NYC Administrative Code SECTION 7 – BONDING

7.1 GENERAL.—All multiple wythe masonry loadbearing and non-loadbearing walls shall be bonded in accordance with one of the methods indicated in sections 7.2 through 7.4. For grouted masonry see section 8.

7.2 BONDING WITH MASONRY HEADERS.—Where the facing and backing of solid masonry construction are bonded by means of masonry headers, at least 14 per cent of the wall surface of each face shall be composed of headers extending at least 3 in. into the backing. The distance between adjacent full length headers shall not exceed 24 in. either vertically or horizontally. In walls in which a single header does not extend through the wall, headers from the opposite sides shall overlap at least 3 in., or headers from opposite sides shall be covered with another header course overlapping the header below at least 3 in.

7.3 BONDING WITH METAL TIES.—The facing and backing (adjacent wythes) of masonry walls shall be bonded with corrosion-resistant 3/16 in. diameter (1/8 in. diameter for veneer), steel ties or metal wire of equivalent stiffness embedded in the horizontal mortar joints. There shall be at least one metal tie for each 2 sq. ft. of wall area. Ties in alternate courses shall be staggered, the maximum vertical distance between ties shall not exceed 24 in., and the maximum horizontal distance shall not exceed 36 in., except that for cavity walls having less than a 4 in. wythe, the maximum vertical distance between ties shall not exceed 16 in. Rods or ties bent to rectangular shape shall be used with hollow masonry units laid with the cells vertical. In other walls, the ends of ties shall be bent to 90 degree angles to provide hooks at least 2 in. long. Additional bonding ties shall be provided at all openings and shall be spaced not more than 3 ft. apart around the perimeter and within 12 in. of the opening.

7.3.1 BONDING OF WALLS.—Walls bonded in accordance with this section or section 7.4 shall conform to the allowable stress, lateral support, thickness, height, and mortar requirements for cavity walls unless the collar joints in such walls are filled with mortar.

7.4 BONDING WITH PREFABRICATED JOINT REINFORCEMENT.—The facing and backing (adjacent wythes) of masonry walls may be bonded with prefabricated joint reinforcement. There shall be at least one cross wire serving as a tie for each 2 sq. ft. of wall area. The vertical spacing of the reinforcement shall not exceed 16 in.

7.5 BONDING FACED OR COMPOSITE WALLS.—Faced or composite walls may be bonded as provided for in sections 7.2, 7.3, and 7.4. Where the facing and backing are bonded by means of masonry headers, such headers shall extend at least 3 in. into a hollow masonry back-up unit specifically designed to receive and provide mortar bedding for the header.

7.6 BONDING CAVITY AND MASONRY BONDED HOLLOW WALLS.—

7.6.1 Cavity walls.—Wythes of cavity walls shall be bonded as required in sections 7.3 or 7.4.

7.6.2 Masonry bonded hollow walls.—Wythes of masonry bonded hollow walls shall be bonded as required in section 7.2.

7.7 MASONRY LAID IN STACK BOND.—Where unit masonry is laid in stack bond, continuous prefabricated joint reinforcement or other steel bar or wire reinforcement shall be embedded in the horizontal mortar beds at vertical intervals not to exceed 16 in. The longitudinal reinforcement shall be not less than no. 9 steel wire gage. At least one longitudinal bar or wire shall be provided in the prefabricated unit for each 6 in. of wall thickness or fraction thereof.

7.8 ASHLAR, NATURAL OR CAST STONE.—In ashlar masonry, bond stones uniformly distributed shall be provided to the extent of at least 10 per cent of the wall area. Such bond stones shall extend at least 4 in. into the backing wall. Rubble stone masonry, 24 in. thick or less, shall have bond stones with a maximum spacing of 3 ft. vertically or horizontally and, if the masonry is thicker than 24 in. shall have one bond stone for each 6 sq. ft. of wall surface on both sides.

7.9 LONGITUDINAL BOND.—In each wythe of masonry loadbearing and non-loadbearing walls, at least 60 per cent of the stretchers in any transverse vertical plane shall lap the units above and below at least 2 in. or 1/3 the height of the unit, whichever is greater, or the masonry walls or partitions shall be reinforced longitudinally as required in section 7.7.

7.10 BONDING OF INTERSECTING WALLS AND PARTITIONS.—Bonding of intersection walls shall be as required in section 9.2.