NYC Administrative Code RS 9-5 MINIMUM DESIGN WIND PRESSURES
1. DESIGN WIND PRESSURES ON STRUCTURAL FRAMES.—Minimum design pressures due to wind acting on vertical surfaces shall be in accordance with table RS 9–5–1, and minimum design pressures acting normal to horizontal or inclined surfaces shall be in accordance with table RS 9–5–2. The occurrence of the pressures on vertical, horizontal, and inclined surfaces of the building shall be considered as simultaneous.
TABLE RS 9–5–1 Design Wind Pressures on Vertical Surfaces
Height Zone (ft. above curb level) Design Wind Pressure on Vertical Surfaces (psf of projected solid surface) Structural Frame Panels Glass • 0–50 (signs and similar constructions of shallow depth only) 15 — • 0–100 20 30 • 101–300 25 30 • 301–600 30 35 • 601–1,000 35 40 • Over 1,000 40 40
TABLE RS 9–5–2 Design Wind Pressures on Horizontal and Inclined Surfaces
Roof Slope Design Wind Pressure Normal to Surface 30 degrees or less Either pressure or suction equal to 40 per cent of the values in Table RS9–5–1 over the entire roof area More than 30 degrees Windward Slope—pressure equal to 60 per cent of values in Table RS9–5–1.Leeward slope—suction equal to 40 per cent of values to Table RS9–5–1.
2. WALL ELEMENTS.—For design of mullions, muntins, girts, panels, and other wall elements (including their fastenings), other than glass panels, the wind pressure acting normal to wall surfaces shall be 30 psf or a 20 psf suction, for all height zones up to 500 ft. These values shall be deemed to include allowance for gust pressures. For height zones over 500 ft., the applicable design pressures shall be specially investigated, but shall not be less than the values indicated in table RS 9–5–1.
3. ROOF ELEMENTS.—The wind pressures acting on purlins, roofing, and other roof elements (including their fastenings) supporting small contributory areas of wind presentment shall be 1 1/2 times the values given in table RS 9–5–2.
4. OTHER BUILDING ELEMENTS.—Minimum wind pressures to be used in the design of other building elements shall be the values in table RS 9–5–1 multiplied by the following shape factors given in table RS 9–5–3.
TABLE RS 9–5–3 Shape Factors
Construction Shape Factor • Signs (and their supports), or portions thereof, having 70 per cent or more of solid surface 1.5 • Signs (and their supports), or portions thereof, having less than 70 per cent of solid surface 2.0 • Tanks, cooling towers, and similar constructions 1.5 • Upright, circular cylindrical surfaces 0.7 • Square and rectangular chimneys 1.5
For special structures such as curved and saw-toothed roofs, guys and cables, open trussed structures, parallel solid girders, and spheres, the design wind pressure shall be determined on the basis of recognized engineering analysis or by test.
5. EAVES AND CORNICES.—Eaves, cornices, and overhanging elements of the building shall be designed for upward pressures of twice the values given in table RS 9–5–1.
6. WIND LOAD BY MODEL TEST.—In lieu of the design wind pressures established in section 1 and 2 of this reference standard, and subject to review and approval of the commissioner, design wind pressures may be approximated from suitably conducted model tests. The tests shall be predicated on a basic wind velocity of 80 mph at the 30 ft. level, and shall simulate and include all factors involved in considerations of wind pressure, including pressure and suction effects, shape factors, functional effects, gusts, and internal pressures and suctions.
7. CONSTRUCTION ELEVATOR AND MATERIAL HOIST TOWER BACK STRUCTURES
DEFINITIONS:
Back Structure: A system of landing platforms and/or supports designed to transmit construction elevator or material hoist tower loads into the building structure.
Inland: As defined by ASCE 7–98, exposure Category A
Coastal: As defined by ASCE 7–98, exposure Category D
WIND LOADS
{W} Storm Wind Load: equivalent to 25 yr. Mean recurrence wind per ASCE 7–98 standard, taking into account the exposure terrain, height zone, shielding coefficients, etc. In lieu of detailed analysis by the design professional, the following values may be used:
Design storm wind (25 yr. Mean Recurrence)
Wind pressure loading (in psf) on gross cross sectional area of the back structure
Zone/Elevation 0–50 feet 50–150 feet 150–400 feet 400–700 feet >700 feet Inland 14.4 20.7 25.6 33.8 40 Coastal 14.4 25.6 43.2 65.5 69.6
Unless the structure is fully enclosed in curtain walls, the following wind loading shall be analyzed:
1. Parallel to the building facade per the above table.
2. Normal to the building facade at one-half the value of the above table.
Wind directions shall be considered to be non-concurrent.
{w} In-Service wind: a 35 mph (wind pressure of 3.13 psf) from any direction acting on the back structure.