NYC Administrative Code RS 5-17 STANDARDS FOR THE INSTALLATION OF SMOKE SHAFTS
1. Smoke shafts shall be constructed as required for shafts in section 27-344.
2. Shafts may serve more than a single compartment on a given floor but in all cases shall have at least one wall common to or abutting the compartments served, or each added compartment shall be connected to the shaft by an individual duct with the same fire resistive rating as required for the smoke shaft.
3. The size of the shaft shall be uniform throughout and of such dimensions as to provide 60 air changes per hour in the largest compartment served and at a velocity of not less than 1,600 fpm nor more than 4,000 fpm.
4. Openings into the shaft shall be provided at each floor and shall be of a size to permit the number of air changes prescribed in 3 above at a maximum air velocity of 3,000 fpm. Such openings shall be located as high as possible and designed to vent the entire compartment. They shall be equipped with an opening protective or closure having a fire protective rating complying with table 5–3 (§ 27-342). Such closures shall be automatically openable individually upon the activation of a detector located at the return shaft of the compartment and upon the activation of any other detectors installed within the compartment.
5. An approved, automatically controlled, exhaust fan of such capacity as to exhaust 60 air changes per hour from the largest compartment served by the shaft and capable of maintaining not less than a 2-inch negative static pressure at its inlet under flow conditions shall be installed in the shaft.
a. The fan shall be located so that the bottom of the fan inlet is located not less than 3 feet above the top of the automatic protective closure in the highest fire floor served by the shaft.
b. The shaft shall terminate at least 3 feet above the roof level where it penetrates the roof and shall be provided with a protective weather closure which can be opened manually from the outside.
c. When the closure in the required opening on a floor opens, this shall automatically open the weather closure and start the fan.
d. The shaft exhaust fan shall also be controlled from a local start-stop station at the fan, and at either the mechanical control center or the fire command station.
e. The fan shall be operated from circuits that are separate from the general lighting and power circuits, either taken off ahead of the main switch or connected to an emergency power source when such source is provided.