RS 14-15. MINIMUM INSTALLATION CLEARANCES FOR HEAT PRODUCTION EQUIPMENT
REFERENCE STANDARD RS 14–15 Minimum installation clearances for heat production equipment a
EQUIPMENT CLEARANCES (in.) Residential Type Equipment for Installation in Large Room b Above Top of Casing or Equipment From Top and Sides of Warm- Air Bonnet or Plenum From Front c From Back From Sides Boilers & Water Heaters— Steam boilers—15 psi Water boilers—250°F Water heaters—200°F (all water walled or jacketed) Automatic oil or comb. gas- oil Automatic gas Solid 6 6 6 — — — 24 18 48 6 6 6 6 6 6 Furnaces, Central— Gravity, upflow, downflow, horizontal and duct. Warm-air 250°F max. Automatic oil or comb. gas-oil Automatic gas Solid Electric 6 6 18 6 6 6 18 6 24 18 48 18 6 6 18 6 6 6 18 6 Furnaces, Floor— For mounting in combustible floor Automatic oil or comb. gas-oil 36 — 12 12 12 Heat Exchanger— Steam—15 psi max. Hot water—250°F max. Automatic gas 36 1 1 — 1 1 12 1 1 12 1 1 12 1 1 Room Heaters— Circulating type (vented or unvented) Radiant type (vented or unvented) Oil and solid Gas Oil and solid Gas Gas with double metal or ceramic back 36 36 36 36 36 — — — — — 24 24 36 36 36 12 12 36 18 12 12 12 36 18 18 Radiators— Steam or hot water Gas 36 — 6 6 6 Ranges— Firing Cooking Stoves (vented or unvented) Oil Gas Solid-clay-lined firepot Solid-unlined firepot 30 f 30 f 30 f 30 f — — — — — — — — 9 6 24 36 24 6 24 36 Electric 30 f — — 6 Clothes Dryers that conform to applicable standards Gas 6 — 24 6 Electric 6 — 24 0
EQUIPMENT CLEARANCES (in.) Commercial-Industrial Type Low Temperature Equipment (Any and all physical sizes except as noted) Above Top of Casing or Equipment d From Top and Sides of Warm- Air Bonnet or Plenum From Front From Back d From Sides d Boilers and Water Heaters— 100 cu. ft. or less (any psi steam) Any size (50 psi or less) All fuels All fuels 18 18 — — 48 48 18 18 18 18 Unit heaters— Floor mounted or suspended (any size) Steam or Hot Water— Oil or comb. gas-oil 1 6 — — — 24 1 18 1 18 Suspended (100 cu. ft. or less) Suspended (100 cu. ft. or less) Suspended (over 100 cu. ft.) Gas All fuels All fuels 6 18 18 — — — 18 48 48 18 18 18 Floor mounted (any size) Ranges— Floor mounted All fuels 48 — 48 18 18 Other Low Temperature Industrial Equipment floor mounted or suspended All fuels 18 18 48 18 18
EQUIPMENT CLEARANCES (in.) Commercial-Industrial Type Medium Temperature Equipment Above Top of Casing or Equipment e From Top and Sides of Warm- Air Bonnet or Plenum From Front From Back e From Sides e Boilers and water heaters— Over 50 psi or Over 100 cu. ft. All fuels 48 — 96 36 36 Other med. temp. industrial equipment—all sizes All Fuels 48 36 96 36 36 incinerators—all sizes 48 — 96 36 36 Industrial type High-Temperature Equipment High temperature equipment All sizes All fuels 180 — 360 120 120
NOTES FOR REFERENCE STANDARD RS 14–15.—
a See reference standard RS 14–16 for reduction of clearance.
b Large rooms are those that are large in comparison to the size of the equipment and have a volume equal to at least 12 times the total volume of a furnace and at least 16 times the total volume of a boiler. If the actual ceiling height of a room is greater than 8 ft., the volume of a room shall be figured on the basis of a ceiling height of 8 ft.
c The minimum dimension shall be that necessary for servicing the equipment, including access for cleaning and normal care, tube removal, etc.
d If the equipment is encased in brick, the 18 in. clearance above and at the sides and back may be reduced to not less than 12 in.
e If the equipment is encased in brick the clearance above may be reduced to not less than 36 in., and at sides and back may be reduced to not less than 18 in.
f To combustible material or metal cabinet. If the underside of such combustible material or metal cabinet is protected with asbestos mill board at least 1/4 in. thick covered with sheet metal of not less than no. 28 U.S. Standard gauge, the distance may be reduced to not less than 24 in.
RS 14-16
Reduced Minimum Clearances for Equipment, using Specified Forms of Protection a
Specified Form of Protection Reduced Clearances (in.) Where the Required Clearance with no Protection is: 36 in. 18 in. 12 in. 6 in. Above Side and Rear Above Side and Rear Above Side and Rear Above Side and Rear (a) 1/4 in. asbestos millboard spaced out 1 in. b 30 18 15 9 9 6 3 2 (b) 28 gauge sheet metal on 1/4 in. asbestos millboard 24 18 12 9 9 6 3 2 (c) 28 gauge sheet metal spaced out 1 in. b 18 12 9 6 6 4 2 2 (d) 28 gauge sheet metal on 1/8 in. asbestos millboard spaced out 1 in. b 18 12 9 6 6 4 2 2 (e) 1 1/2 in. asbestos cement covering on heating equipment 18 12 9 6 6 4 2 1 (f) 1/4 in. asbestos millboard on 1 in. mineral fiber bats reinforced with wire mesh or equivalent 18 12 6 6 4 4 2 2 (g) 22 gauge sheet metal on 1 in. mineral fiber bats reinforced with wire or equivalent 18 12 4 3 2 2 2 2 (h) 1/4 in. asbestos cement board or 1/4 in. asbestos millboard 36 36 18 18 12 12 4 4 (i) 1/5 in. cellular asbestos 36 36 18 18 12 12 3 3
Notes—
a Except for the protection described in (e), all clearances shall be measured from the outer surface of the equipment to the combustible material disregarding any intervening protection applied to the combustible material.
b Spacers shall be of non combustible material.
Applicable to the combustible material, unless otherwise specified, and covering all surfaces within the distance specified as the required clearance with no protection.
RS 14-17
Minimum Equipment Foundation Mountings Requirements
Noncombustible Construction Equipment Classification Fuels Fire Resistance Rating Extension Beyond Equipment Low Temperature All fuels 2 hr. 18 in. on all sides Medium Gas and liquid fuels 3 hr. 3 ft. on all sides Temperature Solid fuels 3 hr. 3 ft. on all sides and 8 ft. on firing side and ash removal side High Temperature All fuels 4 hr. 10 ft. on all sides and 30 ft. at front or side where hot products are removed
Combustible Construction Exceptions Base (in.) Open Clearance Under Applying To: Type of Protection Mounted on Combustible Surface Ext. of Protection Beyond Eqt. All Sides (in.) Solid Fuel-Firing Side at Ash Removal Side (in.) Low temperature equipment 18 1.4 in. asbestos millboard 0 18 8 1/2 in. asbestos millbd. covered with no less than 0.24 Mfg's Standard Gauge Sheet 6 18 4 4 in. of hollow clay or concrete tile 0 18 0 2 courses of 4 in. hollow clay or concrete tile covered with 3/16 in. steel plate 0 18 Medium temperature equipment 24 4 in. of hollow clay or concrete tile 0 18 Boilers, furnaces, and warm air furnaces for heating one-family dwellings; and to floor mounted unit heaters 4 1/4 in. asbestos millboard covered with not less than 0.24 Mfg's Standard Gauge Sheet 6 18 0 4 in. of hollow clay or concrete tile 0 18 Commercial or restaurant type cooking equipment 18 A metal baffle between burner and floor 0 18 8 3/8 in. asbestos millbd. 6 18 4 4 in. of hollow clay or concrete tile 0 18 0 2 courses of 4 in. hollow clay or concrete tile covered with 3/16 in. steel plate 0 0 18 18 Domestic type floor mounted cooking and rm. heating eqpt., such as, stoves, ranges, space heaters, fuel fired steam or hot water radiators and hot water 18 4 A metal baffle between burner and floor 1/2 in. asbestos millbd. covered with not less than No. 24 Mfg's Standard Gauge Sheet 0 0 — 18
Notes for Combustible Construction:
Hollow tile shall be set with ends unsealed and joints matched so as to provide for the circulation of air through the tile. Where two courses of hollow tile are required, the tiles courses shall be laid at right angles to each other with the ends unsealed and joints matched so as to provide for the circulation of air through each course.
Low temperature equipment with a water cooled base and a grate area of less than 3 sq. ft., or low temperature equipment in which the combustion chamber is located at least 12 in. above the floor, may rest directly on a sheet metal base of not less than no. 14 manufacturer's standard gauge sheet steel without heat insulation on combustible construction.
Where the floor protection used does not provide a monolithic surface of steel, concrete, or cement, the side or surface where ashes are removed or where traffic or other usage would wear the protection away shall be covered with no. 24 manufacturer's standard gauge sheet steel or equivalent material.
RS 14-18
ANSI/NFiPA 211–1988—Standard for chimneys, fireplaces, vents and solid fuel burning appliances.
RS 14-19
UL 127–1988—Standard for factory-built fireplaces, as modified by reference standard RS 15–15.
RS 14-21
UL 1482–1988—Standard for room heaters, solid fuel type (September 1988 Revision).
RS 14-22
SMACNA 1992 Fibrous Glass Duct Construction Standard; SMACNA 1995 HVAC Duct Construction Standards—Metal and Flexible; and SMACNA 1985 HVAC Air Duct Leakage Test Manual; as modified.
Modifications:
1) Ducts shall be constructed in accordance with §2–3.1 of Reference Standard RS 13–1; Chapter 2 of Reference Standard RS 13–4; or Chapter 2 of Reference Standard RS 14–1; as applicable.
2) The New York State Energy Conservation Construction Code sets forth requirements for leakage testing of ducts which supercede those contained in this Reference Standard. The leakage testing requirements of this Reference Standard apply to buildings exempted from compliance with the New York State Energy Conservation Construction Code.
RS 15. CHIMNEYS AND GAS VENTS
List of Referenced National Standards RS 15–1 National Fuel Gas Code. RS 15–2 Gas: Cooking, Drying, Heating, Refrigeration, Water Heaters. RS 15–3 Mortar for Unit Masonry. RS 15–4 Clay Flue Linings. RS 15–5 Castable Refractories. RS 15–6 Refractories for Incinerators and Boilers. RS 15–7 Refractories for Incinerators and Boilers. RS 15–8 Chemical-Resistant Masonry Units. RS 15–8A Chimneys, Factory-built, Residential Type and Building Heating Appliances. RS 15–9 Low Heat Appliance Chimneys. RS 15–10 Medium Heat Appliance Factory-built Chimneys. RS 15–11 Factory-built Chimneys, 1400 Degrees Fahrenheit. RS 15–12 Factory-built Chimneys, 650°C. RS 15–13 Gas Vents. RS 15–14 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances. RS 15–15 Factory-built Fireplaces, Modified. RS 15–16 Chimney Liners.
LIST OF REFERENCED NATIONAL STANDARDS
AGA/ANSI–Z223.1 NFiPA—National Fuel Gas Code, and Addenda Z223.1a–1987—1984
ANSI–Z21.1—Household Cooking Gas Appliances, and Addenda Z21.1a–1982, Z21.1b–1984—1982
ANSI–Z21.2—Gas Hose Connectors for Portable Indoor Gas-Fired Equipment, and Addenda Z21.2a–1985, Z21.2b–1987—1983
ANSI–Z21.3—Hotel and Restaurant Gas Ranges and Unit Broilers—1982
ANSI–Z21.5.1—Gas Clothes Dryers, Volume I, Type 1 Clothes Dryers—1982
ANSI–Z21.5.2—Gas Clothes Dryers, Volume II, Type 2 Clothes Dryers, and Addenda Z21.5.2a–1981, Z21.5.2b–1982—1979
ANSI–Z21.8—Installation of Domestic Gas Conversion Burners—1984
ANSI–Z21.10.1—Gas Water Heaters, Volume I—Storage Water Heaters with Input Ratings of 75,000 BTU per Hour or Less—1987
ANSI–Z21.10.3—Gas Water Heaters, Volume III—Storage with Input Ratings above 75,000 BTU per Hour, Circulating and Instantaneous Water Heaters—1987
ANSI–Z21.11.1—Gas-Fired Room Heaters, Volume I, Vented Room Heaters, and Addenda Z21.11.1a–1985—1983
ANSI–Z21.11.2—Gas-Fired Room Heaters, Volume II, Unvented Room Heaters, and Addenda Z21.11.2a–1984—1983
ANSI–Z21.12—Draft Hoods, and Addenda Z21.12a–1983—1981
ANSI–Z21.13—Gas-Fired Low Pressure Steam and Hot Water Boilers, and Addenda Z21–13a–1983—1982
ANSI–Z21.15—Manually Operated Gas Valves, and Addenda Z21.15a–1983, Z21.15b–1984—1979
ANSI–Z21.17—Domestic Gas Conversion Burners—1984
ANSI–Z21.19—Refrigerators Using Gas Fuel, and Addenda Z21.19a–1984—1983
ANSI–Z21.20—Automatic Gas Ignition Systems and Components, and Addenda Z21.20a–1987—1985
ANSI–Z21.21—Automatic Valves for Gas Appliances, and Addenda Z21.21a–1977, Z21.21b–1981—1974
ANSI–Z21.22—Relief Valves and Automatic Gas Shut Off Devices for Hot Water Supply Systems—1986
ANSI–Z21.23—Gas Appliance Thermostats, and Addenda Z21.23a–1985—1980
ANSI–Z21.24—Metal Connectors for Gas Appliances—1987
ANSI–Z21.27—Hotel and Restaurant Gas Deep Fat Fryers, and Addenda Z21.27a–1975, Z21.27b–1978—1974
ANSI–Z21.28—Commercial Gas Baking and Roasting Ovens, and Addenda Z21.28a–1975, Z21.28b–1978—1974
ANSI–Z21.40.1—Gas-Fired Absorption Summer Air Conditioning Appliances, and Addenda Z21.40.1a–1982—1981
ANSI–Z21.41—Quick-Disconnect Devices for Use with Gas Fuel, and Addenda Z21.41a–1981, Z21.41b–1983—1978
ANSI–Z21.42—Gas-Fired Illuminating Appliances, and Addenda Z21.42a–1973, Z21.42b–1981—1971
ANSI–Z21.44—Gas-Fired Gravity and Fan Type Direct Vent Wall Furnaces, and Addenda Z21.44a–1985—1985
ANSI–Z21.45—Flexible Connectors of Other than All Metal Construction for Gas Appliances, and Addenda Z21.45a–1987—1985
ANSI–Z21.46—Gas-Fired Kettles, Steam Cookers and Steam Generators, and Addenda Z21.46a–1975, Z21.46b–1978—1974
ANSI–Z21.47—Gas-Fired Central Furnaces (Except Direct Vent Central Furnaces)—1987
10 CFR Part 430—Test Procedures for Furnaces—1980
ANSI–Z21.48—Gas-Fired Gravity and Fan Type Floor Furnaces—1986
ANSI–Z21.49—Gas-Fired Gravity and Fan Type Vented Wall Furnaces—1986
ANSI–Z21.50—Vented Decorative Gas Appliances—1986
ANSI–Z21.52—Gas-Fired Single Firebox Boiler, and Addenda Z21.52a–1973—1971
ANSI–Z21.54—Gas Hose Connectors for Portable Outdoor Gas-Fired Appliances, and Addenda Z21.53a–1983, Z21.54b–1985—1979
ANSI–Z21.55—Gas-Fired Sauna Heaters, and Addenda Z21.55a–1980, Z21.55b–1981—1979
ANSI–Z21.56—Gas-Fired Pool Heaters and Addenda Z21.56a–1987—1986
ANSI–Z21.57—Recreational Vehicle Cooking Gas Appliances, and Addenda Z21.57a–1982, Z21.57b–1984—1982
ANSI–Z21.58—Outdoor Cooking Gas Appliances—1987
ANSI–Z21.59—Gas-Fired High Pressure Steam and Hot Water Boilers—1974
ANSI–Z21.60—Decorative Gas Appliances for Installation in Vented Fireplaces, and Addenda Z21.60a–1982, Z21.60b–1984—1981
ANSI–Z21.64—Direct Vent Central Furnaces, and Addenda Z21.64a–1986, Z21.64b–1987—1985
ANSI–Z21.65—Separated Combustion System Central Furnaces—1978
ANSI–Z83.2—Gas Atmosphere Generators—1977
ANSI–Z83.3—Gas Utilization Equipment in Large Boilers, and Addenda Z83.3a–1972, Z83.3b–1976—1971
ANSI–Z83.4—Direct Gas-Fired Make-Up Air Heaters, and Addenda Z83.4a–1986—1985
ANSI–Z83.6—Gas-Fired Infrared Heaters, and Addenda Z83.6a–1984, Z83.6b–1985—1982
ANSI–Z83.7—Gas-Fired Construction Heaters—1974
ANSI–Z83.8—Gas Unit Heaters, and Addenda Z83.8a–1986—1985
ANSI–Z83.9—Gas-Fired Duct Furnaces—1986
ANSI–Z83.11—Gas Food Service Equipment—Ranges and Unit Broilers—1986
ANSI–Z83.12—Gas Food Service Equipment—Baking and Roasting Ovens—1986
ANSI–Z83.13—Gas Food Service Equipment—Deep Fat Fryers—1986
ANSI–Z83.14—Gas Food Service Equipment—Counter Appliances—1986
ANSI–Z83.15—Gas Food Service Equipment—Kettles, Steam Cookers, and Steam Generators—1986
ANSI/UL 103—Standard for Chimneys, Factory-Built Residential Type and Building Heating Appliances (February 1989 Revision)—1988
ANSI/UL 441—Standard for Gas Vents—1986
ANSI/UL 710—Grease Extractors for Exhaust Ducts—1981
ANSI/UL 959—Standard for Medium Heat Appliance Factory-Built Chimneys (August 1988 Revision)—1986
UL 103 TYPE HT—Standard for Low Heat Appliance Chimneys with High Temperature Tests Added—1983
UL 127—Standard for Factory-Built Fireplaces, as Modified—1988
UL 795—Commercial Industrial Gas-Heating Equipment, February 1982 Revision—1973
UL 1777—Chimney Liners—1988
ULC S–629M—Standard for 650°C Factory-Built Chimneys—1981
ANSI/NFiPA 211—Chimneys, Fireplaces and Vents—1984
ANSI/NFiPA 211—Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances—1988
ANSI/ASTM C 105—Specification for Ground Fireclay as a Refractory Mortar for Laying Up Fireclay Brick (Reapproved 1981)—1947
ANSI/ASTM C 270—Standard Specification for Mortar for Unit Masonry—1988
ANSI/ASTM C 315—Specifications for Clay Flue Linings (Reapproved 1983)—1978c
ANSI/ASTM C 401—Classification of Castable Refractories—1984
ANSI/ASTM C 64—Specifications for Refractories for Incinerators and Boilers (Reapproved 1977)—1972
ANSI/ASTM C 279—Specifications for Chemical Resistant Masonry—1979
Note: Wherever in these standards reference is made to the "National Electrical Code" the work so covered shall meet the requirements of the Electrical Code of the City of New York.
RS 15-1
AGA/ANSI–Z223.1/NFiPA No. 54–1984—National Fuel Gas Code, and Addenda Z223.1a–1987.
RS 15-2
ANSI–Z21.1–1982—Household Cooking Gas Appliance, and Addenda Z21.1a–1982, Z21.1b–1984.
ANSI–A21.2–1983—Gas Hose Connectors for Portable Indoor Gas-Fired Equipment, and Addenda Z21.2a–1985, Z21.2b–1987.
ANSI–Z21.3–1982—Hotel and Restaurant Gas Ranges and Unit Broilers.
ANSI–Z21.5.1–1982—Gas Clothes Dryers, Volume I, Type 1 Clothes Dryers.
ANSI–Z21.5.2–1979—Gas Clothes Dryers, Volume II, Type 2 Clothes Dryers, and Addenda Z21.5.2a–1981, Z21.5.2b–1982.
ANSI–Z21.8–1984—Installation of Domestic Gas Conversion Burners.
ANSI–Z21.10.1–1987—Gas Water Heaters, Volume I, Storage Water Heaters with Input Ratings of 75,000 BTU per Hour or Less.
ANSI–Z21.10.3–1987—Gas Water Heaters, Volume III, Storage with Input Ratings above 75,000 BTU per Hour, Circulating and Instantaneous Water Heaters.
ANSI–Z21.11.1–1983—Gas-Fired Room Heaters, Volume I, Vented Room Heaters, and Addenda Z21.11.1a–1985.
ANSI–Z21.11.2–1983—Gas-Fired Room Heaters, Volume II, Unvented Room Heaters, and Addenda Z21.11.2a–1984.
ANSI–Z21.12–1981—Draft Hoods, and Addenda Z21.12a–1983.
ANSI–Z21.13–1982—Gas-Fired Low Pressure Steam and Hot Water Boilers, and Addenda Z21.13a–1983.
ANSI–Z21.15–1979—Manually Operated Gas Valves, and Addenda Z21.15a–1981, Z21.15b–1984.
ANSI–Z21.17–1984—Domestic Gas Conversion Burners.
ANSI–Z21.19–1983—Refrigerators Using Gas Fuel, and Addenda Z21.19a–1984.
ANSI–Z21.20–1985—Automatic Gas Ignition Systems and Components, and Addenda Z21.20a–1987.
ANSI–Z21.21–1974—Automatic Valves for Gas Appliances, and Addenda Z21.21a–1977, Z21.21b–1981.
ANSI–Z21.22–1986—Relief Valves and Automatic Gas Shut Off Devices for Hot Water Supply Systems.
ANSI–Z21.23–1980—Gas Appliance Thermostats, and Addenda Z21.23a–1985.
ANSI–Z21.24–1987—Metal Connectors for Gas Appliances.
ANSI–Z21.27–1974—Hotel and Restaurant Gas Deep Fat Fryers, and Addenda Z21.27a–1975, Z21.27b–1978.
ANSI–Z21.28–1974—Commercial Gas Baking and Roasting Ovens, and Addenda Z21.28a–1975, Z21.28b–1978.
ANSI–Z21.40.1–1981—Gas-Fired Absorption Summer Air Conditioning Appliances, and Addenda Z21.40.1a–1982.
ANSI–Z21.41–1978—Quick-Disconnect Devices for Use with Gas Fuel, and Addenda Z21.41a–1981, Z21.41b–1983.
ANSI–Z21.42–1971—Gas-Fired Illuminating Appliances, and Addenda Z21.42a–1973, Z21.42b–1981.
ANSI–Z21.44–1985—Gas-Fired Gravity and Fan Type Direct Vent Wall Furnaces, and Addenda Z21.44a–1985.
ANSI–Z21.45–1985—Flexible Connectors of Other than All Metal Construction for Gas Appliances, and Addenda Z21.45a–1987.
ANSI–Z21.46–1974—Gas-Fired Kettles, Steam Cookers and Steam Generators, and Addenda Z21.46a–1975, Z21.46b–1978.
10 CFR Part 430–1980 Test Procedures for Furnaces.
ANSI–Z21.47–1987—Gas-Fired Central Furnaces (Except Direct Vent Central Furnaces).
ANSI–Z21.48–1986—Gas-Fired Gravity and Fan Type Floor Furnaces.
ANSI–Z21.49–1986—Gas-Fired Gravity and Fan Type Vented Wall Furnaces.
ANSI–Z21.50–1986—Vented Decorative Gas Appliances.
ANSI–Z21.52–1971—Gas-Fired Single Firebox Boiler, and Addenda Z21.52a–1973.
ANSI–Z21.54–1979—Gas Hose Connectors for Portable Outdoor Gas-Fired Appliances, and Addenda Z21.54a–1983, Z21.54b–1985.
ANSI–Z21.55–1979—Gas-Fired Sauna Heaters, and Addenda Z21.55a–1980, Z21.55b–1981.
ANSI–Z21.56–1986—Gas-Fired Pool Heaters.
ANSI–Z21.57–1982—Recreational Vehicle Cooking Gas Appliances, and Addenda Z21.57a–1982, Z21.57b–1984.
ANSI–Z21.58–1987—Outdoor Cooking Gas Appliances.
ANSI–Z21.59–1974—Gas-Fired High Pressure Steam and Hot Water Boilers.
ANSI–Z21.60–1981—Decorative Gas Appliances for Installation in Vented Fireplaces, and Addenda Z21.60a–1982, Z21.60b–1984.
ANSI–Z21.64–1985—Direct Vent Central Furnaces, and Addenda Z21.64a–1986, Z21.64b–1987.
ANSI–Z21.65–1978—Separated Combustion System Central Furnaces.
ANSI–Z83.2–1977—Gas Atmosphere Generators.
ANSI–Z83.3–1971—Gas Utilization Equipment in Large Boilers, and Addenda Z83.3a–1972, Z83.3b–1976.
ANSI–Z83.6–1982—Gas-Fired Infrared Heaters, and Addenda Z83.6a–1984, Z83.6b–1985.
ANSI–Z83.7–1974—Gas-Fired Construction Heaters.
ANSI–Z83.8–1985—Gas Unit Heaters, and Addenda Z83.8a–1986.
ANSI–Z83.9–1986—Gas-Fired Duct Furnaces.
ANSI–Z83.11–1986—Gas Food Service Equipment—Ranges and Unit Broilers.
ANSI–Z83.12–1986—Gas Food Service Equipment—Baking and Roasting Ovens.
ANSI–Z83.13–1986—Gas Food Service Equipment—Deep Fat Fryers.
ANSI–Z83.14–1986—Gas Food Service Equipment—Counter Appliances.
ANSI–Z83.15–1986—Gas Food Service Equipment—Kettles, Steam Cookers and Steam Generators.
ANSI/UL 710–1981—Grease Extractors for Exhaust Ducts.
UL 795–1973—Commercial-Industrial Gas-Heating Equipment, February 1982 Revision.
ANSI/NFiPA 211–1984—Chimneys, Fireplaces and Vents.
RS 15-4
ANSI/ASTM C 315 1978c—Specifications for Clay Flue Linings (Reapproved 1983).
RS 15-6
ANSI/ASTM C 64 1972—Specifications for Refractories for Incinerators and Boilers (Reapproved 1977).
ANSI/ASTM C 105–1947—Specifications for Ground Fireclay as a Refractory Mortar for Laying Up Fireclay Brick (Reapproved 1981).
RS 15-7
ANSI/ASTM C 64 1972—Specifications for Refractories for Incinerators and Boilers (Reapproved 1977).
RS 15-8[A]
ANSI/UL 103–1988—Standard for Chimneys, Factory-Built, Residential Type and Building Heating Appliances (February 1989 Revision).
RS 15-9
UL 103 Type HT–1988—Standard for Low Heat Appliance Chimneys With High Temperature Tests Added (February 1989 Revision).
RS 15-10
ANSI/UL 959–1986—Standard for Medium Heat Appliance Factory-Built Chimneys (August 1988 Revision).
RS 15-11
Factory-built Chimneys, 1400 Degrees Fahrenheit.
1. Application. Factory-built 1400 degree Fahrenheit chimneys are intended for venting fuel gases, at a temperature not exceeding 1400 degrees Fahrenheit under continuous operating conditions, from building heating appliances and other low heat appliances as specified in the Chimney Selection Chart of the National Fire Protection Association Standard No. 211.
2. Installation. These chimneys are to be installed in accordance with the installation instructions provided with each chimney assembly. They are not to be enclosed within combustible construction, but an interior chimney is to be enclosed in a noncombustible fire resistant shaft of appropriate size and rating where the chimney extends through any story of a building above that in which the connected appliance is located. An unenclosed chimney may be placed adjacent to walls of combustible construction at the clearances specified for each chimney section in the individual listing and acceptance and in article 15 of this code.
3. Chimney system. Each 1400 degree Fahrenheit factory-built chimney consists of one or more chimney sections, a chimney cap, lateral supports, thimble and flashing assembly as needed and other parts as specified in the installation instructions provided with each chimney system.
4. Standards. The equipment shall comply with the following standards:
ANSI/UL 103–1988—Standard for chimneys, factory-built, residential type and building heating appliances (February 1989 revision).
ANSI/UL 959–1986—Standard for medium heat appliance factory-built chimneys.
5. Identification. Equipment listed and accepted by this standard shall be identified with the following: "1400 Degree Fahrenheit Chimney Part".
RS 15-14
ANSI/NFiPA 211–1988—Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances.
RS 15-15
UL 127–1988—Standard for Factory-Built Fireplaces, as Modified.
MODIFICATIONS—The provisions of UL 127–1988 shall be subject to the following modifications:
1.6 These requirements also cover fixed blowers and other electrical accessories for factory-built fireplaces, rated at 600 volts or less, and intended to be employed in ordinary locations in accordance with the New York City Electrical Code.
1.7 The factory-built chimneys servicing factory-built fireplaces covered by these requirements shall be installed only in buildings in residential occupancy groups J-2 and J-3 not more than forty feet or three stories in height when used with a 1700 degree Fahrenheit chimney.
RS 16. PLUMBING AND GAS PIPING [Repealed]
(Repealed City Record 9/18/2017, eff. 10/18/2017)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058, L.L. 1989/100, L.L. 1993/013, L.L. 1995/074, L.L. 1995/089, L.L. 1996/065, L.L. 1997/071, and L.L. 1999/010.
RS 17. FIRE ALARMS, DETECTION AND EXTINGUISHING EQUIPMENT
List of Referenced National Standards RS 17–1 Standpipe System Construction. RS 17–2 Installation of Sprinkler Systems. RS 17–2A Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height. RS 17–2B Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes. RS 17–3 Installation of Fire, Sprinkler, Standpipe Smoke Detection, Oxygen, Nitrous Oxide, and other Alarm and Extinguishing Systems. RS 17–3A Installation of Class E, Class C and Class J Fire Alarm Signal Systems. RS 17–3B Installation of Modified Class E and Modified Class J Fire Alarm Signal Systems. RS 17–3C Installation of Visual and Auxiliary Alarms Required by § 27-292.15. RS 17–4 Water Cooling Towers. RS 17–5 National Fire Alarm Code. RS 17–5E Automatic Fire Detectors. RS 17–6 Cast-Iron Threaded Fittings, Class 125 and 250. RS 17–6A Valves and Related Products for Fire Protection Service. RS 17–7 Grey Iron and Ductile-Iron Fittings 3-inch Through 48-inch for Water and Other Liquids. RS 17–8 Rubber Gasket Joints for Ductile-Iron and Grey-Iron Pressure Pipe and Fittings. RS 17–9 Pipe Fittings for Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperatures. RS 17–10 Water Tanks for Private Fire Protection. RS 17–11 Single and Multiple Station Smoke Detectors. RS 17–12 Household Fire Warning Equipment. RS 17–13 Single and Multiple Station Carbon Monoxide Detectors. RS 17–14 Installation of Household Carbon Monoxide (CO) Warning Equipment.
LIST OF REFERENCED NATIONAL STANDARDS
ANSI/NFiPA No. 13—Standard for the Installation of Sprinkler System, as Modified—1989
ANSI/NFiPA No. 13R—Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height—1994
ANSI/NFiPA No. 13D—Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes—1994
ANSI/NFiPA No. 214—Standard for Water-Cooling Towers—1988
ANSI/NFPA No. 72—National Fire Alarm Code—1993
ANSI/ASME B16.4—Cast-Iron Threaded Fittings, Class 125 and 250—1985
UL No. 193—Alarm Valves for Fire-Protection Service (Revision 9/88)—1988
UL No. 260—Dry Pipe and Deluge Valves for Fire Protection Service—1988
UL No. 262—Gate Valves for Fire-Protection Service—1988
UL No. 312—Check Valves for Fire-Protection Service (Revision 10/89)—1988
UL No. 668—Hose Valves for Fire-Protection Service—1988
UL No. 753—Alarm Accessories for Automatic Water-Supply Control Valves for Fire-Protection Service (Revision 8/89)—1989
UL No. 789—Indicator Posts for Fire-Protection Service (Revision 3/89)—1987
UL No. 1091—Butterfly Valves for Fire-Protection Service—1986
UL No. 1468—Direct-Acting Pressure-Reducing and Pressure-Control Valves for Fire-Protection Service—1985
UL No. 1486—Quick Opening Devices for Dry Pipe Valves for Fire-Protection Service (Revision 7/85)—1979
UL No. 1726—Automatic Drain Valves for Standpipe Systems (Revision 9/88)—1985
UL No. 1739—Pilot-Operated Pressure-Control Valves for Fire-Protection Service—1988
ANSI A21.10/AWWA C110—Ductile-Iron and Grey-Iron Fittings, 3-inch Through 48-inch, for Water and Other Liquids—1987
ANSI A21.11/AWWA C111—Rubber Gasket Joints for Ductile-Iron and Grey-Iron Pressure Pipe and Fittings—1985
ANSI/ASTM A 234—Specification for Pipe Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperatures—1988
ANSI/NFiPA No. 22—Standard for Water Tanks for Private Fire Protection—1987
UL No. 217—Single and Multiple Station Smoke Detectors including Revision of February 19, 1989—1989
ANSI/NFiPA No. 74—Standard for the Installation, Maintenance, and Use of Household Fire Warning Equipment, as Modified—1989
ANSI/NFiPA No. 20—Installation of Centrifugal Fire Pumps—1990
ANSI/NFiPA No. 231—Standard of Indoor General Storage—1990
ANSI/NFiPA No. 231C—Standard for Rack Storage of Materials—1986
ANSI/NFiPA No. 20—Installation of Centrifugal Fire Pumps—1990
ANSI/NFiPA No. 231—Standard of Indoor General Storage—1990
ANSI/NFiPA No. 231C—Standard for Rack Storage of Materials—1986
RS 17-1. STANDPIPE SYSTEM CONSTRUCTION
This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 17-1 at American Legal Publishing.
1. MATERIALS FOR STANDPIPE SYSTEMS.—
(a) Pipe.—
(1) Pipe for standpipe systems shall be in accordance with table RS 17–1–1, and shall conform to the standards of table RS 16–1, of reference standard RS-16.
(2) Pipe for buried sections of the standpipe system, whether inside or outside of the building, shall be red brass, type "TP" threadless copper, hard temper type "K" copper tubing, galvanized wrought iron, galvanized steel, cast iron, or equivalent material. All such pipe, other than cast iron, shall be adequately wrapped or otherwise protected against corrosion.
(3) The name of the manufacturer and the pressure to which the pipe was tested shall be permanently and legibly indicated on all pipe used in standpipe systems.
(4) Only new pipe shall be used in standpipe system.
(b) Fittings.—
(1) Fittings used in standpipe systems above ground shall be malleable cast iron or cast steel conforming to reference standard RS 17–6.
(2) Fittings used in standpipe systems underground shall be cast iron conforming to reference standard RS 17–7 or RS 17–8.
(3) Pressure ratings shall be cast in or on the fittings. (See table RS 17–1–1 for required ratings.)
(4) Fittings used in standpipe systems that are of welded construction shall be of a type for welding purposes conforming to reference standard RS 17–9.
(5) Approved mechanical joint couplings may be used in the standpipe system. Fittings used in conjunction with the coupling shall be designed for use with the coupling.
(c) Valves.—
(1) Valves and related products used in fire protection shall be approved and comply with reference standard RS 17–6A.
(2) O. S. & Y. indicating valves (with indicator readily visible from the floor) shall be provided to permit any riser or other section to be shut off while remaining risers or sections continue in use. Valves shall be flanged, mechanically coupled, or wafer type and with bodies of cast iron, ductile iron cast steel or approved equivalent material having nonferrous metal seat rings. See Table 17–1–1 for required ratings and Figures RS 17–1–1 and RS 17–1–2 for valve locations.
TABLE RS 17–1–1 Required Ratings of Pipe, Fittings and Valves in Standpipe Systems for Various Heights of Buildings c, d
Distance from Upper Tank Check to 1st Floor or Fire Pump (ft.) Class of 2 1/2 Hose Outlet Valves Type of Pipe Fittings (wwp in psi) Check and Gate Valves (wwp in psi) 0 to 115 A a Schedule 10 or 40 carbon steel 300 175 115 to 270 A a Schedule 10 or 40 carbon steel 300 250 270 to 425 B b Schedule 40 carbon steel 350 350 425 to 657 B b Schedule 40 carbon steel 500 500 625 to 1,112 B b Schedule 80 carbon steel 800 800 1,112 and over B b Schedule 80 carbon steel 1,000 1,000
Notes.—
a For installation in buildings not exceeding 300 ft. in height or the uppermost 300 ft. in taller buildings. Valve shall close tightly against 300 psi normal hydraulic pressure and shall withstand a hydraulic test pressure of 750 psi.
b For installation in the lower portions of buildings exceeding 300 ft. in height. Valve shall close tightly against 400 psi normal hydraulic pressure and shall withstand a hydraulic test pressure at 1,250 psi.
c Six inches and larger section and riser control valves shall have a valved bypass.
d Siamese connections shall be rated for the same pressure as is required for interior fittings and valves.
(3) In single riser systems, or where a single riser extends through an upper portion of the building supplying hose outlet valves more than 150 ft. above the curb level, section valves shall be installed in the single riser at the floor where the single riser starts and at increments of not more than 100 ft. above the first valve. The section valve or valves in the upper section of the riser shall be located so as to divide the riser into increments as shown in figure RS 17–1–1 and RS 17–1–2.
(4) Riser control valves shall, where practicable, be located within a required stair enclosure serving the entrance floor. Where the stair enclosure extends to the basement or cellar, the rise control valve may be located within the stair enclosure at, or in, the basement or cellar ceiling, provided that a sign indicating the valve location is installed within the stair enclosure at the entrance floor. The hose outlet valve for the entrance floor shall be located on the riser side of the riser control valve. Riser control valves shall not be required on a vertical line supplying one or two hose outlet valves.
(5) Where riser control or section valves are located outside of a required stair enclosure, the valves shall be of such type and so installed so as to be remotely operated by either electric motors or hydraulic means. The remote control shall be from either the entrance floor or from the fire pump room. Operating devices shall be grouped, suitably housed, and kept locked with a fire department lock and key. The door of the housing shall be embossed to indicate the purpose of the device. Instructions for operating the remote valves by the control devices shall be legible, detailed, and complete, and shall be permanently secured to the inner face of the door.
(6) Each valve shall be so designed and installed as to permit its manual operation at the valley location. Pressure ratings on the name of the manufacturer shall be cast on, or in, each valve used in the system.
(7) The position of each remotely controlled valve, whether open or closed, shall be indicated at its remote control point and also at the valve.
(8) Valves shall be readily accessible for inspection, repair, and use. If a valve is placed so that its operating mechanism is more than 7 ft. above a floor or stair landing, a 12 in. wide wrought iron, steel or equivalent ladder securely fastened, shall be provided for access to the valve. In lieu of a ladder, chain operated mechanisms are permissible and shall be padlocked securely in place.
(9) Each control valve shall be conspicuously marked with the number assigned to it on the riser diagram for the standpipe system. Metal numbered tags at least 2 in. in diameter shall be securely attached to the valve. Each valve shall have a metal sign stating "STANDPIPE CONTROL VALVE" securely hung from the valve.
(10) Each control valve not remotely controlled shall be sealed with a lock and chain in its normal position. If the normal position is the closed position, a metal placard stating such fact shall be conspicuously attached to the valve.
(d) Check valves.—
(1) Check valves shall be flanged, malleable cast iron or cast steel body having nonferrous metal seat rings and bearings. Swing-type valves shall be installed horizontally in pipes from each siamese hose connection, and in piping from each tank, pump, and city water connection. Spring loaded check valves of the beveled seat type and guided on the top and bottom may be installed in the vertical position on the discharge side of any fire pump.
(2) Check valves other than those in siamese and fire pump lines shall be provided with an indicating shutoff valve that is flanged and bolted to the inlet and outlet of such check valves. The valves on the suction and discharge of the fire pump shall be deemed to comply with this requirement when the discharge valve is placed on the discharge side of the check valve. One of the shutoff valves placed on each side of the tank check valve may be of the remote control type, and when used, shall be on the downstream side of such check valve.
(e) Supports.—Piping in standpipe systems shall be adequately supported by clamps, hangers, or other supporting devices.
2. SIAMESE CONNECTIONS.—
(a) Design and construction.—
(1) Siamese hose connections shall have a clapper valve in each outlet branch unless such connection is at the shore end of a standpipe system also supplied by a siamese hose connection of the type specified for fireboat use.
(2) Siamese connections for fireboat use shall have two 3 1/2 in. swivels with fire department female threads. All other siamese hose connections, except those of the shore end type, shall have two 3 in. swivels with fire department female threads.
(3) All shore end siamese connections shall have 3 in. male hose threads and shall be subject to the approval of the fire department. In lieu of a check valve, each branch may have a drip and a long stem valve, which shall be placed within the structure or otherwise protected against freezing. No siamese connections provided for fireboat use shall be installed in any standpipe system whose water supply is taken from the city water mains.
(b) Marking.—Each siamese connection shall be provided with caps painted red, and shall have the word "Standpipe" in letters 1 in. high and 1/8 in. deep cast in the body or on a non-ferrous metal plate secured to the connections or mounted on the wall in a visible location, except that caps of each siamese connection used for combination standpipe and sprinkler systems shall be painted yellow and the words shall read "COMBINATION STANDPIPE AND SPRINKLER SYSTEMS."
(c) Location.—
(1) Siamese connections shall be placed between 18 in. and 36 in. above the sidewalk level.
(2) Siamese connections shall be of the flush or free standing type and, with the exception of the swivel caps, shall not project beyond the street line. The riser pipe to a free standing siamese connection shall be red brass. When siamese connections are installed in wall recesses, the recesses shall be of ample size to permit the convenient hose attachment.
(d) Check valve.—Each siamese connection shall be provided with a check valve inside of the building or in a valve pit outside of the building.
(e) Drip valve.—A 3/4 in. automatic ball drip valve shall be placed between the siamese connection and the check valve, except that on a fireboat siamese connection, a 1/2 in. open drip without a shutoff may be used. Automatic ball drips shall be placed in the horizontal position.
3. HOSE STATIONS.—
(a) Hose outlet valves.—
(1) On each floor at each riser, the required 2 1/2 in. angle hose valve shall be of a class as indicated in table RS 17–1–1.
(2) At the top of the highest riser there shall be provided, above the main roof level, a three-way manifold equipped with three 2 1/2 in. hose valves with hose valve caps. The lowest valve shall be located with the hose end at least 18 in. above the roof and the highest valve with the hose end not more than 60 in. above the roof. The manifold may be set in a horizontal or vertical position, provided the hose outlets are set between 18 in. and 60 in. above the roof level.
(3) Where the manifold is located other than within a heated stair enclosure, the control valve shall be located in a horizontal run of piping below the roof, with a long stem extending through the roof and equipped with a wheel handle at its upper end at least 12 in. above the roof. Between the control valve and the manifold there shall be provided within the heated space a 1/2 in. open drip or a 3/4 in. automatic ball drip, with the drip pipe extended to spill over a plumbing fixture or drain.
(b) Stations within stair enclosures.—
(1) In occupancies where a 2 1/2 in. fire hose is mandatory, the hose shall be connected to the 2 1/2 in. hose valve within the stair enclosure.
(2) In occupancies where 1 1/2 in. fire hose is permitted, a 2 1/2 in. x 1 1/2 in. brass or bronze non-swivel reducing coupling shall be attached to the 2 1/2 in. hose valve, or an auxiliary hose station may be provided.
(c) Branch sizes to hose stations.—
(1) The branch size shall be predicated on the developed length from the riser or cross connection to the required 2 1/2 in. hose valve station as follows:
Up to 4 ft.—2 1/2 in.
Over 4 ft.—3 in. to 25 ft.
Over 25 ft.—4 in.
(2) No valve shall be placed between the hose station valve and the riser or cross connection, except that on branches that serve three or more hose stations, a valve shall be provided at the riser or cross connection.
(3) Not more than one hose outlet shall be supplied from a 2 1/2 in. or 3 in. branch.
(d) Auxiliary hose stations branch size.—
(1) Branch piping from the required riser to an auxiliary hose station may be 2 1/2 in. I.P.S., and no valve shall be installed in the branch pipe with the exception of the 1 1/2 in. hose valve at the auxiliary hose station.
(e) Size, type and quality of hose.—
(1) At each hose station, hose shall be provided of a size, type and quality as required by the provisions of the building code.
(f) Nozzles.—
(1) Nozzles on 2 1/2 in. hose, except hose for yard hydrants, shall be at least 15 in. in length, and shall have a smooth bore with a 1 in. or 1 1/8 in. discharge orifice.
(2) Nozzle for hose used on yard hydrant systems shall be equipped with a playpipe conforming the requirements of the fire department.
(3) Nozzles on hose at auxiliary hose stations shall be approved adjustable combination fog nozzles. Where 1 1/2 in. hose is within the stair enclosure, the nozzle may be a 1/2 in. smooth bore nozzle at least 12 in. in length or an adjustable combination fog nozzle.
(g) Hose and valve cabinets.—
(1) When the hose is kept in a cabinet, such cabinet shall be equipped with a single swinging door that shall have an 8 in. high panel of clear wired glass at the level of the hose valve and rack. The door width shall be the full inside width of the cabinet, and the glass panel shall be at least 90 per cent of the width of the door. Where an extinguisher or other appurtenances are installed with the cabinet, the door shall have a clear wired glass panel the full 90 per cent of the door area.
(2) The hose valve within a stair enclosure may be kept in a cabinet. Such cabinet shall be equipped with a single swinging door that shall have a clear wired glass panel 90 per cent of the door area. The valve shall be placed in the cabinet to permit coupling of 2 1/2 in. hose to the valve without causing kinks in the hose.
(3) Each cabinet shall be readily accessible and the door shall be kept unlocked.
(4) Cabinets may have solid metal doors when located in the entrance hall of a building. All such hose cabinets or closets shall be permanently marked "FIRE HOSE" across the door panel in red letters at least 1 in. high, and shall not be used for any other purpose but concealing the hose station.
(h) Hose rack.—
(1) The hose at each outlet shall be kept upon a hose rack firmly supported and placed between 5 ft. and 6 ft. 6 in. above the floor or landing.
(2) The use of dump or reel type racks is prohibited.
4. TANKS IN STANDPIPE SYSTEM.—
(a) Construction and support of tanks.—Tanks for the standpipe system supply shall be constructed and supported in accordance with the provisions of reference standard RS 16, reference standard RS 17–2, and applicable provisions of the building code for loads and structural work.
(b) Combination tanks.—gravity tanks may be used to provide the required primary water supply to the standpipe system and/or domestic water in a building provided all the following conditions are met.
(1) The connections to the tank are made in such manner as to provide the required sprinkler and/or fire standpipe reserve. The domestic supply is above the sprinkler and/or standpipe reserve. The standpipe reserve is above the sprinkler reserve. Where a standpipe riser is used to supply water to sprinklers in buildings classified in occupancy group E, 100 feet or more in height, and in existing office buildings, 100 feet or more in height, the connection to the tank shall be made in such a manner as to provide the required sprinkler or standpipe reserve, whichever is greater.
(2) The connections to the system are made outside of the tank. When connections or piping are installed inside the tank, the piping shall be assembled without couplings and shall be of red brass.
(3) The tank is filled by means of an automatic pump at a rate of not less than 65 gpm.
(c) Filling of tanks.—
(1) Pressure or gravity tanks shall be filled at the rate of at least 65 gpm. Pipes used to fill the tanks shall not be used for any other purpose; nor shall required fire-pumps be used for filling purposes.
(2) Where there is sufficient pressure in the city water main to fill tanks at the required rate during all hours of each day, and a filling pump is not provided, the connection to the city water supply shall be made near the point where the city water service enters the building.
(3) A combined fire standpipe reserve and domestic water tank shall only be filled by direct public water connection or separate fill pumps, or direct connection to equipment, or pumps used to supply domestic water systems in accordance with Reference Standard RS 16.
(d) Emergency drains on standpipe tanks.—Each standpipe tank shall be provided with a drain of at least 4 in. size. Each drain pipe shall be controlled by a manually operated outside screw and yoke type valve located so as to be readily accessible. The drain shall be installed in accordance with the provisions of reference standard RS 16.
(e) Heating of standpipe tanks.—
(1) Where the water in the tank is subject to freezing, the tank shall be equipped with a tank heater in accordance with the provisions of reference standard RS 17–10.
(2) Where both the standpipe supply and domestic water supply are combined in a single tank, heating of such tank shall not be required in hotels, multiple dwellings, hospitals, or other occupancies where the domestic supply is drawn upon during all hours of every day of the week.
(f) Strainer.—
(1) Every standpipe gravity or suction tank shall be provided with a brass or bronze strainer at the discharge to risers or to pump supply lines.
(2) Each strainer shall have clear openings with an aggregate area equal to, or more than, the required area of the pipe into which the tank discharges. Openings shall be not more than 1 in. nor less than 1/2 in. in diameter.
(g) Overflow pipe for standpipe tanks.—Each gravity standpipe tank shall be provided with an overflow in accordance with the provisions of reference standard RS 16.
(h) Access to standpipe tanks.—Access to the top of each gravity tank shall be by means of a steel or wrought iron gooseneck ladder, constructed of flat side bars at least 2 in. by 3/8 in. or equivalent, spaced at least 14 in. apart, with round or square rungs at least 5/8 in. thick spaced not more than 12 in. on centers. The ladder shall be rigidly braced, and shall not tip outward from the vertical at any point. When ladders exceed 25 ft. in height, body irons spaced not more than 2 ft. on center and an iron platform at least 14 in. square, rigidly secured to the stringers of the ladder or other type of enclosed safe access, shall be provided near the top of the tank.
(i) Tank alarms for standpipe systems.—
(1) Gravity tanks not filled by an automatic pump or by city pressure shall be equipped with a high and low water level electrical alarm system.
(2) All pressure tanks used to provide the required primary water supply of a standpipe system shall be equipped with a high and low air pressure and a high and low water level electrical alarm system. Air-to-water ratio shall be 1 to 2 and shall be maintained by automatic electrical controls.
5. FIRE PUMPS IN STANDPIPE SYSTEMS.—
(a) Installation of Standpipe fire pumps.—
(1) Firepumps shall be placed on concrete (foundations) pads at least 12" above the pump room floor level with a clearance of at least 3' shall be maintained on all sides of the pad from walls or from other equipment in the pump room. In the event of the use of a vertical shaft centrifugal fire pump, the 12" high concrete pad may be omitted, provided the bottom of the electric driving motor and all electric appurtenances are raised at least 12" above the pump floor.
(2) The control of the manual fire pump shall be designed to operate at predetermined speeds to give pressure increments of 50 psig. The first step of the starter shall produce 100 psig at the pump, and each succeeding step shall produce increments of 50 psig up to the required pump pressure.
(3) Each automatic fire pump shall be equipped with a 3 in. pressure relief valve installed in the pump discharge. Such relief valve shall be set to relieve below the shutoff head of the pump, but above the pressure required to maintain the operating pressure at the highest hose valve. The discharge from the relief valve may be piped back into the suction side of the pump on the pump side of the suction valve provided a visual sight glass is installed in the discharge of the relief valve. Automatic fire pumps may be provided with a time delay switch to insure a minimum running time for the pump.
(4) Each manually operated fire pump shall be equipped with a 3 in. pressure relief valve for 500 gpm pumps and a 4 in. pressure relief valve for 750 gpm pumps. The relief shall be installed in the pump discharge line and set to relieve at a pressure not to exceed 15 lb. over the pressure required to deliver the rated capacity of the pump at the highest hose outlet. Discharge of the relief valve may be piped back into the suction side of the pump on the pump side of the suction valve provided a visual sight glass is installed in the discharge of the relief valve.
(5) Each manually operated fire pump shall also be equipped with a test valve installed in the pump discharge line that may be connected to the discharge side of the relief valve if the discharge pipe is piped back to the suction side of the pump as provided in (4) above. The size of the test line shall be 3 in. for a 500 gpm pump and 4 in. for a 750 pgm pump.
(6) The check valves in the pump discharge shall be either swing type or spring loaded.
(b) Wiring for fire pumps.—
(1) When the fire pump feeder conductors are routed through the building(s), they shall be enclosed by two (2) inches of concrete or shall be listed electrical circuit protective systems with a minimum of one-hour fire resistance.
RS 17-2
This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 17-2 at American Legal Publishing.
[Standard for the Installation of Sprinkler Systems]
ANSI/NFiPA No. 13–1983—Standard for the Installation of Sprinkler Systems.
MODIFICATIONS—The provisions of NFiPA No. 13–1989 shall be subject to the following modifications. The section and paragraph numbers are from that standard.
CHAPTER 1—GENERAL INFORMATION
1–1 Delete.
1–4 Delete.
1–6 Delete.
1–7 Classification of Occupancies.
Add 1–7.5 For purposes related to sprinkler installation, classification of occupancies in Paragraphs 1–7.2.1, 1–7.3.1, 1–7.3.2, 1–7.3.3 and 1–7.4.1 shall be considered as equivalent to classifications of buildings and spaces in the building code as follows:
Light Hazard—E, G, H-1, H-2, J-1, J-2, J-3.
Ordinary Hazard—B-1, B-2, D-1, D-2, C, F-1, F-3, F-4.
Extra Hazard—A.
1–9 Delete.
1–10 Delete.
1–11.1 Delete.
1–11.2 Delete except for 1–11.2.4 and 1–11.2.5
1–11.3 Delete.
1–12 Delete.
CHAPTER 2—WATER SUPPLIES
2–1 Delete.
Revise table 2–2.1 (A) to read as follows:
TABLE 2–2.1 (A) Guide to Water Supply Requirements for Pipe Schedule Sprinkler Systems
Occupancy Classification Residual Pressure Required (See Note 1) Acceptable Flow at Base of Riser (See Note 2) Duration in Minutes (See Note 3) Light Hazard 15 psi 500– 750 gpm 30 (Note 4) Ordinary Hazard (Group 1) 15 psi or higher 700–1,000 gpm 30 Ordinary Hazard (Group 2) 15 psi or higher 850–1,500 gpm 30 Ordinary Hazard (Group 3) Pressure and flow requirements for sprinklers and hose streams to be determined from Table 2–2.1 (B). 30 Warehouses Pressure and flow requirements as determined by Chapter 7 and subject to Commissioner's approval. High-Rise Buildings Pressure and flow requirements for sprinklers in accordance with Chapter 8. Woodworker's Shop See Appendix A Pressure and flow requirements subject to Commissioner's approval. Extra Hazard Pressure and flow requirements subject to Commissioner's approval.
Notes:
1. The pressure required at the base of the sprinkler(s) is defined as the residual pressure required of the elevation at the highest sprinkler plus the pressure required to reach this elevation.
2. The lower figure is the minimum flow ordinarily acceptable for pipe schedule sprinkler systems. The higher flow should normally suffice for all cases under each group.
3. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
4. In existing buildings only, the Commissioner may authorize reduction of storage to 20 minutes provided there are provisions for acceptable mechanical automatic means of makeup to the storage tank.
5. Where the water supply to a system sized in accordance with the pipe sizing schedules is taken from a water storage tank, the adequacy of the tank capacity shall be verified with a hydraulic calculation.
6. This occupancy classification shall apply when the warehouse contains high-piled or rack storage as defined in section 4–1.3.8 and complies with the requirements of NFiPA 321 and 231C.
The following conditions should be met for determining acceptable means for makeup:
a) Automatic means of makeup for a tank fire reserve should be capable of pumping water into the tank at a rate, for a period of 20 minutes, sufficient to equal the difference between the normal 30-minute demand and the alternate 20-minute demand. The demand required is established by calculations for the "most demanding remote area from the riser as shown by examples of Appendix A of NFiPA 13–1989 and as now determined for the 30-minute demand.
b) There should be at least two (2) automatic means of makeup, each having the same capacity, so that in the event a unit must be removed for repairs the other unit can be placed in service.
c) An approved low water alarm is to be provided and located at a point 500 gallons above the available fire reserve level.
5. Where the water supply to a system sized in accordance with the pipe sizing schedules is taken from a water storage tank, the adequacy of the tank capacity shall be verified with a hydraulic calculation.
6. This occupancy classification shall apply when the warehouse contains high-piled or rack storage as defined in Section 4–1.3.10 and complies with the requirements of NFiPA 231 and 231C.
Delete Table 2–2.1 (b) in its entirety, except for Density Curves and add the following:
TABLE 2–2.1.1(b) Table and Design Curves for Determining Density, Area of Sprinkler Operation and Water Supply Requirements for Hydraulically Designed Sprinkler Systems Minimum Water Supply Requirements
Hazard Classification Sprinklers Only—gpm Duration in Minutes (See Notes 1, 2, & 3) Light See 2–2.1.3 30 Ord.—Gp. 1 See 2–2.1.3 40 Ord.—Gp. 2 See 2–2.1.3 40 Ord.—Gp. 3 See 2–2.1.3 40
For SI Units: 1 gpm = 3.785 L/min.
________________________________________
Notes:
1. In existing buildings only, the Commissioner may authorize reduction of storage to 20 minutes provided there are provisions for acceptable mechanical automatic means of makeup to the storage tank. Where 20 minutes storage cannot be achieved with existing storage facilities, alternative means of supply may be considered by the Commissioner. In any event, no fire reserve storage facility shall have less than 3500 gallons.
2. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
3. In no case shall existing sprinkler storage capacities be reduced to less than the amount required for comparable new construction.
4. In fully sprinklered buildings the storage capacity of the fire reserve in the tank shall be as required for the sprinkler demand, but shall not be less than 3500 gallons in buildings with a single fire standpipe riser nor less than 5000 gallons in buildings with multiple fire standpipe risers.
5. Storage in light hazard occupancies where not more than 15 percent of the building is of ordinary hazard may have storage capacity predicated on light hazard occupancy.
The following conditions should be met for determining acceptable automatic means of makeup:
a) Automatic means of makeup for a tank fire reserve should be capable of pumping water into the tank at a rate, for a period of 20-minutes, sufficient to equal the difference between the normal 30-minute demand and the alternate 20-minute demand. The demand required is established by calculations for the most demanding remote area from the riser as shown by examples of Appendix A of NFiPA 13–1989 and as now determined by the 30-minute demand.
b) There should be at least two (2) automatic means of makeup, each having the same capacity, so that in the event that a unit must be removed for repairs the other unit can be placed in service.
c) An approved low water alarm is to be provided and located at a point 500 gallons above the fire level reserve.
2. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
3. In no case shall existing sprinkler storage capacities be reduced to less than the amount required for comparable new construction.
4. In fully sprinklered buildings the storage capacity of the fire reserve in the tank shall be as required for the sprinkler demand, but shall not be less than 3500 gallons in buildings with a single fire standpipe riser nor less than 5000 gallons in buildings with multiple fire standpipe risers.
5. Storage in light hazard occupancies where not more than 15 percent of the building is of ordinary hazard may have storage capacity predicated on light hazard occupancy provided that any such space shall not exceed 5,000 square feet in area.
2–2.4.1 to 2–2.4.6 Delete Except 2–2.4.3
2–3 Connections of Water Works Systems.
2–3.1.2 Delete.
2–4 Gravity Tanks.
2–4.2 Add an additional sentence to read as follows: "If any of the sprinkler heads are supplied from domestic water tanks, the combined water supply in the tank shall be at least 5,000 gallons. Further, that the sprinkler supply shall be taken from the lowest level of the tank."
Add 2–4.3 Combined Use. In E, F, G, H and J Occupancies, with only limited ordinary hazard areas, the sprinkler and standpipe reserve may be common to both. Reserve shall be sized for whichever demand is the greater.
Interpretation:
Limited, may be defined as less than 30% of a floor area.
Add 2–4.3.1 Buildings whose occupancies are more than 85 percent light hazard, may have a light hazard water supply provided the ordinary hazard areas are designed for ordinary hazard requirements in respect to sprinkler spacing and pipe sizing.
Add 2–4.3.2 Combined standpipe and sprinkler systems may be used in D-2 Laboratory Occupancies, E, F, G, H and J. If an automatic fire pump is used as the primary supply, the requirements of 2–5.3 shall be complied with.
2–5 Pumps.
Add 2–5.3 Combined Use. In light hazard occupancies with only limited ordinary hazard areas, an automatic fire pump serving the lower 300 feet of the standpipe system may be used as the primary supply to the sprinkler system, provided that a secondary power supply is available to drive the pump; and such power supply shall be automatic switching.
Add 2–5.4 In hydraulically designed sprinkler systems supplied from a gravity tank, the pressure may be increased by means of an automatic, special service fire pump. The pump shall be sized to satisfy the requirements of table 2–2.1 (A) or table 2–2.1 (B) and shall be arranged in a bypass to permit the portion of the system so supplied to be serviced by the system's siamese connections.
(a) The pump need not be supplied from the street side of the building service switch, but the electrical service and pump operation shall be fully supervised. Provided that a secondary power supply is available to drive the pump; and such power supply shall be automatic switching.
2–5.5 Wiring for fire pumps.—When the fire pump feeder conductors are routed through the building(s), they shall be enclosed by two (2) inches of concrete or shall be listed electrical circuit protective systems with a minimum of one-hour fire resistance.
2–6 Pressure Tanks.
Delete 2–6.1 to 2–6.3 and substitute:
2–6.1 Acceptability.
2–6.1.1 A pressure tank in accordance with table 2–2.1 (A) or 2–2.1 (B) is an acceptable water supply source. The total available quantity of water in pressure tanks need not exceed 15,000 gal. when there is a secondary source of water supply available from a gravity tank or a street connection acceptable to the Commissioner of Buildings. The maximum gross capacity of a single pressure tank shall be 9,000 gal.
2–6.1.2 Each tank shall be kept at a maximum of 2/3 full of water and a minimum of 1/3 full of air maintained under a minimum pressure of 75 psig. The water-to-air ratio shall be so proportioned and the tank so located that a minimum pressure of 15 psig will be available on the highest line of sprinklers below the main roof when all the water is being discharged from the tank.
2–6.1.3 The tank supports shall be designed on the basis of the tank being full of water.
2–6.2 The tanks shall be supplied with water through a fixed pipe, independent of the sprinkler piping, and at least 2 inch in size. The water supply and connection shall be capable of supplying the tank at a rate of at least 65 gpm without reducing the pressure in the tank. The tank shall have a fixed water level plate on the end of the tank opposite the gauge glass, or equivalent devices, to indicate the level of the water in the tank.
2–6.3 The air compressor shall be provided with automatic controls for maintaining the air-to-water ratio. The capacity of the compressor shall be sufficient to build up the tank pressure to 75 psig within 3 hr. or less.
2–6.4 Pressure tanks shall be provided with approved closed circuit high and low water and high low air alarms.
2–6.5 Pressure tanks shall be located at or above the top level of sprinklers.
Delete 2–7 and 2–8.
CHAPTER 3—SYSTEM COMPONENTS
3–1.1 Delete.
3–1.1.1 Delete.
3–1.1.4 Delete.
3–1.1.5 Delete.
Add the following, in lieu of the above:
Piping Specifications.
3–1.1 Pipe or tube used in sprinkler systems shall be wrought steel, wrought iron, drawn seamless copper tube or threadless copper pipe.
The chemical and physical properties of wrought steel or wrought iron pipe should be at least equal to those manufactured in accordance with the specifications of the American Society for Testing and Materials for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Ordinary Uses, ANSI/ASTM Designation A 120–77; or for Welded Wrought-Iron Pipe, ASTM Designation A 72–68. Dimensions for wrought steel or wrought iron pipe should be in accordance with the American Standard for Wrought Steel and Wrought Iron Pipe, ANSI B36.10–1979. Pipe used in sprinkler systems should be designed to withstand a working pressure of not less than 175 psi. It is intended that this sprinkler standard permit the use of "standard wall" pipe as described in ANSI B36.10–1979 for pressure up to 300 psi. Schedule 40 pipe is considered "standard wall" pipe. Schedule 30 pipe is acceptable in sizes 8 inch and larger. However, "light wall," schedule 10 pipe is acceptable in sizes 8 inch and smaller, provided such pipe is Approved by the Board of Standards and Appeals for working pressure of not less than 175 psi.
Tube or threadless pipe used in sprinkler systems shall be drawn seamless copper tube or threadless copper pipe conforming to the chemical and physical properties of one of the following standards issued by the American Society for Testing and Materials:
Seamless Copper Tube ANSI/ASTM B 75–79
Seamless Copper Water Tube ANSI/ASTM B 88–76
General Requirements for Wrought Seamless Copper and Copper-Alloy Tube ANSI/ASTM B 251–76
Threadless Copper Pipe ANSI/ASTM B 302–76
Copper Tube or threadless pipe used in sprinkler systems as specified in the above standards shall be limited to wet systems for light and ordinary hazard occupancies using sprinkler heads having 165 F. rating or less, and shall have minimum wall thicknesses capable of withstanding a working pressure of not less than 175 psig at a service temperature of 300 F. for both annealed and drawn tempers. Copper Water Tube Types K and L ANSI/ASTM B 88–76 and Threadless Copper Pipe Type TP (ANSI/ASTM B 302–76) are acceptable.
Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency and acceptable to the Commissioner. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.,
1. Pressure rating.
2. Beam strength (hangers).
3. Corrosion (chemical and electrolytic).
4. Resistance to failure when exposed to elevated temperatures.
5. Methods of joining (strength, permanence, fire hazard).
6. Availability of fittings (for sprinkler outlets and proper routings).
7. Toxicity.
3–1.1.5 Delete, and substitute the following:
3–1.1.5 Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency acceptable to the Commissioner. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.
1. Pressure rating
2. Beam strength (hangers)
3. Corrosion (chemical and electrolytic)
4. Resistance to failure when exposed to elevated temperatures
5. Methods of joining (strength, permanence, fire hazard)
6. Availability of fittings (for sprinkler outlets and proper routings)
7. Physical characteristics related to integrity during earthquakes.
8. Toxicity
9. Combustibility
10. Movement during sprinkler operation (water distribution).
3–2 Definitions. Add the following: Fire Section—See subarticle 201.0. Each floor of a sprinklered building may be considered a fire section.
Add 3–3.4.1 In altering existing sprinkler systems which contain 3/4-inch pipe, the existing 3/4-inch pipe may be retained except that extension from such 3/4-inch pipe shall be made using pipe having a minimum diameter of one-inch.
3–3.7 One and One-Half-Inch Hose Connections. Delete.
3–3.8 Hose Connections For Fire Department Use. Delete.
Add the following in lieu of the above:
3–3.7 Fire Standpipe Hose Connections. Where permitted in E, F, G, H and J occupancies by Section 2–4.3, and where permitted by the Commissioner, the sprinkler systems may be connected to the distribution system of mains and risers serving the required standpipe hose connections. Connections to the common sprinkler and standpipe systems shall be valved and fitted with an approved supervised tamper switch and flow detector.
3–3.1 Delete the first sentence and add the following:
"The maximum floor area to be protected by a single riser, from a control and alarm device, on any one floor shall be as follows:"
3–4 Pipe Schedules.
3–4.1.1 Delete—Add the following:
3–4.1.1 A test pipe of not less than 1-inch diameter terminating in a smooth bore corrosion resistant outlet giving a flow equivalent to one sprinkler shall be provided. This test pipe shall be provided for each system through a pipe not less than 1-inch in diameter, in the upper story, and the connection should preferably be piped from the end of the most remote branch line. The discharge should be at a point where it can be readily observed. In locations where it is not practical to terminate the test pipe outside the building, the test pipe may terminate in a drain. In this event, the test connection shall be made using an approved sight test connection containing a smooth bore corrosion resistant orifice giving a flow equivalent to one sprinkler. The test valve shall be located at an accessible point, and preferably not over seven feet above the floor. The control valve on the test connection shall be located at a point not exposed to freezing.
Add 3–4.4.1 In buildings having mezzanine floors, large platforms, or large openings between floors which cannot be closed or satisfactorily cut off, the possibility that all or most of the sprinklers might be opened by a single fire should be considered in determining the size of risers. Where occupancy and construction are exceptionally good and where there is little likelihood of a fire spreading beyond the vicinity of its origin, the size of the feed main should be based on the total number of sprinklers in the main area plus half the number in the area not cut off. A sprinkler water curtain may be considered an exceptionable cut off for openings of less than 1,000 square feet.
Add 3–4.6 Sizes for Domestic Water Piping. Where permitted by the building code, 10 or less heads, that are connected to the domestic water system shall have the piping sized in accordance with the tables herein and the domestic water line to which the sprinkler line connected thereto. Connections may be made directly to cross-connections or headers.
3–6.2.3 Delete first sentence and change to read: Each interior sectional or floor control valve shall be provided with a drain connection sized as shown in Table 3–6.2.3 so as to drain that portion of the system controlled by the sectional or floor valve.
TABLE 3–6.2.3
Sectional or Floor Valve Size Minimum Size of Drain Connection Up to 2 1/2 in. 1 in. 3 in., 3 1/2 in., 4 in. 1 1/4 in. 5 in. and 6 in. 1 1/2 in. 8 in. 2 in.
Delete Section 3–7.4 and substitute the following:
3–7.4 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-3, BCuP-5, BAG-2 (ANSI/AWS A5.8–89) may be used.
Add Lead free solder joints may be permitted for wet pipe systems in Light Hazard Occupancies when the temperature classification of the installed sprinklers is Ordinary or Intermediate.
3–8 Fittings.
Renumber Section 3–8.1.4 to 3–8.1.6
Renumber Section 3–8.1.5 to 3–8.1.7
Add a new Section 3–8.1.4 to read as follows:
3–8.1.4 Fittings used in the assembly of copper tube shall conform to the following standards issued by the American National Standards Institute:
Bronze Flanges and Flanged Fittings 150 to 300 lb. ANSI B16.24–79
Add a new section 3–8.1.5 to read as follows:
3–8.1.5 Fittings used in the assembly of threadless copper pipe (Type TP) shall conform to the following standards:
Cast Bronze, Brazed-Joint Pressure Fittings Dimensions MIL F–1183 J–87 Chemical and physical properties ANSI/ASTM B 61–86 or ANSI/ASTM B 62–86 Bronze Flanges and Flanged Fittings 150 and 300 lb. ANSI B16.24–79
3–8.6 One and One-Half-Inch Hose Connections. Delete.
3–8.7 Hose Connections for Fire Department Use. Delete.
Add the following in lieu of the above.
3–8.7 Fire Standpipe Hose Connections. Where permitted in E, F, G, H and J Occupancies by Section 2–4.3 and where permitted by the Commissioner, the sprinkler system may be connected to the distribution system of mains and risers serving the required stand pipe hose connections. Connections to the common sprinkler and standpipe systems shall be valved and fitted with an approved supervised tamper switch and flow detector.
3–9 Valves.
3–9.1.1 Delete—Add the following:
3–9.1.1 A test pipe of not less than 1-inch diameter terminating in a smooth bore corrosion resistant outlet giving a flow equivalent to one sprinkler shall be provided. This test pipe shall be provided for each system through a pipe not less than 1 inch in diameter in the upper story, and the connection should preferably be piped from the end of the most remote branch line. The discharge should be at a point where it can be readily observed. In locations where it is not practical to terminate the test pipe outside the building, the test pipe may terminate into a drain. In this event, the test connection shall be made using an approved sight test connection containing a smooth bore corrosion resistant orifice giving a flow equivalent to one sprinkler. The test valve shall be located at an accessible point and preferably not over seven feet above the floor. The control valve on the test connection shall be located at a point not exposed to freezing.
3–9.1.1 Add the following sentences:
An approved indicating shutoff valve may be used in lieu of an O.S.&Y. gate valve wherever referred to in these modifications except such valve shall not be part of the pressure reducing valve. The indicator shall be readily visible from the floor.
3–9.2 Valves Controlling Sprinkler Systems.
3–9.2.3 Delete exception #2.
3–9.2.5 Delete.
3–9.2.6 Delete.
3–9.2.7 Delete.
Add 3–9.2.5 Where there is one water supply connection a check valve shall be installed. Such check valve may be a swing check, an approved fire meter or an approved detector check.
Add 3–9.2.6 Where a system having only one dry-pipe valve is supplied with city water and Fire Department connection, it will be satisfactory to install the main check valve in water supply connection in a vertical position immediately inside of the building after the main indicating valve.
Add 3–9.2.7 Where either a wet or dry pipe sprinkler system is supplied by city water and a Fire Department connection and has more than one riser with O.S.&Y. gate valve in each, and the whole system is controlled by one outside post indicator valve, it will be satisfactory to install the main check valve in the water supply connection immediately inside building. If the supply is controlled by an underground gate valve with a Department of Environmental Protection standard roadway box, the main check valve in the water supply connection should be installed immediately after the O.S.&Y. gate valve inside the building.
Add 3–9.2.8 Where a wet pipe sprinkler system is supplied by city water and a Fire Department connection with only one riser, the alarm valve will be considered as a check valve and an additional check will not be required.
Add 3–9.2.9 A gate valve should be installed on each side of each check valve under conditions other than described in Paragraphs 3–9.2.6, 3–9.2.7 and 3–9.2.8. However, this shall not apply to Fire Department Siamese check valves.
Add 3–9.2.10 Where a gravity tank is located on a tower in the yard, the gate valve on the tank side of the check valve shall be of O.S.&Y. type; the other shall be either an O.S.&Y. valve or an indicator post valve. Where a gravity tank is located on a building, both gate valves shall be the O.S.&Y. type; and all fittings inside the buildings, except the drain tee fill line, and heater connections, shall be under the control of a gate valve.
Add 3–9.2.11 In a city connection serving as one source of supply the city valve in the connection may serve as one of the required gate valves. An O.S.&Y. valve or an indicator post valve should be installed on the systems (water supply) side of the check valve.
Add 3–9.2.12 A connection from public water system shall not extend into or through a building unless such connection is under the control of an outside indicator post or O.S.&Y. gate or under the control of an inside O.S.&Y. gate valve located near the outside wall of the building.
Add 3–9.2.13 When a pump, located in a combustible pump house or exposed to danger from fire or falling walls, or a tank discharges into a yard main valve, fed by another supply, either the check valve in the connection shall be located in a pit or the gate valve should be of the indicator post type, located a safe distance outside of buildings.
Add 3–9.2.14 Check valves on tank or pump connections, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building is entirely of one fire area, when it is ordinarily considered satisfactory to locate the check valve over-head in the lowest level.
Add 3–9.2.15 All gate valves controlling water supplied for sprinklers shall be located where readily accessible and when necessary, permanent ladders, clamped treads on risers, chains and wheels, or other accepted means should be provided.
Add 3–9.2.16 Section Valves in Underground Fire Mains. Large yard systems shall have section controlling valves at appropriate points, in order to permit sectionalizing the system in the event of a break, or for the making of repairs or extension (See Standard for Outside Protection, ANSI/NFiPA No. 24–87).
Add 3–9.2.17 Floor Valves. Floor control valves shall be provided where required or in special cases where area or height, or number of tenants is excessive, both in manufacturing and mercantile buildings, or where contents are more than ordinarily susceptible to damage. Floor valves shall be located where they are readily accessible. They are to be O.S.&Y. or indicating type located ahead of the inlet of any pressure reducing valve.
Add 3–9.2.18 Indicator Posts for Gate Valves.
Add 3–9.2.18.1 Outside Control shall be provided.
Add 3–9.2.18.2 Where sprinklers are supplied from a yard main, an approved outside indicator post gate valve shall be placed in the connecting pipe at a safe distance from the building.
Add 3–9.2.18.3 Indicator post valves should be located not less than 40 feet from buildings; but where necessary to place a valve close to a building, it should be located at a blank part of the wall.
Add 3–9.2.18.4 When a building has no basement, and an outside post indicator control cannot be furnished, a short post indicator may be installed in a horizontal position in riser with handwheel projecting outside of wall.
Add 3–9.2.19 Pits for Underground Valves. Pits for underground valves except those located at the base of a tank riser, are described in the Standard for Outside Protection (ANSI/NFiPA No. 24–87). For pits protecting valves located at the base of a tank riser, refer to RS 10.
Add 3–9.2.20 Securing of Valves. All gate valves in supply pipes to automatic sprinklers, whether or not of indicator or post pattern, shall be sealed open in a satisfactory manner.
Add 3–9.2.21 Valves controlling sprinkler supplied from the standpipe system shall be approved for standpipe service in the pressure zone in which it is installed. They shall be O.S.&Y. or indicating valves and shall be located ahead of the inlet of any pressure reducing valve installed.
3–9.3.4. Delete.
3–11.5.2 Add to first sentence: and subject to the Commissioner's approval.
3–12.3.2 Delete this section, and substitute the following:
Dry Pipe Valves. The alarm apparatus for a dry-pipe system shall consist of approved low and high air pressure alarm attachments to the dry-pipe valve. When a dry-pipe valve is located on the system side of an alarm valve, the actuating device of the alarms for the dry-pipe valve may be connected to the alarms on the wet-pipe system.
Delete Section 3–12.4 and add the following, in lieu of the above:
3–12.4 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classes BCuP-3, BCuP-5, BAG-2 (ANSI/AWS A5.8–77) may be used.
3–12.6 Delete this section and add: refer to RS 17–3.
3–12.7 Delete this section and add: refer to RS 17–3.
3–12.8 Delete this section, and substitute the following:
Identification Signs. Identification signs shall be provided for outside alarm devices. The sign should be located near the device in a conspicuous position and shall be worded as follows: "SPRINKLER FIRE ALARM—WHEN BELL RINGS CALL FIRE DEPARTMENT OR POLICE."
Add 3–12.9 Drains.
Add 3–12.9.1 Where vents are necessary for satisfactory electric alarm switch operations, such vents should be properly piped to a drain.
Add 3–12.9.2 Drains from alarm devices shall be so arranged that there will be no danger of freezing, and so that there will be no overflowing at the alarm apparatus, at domestic connections or elsewhere with the sprinkler drains wide open and under pressure.
Add 3–12.9.3 Drain from retarding chamber and electric alarm switch should preferably discharge through an open cone and be run separate from main system drains to a safe and visible point of free discharge or to sewer or ground drain. Drain from water-motor-operated alarm device may run separately to sewer or ground drain or may be connected to drain from retarding chamber at a point between such sewer and a check valve on this drain, a union or plug being inserted in the drain from the alarm device to permit inspection. Where checks are used they shall be so located as to have the equivalent of at least a four-foot head and shall not be installed in a vertical position.
Add 3–12.9.4 Where drains are conveyed to a sewer, a proper trap shall be provided.
Add 3–12.9.5 Where it is necessary to drain alarm valves outside the wall, an open discharge cone shall be provided inside to break the pipe line so that cold air will not conduct directly into the retarding chamber. Alternately, all drains shall have at least 4 feet of pipe beyond the valves, in a warm area.
3–13 Fittings.
Renumber Section 3–13.1.4 to 3–13.1.6.
Renumber Section 3–13.1.5 to 3–13.1.7.
Add a new section 3–13.1.4 to read as follows:
3–13.1.4 Fittings used in the assembly of copper tube shall conform to the following standards issued by the American National Standards Institute:
Bronze Flanges and Flanged Fittings 150 to 300 lb. ANSI B16.24–79
Add a new section 3–13.1.5 to read as follows:
3–13.1.5 Fittings used in the assembly of threadless copper pipe (Type TP) shall conform to the following standards:
Cast Bronze, Brazed-Joint Pressure Fittings Dimensions MIL F–1183 G–78 Chemical and physical properties ANSI/ASTM B 61–76 or ANSI/ASTM B 62–80 Bronze Flanges and Flanged Fittings 150 and 300 lb. ANSI B16.24–79
3–14 Valves.
3–14.1.1 Add the following sentence:
"An Approved indicating valve may be used in lieu of an O.S.&Y. gate valve wherever referred to in these modifications except where such valve is to be installed in conjunction with a pressure reducing valve."
3–14.2 Valves Controlling Sprinkler Systems.
Amend 3–14.2.1 as follows:
3–14.2.1 Each system shall be provided with a listed indicating valve so located as to control all sources of water supply except fire department connections [when arranged as specified in 2.7.3].
3–14.2.5 Delete.
3–14.2.6 Delete.
3–14.2.7 Delete.
Add 3–14.2.5 Where there is one water supply connection a check valve shall be installed. Such check valve may be a swing check, an approved fire meter or an approved detector check.
Add 3–14.2.6 Where a system having only one dry-pipe valve is supplied with city water and Fire Department connection, it will be satisfactory to install the main check valve in water supply connection in a vertical position immediately inside of the building after the main indicating valve.
Add 3–14.2.7 Where either a wet or dry pipe sprinkler system is supplied by city water and a Fire Department connection and has more than one riser with O.S.&Y. gate valve in each, and the whole system is controlled by one outside post indicator valve, it will be satisfactory to install the main check valve in the water supply connection immediately inside building. If the supply is controlled by an underground gate valve with an approved roadway box, the main check valve in the water supply connection should be installed immediately after the O.S.&Y. gate valve inside the building.
Add 3–14.2.8 Where a wet pipe sprinkler system is supplied by city water and a Fire Department connection with only one riser, the alarm valve will be considered as a check valve and an additional check will not be required.
Add 3–14.2.9 A gate valve should be installed on each side of each check valve under conditions other than described in Paragraphs 3–14.2.6, 3–14.2.7 and 3–14.2.8. However, this shall not apply to Fire Department Siamese check valves.
Add 3–14.2.10 Where a gravity tank is located on a tower in the yard, the gate valve on the tank side of the check valve shall be of O.S.&Y. type; the other shall be either an O.S.&Y. valve or an indicator post valve. Where a gravity tank is located on a building, both gate valves shall be the O.S.&Y. type; and all fittings inside the buildings, except the drain tee fill line, and heater connections, shall be under the control of a gate valve.
Add 3–14.2.11 In a city connection serving as one source of supply the city valve in the connection may serve as one of the required gate valves. An O.S.&Y. valve or an indicator post valve should be installed on the water supply side of the check valve.
Add 3–14.2.12 A connection from public water system shall not extend into or through a building unless such connection is under the control of an outside indicator post of O.S.&Y. gate or under the control of an inside O.S.&Y. gate valve located near the outside wall of the building.
Add 3–14.2.13 When a pump, located in a combustible pump house or exposed to danger from fire or falling walls, or a tank discharges into a yard main fed by another supply, either the check valve in the connection shall be located in a pit or the gate should be of the indicator post type, located a safe distance outside of buildings.
Add 3–14.2.14 Check valves on tank or pump connections, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building is entirely of one fire area, when it is ordinarily considered satisfactory to locate the check valve over-head in the lowest level.
Add 3–14.2.15 All gate valves controlling water supplied for sprinklers shall be located where readily accessible and when necessary, permanent ladders, clamped treads on risers, chains and wheels, or other accepted means should be provided.
Add 3–14.2.16 Section Valves in Underground Fire Mains. Large yard systems shall have section controlling valves at appropriate points, in order to permit sectionalizing the system in the event of a break, or for the making of repairs or extension. (See Standard for Outside Protection, ANSI/NFiPA No. 24).
Add 3–14.2.17 Floor Valves. Floor control valves shall be provided where required or in special cases where area or height, or number of tenants is excessive, both in manufacturing and mercantile buildings, or where contents are more than ordinarily susceptible to damage. Floor valves shall be located where they are readily accessible. They are to be O.S.&Y. type located ahead of the inlet of any pressure reducing valve.
Add 3–14.2.18 Indicator Posts for Gate Valves.
Add 3–14.2.18.1 Outside control shall be provided.
Add 3–14.2.18.2 Where sprinklers are supplied from a yard main, an approved outside indicator post gate valve shall be placed in the connecting pipe at a safe distance from the building.
Add 3–14.2.18.3 Indicator post valves should be located not less than 40 feet from buildings; but where necessary to place a valve close to a building, it should be located at a blank part of the wall.
Add 3–14.2.18.4 When a building has no basement, and an outside post indicator control cannot be furnished, a short post indicator may be installed in a horizontal position in riser with handwheel projecting outside of wall.
Add 3–14.2.19 Pits for Underground Valves. Pits for underground valves except those located at the base of a tank riser, are described in the Standard for Outside Protection (ANSI/NFiPA No. 24). For pits protecting valves located at the base of a tank riser, refer to the Standard for Water Tanks for Private Fire Protection (ANSI/NFiPA No. 22).
Add 3–14.2.20 Securing of Valves. All gate valves in supply pipes to automatic sprinklers, whether or not of indicator or post pattern, shall be sealed open in a satisfactory manner.
Add 3–14.2.21 Valves controlling sprinkler supplied from the standpipe system shall be approved for standpipe service in the pressure zone in which it is installed. They shall be O.S.&Y. valves and shall be located ahead of the inlet of any pressure reducing valve installed.
3–15 Hangers.
3–15.1.10 Delete this section and substitute the following:
3.15.1.10 Maximum Distance Between Hangers. With Steel pipe as specified in this Chapter, the maximum distance between hangers shall not exceed 12 feet for 1 and 1 1/4 inch sizes nor 15 feet for sizes 1 1/2 inch and larger except as provided in 3–15.6 See Figure A-3-15.1.10.
With copper tube or pipe as specified in this chapter maximum spacing between hangers shall not exceed the distance indicated on Figure A–3–15.5.4 with steel band and ring hangers confirming therewith.
HANGER SPACING FOR COPPER PIPE AND COPPER TUBE—HORIZONTAL RUNS HORIZONTAL RUN HANGER SPACING
Tube Size Spacing 3/4" to 1" 5–8 feet 1 1/4" and 1 1/2" 8–10 feet 2" and 3" 10–12 feet 4"—8" 12–15 feet
SIZING OF SPS** STEEL STRAP AND RING HANGERS FOR USE WITH COPPER TUBE
SPS Steel Strap or Ring Hanger
Copper Tube Size inches Nominal Outside Diameter, inches Size inches Minimum Inside Diameter, inches 3/4 0.875 1/2 or v 1.050 or 1.315 1 1.125 3/4 or 1 1.315 1 1/4 1.375 1 1.660 1 1/2 1.625 1 1/4 0.840 or 1.050 2* 2.125 2* 2.375
** Above 2–inch, use the same SPS hanger size as the tube size.
** Standard Pipe Size Figure 1–3–15.5.4.
3–16.6.3 Delete this Section, and substitute the following:
The use of sprinklers with temperature ratings higher than ordinary shall be in accordance with the maximum ceiling temperatures given in table 3–16.6.1, except that intermediate or high temperature sprinklers may be used in other than light hazard occupancies. The use of high temperature sprinklers shall be limited to buildings with structural steel fully protected. High temperature sprinklers may also be used if there is high piled storage which is in compliance with NFiPA 231 and NFiPA 231 C.
3–17.3.2 Delete this section, and substitute the following:
Dry Pipe Valves. The alarm apparatus for a dry-pipe system shall consist of approved flow and low and high air alarm attachments to the dry-pipe valve. When a dry-pipe valve is located on the system side of an alarm valve, the actuating device of the alarms for the dry-pipe valve may be connected to the alarms on the wet-pipe system.
3–17.7 Delete this section, and substitute the following:
Identification Signs. It is essential to provide identification signs for outside alarm devices. The sign should be located near the device in a conspicuous position and shall be worded as follows: "SPRINKLER FIRE ALARM—WHEN BELL RINGS CALL FIRE DEPARTMENT OR POLICE."
Add 3–17.8 Drains.
Add 3–17.8.1 Where vents are necessary for satisfactory electric alarm switch operation, such vents should be properly piped to a drain.
Add 3–17.8.2 Drains from alarm devices shall be so arranged that there will be no danger of freezing, and so that there will be no overflowing at the alarm apparatus, at domestic connections or elsewhere with the sprinkler drains wide open and under pressure.
Add 3–17.8.3 Drain from retarding chamber and electric alarm switch should preferably discharge through an open cone and be run separate from main system drains to a safe and visible point of free discharge or to sewer or ground drain. Drain from water-motor-operated alarm device may run separately to sewer or ground drain or may be connected to drain from retarding chamber at a point between such sewer and a check valve on this drain, a union or plug being inserted in the drain from the alarm device to permit inspection. Where checks are used they shall be so located as to have the equivalent of at least a four-foot head and shall not be installed in a vertical position.
Add 3–17.8.4 Where drains are conveyed to a sewer, a proper trap shall be provided.
Add 3–17.8.5 Where necessary to drain alarm valves outside the wall, an open discharge cone shall be provided inside to break the pipe line so that cold will not be conducted directly into the retarding chamber. Alternately, all drains shall have at least 4 foot of pipe beyond the valves, in a warm area.
CHAPTER 4—SPACING, LOCATION AND POSITION OF SPRINKLERS
4–1.2 Delete.
4–2.2.1 Delete the first sentence and add the following:
"The maximum floor area to be protected by a single riser, from a control and alarm device, on any one floor shall be as follows:"
4–4.7.1 Delete.
4–4.7.2.1 Delete.
4–4.7.2.2 Delete.
4–4.7.2.3 Add to last sentence:
when required by other sections of this code
Delete the Exception.
4–4.7.2.4 Delete.
4–4.8 Add the following:
Sprinklers shall be provided in chute vestibules on all floors, if no vestibule exists, then sprinklers shall be provided above chute doors and shall be located no more than 1-foot horizontally from face of chute door.
All building service chute sprinkler systems shall be provided with a local water flow and valve supervisory alarm and be connected to an authorized fire alarm central office.
4–4.8.1 Delete.
4–4.8.2 Delete.
4–4.8.2.4 Delete.
Add 4–4.17.4 Safe deposits or other vaults of fire-resistive construction will not require sprinkler protection when used for the storage of records, files and other documents when stored in metal cabinets.
4–4.8.1 Delete and substitute the following:
In cooking areas protected by automatic sprinklers, sprinklers shall be provided to protect commercial-type cooking equipment and ventilation systems that are designed to carry away grease laden vapors unless otherwise protected (see RS 13–2 and RS 13–3). Sprinklers shall be so located as to give complete coverage of cooking surfaces, within exhaust ducts, within exhaust hood plenum chamber, and under filters, if any.
Add 4–4.16.4 Safe deposits or other valves of less than 1,000 cubic feet in size of fire-resistive construction may not require sprinkler protection when used for the storage of records, files and other documents, when stored in metal cabinets. These vaults shall be equipped with either a smoke or heat detection system connected to an authorized fire alarm central office.
4–4.17.1 Delete, and substitute the following:
In cooking areas protected by automatic sprinklers, sprinklers shall be provided to protect commercial-type cooking equipment and ventilation systems that are designed to carry away grease laden vapors unless otherwise protected (see RS 13–2 and RS 13–3). Sprinklers shall be so located as to give complete coverage of cooking surfaces, within exhaust ducts, within exhaust hood plenum chamber, and under filters, if any.
4–4.19.2 Add the following:
and provided that hard wired smoke detectors are provided in the sleeping rooms.
Add section 4-4.19.4 to follow section 4-4.19.3 as follows:
4-4.19.4 In buildings and spaces classified in Occupancy Groups J-2 and J-3, sprinklers may be omitted from bathrooms, water closet compartments, general toilet rooms and shower rooms.
Add section 4-4.19.5 to follow section 4-4.19.4 as follows:
4-4.19.5 In buildings and spaces classified in Occupancy Groups J-2 and J-3, sprinklers may be omitted from clothes closets, linen closets and pantries.
CHAPTER 5—TYPES OF SYSTEMS
5–3.4 Delete and substitute the following:
Location and Spacing of Fire Detection Devices. Spacing of fire detection devices shall be in accordance with their listing by nationally recognized testing laboratories or in accordance with manufacturer's specifications, subject to the approval of the Commissioner of Buildings.
5–3.5 Delete and substitute the following:
Location and Spacing of Fire Detection Devices. Spacing of fire detection devices shall be in accordance with their listing by a nationally recognized testing laboratory or in accordance with the manufacturer's specifications, subject to the approval of the Commissioner of Buildings.
Fig. 5–5.4 Delete and substitute the following:
Fig. 5–5.4 See detail of Typical Installation.
CHAPTER 6—OUTSIDE SPRINKLERS FOR PROTECTION AGAINST EXPOSURE FIRES
6–1 Water Supply and Control. Delete.
6–2 System Components. Delete.
CHAPTER 7—HYDRAULICALLY DESIGNED SPRINKLER SYSTEMS
7–1.1.2 Delete and substitute the following:
7–1.1.2 The design basis for such a system supersedes the rules in the sprinkler standard governing pipe schedules except that all systems continue to be limited by area, and pipe shall be not less than 1 inch nominal for ferrous piping and 3/4 inch nominal for copper tube and threadless copper pipe. The size of the pipe, number of sprinklers per branch line and number of branch lines per cross main are otherwise limited only by the available water supply.
However, sprinkler spacing and all other rules covered in this and other applicable standards shall be observed.
7–2.1 Delete and substitute the following:
Design criteria and calculations shall be submitted to the Commissioner along with the plans to obtain the necessary approval.
Table 7–4.3.1.4 Delete under column Pipe or Tube, "Plastic (listed)—All" and under C Value, Delete "150".
CHAPTER 8—PIPE SCHEDULE SYSTEMS
8–1 Delete and substitute the following:
The provisions of this Chapter shall apply to buildings of Class 1 construction, predominantly light hazard occupancy, and more than 100 feet high.
Add 8–1.2.1 Combined Systems Risers—Risers providing the water supply for both standpipe and sprinkler systems shall have a minimum diameter of 6-inches, however, a minimum diameter of 4-inches may be authorized in existing buildings if hydraulic calculations indicate that an adequate supply of water can be assured.
Add 8–1.2.2 When a combined riser is fed by a special service fire pump, a minimum diameter of 4-inches is required to feed fire hose stations. Riser size beyond last hose station is to be determined by hydraulic calculations.
Add 8–1.3.1 In buildings having mezzanine floors, large platforms, or large openings between floors which cannot be closed or satisfactorily cut off, the possibility that all or most of the sprinklers might be opened by a single fire should be considered in determining the size of risers. Where occupancy and construction are exceptionally good, and where there is a little likelihood of a fire spreading beyond the vicinity of its origin, the size of the feed main may be based on the total number of sprinklers in the main area plus half the number in the secondary area. A sprinkler water curtain may be considered an acceptable cut off for openings of less than 1,000 square feet.
Add 8–1.4 Sizes for Domestic Water Piping. Where permitted by the building code, 10 or less heads, that are connected to the domestic water system shall have the piping sized in accordance with the tables herein, and the domestic water line to which the sprinkler piping is connected shall be at least the size of the sprinkler line connected thereto. Connections may be made directly to cross-connections or headers.
8–3.2 Delete.
8–4.2 Add the following to the first sentence: "or as modified by Table 2–2.1B."
8–4.3 Delete.
8–4.4 Add the following:
8–4.4 Combined Systems. Risers providing the water supply for both standpipe and sprinkler systems shall have a minimum diameter of 6 inches: provided, however, a minimum diameter of 4 inches may be authorized in existing buildings if hydraulic calculations indicate that an adequate supply of water can be assured.
CHAPTER 10—DELETE
Appendix A, B and C and D shall be considered part of this Reference Standard, subject to the following modifications:
A–1–7.2.1 Delete.
A–1–7.3.1 Delete.
A–1–7.3.2 Delete.
A–1–7.3.3 Delete.
A–1–7.4 Delete and substitute the following:
A–1–7.4 New installations protecting extra hazard occupancies may be hydraulically designed or pipe schedule systems may be utilized, provided that a sufficient volume of water is supplied, and the water pressure is adequate. When the pipe schedule is used hydraulic calculations shall be done to prove that adequate water volume and water pressure are available.
A–1–7.4.1 Delete.
A–1–8.1.2 Delete and substitute the following:
A–1–8.1.2 Used equipment shall not be permitted unless completely overhauled by the manufacturers; and shall be subject to the approval of the Commissioner.
A–1–9 Delete.
A–2–2.3.3 Delete.
A–2–6.3 Amend sub-section titled "Location of Pressure Tanks" to read as follows:
Pressure tanks shall be located at or above the top level of sprinklers.
A–2–7.1 Delete.
A–2–7.2 Delete.
A–2–7.3 Delete.
A–3–1.1.5 Delete.
A–3–3.2 Delete.
A–3–3.7 Delete.
A–3–7.4 Delete and substitute the following:
A–3–7.4 The fire hazard of the brazing and welding process should be suitably safeguarded. Fire guards having Certificates of Fitness from the Fire Department shall be provided as required, and portable fire fighting equipment shall be provided.
Add new sentence:
Self-cleaning fluxes shall not be used. Continued corrosive action after the soldering process is completed could result in leaks from the seats of sprinklers.
A–3–10.2 In second paragraph, delete the words "copper tube" and substitute "brass piping or equivalent".
A–3–12.4 Delete and substitute following:
A–3–12.4 The fire hazard of the brazing and welding process should be suitably safeguarded. Fire guards having Certificates of Fitness from the Fire Department shall be provided as required and portable fire fighting equipment shall be provided.
A–4–4.4.4 Add to end of first sentence:
Subject to the approval of the Commissioner.
A–5–3.3 Delete paragraph (b) and add:
(b) The dry-pipe valve should be adequately pressurized to conform to manufacturer's design and available water pressure.
B–4–2.4.6 Delete.
B–7 Delete.
Appendix C Referenced Publications Delete.
RS 17-2A. STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES UP TO AND INCLUDING SIX STORIES IN HEIGHT
ANSI/NFPA No. 13R–1994—Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height.
Modifications—The provisions of NFPA No. 13R—1994 shall be subject to the following modifications. The section and paragraph numbers are from that standard.
PREFACE
Change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.
CHAPTER 1—GENERAL INFORMATION
Section 1-1—Change four stories to six stories.
Section 1-3—The definition of Multipurpose Piping shall be deleted.
Section 1-3—The definition of Residential Occupancies shall be deleted. The definition of such use as stated in Title 27, Chapter 1, subchapter 3 of the Building Code shall be used.
Section 1-5.2—Delete and substitute the following: Section 1-5.2—Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.
(a) Pressure rating
(b) Beam strength (hangers)
(c) Corrosion (chemical and electrolytic)
(d) Resistance to failure when exposed to elevated temperatures
(e) Methods of joining (strength, permanence, fire hazard)
(f) Availability of fittings (for sprinkler outlets and proper routings)
(g) Physical characteristics related to integrity during earthquakes
(h) Toxicity
(i) Combustibility
(j) Movement during sprinkler operation (water distribution)
Nonmetallic pipe and tube shall comply with the portions of the ASTM standards specified in Table 1-5.2 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe shall only be used in wet pipe systems. Nonmetallic pipe shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Table 1-5.2 Delete Special Listed Polybutylene (PB) Pipe.
Section 1-5.6 Delete and substitute the following:
Section 1-5.6 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-5, BAG-2 (ANSI/AWS A5.8-89) or other approved methods may be used. Lead free solder joints may be permitted for wet pipe systems when the temperature classification of the installed sprinklers is Ordinary or Intermediate.
Section 1-5.7 Delete and substitute the following:
Section 1-5.7 Other types of fittings may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of fittings other than that described above must involve consideration of many factors as described in Section 1-5.2. Nonmetallic pipe and tube fittings shall comply with the portions of the ASTM standards specified in Table 1-5.7 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe and tube fittings shall only be used in wet pipe systems. Nonmetallic pipe and tube fittings shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Section 1-6.2.1 Change NFPA 13 to RS 17-2, and add the following: "The use of antifreeze solutions other than glycerine-water in sprinkler systems using plastic pipe shall not be permitted."
CHAPTER 2—WORKING PLANS, DESIGN, INSTALLATION, ACCEPTED TESTS AND MAINTENANCE
Section 2-1 Delete
Section 2-1.1 Delete
Section 2-1.1.1 Delete
Section 2-1.1.2 Delete
Section 2-1.2 Delete
Section 2-1.2.1 Delete
Figure 2-1.2.1 Delete
Section 2-1.2.2 Delete
Section 2-1.3 Delete
Section 2-1.3.1 Delete
Section 2-1.3.1.1 Delete
Section 2-1.3.1.2 Delete
Section 2-1.3.1.3 Delete
Section 2-1.3.2 Delete
Section 2-3.2 Add subparagraph (e) as follows:
(e) A common supply main to the building, serving both sprinklers and domestic uses, may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve, i.e., the house control valve, will shut off the domestic water supply.
Section 2-3.3 Delete
Section 2-3.3.1 Delete
Section 2-3.3.2 Delete
Section 2-4.1.1 Delete the "exception"
Renumber Sections 2-4.1.2 and 2-4.1.3 to be as follows:
Section 2-4.1.2 to be 2-4.1.3
Section 2-4.1.3 to be 2-4.1.4
Add new Section 2-4.1.2 to read as follows:
Section 2-4.1.2 Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:
(a) Central station, proprietary or remote station signaling service, or
(b) Local signaling service that will cause the sounding of an audible signal at a constantly attended point.
Exception—Underground gate valves with roadway boxes need not be supervised.
Section 2-4.2 Delete and substitute as follows:
Section 2-4.2 Except in buildings classified in occupancy group J-1, at least one 3 in. (76 mm) single inlet fire department connection shall be provided and located in accordance with Section 27-940 of the Building Code. Buildings classified in occupancy group J-1 shall be provided with siamese connections in accordance with RS 17-2.
Section 2-6 Exception No. 1:—Delete and substitute the following: Sprinklers are not required in bathrooms, water closet compartments, general toilet rooms and shower rooms.
Section 2-6 Exception No. 2:—Delete and substitute the following: Sprinklers are not required in clothes closets, linen closets and pantries.
Section 2-6 At the end of the section add the following:
Location of sprinklers installed in buildings classified in occupancy group J-1 shall be in accordance with the requirements of RS 17-2.
Section 2-7 Delete and substitute the following:
Section 2-7 The owner is responsible for the condition of a sprinkler system and shall properly maintain the sprinkler system in accordance with the Fire Department's rules and regulations.
CHAPTER 3—REFERENCED PUBLICATIONS
Delete in its entirety.
APPENDIX A—EXPLANATORY MATERIAL
A-1-1, first paragraph, Change four to six.
A-1-5.2 Delete
A-1-5.7 Delete
A-2-1.3.2 Delete
A-2-3.3.1 Delete
Figure A-2-3.2(a), (b) and (c) Delete
APPENDIX B—REFERENCED PUBLICATIONS
Delete in its entirety.
NOTE: Subjects that are not covered under this reference standard shall be in accordance with Reference Standard 17-2.
RS 17-2B. STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES
ANSI/NFPA No. 13D—1994 Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes.
Modifications—The provisions of NFPA No. 13D—1994 shall be subject to the following modifications. The section and paragraph numbers are from that standard.
PREFACE
Change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.
CHAPTER 1—GENERAL INFORMATION
Section 1-3 Delete the definition of Multi-purpose Piping System.
Section 1-3 Delete the definition of Pre-engineered System.
Section 1-5.2 Revise the exception to read: Listing may be waived for tanks and pumps.
Section 1-5.3 Delete
Section 1-5.4 Delete and substitute with the following:
Section 1-5.4 Testing of a system can be accomplished by pressurizing the system 50 pounds (3.5 bar) above the normal system operating pressure and checking visually for leakage at each joint or coupling.
Fire Department connections are not required for systems covered by this standard, but may be installed at the discretion of the owner. In these cases, hydrostatic tests in accordance with Reference Standard RS 17-2 are necessary.
Dry systems should also be tested by placing the system under 40 pounds (2.8 bar) air pressure. Any leak that results in a drop in system pressure greater than 2 psi (0.14 bar) in 24 hours should be corrected. Check for leaks using soapy water brushed on each joint or coupling. Leaks will be shown by the presence of bubbles. This test should be made prior to concealing of piping.
CHAPTER 2—WATER SUPPLY
Section 2-2 Add subparagraph (e) as follows:
(e) A common supply main to the building serving both sprinkler and domestic uses may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve, i.e., house control valve, will shut off the domestic water supply.
Section 2-3 Delete
CHAPTER 3—SYSTEM COMPONENTS
Section 3-1.1 Delete the exceptions.
Add new Section 3-1.5 to read as follows:
Section 3-1.5 Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:
(a) Central station, proprietary or remote station signaling service, or
(b) Local signaling service that will cause the sounding of an audible signal.
Exception—Underground gate valves with roadway boxes need not be supervised.
Section 3-3.2 Delete and substitute the following:
Section 3-3.2 Other types of pipe or tubes may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.,
(a) Pressure rating
(b) Beam strength (hangers)
(c) Corrosion (chemical and electrolytic)
(d) Resistance to failure when exposed to elevated temperatures
(e) Methods of joining (strength, permanence, fire hazard)
(f) Availability of fittings (for sprinkler outlets and proper routings)
(g) Physical characteristics related to integrity during earthquakes
(h) Toxicity
(i) Combustibility
(j) Movement during sprinkler operation (water distribution)
Nonmetallic pipe shall comply with the portions of the ASTM standards specified in Table 3-3.2 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe shall only be used in wet pipe systems. Nonmetallic pipe shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Table 3-3.2 Delete Specification for Special Listed Polybutylene (PB) Pipe and ASTM D 3309.
Section 3-3.6 Delete and substitute the following:
Section 3-3.6 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-5, BAG-2 (ANSI/AWS A5.8-89) or other approved methods may be used. Lead free solder joints may be permitted for wet pipe systems when the temperature classification of the installed sprinklers is Ordinary or Intermediate.
Section 3-3.7 Delete and substitute the following:
Section 3-3.7 Other types of fittings may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of fittings other than that described above must involve consideration of many factors as described in Section 3-3.2. Nonmetallic pipe fittings shall comply with the portions of the ASTM standards specified in Table 3-3.7 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe fittings shall only be used in wet pipe systems. Nonmetallic pipe fittings shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Section 3-6 In the Exception, change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.
CHAPTER 4—SYSTEM DESIGN
Section 4-3.3.3.1 Add "The use of antifreeze solutions other than glycerine-water in sprinkler systems using plastic pipe shall not be permitted."
Section 4-3.3.4 shall be modified to read as follows:
Section 4-3.3.4 Arrangement of supply piping and valves. All permitted antifreeze solutions shall be installed in accordance with RS 17-2.
Figure 4-3.3.4 Delete and substitute with:
Figure 5-5.4 "Detail of Typical Installation" of Reference Standard 17-2.
Section 4-4.1 Exception No. 1—Delete NFPA 13, Standard for the installation of sprinkler systems and revise to read "Reference Standard 17-2."
Section 4-4.2 Revise to read as follows:
Section 4-4.2 Minimum Pipe Size—Minimum pipe size including copper and any other acceptable piping shall be 3/4 in. (19 mm).
Section 4-4.3 Delete the exception.
Section 4-6 shall be modified to read as follows: "Sprinklers shall be installed in all areas with the following exceptions:
Exception No. 1—Sprinklers are not required in attics not provided with floors.
Exception No. 2—Sprinklers are not required in clothes closets, linen closets and pantries.
Exception No. 3—Sprinklers are not required in bathrooms, water closet compartments, general toilet rooms and shower rooms.
Exception No. 4—Sprinklers are not required in garages, provided that at least one sprinkler head is located within 3 feet (914 mm) of any communicating opening between the garage and the dwelling.
Exception No. 5—Sprinklers are not required in open attached porches, carports and similar structures."
CHAPTER 5—LIMITED AREA DWELLINGS
Delete in its entirety.
CHAPTER 6—REFERENCED PUBLICATIONS
Delete in its entirety.
APPENDIX A—EXPLANATORY MATERIAL
Section A-1-1 Delete third sentence of first paragraph and revise second sentence to read:
"Residential portions of any other buildings shall be protected with residential sprinklers in accordance with the New York City Building Code."
Revise last paragraph to read "For protection of multiple dwellings, refer to the New York City Building Code."
Section A-1-2 Delete
Section A-1-3 Revise to read "System control valves shall be the indicating type and shall be approved/accepted type."
Section A-1.4 Delete
Section A-1-5.4 Delete
Section A-2.2 Delete entire section including all related diagrams, except for the following:
"When a tank is used for both domestic and fire protection purposes, a low water alarm activated when the water level falls below 110 percent of the minimum quantity specified in Section 2-1 should be provided".
Section A-2.3 Delete all related diagrams.
Section A-2.3(a) Delete
Section A-3-3.1 Delete
Section A-3-3.2 Delete
Section A-3-3.7 Delete
Section A-3-5.6.1 Revise to read as follows:
Section A-3-5.6.1 Decorative painting of residential sprinklers is not to be confused with the temperature identification colors as referenced in Reference Standard 17-2.
Section A-5-5 Delete
Table A-1.2(a) and (b) Delete