NYC Administrative Code SECTION 8 – GROUTED AND FILLED CELL MASONRY
8.1 MATERIALS.—Only solid masonry units shall be used in grouted masonry construction and only vertical cell hollow masonry units shall be used in filled cell construction. In grouted masonry, fine grout (reference standard RS 10–47) shall be used in grout spaces with a least clear dimension less than 2 in. and coarse grout (reference standard RS 10–47) shall be used in grout spaces with a least clear dimension of 2 in. or more. In filled cell masonry, either fine or coarse grout may be used where the least clear dimension of the core is less than 4 in., and coarse grout shall be used where the least clear dimension of the core is 4 in. or more.
8.2 CONSTRUCTION.—
8.2.1. Grouted masonry.—The masonry units in either the inner or outer wythes, but not necessarily both, shall have a 24-hr. cold water absorption of not less than 5 per cent. All masonry units in the inner and outer wythes shall be laid plumb in full head and bed joints and mortar "fins" shall not protrude into spaces designed to be filled with grout. Only type M or S mortar shall be used. All interior joints shall be solidly filled with grout, except that masonry units in the core may be placed or floated in grout poured between the two outer wythes. The grouted longitudinal joints shall be not less than 3/4 in. wide. Where the least clear dimension of the longitudinal vertical joint or core is less than 2 in., the maximum height of pour shall be 12 in. Where the least clear dimension of the longitudinal vertical joint or core is 2 in. or more, the maximum height of grout pour shall not exceed 48 times the least dimension of the longitudinal vertical joint for coarse grout nor 64 times for fine grout, but in no case shall the maximum height or grout pour exceed 12 ft. When grouting is stopped for 1 hr. or longer, the grout pour shall be stopped 1 1/2 in. below the top of a masonry unit and properly rodded or puddled. Masonry bonders shall not be used, but metal wall ties may be used to prevent spreading of the wythes and to maintain vertical alignment of the wall. Where such metal ties are used, they shall be protected as required in section 10.12.
8.2.2. Filled cell masonry.—All units shall be laid plumb with full face shell mortar beds. All head (or end) joints shall be filled solidly with mortar for a distance in from the face of the unit or wall not less than the thickness of the longitudinal face shells. Cross webs adjacent to vertical cores shall be fully bedded in mortar to prevent leakage of grout and mortar "fins" shall not protrude into spaces designed to be filled with grout. Only type M or S mortar shall be used. Bond of masonry units in a single wythe shall be provided by lapping units in alternate vertical courses. Where masonry units are laid in stack bond, continuous joint reinforcement shall be used in the bed joints as required by section 7.7. All filled cell masonry shall be built to preserve the unobstructed vertical continuity of the cores. The minimum continuous clear dimensions of vertical cores shall be 2 in. × 3 in. In filling vertical cores, the grout shall not exceed 4 ft. in height. Grout shall be rodded or puddled during placement to insure complete filling of the core. When grouting is stopped for 1 hr. or longer, the grout pour shall be stopped 1 1/2 in. below the top of a masonry unit.