  6. SECTION 9 – ANCHORAGE

NYC Administrative Code SECTION 9 – ANCHORAGE

9.1 GENERAL.—All elements depending upon one another for continuity or support shall be securely anchored in such a manner as to resist all forces that tend to separate them.

9.2 INTERSECTING WALLS AND PARTITIONS.—Masonry walls and partitions shall be securely anchored or bonded at points where they meet or intersect by one of the following methods:

9.2.1 Bonding.—Walls may be bonded by laying at least 50 per cent of the units at the intersection in a true masonry bond with alternate units having a bearing of at least 3 in. upon the unit below, by metal ties, joint reinforcement, anchors as specified in section 9.2.3., or by other equivalent method.

9.2.2 Interior non-loadbearing walls.—Interior non-loadbearing walls shall be anchored at their intersection, at vertical intervals of not more than 2 ft. on centers, with at least 22 gage corrosion-resistant, corrugated metal ties at least 7/8 in. wide extending at least 4 in. into the masonry or with other ties which provide equivalent anchorage.

9.2.3 Walls carried up separately.—Where the courses of meeting or intersection walls are carried up separately corner intersections shall be made by regularly toothing or blocking with 8-in. maximum offsets and providing metal anchors having a minimum section of 1/4 in. by 1 1/2 in. with ends bent up at least 2 in., or cross pins at the joints. Such anchors shall be at least 2 ft. long with a maximum vertical spacing of 4 ft. Other types of metal ties, joint reinforcement, or anchorage shall be spaced to provide equivalent anchorage at the intersection.

9.3 WALLS ADJOINING OR INTERSECTING STRUCTURAL FRAMING.—Where walls are dependent upon the structural frame for lateral support, they shall be anchored with flexible metal anchors or keyed to the structural members.

9.4 ANCHORAGE OF FURRING.—Masonry furring shall be anchored to the backing with hardware cloth ties consisting of 1/2 in. mesh no. 20 steel wire gage galvanized iron fabric at least 4 in. long and extending at least 1 1/4 in. into the facing and backing or by an equivalent means of anchorage. Ties shall be spaced no more than 24 in. apart vertically and 36 in. apart horizontally. Such masonry furring shall be excluded in calculating the required wall thickness and shall not be considered as having any structural value.

9.5 ANCHORAGE OF FLOOR JOISTS.—Wood floor joists 5 ft. or more above grade bearing in masonry walls shall be anchored to the wall at intervals not to exceed 6 ft. by metal anchors having a minimum cross section of 0.25 sq. in. and at least 16 in. long. The anchors shall be securely fastened to the joists and built at least 3 1/2 in. into the masonry. Joists 5 ft. or more above grade and parallel to the wall shall be tied to the wall with metal straps that are spaced not more than 8 ft. on centers and that engage at least three joists. Anchors shall be in line with the bridging or blocking.

Steel floor joists bearing on masonry shall be anchored to the masonry in a manner at least equivalent to that required for wood joists.

Concrete slabs bearing on masonry walls require no additional anchorage.

The ends of joists, rafters, beams, or girders required to be anchored into walls or bearing partitions shall be continuous and the opposite end shall be similarly anchored into a wall or bearing partition. However, if discontinuous, the discontinuous ends shall lap each other at least 6 in. and shall be well bolted or spiked together, shall be butted and fastened by metal straps or ties, or other means shall be provided for the transfer of thrust between the discontinuous ends.

9.6 ROOF ANCHORAGE.—Roof construction, other than cast-in-place concrete slabs, shall be securely anchored to loadbearing masonry walls with minimum 1/2 in. bolts spaced 8 ft. on center, or their equivalent. The bolts shall extend and be embedded a minimum of 15 in. vertically into the masonry, or where a continuous bond beam is provided, shall be hooked tightly around or welded to at least 0.2 sq. in. of continuous longitudinal bond beam reinforcement placed at least 6 in. from the top of the wall.