  6. SECTION 6 – THICKNESS AND HEIGHT OF MASONRY EMPIRICAL PROVISIONS

NYC Administrative Code SECTION 6 – THICKNESS AND HEIGHT OF MASONRY EMPIRICAL PROVISIONS

6.1 GENERAL.—Compliance with the provisions of this section shall not be required where the design is proportioned on the basis of analysis of stresses.

6.2 MINIMUM THICKNESS.—The provisions of section 5.3 shall apply.

TABLE RS 10–1–7 Minimum Thickness of Masonry

Type of Masonry Nominal Thickness (in.) Loadbearing walls (exterior or interior).— • Solid masonry 5 • Grouted or filled cell masonry 6 • Hollow masonry 6 • Cavity or masonry bonded hollow walls 8a • Stone ashlar masonry 12 • Stone rubble masonry 16c Non-loadbearing walls.— • Exterior walls 4 • Partitions 2 Columns.— • Solid unit masonry 6 • Hollow unit masonry 8 • Facing of faced walls 2b

Notes—

a Overall wall thickness including cavity.

b In no case less than 1/8 the height of the facing unit.

c 12 in. for one story buildings.

6.3 CHANGE IN THICKNESS.—

6.3.1 Variation in thickness.—Except for window-paneled backs, and permissible chases and recesses (section 10.1) walls shall not vary in thickness between their lateral supports. When a change in thickness, due to minimum thickness requirements, occurs between floor levels, the greater thickness shall be carried up to the higher floor level.

6.3.2. Decrease in thickness.—The provisions of section 5.4 shall apply.

6.4 LOADBEARING WALLS.—Where the height of exterior or interior load-bearing masonry walls does not exceed the following requirements, such walls, if they meet the provisions of section 4 with regard to compressive stress and of section 5.3 with regard to minimum thickness, may be considered to be adequate to resist the applied wind loads, and other shearing forces.

6.4.1 Multi-story buildings.—For limitations on 8 in. walls see (f) below.

(a) Exterior solid walls.—The thickness of solid exterior masonry bearing walls shall be at least 8 in. for the top floor and 12 in. for a maximum of 55 ft. measured downward from the top floor level. Any additional height shall be provided by 16 in. lower walls up to a maximum building height of 104 ft. Buildings taller than 104 ft. shall be structurally analyzed and designed. The slenderness ratio shall not exceed 20.

(b) Interior solid walls.—Interior solid walls shall be at least 8 in. thick for the uppermost 55 ft. of wall height and 12 in. for the lower walls for a maximum building height of 104 ft. Taller walls shall be designed by structural analysis.

(c) Cavity walls.—Cavity walls or masonry bonded hollow walls shall be at least 8 in. thick for the top floor and 12 in. thick for the lower walls up to a maximum total height of 40 ft. except that 10 in. cavity walls may be used for a maximum total height of 25 ft. Taller walls shall be designed by structural analysis.

(d) Walls of hollow units.—Loadbearing walls of hollow units shall be at least 8 in. thick for the top floor and at least 12 in. for the lower walls for a maximum building height of 40 ft. Hollow unit walls 40 ft. high may be supported by solid masonry walls whose height is no more than 35 ft. above the first tier of beams.

(e) Stiffened walls.—Where solid masonry bearing walls are stiffened by, and tied to, reinforced concrete floors or masonry cross walls at distances not greater than 20 ft. apart, they may be 12 in. thick for the uppermost 70 ft., measured downward from the top of the wall.

(f) Eight inch walls.—Notwithstanding other provisions in this section, the thickness of masonry bearing walls may be 8 in. where: (1) the total height of the wall above its support does not exceed 35 ft. except for cavity walls for which (c) above shall apply, and (2) the distance from floor-to-floor or floor-to-roof does not exceed 12 ft. and (3) the floor live load does not exceed 60 psf; and (4) the roof is designed so that the dead load imparts no lateral thrust to the wall.

6.4.2. One-story buildings.—The bearing walls of one story buildings shall be at least 6 in. thick provided the vertical loads on the roof impart no lateral thrust to the wall.

6.4.3 Walls of residence buildings.—In residence buildings not more than three stories high, bearing walls other than coursed or rough or random rubble stone, may be 8 in. thick when not over 35 ft. high and the roof is designed so that the dead load imparts no lateral thrust to the wall. Such walls in one story residence buildings, and in one story private garages, may be 5 1/2 in. thick.

6.4.4. Walls above roof level.—Masonry walls above roof level, 12 ft. or less in height, enclosing stairways, machinery rooms, shafts, or penthouses, may be 8 in. thick and may be considered as neither increasing the height nor requiring any increase in the thickness of the wall below. Parapet walls shall conform to the provisions of section 10.4.

6.4.5. Faced or composite walls.—Neither the thickness or height of faced or composite walls, nor the distance between lateral supports, shall exceed that prescribed for masonry of either of the types forming the facing or the backing.

6.4.6. Cavity or masonry bonded hollow walls.—Where both the facing and backing wythes are constructed of solid masonry units, the wythes may be 3 in. thick. Otherwise, the wythes of cavity walls shall each have a thickness of at least 4 in. and the cavity shall be at least 2 in. but not more than 4 in. wide. Wythes less than 4 in. thick shall not have raked joints and the backing wythe of cavity or masonry bonded hollow walls shall be at least as thick as the facing wythe. A cavity or masonry bonded hollow wall may be constructed to its maximum permissible height on top of a solid masonry wall whose maximum height is 35 ft. above the first tier of beams. Roof construction shall be designed so that the dead load imparts no lateral thrust to the wall.

6.4.7. Rubble stone walls.—Rough, random, or coursed rubble stone walls shall be 4 in. thicker than is required for other types of masonry, but in no case less than 12 in. thick.

6.4.8. Wall thickness increase due to span length.—When the clear span between bearing walls or between a bearing wall and an intermediate support is more than 26 ft., the effects of temperature, of rotation of end supports, and of eccentricity shall be investigated. In lieu of such investigation, the thickness of such walls shall be increased 4 in. for each 12 1/2 ft., or fraction thereof, that such span is in excess of 26 ft.

6.5 NON-LOADBEARING WALLS.—Provided that they conform to the provisions of section 5, non-loadbearing masonry walls, including curtain walls and panel walls, may be 4 in. less in thickness than required in section 6.4 for loadbearing walls, except as provided below.

6.5.1. Partitions.—The minimum thickness for partitions shall be as follows:

Height of Walls Thickness • 8 ft. under 2 in. • Over 8 ft. to 12 ft. 3 in. • Over 12 ft. to 16 ft. 4 in. • Over 16 ft. to 20 ft. 6 in. • Over 20 ft. to 24 ft. 8 in.

6.6 OPENINGS IN BEARING WALLS.—The area of openings in any transverse horizontal plane of a bearing wall shall not exceed 50 per cent of the gross sectional area unless the wall panel can be demonstrated by analysis to be structurally adequate with the increased area of openings.