NYC Administrative Code RS 12-1 HEATING
1. HEATING CAPACITY—The heating capacity required in each room or space shall be calculated in accordance with the principles set forth in ASHRAE Handbook—1987 HVAC Systems and Applications.
The calculations of heating capacity shall consider the areas and transmission coefficients of all surfaces exposed to outdoor and temperatures or to unheated areas, and shall include allowance for air infiltration and wind velocity. In spaces with high ceilings, an allowance shall be made for the effect of stratification so that the prescribed temperature will be maintained at a level 5 feet above the floor.