NYC Administrative Code RS 17-3A STANDARDS FOR THE INSTALLATION OF CLASS E, CLASS C AND CLASS J FIRE ALARM SIGNAL SYSTEMS

(Note: References herein to Class E Systems shall be deemed to also include references to Class C and Class J Systems.)

1. (A) SOURCES OF ELECTRICAL POWER

Two sources of electrical power shall be provided as follows:

(1) The primary source shall be generated electric power not exceeding 277/480 volts, supplied by utility company power, or isolated plant.

(2) The secondary source shall be an emergency power system (as per 27-396), emergency generator and/or battery power.

One source of power shall be connected to the system at all times. The primary and secondary power sources shall be so arranged and controlled by automatic transfer switches and/or circuitry that when the primary source of power fails, the secondary source will be connected automatically to the fire alarm signal system. Intermediary devices between the system supply and the source of power, other than fused disconnect switches, transformers, fused cutouts and automatic transfer switches, are prohibited. Such disconnect switches, cutouts, transformers and automatic transfer switches shall supply only the fire alarm system and other Systems covered by this reference standard. When the utility company requires the installation of metering current transformers, the system supply shall be connected on the load side of the current transformers. All installations shall comply with the applicable sections of the New York City Electrical Code.

The primary source of power and the secondary source (if emergency power system or generator) shall each be provided with a means of disconnect from the fire alarm system. For buildings supplied at 120/208 volts, each disconnect shall consist of a fused cutout panel, utilizing cartridge fuses, with provision for interrupting the unfused neutral and all ungrounded conductors. The neutral shall be provided with a removable solid copper bar. The incoming service neutral shall be bonded to the metallic housing of the cutout panel on the line side of the removable bar. The fused cutout panel housing shall consist of a locked metallic cabinet with a hinged door, painted fire department red, and permanently identified as to the system served. For buildings served at 265/460 volts, the primary and secondary service disconnects shall be fused disconnect switches (in lieu of fused cutout panels) in locked, red painted, permanently identified enclosures. The service voltage shall be transformed to 120/208 volts and a fused cutout panel provided within 5 feet of the transformer on the 120/208-volt side. The incoming supply connections shall comply with the NYC Electrical Code, and the fused cutout panel shall comply with the requirements specified hereinbefore.

(B) PRIMARY POWER SOURCE

1. The primary service to the fire alarm system shall be so arranged that the building source of supply can be disconnected without de-energizing the fire alarm supply. To accomplish this, the primary fire alarm supply shall be connected ahead of all building over current protection and/or switching devices.

2. Partial systems such as strobe light control panels, fire alarm, automatic smoke/heat detection, and sprinkler alarm subsystems and/or other associated systems may be connected to an emergency supply riser panel via a tapped connection, and identified, locked fused cutout box located within 5 feet of the tap.

Where an emergency power system is provided in accordance with section § 27-396.4, it shall be connected to the emergency supply riser. Where an E.P.S. is not available, the emergency supply riser shall be connected to a tap ahead of the service switch.

(C) SECONDARY POWER SOURCE

The secondary service to the fire alarm system shall be provided as follows:

1. If the building has a required emergency power system, the secondary source shall be the emergency power system, regardless of whether the primary source is utility company power or an isolated plant.

2. If the building has an emergency generator supplying power to any of the loads listed in § 27-396.4, the secondary source shall be the generator.

3. For all other buildings, the secondary source shall be a battery supply provided in accordance with Reference Standard 17–5 for storage batteries. The battery shall be designed for 24-hour supervisory operation of the system, followed by:

a. 6 hour total system load for systems with voice communication capability (A 45 minute period of voice/alarm operation at maximum connected load shall be considered equivalent to 6 hours of total systems operation),

or

b. 15 minutes of total system load for systems without voice capability.

4. Partial systems and/or associated systems may derive their secondary supply from batteries whether or not the building is equipped with an emergency generator. Batteries shall be designed for 24-hour supervisory operation followed by 5 minutes of total system load.

All alterations to any existing approved fire alarm system involving or consisting of the replacement of the Fire Command Station, Fire Alarm Control Panel, Central Processing Unit, Floor Control Units, Remote Control Units, Data Gathering Panels, Terminal Transmission Board, and other similar or equivalent controls or control panels shall be required to comply with Section C3 above. For systems in buildings, which are in compliance with Sections (C)1 or (C)2 above, compliance with Section (C)3 is optional.

2. ASSOCIATED SYSTEMS.—

Associated systems listed below shall have their actuation added to the Fire Command Station.

(a) Smoke detection systems.

(b) Sprinkler waterflow alarms.

(c) Thermostatic alarms.

(d) Locked door-fail safe release systems.

(e) Elevator communication and interconnection.

(f) Stair pressurization fan(s) and associated damper(s)

3. WIRING.—

a. Power Conductors (Above 75 volts) shall be:

(1) Copper: THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, or XHHW; minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT).

(2) Cable type MI, M.E.A. approved for 2-hour fire resistance rating.

b. Low Voltage Conductors (75 volts and less)

(1) Copper; THHN, THWN/THHN, TFFN, TFN, FEP, RHH, RHW-2, XHH, XHHW, minimum 600 volts; 90 C; for installation in rigid metallic conduit (RMC), intermediate metallic conduit (IMC), electric metallic tubing (EMT)

(2) Minimum wire size No. 18 AWG.W.G.

(3) Multi-conductor cables run in raceways, or exposed as described hereinafter, shall meet the following additional requirements:

a. Type FPLP only; minimum insulation thickness 15 mils; minimum temperature 150C; colored red.

b. Red colored jacket overall; minimum thickness 25 mils.

c. Cable printing as per UL1424; must bear additional description "ALSO CLASSIFIED NYC CERT. FIRE ALARM CABLE," legible without removing jacket.

c. Installation of Conductors and Raceway shall be in accordance with the following:

(1) Power conductors shall not be installed in common raceways with low voltage conductors.

(2) Shall comply with applicable requirements of New York City Electrical Code, except where requirements are exceeded by this Reference Standard.

(3) Conductors other than M.I. cable shall be run in raceway, except as specifically described below.

(4) Multi-conductor cables may be installed without raceway protection where cable is protected by building construction. Where not protected by building construction, cables shall be located 8 feet or more above the finished floor and not subject to physical tampering or hazard. Locations within eight feet of the finished floor that are deemed as "protected by building construction" shall include raised floors, shafts, telephone and communication equipment rooms and closets, and rooms used exclusively for fire alarm system equipment. In any suppression and extinguishing system activated by automatic fire detection, including, but not limited to, pre-action sprinkler, deluge sprinkler, clean air agent, halon, range hood, CO2 and dry chemical, multi-conductor cables shall be installed in RMC, IMC, or EMT.

(5) All wiring within mechanical and elevator equipment rooms shall be run in raceway.

(6) Where wiring is required to be run in raceway, install conductors in rigid metallic conduit (RMC), intermediate metallic conduit (IMC) or electric metallic tubing (EMT); except that multi-conductor cables may also be run in surface metal raceway. Flexible metallic conduit, not exceeding 36" in length, shall be permitted for final connections to initiating and notification devices. Conductors for other electrical systems shall not be installed in raceways containing Reference Standard 17 conductors.

(7) Where allowed to be run without raceway protection, multi-conductor cables shall be installed as follows:

a. Cables shall not depend on ceiling media, pipes, ducts, conduits, or equipment for support. Support independently from the building structure.

b. Secure by cable ties, straps or similar fittings, so designed and installed as not to damage the cable. Secure in place at intervals not exceeding 5'0" on centers and within 12" of every associated cabinet, box or fitting.

(8) Raceways run within 8 feet of finished floor in garage areas, loading docks, mechanical rooms, and elsewhere where subject to mechanical damage, shall be rigid galvanized steel conduit only.

(9) Installation of raceways, boxes and cabinets shall comply with the following general requirements.

a. Covers of boxes and cabinets shall be painted red and permanently identified as to their use.

b. Penetrations of fire-rated walls, floors or ceilings shall be fire stopped.

c. Within stairways, raceways within 8 feet of the floor shall not be installed so as to reduce or obstruct the stairway radius.

d. Raceways or cables shall not penetrate top of any equipment box or cabinet.

(10) All conduits supplying 120-volt power to the fire command station and/or fire alarm control unit and/or to outlying control cabinets, shall contain a green insulated grounding conductor sized in accordance with the New York City Electrical Code (#10 AWG minimum). The grounding conductor shall be connected to the ground bus or other suitable grounding terminal in each box and cabinet in which it enters. At the fuse cutout panel supplying the fire alarm system, provide a grounding electrode conductor sized and installed in accordance with the New York City Electrical Code (#10 AWG minimum).

(11) For cabinets whose 120-volt supply is not derived from the main fire alarm system cutout panel, provide green insulated separate grounding electrode conductors, sized and installed as per New York City Electrical Code (#10 AWG minimum). In steel, framed buildings, a connection to local steel structure will be acceptable.

(12) Splices and terminations of wires and cables shall be as follows:

a. Permitted only in boxes or cabinets specifically approved for the purpose.

b. Utilize mechanical connections specifically approved by U.L. 486 A & C for the conductors, or if soldered, first joined so as to be mechanically and electrically secure prior to soldering and insulating. Temperature rating of completed splices shall equal or exceed the temperature rating of the highest rated conductor.

(13) Wiring for audible and visual alarm notification devices shall be arranged so that a loss of a portion of the wiring on a floor will not render more than 60% of the devices of each type inoperative, and the devices shall be so connected to the circuitry (i.e., by means of alternate circuits) as to maintain at least partial audibility/visibility throughout the entire floor.

4. FIRE ALARM SENDING STATIONS, CLASS "E"—NON-CODED MANUAL STATION, AND FLOOR WARDEN STATION.—

(a) There shall be at least one (1) fire alarm sending station in each story of a building located in each path of escape. Additional stations shall be installed so that no point on any floor shall be more than 200 feet from the nearest station.

(b) A floor warden station on each floor shall be located between required stairways, required vertical exits or other required exits. All types of systems shall include a telephone type handset at the floor warden station with integral signaling to the fire command station and may be a part of the speaker system. The handset shall be red and equipped with armor over the wiring between the handset and its housing that may be installed flush, semi-flush or surface mounted. The housing shall be painted red and identify its function. Equipment shall be installed with a box recessed or surface mounted large enough to include the handset and test facility, by means of a key, to test the floor automatic and manual alarm device wiring. A pilot light shall indicate the live condition of the floor warden station.

Doors of sending stations shall be painted red and lettered "FIRE EMERGENCY—OPEN DOOR TO OPERATE" or words to this effect. Instructions for operating the station shall be permanently affixed or be an integral part of the station. Instruction cards shall be provided at each station protected by glass or plastic. Designation number of station shall be prominently displayed on instruction card or on cover of station.

(c) All current-carrying parts shall be insulated from parts carrying current of opposite polarity with approved insulating material.

(d) All pull-lever type stations shall be constructed with a door or other approved means to protect the "pull-lever" against accidental injury. The wording "IN CASE OF FIRE—OPEN DOOR AND PULL DOWN LEVER" in raised letters or equivalent instructions, shall appear on the door.

(e) For systems using break-glass or break-rod type stations, at least one extra glass rod or glass pane for each station in the system shall be kept in the building. Break glass stations shall have the glass rod or pane mounted on the surface of the station covers or mounted internally in such a manner that the glass must be broken to actuate the sending station. Suitable hammers on chains attached to the stations or other approved means of breaking the glass, shall be provided. Stations accomplishing the "break glass" principle using other approved means shall not be required to provide hammers or spare glasses.

(f) Non-Coded Stations:

(1) Non-coded closed circuit fire alarm stations may be operated by a break-glass or break-rod or a pull lever device so arranged that the alarm cannot be interfered with except by resetting or replacement of the glass or rod by an authorized person.

(2) The construction and materials shall be equivalent to that of the standard approved type coded closed circuit station described in Reference Standard RS 17–3 except that the contacts shall be of sufficient capacity to safely carry the entire operating current of the alarm circuit without excessive heating.

(g) Station Testing Devices.—Provisions shall be made for a silent test of sending station mechanisms without operating the signaling devices. Such test device shall be designed to prevent any person, except those in authority, from operating the same and to prevent the possibility of the box being left inoperative after the test.

(h) Provision shall be made to supply an audible and visual signal at the fire command station from the floor warden station.

(i) A designated station on each floor shall have the capability of operating the loud speakers for that floor.

5. ALARM SOUNDING DEVICES.—

(a) Approved speakers shall be provided as the sounding devices. The alarm sound shall be a generated gong, bell, horn, whistle or other acceptable signal. Chime sounds may be installed only with the approval of the commissioner. Approved speakers shall have heat resistant driven elements and shall conform to Reference Standard RS 17–5.

When recessed speakers are used they shall conform to the performance requirements of Reference Standard RS 17–5. Speakers when mounted on walls shall be mounted upon tenant walls in preference to building core walls.

(b) Recessed speakers if used shall be located not more than 10 feet from the entrance to each required exit to insure proper alarm signal reproduction. This spacing is based upon normal 8 feet–10 feet ceiling height. Surface mounted type speakers shall be mounted within 10 feet of each egress to insure proper alarm signal reproduction. For unusual conditions and higher ceilings, speakers shall not be mounted more than 20 feet above floor.

(c) The alarm sounding devices may be utilized for other audio purposes including building security if means is provided to insure fire alarm priority.

6. FIRE ALARM SYSTEM CONTROL BOARDS AND COMMAND STATIONS.—

(a) Supervising Circuit.—

(1) Class "E" fire alarm systems shall be supervised.

(2) The supervising circuit shall be provided with a trouble signal arranged to sound continuously in case of failure of the primary power source. The trouble signal shall be so located that it will be within audible range of a responsible person in the building.

(3) Trouble signals may be fitted with silencing switches only when the switch is connected in such a manner that the act of silencing the signal by the operation of the switch automatically transfers the trouble signal to a red lamp on the fire command station. When the trouble has been repaired, the alarm signal shall sound until the silencing switch has been reset to operate under normal conditions.

(4) The trouble signal shall give a distinctive signal.

(b) Protection of Sending and Sounding Devices.—In fire alarm signal systems, sending stations and sounding devices shall be enclosed in metal casings, made dust proof and damp proof when necessary, and clearly marked with instructions for use.

(c) Standards of Electric Alarm Apparatus.—All electrically actuated apparatus used in fire alarm systems shall be so designed and constructed that it will operate satisfactorily at an input voltage level 15 per cent below or 10 per cent above normal rated voltage.

(d) Insulation.—

(1) Insulating materials used shall be varnished cambric, Bakelite, mica, or equivalent insulating material.

(2) The use of fiber or paper as an insulating material is prohibited.

(3) The insulating materials used shall be capable of withstanding an insulation breakdown test of 1,000 volts a.c. plus twice operating voltage applied for 1 minute.

(e) Electromagnets.—

(1) Electromagnet windings shall be impregnated with an insulating, moisture repelling compound of the silicone or epoxy type.

(2) Electromagnet coils used on alternating current, when composed of enameled wire shall have additional approved insulation on each wire. The coils may be of the form-wound type.

(3) A protective cover to prevent mechanical damage shall be provided over the entire coil.

(4) Electromagnetic coils shall be fastened to prevent floating.

(5) Electromagnet cores shall be of the best grade of ferrous material so as to reduce to a minimum the possibility of failure due to residual magnetism.

(6) Electromagnet cores for use on alternating current shall be of laminated construction or other approved method to prevent heating and promote efficiency.

(7) Electromagnetic cores of relays shall be treated to prevent corrosion. Paint or varnish shall not be used for this purpose.

(8) Non-magnetic freeze pins shall be used to prevent two magnetic surfaces from making physical contact with each other.

(f) Relays.—

(1) The armatures of all relays shall depend on gravity or magnetic attraction for their operation and may be assisted by a spring.

(2) Adjustments shall be of such a character that they can be securely locked.

(g) Overload protective devices.—Electronic circuits shall provide protection of all equipment and circuits by opening up the circuit to the equipment or devices protected. The operation of this "overload circuit" shall cause the trouble signal to sound at the fire command station.

(h) Control boards shall operate so that troubles in individual zones may be shunted out without affecting the rest of the system.

(i) Provision shall be made for sufficient wire gutter space around the panel. Gutter space shall be a minimum of 2 inches at sides, top, and bottom. Wire in gutter space shall be properly laced in a neat and workmanlike manner on all control boards.

(j) Conduit knockouts shall not be provided in the top of the control board cabinet, unless designed and approved for entry on top.

(k) A wiring diagram of the alarm system approved by the commissioner and the approved card of instruction properly marked and securely fastened shall be provided within the control board cabinet and at the fire command station. When it becomes necessary to mount the diagram outside of the cabinet, the diagram shall be framed under glass or equivalent material.

(l) Control Boards.—

(1) Control boards and amplifiers used for voice communication and alarms shall be located in a safe, moisture and dust free location secure from unauthorized tampering. Otherwise a ventilated cabinet provided with a lock and key, suitably identified, shall be provided.

(2) Amplifiers for class E systems shall have the capacity to deliver sufficient power to operate all alarm sounding devices and voice communication system and have a 50 per cent reserve power capacity. In addition the amplifiers shall be wired in such a manner that the imminent failure or actual failure of amplifiers shall shut down the amplifier and indicate a trouble condition. Removal of an amplifier shall be indicated by a trouble signal at the fire command station. Opening of the control cabinets shall be supervised by a tamper switch producing a manually resetable trouble alarm at the fire command station.

(m) Fire Command Station.—The fire command station shall contain all the components described in the building code and shall have the capability of overriding floor warden stations. The command station console shall be provided with a hinged cover that permits the flashing "FIRE" visible signal to be seen. The cover shall be provided with an approved lock and key. The fire command station shall be provided with an information display system so located as to provide minimum distortion due to an angular line-of-sight and ambient lighting conditions. This display shall have the capability to monitor the following systems in order of listed priority:

(1) Manual Fire Alarm

(2) Smoke Detection

(3) Sprinkler Waterflow

(4) Elevator Lobby Detector

(5) Fire Signal Activation

(6) Central Office Notification

(7) Fan System on—Fan System off

(8) Fail Safe Locked Door

(9) Fire Systems Trouble

(10) Fire Signal Trouble

(11) Tamper Switch Alarm

(12) Power Source

(13) Test/Normal Mode

(14) Other Information as Desired

(15) Stair pressurization fan(s) and associated damper(s).

7. PAINTING OF EQUIPMENT.—All enclosing cases for fire alarm, sprinkler alarm, smoke detection, and associated systems alarm apparatus shall be painted fire department red, except where approval is given by the commissioner to deviate from this requirement. The lobby information display system may be painted or finished to suit the owner of the building.

8. INFORMATION DISPLAY SYSTEMS.—

(a) Information display systems used in connection with Class E Fire Alarm Signal Systems shall be of an approved electrically supervised type. The indicating devices shall describe the purpose they serve. The printed designation on unit or building information display system indicators shall be legible. The mechanism shall be so arranged that once operated, the indicating device must be reset manually. All conditions indicated shall remain displayed until manually cleared at the Fire Command Station. Fire Command Stations shall provide alarm information in a direct manner; no references to numeric codes shall be permitted. Where a CRT display is provided, a specially marked control shall be provided that will enable the system operator to determine the alarm source and other related pertinent information.

(b) A unit information display system shall be so designed that the operation of any station in the unit causes a visible and audible signal.

(c) Trouble displays shall be so arranged that the indicating device will reset automatically when the cause of trouble has been removed. The trouble information display system shall be so designed that it will indicate visible and audible trouble signals in the event of trouble occurring on any circuit monitored. The trouble information display system shall be actuated by the operation of supervisory devices.

(d) A silencing switch shall be provided for trouble signals, but shall not affect subsequent trouble signals.

(e) Information display systems shall be so designed that vibration from without or that caused by a trouble signal within will not operate the indicating devices.

(f) All remote information display systems shall be installed in a separate steel cabinet painted red, provided with approval lock and key. Information display system cabinets shall be marked in white letters at least one inch high with the words "FIRE ALARM INFORMATION DISPLAY SYSTEM, ZONE ——" or "FIRE ALARM TROUBLE INFORMATION DISPLAY SYSTEM", whichever the case may be.

(g) Information display systems located in the lobby of a building whether an integral part of the fire command station or wall mounted shall have the legend "FIRE" in red letters three inches high together with an audible signal in addition to the lamp, target drop, cathode ray tube, light emitting diode, nixie, etc. and a separate or distinctive trouble signal shall sound. The audible signal accompanying an alarm shall be automatically silenced when the fire command station is operated by the fire safety director or his delegated substitute. Remote information display systems shall operate in the same manner.

(h) The display shall provide a minimum of four simultaneous alarm indicators with an overflow indication for additional alarms. Provisions shall be made to distinguish alarm conditions from non-alarm conditions. The display shall be updated as new information becomes available. If the same condition exists for more than one point on a floor or for more than one floor in a building, such as a fire gong actuation or public address, a separate output entry shall be displayed for each point or floor.

(i) Display format.—Each output entry shall include self-identifying mnemonic codes for the type of signal, building or area designation, floor or stair number and point location, and time of day. Systems utilizing gravity drops or lamps as point identification, may provide a hard copy print out.

(j) Maintainability.—

(1) Manual display of all points of annunciation for test purposes shall be provided.

(2) Capability shall be provided for interrogating any station or sensing element for test purposes, either at the remote device or by interrogation from the fire command station. Intervals of testing shall be as approved.

(3) Equipment designed shall be modular so that all repairs may be performed on-site by substitution of duplicate components by authorized personnel.

(4) One each of these parts that are of a modular nature shall be included as spares at the fire command station.

9. LICENSED CONTRACTORS.—Only a person holding a license or a special license in accordance with the provisions of the New York city electrical code, shall install, alter, or repair electrical wiring or apparatus for fire alarm systems in any building.

10. USED OR REBUILT APPARATUS.—Used apparatus shall not be re-used for any interior fire alarm system until the same has been reconditioned in the shop of any approved manufacturer of interior fire alarm apparatus. Approval shall be obtained from the commissioner prior to installation. The use of reconditioned apparatus whose manufacturer has discontinued manufacturing equipment is prohibited.

11. STANDPIPE FIRELINE TELEPHONE AND SIGNAL SYSTEM.—Where the standpipe telephone and signal system is arranged to be used as a modified Class E fire alarm signal system as provided in the building code, retractable telephone handsets shall be provided in pump rooms. The telephone in pump rooms shall be equipped with a loudspeaking receiver so that a voice can be distinctly heard at least 15 feet from the receiver.

12. LOCKED DOOR FAIL SAFE SYSTEMS.—

(a) Stairway reentry doors that locked from the stairway side as permitted in section 27-371 of the administrative code shall be provided with an electrical fail safe strike release mechanism that will permit the door to be opened without a key when any automatic fire-detecting device operates, elevator "Fireman Service" operates or power failure shall occur. In addition, provisions shall be made to permit these doors to be opened from the command station or mechanical control center. This system shall be manually reset.

(b) Wiring for these systems shall comply with rule 6 (a), (b), (c) and (d) of this reference standard and be electrically supervised for open and shorted or grounded circuits.

(c) Transformers for release mechanisms shall be rated for the proper use load, identified and located in proximity of the power supply for other fire alarm systems.

(d) The release mechanisms shall be operated from a separate control relay having the capability of indicating trouble on a separate trouble signal and at the information display system on the command console and at the mechanical control center. The mechanism shall also indicate a "failed" and "open" status on the command console and at the mechanical center.

(e) Where a fail-safe reentry door has been converted to conform to the requirements of this code by means of an electric strike release, provision shall be made to insure that the door will remain "Latched" even if "Unlocked".

13. RADIO SYSTEM.—A radio or radio/wire system shall comply with the following requirements:

(a) The emergency notification portion of the system equipment shall be capable of the following:

(1) Have the capability of individual, group or entire building notification of an alarm tone and voice intelligibility.

(2) Receivers and wire extension speakers shall be permanently mounted to a wall or pillar.

(3) There shall be automatic switch over to emergency battery power supply.

(b) Two way communication shall be accomplished by fixed transmitters and receivers.

(c) Equipment shall be Federal Communications Commission (FCC) approved, FM type, solid state, above 150.8 MHz. Selective signaling shall be accomplished by a minimum of 2 tone code operation.

(d) The antenna shall be designed and installed for use at the fire command station transmitter and be capable of transmitting to all fixed stations.

(e) The fire command station unit shall have the capability of locking out all other remote control points.

14. SPRINKLER WATERFLOW ALARMS.—A sprinkler waterflow alarm may be arranged to be used as part of a modified Class E fire alarm signal system provided: the alarm signal system shall be an approved electrically supervised closed circuit information display system capable of indicating the floor where the sprinkler was activated.

15. Elevator Communication.—Elevator intercommunication shall be acceptable for communications with the Fire Command Station if there is a means of communication proximate to the Fire Command Station.