the material used.
RS 9-3
AASHTO HB–13–1983—Standard Specifications for Highway Bridges, Thirteenth Edition, and 1984, 1985 and 1986 Interim Specifications.
RS 9-4
AREA–1987—Specifications for Steel Railway Bridges, Chapter 15, Steel Structures, Manual for Railway Engineering.
RS 9-5. MINIMUM DESIGN WIND PRESSURES
1. DESIGN WIND PRESSURES ON STRUCTURAL FRAMES.—Minimum design pressures due to wind acting on vertical surfaces shall be in accordance with table RS 9–5–1, and minimum design pressures acting normal to horizontal or inclined surfaces shall be in accordance with table RS 9–5–2. The occurrence of the pressures on vertical, horizontal, and inclined surfaces of the building shall be considered as simultaneous.
TABLE RS 9–5–1 Design Wind Pressures on Vertical Surfaces
Height Zone (ft. above curb level) Design Wind Pressure on Vertical Surfaces (psf of projected solid surface) Structural Frame Panels Glass • 0–50 (signs and similar constructions of shallow depth only) 15 — • 0–100 20 30 • 101–300 25 30 • 301–600 30 35 • 601–1,000 35 40 • Over 1,000 40 40
TABLE RS 9–5–2 Design Wind Pressures on Horizontal and Inclined Surfaces
Roof Slope Design Wind Pressure Normal to Surface 30 degrees or less Either pressure or suction equal to 40 per cent of the values in Table RS9–5–1 over the entire roof area More than 30 degrees Windward Slope—pressure equal to 60 per cent of values in Table RS9–5–1.Leeward slope—suction equal to 40 per cent of values to Table RS9–5–1.
2. WALL ELEMENTS.—For design of mullions, muntins, girts, panels, and other wall elements (including their fastenings), other than glass panels, the wind pressure acting normal to wall surfaces shall be 30 psf or a 20 psf suction, for all height zones up to 500 ft. These values shall be deemed to include allowance for gust pressures. For height zones over 500 ft., the applicable design pressures shall be specially investigated, but shall not be less than the values indicated in table RS 9–5–1.
3. ROOF ELEMENTS.—The wind pressures acting on purlins, roofing, and other roof elements (including their fastenings) supporting small contributory areas of wind presentment shall be 1 1/2 times the values given in table RS 9–5–2.
4. OTHER BUILDING ELEMENTS.—Minimum wind pressures to be used in the design of other building elements shall be the values in table RS 9–5–1 multiplied by the following shape factors given in table RS 9–5–3.
TABLE RS 9–5–3 Shape Factors
Construction Shape Factor • Signs (and their supports), or portions thereof, having 70 per cent or more of solid surface 1.5 • Signs (and their supports), or portions thereof, having less than 70 per cent of solid surface 2.0 • Tanks, cooling towers, and similar constructions 1.5 • Upright, circular cylindrical surfaces 0.7 • Square and rectangular chimneys 1.5
For special structures such as curved and saw-toothed roofs, guys and cables, open trussed structures, parallel solid girders, and spheres, the design wind pressure shall be determined on the basis of recognized engineering analysis or by test.
5. EAVES AND CORNICES.—Eaves, cornices, and overhanging elements of the building shall be designed for upward pressures of twice the values given in table RS 9–5–1.
6. WIND LOAD BY MODEL TEST.—In lieu of the design wind pressures established in section 1 and 2 of this reference standard, and subject to review and approval of the commissioner, design wind pressures may be approximated from suitably conducted model tests. The tests shall be predicated on a basic wind velocity of 80 mph at the 30 ft. level, and shall simulate and include all factors involved in considerations of wind pressure, including pressure and suction effects, shape factors, functional effects, gusts, and internal pressures and suctions.
7. CONSTRUCTION ELEVATOR AND MATERIAL HOIST TOWER BACK STRUCTURES
DEFINITIONS:
Back Structure: A system of landing platforms and/or supports designed to transmit construction elevator or material hoist tower loads into the building structure.
Inland: As defined by ASCE 7–98, exposure Category A
Coastal: As defined by ASCE 7–98, exposure Category D
WIND LOADS
{W} Storm Wind Load: equivalent to 25 yr. Mean recurrence wind per ASCE 7–98 standard, taking into account the exposure terrain, height zone, shielding coefficients, etc. In lieu of detailed analysis by the design professional, the following values may be used:
Design storm wind (25 yr. Mean Recurrence)
Wind pressure loading (in psf) on gross cross sectional area of the back structure
Zone/Elevation 0–50 feet 50–150 feet 150–400 feet 400–700 feet >700 feet Inland 14.4 20.7 25.6 33.8 40 Coastal 14.4 25.6 43.2 65.5 69.6
Unless the structure is fully enclosed in curtain walls, the following wind loading shall be analyzed:
1. Parallel to the building facade per the above table.
2. Normal to the building facade at one-half the value of the above table.
Wind directions shall be considered to be non-concurrent.
{w} In-Service wind: a 35 mph (wind pressure of 3.13 psf) from any direction acting on the back structure.
RS 9-6. EARTHQUAKE LOADS
This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 9-6 at American Legal Publishing.
UBC SECTION 2312–1990—Earthquake Regulations with Accumulative Supplement.
MODIFICATIONS—The provisions of UBC Section 2312 shall be subject to the following modifications. The subdivisions, paragraphs, subparagraphs and items are from this section.
Subdivision (a) General.
Paragraph 1. Minimum seismic design.
Delete this paragraph and substitute the following:
The following types of construction shall, at a minimum, be designed and constructed to resist the effects of seismic ground motions as provided in this section:
• new structures on new foundations;
• new structures on existing foundations; and
• enlargements in and of themselves on new foundations. Buildings classified in New York City occupancy group J-3 and not more than three stories in height need not conform to the provisions of this section.
The Commissioner may require that the following types of construction be designed and constructed to incorporate safety measures as necessary to provide safety against the effects of seismic ground motions at least equivalent to that provided in a structure to which the provisions of this section are applicable:
• new buildings classified in occupancy group J-3 and which are three stories or less in height; and
• enlargements in and of themselves where the costs of such enlargement exceeds sixty percent of the value of the building.
Pursuant to section 27-191 of the code the Commissioner shall have the authority to reject an application for a building permit which fails to comply with the requirements of this section.
Subdivision (b) Definitions.
Delete the definitions of the following terms and substitute the following new definitions:
"ECCENTRIC BRACED FRAME (EBF) is a steel-braced frame designed in conformance with reference standard RS 10–5C.
ESSENTIAL FACILITIES are those structures which are necessary for emergency operations subsequent to a natural disaster.
STORY DRIFT is the displacement of one level relative to the level above or below, including translational and torsional deflections."
Add the following definition before "SHEAR WALL":
"REINFORCED MASONRY SHEAR WALL is that form of masonry wall construction in which reinforcement acting in conjunction with masonry is used to resist lateral forces parallel to the wall and which is designed using reinforcement in conformance with Chapter 7 of reference standard RS 10–2."
Delete the definitions of the five frames under the SPACE FRAME paragraph and substitute the following stand-alone definitions:
"INTERMEDIATE MOMENT-RESISTING FRAME (IMRF) is a concrete frame designed in accordance with the requirements of Chapters 1 through 20 and Sections 21.1, 21.2 and 21.9 of reference standard RS 10–3.
MOMENT-RESISTING FRAME is a frame in which members and joints are capable of resisting forces primarily by flexure.
ORDINARY MOMENT-RESISTING FRAME (OMRF) is a moment-resisting frame conforming to the requirements of Chapters 1 through 20 of reference standard RS 10–3 or reference standards RS 10–5A and RS 10–5C but not meeting the special detailing requirements for ductile behavior.
SPECIAL MOMENT-RESISTING FRAME (SMRF) is a moment-resisting frame conforming to reference standards RS 10–3 or RS 10–5A and RS 10–5C and specially detailed to provide ductile behavior by complying with the requirements of Chapters 1 through 20 and Sections 21.1 through 21.8 of reference standard RS 10–3 or reference standards RS 10–5A and RS 10–5C.
VERTICAL LOAD-CARRYING FRAME is a frame designed to carry all vertical gravity loads."
Subdivision (d) Criteria Selection.
Paragraph 1. Basis for design.
Delete the word "zoning" in the first sentence and delete the last sentence.
Paragraph 2. Seismic Zones.
Delete the title and paragraph and substitute the following:
"2. Seismic Zone. The seismic zone factor, Z, for buildings, structures and portions thereof in New York City shall be 0.15. The seismic zone factor is the effective zero period acceleration for S1 type rock."
Paragraph 3. Site geology and soil characteristics.
Delete the title and the paragraph and substitute the following:
"3. Site geology, soil characteristics and foundations.
A. General.
Soil profile type and site coefficient, S, shall be established in accordance with Table No. 23-J.
B. Liquefaction.
(i) Soils of classes 7–65, 8–65, 10–65 and non-cohesive class 11–65 below the ground water table and less than fifty feet below the ground surface shall be considered to have potential for liquefaction.
(ii) The potential for liquefaction of level ground shall be determined on the basis of Standard Penetration Resistance (N) in accordance with Figure No. 4;
Category A: Soil shall be considered liquefiable.
Category B: Liquefaction is possible.
Soil shall be considered liquefiable for structures of Occupancy Categories I, II and III of Table No. 23-K.
Category C: Liquefaction is unlikely and need not be considered in design.
At any site the highest category of liquefaction potential shall apply to the most critical strata or substrata.
(iii) Liquefiable soils shall be considered to have no passive (lateral) resistance or bearing capacity value during an earthquake. An analysis shall be submitted by an engineer which demonstrates, subject to the approval of the Commissioner, that the proposed construction is safe against liquefaction effects on the soil.
(iv) Where liquefiable soils are present in sloped ground or over sloped nonliquefiable substrata and where lateral displacement is possible, a stability analysis shall be submitted by an engineer which demonstrates, subject to the approval of the Commissioner, that the proposed construction is safe against failure of the soil.
C. Foundation Plates and Sills.
Foundation plates or sills shall be bolted to the foundation or foundation wall with not less than one-half inch nominal diameter steel bolts embedded at least seven inches into the concrete or masonry and spaced not more than six feet apart. There shall be a minimum of two bolts per piece with one bolt located within twelve inches of each end of each piece. A properly sized nut and washer shall be tightened on each bolt to the plate.
D. Foundation Interconnection of Pile Caps and Caissons.
Individual pile caps and caissons of every structure subjected to seismic forces shall be interconnected by ties. Such ties shall be capable of resisting, in tension or compression, a minimum horizontal force equal to the product of ZI/4 and the larger column vertical load at the end of each tie.
Exception: Other approved effective methods of foundation interconnection may be used where it can be demonstrated by an analysis that equivalent restraint and relative displacement can be provided."
Paragraph 5, subparagraph C, Irregular structures.
Delete the entire last sentence in item (i).
Paragraph 6, subparagraph E, Dual system.
Delete items (ii) and (iii) and substitute the following:
"(ii) Resistance to lateral load is provided by shear walls or braced frames and a moment-resisting frame (SMRF, IMRF or OMRF). The moment-resisting frames shall be designed to independently resist at least 25 percent of the design base shear. The shear walls or braced frames shall be designed to resist at least 75 percent of the cumulative story shear at every level. Overturning effects may be distributed in accordance with item (iii) below.
(iii) The two systems shall be designed to resist the total design base shear in proportion to their relative rigidities considering the interaction of the dual system at all levels."
Paragraph 7. Height limits.
Delete this paragraph.
Paragraph 8. Selection of lateral force procedure.
Delete paragraph 8 and substitute the following:
"8. Selection of lateral force procedure. All structures shall be designed using either the static lateral force procedure of Section 2312(e) or using the dynamic lateral force procedure of Section 2312(f). In addition, the dynamic lateral force procedure shall be considered, but is not required, for the design of the following:
A. Structures over 400 feet in height.
B. Irregular structures.
C. Structures located on Soil Profile Type S4 which have a period greater than 1 second. The analysis should include the effects of soils at the site and should conform to Section 2312(f)2."
Paragraph 9, subparagraph C, Irregular features.
Delete this subparagraph and substitute the following:
"C. Irregular features. Only structures having either vertical irregularities Type D or E as defined in Table No. 23-M or horizontal irregularities Type D or E as defined in Table No. 23-N shall be designed to meet the additional requirements of those sections referenced in the tables."
Paragraph 10. Alternate procedures.
Add at the end of the paragraph the words "when such procedures are consistent with this standard and subject to the approval of the Commissioner".
Subdivision (e) Minimum Design Lateral Forces and Related Effects.
Paragraph 1. General, subparagraph A.
Add the words "parking structures" before the word "storage" in the first sentence.
Paragraph 1. General, subparagraph C.
Delete this subparagraph.
Paragraph 2, subparagraph A, Design base shear.
Change the value for the minimum ratio of C/Rw shown at the end of this subparagraph to "0.050".
Paragraph 2, subparagraph B, Structure period.
Delete the values in item (i) for Ct and substitute the following:
"Ct = 0.035 for concrete and steel moment-resisting frames.
Ct = 0.030 for eccentric braced frames.
Ct = 0.030 for dual systems where the building height exceeds 400 feet or 0.020 for heights less than 160 feet and varies linearly from 0.020 to 0.030 for building heights from 160 to 400 feet.
Ct = 0.020 for all other structures."
Delete the sentence immediately after "Ct = 0.020 for all other structures" and substitute the following:
"Alternately, the value of T for structures with concrete or masonry shear walls may be taken as 0.1 (hn)3/4 ÖAc."
Paragraph 3, subparagraph C, Combinations along different axes.
Delete this subparagraph.
Paragraph 6. Horizontal torsional moments.
Delete the fourth paragraph starting with the words "Where torsional irregularity exists" and ending with the words "considered for design."
Paragraph 7, Overturning, subparagraph B.
Delete the words "Seismic Zones 3 and 4" at the beginning of this subparagraph.
Delete item (iii) and substitute the following:
"(iii) Such columns shall meet the detailing or member limitations of reference standard RS 10–3 for concrete and reference standard RS 10–5C for steel structures."
Paragraph 7, subparagraph C.
Delete this subparagraph and substitute the following:
"C. For regular buildings, the force Ft may be omitted when determining the overturning moment to be resisted at the foundation-soil interface."
Paragraph 8. Story drift limitation.
Change the value for the minimum ratio of C/Rw shown at the end of this paragraph to "0.050".
Paragraph 9. P-delta effects.
Delete the last sentence of this paragraph.
Paragraph 10. Vertical component of seismic forces.
Delete this paragraph in its entirety and substitute the following:
"10. Vertical component of seismic forces. Horizontal cantilever components shall be designed for a net upward force of 0.05 Wp."
Subdivision (f) Dynamic lateral force procedure.
Paragraph 2. Ground motion.
Add the following at the end of subparagraph A:
"For soil type S4 profile, see B below."
Add the following at the end of subparagraph B:
"The design of all structures located on a soil type S4 profile shall be based on properly substantiated site-specific spectra."
Paragraph 5, subparagraph C, Scaling of results.
Add after the word "procedures" in the first sentence, the words "including the appropriate Importance Factor, I,".
Delete item (i) and substitute the following:
"(i) The base shear shall be increased to the following percentage of the value determined from the procedures of Section 2312(e), including consideration of the minimum value of C/Rw, except that the coefficient C, for a period T greater than 3 seconds, may be calculated as 1.80 S/T:
(a) 100 percent for irregular buildings; or
(b) 90 percent for regular buildings, except that the base shear shall not be less than 80 percent of that determined from Section 2312(e) using the period, T, calculated from Method A."
Paragraph 5, subparagraph D, Directional effects.
Delete the words "and prestressed elements" in the second sentence and delete the word "Alternately" at the start of the third sentence.
Paragraph 5, subparagraph F, Dual systems.
Delete this subparagraph and substitute the following:
"F. Dual Systems. Where the lateral forces are resisted by a dual system, as defined in Section 2312(d)6E above, the combined system shall be capable of resisting the base shear determined in accordance with this section. The moment-resisting frame, shear walls and braced frames shall conform to Section 2312(d)6E. The moment-resisting frame may be analyzed using either the procedures of Section 2312(e)4 or those of Section 2312(f)5."
Paragraph 6. Time history analysis.
Add the following words at the end of the sentence: "and the results shall be scaled in accordance with Section 2312(f) 5C".
Subdivision (h) Detailed Systems Design Requirements.
Paragraph 1. General.
Delete the words "Chapters 24 through 28" in the fourth sentence of the first paragraph and insert the words "reference standard RS 10".
Delete the words "in Seismic Zones 2, 3 and 4" in the second and fourth paragraphs.
Paragraph 2, subparagraph A, General.
Delete the words "Chapters 24 through 27" at the end of this subparagraph and insert the words "reference standard RS 10".
Paragraph 2, subparagraph C, Connections.
Delete this subparagraph.
Paragraph 2, subparagraph D, Deformation compatibility.
Delete the words "to the reinforcing steel" from the last sentence.
Paragraph 2, subparagraph G, Concrete frames.
Delete this subparagraph and substitute the following:
"G. Concrete frames. Concrete frames required by design to be part of the lateral force resisting system shall, at a minimum, be intermediate moment-resisting frames, except as noted in Table 23–0."
Paragraph 2, subparagraph H, Anchorage of concrete or masonry walls.
Delete the words "Section 2310" in the fifth line and insert the words "reference standards RS 9–6, 10–1B and 10–2".
Paragraph 2, subparagraph I, Diaphragms.
Delete items (iv), (v) and (vi).
Paragraph 2, subparagraph J, Framing below the base.
Delete the words "Chapters 26 and 27" in the third line and insert the words "reference standards RS 10–3 and RS 10–5C".
Paragraph 2, subparagraph K, Building separations.
Delete this subparagraph and substitute the following:
"K. Building Separations. All structures shall be separated from adjoining structures. Separation due to seismic forces shall allow for 1 inch displacement for each 50 feet of total building height. Smaller separation may be permitted when the effects of pounding can be accommodated without collapse of the building."
Subdivision (i) Nonbuilding Structures.
Paragraph 4. Other nonbuilding structures.
Delete in the first sentence of item (iii) the word "national" and insert the word "reference", and delete the words "seismic zones and" in the paragraph following item (iii).
Subdivision (j) Earthquake-recording Instrumentations.
Delete this subdivision.
Table No. 23-I, Seismic Zone Factor Z.
Delete this table and substitute the following new table:
Table No. 23-I Seismic Zone Factor Z
ZONE NEW YORK CITY Z 0.15
Table No. 23-J, Site Coefficients.
Delete this table and notes and substitute the following new table and notes:
Table No. 23-J Site Coefficients
Type Descriptions Factor S0 A profile of Rock materials of class 1–65 to 3–65 0.67 S1 A soil profile with either: (a) Soft Rock (4–65) or Hardpan (5–65) or similar material characterized by shear-wave velocity greater than 2,500 feet per second, or (b) Medium Compact to Compact Sands (7–65) and Gravels (6–65) or Hard Clays (9–65), where the soil depth is less than 100 feet. 1.0 S2 A soil profile with Medium Compact to Compact Sands (7–65) and Gravels (6–65) or Hard Clays (9–65), where the soil depth exceeds 100 feet. 1.2 S3 A total depth of overburden of 75 feet or more and containing more than 20 feet of Soft to Medium Clays (9–65) or Loose Sands (7–65, 8–65) and Silts (10–65), but not more than 40 feet of Soft Clay or Loose Sands and Silts. 1.5 S4 A soil profile containing more than 40 feet of Soft Clays (9–65) or Loose Sands (7–65, 8–65), Silts (10–65) or Uncontrolled Fills (11–65), where the shear-wave velocity is less than 500 feet per second. 2.5
Notes:
1. The site S Type and corresponding S Factor shall be established from properly substantiated geotechnical data with the classes of materials being defined in accordance with Section 27-675 (C26–1103.1) of the administrative code of the City of New York.
2. The soil profile considered in determining the S Type shall be the soil on which the structure foundations bear or in which pile caps are embedded and all underlying soil materials.
3. Soil density/consistency referred to in the table should be based on standard penetration test blow counts (N-values) and taken as: (a) for sands, loose—where N is less than 10 blows per foot, medium compact—where N is between 10 and 30, and compact—where N is greater than 30 blows per foot; and (b) for clays, soft—where N is less than 4 blows per foot, medium—where N is between 4 and 8, stiff to very stiff—where N is between 8 and 30, and hard—where N is greater than 30 blows per foot.
4. When determining the type of soil profile for profile descriptions that fall somewhere in between those provided in the above table, the S Type with the larger S factor shall be used.
5. For Loose Sands, Silts or Uncontrolled Fills below the ground water table, the potential for liquefaction shall be evaluated by the provisions of Section 2312(d)3.
Table No. 23-K, Occupancy Categories.
Add the words "Buildings for schools through secondary or day-care centers—capacity more than 250 students" below the words "Fire and police stations" in the Essential Facilities category, and delete those words from within the Special Occupancy Structure Category.
Add in item III Special Occupancy Structure to the words, "All structures with occupancy > 5000 persons", the words "excluding Occupancy Group E buildings".
Table No. 23-O, Structural Systems.
Delete this table and notes and substitute the following new Table No. 23-O and notes.
Table No. 23-O Structural Systems
Basic Structural System Lateral Load-Resisting System Description R w A. Bearing WallSystem 1. Light-framed walls with shear panels 1. a. Plywood walls for structures three stories or less 8 1. b. All other light-framed walls 6 2. Shear Walls 2. a. Concrete 6 2. b. Reinforced masonry 5 3. Light steel-framed bearing walls with tension-only bracing 4 4. Braced frames where bracing carries gravity load 4. a. Steel 6 4. b. Concrete 4 4. c. Heavy timber 4 B. Building Frame 1. Steel eccentric braced frame (EBF) 10 B. System 2. Light-framed walls with shear panels 2. a. Plywood walls for structures three-stories or less 9 2. b. All other light-framed walls 7 3. Shear Walls 3. a. Concrete 8 3. b. Reinforced masonry 6 4. Concentric braced frames 4. a. Steel 8 4. b. Concrete 8 4. c. Heavy Timber 8 C. Moment-Resisting Frame 1. Special moment-resisting frames (SMRF) 1. a. Steel 12 C. System 1. b. Concrete 12 2. Concrete intermediate moment-resisting frames (IMRF) 8 3. Ordinary moment-resisting frames (OMRF) 3. a. Steel 6 3. b. Concrete4 4 D. Dual System 1. Shear Walls 1. a. Concrete with SMRF 12 1. b. Concrete with steel OMRF 6 1. c. Concrete with concrete IMRF 9 1. d. Concrete with concrete OMRF 5 1. e. Reinforced masonry with SMRF 8 1. f. Reinforced masonry with steel OMRF 6 1. g. Reinforced masonry with concrete IMRF 7 2. Steel eccentric braced frame 2. a. With steel SMRF 12 2. b. With steel OMRF 6 3. Concentric braced frames 3. a. Steel with steel SMRF 10 3. b. Steel with steel OMRF 6 3. c. Concrete with concrete SMRF 9 3. d. Concrete with concrete IMRF 6
Notes:
1. Basic structural systems are defined in Section 2312(d)6.
2. See Section 2312(e)3 for combinations of structural systems.
3. See Sections 2312(d)8C and 2312(d)9B for undefined systems.
4. Prohibited with S3 or S4 soil profiles or where the height exceeds 160 feet.
Table No. 23-P, Horizontal Force Factor Cp.
Delete this table and notes and substitute the following new Table No. 23-P and notes:
Table No. 23-P Horizontal Force Factor Cp 1
Elements of Structures, Nonstructural Components and Equipment Value of C p I. Part of Portion of Structure I. 1. Walls, including the following: I. 1. a. Unbraced (cantilevered) parapets. 2.00 I. 1. b. Other exterior walls above street grade2. 0.75 I. 1. c. All interior bearing walls. 0.75 I. 1. d. All interior nonbearing walls and partitions around vertical exits, including offsets and exit passageways. 0.75 I. 1. e. Nonbearing partitions and masonry walls in areas of public assembly > 300 people. 0.75 I. 1. f. All interior nonbearing walls and partitions made of masonry in Occupancy I, II and III. 0.75 I. 1. g. Masonry or concrete fences at grade over 10 feet high. 0.50 I. 2. Penthouses (defined in article 2 of subchapter 2 of chapter 1 of title 27 of the building code) except where framed by an extension of the building frame. 0.75 I. 3. Connections for prefabricated structural floor and roof elements other than walls (see above) with force applied at center of gravity. 0.75 I. 4. Diaphragms3. II. Nonstructural Components II. 1. a. Exterior ornamentation and appendages including cornices, ornamental statuaries or similar pieces of ornamentation. 2.00 II. 1. b. Interior ornamentation and appendages in areas of public assembly including cornices, ornamental statuaries or similar pieces of ornamentation. 2.00 II. 2. Chimneys, stacks, trussed towers and tanks on legs. II. 2. a. Supported on or projecting as an unbraced cantilever above the roof more than one-half its total height. 2.00 II. 2. b. All others, including those supported below the roof with unbraced projection above the roof less than one-half its height, or braced or guyed to the structural frame at or above its center of mass. 0.75 II. 3. Exterior signs and billboards. 2.00 III. Equipment and Machinery 4 III. 1. Tanks and vessels (including contents), including support systems and anchorage. 0.75
Notes:
1. See Section 2312(g)2 for additional requirements for determining Cp for nonrigid equipment or for items supported at or below grade.
2. See Section 2312(h)2D(iii) and Section 2313(g)2.
3. See Section 2312(h)2I.
4. Equipment and machinery include such items as pumps for fire sprinklers, motors and switch gears for sprinkler pumps, transformers and other equipment related to life-safety including control panels, major conduit ducting and piping serving such equipment and machinery.
Figure No. 3, Normalized Response Spectra Shapes.
Delete the Figure No. 3 and insert the new Figure 3 and Table No. 23-R.
Table No. 23-R Spectral Acceleration in Fraction of G 5% Damping
T-SEC S 0 S 1 S 2 S 3 .01 0.150 0.150 0.150 0.150 .02 0.150 0.150 0.150 0.150 .05 0.375 0.283 0.262 0.244 .075 0.375 0.375 0.336 0.303 .090 0.375 0.375 0.375 0.334 .112 0.375 0.375 0.375 0.375 .267 0.375 0.375 0.375 0.375 .40 0.250 0.375 0.375 0.375 .48 0.208 0.313 0.375 0.375 .60 0.167 0.250 0.300 0.375 1.00 0.100 0.150 0.180 0.225 2.00 0.050 0.075 0.090 0.113 3.00 0.033 0.050 0.060 0.075
Note: This table presents acceleration (g) versus natural period (seconds) to facilitate the presentation of spectra in log-log form.
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1995/017.
RS 10. STRUCTURAL WORK
List of Referenced National Standards RS 10–1A Masonry. RS 10–1B Masonry. RS 10–2 Reinforced Masonry. RS 10–3 Reinforced Concrete. RS 10–4 Precast Concrete and Prestressed Concrete. RS 10–5A Design, Fabrication and Erection of Structural Steel for Buildings. RS 10–5B Load and Resistance Factor Design Specification for Structural Steel Buildings. RS 10–5C Steel Structures Resisting Earthquake Forces. RS 10–6 Design of Cold-Formed Steel Structural Members. RS 10–6A Design of Cold-Formed Stainless Steel Structural Members. RS 10–7 Long Span Steel Joists, LH-Series and Deep Longspan Joists, DLH-Series. RS 10–8 Lumber and Timber Construction. RS 10–9 Plywood Construction. RS 10–10A Specification for Aluminum Structures Allowable Stress Design RS 10–10B Specification for Aluminum Structures Load and Resistance Factor Design of Buildings and Similar Type Structures RS 10–11 Specifications for Aluminum Materials. RS 10–12 Gypsum Concrete. RS 10–13 Span for Joists and Rafters. RS 10–14 Evaluation of Strength Test Results of Concrete. RS 10–15 Shotcreting. RS 10–16 Obtaining and Testing Drilled Cores and Sawed Beams of Concrete. RS 10–17 Test for Compressive Strength of Cylindrical Concrete Specimens. RS 10–18 Structural Glued Laminated Timber. RS 10–19 Gypsum Sheathing Board. RS 10–20 Preservative Treatment of Lumber, Timbers, Bridge Ties and Mine Ties by Pressure Processes. RS 10–21 Making and Curing Concrete Test Specimens. RS 10–22 Preservative Treatment of Plywood by Pressure Process. RS 10–23 Zinc Coating (Hot Dip) on Iron and Steel Hardware. RS 10–24 Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles. RS 10–24A Zinc-Coated Parallel and Helical Steel Wire Structural Strand. RS 10–24B Zinc-Coated Steel Structural Wire Rope. RS 10–26 Zinc (Slab Zinc). RS 10–27 Fiberboard Nail-Base Sheathing. RS 10–28 Preservative Treatment of Poles by Pressure Processes. RS 10–29 Care of Pressure-Treated Wood Products. RS 10–30 Sampling and Testing Brick and Structural Clay Tile. RS 10–31 Building Brick (Solid Masonry Units Made from Clay or Shale). RS 10–31A Facing Brick (Solid Masonry Units Made from Clay or Shale). RS 10–31B Hollow Brick (Hollow Masonry Units Made from Clay or Shale). RS 10–32 Calcium Silicate Face Brick (Sand-Lime Brick). RS 10–33 Concrete Building Brick. RS 10–34 Structural Clay Loadbearing Wall Tile. RS 10–35 Structural Clay Non-Loadbearing Tile. RS 10–36 Solid Loadbearing Concrete Masonry Units. RS 10–37 Hollow Loadbearing Concrete Masonry Units. RS 10–38 Hollow Non-Loadbearing Concrete Masonry Units. RS 10–39 Gypsum Partition Tile or Block. RS 10–40 Ceramic Glazed Structural Clay Facing Tile, Facing Brick and Solid Masonry Units. RS 10–41 Zinc-Coated (Galvanized) Steel Woven Wire Fence Fabric. RS 10–42 Hard-Drawn Copper-Clad Steel Wire. RS 10–43 Stone, Architectural, Cast. RS 10–44 Chemical Admixtures for Concrete. RS 10–45 Report of Committee 334 of the American Concrete Journal of the American Concrete Institute. RS 10–46 Mortar for Unit Masonry. RS 10–47 Grout for Reinforced and Non-Reinforced Masonry. RS 10–48 Gypsum. RS 10–49 Test for Slump of Portland Cement Concrete. RS 10–50 [Deleted.] RS 10–51 Sampling Fresh Concrete. RS 10–52 Making and Curing Concrete Test Specimens in the Field. RS 10–53 Plywood Design Specifications. RS 10–54 Structural-Use Panels. RS 10–55 Plywood-Lumber Components. RS 10–56 Structural-Use Panels. RS 10–57 Standard for Construction and Industrial Plywood. RS 10–58 Diaphragms-Design/Construction Guide. RS 10–61 Standard for Testing Air Content of Freshly Mixed Concrete by Volumetric Method. RS 10–62 Standard for Testing Air Content of Freshly Mixed Concrete by Pressure Method. RS 10–63 Standard for Testing Unit Weight Yield and Air Content of Concrete. RS 10–64 Standard for Testing Unit Weight of Structural Lightweight Concrete. RS 10–65 Selecting Proportions for Structural Lightweight Concrete. RS 10–67 Safety Glazing Material Used in Buildings. RS 10–68 Specifications for Flat Glass.
LIST OF REFERENCED NATIONAL STANDARDS
ANSI–A41.2—Building Code Requirements for Reinforced Masonry as Modified—1960
ANSI/ACI–318—Building Code Requirements for Reinforced Concrete (with Modifications)—1983
ACI–525—Minimum Requirements for Thin Section Precast Concrete Construction as Modified—1963
AISC Steel Specification—Specification for the Design, Fabrication, and Erection of Structural Steel for Buildings, Effective November 1, 1978, and Supplement No. 1, Effective March 11, 1986, as Modified—1978
RCSCEF/AISC—Specifications for Structural Joints Using ASTM A 325 or A 490 Bolts. Approved November 13, 1985—1985
AISI—Specification for the Design of Cold-Formed Steel Structural Members August 19, 1986, as Modified—1986
AISI—Specification for the Design of Cold-Formed Stainless Steel Structural Members—1974
SJI—Standard Specifications for Open Web Steel Joists, H-Series, February 15, 1978, Revised November 7, 1983, as Modified—1978
SJI—Standard Specifications for Open Web Steel Joists, K-Series, November 4, 1985, Revised May 19, 1987—1985
SJI—Standard Specifications for Long Span Steel Joists, and LH-Series and Deep Long Span Steel Joists, and DLH-Series, February 5, 1978, Revised May 19, 1987, as Modified—1978
SJI—Standard Specification for Joist Girders, May 15, 1978, Revised May 19, 1987 as Modified—1978
SJI—Standard Specifications, Load Tables and Weight Tables for Steel Joists and Joist Girders—1988
ACI 506.2—Specification for Materials, Proportioning and Application of Shotcrete—1983 Revision—1977
NFoPA—National Design Specifications for Wood Construction and its January 1986 Supplement with 1987 Revisions—1986
ASTM C 317 76—Standard Specification for Gypsum Concrete (Reapproved 1981)—1976
NFoPA—Span Tables for Joists and Rafters—1977
ACI–214—Recommended Practice for Evaluation of Strength Test Results of Concrete (Reapproved 1983)—1977
ANSI/ASTM C 42—Standard Method of Obtaining and Testing Drilled Cores and Sawed Beams of Concrete—1984a
ANSI/ASTM C 39—Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens—1984
ASTM B 209—Standard Specification for Aluminium and Aluminium-Alloy Street and Plate—1988
ASTM B 308—Standard Specification for Aluminium-Alloy 6061–T6 Standard Structural Shapes, Rolled or Extruded—1988
ASTM B 429—Standard Specification for Aluminium Alloy Extruded Structural Pipe and Tube—1988
ANSI/AITC–A190.1—Structural Glued Laminated Timber and AITC 200–83 Inspection Manual—1983
ANSI/ASTM C 79—Standard Specification for Gypsum Sheathing Board—1987
AWPA–C2—Standard for the Preservative Treatment of Lumber, Timbers, Bridge Ties and Mine Ties by Pressure Processes—1988
ANSI/ASTM C 192—Standard Method of Making and Curing Concrete Test Specimens in the Laboratory—1981
AWPA–C9—Standard for the Preservative Treatment of Plywood by Pressure Processes—1985
ANSI/ASTM A 153—Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware—1982
ASTM A 90—Tests for Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles—1981
ANSI/ASTM A 586—Standard Specification for Zinc-Coated Steel Parallel and Helical Steel Wire Structural Strand—1986
ASTM A 603—Standard Specification for Zinc-Coated Steel Structural Wire Rope—1988
ASTM A 434—Specification for Quenched and Tempered Alloy Steel Bars, Hot-Wrought or Cold Finished—1981
ASTM B 6—Standard Specification for Zinc (Slab Zinc)—1987
ASTM D 2277—Specification for Fiberboard Nail-Base Sheathing—1987
AWPA–C4—Standard for Preservative Treatment of Poles by Pressure Processes—1988
AWPA–M4—Standard for the Care of Pressure-Treated Wood Products—1984
ANSI–A82.1/ASTM C 67—Standard Methods of Sampling and Testing Brick and Structural Clay Tile—1987
ANSI–A98.1/ASTM C 62—Standard Specification for Building Brick (Solid Masonry Units Made from Clay or Shale)—1988
ANSI–A99.1/ASTM C 216—Standard Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale)—1987a
ANSI–ASTM C 652—Standard Specification for Hollow Brick (Hollow Masonry Units Made from Clay or Shale)—1988
ANSI–A78.1/ASTM C 73—Standard Specification for Calcium Silicate Face Brick (Sand-Lime Brick)—1985
ANSI–A75.1/ASTM C 55—Standard Specification for Concrete Building Brick—1985
ANSI–A74.1/ASTM C 34—Standard Specification for Structural Clay Load-Bearing Wall Tile—1984
ANSI/ASTM C 56—Standard Specification for Structural Clay Non-Load Bearing Tile (Reapproved 1986)—1971
ANSI–A81.1/ASTM C 145—Standard Specification for Solid Load-Bearing Concrete Masonry Units—1985
ANSI–A79.1/ASTM C 90—Standard Specification for Hollow, Load-Bearing Concrete Masonry Units—1985
ANSI–A80.1/ASTM C 129—Standard Specification for Hollow, Non-Load Bearing Concrete Masonry Units—1985
ANSI/ASTM C 52—Standard Specification for Gypsum Partition Tile or Block (Reapproved 1977)—1954
ANSI/A101.1/ASTM C 126—Standard Specification for Ceramic Glazed Structural Clay Facing Tile, Facing Brick and Solid Masonry Units—1986
ANSI/ASTM A 116—Standard Specification for Zinc-Coated (Galvanized) Steel Woven Fence Fabric—1988
ANSI/ASTM B 227—Standard Specifications for Hard-Drawn Copper-Clad-Steel Wire (Reapproved 1980)—1970
FS SS–S–721C—Stone, Architectural, Cast—1964
ANSI/ASTM C 494—Standard Specification for Chemical Admixtures for Concrete—1986
ACI–ASCE–334—Concrete Shell Structures Practice and Commentary. Report of Committee 334 of American Concrete Journal of the American Concrete Institute, Proc. V61, M.9, Sept. 1964 (Revised 1982)—1964
ANSI/ASTM C 270—Standard Specification for Mortar for Unit Masonry—1988
ANSI/ASTM C 476—Standard Specification for Grout for Reinforced and Non-Reinforced Masonry—1983
ANSI/ASTM C 22—Standard Specification for Gypsum—1983
ASTM C 143—Standard Test Method for Slump of Portland Cement Concrete—1978
ANSI/ASTM C 172—Standard Method of Sampling Freshly Mixed Concrete—1982
ANSI/ASTM C 31—Standard Method of Making and Curing Concrete Test Specimens in the Field—1987
APA—Plywood Design Specifications—1986
APA PRP–108—Performance Standards and Policies for Structural-Use Panels—1986
APA—Design and Fabrication Specification of all Plywood Lumber Components—1985
TECO—Standard and Policies for Structural-Use Panels—1981
DOC PS 1–83—U.S. Product Standard for Construction & Industrial Plywood (Revised June 1987)—1983
ACI–211.2—Standard Practice for Selecting Proportions for Structural Lightweight Concrete—1981
ANSI–Z97.1—Safety Performance Specifications and Methods of Test for Safety Glazing Materials Used in Buildings—1984
ASTM C 1036—Standard Specification for Flat Glass—1985
ASTM C 1048—Standard Specification for Heat-Treated Flat Glass Kind HS, Kind FT Coated and Uncoated Glass—1987
AISC–LRFD—Load and Resistance Factor Design Specification for Structural Steel Buildings, effective September 1, 1986, as Modified—1986
ANSI/ASTM C 173—Standard Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method—1978
ANSI/ASTM C 231—Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method—1982
ANSI/ASTM C 138—Standard Test Method for Unit Weight, Yield, and Air Content (Gravimetric) of Concrete—1981
ANSI/ASTM C 567—Standard Test Method for Unit Weight of Structural Lightweight Concrete—1985
AA Aluminum Design Manual Part 1-A—Specification for Aluminum Structures Allowable Stress Design (Seventh Edition, January 2000)—2000.
AA Aluminum Design Manual Part 1-B—Specification for Aluminum Structures Load and Resistance Factor Design of Buildings and Similar Type Structures (Second Edition, January 2000)—2000.
ACI 530/ASCE 5—Building Code Requirements for Masonry Structures, as modified—1992.
ACI 530.1/ASCE 6—Specifications for Masonry Structures, as modified—1992.
ANSI/ACI-318—Building Code Requirements for Reinforced Concrete, as modified—1989.
MNL-120—Prestressed Concrete Institute Design Handbook, Third Edition—1985.
UBC Section 2723—Steel Structures Resisting Forces Induced by Earthquake Motions in Seismic Zones Nos. 1 and 2 with Accumulative Supplement, as modified—1990.
AITC 117—Specification for Structural Glued Laminated Timber of Softwood Species—Design Standard—1987 and Manufacturing Standard—1988.
APA Form No. L350C—Diaphragms-Design/Construction Guide—1989.
APA Form No. E30K—Residential & Commercial Design/Construction Guide—1989.
RS 10-1A. MASONRY
Section
1 General.
2 Definitions.
3 Materials.
4 Design.
5 Lateral Support.
6 Thickness and Height of Masonry Empirical Provisions.
7 Bonding.
8 Grouted and Filled Cell Masonry.
9 Anchorage.
10 Miscellaneous Requirements.
11 Veneer.
12 Miscellaneous Structures and Systems.
SECTION 1 – GENERAL (REFERENCE STANDARD RS 10–1A MASONRY)
1.1 Scope.—This standard provides minimum requirements for the design and construction of non-enlargement alterations to unit masonry in buildings constructed on or before the effective date of this local law as an alternate to RS 10–1B, not including plain or reinforced unit concrete, reinforced gypsum, or reinforced unit masonry. All new construction and enlargement alterations in and of themselves of unit masonry on new or existing foundations, not including plain reinforced concrete, reinforced gypsum, or reinforced unit masonry shall comply with reference standard RS 10–1B.
1.2 DIMENSIONS.—Unless the word "actual" is used, the dimensional requirements for masonry and for masonry units given in this standard are nominal. The measured dimensions of masonry shall be not more than 1/2 in. less than the required nominal dimensions.
SECTION 2 – DEFINITIONS (REFERENCE STANDARD RS 10–1A MASONRY)
Architectural terra cotta.—(See ceramic veneer)
Ashlar masonry.—Masonry composed of rectangular units having sawed, dressed, or squared beds, properly bonded, and laid in mortar.
Backup.—That part of a masonry wall behind the facing.
Bonder.—A masonry unit that overlaps two or more adjacent wythes of masonry to bind or tie them together.
Brick.—A masonry unit, not less than 75 per cent solid, having a shape approximating a rectangular prism, made from burned clay or shale, or mixture thereof. Brick may be composed of other materials when so designated, as for example, "concrete brick" and "sand-lime brick".
Buttress.—A bonded column of masonry built as an integral part of the wall and projecting from either or both surfaces decreasing in cross-sectional area from base to top.
Ceramic veneer.—Hard-burned, glazed or unglazed, non-load-bearing clay masonry units, solid or hollow, plain or ornamental.
Chase.—A continuous recess in a wall to receive pipes, ducts, conduits, etc.
Collar joint.—The vertical longitudinal joint between wythes of masonry.
Column.—A vertical compression member whose width does not exceed three times its thickness.
Coping.—The materials or masonry units used to form a cap or finish on top of a wall, column, chimney, or pilaster to protect the masonry below from penetration of water.
Corbelling.—The projecting of successive courses of masonry out from the face of the wall to increase the wall thickness or to form a shelf or ledge.
Course.—One of the continuous horizontal layers of masonry units bonded together with mortar.
Cross-sectional area.—Net cross-sectional area of a masonry unit shall be taken as the gross cross-sectional areas minus the area of the cores or cellular spaces. Gross cross-sectional area of scored units shall be determined to the outside of the scoring but the cross-sectional area of the grooves shall not be deducted from the gross cross-sectional area to obtain the net cross-sectional area.
Effective height.—The height of a wall or column which is assumed for purposes of calculating the slenderness ratio. (See section 4.4.2.)
Effective thickness.—The thickness of a wall or column that is assumed for purposes of calculating the slenderness ratio. (See section 4.4.3.)
Filled cell masonry.—Masonry construction made with vertical cell hollow units in which all cells and voids are filled by pouring grout therein.
Grouted masonry.—Masonry construction made with solid masonry units in which the collar joints are filled by pouring grout therein.
Header.—A brick or other masonry unit laid with the end surface exposed.
Hollow masonry unit.—A masonry unit whose net cross-sectional area in any plane parallel to the bearing surface is less than 75 per cent of its gross cross-sectional area measured in the same plane. (See cross-sectional area.)
Masonry.—A built-up construction or combination of masonry units set in mortar.
Parging.—The process of applying a coat of mortar to masonry construction.
Partition.—An interior non-loadbearing wall supporting no vertical load other than its own weight.
Pilaster.—A bonded or keyed column of masonry having uniform cross section throughout its height; built as part of a wall and projecting from either or both surfaces. A pilaster may serve as either a vertical beam, or a column, or both.
Rubble.—
(1) Coursed rubble.—Masonry composed of roughly shaped stones fitting approximately on level beds, well bonded, and brought at vertical intervals to continuous level beds or courses.
(2) Random rubble.—Masonry composed of roughly shaped stones, well bonded and brought at irregular vertical intervals to discontinuous but approximately level beds or courses.
(3) Rough or ordinary rubble.—Masonry composed of nonshaped or field stones laid without regularity or coursing, but well bonded.
Solid masonry unit.—A masonry unit whose net cross-sectional area in every plane parallel to the bearing surface is 75 per cent or more of its gross cross-sectional area measured in the same plane. (See cross-sectional area.)
Veneer.—A single facing wythe of masonry units or similar materials securely attached to a wall for the purpose of providing ornamentation, protection, insulation, etc., but not so bonded or attached as to be considered as exerting common reaction under load.
Wall.—A vertical compression member having a horizontal dimension, measured at right angles to the thickness, of more than three times the thickness.
(1) Cavity wall.—A wall built of masonry units so arranged as to provide a continuous air space within the wall between the inner and outer wythes (with or without insulating material), and in which the wythes are tied together with metal ties.
(2) Composite wall.—A multiple-wythe wall in which at least one of the wythes is dissimilar to the other wythe or wythes with respect to type of masonry unit, mortar, or construction.
(3) Curtain wall.—An exterior non-load-bearing wall.
(4) Faced walls.—A composite wall in which the masonry facing and the backing are so bonded as to exert a common reaction under load.
(5) Hollow-masonry wall.—A wall built of hollow masonry units.
(6) Loadbearing wall.—A wall that supports any vertical load in addition to its own weight.
(7) Masonry bonded hollow wall.—A wall built of masonry so arranged as to provide an air space within the wall between the inner and outer wythes and in which the wythes are bonded together with solid masonry units.
(8) Non-loadbearing wall.—A wall that supports no vertical load other than its own weight.
(9) Panel wall.—An exterior non-loadbearing wall in skeleton frame construction, wholly supported at each story.
(10) Solid masonry wall.—A wall built of solid masonry units laid continguously, with joints between units filled with mortar or grout.
(11) Veneered wall.—A composite wall having a facing of masonry units or other weather-resisting noncombustible materials securely attached to the backing, but not so bonded as to intentionally exert common action under load. (See section 11.)
Wythe.—Each continuous vertical longitudinal section of a wall. For walls of unit masonry, each wythe is one masonry unit in thickness.
SECTION 3 – MATERIALS
3.1 QUALITY.—Masonry materials shall conform to the standards and requirements set forth herein. Where no standards are established, the quality of materials shall be based on generally accepted good practice.
3.2. MASONRY UNITS.—Except as noted in sections 3.2.1 to 3.2.3, the quality of all masonry units used in building shall conform to the standard and grade shown in table RS 10–1.1. Manufacturer's certification as to the suitability of the material for the proposed use shall be submitted for all masonry units used in structural applications.
3.2.1 Ceramic veneer.—All ceramic veneer shall have a strong homogeneous body conforming to the following physical requirements:
(a) The average compressive strength of at least five 1 in. square specimens shall be not less than 5,000 psi with no individual specimen testing less than 4,500 psi. Compression tests shall be made on five specimens, 1 in. by 1 in. face size and the full thickness of the ceramic veneer. Loads shall be applied to the test specimens in a direction parallel to the exposed face. Specimens shall be capped and tested in accordance with reference standard RS 10–30.
TABLE RS 10–1–1 Material Standards
Units Reference Standard Severe Exposure Minimum Grade Moderate Exposure No Exposure Brick— • Clay or shale RS 10–31 SW MW NW • Sandlime RS 10–32 SW MW NW • Concrete RS 10–33 U Pc G Structural Clay Tile— • Loadbearing RS 10–34 LBX LBX LB • Non-Loadbearing RS 10–35 not permitted not permitted NB Concrete Masonry Units— • Solid loadbearing RS 10–36 U Pc G • Hollow loadbearing RS 10–37 U Pc G • Hollow non-loadbearing RS 10–38 not permitted permitted permitted Gypsum a— • Partition tile or block RS 10–39 not permitted not permitted permitted a • Cast Stone RS 10–43 permitted permitted permitted Ceramic Glazed Clay Masonry Units b— • Solid Units RS 10–40 permitted permitted permitted • Hollow Units RS 10–40 permitted permitted permitted Prefaced Concrete Masonry Units— RS 10–33 permitted permitted permitted RS 10–36 permitted permitted permitted RS 10–37 permitted permitted permitted
Notes—
a Gypsum partition tile or block shall not be used in bearing walls, or where subject to continuous dampness. Gypsum partition tile or block shall not be used for partitions to receive Portland cement plaster, ceramic tile, marble or structural glass wainscots unless self-furring metal lath is placed over the gypsum tile.
b Requirements for finish do not apply.
c Grade P may be used for "severe exposure" if protective coatings to prevent water penetration are applied on exterior face.
(b) The average absorption of not less than five specimens by 5 hr. boiling shall not exceed 16 per cent with no individual specimen exceeding 18 per cent. Absorption tests shall be made on five specimens, 6 in. by 6 in. in face size and the full thickness of the ceramic veneer. Absorption tests shall be made in accordance with reference standard RS 10–30.
3.2.2. Glass block.—Block may be solid or hollow; mortar bearing surfaces of the blocks shall be provided with a surface or a coating material to afford adhesion between mortar and block.
3.2.3. Natural stone.—Stone used in masonry shall be sound, free from friable inclusions and have characteristics of strength, durability and resistance to impact and abrasion commensurate with the proposed use.
3.3. METAL ANCHORS AND TIES.—Where corrosion-resistant anchors or ties are called for, they shall be copper coated or zinc coated, or of metal having corrosion-resistant qualities equivalent to zinc-coated mild steel.
(a) Zinc coatings on iron or steel shall conform to reference standard RS 10–23, class B–1, B–2, or B–3.
(b) Zinc coatings on wire shall conform to reference standard RS 10–41, class 1.
(c) Copper coated wire shall conform to reference standard RS 10–42, grade 30 HS.
3.3.1. Prefabricated joint reinforcement.—Prefabricated wire reinforcement for embedment in horizontal mortar joints shall consist of two or more longitudinal wires welded to cross wires. The distance between welded contacts of cross wires with each longitudinal wire shall not exceed 6 in. and 16 in. for smooth and deformed longitudinal wires, respectively. Longitudinal wires and cross wires shall be not less than no. 9 steel wire gage where used in 3/8 in. or thicker mortar joints and not less than no. 12 steel wire gage where used in thinner mortar joints. Cross wires of joint reinforcement that are used to bond the facing and backing of masonry, including cavity walls, shall be corrosion resistant and not less than no. 9 gage. The out-to-out spacing of longitudinal wires shall be such that the wires will be thoroughly embedded in the mortar joints as required in section 10.12.
3.3.2. Unit ties, anchors, or steel bar reinforcement.—Unit metal ties, anchors, or steel bar reinforcements for embedment in horizontal mortar joints shall conform to the applicable requirements of sections 7, 9, 10, and 11 or shall be equivalent in strength and stiffness to the size specified. Any such materials shall have a minimum 30,000 psi. yield strength.
3.4. MASONRY MORTAR AND GROUT.—Mortar, except gypsum, shall conform to reference standard RS 10–46. Grout shall conform to the applicable requirements of reference standard RS 10–47. Gypsum mortar shall be composed of one part gypsum, meeting the requirements of reference standard RS 10–48, to not more than three parts sand by weight. Water shall be clean and potable. Type H mortar shall be subject to controlled inspection and shall have a compressive strength of at least 6,000 psi when tested after 28 days at a cure of 75° F and 50% Relative Humidity, in accordance to ASTM C–109 and shall consist of:
1 bag (94 lbs.) Type I or III portland cement
50 lbs. ground limestone
3 1/4 cu. ft. mortar sand conforming to ASTM C 144
4 gallons polyvinylidene chloride latex having a solids content of at least 46%.
Prior to commencement of construction the supplier of the mortar shall submit an affidavit certifying that all the required ingredients specified have been supplied and included in the mix.
3.4.1. Types of mortar permitted.—Unit masonry shall be laid in mortar of the type specified in table RS 10–1–2.
SECTION 4 – DESIGN
4.1. GENERAL.—The design of masonry may be predicated upon analysis of stress or upon the empirical provisions indicated in this reference standard. The provisions of this section shall apply only where the design is predicated on analysis of stress. Except as specifically indicated, stresses shall be calculated on the basis of actual rather than nominal dimensions. For provisions relating to infrequent stress conditions the structural design provisions of the building code on combination of loads shall apply.
TABLE RS 10–1–2 Types of Mortar Permitted
Type of Masonry Type of Mortar Permitted a Masonry in contact with earth H, M or Sb Grouted and filled cell masonry H, M or S Masonry above grade or interior masonry: • Columns of solid units H, M, S, N or O • Columns of hollow units H, M or S • Walls of solid units H, M, S, N or O • Walls of hollow units H, M, S or N • Cavity walls and masonry bonded hollow walls H, M, S or N • Glass Block Masonry S or N • Non-loadbearing partitions and fireproofing H, M, S, N, O or Gypsum • Gypsum partition tile or block Gypsum • Linings of existing masonry, either above or below grade H, M or S
Notes—
a M, S, N, and O as defined by reference standard RS 10–46.
b Type N mortar may be used where masonry in contact with the earth will not be exposed to frost.
4.2. ALLOWABLE COMPRESSIVE STRESSES.—
4.2.1. General.—The allowable compressive stress in any type of masonry construction due to axial loads shall not exceed 0.25f 'm for walls or 0.2f 'm for columns. The allowable compressive stress in type H mortar construction due to flexural loads shall be 0.33 f ' m . The value of f ' m shall be based on the cross-sectional area (A g ) as defined in Sections 4.4.4 (a) and (b). Where Method No. 1 (Section 4.2.2(a)) is used, the value of f ' m shall be the specified minimum 28-day compressive strength of the masonry or the specified minimum compressive strength at any earlier age at which the masonry may be expected to receive its full load. Plans shall show the compressive strength of masonry (f ' m ) at a specified age for which the several parts of the structure were designed. Where Method No. 2 (Section 4.2.2(b)) is used, the tabulated values of f ' m shall be multiplied by the ratio of the strength of the mortar at a given age to the specified strength of the mortar at the age of 28 days, except that said ratio shall not be taken as greater than 1.0.
4.2.2. Determination of compressive strength of masonry.—The determination of the compressive strength of masonry (f ' m ) shall be made by one of the following methods:
(a) Method no. 1—Prism tests.—When the compressive strength of the masonry is to be established by preliminary tests, the tests shall be made in advance of the operations, using prisms built of similar materials under the same conditions and, insofar as possible, with the same bonding arrangements as for the structure. In building the prisms, the moisture content of the units at the time of laying, the consistency of the mortar, the thickness of mortar joints, and the workmanship shall be the same as will be used in the structure. Assembled specimens shall be at least 16 in. high and shall have a height-to-thickness ratio (h/t) of at least 2 but not more than 5. If the (h/t) ratio of the prisms tested is less than 5, the compressive strength values indicated by the tests shall be corrected by multiplying by the factor indicated in table RS 10–1–3.
TABLE RS 10–1–3 Correction Factors for h/t Ratio
Ratio of height to thickness (h/t) 2.0 2.5 3.0 3.5 4.0 5.0 Correction Factor a 0.73 0.80 0.86 0.91 0.95 1.00
a Interpolate to obtain intermediate values.
Prisms shall be tested after aging for 28 days in accordance with the applicable provisions of reference standard RS 10–17. Seven-day tests may be used, provided the relation between the 7- and 28-day strengths of the masonry is established by tests of the materials used. Not less than five specimens shall be tested.
(b) Method no. 2—Unit tests.—In lieu of prism tests, an assumed value of f 'm may be interpolated from the values in Table 10–1–4. Compressive strength of the masonry units shall be determined from tests conducted in accordance with applicable ASTM specifications.
TABLE RS 10–1–4 Assumed Compressive Strength of Masonry a b
Compressive Strength of units (psi) Assumed Compressive Strength of Masonry f ' m (psi) Type H Mortar Type M Mortar Type S Mortar Type N Mortar Type O Mortar Solid Clay or Shale Units • 14,000 or more 5,000 4,600 3,900 3,200 — • 10,000 5,000 3,400 2,900 2,400 — • 6,000 5,000 2,200 1,900 1,600 — • 2,000 1,000 1,000 900 800 — Solid Concrete or Sand-Lime Units • 6,000 2,000 2,000 1,700 1,400 — • 4,000 1,500 1,500 1,300 1,100 — • 2,500 1,100 1,100 1,000 900 — • 1,800 950 950 860 770 — • 1,200 800 950 860 770 — Hollow Units (Clay, Shale, or Concrete)* • 6,000 5,000 2,000 1,700 1,400 — • 4,000 1,500 1,500 1,300 1,100 — • 2,000 1,000 1,000 900 800 — • 1,000 750 750 700 650 — Stone Ashlar Masonry • Granite 4,300 4,300 3,850 3,400 2,700 • Limestone or marble 2,700 2,700 2,400 2,150 1,750 • Sandstone or caststone 2,150 2,150 1,900 1,700 1,350 • Rubble stone, coursed, rough rough or random 750 750 650 550 450
Notes—
a Where masonry cement mortar is used, if the amounts of Portland cement and lime are established and conform to the requirements for the mortar type indicated in the table, the values in this table apply. Masonry cement mortar in which the proportions are not identified shall not be used for masonry construction proportioned on the basis of the analysis of stress.
b For grouted masonry and filled cell masonry, f 'm shall be based on the values given for solid units and hollow units respectively. See Section 8.
c The ratio of the bedded area to gross area shall not be less than 0.25. For units having a lesser ratio of mortar bedded area than 0.25, the f 'm values shall be determined by Method No. 1 (prism tests).
4.3 ALLOWABLE FLEXURAL, TENSION, AND SHEAR STRESSES.—The allowable stresses in flexural tension and in shear shall not exceed the values set forth in table RS 10–1–5, except as permitted in other sections of this reference standard. The resistance in flexural tension and shear where the wall section is penetrated by flashing shall be investigated on the basis that the resistance is limited to the fractional resistance.
4.3.1 The allowable flexural tension stress for masonry constructed with Type H mortar shall be the same as with Type M or S mortar (Table RS 10–1–5) except that when clay or shale masonry units are used the allowable flexural tension shall be 0.30f 't but not greater than 112 psi and the allowable shear shall be 100 psi provided:
a). The brick is ASTM C 62–69 grade SW or MW.
b). The brick has no silicone treatment.
c). The initial rate of absorption of the brick does not exceed 35 grams/minute 730 square inches when tested in accordance with ASTM C 67–62.
d). The brick are extruded side cut units.
e). The average compressive strength of the brick units is 6,000 psi when tested in accordance with ASTM C 67–69.
f). f 't is determined by building 5 stack bond single wythe prisms one brick wide and seven brick tall. The prisms shall be cured for 28 days at about 75° F and 50% relative humidity. Specimens shall then be tested as a simple beam with third point loading as described in ASTM C 78–64.
g). Test reports indicating the determination of f 't shall be submitted by either the applicant or the Architect or Engineer designated for Controlled Inspection prior to commencement of construction of masonry.
4.3.2 The allowable flexural tension stress for masonry constructed with Type H mortar and clay or shale masonry units which do not meet the requirements of section 4.3.1 (c) through (d) shall be 0.30f 't provided f 't is determined by ASTM E 72–61, uniform transverse load strength method B after 28 days cure at 75° F and 50% R.H. The test panels shall be single wythe, 8 feet tall and 4 feet wide. In addition, units producing wall strength less than 360 psi when tested as outlined above must be tested by building additional single wythe panels constructed and tested for uniform transverse load strengths immediately after being subjected to the National Bureau of Standard Water permeability Tests for a period of five days following the normal 28 day cure.
4.3.3 Wetting of brick in construction of masonry using Type H mortar shall not be permitted.
4.3.4 Allowable flexural tension stresses for masonry constructed by Type H mortar may be increased 33 1/8% when considering wind load.
4.4 DESIGN OF MASONRY WALLS AND COLUMNS.—
4.4.1. Slenderness ratio.—
(a) The slenderness ratio (ratio of effective height, h ', or length of the wall panel to the effective thickness, t) shall not exceed 30 for walls of solid units, 20 for walls of hollow units, and 25 for walls of filled cell or grouted masonry.
(b) The slenderness ratio (ratio of the effective height, h ', to the least effective thickness, t) shall not exceed 25 for columns of solid units, 15 for columns of hollow units and 20 for columns of filled cell or grouted masonry.
(c) The slenderness ratio shall not exceed 40 for walls and columns of masonry constructed with type H mortar.
4.4.2 Effective height.—The effective height, h ', of columns and wall shall be determined by the architect or engineer who prepares the plans, who shall consider the conditions of end restraint provided in the particular case.
TABLE RS 10–1–5 Allowable Stresses in Flexural Tension and in Shear
Allowable Stresses (psi) on Cross-Sectional Area (Except as Noted) Normal to bed joints a Parallel to bed joints b Construction Type d Flexural Tension Shear Mortar Type c H M or S N H M or S N H M or S N Clay or Shale Masonry Units: • Solid 112 f 36 28 112 f 72 56 100 50 40 • Hollow e 112 f 15 10 112 f 30 20 100 30 20 Concrete Masonry Units: • Solid 25 f 25 18 50 f 50 36 30 30 20 • Hollow e 15 f 15 10 50 f 30 20 30 30 20 Sand-Lime Masonry Units: • Solid 30 f 30 20 60 f 60 40 40 40 35 • Hollow e 15 f 15 10 30 f 30 20 30 30 20 Stone Masonry Units: • Natural Stone 25 f 25 18 50 f 50 36 30 30 20 • Cast Stone 25 f 25 18 50 f 50 46 30 30 20
Notes—
a Direction of stress is normal to bed joints construction.
b Direction of stress is parallel to bed joints. If masonry is laid in stack bond, tensile stress values for tension parallel to bed joints shall not be used.
c Where masonry cement mortars are used, if the amount of Portland cement and lime is established and conforms to the requirements for Type M, S, or N mortar, the provisions of this table shall apply. Masonry cement mortar in which the proportions are not identified shall not be used for masonry construction proportioned on the basis of the analysis of stress.
d For computing flexural resistance, the moment of inertia of a cavity wall shall be based on the assumption that the two wythes act independently. The moment of inertia of a masonry bonded hollow wall may be based on the assumption that there is adequate shear resistance between the wythes to assure that they act together.
e Net area in contact with mortar.
f The allowable flexural tensile stress may be increased by 33 1/8% (or to 150 psi) when considering wind load.
4.4.3. Effective thickness.—
(a) For solid masonry, grouted masonry, filled cell masonry, hollow masonry, and masonry bonded hollow walls, the effective thickness, t, shall be taken as the actual thickness.
(b) For cavity walls loaded on both wythes, the effective thickness, t, shall be taken as 2/3 the sum of the actual thickness of both wythes.
(c) For cavity walls loaded on one wythe only, the effective thickness, t, shall be taken as the actual thickness of the loaded wythe or 2/3 the sum of the actual thickness of both wythes, whichever is the lesser value.
(d) For columns, the effective thickness shall be taken as the least actual thickness.
4.4.4. Allowable vertical loads.—
(a) AXIAL LOADS ON WALLS—Allowable axial loads on masonry walls P, shall be computed by the following formula:
P=c(0.25f 'm)Ag
Where:
c = stress reduction factor given in table RS 10–1-c, corresponding to the slenderness ratio
Ag = cross-sectional area of the wall.
For solid masonry, grouted masonry, stone masonry and filled cell masonry, Ag shall be computed on the basis of actual thickness without deduction for cells or cores.
For hollow masonry walls, Ag shall be taken as the net cross-sectional area of the units. Where the ratio of mortar bedded area to gross area is less than 0.25, Ag shall then be multiplied by a factor equal to mortar bedded area divided by 0.25 times the gross area.
Where both wythes of a cavity wall support vertical load, Ag shall be taken as cross-sectional area of wall computed as above minus the actual area of the cavity between wythes. Where only one wythe supports vertical load, Ag shall be taken as the cross-sectional area of the loaded wythe computed as above.
(b) AXIAL LOADS ON COLUMNS—Allowable axial loads on masonry columns shall be computed by the following formula:
P=c(0.20f 'm)Ag
Where:
c = stress reduction factor given in table RS 10–1-c corresponding to the slenderness ratio
Ag = cross-sectional area of the column
For solid masonry, grouted masonry, stone masonry, and filled cell masonry, Ag shall be computed on the basis of actual thickness without deduction for cells or cores.
For hollow masonry columns, Ag shall be taken as the net cross-sectional area of the units. Where the ratio of mortar bedded area to gross area is less than 0.25, Ag shall then be multiplied by a factor equal to mortar bedded area divided by 0.25 times the gross area.
(c) ECCENTRIC LOAD—
(1) Where the eccentricity of the loads on the member does not exceed 1/3 the thickness, the allowable vertical load on walls and columns shall be computed in accordance with section 4.4.4(a) and section 4.4.4(b), respectively, using the stress reduction factors given in table RS 10–1–6.
TABLE RS 10–1–6 Stress Reduction Factors (c) a
Slenderness Ratio Eccentricity as a Proportion of the Thickness of the Member 0 to 1/20 1/6 1/3 5 1.00 0.66 0.32 10 0.92 0.63 0.27 15 0.79 0.56 0.22 20 0.64 0.42 0.16 25 0.49 0.36 0.12 30 0.38 0.27 0.–8 35 0.27 40 0.21
Notes—
a Linear interpolation between values for stress factors is permissible.
(2) Where the eccentricity exceeds 1/3 the thickness, the maximum tensile stress in the masonry, assuming linear stress distribution (P/A ± M/S), shall not exceed the values given in table RS 10–1–5 or the member shall be reinforced in accordance with the requirements of reference standard RS 10–2.
(3) In computing the eccentricity of loads on walls and columns, consideration shall be given to the effects of lateral load, eccentricity of vertical load, and the deflection, thermal and other movements of members. For solid masonry, grouted masonry, filled cell masonry, hollow masonry, masonry bonded hollow walls and cavity walls loaded on both wythes, the eccentricity shall be considered with respect to the centroidal axis of the member. For composite members, the eccentricity shall be considered with respect to the centroidal axis of the transformed area of the member. For cavity walls loaded on one wythe, the eccentricity shall be considered with respect to the centroidal axis of the loaded wythe.
4.5 COMPOSITE WALLS OR FACED WALLS.—In composite walls, faced walls, or other structural members composed of different kinds or grades of units or mortars, the maximum stresses shall not exceed the allowable stresses for the weakest of the combinations of units and mortars of which the member is composed. In cavity walls, where only one wythe supports vertical load, the stresses shall not exceed the allowable stresses for the units and mortars comprising that wythe.
4.6 DISTRIBUTION OF CONCENTRATED LOADS.—The length of the wall to be considered as effective in resisting a concentrated load shall not exceed the center-to-center distance between loads, nor shall it exceed the width of bearing plus four times the wall thickness. Concentrated loads shall not be considered as distributed by metal ties, or distributed across continuous vertical joints.
4.7 BEARING STRESSES.—Allowable bearing stresses may be taken as 1.5 times the corresponding allowable compressive stress, provided that the area of the bearing plate does not exceed 1/3 of the area of the member supporting the bearing plate and the least distance between the edges of the loaded and unloaded areas is a minimum of 1/4 of the parallel side dimension of the loaded area. For bearing on the full area, the allowable bearing stress shall be taken as equal to the allowable compressive stress. For reasonably concentric bearing areas greater than 1/3, but less than the full area, the allowable bearing stress shall be interpolated between 1.0 and 1.5 times the allowable compressive stress.
SECTION 5 – LATERAL SUPPORT
5.1 METHOD OF SUPPORT.—Lateral support for masonry walls may be obtained by cross walls, columns, pilasters, or buttresses, where the limiting distance is measured horizontally; or by floors, roofs, spandrel beams, or girts, where the limiting distance is measured vertically. Sufficient bonding or anchorage shall be provided between the walls and the supports to resist the assumed wind or other horizontal forces, acting either inward or outward, and shall meet the requirements of section 9.5. All members relied upon for lateral support shall be designed on the basis of allowable stress and shall have sufficient strength to transfer the horizontal force, acting in either direction, to adjacent structural members or to the ground. Where walls are dependent upon floors or roofs for their lateral support, provision shall be made in the building to transfer the lateral forces to the ground.
5.2 HEIGHT AND THICKNESS LIMITATIONS.—
5.2.1 General.—Masonry walls, whether loadbearing or nonloadbearing, shall be provided with lateral support by means of horizontal or vertical members or constructions at intervals not to exceed those specified in section 4.4.1 or, for non-loadbearing walls or for loadbearing walls where it is desired to obviate the need for structural analysis, at intervals not to exceed those specified in this section.
Where a masonry wall containing no openings is supported in both horizontal and vertical spans, the allowable distance between lateral supports as indicated in this section may be increased; but if both horizontal and vertical distances exceed the allowable distance, the sum of the horizontal and vertical spans between supports may be no more than three times the allowable distance permitted for support in only one direction.
5.2.2 Load bearing exterior masonry walls.—Except as provided in section 6.4 load bearing exterior masonry walls shall be proportioned on the basis of structural analysis.
5.2.3 Non-loadbearing exterior masonry walls.—In lieu of structural analysis, non-loadbearing exterior masonry walls may be proportioned so that the maximum slenderness ratio does not exceed 20. In the case of a gable, the height of the wall shall be based on the average height. Where the wall panel contains openings having a dimension in excess of 50 per cent of the corresponding dimension of the panel, the wall shall be proportioned by structural analysis.
5.2.4 Interior loadbearing walls.—In lieu of analysis of stresses, interior loadbearing masonry walls may be proportioned so that the maximum slenderness ratio does not exceed 20.
5.2.5 Partitions.—The distance between lateral supports of partitions 3 in. or greater in thickness shall not exceed 48 times the nominal thickness of the partition, excluding plaster, and for partitions less than 3 in. thick, 48 times the actual thickness, including plaster.
5.2.6 Faced or composite walls.—The slenderness ratio for faced or composite walls shall not exceed the value allowed for the weakest of the combination of masonry units or mortars of which the wall is composed.
5.2.7 Rubble stone masonry.—In lieu of structural analysis, rubble stone masonry walls may be proportioned so that the slenderness ratio does not exceed 14 for exterior walls and 16 for interior walls.
5.3 MINIMUM THICKNESS.—Whether proportioned on the basis of analysis of stresses or empirical rules, in no case shall the thickness of masonry construction be less than the dimensions shown in table RS10–1–7 except when type H mortar is used and the construction is proportioned on the basis of analysis stresses. When type H mortar is used the minimum nominal thickness of masonry shall be 4 inches. The minimum thickness of a wythe shall be 2 in.
5.4 DECREASE IN THICKNESS.—Whether proportioned on the basis of empirical provisions or the analysis of stresses, where walls of hollow units or masonry bonded hollow walls are decreased in thickness, a course or courses of solid masonry shall be interposed between the wall below and the thinner wall above, or special units or construction shall be used that will adequately transmit the loads from the shells of the units above to the shells of those below.
SECTION 6 – THICKNESS AND HEIGHT OF MASONRY EMPIRICAL PROVISIONS
6.1 GENERAL.—Compliance with the provisions of this section shall not be required where the design is proportioned on the basis of analysis of stresses.
6.2 MINIMUM THICKNESS.—The provisions of section 5.3 shall apply.
TABLE RS 10–1–7 Minimum Thickness of Masonry
Type of Masonry Nominal Thickness (in.) Loadbearing walls (exterior or interior).— • Solid masonry 5 • Grouted or filled cell masonry 6 • Hollow masonry 6 • Cavity or masonry bonded hollow walls 8a • Stone ashlar masonry 12 • Stone rubble masonry 16c Non-loadbearing walls.— • Exterior walls 4 • Partitions 2 Columns.— • Solid unit masonry 6 • Hollow unit masonry 8 • Facing of faced walls 2b
Notes—
a Overall wall thickness including cavity.
b In no case less than 1/8 the height of the facing unit.
c 12 in. for one story buildings.
6.3 CHANGE IN THICKNESS.—
6.3.1 Variation in thickness.—Except for window-paneled backs, and permissible chases and recesses (section 10.1) walls shall not vary in thickness between their lateral supports. When a change in thickness, due to minimum thickness requirements, occurs between floor levels, the greater thickness shall be carried up to the higher floor level.
6.3.2. Decrease in thickness.—The provisions of section 5.4 shall apply.
6.4 LOADBEARING WALLS.—Where the height of exterior or interior load-bearing masonry walls does not exceed the following requirements, such walls, if they meet the provisions of section 4 with regard to compressive stress and of section 5.3 with regard to minimum thickness, may be considered to be adequate to resist the applied wind loads, and other shearing forces.
6.4.1 Multi-story buildings.—For limitations on 8 in. walls see (f) below.
(a) Exterior solid walls.—The thickness of solid exterior masonry bearing walls shall be at least 8 in. for the top floor and 12 in. for a maximum of 55 ft. measured downward from the top floor level. Any additional height shall be provided by 16 in. lower walls up to a maximum building height of 104 ft. Buildings taller than 104 ft. shall be structurally analyzed and designed. The slenderness ratio shall not exceed 20.
(b) Interior solid walls.—Interior solid walls shall be at least 8 in. thick for the uppermost 55 ft. of wall height and 12 in. for the lower walls for a maximum building height of 104 ft. Taller walls shall be designed by structural analysis.
(c) Cavity walls.—Cavity walls or masonry bonded hollow walls shall be at least 8 in. thick for the top floor and 12 in. thick for the lower walls up to a maximum total height of 40 ft. except that 10 in. cavity walls may be used for a maximum total height of 25 ft. Taller walls shall be designed by structural analysis.
(d) Walls of hollow units.—Loadbearing walls of hollow units shall be at least 8 in. thick for the top floor and at least 12 in. for the lower walls for a maximum building height of 40 ft. Hollow unit walls 40 ft. high may be supported by solid masonry walls whose height is no more than 35 ft. above the first tier of beams.
(e) Stiffened walls.—Where solid masonry bearing walls are stiffened by, and tied to, reinforced concrete floors or masonry cross walls at distances not greater than 20 ft. apart, they may be 12 in. thick for the uppermost 70 ft., measured downward from the top of the wall.
(f) Eight inch walls.—Notwithstanding other provisions in this section, the thickness of masonry bearing walls may be 8 in. where: (1) the total height of the wall above its support does not exceed 35 ft. except for cavity walls for which (c) above shall apply, and (2) the distance from floor-to-floor or floor-to-roof does not exceed 12 ft. and (3) the floor live load does not exceed 60 psf; and (4) the roof is designed so that the dead load imparts no lateral thrust to the wall.
6.4.2. One-story buildings.—The bearing walls of one story buildings shall be at least 6 in. thick provided the vertical loads on the roof impart no lateral thrust to the wall.
6.4.3 Walls of residence buildings.—In residence buildings not more than three stories high, bearing walls other than coursed or rough or random rubble stone, may be 8 in. thick when not over 35 ft. high and the roof is designed so that the dead load imparts no lateral thrust to the wall. Such walls in one story residence buildings, and in one story private garages, may be 5 1/2 in. thick.
6.4.4. Walls above roof level.—Masonry walls above roof level, 12 ft. or less in height, enclosing stairways, machinery rooms, shafts, or penthouses, may be 8 in. thick and may be considered as neither increasing the height nor requiring any increase in the thickness of the wall below. Parapet walls shall conform to the provisions of section 10.4.
6.4.5. Faced or composite walls.—Neither the thickness or height of faced or composite walls, nor the distance between lateral supports, shall exceed that prescribed for masonry of either of the types forming the facing or the backing.
6.4.6. Cavity or masonry bonded hollow walls.—Where both the facing and backing wythes are constructed of solid masonry units, the wythes may be 3 in. thick. Otherwise, the wythes of cavity walls shall each have a thickness of at least 4 in. and the cavity shall be at least 2 in. but not more than 4 in. wide. Wythes less than 4 in. thick shall not have raked joints and the backing wythe of cavity or masonry bonded hollow walls shall be at least as thick as the facing wythe. A cavity or masonry bonded hollow wall may be constructed to its maximum permissible height on top of a solid masonry wall whose maximum height is 35 ft. above the first tier of beams. Roof construction shall be designed so that the dead load imparts no lateral thrust to the wall.
6.4.7. Rubble stone walls.—Rough, random, or coursed rubble stone walls shall be 4 in. thicker than is required for other types of masonry, but in no case less than 12 in. thick.
6.4.8. Wall thickness increase due to span length.—When the clear span between bearing walls or between a bearing wall and an intermediate support is more than 26 ft., the effects of temperature, of rotation of end supports, and of eccentricity shall be investigated. In lieu of such investigation, the thickness of such walls shall be increased 4 in. for each 12 1/2 ft., or fraction thereof, that such span is in excess of 26 ft.
6.5 NON-LOADBEARING WALLS.—Provided that they conform to the provisions of section 5, non-loadbearing masonry walls, including curtain walls and panel walls, may be 4 in. less in thickness than required in section 6.4 for loadbearing walls, except as provided below.
6.5.1. Partitions.—The minimum thickness for partitions shall be as follows:
Height of Walls Thickness • 8 ft. under 2 in. • Over 8 ft. to 12 ft. 3 in. • Over 12 ft. to 16 ft. 4 in. • Over 16 ft. to 20 ft. 6 in. • Over 20 ft. to 24 ft. 8 in.
6.6 OPENINGS IN BEARING WALLS.—The area of openings in any transverse horizontal plane of a bearing wall shall not exceed 50 per cent of the gross sectional area unless the wall panel can be demonstrated by analysis to be structurally adequate with the increased area of openings.