NYC Administrative Code RS 10-5B

AISC-LRFD Load and Resistance Factor Design Specification for Structural Steel Buildings, effective December 1, 1993.

MODIFICATIONS—The provisions of AISC-LRFD Load and Resistance Factor Design Specifications for Structural Steel Buildings, December 1, 1993 shall be subject to the following modifications. The section and paragraph numbers are from that standard.

A3 MATERIAL—Revise the first line of Subsection 1. and add a new Subsection 7. to read as follows:

"Material conforming to the following standard specifications shall be used."

"7. Special Steels.

Steels other than those listed above may be used in accordance with the provisions of this reference standard when approved by the NYCDOB for such use."

A4 LOADS AND LOAD COMBINATIONS—Add the following as paragraph one.

"The provisions of the building code for loads shall apply. The load factors and load combinations contained in Subsections 1., 2. and 3. of this section shall be used in conjunction with designs based on the use of this AISC-LRFD specification."

A6 REFERENCED CODES AND STANDARDS—Revise the list of publications of the following listed standards to read as follows:

American Society of Civil Engineers

ASCE 7-93

American Society for Testing and Materials

ASTM A6–94a ASTM A 53–93a ASTM A 194–94a ASTM A 325–94 ASTM A 490–93 ASTM A 502–93 ASTM A 563–94 ASTM A 588–94 ASTM A 618–93 ASTM A 709–94 ASTM C 330–89 ASTM A 27–93 ASTM A 148–93b ASTM A 242–93a ASTM A 354–94 ASTM A 500–93 ASTM A 514–94a ASTM A 570–92 ASTM A 606–91a ASTM A 668–93 ASTM A 852–93a ASTM F 436–93 ASTM A 36–94 ASTM A 193–94b ASTM A 307–94 ASTM A 449–93 ASTM A 501–93 ASTM A 529–94 ASTM A 572–94b ASTM A 607–92a ASTM A 687–93 ASTM C 33–93

American Welding Society

AWS D1.1–94 AWS A5.17–89 AWS A5.23–90 AWS A5.1–91 AWS A5.18–93 AWS A5.28–90 AWS A5.5–89 AWS A5.20–89 AWS A5.29–89

CHAPTER B DESIGN REQUIREMENTS

Add the following at the end of the section.

"The applicable provisions of the Building Code for moving loads shall apply."

CHAPTER I COMPOSITE MEMBERS

I1. DESIGN ASSUMPTIONS—Add the following paragraph at the beginning of the section.

"Concrete-Plain and Reinforced—All concrete materials and reinforcing shall meet the applicable requirements of the building code. Composite construction used for member subject to heavy vehicle loads, as defined in the building code for moving loads (except where the applied vehicle is limited to passenger cars), shall be proportioned in accordance with the requirements of Reference Standard RS 9-3."

I3. FLEXURAL MEMBERS—Add the following to the end of the second paragraph in subsection 3. Strength of Concrete-encased Beams.

"provided the encased beam is A36 structural steel not more than 40 in. in depth and the concrete has a minimum compressive strength of 3,000 lbs. per square inch and is made with ASTM C 33 aggregate."

15. SHEAR CONNECTORS—Add the following paragraphs after the first paragraph of subsection 1. Materials.

"For aggregate not complying with ASTM C 33, the Department of Buildings' Rules for Design of Composite Construction with Metal Decks or Lightweight Concrete, dated September 8, 1975 or as subsequently revised, shall be adhered to. Working values for use with construction for which design values have not been established in accordance with the foregoing and for connector types other than those covered by Subsections 3. and 4. of Section I5 shall be established by a prequalified load test as set forth in § 27-599. The minimum specified compressive strength of concrete (f'c) shall be 3,000 psi.

I6. SPECIAL CASES—Add the following to the end of the paragraph.

"satisfactory to the commissioner."

CHAPTER J CONNECTIONS, JOINTS AND FASTENERS

JI GENERAL PROVISIONS

8. Placement of Welds and Bolts—At the end of the last sentence add the following:

"The foregoing provisions notwithstanding, the eccentricity perpendicular to the plane of the connection shall be considered in proportioning both the number and the connection."

12. WELDS—Add the following paragraph at the beginning of the section before the initial paragraph.

"The provisions of the building code for welding operations, the Board of Standards and Appeals' Rules for Arc and Gas Welding and Oxygen Cutting and Steel Covering the Specifications for Design, Fabrication and Inspection of Arc and Gas Welded Steel Structures and Qualification of Welders and Supervisors, and the Board of Standards and Appeals' rules for Electro-slag Welding Approvals shall apply."

Add the following paragraph after the first paragraph in Section J2.

"Welding equipment used to perform submerged-arc, gas metal-arc and flux cored arc welding of high strength steel and electro-slag or electro-gas welding of all steel shall be approved."

J3. BOLTS AND THREADED PARTS

2. Size and Use of Holes—Add the following after the title of paragraph c., d., and e.

"subject to the approval of the engineer of record,"

6. Combined Tension and Shear in Slip-critical Joints—Add the following:

"Allowable stresses for a combination of loads for A325 and A490 bolts shall be used in slip-critical connections. The applicable provisions of the Building Code for wind load shall apply."

K2. PONDING—Add the following paragraph at the end of the section.

"In roof systems where secondary members are made up of materials other than steel, the depth of the beams and girders supporting flat roofs shall not be less than fb/600 times their span length whether designed as simple or continuous spans."

K3. FATIGUE—Add the following paragraph

"The design of overhead beams for elevators and hoisting apparatus and their immediate supporting framing and their connections shall be designed for fatigue loading."

L2. EXPANSION AND CONTRACTION—Precede the present text with the following:

"The provisions of the building code for loads due to thermal forces shall apply.

All exterior members of structural steel, except roofing and siding, that are exposed to the weather shall have a protective coating as required by the provisions of Section M3.9 and shall have a minimum thickness of metal of 0.23 in. Exception: The minimum thickness of metal may conform to the requirements for stress under the following conditions:

1. Exterior members exposed to the weather—A type of atmospheric corrosion resistant steel is used or exposed surfaces are zinc coated with a minimum weight of coating of approximately 0.6 ounces per square foot of exposed surface and covered with a protective coating as required by section M3. or exposed surfaces are protected by other means.

2. Members not exposed to the weather—All members, except that members located where they would be subject to accidental impact, shall be stiffened to resist such impact.

3. Roofing and siding—All members, provided that surfaces which are exposed to the weather, shall have a protective coating.

4. Temporary construction that will be in place for a period of one year or less, provided that all surfaces which are exposed to the weather shall have a protective coating.

5. Joists or purlins that are exposed to the weather but which do not support more than 200 sq. ft. of floor or roof area, and which have a protective coating as required by section M3."

CHAPTER M FABRICATION, ERECTION AND QUALITY CONTROL

M1. SHOP DRAWINGS—Add the following after the first paragraph.

"The plans shall include the location of oversized, short-slotted or long-slotted holes."

M3. SHOP PAINTING—Delete this section and substitute the following:

"M3. PAINTING OF STRUCTURAL STEEL

(a) All structural steel, except as provided in subsection (b) of this section, shall receive one coat of paint, zinc, or bituminous coating, or equivalent metal protection before erection. The protection shall be applied thoroughly and evenly to dry surfaces which have been cleaned of loose mill scale, loose rust, weld slag flux deposit, dirt and other foreign matter. Oil and grease deposits shall be removed. Surfaces inaccessible after assembly shall be treated as required above prior to assembly.

(b) Surfaces of structural steel shall not be required to receive metal protection when the structural steel is used under the conditions listed in paragraph (1) through (7) below. However, these surfaces shall be cleaned of oil and grease by solvent cleaners and be cleaned of dirt and other foreign material by thorough brushing with a fiber brush.

(1) Structural steel that is encased in concrete (other than cinder concrete) or surfaces that abut concrete (other than cinder concrete) at interior locations.

(2) Structural steel encased in non-corrosive fire resistive materials that are bonded or secured to the steel surfaces by approved means.

(3) Surfaces of structural steel that are to be riveted, bolted or welded together.

(4) Surfaces of structural steel within 2 in. of field welds shall be free of protective coatings that would prevent proper welding or produce objectionable fumes while welding is being done.

(5) Surfaces of structural steel that have been machine finished.

(6) Surfaces of types of structural steel that have been specifically approved for use without metal protection.

(7) Structural steel members that are completely concealed by interior finish such as lath and plaster, masonry, etc., need not be painted except that where such members are subject to condensation from piping, are in shower or steam rooms, are exposed to chemical fumes or are exposed to other conditions of potentially aggressive corrosion.

(c) Parts of structural members left unpainted because of welding, bolting or riveting operations, not exempted from painting by the provisions of subsection (b) above, shall receive a field application of metal protection as prescribed in subsection a. above.

(d) Structural steel that will remain exposed to the weather or to a corrosive atmosphere shall receive an additional coat of metal protection of another color after erection, except for types of structural steels that have been specifically approved for use under exposure to the weather without protection.

(e) All abrasions to, or deteriorations of, the protective coating shall be spot painted."

M4. ERECTION—Add the following to subsection 7. Field Connections.

"Field connections shall meet the requirements for corresponding types of shop connections described in section M2., subsection 5, Bolted Construction. No holes, copes or cuts of any type shall be made to facilitate erection unless specifically shown on the shop drawings or authorized in writing by the engineer or architect of record.

M4. ERECTION—Add the following new subsection 8.

"8. Handling and Storing Materials.

All steel members shall be shipped and handled in a manner that will not cause injury to protective coatings or permanent deformations of the members. Steel members shall not be dropped, thrown, or dragged. Any bends, crimps or other evidence of permanent deformations shall be straightened by methods approved by the engineer or architect of record or the piece shall be rejected. Materials shall be stored out of contact with the ground, kept clean, and, in general, protected against damage and corrosion."

M5. QUALITY CONTROL—Add the following paragraph before the initial paragraph:

"The requirements of the building code for quality control shall also apply."

Add this section following Section M5.5 Identification of Steel:

All connections, both field and shop, shall be subject to Controlled Inspection pursuant to the requirements of § 27-132, § 27-585 and Table 10–2 of § 27-586 of the Administrative Building Code."