NYC Administrative Code RS 17-3C STANDARDS FOR THE INSTALLATION OF VISUAL AND AUXILIARY ALARMS REQUIRED BY SECTION 27-292.15

1. DEFINITIONS.—

(a) Visual Alarms (Strobe):

Visual alerting device which when activated by either an integral or an external initiating device provides an alarm signal in the form of a flashing high intensity light source (usually xenon) with frequency approximately of one (1) Hz.

(1) System Type Strobe: A strobe connected by direct wiring to an overall fire alarm system and upon which it depends for its actuating signal.

(2) Extension Type Strobe: A strobe connected by direct wiring to a single station smoke detector and upon which it depends for its actuating signal.

(b) Auxiliary Alarms.—

(1) Portable System Type Strobe: Strobe equipped with cord and plug (power supply), and a receiver arranged to detect the presence of the alarm tone, emitted by the fire alarm system thereby causing it to operate (flash).

2. GENERAL REQUIREMENTS.—

(a) An installation of a new fire alarm and signal system incorporating audible devices intended to evacuate building occupants shall require strobes to be installed as part of the system.

(b) Installation of strobes in existing buildings may either be installed as part of an interior fire alarm and signal system or be connected to an approved strobe control panel.

3. POWER SUPPLY.—

(a) Except as noted in (b) below, strobes that are subject to the requirements of section two above, shall derive power from the interior fire alarm and signal system.

(b) When not powered by the interior fire alarm and signal system, independent strobe control panels shall supply power to strobes. Such control panels shall derive their power from a normal or emergency 120-volt source supplying the floor, via a separately installed locked fire alarm cutout connected to electrical supply in accordance with the requirements of the Electrical Code.

4. STROBE CONTROL PANEL.—

(a) A strobe control panel shall be approved by the Bureau of Electrical Control or approved by the Board of Standards and Appeals.

(b) The panel shall cause fire alarm signal received from interior fire alarm system to activate strobes.

(c) The panel shall have a battery and charger capable of providing at least fifteen (15) minutes of full system alarm operation following twenty-four (24) hours of supervisory operation.

(d) Strobes may be reset from the fire command station by an identified reset device. When strobes cannot be turned off from the fire command station, a timer to shut off the strobes and reset the panel five (5) minutes after they are activated shall be provided in the panel.

(e) The panel shall incorporate electrical supervision of

(1) Alarm circuitry for strobes,

(2) Initiating circuitry from the building fire alarm system, and

(3) The 120 VAC power source, and battery.

(f) The panel shall have a trouble contact for reporting to the interior fire alarm and signal system and shall have remote trouble bell.

(g) The panel shall be capable of disconnecting any flashing or in-motion lighting that may make strobes ineffective.

5. WIRING.—The flashing strobes powered either through an interior fire alarm and signal system or independently through a control panel shall operate in conjunction with the audible signals and shall:

(a) Meet the requirements of Reference Standard RS 17–3A when required in a Class E, Class C and Class J fire alarm signal and signal system.

(b) Meet the requirements of Reference Standard RS 17–3B when required in a Modified Class E and Modified Class J fire alarm and signal system and

(c) Meet the requirements of Reference Standard RS 17–3 when required in any other fire alarm and signal system.

6. PORTABLE SYSTEM TYPE STROBE.—

(a) The strobe shall have a battery and charger capable of providing at least five (5) minutes of strobe operation following twenty-four (24) hours of supervisory operations.

(b) The strobe shall have a visual trouble indication when power is lost.

7. LOCATION OF STROBES.—

(a) When strobes are installed on walls, they shall be a minimum of 80 inches above the floor or a maximum of 6 inches below the ceiling.

(b) When strobes are installed in ceilings, there shall be no other devices (such as exit lights) or building appurtenances (such as beams or smoke curtains) within 5 feet of the strobe.