NYC Administrative Code RS 17-2B STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES

ANSI/NFPA No. 13D—1994 Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes.

Modifications—The provisions of NFPA No. 13D—1994 shall be subject to the following modifications. The section and paragraph numbers are from that standard.

PREFACE

Change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.

CHAPTER 1—GENERAL INFORMATION

Section 1-3 Delete the definition of Multi-purpose Piping System.

Section 1-3 Delete the definition of Pre-engineered System.

Section 1-5.2 Revise the exception to read: Listing may be waived for tanks and pumps.

Section 1-5.3 Delete

Section 1-5.4 Delete and substitute with the following:

Section 1-5.4 Testing of a system can be accomplished by pressurizing the system 50 pounds (3.5 bar) above the normal system operating pressure and checking visually for leakage at each joint or coupling.

Fire Department connections are not required for systems covered by this standard, but may be installed at the discretion of the owner. In these cases, hydrostatic tests in accordance with Reference Standard RS 17-2 are necessary.

Dry systems should also be tested by placing the system under 40 pounds (2.8 bar) air pressure. Any leak that results in a drop in system pressure greater than 2 psi (0.14 bar) in 24 hours should be corrected. Check for leaks using soapy water brushed on each joint or coupling. Leaks will be shown by the presence of bubbles. This test should be made prior to concealing of piping.

CHAPTER 2—WATER SUPPLY

Section 2-2 Add subparagraph (e) as follows:

(e) A common supply main to the building serving both sprinkler and domestic uses may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve, i.e., house control valve, will shut off the domestic water supply.

Section 2-3 Delete

CHAPTER 3—SYSTEM COMPONENTS

Section 3-1.1 Delete the exceptions.

Add new Section 3-1.5 to read as follows:

Section 3-1.5 Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:

(a) Central station, proprietary or remote station signaling service, or

(b) Local signaling service that will cause the sounding of an audible signal.

Exception—Underground gate valves with roadway boxes need not be supervised.

Section 3-3.2 Delete and substitute the following:

Section 3-3.2 Other types of pipe or tubes may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.,

(a) Pressure rating

(b) Beam strength (hangers)

(c) Corrosion (chemical and electrolytic)

(d) Resistance to failure when exposed to elevated temperatures

(e) Methods of joining (strength, permanence, fire hazard)

(f) Availability of fittings (for sprinkler outlets and proper routings)

(g) Physical characteristics related to integrity during earthquakes

(h) Toxicity

(i) Combustibility

(j) Movement during sprinkler operation (water distribution)

Nonmetallic pipe shall comply with the portions of the ASTM standards specified in Table 3-3.2 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe shall only be used in wet pipe systems. Nonmetallic pipe shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.

Table 3-3.2 Delete Specification for Special Listed Polybutylene (PB) Pipe and ASTM D 3309.

Section 3-3.6 Delete and substitute the following:

Section 3-3.6 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-5, BAG-2 (ANSI/AWS A5.8-89) or other approved methods may be used. Lead free solder joints may be permitted for wet pipe systems when the temperature classification of the installed sprinklers is Ordinary or Intermediate.

Section 3-3.7 Delete and substitute the following:

Section 3-3.7 Other types of fittings may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of fittings other than that described above must involve consideration of many factors as described in Section 3-3.2. Nonmetallic pipe fittings shall comply with the portions of the ASTM standards specified in Table 3-3.7 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe fittings shall only be used in wet pipe systems. Nonmetallic pipe fittings shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.

Section 3-6 In the Exception, change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.

CHAPTER 4—SYSTEM DESIGN

Section 4-3.3.3.1 Add "The use of antifreeze solutions other than glycerine-water in sprinkler systems using plastic pipe shall not be permitted."

Section 4-3.3.4 shall be modified to read as follows:

Section 4-3.3.4 Arrangement of supply piping and valves. All permitted antifreeze solutions shall be installed in accordance with RS 17-2.

Figure 4-3.3.4 Delete and substitute with:

Figure 5-5.4 "Detail of Typical Installation" of Reference Standard 17-2.

Section 4-4.1 Exception No. 1—Delete NFPA 13, Standard for the installation of sprinkler systems and revise to read "Reference Standard 17-2."

Section 4-4.2 Revise to read as follows:

Section 4-4.2 Minimum Pipe Size—Minimum pipe size including copper and any other acceptable piping shall be 3/4 in. (19 mm).

Section 4-4.3 Delete the exception.

Section 4-6 shall be modified to read as follows: "Sprinklers shall be installed in all areas with the following exceptions:

Exception No. 1—Sprinklers are not required in attics not provided with floors.

Exception No. 2—Sprinklers are not required in clothes closets, linen closets and pantries.

Exception No. 3—Sprinklers are not required in bathrooms, water closet compartments, general toilet rooms and shower rooms.

Exception No. 4—Sprinklers are not required in garages, provided that at least one sprinkler head is located within 3 feet (914 mm) of any communicating opening between the garage and the dwelling.

Exception No. 5—Sprinklers are not required in open attached porches, carports and similar structures."

CHAPTER 5—LIMITED AREA DWELLINGS

Delete in its entirety.

CHAPTER 6—REFERENCED PUBLICATIONS

Delete in its entirety.

APPENDIX A—EXPLANATORY MATERIAL

Section A-1-1 Delete third sentence of first paragraph and revise second sentence to read:

"Residential portions of any other buildings shall be protected with residential sprinklers in accordance with the New York City Building Code."

Revise last paragraph to read "For protection of multiple dwellings, refer to the New York City Building Code."

Section A-1-2 Delete

Section A-1-3 Revise to read "System control valves shall be the indicating type and shall be approved/accepted type."

Section A-1.4 Delete

Section A-1-5.4 Delete

Section A-2.2 Delete entire section including all related diagrams, except for the following:

"When a tank is used for both domestic and fire protection purposes, a low water alarm activated when the water level falls below 110 percent of the minimum quantity specified in Section 2-1 should be provided".

Section A-2.3 Delete all related diagrams.

Section A-2.3(a) Delete

Section A-3-3.1 Delete

Section A-3-3.2 Delete

Section A-3-3.7 Delete

Section A-3-5.6.1 Revise to read as follows:

Section A-3-5.6.1 Decorative painting of residential sprinklers is not to be confused with the temperature identification colors as referenced in Reference Standard 17-2.

Section A-5-5 Delete

Table A-1.2(a) and (b) Delete

APPENDIX B—REFERENCED PUBLICATIONS

Delete in its entirety.