NYC Administrative Code Title 27, Chapter 1 Building Code, part 15 of 17
RS 17-3 to RS 17-4: 5 sections.
RS 17-3. STANDARDS FOR THE INSTALLATION OF FIRE, SPRINKLER, STANDPIPE, SMOKE DETECTION, OXYGEN, NITROUS OXIDE, AND OTHER ALARM AND EXTINGUISHING SYSTEMS
"Installation, source of energy, wiring and other requirements shall comply with the applicable provisions of sections one through fourteen, inclusive; provided, however, that fire protection pre-signal systems for buildings in occupancy group G, of construction group 1-A (fireproof) may comply with the provisions of section 15 in lieu of sections 1 through 14, when such pre-signal systems are installed or existing systems are modified to provide fire alarm signal service under adverse malicious false alarm conditions, and when permitted by the Fire Commissioner."
1. A. SOURCES OF ELECTRICAL POWER.—
Two sources of electrical power shall be provided as follows:
(1) The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
(2) The secondary source shall be an emergency power system (as per 27-396), emergency generator and/or battery power.
One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the "New York City Electrical Code." The primary source of power and the secondary source (if emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208-volt side. The incoming supply connections shall comply with the NYC Electrical Code, and the fused cutout panel shall comply with the requirements specified herein before.
B. PRIMARY POWER SOURCE
(1) The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
(2) Partial systems such as strobe light-control panels, partial fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and an identified, locked fused cutout box located within 5 feet of the tap.
Where an emergency power system (E.P.S.) is provided in accordance with section 27-396.4, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.
C. SECONDARY POWER SOURCE
The secondary service to the fire alarm system shall be provided as follows:
(1) If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
(2) If the building has an emergency generator supplying power to any of the loads listed in 27-396.4, the secondary source shall be the generator.
(3) For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17–5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by
(a) 6 hour total system load for systems with voice communication capability (A 45 minute period of voice/alarm operation at maximum connected load shall be considered equivalent to 6 hours of total system operation), or
(b) 15 minutes of total system load for systems without voice capability.
(4) Partial systems and/or associated systems may derive their secondary supply from batteries whether or not the building is equipped with an emergency generator. Batteries shall be designed for 24-hour supervisory operation followed by 5 minutes of total system load.
All alterations to any existing approved fire alarm system involving or consisting of the replacement of the Fire Command Station, Fire Alarm Control Panel, Central Processing Unit, Floor Control Units, Remote Control Units, Data Gathering Panels, Terminal Transmission Board, and other similar or equivalent controls or control panels shall be required to comply with section C(3) above. For systems in buildings that are in compliance with sections C(1) or C(2) above, compliance with section C(3) is optional.
2. CLASSIFICATION OF SYSTEMS.—Systems shall be classified as follows:
(a) Manual interior fire alarm.
(b) Standpipe fire line telephone and signaling.
(c) Automatic heat, smoke, or products-of-combustion fire detecting and alarm, as follows:
(1) Fixed temperature solder or bimetallic spot type heat detection.
(2) Fixed temperature heat detecting wire.
(3) Rate-of-rise pneumatic tube heat detection.
(4) Photoelectric type smoke detection.
(5) Products-of-combustion ionization detection.
(d) CO2 extinguishing.
(e) Hood smothering and fan shutdown.
(f) Sprinkler alarm.
(g) Ventilation duct smoke and fire detection and fan shutdown.
(h) Oxygen and nitrous oxide alarm.
(i) Escalator fire door alarm.
Where fire alarm, sprinkler alarm, and/or automatic fire detection systems are installed in the same building, wiring interconnections shall be provided between the control boards of the Systems, and necessary actuating relays and transmitters shall be provided in the control boards, so that actuation of the sprinkler alarm and/or fire detection systems will activate the fire alarm system, and so that actuation of the fire alarm system will de-energize all fans, with the exception of those fans used for the Stair Pressurization System, controlled by the automatic detection system.
3. WIRING.—
A. Power Conductors (Above 75 volts) shall be:
(1) Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW; minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
(2) Cable type MI, M.E.A. approved for 2-hour fire resistance rating.
B. Low Voltage Conductors (75 volts and less) shall be:
(1) Copper; THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, XHHW, minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT)
(2) Minimum wire size No. 18 AWG.
(3) Multiconductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
(a) Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150 C; colored red.
(b) Red colored jacket overall; minimum thickness 25 mils.
(c) Cable printing as per UL1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE" legible without removing jacket.
C. Installation of Conductors and Raceway shall be in accordance with the following:
(1) Power conductors shall not be installed in common raceways with low voltage conductors.
(2) Comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
(3) Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
(4) Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment. In any suppression and extinguishing system activated by automatic fire detection, including, but not limited to, pre-action sprinkler, deluge sprinkler, clean air agent, halon, range hood, CO2 and dry chemical, multi-conductor cables shall be installed in RMC, IMC, or EMT.
(5) All wiring within mechanical and elevator equipment rooms shall be run in raceway.
(6) Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
(7) Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT), except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing Reference Standard 17 conductors.
(8) Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
(a) Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support. Support independently from the building structure.
(b) Secure by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Secure in place at intervals not exceeding 5'-0" on centers and within 12" of every associated cabinet, box or fitting.
(9) Installation of raceways, boxes and cabinets shall comply with the following general requirements.
(a) Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
(b) Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
(c) Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
(d) Raceways or cables shall not penetrate top of any equipment box or cabinet.
(10) All conduits supplying 120-volt power to the fire command station and/or fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
(11) For cabinets whose 120-volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel-framed buildings, a connection to local steel structure will be acceptable.
(12) Splices and terminations of wires and cables shall be as follows:
(a) Permitted only in boxes or cabinets specifically approved for the purpose.
(b) Utilize mechanical connections specifically approved by U.L. 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
(13) Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e., by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.
4. FIRE ALARM SENDING STATIONS.—
(a) In manual fire alarm signal systems, the metal case enclosing exposed or surface alarm boxes shall be of cast iron or cast No. 43 aluminum or approved aluminum-zinc alloy, and shall be drilled and tapped to receive the conduit. Where exposed to moisture, the box shall be enclosed in a weatherproof outer shell. In new buildings, approved galvanized sheet steel back-boxes embedded in the wall may be used and the conduits shall be secured by lock nuts and bushings.
(1) A floor warden station with a speaker mechanism having a fire resistant assembly and a manual fire alarm station may be installed in the same housing. A self-restoring push button that will silence an alarm speaker while being held in place, shall be required wherever such speaker is within 8 feet of a floor warden station.
(b) All current-carrying parts shall be insulated from parts carrying current of opposite polarity with approved insulating material.
(c) All coded pull-lever type stations shall be constructed with a door or other approved means to protect the pull lever against accidental injury. The wording "IN CASE OF FIRE—OPEN DOOR AND PULL DOWN LEVER" in raised letters, or equivalent instructions, shall appear on the door.
(d) In systems using break-glass or break-rod type stations, at least one extra glass rod or glass pane for each station in the system shall be kept in the building. Break-glass boxes shall have the glass rod or pane mounted on the surface of the station covers or mounted internally in such a manner that the glass must be broken to actuate the sending station. Suitable hammers on chains attached to the boxes, or other approved means of breaking the glass, shall be provided.
(e) The box or station of a coded system shall be so designed that once started, the proper transmission of a complete set of signals cannot be interfered with by manipulation of its starting device.
(f) Each closed circuit coded box or station shall be arranged to send a definite code of signals to indicate the floor or portion of the floor on which it is located.
(g) Not less than 3, nor more than 20, taps or blasts shall be given at each revolution of the code wheel. The code wheel shall revolve at least four times for each operation of its starting device and shall be of metal properly insulated from ground.
(h) Boxes or stations used in systems in which whistles, vibrating bells, or horns are employed shall be so timed that the sounding devices will give the code signals clearly.
(i) Contact points shall be in multiple.
(j) Contact points and contacts of the testing devices shall be of silver or other approved material and of the scraping type. The contact points and contacts shall be secured in a substantial manner to springs of phosphor bronze or other approved material, and shall be so designed as to positively break a circuit carrying 0.10 ampere at 250 volts under actual operating conditions.
(k) Lever boxes shall be so designed as to automatically wind when the lever is pulled for an alarm. Boxes requiring glass replacements shall be so arranged that replacement cannot be made without resetting the mechanism for another alarm.
(l) Where it becomes necessary to install more than one set of contacts operating from code wheel, approval must be obtained from the fire commissioner before the installation. This shall not include pre-signal features. The box shall have its code signal number plainly marked thereon.
(m) Uncoded boxes.—
(1) Uncoded closed circuit fire alarm stations may be operated by a break-glass or break-rod or a pull lever device so arranged that the alarm cannot be interfered with except by resetting or replacement of the glass or rod by an authorized person.
(2) The construction and materials shall be equivalent to that of the standard approved type coded closed circuit station, except that the contacts shall be of sufficient capacity to safely carry out the entire operating current of the gong circuit without excessive heating.
(n) Station testing devices.—
(1) Each fire alarm system shall be provided with an auxiliary device to test the signaling devices. The auxiliary device shall be located in one of the alarm boxes or mounted on the control board. Such testing device shall be arranged so that the test is made without operating the break wheel of the box or interfering with the dual operating feature.
(2) Provisions shall be made for a silent test of coded alarm box mechanisms without operating the signaling devices. Such test device shall be designed to prevent any person, except those in authority, from operating the same and to prevent the possibility of the box being left inoperative after the test.
5. ALARM SOUNDING DEVICES.—
(a) Alarm sounding devices shall be sufficient in number to be clearly audible to all occupants of a building. Approved gongs shall be provided as the sounding devices. Where gongs or bells are not audible, approved horns or whistles may be provided. Chimes and other alarm sounding devices may be installed only with the approval of the commissioner.
(b) Gong shells shall be pinned to prevent turning and then securely fastened to their supports by a machine cap screw at least 3/8 in. in diameter.
(c) Gong shells shall be covered with a rust preventive. The gong support and gong frames shall be cast in one piece.
6. FIRE ALARM SYSTEM CONTROL BOARDS.—
(a) Supervising circuit.—
(1) A small current flow shall be maintained to constantly supervise each circuit. A millimeter, or other approved current indicator, shall be provided and connected so as to indicate the supervising current.
(2) The supervising circuit shall be provided with a trouble bell operating an open circuit and arranged to ring continuously in case of failure of the system. The trouble bell shall be so located that it will be within audible range of a responsible person in the building.
(3) Trouble bells may be fitted with silencing switches only when the switch is connected in such a manner that the act of silencing the bell by the operation of the switch automatically transfers the trouble signal to a red lamp on the control board. When the trouble has been repaired, the alarm bell shall ring until the silencing switch has been reset to operate under normal conditions.
(4) The trouble bell shall be of the vibrating type and shall give a distinctive signal.
(b) Protection of sending and sounding devices.—
(1) In fire alarm signal systems, moving parts of sending stations and sounding devices shall be enclosed in metal casings, made dust proof and damp proof when necessary, and clearly marked with instruction for use.
(2) Whenever necessary, hammer rods of gongs shall be suitably protected against mechanical damage by the use of a guard or equivalent means. If subject to possible mechanical damage, the entire device shall also be enclosed in a protecting case made of approved wire netting or perforated metal. All casings shall be insulated from current carrying parts, but shall be grounded to the conduit.
(c) Standards of electric alarm apparatus.—All electrically actuated apparatus used in fire alarm systems shall be so designed and constructed that it will operate satisfactorily at a current flow of 15 per cent above or below the normal operating current.
(d) Insulation.—
(1) Insulating materials used shall be varnished cambric, bakelite, mica, or equivalent insulating material.
(2) The use of fiber or paper as an insulating material for the fire alarm signal systems is prohibited.
(3) The insulating materials used shall be capable of withstanding an insulation breakdown test of 1,000 volts a.c. plus twice operating voltage applied for 1 minute.
(e) Electromagnets.—
(1) Electromagnet windings shall be impregnated with an insulating, moisture repelling compound of the silicone or epoxy type.
(2) Electromagnet coils used on alternating current, when composed of enameled wire, shall have an additional approved insulation on each wire. The coils may be of the form-wound type.
(3) A protective cover to prevent mechanical damage shall be provided over the entire coil.
(4) Electromagnetic coils shall be fastened to prevent floating.
(5) Electromagnet cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.
(6) Electromagnet cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and promote efficiency.
(7) Electromagnet cores of relays and gongs shall be treated to prevent corrosion. Paint or varnish shall not be used for this purpose.
(8) Nonmagnetic freeze pins shall be used to prevent two magnetic surfaces from making physical contact with each other.
(f) Relays.—
(1) The armatures of all relays shall depend on gravity or magnetic attraction for their operation. However, armature operation may be initiated by flat-type springs when permitted by the commissioner. The use of spiral springs is prohibited.
(2) Adjustments shall be of such a character that they can be securely locked.
(3) Contact points shall be of sufficient area to carry the current used in operation and to insure long life. They shall be of pure silver or other approved material and properly riveted to their support. Contact arms shall be of phosphor bronze, and shall be of the dead beat type. Contact assemblies shall be of such a character that their operation is of a scraping self-cleaning nature. The use of condensers across contacts in order to absorb the arc in any part of a fire alarm circuit is prohibited.
(4) Relays shall be free from objectionable hum when used on alternating current.
(g) Time limit delay device.—
(1) All gong circuit shell and special signal apparatus may be protected by a time limit delay device. This time limit delay device shall consist of a heating coil so designed that the normal operating current will have little or no effect upon a thermostatic bimetallic bar or strip contained therein. Any abnormal increase over operating current or the continued cumulative heating effect thereof after a period of at least 3 minutes, but not more than 20 minutes, shall cause the thermostatic element to expand. The expansion of this element shall automatically open the source of current supply to the gongs or devices protected. The operation of the time limit delay device shall cause the trouble bell to ring.
(2) Time limit delay devices shall be so connected in the fire alarm circuit that their operation will not open the fire alarm box circuits.
(3) Where, due to the extent of the installation, it becomes necessary to install a number of time limit delay devices, the operation of a single time limit delay device shall not affect other sounding devices similarly protected.
(4) A contactor relay to operate the sounding devices shall be provided on all direct gong circuits exceeding two in number. Gong circuits not requiring contactor relays shall be operated by contacts properly phased for the armature of the box circuit relay.
(5) A separate time limit delay device, contactor supervisory relay and gong supervisory relay, shall be provided for each four gong circuits or fraction thereof.
(h) Switches.—Triple pole, double throw, broken back knife switches properly supervised, and connected to emergency resistors, shall be provided on all box and gong circuits when the circuits exceed three in number.
(i) Instruments.—A separate approved milliammeter, or other approved current indicator, shall be provided for the box circuit and each four gong circuits on the control board when the gong circuits exceed three in number. A separate milliammeter shall be provided to indicate the supervisory current of contactor relays and emergency switch circuits. This meter shall be known as the "board meter."
(j) Resistors.—
(1) Resistors shall be of the vitreous enameled type and shall be mounted on the front or face of control panels. Wire wound resistors, protected by a suitable metal guard, may be used when permitted by the commissioner. Ferrule or knife contact type resistors shall not be used.
(2) A protective resistor shall be placed in the negative, or live, lead of all box circuits to protect the contacts of the boxes in the event of a ground. This resistor shall have a resistance of at least 300 ohms, but no more than 750 ohms.
(3) All relays, current indicators, resistors, time limit delay devices, and other apparatus used in connection with the operation and supervision of closed circuit fire alarm signal systems shall be properly mounted on a panel of approved material in a metal cabinet provided with lock and key. The control board shall be located in a place where it will be subject to the least vibration and least chance of mechanical damage. The location shall be free from moisture, flammable gases, and dust. Furthermore, the control panel shall be located so that it can be kept under the frequent view of a responsible occupant of the building delegated by the owner to be in charge.
(4) Control board panels shall be of insulating material such as ebony asbestos, bakelite, or other approved materials at least 1/2 in. thick. Control boards mounted in each cabinet shall be securely fastened in each corner.
(5) Provision shall be made for sufficient wire gutter space around the panel. Gutter space shall be a minimum of 2 in. at sides, top, and bottom. Wire in gutter space shall be properly laced in a neat and workmanlike manner on all control boards.
(6) Conduit knockouts shall not be provided in the top of the control board cabinet.
(7) A wiring diagram of the alarm system approved by the commissioner and the approved card of instruction properly marked and securely fastened shall be provided within the control board cabinet. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be framed under glass or equivalent material.
(8) All control board cabinets shall be provided with sight holes and glass panels to make meters on the inside of the cabinets visible from the outside.
(9) Control boards may be of the solid state circuitry type with modular construction and replacement components.
7. PAINTING OF EQUIPMENT.—
All enclosing cases for fire alarm, sprinkler alarm, smoke detection, and oxygen and nitrous oxide alarm apparatus shall be painted fire department red, except where approval is given by the commissioner to deviate from this requirement.
8. CLOSED CIRCUIT ANNUNCIATORS.—
(a) Annunciators used in connection with unit and general fire alarm systems shall be of an approved closed circuit type. The annunciator shall have approved types of relays equipped with a target shutter or other indicating device. The indicating device shall have marked thereon a description of the purpose it serves. The printed designation on unit or building annunciator's indicators shall be legible. The mechanism shall be so arranged that once operated the indicating device must be reset manually.
(b) A unit annunciator shall be so designed that the operation of any station in the unit causes a visible and audible signal. The unit annunciator shall be actuated by contact on a code wheel of the fire alarm station, or by contact on a relay connected to the fire alarm box circuit. In no case shall the station fire alarm circuit be used for this purpose.
(c) Trouble annunciators shall be so arranged that the indicating device will reset automatically when the cause of the trouble has been removed. The trouble annunciator shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit panelboard of unit annunciators. The trouble annunciator shall be actuated by the operation of contacts on all supervisory relays. Each relay of this annunciator shall be provided with two sets of contacts so arranged that one set will operate the 110-volt trouble signal, and the other set will actuate the register, if a register is used.
(d) A trouble buzzer switch lamp shall be mounted on the inside of each unit annunciator cabinet on the panel.
(e) A trouble bell, switch, and lamp shall be mounted on the inside of each trouble annunciator cabinet on the panel. Trouble bell may be placed at a distance from the annunciator by approval of the commissioner.
(f) Relay drops of annunciator shall be so designed that vibration from without or that caused by the trouble signal within will not operate the indicating devices.
(g) All annunciators shall be installed in a separate red enameled steel cabinet provided with an approved lock and key. Annunciators shall be marked in white letters at least 1 in. high with the words: "FIRE ALARM ANNUNCIATOR, ZONE" or "FIRE ALARM TROUBLE ANNUNCIATOR", whichever the case may be.
9. AUTOMATIC HEAT AND SMOKE FIRE DETECTION SYSTEMS.—
(a) Classifications.—Automatic heat and smoke fire detection systems shall be classified as follows:
(1) Fixed temperature solder or bimetallic spot-type heat detection.
(2) Fixed temperature heat detecting wire.
(3) Rate-of-rise pneumatic-tube heat detection.
(4) Photoelectric-type smoke detection.
(5) Products-of-combustion ionization detection.
(b) Plans.—Floor layouts shall show the automatic fire alarm signal equipment and its location, number of thermostatic heads, transmitters, control board, and sounding apparatus; also, all exits, partitions, and enclosures shall be identified on the layouts. The layouts shall be approved by the commissioner and the fire commissioner before work is started on the installation.
(c) Wiring and electrical apparatus.—
(1) All electrical wiring, signal apparatus, and thermostatic actuating devices shall be connected and operated on closed supervised electric circuits, and conform to the requirements for the installation of interior fire alarm systems.
(2) Approved automatic-type systems shall be installed under the supervision of the commissioner.
(3) When installed in connection with approved interior alarm systems, automatic systems shall have this connection made through an approved combination manual and automatic transmitter.
(4) When installed in connection with dry valves or other fire protective devices, automatic systems shall actuate the dry valve or devices through an approved magnetic trip.
(5) In automatically operated systems, each system shall have at least one manual fire alarm box as an auxiliary means for actuating the alarm system.
(6) Automatic systems shall be arranged to transmit a prescribed code signal as required by the fire commissioner.
(7) Closed circuit annunciators shall be provided in connection with automatic thermostatic systems when required by the fire commissioner.
(8) Transmitters, manual alarm boxes, testing boxes, and annunciators shall be so installed that a considerable jar cannot start their mechanism.
(9) Transmitters that require rewinding after operation shall be provided with a trouble bell to indicate a run-down condition.
(10) The trouble bell shall be arranged to give a distinctive signal different in tone from the trouble bell supervising the thermostatic alarm circuit.
(11) Each automatic thermostatic system shall have one or more combination manual and automatic transmitters located in a natural path of escape for each thermostatic circuit, wherever the thermostatic alarm actuates the interior alarm system.
(12) All thermostatic devices shall operate on a closed supervised electric circuit.
(13) The thermostatic wiring may return to the control board and the end line resistor mounted thereon. This end line resistor may be in the form of a supervising relay.
(d) Control boards.—Thermostatic automatic systems shall be operated from properly supervised approved closed circuit control boards installed in a locked metal cabinet, which shall be painted fire department red and marked in 1 in. high white letters with the words "AUTOMATIC THERMOSTATIC FIRE ALARM".
(e) Signal apparatus.—Gongs, horns, or bells, shall be provided, where shown on plans in connection with each thermostatic alarm system, so that the signals will be clearly audible throughout the building or portion of the building requiring a fire alarm system. All thermostatic alarm systems shall be connected to an approved central office for transmission of an early alarm to the fire department.
(f) Testing.—The thermostatic alarm system shall be so arranged that a periodic test of the entire system can be made by the person in charge of the building.
(g) Thermostat installation.—
(1) Thermostats shall be placed throughout the building, or portion of the building, including the inside of all closets, cellars, basements, lofts, and elevator wells, and under stairs as shown on approved plans.
(2) No portion of the building shall be exempt without written approval of the commissioner.
(3) Approval shall be obtained before the installation of high-temperature thermostats in boiler rooms, heating boxes, skylights, and other extra hazardous locations.
(4) The distribution of thermostatic heads and devices shall be in accordance with the requirements of Reference Standard RS 17–5 and as required herein.
(5) The distance from a wall or partition to a thermostat shall not exceed 1/2 the distance between thermostats in the same direction.
(6) A line of thermostats shall be run on each side of partitions.
(7) Spot thermostats of the solder type shall be arranged on smooth ceiling not more than 15 ft. apart, and at intervals of 15 ft. on each line.
(8) On irregular ceilings the thermostats shall follow the spacing as required in (7) above as near as possible, except that in no case shall the area protected by any signal head exceed 225 sq. ft.
(9) In ceilings on which there are bays, one or more heads shall be placed in each bay so the area protected does not exceed 225 sq. ft. for any head.
(10) Not more than 65 heads shall be installed on any supervised circuits.
(11) A thermostatic circuit shall not serve or protect more than the area of any one floor or story, except by special permission.
(h) Fire detecting wire systems.—
(1) Thermostatic systems of the fire-detecting-wire type shall have the thermostatic wire so arranged and installed that there is minimum possibility of the wire being damaged.
(2) Where necessary, fire-detecting wire shall be protected against mechanical injury.
a. Each circuit shall consist of a continuous length of fire-detecting wire not exceeding 1,000 ft., and shall not protect an area greater than that of any one floor or story, except by special permission.
b. Lines of fire detecting wire shall be so located throughout the area protected that they shall not be more than 15 ft. apart and so that no point on the ceiling will be more than 7 1/2 ft. from the nearest point of fire detecting wire, unless of a type approved for greater coverage.
c. Fire-detecting wire may be run either directly on ceilings or on side walls if the wire is placed not more than 20 in. below the ceiling, or on lower sides of timbers or projections.
d. Fire-detecting wire shall be securely fastened to its support in a manner that will not cause damage to the insulation or the outer braid.
e. Wiring, circuits, and all devices connected thereto shall comply in all respects with the requirements for manual fire alarms.
(i) Rate-of-rise pneumatic tube systems.—
***(1) Thermostatic systems of the rate-of-rise pneumatic tube type shall have the pneumatic tubing so arranged and installed that the possibility of mechanical damage is minimized. Where necessary, copper tubing shall be protected against damage.
a. Each circuit shall consist of a continuous length of tubing not exceeding 1,000 ft. without branches or alternative paths.
b. Tubing shall be enclosed in conduit or otherwise insulated or legged in order to isolate signals.
c. In every enclosed space or separate room, there shall be at least 5 per cent of the total length of the exposed tubing or circuit.
d. In no case shall less than 25 ft. of exposed tubing be used in any enclosed space or separate room.
e. Lines of tubing shall be so disposed throughout the area to be protected that they will not be more than 30 ft. apart, and so that no point on the ceiling will be more than 15 ft. from the nearest point of tubing.
f. Tubing must be run either directly on ceilings, or on side walls if the tubing is placed not more than 20 in. below the ceiling, or on lower sides of timbers or projections.
g. In rooms where timbers or other projections form bays more than 1 ft. deep and 8 ft. wide between beam centers, at least one line of tubing must be run in each bay.
h. Wiring circuits and all devices connected thereto shall comply in all respects with the requirements for the manual fire alarms.
i. The service connection for an automatic thermostatic alarm system shall be taken at the street side of the service switch in a manner approved by the commissioner.
(j) Unusual construction.—Approval of the fire commissioner shall be required to install thermostatic devices under floors or roofs of removable-panel construction.
(k) Existing installations.—Thermostatic alarm systems previously installed and approved by the fire commissioner shall be accepted as long as they are maintained in good working order, and there is not a change in building height or construction. Where alterations interfere with the proper distribution of thermostatic heads, additional heads shall be installed.
(l) Photoelectric smoke detection systems.—These systems shall be installed in accordance with the requirements of Reference Standard RS 17–5. The requirements of the building code affecting the design and operation of smoke detecting systems in duct systems, shall apply.
(m) Products-of-combustion-type ionization detection systems.—These systems shall be installed in accordance with Underwriters Laboratory requirements.
(n) Unusual construction.—Approval of the fire commissioner shall be required to install thermostatic, photoelectric, or ionization type detection devices under floors or roofs of removable panel construction.
10. CO2 EXTINGUISHING SYSTEMS.—Carbon dioxide extinguishing systems shall be installed in accordance with Underwriters' Laboratory requirements.
11. HOOD SMOTHERING AND FAN SHUTDOWN SYSTEMS.—
(a) General.—The requirements of the building code affecting the design and operation of automatic fire extinguishing systems for installation in hoods and ducts that exhaust fumes from commercial cooking equipment, shall apply.
(b) Source of power.—A local source of electric power for the system shall be utilized. Control wiring shall be of the "fail safe" type so that loss of control power will shut off all equipment.
(c) Test switch.—A test switch shall be provided, and wired so as to permit testing of the control wiring against shorts or open-circuits without actuation of the smothering system.
(d) Alarm sounding device.—A local alarm gong shall be provided, and shall sound upon actuation of the smothering system.
12. CENTRAL OXYGEN AND NITROUS OXIDE ALARM SYSTEMS.—A closed circuit electrical alarm system shall be provided to give visible and audible signals when the pressure in the system varies 8 lbs. above or below the normal line pressure of 50 lbs. Alarm indicating panels shall be so located in the hospital that they are under 24 hr. observation by a responsible person, or persons, delegated by the owner. Additional indicating panels may be provided in other locations subject to the approval of the fire commissioner.
13. LICENSED CONTRACTORS.—Only a person holding a license, or a special license in accordance with the provisions of the New York City electrical code, shall install, alter or repair electrical wiring or apparatus for fire alarm systems in any building. Upon approval by the commissioner, a manufacturer's designated representative may alter or repair a specific fire alarm system.
14. USED OR REBUILT APPARATUS.—Used apparatus shall not be re-used for any interior fire alarm system until the same has been reconditioned in the shop of an approved manufacturer of interior fire alarm apparatus. Approval shall be obtained from the commissioner prior to installation. The use of reconditioned apparatus whose manufacturer has discontinued manufacturing equipment is prohibited.
15. FIRE PROTECTIVE PRE-SIGNAL SYSTEMS FOR CLASS "G" ASSEMBLY AND EDUCATIONAL OCCUPANCY BUILDINGS IN GROUP 1-A (FIREPROOF) CONSTRUCTION.—
I—SCOPE
When permitted by the Fire Commissioner, new fire signal system characteristics for pre-signal operation and existing manual coded and non-coded fire station signal modifications for pre-signal operation, shall be in accordance with the following schedule in its entirety and in accordance with Reference Standards RS 17–3, RS 17–3A, RS 17–3B and other applicable standards and permitted only in Class "G" educational occupancy buildings of Group 1-A fireproof construction. Interior alarm systems installed or altered in accordance with this standard shall be designated as "Class G Systems".
II—FUNCTION SCHEDULE
A. Introduction of a time delay between the operation of a coded, master coded or non-coded manual interior fire alarm station and the audible evacuation signal shall be limited to an adjustable interval of 0–180 seconds. The specific duration of the time delay shall be determined by the Fire Commissioner for each specific premises where permitted. The time delay, when instituted by a manual station, shall also be effective for fan shutdown and other auxiliary equipment. There shall be no delay on automatic detection.
B. Alphanumeric annunciation of each manual and each automatic initiation for registration of the location of the device producing the alarm with response instructions determined and authorized by the Fire Commissioner. The registration shall indicate in seconds the delay time remaining for the last signal initiation and shall be visible to and in the immediate vicinity of the Chief Building Administrator's office.
C. Means for cancellation of a manual signal initiation within its introduced time delay accessible only to the Chief Building Administrator. Cancellation shall not be possible for fifty (50%) percent of the delay time expiration.
D. Means for by-passing the introduced time delay after a manual device initiation to produce the evacuation sounding and after normal school hours. The means shall be in the immediate vicinities of the Chief Building Administrator's office and the Building Engineer's office.
E. Master coding for the evacuation signal, providing for single stroke gong systems an evacuation signal comprising four rounds of three single stroke gong soundings only, or providing for dedicated loud speaker systems an evacuation signal comprising a rising tone of three seconds duration starting at a frequency of 400 hertz and ending with a frequency of 1,000 hertz, repeated twelve times.
F. Automatic notification to the Fire Department via a class 3 manual station located in the vicinity of the Principal Administrator's office.
III—EQUIPMENT REQUIREMENTS
A. The acceptable means to provide the previously defined characteristics and modifications may include digital electronic circuitry with logic in accordance with the reference standard and as approved and with information interchange in accordance with the reference as approved. Where digital electronic circuitry is used, reliability rates shall be equal to or greater than the equivalent reliability rates for the relay circuitry that may be designed for this purpose. The acceptable means shall be uniform for a given installation. Where digital electronic circuitry is chosen as the acceptable means for a given installation the entire circuitry for this installation shall be digital electronic without exception.
B. The digital electronic alphanumeric annunciation may take one of the following three forms:
1. A fixed lettered display with characters a minimum height of one quarter inch, resulting from the conversion of a manual or automatic device initiation to a unique point.
2. A dot matrix display of a duration at least equal to the duration of the system's interrupt mode and originating in the manner of the fixed lettered display. The matrix shall be a minimum of seven by five dots per character.
3. A cathode ray tube display of duration in the manner of the dot matrix display and origination in the manner of the fixed lettered display. The minimum character height shall be one quarter inch.
In addition the following form shall be provided in conjunction with one of the foregoing:
A teletypewriter is to receive only mode with origination in the matter of the fixed lettered display.
C. Other digital electronic alphanumeric annunciation devices such as liquid crystals or light emitting diodes or the like may be installed for this purpose in lieu of one of the above three forms when approved for use and acceptable to the Fire Commissioner.
D. All system events shall be recorded in hard copy along with the date and time of each particular event. These events shall include the following:
1. The manual or automatic device initiation.
2. The elapsed time in seconds from the manual or automatic initiation to the cancellation or the by-pass as above defined.
3. The elapsed time in seconds from the manual or automatic initiation to the evacuation sounding as above defined.
E. Where a loud speaker system is used for the evacuation sounding, its amplifiers shall be designed for one hundred and fifty (150%) percent of rated load with a minimum of two discrete amplifiers. The loud speaker system may be used for voice communication, provided the evacuation signal use has priority. Speakers used for fire alarm systems shall be rated for 400 degrees F. and approved by the Board of Standards and Appeals. These speakers and amplifier requirements apply to all systems installed under any and all provisions of this code.
F. All fire protective pre-signal systems shall be operated daily when the building is occupied and a log shall be kept of such operation, accessible to the Commissioner. The hard copy of system events may be considered the required log. All equipment must be approved by Board of Standards and Appeals and acceptable to the Commissioners of Buildings and Fire Department, prior to installation.
IV— DETAILED STANDARDS FOR THE INSTALLATION OF CLASS "G" FIRE SIGNAL SYSTEMS
A. SOURCES OF ELECTRICAL POWER
Two sources of electrical power shall be provided as follows:
(1) The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
(2) The secondary source shall be an emergency power system (as per 27-396), emergency generator and/or battery power.
One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the "New York City Electrical Code." The primary source of power and the secondary source (if emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208-volt side. The incoming supply connections shall comply with the NYC Electrical Code, and the fused cutout panel shall comply with the requirements specified herein before.
B. PRIMARY POWER SOURCE
(1) The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
(2) Partial systems such as strobe light control panels, partial fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and an identified, locked fused cutout box located within 5 feet of the tap.
Where an emergency power system (E.P.S.) is provided in accordance with § 27-396.4, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.
C. SECONDARY POWER SOURCE
The Secondary service to the fire alarm system shall be provided as follows:
(1) If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
(2) If the building has an emergency generator supplying power to any of the loads listed in 27-396.4, the secondary source shall be the generator.
(3) For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17–5 for primary batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by
(a) 6 hour total system load for systems with voice communication capability (A 45 minute period of voice/alarm operation at maximum connected load shall be considered equivalent to 6 hours of total system operation), or
(b) 15 minutes of total system load for systems without voice capability.
(4) Partial systems and/or associated systems may derive their secondary supply from batteries whether or not the building is equipped with an emergency generator. Batteries shall be designed for 24-hour supervisory operation followed by 5 minutes of total system load.
All alterations to any existing approved fire alarm system involving or consisting of the replacement of the Fire Command Station, Fire Alarm Control Panel, Central Processing Unit, Floor Control Units, Remote Control Units, Data Gathering Panels, Terminal Transmission Board, and other similar or equivalent controls or control panels shall be required to comply with Section (C3) above. For systems in buildings which are in compliance with Sections (C)1 or (C2) above, compliance with Section (C3) is optional.
D. ASSOCIATED SYSTEMS
Associated systems listed below shall have their actuation added to the Fire Control Panel:
1. Smoke detection systems.
2. Sprinkler water flow alarms.
3. Thermostatic alarms.
4. Fan shut down for HVAC and automatic smoke exhausters.
5. Stage fire control and deluge systems.
6. Other approved systems.
NOTE: The associated systems listed above shall all be interconnected with the Class "G" fire signal systems and shall have their alarm and common trouble signals indicated at the main control board.
E. WIRING
(1) Power Conductors (Above 75 volts) shall be:
(a) Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW; minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
(b) Cable type MI, M.E.A. approved for 2-hour fire resistance rating.
(2) Low Voltage Conductors (75 volts and less) shall be:
(a) Copper; THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, XHHW, minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT)
(b) Minimum wire size No. 18 AWG.
(c) Multiconductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
• Type FPLP only: minimum insulation thickness 15 mils; minimum temperature 150 C; colored red.
• Red colored jacket overall; minimum thickness 25 mils.
• Cable printing as per UL1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE" legible without removing jacket.
(3) Installation of Conductors and Raceway shall be in accordance with the following:
(a) Power conductors shall not be installed in common raceways with low voltage conductors.
(b) Comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
(c) Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
(d) Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment. In any suppression and extinguishing system activated by automatic fire detection, including, but not limited to, pre-action sprinkler, deluge sprinkler, clean air agent, halon, range hood, CO2 and dry chemical, multi-conductor cables shall be installed in RMC, IMC, or EMT.
(e) All wiring within mechanical and elevator equipment rooms shall be run in raceway.
(f) Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
(g) Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT), except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing Reference Standard 17 conductors.
(h) Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
• Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support. Support independently from the building structure.
• (2) Secure by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Secure in place at intervals not exceeding 5'-0" on centers and within 12" of every associated cabinet, box or fitting.
(i) Installation of raceways, boxes and cabinets shall comply with the following general requirements.
• Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
• Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
• Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
• Raceways or cables shall not penetrate top of any equipment box or cabinet.
(j) All conduits supplying 120-volt power to the fire command station and/or fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
(k) For cabinets whose 120-volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel-framed buildings, a connection to local steel structure will be acceptable.
(l) Splices and terminations of wires and cables shall be as follows:
• Permitted only in boxes or cabinets specifically approved for the purpose.
• Utilize mechanical connections specifically approved by U.L. 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
(m) Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e., by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.
F. FIRE SIGNAL SENDING STATIONS, CLASS "G" NON-CODED MANUAL STATION AND THE FIRE SIGNAL CONTROL STATION
1. There shall be at least one (1) fire signal sending station in each story of a building located in each path of escape. Additional stations shall be installed so that no point on any floor shall be more than two hundred feet from the nearest station.
2. Doors of sending stations shall be painted Fire Department "red" and lettered: "Fire Emergency—Open Door to Operate", or words to that effect. The instructions for operating the station shall be prominently displayed on an instruction card or, the cover of the station.
3. All current carrying parts shall be insulated from parts carrying current of opposite polarity with approved insulating material.
4. All pull lever type stations shall be constructed with an outer door and means to protect the pull lever against accidental operations. The wording: "In Case of Fire, Open Door and Pull Down Lever", in raised letters or the equivalent instructions, shall appear on the door.
5. For systems using break-glass or break-rod type stations, at least one extra glass pane or glass rod for each station in the system shall be kept in the building. Break glass stations shall have the glass rod or pane mounted on the surface of the station covers or, mounted internally in such a manner that the glass must be broken to actuate the sending station. Suitable hammers on chains attached to the stations, or other approved means for breaking the glass, shall be provided. Stations accomplishing the "break glass" principal using other approved means shall not be required to provide hammers or spare glass.
6. Non-coded stations.
a. Non-coded closed circuit fire signal stations shall be operated by a break-glass or break-rod or pull lever device so arranged that the signal cannot be interfered with except by resetting or replacement of the glass or rod by an authorized person.
b. The construction and materials shall be equivalent to that of the standard approved type coded closed circuit station described in Reference Standard RS 17–3, except that the contacts shall be of sufficient capacity to safely carry the entire operating current of the signal circuit without excessive heating.
7. Stations testing devices. Provisions shall be made for a silent test of sending station mechanisms without operating the signaling devices. Such test device shall be designed to prevent any person, except those in authority, from operating the test device and to prevent the possibility of the box being left inoperative after the test.
8. Provisions shall be made to supply an audible as well as visual signal at the fire signal control station from the fire signal station.
G. EVACUATION SOUNDING DEVICES
1. Approved single stroke gongs or dedicated loud speakers shall be provided as the sounding devices. Approved loud speakers shall have heat resistant driven elements and shall conform to Reference Standard RS 17–5. When recessed loud speakers are used, they shall conform to the performance requirements of Reference Standard RS 17–5. The loud speakers, when mounted on walls, shall be mounted upon interior walls in preference to building core walls.
2. Recessed loud speakers, if used, shall be located not more than ten feet from the entrance to each required exit to insure proper evacuation signal reproduction. This spacing is based upon normal eight feet to ten feet ceiling height. Surface mounted loud speakers shall be mounted within ten feet of each egress to insure proper evacuation signal reproduction. For unusual conditions and higher ceilings, the loud speakers shall not be mounted more than twenty feet above the floor.
3. For new fire protective signal systems only, in the entire building when at least twenty-five (25%) percent of the occupants have hearing impairments and in those areas where the ambient noise level exceeds ninety decibels (90 dBA) on the "A" scale, provided in all applicable areas at least one visual evacuation signal. This signal shall be a xenon lamp flasher having a minimum flash intensity of one million candlepower, dissipating for each lamp flash a minimum energy of fifteen joules, and shall be wall mounted at a minimum height of nine feet above the floor. The lamp flasher shall be totally enclosed so that all visible and ultraviolet radiations at or below its center line shall be blocked and so that all visible upward radiation, shall be transmitted. The visual evacuation signal shall flash once every three seconds, repeated twelve times.
4. The evacuation sounding devices may be utilized for other audible purposes, including building security, when means is provided to insure fire evacuation signal priority.
H. FIRE SIGNAL SYSTEM CONTROL STATION
1. Supervising Circuits.
a. Class "G" fire protective signal systems shall be supervised, except for the alphanumeric annunciator.
b. The supervising circuit shall be provided with a trouble signal arranged to sound continuously in case of failure of the primary power source or other derangements. The trouble signal shall be so located that it will be within audible range of a responsible person in the building.
c. Trouble signals may be fitted with silencing switches only when the switch is connected in such a manner that the act of silencing the signal by the operation of the switch will automatically transfer the trouble signal to a red lamp on the fire signal control station. When the trouble has been repaired, the alarm signal shall sound until the silencing switch has been reset to operate under normal conditions.
d. The trouble signal shall give a distinctive tone.
2. Protection of Sending and Sounding Devices. In fire protective signal systems, the sending stations and sounding devices shall be enclosed in metal casings, made dust proof and damp proof when necessary, and shall be clearly marked with instructions for use.
3. Standards of Electrical Signal Apparatus. All electrically actuated apparatus used in fire protective signal systems shall be so designed and constructed that it will operate satisfactorily at an input voltage level of twenty (20) percent below or ten (10) percent above the normal rated voltage.
4. Insulation.
a. Insulating materials used shall be varnished cambric, bakelite, mica or other equivalent insulating material.
b. The use of fiber or paper as an insulating material is prohibited.
c. The insulating materials used shall be capable of withstanding an insulation breakdown test of one thousand volts a.c., plus twice the operating voltage applied for one minute.
5. Electromagnets.
a. Electromagnetic windings shall be impregnated with an insulating and moisture-repelling compound of the silicone or epoxy type.
b. Electromagnetic coils used on alternating current, when composed of enameled wire, shall have additional approved insulation on each wire. The coils may be of the form wound type.
c. A protective cover to prevent mechanical damage shall be provided over the entire coil.
d. Electromagnetic coils shall be fastened to prevent floating.
e. Electromagnetic cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.
f. Electromagnetic cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and to promote efficiency.
g. Electromagnetic cores of relays shall be treated to prevent corrosion. Paint or varnish shall not be used for this purpose.
h. Nonmagnetic freeze pins shall be used to prevent two magnetic surfaces from making physical contact with each other.
6. Wiring.
a. All connections shall be secure and properly protected and, where subject to motion, shall be of approved flexible wire. All wiring of the fire signal control station, the fire station circuits and the supervisory circuits, shall be approved.
b. Binding posts, when used, shall be of such design that the wire is held between two flat surfaces. Binding posts shall be mounted on an approved terminal block or insulating strip. The spaces between the binding posts shall be at least one-half inch, unless they are separated by approved barriers.
c. Digital electronic printed circuit cards, when used, shall be one-sixteenth inch thick glass fiber epoxy resin. The cards shall have color coded ejectors used to group cards according to function so that they may be located quickly and shall have plated through holes as feed through on all logic cards. The connection fingers shall be gold, plated over nickel.
7. Overload Protective Devices. The digital electronic circuits shall provide protection of all equipment and circuits by opening up the circuit to the equipment or devices protected. The operation of this overload circuit shall cause the trouble signal to sound at the fire signal control station.
8. The control boards shall operate so that trouble in an individual zone may be shunted out without affecting the operation of the rest of the zones of the system.
9. Provision shall be made for sufficient wire gutter space around the panel. The gutter space shall be a minimum of two inches at the sides, the top and the bottom. The wire in the gutter space shall be properly laced in a neat and workmanlike manner on all control boards.
10. Conduit knockouts shall not be provided in the top of the control board cabinet, unless designed and approved for entry on top.
11. A wiring diagram of the fire protective signal system approved by the Fire Commissioner and the approved card of instruction properly marked, shall be provided and securely fastened within the control board cabinet and at the fire signal control station. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be framed under glass or an equivalent material.
12. Control Boards.
a. The control boards and amplifiers used for voice communication and alarm shall be located in a safe, moisture and dust free location secure from unauthorized tampering. Otherwise a ventilated cabinet provided with a lock and a key suitably identified, shall be provided.
b. The amplifiers for the Class "G" systems shall have the capacity to deliver sufficient power to operate all evacuation sounding devices and the voice communication systems, and have a fifty (50) percent reserve power capacity. In addition, the amplifiers shall be wired in such a manner that the imminent failure or actual failure of amplifiers shall shut down the amplifiers and shall indicate a trouble condition. The removal of an amplifier shall be indicated by a trouble signal at the fire signal control station. The opening of the control cabinets shall be supervised by a tamper switch producing a manually resetting trouble alarm at the fire signal control station.
13. Fire Control Station. The Station shall consist of the following equipment:
a. Time delay means in accordance with Section II A. above. At the end of the time delay or, at the time of the by-pass, the interior evacuation signal shall sound and all interconnected controls shall operate.
b. Alphanumeric annunciation in accordance with Section II B. above.
c. A key controlled signal cancellation in accordance with Section II C. above.
d. A by-pass means in accordance with Section II D. above.
e. A printer which records system events in accordance with the Equipment Requirements of this standard, located in the Building Engineer's office.
f. Five day week digital electronic clocks to revert the pre-signal operation to normal (zero time delay) operation after normal building hours, and permitting immediate evacuation sounding after signal initiation determined by matching two successive code rounds.
I. PAINTING OF EQUIPMENT
All enclosing cases for fire signal, sprinkler alarm detection and associated systems alarm apparatus shall be painted Fire Department "red", except where approval is given by the Commissioner to deviate from this requirement.
J. INFORMATION DISPLAY SYSTEMS
1. The indicating devices shall describe the purposes they serve. The printed designation on unit or building information display systems indicators shall be legible. All conditions indicated shall remain displayed in accordance with the Equipment Requirements of this standard.
2. A unit information display system shall be so designed that the operation of any station in the unit shall cause a visible and audible signal.
3. Trouble displays shall be so arranged that the indicating device will reset automatically when the cause of the trouble has been removed. The trouble information display system shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit monitored. The trouble information display system shall be actuated by the operation of supervisory devices.
4. There shall be a silencing means for trouble signals that shall not affect subsequent trouble signals.
5. The information display systems shall be so designed that vibration from without or that caused by a trouble signal within will not operate the indicating devices.
6. All remote information display systems shall be installed in a separate steel cabinet painted Fire Department "red" and provided with approved lock and key. The information display system cabinets shall be marked in white letters at least one inch high with the words: "Fire Signal Information Display System, Zone . . .", or "Fire Signal Trouble Information Display System", whichever the case may be.
7. The information display systems shall be wall mounted and shall have the legend "Fire" in red letters three inches high together with an audible signal, in addition to the alphanumeric annunciation, and a separate and distinctive trouble signal shall sound. The audible signal accompanying an alarm shall be silenced when the equipment is operated by the Chief Building Administrator or his delegated substitute.
8. The display shall provide a minimum of four simultaneous alarm indications with an overflow memory for additional alarms. Provisions shall be made to distinguish alarm conditions from non-alarm conditions. The display shall be updated as new information becomes available. If the same condition exists for more than one point on a floor or, for more than one floor in a building, a separate output entry shall be displayed for each point on the floor or floors.
9. Display Format. Each output entry shall include self identifying memory codes for the type of signal building or area designation, floor or stair number and point location, and time of day.
10. Maintainability.
a. Manual display of all points of annunciation for test purposes shall be provided.
b. The capability shall be provided for interrogation of any station or sensing element for test purposes, either at the remote device or by interrogation from the office control location. Intervals for testing shall be as approved by the Fire Commissioner.
c. The equipment design shall be modular so that all repairs may be performed at the building site by substitution of duplicate components by authorized repair personnel.
d. On each one of those parts that are of a modular nature shall be included as spares at the control station.
K. LICENSED CONTRACTORS
Only a person holding a license or a special license in accordance with the provisions of the New York City Electrical Code shall install or alter the electrical wiring or apparatus for fire protective signal systems in any building.
L. USED OR REBUILT APPARATUS
Used apparatus shall not be re-used for any interior fire signal system until this used apparatus has been reconditioned in the shop of an approved manufacturer of interior fire alarm apparatus. Approval shall be obtained from the Commissioner prior to installation. The use of reconditioned apparatus whose manufacturer has discontinued manufacturing equipment is prohibited.
RS 17-3A. STANDARDS FOR THE INSTALLATION OF CLASS E, CLASS C AND CLASS J FIRE ALARM SIGNAL SYSTEMS
(Note: References herein to Class E Systems shall be deemed to also include references to Class C and Class J Systems.)
1. (A) SOURCES OF ELECTRICAL POWER
Two sources of electrical power shall be provided as follows:
(1) The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
(2) The secondary source shall be an emergency power system (as per 27-396), emergency generator and/or battery power.
One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other Systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the New York City Electrical Code.
The primary source of power and the secondary source (if emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with a hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208-volt side. The incoming supply connections shall comply with the NYC Electrical Code, and the fused cutout panel shall comply with the requirements specified hereinbefore.
(B) PRIMARY POWER SOURCE
1. The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
2. Partial systems such as strobe light control panels, fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and identified, locked fused cutout box located within 5 feet of the tap.
Where an emergency power system is provided in accordance with section § 27-396.4, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.
(C) SECONDARY POWER SOURCE
The secondary service to the fire alarm system shall be provided as follows:
1. If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
2. If the building has an emergency generator supplying power to any of the loads listed in § 27-396.4, the secondary source shall be the generator.
3. For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17–5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by:
a. 6 hour total system load for systems with voice communication capability (A 45 minute period of voice/alarm operation at maximum connected load shall be considered equivalent to 6 hours of total systems operation),
or
b. 15 minutes of total system load for systems without voice capability.
4. Partial systems and/or associated systems may derive their secondary supply from batteries whether or not the building is equipped with an emergency generator. Batteries shall be designed for 24-hour supervisory operation followed by 5 minutes of total system load.
All alterations to any existing approved fire alarm system involving or consisting of the replacement of the Fire Command Station, Fire Alarm Control Panel, Central Processing Unit, Floor Control Units, Remote Control Units, Data Gathering Panels, Terminal Transmission Board, and other similar or equivalent controls or control panels shall be required to comply with Section C3 above. For systems in buildings, which are in compliance with Sections (C)1 or (C)2 above, compliance with Section (C)3 is optional.
2. ASSOCIATED SYSTEMS.—
Associated systems listed below shall have their actuation added to the Fire Command Station.
(a) Smoke detection systems.
(b) Sprinkler waterflow alarms.
(c) Thermostatic alarms.
(d) Locked door-fail safe release systems.
(e) Elevator communication and interconnection.
(f) Stair pressurization fan(s) and associated damper(s)
3. WIRING.—
a. Power Conductors (Above 75 volts) shall be:
(1) Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW; minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
(2) Cable type MI, M.E.A. approved for 2-hour fire resistance rating.
b. Low Voltage Conductors (75 volts and less)
(1) Copper; THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, XHHW, minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC), electric metallic tubing (EMT)
(2) Minimum wire size No. 18 AWG.W.G.
(3) Multi-conductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
a. Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150C; colored red.
b. Red colored jacket overall; minimum thickness 25 mils.
c. Cable printing as per UL1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE," legible without removing jacket.
c. Installation of Conductors and Raceway shall be in accordance with the following:
(1) Power conductors shall not be installed in common raceways with low voltage conductors.
(2) Shall comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
(3) Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
(4) Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment. In any suppression and extinguishing system activated by automatic fire detection, including, but not limited to, pre-action sprinkler, deluge sprinkler, clean air agent, halon, range hood, CO2 and dry chemical, multi-conductor cables shall be installed in RMC, IMC, or EMT.
(5) All wiring within mechanical and elevator equipment rooms shall be run in raceway.
(6) Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT); except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing Reference Standard 17 conductors.
(7) Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
a. Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support. Support independently from the building structure.
b. Secure by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Secure in place at intervals not exceeding 5'0" on centers and within 12" of every associated cabinet, box or fitting.
(8) Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
(9) Installation of raceways, boxes and cabinets shall comply with the following general requirements.
a. Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
b. Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
c. Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
d. Raceways or cables shall not penetrate top of any equipment box or cabinet.
(10) All conduits supplying 120-volt power to the fire command station and/or fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
(11) For cabinets whose 120-volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel, framed buildings, a connection to local steel structure will be acceptable.
(12) Splices and terminations of wires and cables shall be as follows:
a. Permitted only in boxes or cabinets specifically approved for the purpose.
b. Utilize mechanical connections specifically approved by U.L. 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
(13) Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e., by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.
4. FIRE ALARM SENDING STATIONS, CLASS "E"—NON-CODED MANUAL STATION, AND FLOOR WARDEN STATION.—
(a) There shall be at least one (1) fire alarm sending station in each story of a building located in each path of escape. Additional stations shall be installed so that no point on any floor shall be more than 200 feet from the nearest station.
(b) A floor warden station on each floor shall be located between required stairways, required vertical exits or other required exits. All types of systems shall include a telephone type handset at the floor warden station with integral signaling to the fire command station and may be a part of the speaker system. The handset shall be red and equipped with armor over the wiring between the handset and its housing that may be installed flush, semi-flush or surface mounted. The housing shall be painted red and identify its function. Equipment shall be installed with a box recessed or surface mounted large enough to include the handset and test facility, by means of a key, to test the floor automatic and manual alarm device wiring. A pilot light shall indicate the live condition of the floor warden station.
Doors of sending stations shall be painted red and lettered "FIRE EMERGENCY—OPEN DOOR TO OPERATE" or words to this effect. Instructions for operating the station shall be permanently affixed or be an integral part of the station. Instruction cards shall be provided at each station protected by glass or plastic. Designation number of station shall be prominently displayed on instruction card or on cover of station.
(c) All current-carrying parts shall be insulated from parts carrying current of opposite polarity with approved insulating material.
(d) All pull-lever type stations shall be constructed with a door or other approved means to protect the "pull-lever" against accidental injury. The wording "IN CASE OF FIRE—OPEN DOOR AND PULL DOWN LEVER" in raised letters or equivalent instructions, shall appear on the door.
(e) For systems using break-glass or break-rod type stations, at least one extra glass rod or glass pane for each station in the system shall be kept in the building. Break glass stations shall have the glass rod or pane mounted on the surface of the station covers or mounted internally in such a manner that the glass must be broken to actuate the sending station. Suitable hammers on chains attached to the stations or other approved means of breaking the glass, shall be provided. Stations accomplishing the "break glass" principle using other approved means shall not be required to provide hammers or spare glasses.
(f) Non-Coded Stations:
(1) Non-coded closed circuit fire alarm stations may be operated by a break-glass or break-rod or a pull lever device so arranged that the alarm cannot be interfered with except by resetting or replacement of the glass or rod by an authorized person.
(2) The construction and materials shall be equivalent to that of the standard approved type coded closed circuit station described in Reference Standard RS 17–3 except that the contacts shall be of sufficient capacity to safely carry the entire operating current of the alarm circuit without excessive heating.
(g) Station Testing Devices.—Provisions shall be made for a silent test of sending station mechanisms without operating the signaling devices. Such test device shall be designed to prevent any person, except those in authority, from operating the same and to prevent the possibility of the box being left inoperative after the test.
(h) Provision shall be made to supply an audible and visual signal at the fire command station from the floor warden station.
(i) A designated station on each floor shall have the capability of operating the loud speakers for that floor.
5. ALARM SOUNDING DEVICES.—
(a) Approved speakers shall be provided as the sounding devices. The alarm sound shall be a generated gong, bell, horn, whistle or other acceptable signal. Chime sounds may be installed only with the approval of the commissioner. Approved speakers shall have heat resistant driven elements and shall conform to Reference Standard RS 17–5.
When recessed speakers are used they shall conform to the performance requirements of Reference Standard RS 17–5. Speakers when mounted on walls shall be mounted upon tenant walls in preference to building core walls.
(b) Recessed speakers if used shall be located not more than 10 feet from the entrance to each required exit to insure proper alarm signal reproduction. This spacing is based upon normal 8 feet–10 feet ceiling height. Surface mounted type speakers shall be mounted within 10 feet of each egress to insure proper alarm signal reproduction. For unusual conditions and higher ceilings, speakers shall not be mounted more than 20 feet above floor.
(c) The alarm sounding devices may be utilized for other audio purposes including building security if means is provided to insure fire alarm priority.
6. FIRE ALARM SYSTEM CONTROL BOARDS AND COMMAND STATIONS.—
(a) Supervising Circuit.—
(1) Class "E" fire alarm systems shall be supervised.
(2) The supervising circuit shall be provided with a trouble signal arranged to sound continuously in case of failure of the primary power source. The trouble signal shall be so located that it will be within audible range of a responsible person in the building.
(3) Trouble signals may be fitted with silencing switches only when the switch is connected in such a manner that the act of silencing the signal by the operation of the switch automatically transfers the trouble signal to a red lamp on the fire command station. When the trouble has been repaired, the alarm signal shall sound until the silencing switch has been reset to operate under normal conditions.
(4) The trouble signal shall give a distinctive signal.
(b) Protection of Sending and Sounding Devices.—In fire alarm signal systems, sending stations and sounding devices shall be enclosed in metal casings, made dust proof and damp proof when necessary, and clearly marked with instructions for use.
(c) Standards of Electric Alarm Apparatus.—All electrically actuated apparatus used in fire alarm systems shall be so designed and constructed that it will operate satisfactorily at an input voltage level 15 per cent below or 10 per cent above normal rated voltage.
(d) Insulation.—
(1) Insulating materials used shall be varnished cambric, Bakelite, mica, or equivalent insulating material.
(2) The use of fiber or paper as an insulating material is prohibited.
(3) The insulating materials used shall be capable of withstanding an insulation breakdown test of 1,000 volts a.c. plus twice operating voltage applied for 1 minute.
(e) Electromagnets.—
(1) Electromagnet windings shall be impregnated with an insulating, moisture repelling compound of the silicone or epoxy type.
(2) Electromagnet coils used on alternating current, when composed of enameled wire shall have additional approved insulation on each wire. The coils may be of the form-wound type.
(3) A protective cover to prevent mechanical damage shall be provided over the entire coil.
(4) Electromagnetic coils shall be fastened to prevent floating.
(5) Electromagnet cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.
(6) Electromagnet cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and promote efficiency.
(7) Electromagnetic cores of relays shall be treated to prevent corrosion. Paint or varnish shall not be used for this purpose.
(8) Non-magnetic freeze pins shall be used to prevent two magnetic surfaces from making physical contact with each other.
(f) Relays.—
(1) The armatures of all relays shall depend on gravity or magnetic attraction for their operation and may be assisted by a spring.
(2) Adjustments shall be of such a character that they can be securely locked.
(g) Overload protective devices.—Electronic circuits shall provide protection of all equipment and circuits by opening up the circuit to the equipment or devices protected. The operation of this "overload circuit" shall cause the trouble signal to sound at the fire command station.
(h) Control boards shall operate so that troubles in individual zones may be shunted out without affecting the rest of the system.
(i) Provision shall be made for sufficient wire gutter space around the panel. Gutter space shall be a minimum of 2 inches at sides, top, and bottom. Wire in gutter space shall be properly laced in a neat and workmanlike manner on all control boards.
(j) Conduit knockouts shall not be provided in the top of the control board cabinet, unless designed and approved for entry on top.
(k) A wiring diagram of the alarm system approved by the commissioner and the approved card of instruction properly marked and securely fastened shall be provided within the control board cabinet and at the fire command station. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be framed under glass or equivalent material.
(l) Control Boards.—
(1) Control boards and amplifiers used for voice communication and alarms shall be located in a safe, moisture and dust free location secure from unauthorized tampering. Otherwise a ventilated cabinet provided with a lock and key, suitably identified, shall be provided.
(2) Amplifiers for class E systems shall have the capacity to deliver sufficient power to operate all alarm sounding devices and voice communication system and have a 50 per cent reserve power capacity. In addition the amplifiers shall be wired in such a manner that the imminent failure or actual failure of amplifiers shall shut down the amplifier and indicate a trouble condition. Removal of an amplifier shall be indicated by a trouble signal at the fire command station. Opening of the control cabinets shall be supervised by a tamper switch producing a manually resetable trouble alarm at the fire command station.
(m) Fire Command Station.—The fire command station shall contain all the components described in the building code and shall have the capability of overriding floor warden stations. The command station console shall be provided with a hinged cover that permits the flashing "FIRE" visible signal to be seen. The cover shall be provided with an approved lock and key. The fire command station shall be provided with an information display system so located as to provide minimum distortion due to an angular line-of-sight and ambient lighting conditions. This display shall have the capability to monitor the following systems in order of listed priority:
(1) Manual Fire Alarm
(2) Smoke Detection
(3) Sprinkler Waterflow
(4) Elevator Lobby Detector
(5) Fire Signal Activation
(6) Central Office Notification
(7) Fan System on—Fan System off
(8) Fail Safe Locked Door
(9) Fire Systems Trouble
(10) Fire Signal Trouble
(11) Tamper Switch Alarm
(12) Power Source
(13) Test/Normal Mode
(14) Other Information as Desired
(15) Stair pressurization fan(s) and associated damper(s).
7. PAINTING OF EQUIPMENT.—All enclosing cases for fire alarm, sprinkler alarm, smoke detection, and associated systems alarm apparatus shall be painted fire department red, except where approval is given by the commissioner to deviate from this requirement. The lobby information display system may be painted or finished to suit the owner of the building.
8. INFORMATION DISPLAY SYSTEMS.—
(a) Information display systems used in connection with Class E Fire Alarm Signal Systems shall be of an approved electrically supervised type. The indicating devices shall describe the purpose they serve. The printed designation on unit or building information display system indicators shall be legible. The mechanism shall be so arranged that once operated, the indicating device must be reset manually. All conditions indicated shall remain displayed until manually cleared at the Fire Command Station. Fire Command Stations shall provide alarm information in a direct manner; no references to numeric codes shall be permitted. Where a CRT display is provided, a specially marked control shall be provided that will enable the system operator to determine the alarm source and other related pertinent information.
(b) A unit information display system shall be so designed that the operation of any station in the unit causes a visible and audible signal.
(c) Trouble displays shall be so arranged that the indicating device will reset automatically when the cause of trouble has been removed. The trouble information display system shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit monitored. The trouble information display system shall be actuated by the operation of supervisory devices.
(d) A silencing switch shall be provided for trouble signals, but shall not affect subsequent trouble signals.
(e) Information display systems shall be so designed that vibration from without or that caused by a trouble signal within will not operate the indicating devices.
(f) All remote information display systems shall be installed in a separate steel cabinet painted red, provided with approval lock and key. Information display system cabinets shall be marked in white letters at least one inch high with the words "FIRE ALARM INFORMATION DISPLAY SYSTEM, ZONE ——" or "FIRE ALARM TROUBLE INFORMATION DISPLAY SYSTEM", whichever the case may be.
(g) Information display systems located in the lobby of a building whether an integral part of the fire command station or wall mounted shall have the legend "FIRE" in red letters three inches high together with an audible signal in addition to the lamp, target drop, cathode ray tube, light emitting diode, nixie, etc. and a separate or distinctive trouble signal shall sound. The audible signal accompanying an alarm shall be automatically silenced when the fire command station is operated by the fire safety director or his delegated substitute. Remote information display systems shall operate in the same manner.
(h) The display shall provide a minimum of four simultaneous alarm indicators with an overflow indication for additional alarms. Provisions shall be made to distinguish alarm conditions from non-alarm conditions. The display shall be updated as new information becomes available. If the same condition exists for more than one point on a floor or for more than one floor in a building, such as a fire gong actuation or public address, a separate output entry shall be displayed for each point or floor.
(i) Display format.—Each output entry shall include self-identifying mnemonic codes for the type of signal, building or area designation, floor or stair number and point location, and time of day. Systems utilizing gravity drops or lamps as point identification, may provide a hard copy print out.
(j) Maintainability.—
(1) Manual display of all points of annunciation for test purposes shall be provided.
(2) Capability shall be provided for interrogating any station or sensing element for test purposes, either at the remote device or by interrogation from the fire command station. Intervals of testing shall be as approved.
(3) Equipment designed shall be modular so that all repairs may be performed on-site by substitution of duplicate components by authorized personnel.
(4) One each of these parts that are of a modular nature shall be included as spares at the fire command station.
9. LICENSED CONTRACTORS.—Only a person holding a license or a special license in accordance with the provisions of the New York city electrical code, shall install, alter, or repair electrical wiring or apparatus for fire alarm systems in any building.
10. USED OR REBUILT APPARATUS.—Used apparatus shall not be re-used for any interior fire alarm system until the same has been reconditioned in the shop of any approved manufacturer of interior fire alarm apparatus. Approval shall be obtained from the commissioner prior to installation. The use of reconditioned apparatus whose manufacturer has discontinued manufacturing equipment is prohibited.
11. STANDPIPE FIRELINE TELEPHONE AND SIGNAL SYSTEM.—Where the standpipe telephone and signal system is arranged to be used as a modified Class E fire alarm signal system as provided in the building code, retractable telephone handsets shall be provided in pump rooms. The telephone in pump rooms shall be equipped with a loudspeaking receiver so that a voice can be distinctly heard at least 15 feet from the receiver.
12. LOCKED DOOR FAIL SAFE SYSTEMS.—
(a) Stairway reentry doors that locked from the stairway side as permitted in section 27-371 of the administrative code shall be provided with an electrical fail safe strike release mechanism that will permit the door to be opened without a key when any automatic fire-detecting device operates, elevator "Fireman Service" operates or power failure shall occur. In addition, provisions shall be made to permit these doors to be opened from the command station or mechanical control center. This system shall be manually reset.
(b) Wiring for these systems shall comply with rule 6 (a), (b), (c) and (d) of this reference standard and be electrically supervised for open and shorted or grounded circuits.
(c) Transformers for release mechanisms shall be rated for the proper use load, identified and located in proximity of the power supply for other fire alarm systems.
(d) The release mechanisms shall be operated from a separate control relay having the capability of indicating trouble on a separate trouble signal and at the information display system on the command console and at the mechanical control center. The mechanism shall also indicate a "failed" and "open" status on the command console and at the mechanical center.
(e) Where a fail-safe reentry door has been converted to conform to the requirements of this code by means of an electric strike release, provision shall be made to insure that the door will remain "Latched" even if "Unlocked".
13. RADIO SYSTEM.—A radio or radio/wire system shall comply with the following requirements:
(a) The emergency notification portion of the system equipment shall be capable of the following:
(1) Have the capability of individual, group or entire building notification of an alarm tone and voice intelligibility.
(2) Receivers and wire extension speakers shall be permanently mounted to a wall or pillar.
(3) There shall be automatic switch over to emergency battery power supply.
(b) Two way communication shall be accomplished by fixed transmitters and receivers.
(c) Equipment shall be Federal Communications Commission (FCC) approved, FM type, solid state, above 150.8 MHz. Selective signaling shall be accomplished by a minimum of 2 tone code operation.
(d) The antenna shall be designed and installed for use at the fire command station transmitter and be capable of transmitting to all fixed stations.
(e) The fire command station unit shall have the capability of locking out all other remote control points.
14. SPRINKLER WATERFLOW ALARMS.—A sprinkler waterflow alarm may be arranged to be used as part of a modified Class E fire alarm signal system provided: the alarm signal system shall be an approved electrically supervised closed circuit information display system capable of indicating the floor where the sprinkler was activated.
15. Elevator Communication.—Elevator intercommunication shall be acceptable for communications with the Fire Command Station if there is a means of communication proximate to the Fire Command Station.
RS 17-3B. STANDARDS FOR THE INSTALLATION OF MODIFIED CLASS E, AND MODIFIED CLASS J FIRE ALARM SIGNAL SYSTEMS
(Note: References herein shall be deemed to also include references to Modified Class J Systems.)
1. (A) SOURCES OF ELECTRICAL POWER
Two sources of electrical power shall be provided as follows:
(1) The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.
(2) The secondary source shall be an emergency power system (as per 27-396), emergency generator and/or battery power.
One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other Systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the New York City Electrical Code.
The primary source of power and the secondary source (if emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with a hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208-volt side. The incoming supply connections shall comply with the NYC Electrical Code, and the fused cutout panel shall comply with the requirements specified hereinbefore.
(B) PRIMARY POWER SOURCE
1. The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.
2. Partial systems such as strobe light control panels, partial fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and identified, locked fused cutout box located within 5 feet of the tap.
Where an emergency power system is provided in accordance with § 27-396.4, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.
(C) SECONDARY POWER SOURCE
The secondary service to the fire alarm system shall be provided as follows:
1. If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.
2. If the building has an emergency generator supplying power to any of the loads listed in § 27-396.4, the secondary source shall be the generator.
3. For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17–5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by:
a. 6 hour total system load for systems with voice communication capability (A 45 minute period of voice/alarm operation at maximum connected load shall be considered equivalent to 6 hours of total systems operation),
or
b. 15 minutes of total system load for systems without voice capability.
4. Partial systems and/or associated systems may derive their secondary supply from batteries whether or not the building is equipped with an emergency generator. Batteries shall be designed for 24-hour supervisory operation followed by 5 minutes of total system load.
All alterations to any existing approved fire alarm system involving or consisting of the replacement of the Fire Command Station, Fire Alarm Control Panel, Central Processing Unit, Floor Control Units, Remote Control Units, Data Gathering Panels, Terminal Transmission Board, and other similar or equivalent controls or control panels shall be required to comply with Section C3 above. For systems in buildings, which are in compliance with Sections (C)1 or (C)2 above, compliance with Section (C)3 is optional.
2. ASSOCIATED SYSTEMS.—
Associated systems listed below shall have their actuation added to the Fire Command Station.
(a) Smoke detection systems
(b) Sprinkler waterflow alarms
(c) Thermostatic alarms
(d) Locked door—fail safe release systems
(e) Elevator communication and interconnection.
3. WIRING.—
a. Power Conductors (Above 75 volts) shall be:
(1) Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW; minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).
(2) Cable type MI, M.E.A. approved for 2-hour fire resistance rating.
b. Low Voltage Conductors (75 volts and less)
(1) Copper; THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, XHHW, minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC), electric metallic tubing (EMT), and
(2) Minimum wire size No. 18 AWG.W.G.
(3) Multi-conductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:
a. Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150C; colored red.
b. Red colored jacket overall; minimum thickness 25 mils.
c. Cable printing as per UL1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE," legible without removing jacket.
c. Installation of Conductors and Raceway shall be in accordance with the following:
(1) Power conductors shall not be installed in common raceways with low voltage conductors.
(2) Shall comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.
(3) Conductors other than M.I. cable shall be run in raceway, except as specifically described below.
(4) Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within 8 feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment. In any suppression and extinguishing system activated by automatic fire detection, including, but not limited to, pre-action sprinkler, deluge sprinkler, clean air agent, halon, range hood, CO2 and dry chemical, multi-conductor cables shall be installed in RMC, IMC, or EMT.
(5) All wiring within mechanical and elevator equipment rooms shall be run in raceway.
(6) Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.
(7) Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT); except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing Reference Standard 17 conductors.
(8) Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:
a. Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support. Support independently from the building structure.
b. Secure by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Secure in place at intervals not exceeding 5'0" on centers and within 12" of every associated cabinet, box or fitting.
(9) Installation of raceways, boxes and cabinets shall comply with the following general requirements.
a. Covers of boxes and cabinets shall be painted red and permanently identified as to their use.
b. Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.
c. Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.
d. Raceways or cables shall not penetrate top of any equipment box or cabinet.
(10) All conduits supplying 120-volt power to the fire command station and/or fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AW minimum). The grounding conductor shall be connected to the ground buss or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).
(11) For cabinets whose 120-volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel, framed buildings, a connection to local steel structure will be acceptable.
(12) Splices and terminations of wires and cables shall be as follows:
a. Permitted only in boxes or cabinets specifically approved for the purpose.
b. Utilize mechanical connections specifically approved by U.L. 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.
(13) Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e., by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.
4. FIRE ALARM SENDING STATIONS, MODIFIED CLASS "E"—NON-CODED MANUAL STATION AND FLOOR WARDEN STATION.—
(a) There shall be at least one (1) fire alarm sending station in each story of a building located in each path of escape. Additional stations shall be installed so that no point on any floor shall be more than 200 feet from the nearest station.
(b) A floor warden station on each floor shall be located between required stairways, required vertical exits or other required exits. All types of systems shall include a telephone type handset at the floor warden station with integral signaling to the fire command station and may be a part of the speaker system. The handset shall be red and equipped with armor over the wiring between the handset and its housing that may be installed flush, semi-flush or surface mounted. The housing shall be painted red and identify its function. Equipment shall be installed within a box recessed or surface mounted, large enough to include the handset and test facility, by means of a key, to test the floor automatic and manual alarm device wiring. A pilot light shall indicate the live condition of the floor warden station.
Doors of sending stations shall be painted red and lettered "FIRE EMERGENCY—OPEN DOOR TO OPERATE" or words to this effect. Instructions for operating the station shall be permanently affixed or be an integral part of the station. Instruction cards shall be provided at each station protected by glass or plastic. Designation number of station shall be prominently displayed on instruction card or on cover of station.
(c) All current-carrying parts shall be insulated from parts carrying current of opposite polarity with approved insulating material.
(d) All pull-lever type stations shall be constructed with a door or other approved means to protect the "pull lever" against accidental injury. The wording "IN CASE OF FIRE—OPEN DOOR AND PULL DOWN LEVER" in raised letters or equivalent instructions, shall appear on the door.
(e) For systems using break-glass or break-rod type stations, at least one extra glass rod or glass pane for each station in the system shall be kept in the building. Break glass stations shall have the glass rod or pane mounted on the surface of the station covers or mounted internally in such manner that the glass must be broken to actuate the sending station. Suitable hammers on chains attached to the stations or other approved means of breaking the glass, shall be provided. Stations accomplishing the "break glass" principle using other approved means shall not be required to provide hammers or spare glasses.
(f) Non-coded stations.—
(1) Non-coded closed circuit fire alarm stations may be operated by a break-glass or break-rod or a pull lever device so arranged that the alarm cannot be interfered with except by resetting or replacement of the glass or rod by an authorized person.
(2) The construction and materials shall be equivalent to that of the standard approved type coded closed circuit station described in Reference Standard RS 17–3 except that the contacts shall be of sufficient capacity to safely carry the entire operating current of the alarm circuit without excessive heating.
(g) Station testing devices.—Provisions shall be made for a silent test of sending station mechanisms without operating the signaling devices. Such test device shall be designed to prevent any person, except those in authority, from operating the same and to prevent the possibility of the box being left inoperative after the test.
(h) Provision shall be made to supply an audible and visual signal at the fire command station from the floor warden station.
5. ALARM SOUNDING DEVICES.—
(a) Approved speakers shall be provided as the sounding devices. The alarm sound shall be a generated gong, bell, horn, whistle or other acceptable signal. Chime sounds may be installed only with the approval of the commissioner. Approved speakers shall have heat resistant driven elements and shall conform to Reference Standard RS 17–5.
When recessed speakers are used they shall conform to the performance requirements of Reference Standard RS 17–5. Speakers when mounted on walls shall be mounted upon tenant walls in preference to building core walls.
(b) Recessed speakers if used shall be located not more than 10 feet from the entrance to each required exit to insure proper alarm signal reproduction. This spacing is based upon normal 8 feet–10 feet ceiling height. Surface mounted type speakers shall be mounted within 10 feet of each egress to insure proper alarm signal reproduction. For unusual conditions and higher ceilings, speakers shall not be mounted more than 20 feet above floor.
(c) The alarm sounding devices may be utilized for other audio purposes including building security if means is provided to insure fire alarm priority.
6. FIRE ALARM SYSTEM CONTROL BOARDS AND COMMAND STATIONS.—
(a) Supervising Circuit.—
(1) Modified class "E" fire alarm systems shall be supervised.
(2) The supervising circuit shall be provided with a trouble signal arranged to sound continuously in case of failure of the power source. The trouble signal shall be so located that it will be within audible range of a responsible person in the building.
(3) Trouble signals may be fitted with silencing switches only when the switch is connected in such a manner that the act of silencing the signal by the operation of the switch automatically transfers the trouble signal to a red lamp on the fire command station. When the trouble has been repaired, the alarm signal shall sound until the silencing switch has been reset to operate under normal conditions.
(4) The trouble signal shall give a distinctive signal.
(b) Protection of Sending and Sounding Devices.—In fire alarm signal systems, sending stations and sounding devices shall be enclosed in metal casings, made dust proof and damp proof when necessary, and clearly marked with instructions for use.
(c) Standards of Electric Alarm Apparatus.—All electrically actuated apparatus used in fire alarm systems shall be so designed and constructed that it will operate satisfactorily at an input voltage level 15 per cent below or 10 per cent above normal rated voltage.
(d) Insulation.—
(1) Insulating materials used shall be varnished cambric, bakelite, mica, or equivalent insulating material.
(2) The use of fiber or paper as an insulating material is prohibited.
(3) The insulating materials used shall be capable of withstanding an insulation breakdown test of 1,000 volts a.c. plus twice operating voltage applied for 1 minute.
(e) Electromagnets.—
(1) Electromagnet windings shall be impregnated with an insulating, moisture repelling compound of the silicone or epoxy type.
(2) Electromagnet coils used on alternating current, when composed of enameled wire shall have additional approved insulation on each wire. The coils may be of the form-wound type.
(3) A protective cover to prevent mechanical damage shall be provided over the entire coil.
(4) Electromagnetic coils shall be fastened to prevent floating.
(5) Electromagnet cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.
(6) Electromagnet cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and promote efficiency.
(7) Electromagnetic cores of relays shall be treated to prevent corrosion. Paint or varnish shall not be used for this purpose.
(8) Non-magnetic freeze pins shall be used to prevent two magnetic surfaces from making physical contact with each other.
(f) Relays.—
(1) The armatures of all relays shall depend on gravity or magnetic attraction for their operation and may be assisted by a spring.
(2) Adjustments shall be of such a character that they can be securely locked.
(g) Overload protective devices.—Electronic circuits shall provide protection of all equipment and circuits by opening up the circuit to the equipment or devices protected. The operation of this "overload circuit" shall cause the trouble signal to sound at the fire command station.
(h) Control boards shall operate so that troubles in individual zones may be shunted out without affecting the rest of the system.
(i) Provision shall be made for sufficient wire gutter space around the panel. Gutter space shall be a minimum of 2 inches at sides, top, and bottom. Wire in gutter space shall be properly laced in a neat and workmanlike manner on all control boards.
(j) Conduit knockouts shall not be provided in the top of the control board cabinet unless designed and approved for entry on top.
(k) A wiring diagram of the alarm system approved by the commissioner and the approved card of instruction properly marked and securely fastened shall be provided within the control board cabinet and at the fire command station. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be framed under glass or equivalent material.
(l) Control Boards.—
(1) Control boards and amplifiers used for voice communication and alarms shall be located in a safe, moisture and dust free location secure from unauthorized tampering. Otherwise a ventilated cabinet provided with a lock and key, suitably identified, shall be provided.
(2) Amplifiers for modified class "E" systems shall have the capacity to deliver sufficient power to operate all alarm sounding devices and voice communication system and have a 50 per cent reserve power capacity. In addition the amplifiers shall be wired in such a manner that the imminent failure or actual failure of amplifiers shall shut down the amplifier and indicate a trouble condition. Removal of an amplifier shall be indicated by a trouble signal at the fire command station. Opening of the control cabinets shall be supervised by a tamper switch producing a manually resettable trouble alarm at the fire command station.
(m) Fire Command Station.—The fire command station shall contain all the components described in the building code and shall have the capability of overriding floor warden stations. The command station console shall be provided with a hinged cover which permits the flashing "FIRE" visible signal to be seen. The cover shall be provided with an approved lock and key. The fire command station shall be provided with an information display system so located as to provide minimum distortion due to an angular line-of-sight and ambient lighting conditions. This display shall have the capability to monitor the following systems in order of listed priority:
(1) Manual Fire Alarm
(2) Smoke Detection
(3) Sprinkler Waterflow
(4) Elevator Lobby Detector
(5) Fire Signal Activation
(6) Central Office Notification
(7) Fan System On—Fan System Off
(8) Fail Safe Locked Door
(9) Fire Systems Trouble
(10) Fire Signal Trouble
(11) Tamper Switch Alarm
(12) Power Source
(13) Test/Normal Mode
(14) Other Information as Desired
7. PAINTING OF EQUIPMENT.—All enclosing cases for fire alarm, sprinkler alarm, smoke detection, and associated systems alarm apparatus shall be painted fire department red, except where approval is given by the commissioner to deviate from this requirement. The lobby information display system may be painted or finished to suit the owner of the building.
8. INFORMATION DISPLAY SYSTEMS.—
(a) Information display systems used in connection with modified class E fire alarm signal systems shall be of an approved electrically supervised type. The indicating devices shall describe the purpose they serve. The printed designation on unit or building information display system indicators shall be legible. The mechanism shall be so arranged that once operated, the indicating device must be reset manually. All conditions indicated shall remain displayed until manually cleared at the fire command station.
(b) A unit information display system shall be so designed that the operation of any station in the unit causes a visible and audible signal.
(c) Trouble displays shall be so arranged that the indicating device will reset automatically when the cause of trouble has been removed. The trouble information display system shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit monitored. The trouble information display system shall be actuated by the operation of supervisory devices.
(d) A silencing switch shall be provided for trouble signals, but shall not affect subsequent trouble signals.
(e) Information display systems shall be so designed that vibration from without or that caused by a trouble signal within will not operate the indicating devices.
(f) All remote information display systems shall be installed in a separate steel cabinet painted red, provided with approved lock and key. Information display system cabinets shall be marked in white letters at least one inch high with the words: "FIRE ALARM INFORMATION DISPLAY SYSTEM, ZONE ——" or "FIRE ALARM TROUBLE INFORMATION DISPLAY SYSTEM", whichever the case may be.
(g) Information display systems located in the lobby of a building whether an integral part of the fire command station or wall mounted shall have the legend "FIRE" in red letters three inches high together with an audible signal in addition to the lamp, target drop, cathode ray tube, light emitting diode, nixie, etc. and a separate or distinctive trouble signal shall sound. The audible signal accompanying an alarm shall be automatically silenced when the fire command station is operated by the fire safety director or his delegated substitute. Remote information display systems shall operate in the same manner.
(h) The display shall provide a minimum of four simultaneous alarm indicators with an overflow indication for additional alarms. Provisions shall be made to distinguish alarm conditions from non-alarm conditions. The display shall be updated as new information becomes available. If the same condition exists for more than one point on a floor or for more than one floor in a building, such as a fire gong actuation or public address, a separate output entry shall be displayed for each point or floor.
(i) Display Format.—Each output entry shall include self-identifying mnemonic codes for the type of signal, building or area designation, floor or stair number and point location, and time of day. Systems utilizing gravity drops or lamps as point identification, may provide a hard copy print out.
(j) Maintainability.—
(1) Manual display of all points of annunciation for test purposes shall be provided.
(2) Capability shall be provided for interrogating any station or sensing element for test purposes, either at the remote device or by interrogation from the fire command station. Intervals of testing shall be as approved.
(3) Equipment design shall be modular so that all repairs may be performed on-site by substitution of duplicate components by authorized personnel.
(4) One each of these parts that are of a modular nature shall be included as spares at the fire command station.
9. LICENSED CONTRACTORS.—Only a person holding a license or a special license in accordance with the provisions of the New York City electrical code, shall install, alter, or repair electrical wiring or apparatus for fire alarm systems in any building.
10. USED OR REBUILT APPARATUS.—Used apparatus shall not be re-used for any interior fire alarm system until the same has been reconditioned in the shop of any approved manufacturer of interior fire alarm apparatus. Approval shall be obtained from the commissioner prior to installation. The use of reconditioned apparatus whose manufacturer has discontinued manufacturing equipment is prohibited.
11. STANDPIPE FIRELINE TELEPHONE AND SIGNAL SYSTEM.—Where the standpipe telephone and signal system is arranged to be used as a modified class E fire alarm signal system as provided in the building code, retractable telephone handsets shall be provided in pump rooms. The telephone in pump rooms shall be equipped with a loudspeaking receiver so that a voice can be distinctly heard at least 15 feet from the receiver.
12. LOCKED DOOR FAIL SAFE SYSTEMS.—
(a) Stairway reentry doors, which are locked from the stairway side as permitted in § 27-371 of the administrative code, shall be provided with an electrical fail safe strike release mechanism that will permit the door to be opened without a key when any automatic fire-detecting device operates, elevator "Fireman Service" operates or power failure shall occur. In addition, provisions shall be made to permit these doors to be opened from the command station or mechanical control center. This system shall be manually reset.
(b) Wiring for these systems shall be electrically supervised for open and shorted or grounded circuits.
(c) Transformers for release mechanisms shall be rated for the proper use load, identified and located in proximity of the power supply for other fire alarm systems.
(d) The release mechanisms shall be operated from a separate control relay having the capability of indicating trouble on a separate trouble signal and at the information display system on the command console and at the mechanical control center. The mechanism shall also indicate a "failed" and "open" status on the command console and at the mechanical control center.
13. RADIO SYSTEM.—A radio or radio/wire system shall comply with the following requirements:
(a) The emergency notification portion of the system equipment shall be capable of the following:
(1) Have the capability of individual, group or entire building notification of an alarm tone and voice intelligibility.
(2) Receivers and wire extension speakers shall be permanently mounted to a wall or pillar.
(3) There shall be automatic switch over to emergency battery power supply.
(b) Two-way communication shall be accomplished by fixed transmitters and receivers.
(c) Equipment shall be Federal Communications Commission (FCC) approved, FM type, solid state, above 150.8 MHz. Selective signaling shall be accomplished by a minimum of 2 tone code operation.
(d) The antenna shall be designed and installed for use at the fire command station transmitter and be capable of transmitting to all fixed stations.
(e) The fire command station unit shall have the capability of locking out all other remote control points.
14. SPRINKLER WATERFLOW ALARMS.—A sprinkler waterflow alarm may be arranged to be used as part of a modified class E fire alarm signal system provided: the alarm signal system shall be an approved electrically supervised closed circuit information display system capable of indicating the floor where the sprinkler was activated.
15. ELEVATOR COMMUNICATION.—Elevator intercommunication shall be acceptable for communications with the Fire Command Station if there is a means of communication proximate to the Fire Command Station.
RS 17-3C. STANDARDS FOR THE INSTALLATION OF VISUAL AND AUXILIARY ALARMS REQUIRED BY SECTION 27-292.15
1. DEFINITIONS.—
(a) Visual Alarms (Strobe):
Visual alerting device which when activated by either an integral or an external initiating device provides an alarm signal in the form of a flashing high intensity light source (usually xenon) with frequency approximately of one (1) Hz.
(1) System Type Strobe: A strobe connected by direct wiring to an overall fire alarm system and upon which it depends for its actuating signal.
(2) Extension Type Strobe: A strobe connected by direct wiring to a single station smoke detector and upon which it depends for its actuating signal.
(b) Auxiliary Alarms.—
(1) Portable System Type Strobe: Strobe equipped with cord and plug (power supply), and a receiver arranged to detect the presence of the alarm tone, emitted by the fire alarm system thereby causing it to operate (flash).
2. GENERAL REQUIREMENTS.—
(a) An installation of a new fire alarm and signal system incorporating audible devices intended to evacuate building occupants shall require strobes to be installed as part of the system.
(b) Installation of strobes in existing buildings may either be installed as part of an interior fire alarm and signal system or be connected to an approved strobe control panel.
3. POWER SUPPLY.—
(a) Except as noted in (b) below, strobes that are subject to the requirements of section two above, shall derive power from the interior fire alarm and signal system.
(b) When not powered by the interior fire alarm and signal system, independent strobe control panels shall supply power to strobes. Such control panels shall derive their power from a normal or emergency 120-volt source supplying the floor, via a separately installed locked fire alarm cutout connected to electrical supply in accordance with the requirements of the Electrical Code.
4. STROBE CONTROL PANEL.—
(a) A strobe control panel shall be approved by the Bureau of Electrical Control or approved by the Board of Standards and Appeals.
(b) The panel shall cause fire alarm signal received from interior fire alarm system to activate strobes.
(c) The panel shall have a battery and charger capable of providing at least fifteen (15) minutes of full system alarm operation following twenty-four (24) hours of supervisory operation.
(d) Strobes may be reset from the fire command station by an identified reset device. When strobes cannot be turned off from the fire command station, a timer to shut off the strobes and reset the panel five (5) minutes after they are activated shall be provided in the panel.
(e) The panel shall incorporate electrical supervision of
(1) Alarm circuitry for strobes,
(2) Initiating circuitry from the building fire alarm system, and
(3) The 120 VAC power source, and battery.
(f) The panel shall have a trouble contact for reporting to the interior fire alarm and signal system and shall have remote trouble bell.
(g) The panel shall be capable of disconnecting any flashing or in-motion lighting that may make strobes ineffective.
5. WIRING.—The flashing strobes powered either through an interior fire alarm and signal system or independently through a control panel shall operate in conjunction with the audible signals and shall:
(a) Meet the requirements of Reference Standard RS 17–3A when required in a Class E, Class C and Class J fire alarm signal and signal system.
(b) Meet the requirements of Reference Standard RS 17–3B when required in a Modified Class E and Modified Class J fire alarm and signal system and
(c) Meet the requirements of Reference Standard RS 17–3 when required in any other fire alarm and signal system.
6. PORTABLE SYSTEM TYPE STROBE.—
(a) The strobe shall have a battery and charger capable of providing at least five (5) minutes of strobe operation following twenty-four (24) hours of supervisory operations.
(b) The strobe shall have a visual trouble indication when power is lost.
7. LOCATION OF STROBES.—
(a) When strobes are installed on walls, they shall be a minimum of 80 inches above the floor or a maximum of 6 inches below the ceiling.
(b) When strobes are installed in ceilings, there shall be no other devices (such as exit lights) or building appurtenances (such as beams or smoke curtains) within 5 feet of the strobe.