NYC Administrative Code RS 17-2
This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 17-2 at American Legal Publishing.
[Standard for the Installation of Sprinkler Systems]
ANSI/NFiPA No. 13–1983—Standard for the Installation of Sprinkler Systems.
MODIFICATIONS—The provisions of NFiPA No. 13–1989 shall be subject to the following modifications. The section and paragraph numbers are from that standard.
CHAPTER 1—GENERAL INFORMATION
1–1 Delete.
1–4 Delete.
1–6 Delete.
1–7 Classification of Occupancies.
Add 1–7.5 For purposes related to sprinkler installation, classification of occupancies in Paragraphs 1–7.2.1, 1–7.3.1, 1–7.3.2, 1–7.3.3 and 1–7.4.1 shall be considered as equivalent to classifications of buildings and spaces in the building code as follows:
Light Hazard—E, G, H-1, H-2, J-1, J-2, J-3.
Ordinary Hazard—B-1, B-2, D-1, D-2, C, F-1, F-3, F-4.
Extra Hazard—A.
1–9 Delete.
1–10 Delete.
1–11.1 Delete.
1–11.2 Delete except for 1–11.2.4 and 1–11.2.5
1–11.3 Delete.
1–12 Delete.
CHAPTER 2—WATER SUPPLIES
2–1 Delete.
Revise table 2–2.1 (A) to read as follows:
TABLE 2–2.1 (A) Guide to Water Supply Requirements for Pipe Schedule Sprinkler Systems
Occupancy Classification Residual Pressure Required (See Note 1) Acceptable Flow at Base of Riser (See Note 2) Duration in Minutes (See Note 3) Light Hazard 15 psi 500– 750 gpm 30 (Note 4) Ordinary Hazard (Group 1) 15 psi or higher 700–1,000 gpm 30 Ordinary Hazard (Group 2) 15 psi or higher 850–1,500 gpm 30 Ordinary Hazard (Group 3) Pressure and flow requirements for sprinklers and hose streams to be determined from Table 2–2.1 (B). 30 Warehouses Pressure and flow requirements as determined by Chapter 7 and subject to Commissioner's approval. High-Rise Buildings Pressure and flow requirements for sprinklers in accordance with Chapter 8. Woodworker's Shop See Appendix A Pressure and flow requirements subject to Commissioner's approval. Extra Hazard Pressure and flow requirements subject to Commissioner's approval.
Notes:
1. The pressure required at the base of the sprinkler(s) is defined as the residual pressure required of the elevation at the highest sprinkler plus the pressure required to reach this elevation.
2. The lower figure is the minimum flow ordinarily acceptable for pipe schedule sprinkler systems. The higher flow should normally suffice for all cases under each group.
3. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
4. In existing buildings only, the Commissioner may authorize reduction of storage to 20 minutes provided there are provisions for acceptable mechanical automatic means of makeup to the storage tank.
5. Where the water supply to a system sized in accordance with the pipe sizing schedules is taken from a water storage tank, the adequacy of the tank capacity shall be verified with a hydraulic calculation.
6. This occupancy classification shall apply when the warehouse contains high-piled or rack storage as defined in section 4–1.3.8 and complies with the requirements of NFiPA 321 and 231C.
The following conditions should be met for determining acceptable means for makeup:
a) Automatic means of makeup for a tank fire reserve should be capable of pumping water into the tank at a rate, for a period of 20 minutes, sufficient to equal the difference between the normal 30-minute demand and the alternate 20-minute demand. The demand required is established by calculations for the "most demanding remote area from the riser as shown by examples of Appendix A of NFiPA 13–1989 and as now determined for the 30-minute demand.
b) There should be at least two (2) automatic means of makeup, each having the same capacity, so that in the event a unit must be removed for repairs the other unit can be placed in service.
c) An approved low water alarm is to be provided and located at a point 500 gallons above the available fire reserve level.
5. Where the water supply to a system sized in accordance with the pipe sizing schedules is taken from a water storage tank, the adequacy of the tank capacity shall be verified with a hydraulic calculation.
6. This occupancy classification shall apply when the warehouse contains high-piled or rack storage as defined in Section 4–1.3.10 and complies with the requirements of NFiPA 231 and 231C.
Delete Table 2–2.1 (b) in its entirety, except for Density Curves and add the following:
TABLE 2–2.1.1(b) Table and Design Curves for Determining Density, Area of Sprinkler Operation and Water Supply Requirements for Hydraulically Designed Sprinkler Systems Minimum Water Supply Requirements
Hazard Classification Sprinklers Only—gpm Duration in Minutes (See Notes 1, 2, & 3) Light See 2–2.1.3 30 Ord.—Gp. 1 See 2–2.1.3 40 Ord.—Gp. 2 See 2–2.1.3 40 Ord.—Gp. 3 See 2–2.1.3 40
For SI Units: 1 gpm = 3.785 L/min.
________________________________________
Notes:
1. In existing buildings only, the Commissioner may authorize reduction of storage to 20 minutes provided there are provisions for acceptable mechanical automatic means of makeup to the storage tank. Where 20 minutes storage cannot be achieved with existing storage facilities, alternative means of supply may be considered by the Commissioner. In any event, no fire reserve storage facility shall have less than 3500 gallons.
2. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
3. In no case shall existing sprinkler storage capacities be reduced to less than the amount required for comparable new construction.
4. In fully sprinklered buildings the storage capacity of the fire reserve in the tank shall be as required for the sprinkler demand, but shall not be less than 3500 gallons in buildings with a single fire standpipe riser nor less than 5000 gallons in buildings with multiple fire standpipe risers.
5. Storage in light hazard occupancies where not more than 15 percent of the building is of ordinary hazard may have storage capacity predicated on light hazard occupancy.
The following conditions should be met for determining acceptable automatic means of makeup:
a) Automatic means of makeup for a tank fire reserve should be capable of pumping water into the tank at a rate, for a period of 20-minutes, sufficient to equal the difference between the normal 30-minute demand and the alternate 20-minute demand. The demand required is established by calculations for the most demanding remote area from the riser as shown by examples of Appendix A of NFiPA 13–1989 and as now determined by the 30-minute demand.
b) There should be at least two (2) automatic means of makeup, each having the same capacity, so that in the event that a unit must be removed for repairs the other unit can be placed in service.
c) An approved low water alarm is to be provided and located at a point 500 gallons above the fire level reserve.
2. Where there is a requirement for a sprinkler alarm, a central station signal shall be provided.
3. In no case shall existing sprinkler storage capacities be reduced to less than the amount required for comparable new construction.
4. In fully sprinklered buildings the storage capacity of the fire reserve in the tank shall be as required for the sprinkler demand, but shall not be less than 3500 gallons in buildings with a single fire standpipe riser nor less than 5000 gallons in buildings with multiple fire standpipe risers.
5. Storage in light hazard occupancies where not more than 15 percent of the building is of ordinary hazard may have storage capacity predicated on light hazard occupancy provided that any such space shall not exceed 5,000 square feet in area.
2–2.4.1 to 2–2.4.6 Delete Except 2–2.4.3
2–3 Connections of Water Works Systems.
2–3.1.2 Delete.
2–4 Gravity Tanks.
2–4.2 Add an additional sentence to read as follows: "If any of the sprinkler heads are supplied from domestic water tanks, the combined water supply in the tank shall be at least 5,000 gallons. Further, that the sprinkler supply shall be taken from the lowest level of the tank."
Add 2–4.3 Combined Use. In E, F, G, H and J Occupancies, with only limited ordinary hazard areas, the sprinkler and standpipe reserve may be common to both. Reserve shall be sized for whichever demand is the greater.
Interpretation:
Limited, may be defined as less than 30% of a floor area.
Add 2–4.3.1 Buildings whose occupancies are more than 85 percent light hazard, may have a light hazard water supply provided the ordinary hazard areas are designed for ordinary hazard requirements in respect to sprinkler spacing and pipe sizing.
Add 2–4.3.2 Combined standpipe and sprinkler systems may be used in D-2 Laboratory Occupancies, E, F, G, H and J. If an automatic fire pump is used as the primary supply, the requirements of 2–5.3 shall be complied with.
2–5 Pumps.
Add 2–5.3 Combined Use. In light hazard occupancies with only limited ordinary hazard areas, an automatic fire pump serving the lower 300 feet of the standpipe system may be used as the primary supply to the sprinkler system, provided that a secondary power supply is available to drive the pump; and such power supply shall be automatic switching.
Add 2–5.4 In hydraulically designed sprinkler systems supplied from a gravity tank, the pressure may be increased by means of an automatic, special service fire pump. The pump shall be sized to satisfy the requirements of table 2–2.1 (A) or table 2–2.1 (B) and shall be arranged in a bypass to permit the portion of the system so supplied to be serviced by the system's siamese connections.
(a) The pump need not be supplied from the street side of the building service switch, but the electrical service and pump operation shall be fully supervised. Provided that a secondary power supply is available to drive the pump; and such power supply shall be automatic switching.
2–5.5 Wiring for fire pumps.—When the fire pump feeder conductors are routed through the building(s), they shall be enclosed by two (2) inches of concrete or shall be listed electrical circuit protective systems with a minimum of one-hour fire resistance.
2–6 Pressure Tanks.
Delete 2–6.1 to 2–6.3 and substitute:
2–6.1 Acceptability.
2–6.1.1 A pressure tank in accordance with table 2–2.1 (A) or 2–2.1 (B) is an acceptable water supply source. The total available quantity of water in pressure tanks need not exceed 15,000 gal. when there is a secondary source of water supply available from a gravity tank or a street connection acceptable to the Commissioner of Buildings. The maximum gross capacity of a single pressure tank shall be 9,000 gal.
2–6.1.2 Each tank shall be kept at a maximum of 2/3 full of water and a minimum of 1/3 full of air maintained under a minimum pressure of 75 psig. The water-to-air ratio shall be so proportioned and the tank so located that a minimum pressure of 15 psig will be available on the highest line of sprinklers below the main roof when all the water is being discharged from the tank.
2–6.1.3 The tank supports shall be designed on the basis of the tank being full of water.
2–6.2 The tanks shall be supplied with water through a fixed pipe, independent of the sprinkler piping, and at least 2 inch in size. The water supply and connection shall be capable of supplying the tank at a rate of at least 65 gpm without reducing the pressure in the tank. The tank shall have a fixed water level plate on the end of the tank opposite the gauge glass, or equivalent devices, to indicate the level of the water in the tank.
2–6.3 The air compressor shall be provided with automatic controls for maintaining the air-to-water ratio. The capacity of the compressor shall be sufficient to build up the tank pressure to 75 psig within 3 hr. or less.
2–6.4 Pressure tanks shall be provided with approved closed circuit high and low water and high low air alarms.
2–6.5 Pressure tanks shall be located at or above the top level of sprinklers.
Delete 2–7 and 2–8.
CHAPTER 3—SYSTEM COMPONENTS
3–1.1 Delete.
3–1.1.1 Delete.
3–1.1.4 Delete.
3–1.1.5 Delete.
Add the following, in lieu of the above:
Piping Specifications.
3–1.1 Pipe or tube used in sprinkler systems shall be wrought steel, wrought iron, drawn seamless copper tube or threadless copper pipe.
The chemical and physical properties of wrought steel or wrought iron pipe should be at least equal to those manufactured in accordance with the specifications of the American Society for Testing and Materials for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Ordinary Uses, ANSI/ASTM Designation A 120–77; or for Welded Wrought-Iron Pipe, ASTM Designation A 72–68. Dimensions for wrought steel or wrought iron pipe should be in accordance with the American Standard for Wrought Steel and Wrought Iron Pipe, ANSI B36.10–1979. Pipe used in sprinkler systems should be designed to withstand a working pressure of not less than 175 psi. It is intended that this sprinkler standard permit the use of "standard wall" pipe as described in ANSI B36.10–1979 for pressure up to 300 psi. Schedule 40 pipe is considered "standard wall" pipe. Schedule 30 pipe is acceptable in sizes 8 inch and larger. However, "light wall," schedule 10 pipe is acceptable in sizes 8 inch and smaller, provided such pipe is Approved by the Board of Standards and Appeals for working pressure of not less than 175 psi.
Tube or threadless pipe used in sprinkler systems shall be drawn seamless copper tube or threadless copper pipe conforming to the chemical and physical properties of one of the following standards issued by the American Society for Testing and Materials:
Seamless Copper Tube ANSI/ASTM B 75–79
Seamless Copper Water Tube ANSI/ASTM B 88–76
General Requirements for Wrought Seamless Copper and Copper-Alloy Tube ANSI/ASTM B 251–76
Threadless Copper Pipe ANSI/ASTM B 302–76
Copper Tube or threadless pipe used in sprinkler systems as specified in the above standards shall be limited to wet systems for light and ordinary hazard occupancies using sprinkler heads having 165 F. rating or less, and shall have minimum wall thicknesses capable of withstanding a working pressure of not less than 175 psig at a service temperature of 300 F. for both annealed and drawn tempers. Copper Water Tube Types K and L ANSI/ASTM B 88–76 and Threadless Copper Pipe Type TP (ANSI/ASTM B 302–76) are acceptable.
Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency and acceptable to the Commissioner. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.,
1. Pressure rating.
2. Beam strength (hangers).
3. Corrosion (chemical and electrolytic).
4. Resistance to failure when exposed to elevated temperatures.
5. Methods of joining (strength, permanence, fire hazard).
6. Availability of fittings (for sprinkler outlets and proper routings).
7. Toxicity.
3–1.1.5 Delete, and substitute the following:
3–1.1.5 Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency acceptable to the Commissioner. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.
1. Pressure rating
2. Beam strength (hangers)
3. Corrosion (chemical and electrolytic)
4. Resistance to failure when exposed to elevated temperatures
5. Methods of joining (strength, permanence, fire hazard)
6. Availability of fittings (for sprinkler outlets and proper routings)
7. Physical characteristics related to integrity during earthquakes.
8. Toxicity
9. Combustibility
10. Movement during sprinkler operation (water distribution).
3–2 Definitions. Add the following: Fire Section—See subarticle 201.0. Each floor of a sprinklered building may be considered a fire section.
Add 3–3.4.1 In altering existing sprinkler systems which contain 3/4-inch pipe, the existing 3/4-inch pipe may be retained except that extension from such 3/4-inch pipe shall be made using pipe having a minimum diameter of one-inch.
3–3.7 One and One-Half-Inch Hose Connections. Delete.
3–3.8 Hose Connections For Fire Department Use. Delete.
Add the following in lieu of the above:
3–3.7 Fire Standpipe Hose Connections. Where permitted in E, F, G, H and J occupancies by Section 2–4.3, and where permitted by the Commissioner, the sprinkler systems may be connected to the distribution system of mains and risers serving the required standpipe hose connections. Connections to the common sprinkler and standpipe systems shall be valved and fitted with an approved supervised tamper switch and flow detector.
3–3.1 Delete the first sentence and add the following:
"The maximum floor area to be protected by a single riser, from a control and alarm device, on any one floor shall be as follows:"
3–4 Pipe Schedules.
3–4.1.1 Delete—Add the following:
3–4.1.1 A test pipe of not less than 1-inch diameter terminating in a smooth bore corrosion resistant outlet giving a flow equivalent to one sprinkler shall be provided. This test pipe shall be provided for each system through a pipe not less than 1-inch in diameter, in the upper story, and the connection should preferably be piped from the end of the most remote branch line. The discharge should be at a point where it can be readily observed. In locations where it is not practical to terminate the test pipe outside the building, the test pipe may terminate in a drain. In this event, the test connection shall be made using an approved sight test connection containing a smooth bore corrosion resistant orifice giving a flow equivalent to one sprinkler. The test valve shall be located at an accessible point, and preferably not over seven feet above the floor. The control valve on the test connection shall be located at a point not exposed to freezing.
Add 3–4.4.1 In buildings having mezzanine floors, large platforms, or large openings between floors which cannot be closed or satisfactorily cut off, the possibility that all or most of the sprinklers might be opened by a single fire should be considered in determining the size of risers. Where occupancy and construction are exceptionally good and where there is little likelihood of a fire spreading beyond the vicinity of its origin, the size of the feed main should be based on the total number of sprinklers in the main area plus half the number in the area not cut off. A sprinkler water curtain may be considered an exceptionable cut off for openings of less than 1,000 square feet.
Add 3–4.6 Sizes for Domestic Water Piping. Where permitted by the building code, 10 or less heads, that are connected to the domestic water system shall have the piping sized in accordance with the tables herein and the domestic water line to which the sprinkler line connected thereto. Connections may be made directly to cross-connections or headers.
3–6.2.3 Delete first sentence and change to read: Each interior sectional or floor control valve shall be provided with a drain connection sized as shown in Table 3–6.2.3 so as to drain that portion of the system controlled by the sectional or floor valve.
TABLE 3–6.2.3
Sectional or Floor Valve Size Minimum Size of Drain Connection Up to 2 1/2 in. 1 in. 3 in., 3 1/2 in., 4 in. 1 1/4 in. 5 in. and 6 in. 1 1/2 in. 8 in. 2 in.
Delete Section 3–7.4 and substitute the following:
3–7.4 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-3, BCuP-5, BAG-2 (ANSI/AWS A5.8–89) may be used.
Add Lead free solder joints may be permitted for wet pipe systems in Light Hazard Occupancies when the temperature classification of the installed sprinklers is Ordinary or Intermediate.
3–8 Fittings.
Renumber Section 3–8.1.4 to 3–8.1.6
Renumber Section 3–8.1.5 to 3–8.1.7
Add a new Section 3–8.1.4 to read as follows:
3–8.1.4 Fittings used in the assembly of copper tube shall conform to the following standards issued by the American National Standards Institute:
Bronze Flanges and Flanged Fittings 150 to 300 lb. ANSI B16.24–79
Add a new section 3–8.1.5 to read as follows:
3–8.1.5 Fittings used in the assembly of threadless copper pipe (Type TP) shall conform to the following standards:
Cast Bronze, Brazed-Joint Pressure Fittings Dimensions MIL F–1183 J–87 Chemical and physical properties ANSI/ASTM B 61–86 or ANSI/ASTM B 62–86 Bronze Flanges and Flanged Fittings 150 and 300 lb. ANSI B16.24–79
3–8.6 One and One-Half-Inch Hose Connections. Delete.
3–8.7 Hose Connections for Fire Department Use. Delete.
Add the following in lieu of the above.
3–8.7 Fire Standpipe Hose Connections. Where permitted in E, F, G, H and J Occupancies by Section 2–4.3 and where permitted by the Commissioner, the sprinkler system may be connected to the distribution system of mains and risers serving the required stand pipe hose connections. Connections to the common sprinkler and standpipe systems shall be valved and fitted with an approved supervised tamper switch and flow detector.
3–9 Valves.
3–9.1.1 Delete—Add the following:
3–9.1.1 A test pipe of not less than 1-inch diameter terminating in a smooth bore corrosion resistant outlet giving a flow equivalent to one sprinkler shall be provided. This test pipe shall be provided for each system through a pipe not less than 1 inch in diameter in the upper story, and the connection should preferably be piped from the end of the most remote branch line. The discharge should be at a point where it can be readily observed. In locations where it is not practical to terminate the test pipe outside the building, the test pipe may terminate into a drain. In this event, the test connection shall be made using an approved sight test connection containing a smooth bore corrosion resistant orifice giving a flow equivalent to one sprinkler. The test valve shall be located at an accessible point and preferably not over seven feet above the floor. The control valve on the test connection shall be located at a point not exposed to freezing.
3–9.1.1 Add the following sentences:
An approved indicating shutoff valve may be used in lieu of an O.S.&Y. gate valve wherever referred to in these modifications except such valve shall not be part of the pressure reducing valve. The indicator shall be readily visible from the floor.
3–9.2 Valves Controlling Sprinkler Systems.
3–9.2.3 Delete exception #2.
3–9.2.5 Delete.
3–9.2.6 Delete.
3–9.2.7 Delete.
Add 3–9.2.5 Where there is one water supply connection a check valve shall be installed. Such check valve may be a swing check, an approved fire meter or an approved detector check.
Add 3–9.2.6 Where a system having only one dry-pipe valve is supplied with city water and Fire Department connection, it will be satisfactory to install the main check valve in water supply connection in a vertical position immediately inside of the building after the main indicating valve.
Add 3–9.2.7 Where either a wet or dry pipe sprinkler system is supplied by city water and a Fire Department connection and has more than one riser with O.S.&Y. gate valve in each, and the whole system is controlled by one outside post indicator valve, it will be satisfactory to install the main check valve in the water supply connection immediately inside building. If the supply is controlled by an underground gate valve with a Department of Environmental Protection standard roadway box, the main check valve in the water supply connection should be installed immediately after the O.S.&Y. gate valve inside the building.
Add 3–9.2.8 Where a wet pipe sprinkler system is supplied by city water and a Fire Department connection with only one riser, the alarm valve will be considered as a check valve and an additional check will not be required.
Add 3–9.2.9 A gate valve should be installed on each side of each check valve under conditions other than described in Paragraphs 3–9.2.6, 3–9.2.7 and 3–9.2.8. However, this shall not apply to Fire Department Siamese check valves.
Add 3–9.2.10 Where a gravity tank is located on a tower in the yard, the gate valve on the tank side of the check valve shall be of O.S.&Y. type; the other shall be either an O.S.&Y. valve or an indicator post valve. Where a gravity tank is located on a building, both gate valves shall be the O.S.&Y. type; and all fittings inside the buildings, except the drain tee fill line, and heater connections, shall be under the control of a gate valve.
Add 3–9.2.11 In a city connection serving as one source of supply the city valve in the connection may serve as one of the required gate valves. An O.S.&Y. valve or an indicator post valve should be installed on the systems (water supply) side of the check valve.
Add 3–9.2.12 A connection from public water system shall not extend into or through a building unless such connection is under the control of an outside indicator post or O.S.&Y. gate or under the control of an inside O.S.&Y. gate valve located near the outside wall of the building.
Add 3–9.2.13 When a pump, located in a combustible pump house or exposed to danger from fire or falling walls, or a tank discharges into a yard main valve, fed by another supply, either the check valve in the connection shall be located in a pit or the gate valve should be of the indicator post type, located a safe distance outside of buildings.
Add 3–9.2.14 Check valves on tank or pump connections, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building is entirely of one fire area, when it is ordinarily considered satisfactory to locate the check valve over-head in the lowest level.
Add 3–9.2.15 All gate valves controlling water supplied for sprinklers shall be located where readily accessible and when necessary, permanent ladders, clamped treads on risers, chains and wheels, or other accepted means should be provided.
Add 3–9.2.16 Section Valves in Underground Fire Mains. Large yard systems shall have section controlling valves at appropriate points, in order to permit sectionalizing the system in the event of a break, or for the making of repairs or extension (See Standard for Outside Protection, ANSI/NFiPA No. 24–87).
Add 3–9.2.17 Floor Valves. Floor control valves shall be provided where required or in special cases where area or height, or number of tenants is excessive, both in manufacturing and mercantile buildings, or where contents are more than ordinarily susceptible to damage. Floor valves shall be located where they are readily accessible. They are to be O.S.&Y. or indicating type located ahead of the inlet of any pressure reducing valve.
Add 3–9.2.18 Indicator Posts for Gate Valves.
Add 3–9.2.18.1 Outside Control shall be provided.
Add 3–9.2.18.2 Where sprinklers are supplied from a yard main, an approved outside indicator post gate valve shall be placed in the connecting pipe at a safe distance from the building.
Add 3–9.2.18.3 Indicator post valves should be located not less than 40 feet from buildings; but where necessary to place a valve close to a building, it should be located at a blank part of the wall.
Add 3–9.2.18.4 When a building has no basement, and an outside post indicator control cannot be furnished, a short post indicator may be installed in a horizontal position in riser with handwheel projecting outside of wall.
Add 3–9.2.19 Pits for Underground Valves. Pits for underground valves except those located at the base of a tank riser, are described in the Standard for Outside Protection (ANSI/NFiPA No. 24–87). For pits protecting valves located at the base of a tank riser, refer to RS 10.
Add 3–9.2.20 Securing of Valves. All gate valves in supply pipes to automatic sprinklers, whether or not of indicator or post pattern, shall be sealed open in a satisfactory manner.
Add 3–9.2.21 Valves controlling sprinkler supplied from the standpipe system shall be approved for standpipe service in the pressure zone in which it is installed. They shall be O.S.&Y. or indicating valves and shall be located ahead of the inlet of any pressure reducing valve installed.
3–9.3.4. Delete.
3–11.5.2 Add to first sentence: and subject to the Commissioner's approval.
3–12.3.2 Delete this section, and substitute the following:
Dry Pipe Valves. The alarm apparatus for a dry-pipe system shall consist of approved low and high air pressure alarm attachments to the dry-pipe valve. When a dry-pipe valve is located on the system side of an alarm valve, the actuating device of the alarms for the dry-pipe valve may be connected to the alarms on the wet-pipe system.
Delete Section 3–12.4 and add the following, in lieu of the above:
3–12.4 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classes BCuP-3, BCuP-5, BAG-2 (ANSI/AWS A5.8–77) may be used.
3–12.6 Delete this section and add: refer to RS 17–3.
3–12.7 Delete this section and add: refer to RS 17–3.
3–12.8 Delete this section, and substitute the following:
Identification Signs. Identification signs shall be provided for outside alarm devices. The sign should be located near the device in a conspicuous position and shall be worded as follows: "SPRINKLER FIRE ALARM—WHEN BELL RINGS CALL FIRE DEPARTMENT OR POLICE."
Add 3–12.9 Drains.
Add 3–12.9.1 Where vents are necessary for satisfactory electric alarm switch operations, such vents should be properly piped to a drain.
Add 3–12.9.2 Drains from alarm devices shall be so arranged that there will be no danger of freezing, and so that there will be no overflowing at the alarm apparatus, at domestic connections or elsewhere with the sprinkler drains wide open and under pressure.
Add 3–12.9.3 Drain from retarding chamber and electric alarm switch should preferably discharge through an open cone and be run separate from main system drains to a safe and visible point of free discharge or to sewer or ground drain. Drain from water-motor-operated alarm device may run separately to sewer or ground drain or may be connected to drain from retarding chamber at a point between such sewer and a check valve on this drain, a union or plug being inserted in the drain from the alarm device to permit inspection. Where checks are used they shall be so located as to have the equivalent of at least a four-foot head and shall not be installed in a vertical position.
Add 3–12.9.4 Where drains are conveyed to a sewer, a proper trap shall be provided.
Add 3–12.9.5 Where it is necessary to drain alarm valves outside the wall, an open discharge cone shall be provided inside to break the pipe line so that cold air will not conduct directly into the retarding chamber. Alternately, all drains shall have at least 4 feet of pipe beyond the valves, in a warm area.
3–13 Fittings.
Renumber Section 3–13.1.4 to 3–13.1.6.
Renumber Section 3–13.1.5 to 3–13.1.7.
Add a new section 3–13.1.4 to read as follows:
3–13.1.4 Fittings used in the assembly of copper tube shall conform to the following standards issued by the American National Standards Institute:
Bronze Flanges and Flanged Fittings 150 to 300 lb. ANSI B16.24–79
Add a new section 3–13.1.5 to read as follows:
3–13.1.5 Fittings used in the assembly of threadless copper pipe (Type TP) shall conform to the following standards:
Cast Bronze, Brazed-Joint Pressure Fittings Dimensions MIL F–1183 G–78 Chemical and physical properties ANSI/ASTM B 61–76 or ANSI/ASTM B 62–80 Bronze Flanges and Flanged Fittings 150 and 300 lb. ANSI B16.24–79
3–14 Valves.
3–14.1.1 Add the following sentence:
"An Approved indicating valve may be used in lieu of an O.S.&Y. gate valve wherever referred to in these modifications except where such valve is to be installed in conjunction with a pressure reducing valve."
3–14.2 Valves Controlling Sprinkler Systems.
Amend 3–14.2.1 as follows:
3–14.2.1 Each system shall be provided with a listed indicating valve so located as to control all sources of water supply except fire department connections [when arranged as specified in 2.7.3].
3–14.2.5 Delete.
3–14.2.6 Delete.
3–14.2.7 Delete.
Add 3–14.2.5 Where there is one water supply connection a check valve shall be installed. Such check valve may be a swing check, an approved fire meter or an approved detector check.
Add 3–14.2.6 Where a system having only one dry-pipe valve is supplied with city water and Fire Department connection, it will be satisfactory to install the main check valve in water supply connection in a vertical position immediately inside of the building after the main indicating valve.
Add 3–14.2.7 Where either a wet or dry pipe sprinkler system is supplied by city water and a Fire Department connection and has more than one riser with O.S.&Y. gate valve in each, and the whole system is controlled by one outside post indicator valve, it will be satisfactory to install the main check valve in the water supply connection immediately inside building. If the supply is controlled by an underground gate valve with an approved roadway box, the main check valve in the water supply connection should be installed immediately after the O.S.&Y. gate valve inside the building.
Add 3–14.2.8 Where a wet pipe sprinkler system is supplied by city water and a Fire Department connection with only one riser, the alarm valve will be considered as a check valve and an additional check will not be required.
Add 3–14.2.9 A gate valve should be installed on each side of each check valve under conditions other than described in Paragraphs 3–14.2.6, 3–14.2.7 and 3–14.2.8. However, this shall not apply to Fire Department Siamese check valves.
Add 3–14.2.10 Where a gravity tank is located on a tower in the yard, the gate valve on the tank side of the check valve shall be of O.S.&Y. type; the other shall be either an O.S.&Y. valve or an indicator post valve. Where a gravity tank is located on a building, both gate valves shall be the O.S.&Y. type; and all fittings inside the buildings, except the drain tee fill line, and heater connections, shall be under the control of a gate valve.
Add 3–14.2.11 In a city connection serving as one source of supply the city valve in the connection may serve as one of the required gate valves. An O.S.&Y. valve or an indicator post valve should be installed on the water supply side of the check valve.
Add 3–14.2.12 A connection from public water system shall not extend into or through a building unless such connection is under the control of an outside indicator post of O.S.&Y. gate or under the control of an inside O.S.&Y. gate valve located near the outside wall of the building.
Add 3–14.2.13 When a pump, located in a combustible pump house or exposed to danger from fire or falling walls, or a tank discharges into a yard main fed by another supply, either the check valve in the connection shall be located in a pit or the gate should be of the indicator post type, located a safe distance outside of buildings.
Add 3–14.2.14 Check valves on tank or pump connections, when located underground, may be placed inside of buildings and at a safe distance from the tank riser or pump, except in cases where the building is entirely of one fire area, when it is ordinarily considered satisfactory to locate the check valve over-head in the lowest level.
Add 3–14.2.15 All gate valves controlling water supplied for sprinklers shall be located where readily accessible and when necessary, permanent ladders, clamped treads on risers, chains and wheels, or other accepted means should be provided.
Add 3–14.2.16 Section Valves in Underground Fire Mains. Large yard systems shall have section controlling valves at appropriate points, in order to permit sectionalizing the system in the event of a break, or for the making of repairs or extension. (See Standard for Outside Protection, ANSI/NFiPA No. 24).
Add 3–14.2.17 Floor Valves. Floor control valves shall be provided where required or in special cases where area or height, or number of tenants is excessive, both in manufacturing and mercantile buildings, or where contents are more than ordinarily susceptible to damage. Floor valves shall be located where they are readily accessible. They are to be O.S.&Y. type located ahead of the inlet of any pressure reducing valve.
Add 3–14.2.18 Indicator Posts for Gate Valves.
Add 3–14.2.18.1 Outside control shall be provided.
Add 3–14.2.18.2 Where sprinklers are supplied from a yard main, an approved outside indicator post gate valve shall be placed in the connecting pipe at a safe distance from the building.
Add 3–14.2.18.3 Indicator post valves should be located not less than 40 feet from buildings; but where necessary to place a valve close to a building, it should be located at a blank part of the wall.
Add 3–14.2.18.4 When a building has no basement, and an outside post indicator control cannot be furnished, a short post indicator may be installed in a horizontal position in riser with handwheel projecting outside of wall.
Add 3–14.2.19 Pits for Underground Valves. Pits for underground valves except those located at the base of a tank riser, are described in the Standard for Outside Protection (ANSI/NFiPA No. 24). For pits protecting valves located at the base of a tank riser, refer to the Standard for Water Tanks for Private Fire Protection (ANSI/NFiPA No. 22).
Add 3–14.2.20 Securing of Valves. All gate valves in supply pipes to automatic sprinklers, whether or not of indicator or post pattern, shall be sealed open in a satisfactory manner.
Add 3–14.2.21 Valves controlling sprinkler supplied from the standpipe system shall be approved for standpipe service in the pressure zone in which it is installed. They shall be O.S.&Y. valves and shall be located ahead of the inlet of any pressure reducing valve installed.
3–15 Hangers.
3–15.1.10 Delete this section and substitute the following:
3.15.1.10 Maximum Distance Between Hangers. With Steel pipe as specified in this Chapter, the maximum distance between hangers shall not exceed 12 feet for 1 and 1 1/4 inch sizes nor 15 feet for sizes 1 1/2 inch and larger except as provided in 3–15.6 See Figure A-3-15.1.10.
With copper tube or pipe as specified in this chapter maximum spacing between hangers shall not exceed the distance indicated on Figure A–3–15.5.4 with steel band and ring hangers confirming therewith.
HANGER SPACING FOR COPPER PIPE AND COPPER TUBE—HORIZONTAL RUNS HORIZONTAL RUN HANGER SPACING
Tube Size Spacing 3/4" to 1" 5–8 feet 1 1/4" and 1 1/2" 8–10 feet 2" and 3" 10–12 feet 4"—8" 12–15 feet
SIZING OF SPS** STEEL STRAP AND RING HANGERS FOR USE WITH COPPER TUBE
SPS Steel Strap or Ring Hanger
Copper Tube Size inches Nominal Outside Diameter, inches Size inches Minimum Inside Diameter, inches 3/4 0.875 1/2 or v 1.050 or 1.315 1 1.125 3/4 or 1 1.315 1 1/4 1.375 1 1.660 1 1/2 1.625 1 1/4 0.840 or 1.050 2* 2.125 2* 2.375
** Above 2–inch, use the same SPS hanger size as the tube size.
** Standard Pipe Size Figure 1–3–15.5.4.
3–16.6.3 Delete this Section, and substitute the following:
The use of sprinklers with temperature ratings higher than ordinary shall be in accordance with the maximum ceiling temperatures given in table 3–16.6.1, except that intermediate or high temperature sprinklers may be used in other than light hazard occupancies. The use of high temperature sprinklers shall be limited to buildings with structural steel fully protected. High temperature sprinklers may also be used if there is high piled storage which is in compliance with NFiPA 231 and NFiPA 231 C.
3–17.3.2 Delete this section, and substitute the following:
Dry Pipe Valves. The alarm apparatus for a dry-pipe system shall consist of approved flow and low and high air alarm attachments to the dry-pipe valve. When a dry-pipe valve is located on the system side of an alarm valve, the actuating device of the alarms for the dry-pipe valve may be connected to the alarms on the wet-pipe system.
3–17.7 Delete this section, and substitute the following:
Identification Signs. It is essential to provide identification signs for outside alarm devices. The sign should be located near the device in a conspicuous position and shall be worded as follows: "SPRINKLER FIRE ALARM—WHEN BELL RINGS CALL FIRE DEPARTMENT OR POLICE."
Add 3–17.8 Drains.
Add 3–17.8.1 Where vents are necessary for satisfactory electric alarm switch operation, such vents should be properly piped to a drain.
Add 3–17.8.2 Drains from alarm devices shall be so arranged that there will be no danger of freezing, and so that there will be no overflowing at the alarm apparatus, at domestic connections or elsewhere with the sprinkler drains wide open and under pressure.
Add 3–17.8.3 Drain from retarding chamber and electric alarm switch should preferably discharge through an open cone and be run separate from main system drains to a safe and visible point of free discharge or to sewer or ground drain. Drain from water-motor-operated alarm device may run separately to sewer or ground drain or may be connected to drain from retarding chamber at a point between such sewer and a check valve on this drain, a union or plug being inserted in the drain from the alarm device to permit inspection. Where checks are used they shall be so located as to have the equivalent of at least a four-foot head and shall not be installed in a vertical position.
Add 3–17.8.4 Where drains are conveyed to a sewer, a proper trap shall be provided.
Add 3–17.8.5 Where necessary to drain alarm valves outside the wall, an open discharge cone shall be provided inside to break the pipe line so that cold will not be conducted directly into the retarding chamber. Alternately, all drains shall have at least 4 foot of pipe beyond the valves, in a warm area.
CHAPTER 4—SPACING, LOCATION AND POSITION OF SPRINKLERS
4–1.2 Delete.
4–2.2.1 Delete the first sentence and add the following:
"The maximum floor area to be protected by a single riser, from a control and alarm device, on any one floor shall be as follows:"
4–4.7.1 Delete.
4–4.7.2.1 Delete.
4–4.7.2.2 Delete.
4–4.7.2.3 Add to last sentence:
when required by other sections of this code
Delete the Exception.
4–4.7.2.4 Delete.
4–4.8 Add the following:
Sprinklers shall be provided in chute vestibules on all floors, if no vestibule exists, then sprinklers shall be provided above chute doors and shall be located no more than 1-foot horizontally from face of chute door.
All building service chute sprinkler systems shall be provided with a local water flow and valve supervisory alarm and be connected to an authorized fire alarm central office.
4–4.8.1 Delete.
4–4.8.2 Delete.
4–4.8.2.4 Delete.
Add 4–4.17.4 Safe deposits or other vaults of fire-resistive construction will not require sprinkler protection when used for the storage of records, files and other documents when stored in metal cabinets.
4–4.8.1 Delete and substitute the following:
In cooking areas protected by automatic sprinklers, sprinklers shall be provided to protect commercial-type cooking equipment and ventilation systems that are designed to carry away grease laden vapors unless otherwise protected (see RS 13–2 and RS 13–3). Sprinklers shall be so located as to give complete coverage of cooking surfaces, within exhaust ducts, within exhaust hood plenum chamber, and under filters, if any.
Add 4–4.16.4 Safe deposits or other valves of less than 1,000 cubic feet in size of fire-resistive construction may not require sprinkler protection when used for the storage of records, files and other documents, when stored in metal cabinets. These vaults shall be equipped with either a smoke or heat detection system connected to an authorized fire alarm central office.
4–4.17.1 Delete, and substitute the following:
In cooking areas protected by automatic sprinklers, sprinklers shall be provided to protect commercial-type cooking equipment and ventilation systems that are designed to carry away grease laden vapors unless otherwise protected (see RS 13–2 and RS 13–3). Sprinklers shall be so located as to give complete coverage of cooking surfaces, within exhaust ducts, within exhaust hood plenum chamber, and under filters, if any.
4–4.19.2 Add the following:
and provided that hard wired smoke detectors are provided in the sleeping rooms.
Add section 4-4.19.4 to follow section 4-4.19.3 as follows:
4-4.19.4 In buildings and spaces classified in Occupancy Groups J-2 and J-3, sprinklers may be omitted from bathrooms, water closet compartments, general toilet rooms and shower rooms.
Add section 4-4.19.5 to follow section 4-4.19.4 as follows:
4-4.19.5 In buildings and spaces classified in Occupancy Groups J-2 and J-3, sprinklers may be omitted from clothes closets, linen closets and pantries.
CHAPTER 5—TYPES OF SYSTEMS
5–3.4 Delete and substitute the following:
Location and Spacing of Fire Detection Devices. Spacing of fire detection devices shall be in accordance with their listing by nationally recognized testing laboratories or in accordance with manufacturer's specifications, subject to the approval of the Commissioner of Buildings.
5–3.5 Delete and substitute the following:
Location and Spacing of Fire Detection Devices. Spacing of fire detection devices shall be in accordance with their listing by a nationally recognized testing laboratory or in accordance with the manufacturer's specifications, subject to the approval of the Commissioner of Buildings.
Fig. 5–5.4 Delete and substitute the following:
Fig. 5–5.4 See detail of Typical Installation.
CHAPTER 6—OUTSIDE SPRINKLERS FOR PROTECTION AGAINST EXPOSURE FIRES
6–1 Water Supply and Control. Delete.
6–2 System Components. Delete.
CHAPTER 7—HYDRAULICALLY DESIGNED SPRINKLER SYSTEMS
7–1.1.2 Delete and substitute the following:
7–1.1.2 The design basis for such a system supersedes the rules in the sprinkler standard governing pipe schedules except that all systems continue to be limited by area, and pipe shall be not less than 1 inch nominal for ferrous piping and 3/4 inch nominal for copper tube and threadless copper pipe. The size of the pipe, number of sprinklers per branch line and number of branch lines per cross main are otherwise limited only by the available water supply.
However, sprinkler spacing and all other rules covered in this and other applicable standards shall be observed.
7–2.1 Delete and substitute the following:
Design criteria and calculations shall be submitted to the Commissioner along with the plans to obtain the necessary approval.
Table 7–4.3.1.4 Delete under column Pipe or Tube, "Plastic (listed)—All" and under C Value, Delete "150".
CHAPTER 8—PIPE SCHEDULE SYSTEMS
8–1 Delete and substitute the following:
The provisions of this Chapter shall apply to buildings of Class 1 construction, predominantly light hazard occupancy, and more than 100 feet high.
Add 8–1.2.1 Combined Systems Risers—Risers providing the water supply for both standpipe and sprinkler systems shall have a minimum diameter of 6-inches, however, a minimum diameter of 4-inches may be authorized in existing buildings if hydraulic calculations indicate that an adequate supply of water can be assured.
Add 8–1.2.2 When a combined riser is fed by a special service fire pump, a minimum diameter of 4-inches is required to feed fire hose stations. Riser size beyond last hose station is to be determined by hydraulic calculations.
Add 8–1.3.1 In buildings having mezzanine floors, large platforms, or large openings between floors which cannot be closed or satisfactorily cut off, the possibility that all or most of the sprinklers might be opened by a single fire should be considered in determining the size of risers. Where occupancy and construction are exceptionally good, and where there is a little likelihood of a fire spreading beyond the vicinity of its origin, the size of the feed main may be based on the total number of sprinklers in the main area plus half the number in the secondary area. A sprinkler water curtain may be considered an acceptable cut off for openings of less than 1,000 square feet.
Add 8–1.4 Sizes for Domestic Water Piping. Where permitted by the building code, 10 or less heads, that are connected to the domestic water system shall have the piping sized in accordance with the tables herein, and the domestic water line to which the sprinkler piping is connected shall be at least the size of the sprinkler line connected thereto. Connections may be made directly to cross-connections or headers.
8–3.2 Delete.
8–4.2 Add the following to the first sentence: "or as modified by Table 2–2.1B."
8–4.3 Delete.
8–4.4 Add the following:
8–4.4 Combined Systems. Risers providing the water supply for both standpipe and sprinkler systems shall have a minimum diameter of 6 inches: provided, however, a minimum diameter of 4 inches may be authorized in existing buildings if hydraulic calculations indicate that an adequate supply of water can be assured.
CHAPTER 10—DELETE
Appendix A, B and C and D shall be considered part of this Reference Standard, subject to the following modifications:
A–1–7.2.1 Delete.
A–1–7.3.1 Delete.
A–1–7.3.2 Delete.
A–1–7.3.3 Delete.
A–1–7.4 Delete and substitute the following:
A–1–7.4 New installations protecting extra hazard occupancies may be hydraulically designed or pipe schedule systems may be utilized, provided that a sufficient volume of water is supplied, and the water pressure is adequate. When the pipe schedule is used hydraulic calculations shall be done to prove that adequate water volume and water pressure are available.
A–1–7.4.1 Delete.
A–1–8.1.2 Delete and substitute the following:
A–1–8.1.2 Used equipment shall not be permitted unless completely overhauled by the manufacturers; and shall be subject to the approval of the Commissioner.
A–1–9 Delete.
A–2–2.3.3 Delete.
A–2–6.3 Amend sub-section titled "Location of Pressure Tanks" to read as follows:
Pressure tanks shall be located at or above the top level of sprinklers.
A–2–7.1 Delete.
A–2–7.2 Delete.
A–2–7.3 Delete.
A–3–1.1.5 Delete.
A–3–3.2 Delete.
A–3–3.7 Delete.
A–3–7.4 Delete and substitute the following:
A–3–7.4 The fire hazard of the brazing and welding process should be suitably safeguarded. Fire guards having Certificates of Fitness from the Fire Department shall be provided as required, and portable fire fighting equipment shall be provided.
Add new sentence:
Self-cleaning fluxes shall not be used. Continued corrosive action after the soldering process is completed could result in leaks from the seats of sprinklers.
A–3–10.2 In second paragraph, delete the words "copper tube" and substitute "brass piping or equivalent".
A–3–12.4 Delete and substitute following:
A–3–12.4 The fire hazard of the brazing and welding process should be suitably safeguarded. Fire guards having Certificates of Fitness from the Fire Department shall be provided as required and portable fire fighting equipment shall be provided.
A–4–4.4.4 Add to end of first sentence:
Subject to the approval of the Commissioner.
A–5–3.3 Delete paragraph (b) and add:
(b) The dry-pipe valve should be adequately pressurized to conform to manufacturer's design and available water pressure.
B–4–2.4.6 Delete.
B–7 Delete.
Appendix C Referenced Publications Delete.