NYC Administrative Code RS 17-1 STANDPIPE SYSTEM CONSTRUCTION
This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 17-1 at American Legal Publishing.
1. MATERIALS FOR STANDPIPE SYSTEMS.—
(a) Pipe.—
(1) Pipe for standpipe systems shall be in accordance with table RS 17–1–1, and shall conform to the standards of table RS 16–1, of reference standard RS-16.
(2) Pipe for buried sections of the standpipe system, whether inside or outside of the building, shall be red brass, type "TP" threadless copper, hard temper type "K" copper tubing, galvanized wrought iron, galvanized steel, cast iron, or equivalent material. All such pipe, other than cast iron, shall be adequately wrapped or otherwise protected against corrosion.
(3) The name of the manufacturer and the pressure to which the pipe was tested shall be permanently and legibly indicated on all pipe used in standpipe systems.
(4) Only new pipe shall be used in standpipe system.
(b) Fittings.—
(1) Fittings used in standpipe systems above ground shall be malleable cast iron or cast steel conforming to reference standard RS 17–6.
(2) Fittings used in standpipe systems underground shall be cast iron conforming to reference standard RS 17–7 or RS 17–8.
(3) Pressure ratings shall be cast in or on the fittings. (See table RS 17–1–1 for required ratings.)
(4) Fittings used in standpipe systems that are of welded construction shall be of a type for welding purposes conforming to reference standard RS 17–9.
(5) Approved mechanical joint couplings may be used in the standpipe system. Fittings used in conjunction with the coupling shall be designed for use with the coupling.
(c) Valves.—
(1) Valves and related products used in fire protection shall be approved and comply with reference standard RS 17–6A.
(2) O. S. & Y. indicating valves (with indicator readily visible from the floor) shall be provided to permit any riser or other section to be shut off while remaining risers or sections continue in use. Valves shall be flanged, mechanically coupled, or wafer type and with bodies of cast iron, ductile iron cast steel or approved equivalent material having nonferrous metal seat rings. See Table 17–1–1 for required ratings and Figures RS 17–1–1 and RS 17–1–2 for valve locations.
TABLE RS 17–1–1 Required Ratings of Pipe, Fittings and Valves in Standpipe Systems for Various Heights of Buildings c, d
Distance from Upper Tank Check to 1st Floor or Fire Pump (ft.) Class of 2 1/2 Hose Outlet Valves Type of Pipe Fittings (wwp in psi) Check and Gate Valves (wwp in psi) 0 to 115 A a Schedule 10 or 40 carbon steel 300 175 115 to 270 A a Schedule 10 or 40 carbon steel 300 250 270 to 425 B b Schedule 40 carbon steel 350 350 425 to 657 B b Schedule 40 carbon steel 500 500 625 to 1,112 B b Schedule 80 carbon steel 800 800 1,112 and over B b Schedule 80 carbon steel 1,000 1,000
Notes.—
a For installation in buildings not exceeding 300 ft. in height or the uppermost 300 ft. in taller buildings. Valve shall close tightly against 300 psi normal hydraulic pressure and shall withstand a hydraulic test pressure of 750 psi.
b For installation in the lower portions of buildings exceeding 300 ft. in height. Valve shall close tightly against 400 psi normal hydraulic pressure and shall withstand a hydraulic test pressure at 1,250 psi.
c Six inches and larger section and riser control valves shall have a valved bypass.
d Siamese connections shall be rated for the same pressure as is required for interior fittings and valves.
(3) In single riser systems, or where a single riser extends through an upper portion of the building supplying hose outlet valves more than 150 ft. above the curb level, section valves shall be installed in the single riser at the floor where the single riser starts and at increments of not more than 100 ft. above the first valve. The section valve or valves in the upper section of the riser shall be located so as to divide the riser into increments as shown in figure RS 17–1–1 and RS 17–1–2.
(4) Riser control valves shall, where practicable, be located within a required stair enclosure serving the entrance floor. Where the stair enclosure extends to the basement or cellar, the rise control valve may be located within the stair enclosure at, or in, the basement or cellar ceiling, provided that a sign indicating the valve location is installed within the stair enclosure at the entrance floor. The hose outlet valve for the entrance floor shall be located on the riser side of the riser control valve. Riser control valves shall not be required on a vertical line supplying one or two hose outlet valves.
(5) Where riser control or section valves are located outside of a required stair enclosure, the valves shall be of such type and so installed so as to be remotely operated by either electric motors or hydraulic means. The remote control shall be from either the entrance floor or from the fire pump room. Operating devices shall be grouped, suitably housed, and kept locked with a fire department lock and key. The door of the housing shall be embossed to indicate the purpose of the device. Instructions for operating the remote valves by the control devices shall be legible, detailed, and complete, and shall be permanently secured to the inner face of the door.
(6) Each valve shall be so designed and installed as to permit its manual operation at the valley location. Pressure ratings on the name of the manufacturer shall be cast on, or in, each valve used in the system.
(7) The position of each remotely controlled valve, whether open or closed, shall be indicated at its remote control point and also at the valve.
(8) Valves shall be readily accessible for inspection, repair, and use. If a valve is placed so that its operating mechanism is more than 7 ft. above a floor or stair landing, a 12 in. wide wrought iron, steel or equivalent ladder securely fastened, shall be provided for access to the valve. In lieu of a ladder, chain operated mechanisms are permissible and shall be padlocked securely in place.
(9) Each control valve shall be conspicuously marked with the number assigned to it on the riser diagram for the standpipe system. Metal numbered tags at least 2 in. in diameter shall be securely attached to the valve. Each valve shall have a metal sign stating "STANDPIPE CONTROL VALVE" securely hung from the valve.
(10) Each control valve not remotely controlled shall be sealed with a lock and chain in its normal position. If the normal position is the closed position, a metal placard stating such fact shall be conspicuously attached to the valve.
(d) Check valves.—
(1) Check valves shall be flanged, malleable cast iron or cast steel body having nonferrous metal seat rings and bearings. Swing-type valves shall be installed horizontally in pipes from each siamese hose connection, and in piping from each tank, pump, and city water connection. Spring loaded check valves of the beveled seat type and guided on the top and bottom may be installed in the vertical position on the discharge side of any fire pump.
(2) Check valves other than those in siamese and fire pump lines shall be provided with an indicating shutoff valve that is flanged and bolted to the inlet and outlet of such check valves. The valves on the suction and discharge of the fire pump shall be deemed to comply with this requirement when the discharge valve is placed on the discharge side of the check valve. One of the shutoff valves placed on each side of the tank check valve may be of the remote control type, and when used, shall be on the downstream side of such check valve.
(e) Supports.—Piping in standpipe systems shall be adequately supported by clamps, hangers, or other supporting devices.
2. SIAMESE CONNECTIONS.—
(a) Design and construction.—
(1) Siamese hose connections shall have a clapper valve in each outlet branch unless such connection is at the shore end of a standpipe system also supplied by a siamese hose connection of the type specified for fireboat use.
(2) Siamese connections for fireboat use shall have two 3 1/2 in. swivels with fire department female threads. All other siamese hose connections, except those of the shore end type, shall have two 3 in. swivels with fire department female threads.
(3) All shore end siamese connections shall have 3 in. male hose threads and shall be subject to the approval of the fire department. In lieu of a check valve, each branch may have a drip and a long stem valve, which shall be placed within the structure or otherwise protected against freezing. No siamese connections provided for fireboat use shall be installed in any standpipe system whose water supply is taken from the city water mains.
(b) Marking.—Each siamese connection shall be provided with caps painted red, and shall have the word "Standpipe" in letters 1 in. high and 1/8 in. deep cast in the body or on a non-ferrous metal plate secured to the connections or mounted on the wall in a visible location, except that caps of each siamese connection used for combination standpipe and sprinkler systems shall be painted yellow and the words shall read "COMBINATION STANDPIPE AND SPRINKLER SYSTEMS."
(c) Location.—
(1) Siamese connections shall be placed between 18 in. and 36 in. above the sidewalk level.
(2) Siamese connections shall be of the flush or free standing type and, with the exception of the swivel caps, shall not project beyond the street line. The riser pipe to a free standing siamese connection shall be red brass. When siamese connections are installed in wall recesses, the recesses shall be of ample size to permit the convenient hose attachment.
(d) Check valve.—Each siamese connection shall be provided with a check valve inside of the building or in a valve pit outside of the building.
(e) Drip valve.—A 3/4 in. automatic ball drip valve shall be placed between the siamese connection and the check valve, except that on a fireboat siamese connection, a 1/2 in. open drip without a shutoff may be used. Automatic ball drips shall be placed in the horizontal position.
3. HOSE STATIONS.—
(a) Hose outlet valves.—
(1) On each floor at each riser, the required 2 1/2 in. angle hose valve shall be of a class as indicated in table RS 17–1–1.
(2) At the top of the highest riser there shall be provided, above the main roof level, a three-way manifold equipped with three 2 1/2 in. hose valves with hose valve caps. The lowest valve shall be located with the hose end at least 18 in. above the roof and the highest valve with the hose end not more than 60 in. above the roof. The manifold may be set in a horizontal or vertical position, provided the hose outlets are set between 18 in. and 60 in. above the roof level.
(3) Where the manifold is located other than within a heated stair enclosure, the control valve shall be located in a horizontal run of piping below the roof, with a long stem extending through the roof and equipped with a wheel handle at its upper end at least 12 in. above the roof. Between the control valve and the manifold there shall be provided within the heated space a 1/2 in. open drip or a 3/4 in. automatic ball drip, with the drip pipe extended to spill over a plumbing fixture or drain.
(b) Stations within stair enclosures.—
(1) In occupancies where a 2 1/2 in. fire hose is mandatory, the hose shall be connected to the 2 1/2 in. hose valve within the stair enclosure.
(2) In occupancies where 1 1/2 in. fire hose is permitted, a 2 1/2 in. x 1 1/2 in. brass or bronze non-swivel reducing coupling shall be attached to the 2 1/2 in. hose valve, or an auxiliary hose station may be provided.
(c) Branch sizes to hose stations.—
(1) The branch size shall be predicated on the developed length from the riser or cross connection to the required 2 1/2 in. hose valve station as follows:
Up to 4 ft.—2 1/2 in.
Over 4 ft.—3 in. to 25 ft.
Over 25 ft.—4 in.
(2) No valve shall be placed between the hose station valve and the riser or cross connection, except that on branches that serve three or more hose stations, a valve shall be provided at the riser or cross connection.
(3) Not more than one hose outlet shall be supplied from a 2 1/2 in. or 3 in. branch.
(d) Auxiliary hose stations branch size.—
(1) Branch piping from the required riser to an auxiliary hose station may be 2 1/2 in. I.P.S., and no valve shall be installed in the branch pipe with the exception of the 1 1/2 in. hose valve at the auxiliary hose station.
(e) Size, type and quality of hose.—
(1) At each hose station, hose shall be provided of a size, type and quality as required by the provisions of the building code.
(f) Nozzles.—
(1) Nozzles on 2 1/2 in. hose, except hose for yard hydrants, shall be at least 15 in. in length, and shall have a smooth bore with a 1 in. or 1 1/8 in. discharge orifice.
(2) Nozzle for hose used on yard hydrant systems shall be equipped with a playpipe conforming the requirements of the fire department.
(3) Nozzles on hose at auxiliary hose stations shall be approved adjustable combination fog nozzles. Where 1 1/2 in. hose is within the stair enclosure, the nozzle may be a 1/2 in. smooth bore nozzle at least 12 in. in length or an adjustable combination fog nozzle.
(g) Hose and valve cabinets.—
(1) When the hose is kept in a cabinet, such cabinet shall be equipped with a single swinging door that shall have an 8 in. high panel of clear wired glass at the level of the hose valve and rack. The door width shall be the full inside width of the cabinet, and the glass panel shall be at least 90 per cent of the width of the door. Where an extinguisher or other appurtenances are installed with the cabinet, the door shall have a clear wired glass panel the full 90 per cent of the door area.
(2) The hose valve within a stair enclosure may be kept in a cabinet. Such cabinet shall be equipped with a single swinging door that shall have a clear wired glass panel 90 per cent of the door area. The valve shall be placed in the cabinet to permit coupling of 2 1/2 in. hose to the valve without causing kinks in the hose.
(3) Each cabinet shall be readily accessible and the door shall be kept unlocked.
(4) Cabinets may have solid metal doors when located in the entrance hall of a building. All such hose cabinets or closets shall be permanently marked "FIRE HOSE" across the door panel in red letters at least 1 in. high, and shall not be used for any other purpose but concealing the hose station.
(h) Hose rack.—
(1) The hose at each outlet shall be kept upon a hose rack firmly supported and placed between 5 ft. and 6 ft. 6 in. above the floor or landing.
(2) The use of dump or reel type racks is prohibited.
4. TANKS IN STANDPIPE SYSTEM.—
(a) Construction and support of tanks.—Tanks for the standpipe system supply shall be constructed and supported in accordance with the provisions of reference standard RS 16, reference standard RS 17–2, and applicable provisions of the building code for loads and structural work.
(b) Combination tanks.—gravity tanks may be used to provide the required primary water supply to the standpipe system and/or domestic water in a building provided all the following conditions are met.
(1) The connections to the tank are made in such manner as to provide the required sprinkler and/or fire standpipe reserve. The domestic supply is above the sprinkler and/or standpipe reserve. The standpipe reserve is above the sprinkler reserve. Where a standpipe riser is used to supply water to sprinklers in buildings classified in occupancy group E, 100 feet or more in height, and in existing office buildings, 100 feet or more in height, the connection to the tank shall be made in such a manner as to provide the required sprinkler or standpipe reserve, whichever is greater.
(2) The connections to the system are made outside of the tank. When connections or piping are installed inside the tank, the piping shall be assembled without couplings and shall be of red brass.
(3) The tank is filled by means of an automatic pump at a rate of not less than 65 gpm.
(c) Filling of tanks.—
(1) Pressure or gravity tanks shall be filled at the rate of at least 65 gpm. Pipes used to fill the tanks shall not be used for any other purpose; nor shall required fire-pumps be used for filling purposes.
(2) Where there is sufficient pressure in the city water main to fill tanks at the required rate during all hours of each day, and a filling pump is not provided, the connection to the city water supply shall be made near the point where the city water service enters the building.
(3) A combined fire standpipe reserve and domestic water tank shall only be filled by direct public water connection or separate fill pumps, or direct connection to equipment, or pumps used to supply domestic water systems in accordance with Reference Standard RS 16.
(d) Emergency drains on standpipe tanks.—Each standpipe tank shall be provided with a drain of at least 4 in. size. Each drain pipe shall be controlled by a manually operated outside screw and yoke type valve located so as to be readily accessible. The drain shall be installed in accordance with the provisions of reference standard RS 16.
(e) Heating of standpipe tanks.—
(1) Where the water in the tank is subject to freezing, the tank shall be equipped with a tank heater in accordance with the provisions of reference standard RS 17–10.
(2) Where both the standpipe supply and domestic water supply are combined in a single tank, heating of such tank shall not be required in hotels, multiple dwellings, hospitals, or other occupancies where the domestic supply is drawn upon during all hours of every day of the week.
(f) Strainer.—
(1) Every standpipe gravity or suction tank shall be provided with a brass or bronze strainer at the discharge to risers or to pump supply lines.
(2) Each strainer shall have clear openings with an aggregate area equal to, or more than, the required area of the pipe into which the tank discharges. Openings shall be not more than 1 in. nor less than 1/2 in. in diameter.
(g) Overflow pipe for standpipe tanks.—Each gravity standpipe tank shall be provided with an overflow in accordance with the provisions of reference standard RS 16.
(h) Access to standpipe tanks.—Access to the top of each gravity tank shall be by means of a steel or wrought iron gooseneck ladder, constructed of flat side bars at least 2 in. by 3/8 in. or equivalent, spaced at least 14 in. apart, with round or square rungs at least 5/8 in. thick spaced not more than 12 in. on centers. The ladder shall be rigidly braced, and shall not tip outward from the vertical at any point. When ladders exceed 25 ft. in height, body irons spaced not more than 2 ft. on center and an iron platform at least 14 in. square, rigidly secured to the stringers of the ladder or other type of enclosed safe access, shall be provided near the top of the tank.
(i) Tank alarms for standpipe systems.—
(1) Gravity tanks not filled by an automatic pump or by city pressure shall be equipped with a high and low water level electrical alarm system.
(2) All pressure tanks used to provide the required primary water supply of a standpipe system shall be equipped with a high and low air pressure and a high and low water level electrical alarm system. Air-to-water ratio shall be 1 to 2 and shall be maintained by automatic electrical controls.
5. FIRE PUMPS IN STANDPIPE SYSTEMS.—
(a) Installation of Standpipe fire pumps.—
(1) Firepumps shall be placed on concrete (foundations) pads at least 12" above the pump room floor level with a clearance of at least 3' shall be maintained on all sides of the pad from walls or from other equipment in the pump room. In the event of the use of a vertical shaft centrifugal fire pump, the 12" high concrete pad may be omitted, provided the bottom of the electric driving motor and all electric appurtenances are raised at least 12" above the pump floor.
(2) The control of the manual fire pump shall be designed to operate at predetermined speeds to give pressure increments of 50 psig. The first step of the starter shall produce 100 psig at the pump, and each succeeding step shall produce increments of 50 psig up to the required pump pressure.
(3) Each automatic fire pump shall be equipped with a 3 in. pressure relief valve installed in the pump discharge. Such relief valve shall be set to relieve below the shutoff head of the pump, but above the pressure required to maintain the operating pressure at the highest hose valve. The discharge from the relief valve may be piped back into the suction side of the pump on the pump side of the suction valve provided a visual sight glass is installed in the discharge of the relief valve. Automatic fire pumps may be provided with a time delay switch to insure a minimum running time for the pump.
(4) Each manually operated fire pump shall be equipped with a 3 in. pressure relief valve for 500 gpm pumps and a 4 in. pressure relief valve for 750 gpm pumps. The relief shall be installed in the pump discharge line and set to relieve at a pressure not to exceed 15 lb. over the pressure required to deliver the rated capacity of the pump at the highest hose outlet. Discharge of the relief valve may be piped back into the suction side of the pump on the pump side of the suction valve provided a visual sight glass is installed in the discharge of the relief valve.
(5) Each manually operated fire pump shall also be equipped with a test valve installed in the pump discharge line that may be connected to the discharge side of the relief valve if the discharge pipe is piped back to the suction side of the pump as provided in (4) above. The size of the test line shall be 3 in. for a 500 gpm pump and 4 in. for a 750 pgm pump.
(6) The check valves in the pump discharge shall be either swing type or spring loaded.
(b) Wiring for fire pumps.—
(1) When the fire pump feeder conductors are routed through the building(s), they shall be enclosed by two (2) inches of concrete or shall be listed electrical circuit protective systems with a minimum of one-hour fire resistance.