NYC Administrative Code SECTION 12 – MISCELLANEOUS STRUCTURES AND SYSTEMS

12.1 FLAT OR SEGMENTAL MASONRY FLOOR OR ROOF ARCHES.—The provisions of this section do not apply when masonry floor or roof arches are proportioned on the basis of structural analysis.

12.1.1 Span. The maximum clean span between supporting beams shall be 8 ft.

12.1.2 Tie rods. All masonry flat arches or segmental arches shall be provided with tie rods in both the exterior and interior spans. The minimum size and spacing of tie rods shall be:

For exterior spans — 1 1/4 in. round rods spaced 4 ft.-6 in. apart.

For interior spans — 7/8 in. round rods spaced 4 ft.-6 in. apart.

Washers shall be used with all tie rods. All tie rods shall have a minimum specified yield point of 33,000 psi.

12.1.3 Flat arches. The depth of flat arches of burnt clay or shale hollow blocks shall be at least 1 1/2 in. for each foot of span, inclusive of the portion of the block extending below the under side of the beam, and such arches shall be at least 6 in. thick. Brick shall not be used for flat arches.

12.1.4 Segmental arches. Segmental arches shall have a rise of at least 1 in. per ft. of span, and the minimum thickness shall be 6 in. for hollow tile arches and 4 in. for brick arches with a span of 5 ft. or less and 8 in. for brick arches with a span exceeding 5 ft.

12.1.5 Structural clay tile arches. The blocks shall be at least two cells deep, shall be laid in type M or S mortar, and shall be properly keyed.

12.1.6 Brick Arches. Brick arches shall be laid in a full bed of type M or S mortar and shall be solidly bonded.

12.1.7 Openings in floors and roofs. Suitable metal framing or reinforcement shall be provided in masonry arch and roof construction around any opening more than 1 ft.-6 in. on a side.

12.2 CHIMNEYS. The design of chimneys shall be predicated on the following requirements:

12.2.1 CHIMNEY WALLS. Chimney walls constructed of perforated radial brick with perforations not exceeding 33 per cent of the gross area may be designed using the values shown in Tables RS 10–1–4 and 10–1–5 applicable to solid units.

*12.2.2 CHIMNEY LININGS. The lining in chimneys shall not be considered as taking either compression or tension stresses.

*12.2.3 CHIMNEY EXPANSION AND CONTRACTION. Expansion and contraction in chimney walls due to temperature variations shall be accommodated solely by the use of steel reinforcing rings.

*12.2.4 REINFORCING RINGS. Reinforcing rings shall be provided at all changes in wall thickness, at the top of the chimney, and above and below all flue openings, but may be omitted at changes in wall thickness for chimneys constructed of perforated radial brick with type M mortar.