NYC Administrative Code SECTION 5 – LATERAL SUPPORT
5.1 METHOD OF SUPPORT.—Lateral support for masonry walls may be obtained by cross walls, columns, pilasters, or buttresses, where the limiting distance is measured horizontally; or by floors, roofs, spandrel beams, or girts, where the limiting distance is measured vertically. Sufficient bonding or anchorage shall be provided between the walls and the supports to resist the assumed wind or other horizontal forces, acting either inward or outward, and shall meet the requirements of section 9.5. All members relied upon for lateral support shall be designed on the basis of allowable stress and shall have sufficient strength to transfer the horizontal force, acting in either direction, to adjacent structural members or to the ground. Where walls are dependent upon floors or roofs for their lateral support, provision shall be made in the building to transfer the lateral forces to the ground.
5.2 HEIGHT AND THICKNESS LIMITATIONS.—
5.2.1 General.—Masonry walls, whether loadbearing or nonloadbearing, shall be provided with lateral support by means of horizontal or vertical members or constructions at intervals not to exceed those specified in section 4.4.1 or, for non-loadbearing walls or for loadbearing walls where it is desired to obviate the need for structural analysis, at intervals not to exceed those specified in this section.
Where a masonry wall containing no openings is supported in both horizontal and vertical spans, the allowable distance between lateral supports as indicated in this section may be increased; but if both horizontal and vertical distances exceed the allowable distance, the sum of the horizontal and vertical spans between supports may be no more than three times the allowable distance permitted for support in only one direction.
5.2.2 Load bearing exterior masonry walls.—Except as provided in section 6.4 load bearing exterior masonry walls shall be proportioned on the basis of structural analysis.
5.2.3 Non-loadbearing exterior masonry walls.—In lieu of structural analysis, non-loadbearing exterior masonry walls may be proportioned so that the maximum slenderness ratio does not exceed 20. In the case of a gable, the height of the wall shall be based on the average height. Where the wall panel contains openings having a dimension in excess of 50 per cent of the corresponding dimension of the panel, the wall shall be proportioned by structural analysis.
5.2.4 Interior loadbearing walls.—In lieu of analysis of stresses, interior loadbearing masonry walls may be proportioned so that the maximum slenderness ratio does not exceed 20.
5.2.5 Partitions.—The distance between lateral supports of partitions 3 in. or greater in thickness shall not exceed 48 times the nominal thickness of the partition, excluding plaster, and for partitions less than 3 in. thick, 48 times the actual thickness, including plaster.
5.2.6 Faced or composite walls.—The slenderness ratio for faced or composite walls shall not exceed the value allowed for the weakest of the combination of masonry units or mortars of which the wall is composed.
5.2.7 Rubble stone masonry.—In lieu of structural analysis, rubble stone masonry walls may be proportioned so that the slenderness ratio does not exceed 14 for exterior walls and 16 for interior walls.
5.3 MINIMUM THICKNESS.—Whether proportioned on the basis of analysis of stresses or empirical rules, in no case shall the thickness of masonry construction be less than the dimensions shown in table RS10–1–7 except when type H mortar is used and the construction is proportioned on the basis of analysis stresses. When type H mortar is used the minimum nominal thickness of masonry shall be 4 inches. The minimum thickness of a wythe shall be 2 in.
5.4 DECREASE IN THICKNESS.—Whether proportioned on the basis of empirical provisions or the analysis of stresses, where walls of hollow units or masonry bonded hollow walls are decreased in thickness, a course or courses of solid masonry shall be interposed between the wall below and the thinner wall above, or special units or construction shall be used that will adequately transmit the loads from the shells of the units above to the shells of those below.