NYC Administrative Code RS 9-2 MINIMUM REQUIREMENTS FOR UNIFORMLY DISTRIBUTED AND CONCENTRATED LIVE LOADS UNIFORMLY DISTRIBUTED LIVE LOADS

Occupancy or Use of Spaces Live load (psf) • Assembly spaces Drill rooms 150 • Assembly spaces having fixed seats, including auditorium areas in churches, schools, theaters, courthouses, lodges, lecture halls, and similar buildings 60a • Dance floors, restaurant serving and dining areas, mess halls, museums, gymnasiums, skating rinks, promenades, and roof gardens 100 • Private assembly spaces, including conference rooms and card rooms 50 • Stadium, grandstand, and reviewing stand seating areas 100 • Other assembly spaces See note d • Balconies Exterior See note b Interior (as required for occupancy or use) Mezzanines (as required for occupancy or use) • Catwalks 30 • Corridors (1) Corridors in schools 100 • (2) Corridors, elevators, and stairs in office buildings (other than first floor lobbies) 75 • (3) Corridors serving first floor elevator lobbies, auditoriums, and similar areas of public assembly 100 (4) Other (same as that required for the occupancy of the area being served) Elevator machine rooms (see Reference Standard RS-18) • Equipment rooms, including pump rooms, generator rooms, transformer vaults, and areas for switch gear, ventilating, air conditioning, and similar electrical and mechanical equipment 75 • Fire escapes Multiple dwellings 40 • Others 100 • Hospitals Operating rooms, laboratories, and service areas 60 • Rooms and wards 40 • Personnel areas 40 Other (as required for occupancy or use of the area) • Libraries Reading and study room areas 60 Stack areas (see Storage) Other (as required for occupancy or use of the area) • Lobbies and similar areas 100 • Manufacturing and repair areas 100 • Marquees 60 • Office areas (not including record storage areas) 50 • Parking areas For passenger cars, provided that the clear headroom at the entrance does not exceed 8 ft. 50 • Penal institutions Cell blocks 40 Other (as required for occupancy or use of the area) • Plaza areas (open) accessible to the public (including landscaped portions) 100 • Recreational areas Bowling alleys (alleys only) 40 • Poolrooms 75 • Other (see assembly areas) Residential areas Dormitories Non-partitioned 60 • Partitioned 40 • Dwellings Multi-family units Apartments 40 • Public rooms (as required for occupancy or use) One- and two-family units First floor 40 • Upper floors and habitable attics 30 • Uninhabitable attics 20c • Hotels Guest rooms 40 • Public rooms (as required for occupancy or use) Schools Classrooms 40 • Shops (automotive and press shops) 100 • Shops (others) 60 • Other (as required for occupancy or use of the area) Stairs and exit passages (same as Fire escapes) Storage Light 100 • Warehouse 150 • Stores Wholesale sales 100 • Retail sales Basement and first floor 100 • Upper floors 75 • Telephone equipment rooms 80 • Theaters Dressing rooms 40 • Projection room 100 • Stage floor 150 • Toilet areas 40

Notes:

a Uniform load shall be applied to the gross floor area.

b 150 per cent of live load on adjoining occupied area, but not more than 100 psf.

c Live load need be applied to joists or to bottom chords of trusses or trussed rafters only in those portions of attic space having a clear height of 42 in. or more between joist and rafter in conventional rafter construction; and between bottom chord and any other member in trussed or trussed rafter construction. However, joists or the bottom chords of trusses or trussed rafters shall be designed to sustain the imposed dead load or 10 psf, whichever is greater, uniformly distributed over the entire span.

d Live loads for assembly spaces other than those described in this reference standard shall be determined from the occupant load requirements as established by section 27-358 using the formula 100/net floor area per occupant but shall not be less than 50 psf nor more than 100 psf.

Concentrated Live Loads

Use or Location Load (lbs.) a Remarks Elevator machine room floor See Reference Standard RS-18 Gratings, checkered plates and similar metal decks 200 (on area of 1.0 sq. in.) Nonconcurrent with uniform live load. Floor registers and similar floor insets 250 (on area of 2 ft. × 2 ft.) Nonconcurrent with uniform live load. Parking areas—passenger vehicles accommodating nine passengers, or less 2,500 (on area of 20 sq. in.) For slab or deck design The concentrated load may be assumed to represent the reaction of a jack placed under one end of the vehicle. Omit uniform live load in area (6 ft. × 9 ft.) representing one half the vehicle, adjacent to the point of load concentration. 1,500 (each wheel) To be used in lieu of uniform live load in stalls of mechanized garages where there is no slab or deck. Parking areas—trucks, buses and passenger vehicles accommodating more than nine passengers 150 per cent of maximum wheel load with vehicle loaded (on area of 20 sq. in.) Same as for Parking areas—passenger vehicles accommodating nine passengers, or less. Floor of office areas 2,000 Nonconcurrent with uniform live load. Resident and multiple dwellings 200 (on area of 4.0 sq. in.) Nonconcurrent with uniform live load. Scuttles and skylight ribs 200 Nonconcurrent with uniform live load. Steel joists—for each individual joist 800 (for trussed joists apply at a panel point) Nonconcurrent with uniform live load. Roofs 250 (on area of 2 ft. × 2 ft.) Nonconcurrent with uniform live load. Not applicable for awnings, canopies, and similar constructions where access by persons is difficult and not intended. Stair and fire escape treads 300 (on area 1 ft. wide by depth of the tread and spaced at 3 ft. center-to-center) Nonconcurrent with uniform live load. Boiler rooms 3,000 The concentrated load of 3,000 lbs. may be assumed to represent the weight of minor items of equipment (pumps, etc.) in temporary locations during installation. In addition provision shall be made for supporting the weight of the empty boiler at pertinent locations on the floor to provide for replacement of the boiler

Note—

a Except when otherwise indicated loads are assumed to be applied over an area 2 1/2 ft. × 2 1/2 ft.

UNIFORMLY DISTRIBUTED AND CONCENTRATED LIVE LOADS FOR CONSTRUCTION ELEVATOR AND MATERIAL HOIST TOWER BACK STRUCTURES

DEFINITION:

Back Structure: A system of landing platforms and/or supports designed to transmit construction elevator or material hoist tower loads into the building structure.

WALKWAY PLATFORMS

{L} Live Load

1. Uniformly Distributed: 100 psf defined by the area enclosed by handrail, or by the gross area of the walkway if handrails are not provided.

2. Concentrated: 40% of the highest rated capacity of the hoist cars, non-concurrently with the uniform load, acting on a 4 square inch area anywhere within the boundary of handrail, or within the gross area of the walkway if handrails are not provided.

FRAME STRUCTURE

{L} Live load values determined by detailed analysis performed by the design professional acting on any combination of differing floor levels equal to the number of hoist cars plus one but not less than 50 psf or the carrying capacity of the elevator cars and hoist cars, whichever is greater.

SNOW LOAD

{S} 20 psf acting on the top two floors of gross plan area of the back structure.

ICE LOAD

{I} 40% of the dead load or a detailed analysis performed by the design professional based on the equivalent of one-quarter inch ice.

DYNAMIC LOADING

{d} Lateral force and moment resulting from the starting and stopping of the hoist cars. When more than one car is in operation, the dynamic loading shall reflect the most critical combination. The Dynamic loading is to be considered basic loading. Impact loading need not be considered.

DEAD LOADS {D}—REFER TO RS 9–1

WIND LOADS {W} & {w}—REFER TO RS 9–5

DESIGN LOAD COMBINATIONS

For Allowable Stress Design, factors used in loading combinations conform to 27-594 of the Building Code. The back structures shall be designed for the critical combination of:

1. {D} + {L} + {d}

2. 0.67 ({D} + {W})

3. 0.75 ({D} + {L} + {d} + {w})

4. 0.67 ({D} + {I} + {w} + {S})

Load factors for LRFD designs shall adhere to the LRFD recommendations and guidelines contained in the reference standard for the material used.