NYC Administrative Code SECTION 11 – VENEER

11.1 GENERAL.—Veneer as used in this section refers to an exposed facing wythe of brick, tile, ceramic veneer, terra cotta, concrete masonry units, cast stone, natural stone, or similar weather-resistant noncombustible masonry units laid in mortar and securely attached to a surface for the purpose of providing ornamentation, protection or insulation, but not intentionally so bonded as to exert common action under load.

11.1.1 Limitations.—Veneer shall not be assumed to add to the strength of any wall, nor shall it be assumed to support any load other than its own weight. No veneer shall be less than the thicknesses specified in table RS 10–1–9. The height and length of veneer areas shall be unlimited, except as required to control expansion and contraction and except as provided in subdivision 11.2.

Table RS 10–1–9 Minimum Thickness of Masonry Veneer

Type of Veneer Minimum Thickness Actual (in.) Anchored Type: • Solid masonry units 1 5/8 • Hollow masonry units 1 5/8 • Ceramic veneer 1 5/8 Adhesion Type: • Solid masonry units 1/2 • Ceramic veneer 1/2

11.1.2 Design.—All anchor attachments shall be designed to resist a positive or negative horizontal force of 30 psf, and adhesion type veneer shall be designed to have a bond sufficient to withstand a shearing stress of 50 psi. In lieu of design, veneer may be installed in accordance with the requirements of section 11.2.1 and 11.3.1.

11.1.3 Support of veneer.—The weight of all anchored type veneer shall be supported upon footings, foundation walls, or other supports. Veneer above openings shall be supported upon lintels.

11.2 VENEER ON WOOD.—Anchored masonry veneer attached to wood frame structures shall be supported on footings or foundation walls. The height of the veneer shall not exceed 35 feet measured from the top of the supporting footings or foundation walls. Where anchored veneer exceeding 20 feet in height is applied, it shall be supported in a manner that will provide for movement between the veneer and its backing.

11.2.1 Attachment.—Veneer of unit masonry shall be attached directly to wood studs, by one of the following means:

(a) With at least 22 gage corrosion-resistance corrugated steel ties at least 7/8 in. wide at vertical intervals of not more than 24 in. and horizontal intervals of not more than 32 in., but in no case less than one tie for each 3 1/2 sq. ft. of wall area.

(b) Directly to a 1 in. reinforced cement mortar base.

11.3 VENEER ON MASONRY.—Veneer attached to masonry or concrete backing shall not be limited in height other than by compressive stresses.

11.3.1 Attachment.—Veneer shall be securely attached to the masonry or concrete backing by one of the following means or by a means that is equivalent in strength:

(a) Metal ties conforming to section 7.3 except that ties shall be spaced not more than 24 in. apart either horizontally or vertically.

(b) Corrosion-resistant dovetail slot anchors where the backing and the veneer has been designed for this type of attachment. Such anchors shall be formed from at least 16 gage steel at least 1 in. wide.

(c) Adhesion type masonry veneer shall be installed in accordance with the manufactures' recommendations and setting plans.

(d) Where anchored veneer is not grouted to the backing, it shall be supported in a manner that will provide for movement between the veneer and its backing.