NYC Administrative Code RS 10-8 LUMBER AND TIMBER CONSTRUCTION
AF&PA 1991 National Design Specification for Wood Construction—and its 1991 Supplement with 1993 Revisions.
MODIFICATIONS—The provisions of AF&PA—National Design Specifications for Wood Construction shall be subject to the following modifications. The section and paragraph numbers are from that standard.
Part 1—General Requirements for Structural Design
1.4.2—Governed by Codes.
The provisions of the New York City Building Code shall constitute the minimum design loads.
Part IV—Sawn Lumber
4.1.2.1—When the design values specified herein are used, the lumber, including end-jointed or edge-jointed lumber shall be identified in accordance with the provisions of the Building Code for Identification. See Sections 26-251 and 27-618 of the code.
Part XIII—Metal Connector Plates
13.2—Design Values for Metal Connector Plates.
13.2.1—Tests for Design Values.
Tests to determine lateral design values for metal connector plates shall be conducted in accordance with ASTM Standard D 1761–88 (Reference 13) or other approved test methods. The strength value of the metal connector plate in tension and shear shall be determined in accordance with ASTM E 489–81, Tensile Strength Properties of Steel Truss Plates and ASTM E 767–80, Shear Resistance of Steel Truss Plates. The design value for normal load duration shall be determined by dividing the test load at wood-to-wood slip of 0.03" by 1.6 or by dividing the ultimate test load by 3.0, using the smaller of the two values as the design value (see Reference 43 for additional information). Design values determined in accordance with these test procedures shall be multiplied by all applicable adjustment factors (see Table 7.3.1) to obtain allowable design values.
13.2.3—Testing.
Full scale tests on representative trusses shall be conducted with ASTM E 73–84 Standard Methods of Testing Truss Assemblies.
13.2.4—Handling, Installation and Bracing.
Handling, installation and bracing metal plate connected wood trusses shall be in accordance with the recommendations of Truss Plate Institute, TPI-HIB-91, Commentary and Recommendations for Handling, Installing and Bracing Metal Plate Connected Wood Trusses.
Part XVI—Fire Protection
16.1—Scope.
This part is added to provide current State-of-the-Art requirements for firestopping of concealed spaces above dropped ceiling and above ceilings attached to open web combustible trusses. These requirements are in addition to Sections 27-327 and 27-345 of the Building Code.
16.2—General.
16.2.1—General Requirement for Firestopping.
The space between the ceiling and the floor or roof above shall be divided by providing firestopping where ceilings are suspended below solid joists or suspended from or attached directly to the bottom of open wood floor trusses in buildings of combustible construction.
16.2.1.1—The space shall be divided into approximately equal areas not greater than 500 square feet in buildings of combustible construction. The firestopping shall generally be provided parallel to the main framing members. The roof trusses of private dwellings with roofs having a slope greater than 15 degrees from the horizontal may be excluded from this requirement.
16.2.1.2—Exception—Where the space above the ceiling is of combustible construction and the building is sprinklered in accordance with reference standard RS 17–2, above and below the ceiling, the firestopping may be omitted.