NYC Administrative Code Title 27, Chapter 1 Building Code, part 10 of 17

§ 27-972 to SECTION 6 – TEST METHOD FOR DETERMINING DEFLECTION: 71 sections.

§ 27-972. Systems required for specific occupancies

Open this section

(a) In any type of one-story building where a fire alarm system is required and where the floor area is not more than twenty-five hundred square feet, an uncoded closed circuit fire alarm system may be used.

(b) Private and public schools. Master coded systems shall be used in all schools, except that schools having more than fifteen hundred students shall have an individually coded system.

(c) Single and multi-tenant factory buildings.

(1) In factory buildings, an individually coded closed circuit fire alarm system shall be installed except as hereinafter provided. An uncoded circuit fire alarm system may be used in buildings not exceeding two stories in height, having not more than twenty-five hundred square feet in area in any one story, and having not more than one hundred persons in a single factory nor more than fifty persons in a multiple tenant factory above the first or ground floor.

(2) Special fire alarm signal systems may be designed for use in buildings subject to the approval of the commissioner.

(d) A common coded closed circuit system may be used in a motion picture studio, and in addition, an approved rate-of-rise or other approved thermostatic fire alarm system, with direct connections to a central office of an approved operating fire alarm company or the fire alarm telegraph central station, shall be provided for protecting the open studio door. Also there shall be one or more manual fire alarm boxes, which shall be located so as to be readily accessible from the open studio door.

(e) Hospitals, asylums, and nursing homes. Buildings classified in occupancy group H-2 shall meet the following requirements:

(1) An individually coded closed circuit fire alarm system shall be provided in accordance with subdivision (c) of section 27-971 except where the fire commissioner shall have approved an individually coded closed circuit presignal fire alarm system as described in subdivision (d) of section 27-971. All fire alarm systems shall be activated by sprinkler waterflow and by all other fire detection devices installed in the building.

(2) Alarm systems shall be installed in zones of a maximum size of twenty thousand square feet.

(3) Manual fire alarm sending stations shall be at staff locations only.

(4) Where two or more buildings are served by one fire brigade, a combination unit or zone and a general alarm coded closed circuit fire alarm system shall be provided and an approved indicating annunciator installed in each building. Upon initiation of a station signal, general alarm signaling devices shall sound in engine rooms and subgrade areas of each building, and unit or zoned alarm signaling devices shall sound throughout all areas in only the building wherein the station signal was initiated. In the building where the station signal has been initiated, an approved annunciator shall indicate the station at which the signal is initiated.

(f) Buildings classified in occupancy group E, one hundred feet or more in height, and existing office buildings one hundred feet or more in height except as provided in subdivision (g) of this section shall be provided with a class E fire alarm signal system as follows:

(1) It shall be a special electrically supervised approved direct wire, radio or combination thereof fire alarm signal system consisting of an interior fire alarm and voice communicating system so arranged that the operation of any station will identify its location at the fire command station as required by section 27-975 of this article, at the mechanical control center and at the regularly assigned location of the fire safety director. This identification signal shall be accomplished by means of an information display system which shall be manually resettable from the fire command station only.

(2) The nomenclature used for the location identification system shall be subject to the approval of the fire commissioner.

(3) In addition to the visual devices required above, audible signal devices indicating operation of the fire alarm signal system shall be provided at the fire command station, mechanical control center and the regularly assigned location of the fire safety director. Provisions shall be made for silencing the audible signal and transferring this signal to lamp indication.

(4) Operation of a manual station shall automatically transmit a fire alarm signal to the fire department via a central office of an operating company franchised by the board of estimate, and cause the fire alarm signal system to sound continuously throughout the floor where activated and the floor above.

(5) The fire alarm signal may be sounded over loud speakers as provided in reference standard RS 17-3A so located that their operation will be heard clearly above any ambient noise, and shall be controlled from the fire command station in such a manner that the fire alarm signal can be sounded on the individual floors or throughout the building.

(6) Provision shall be made whereby the fire command station may permit the floor station to make announcements over the loud speaker system.

(7) The loud speaker amplifier system shall be so designed and installed that approximately fifty (50) percent of the system shall remain operable for the transmission and audibility of signals and intelligibility of voice communication over the loud speaker system throughout the building, in the event the other fifty (50) percent become inoperable. The electrical supply for this fire alarm system, including the amplifiers, shall be in accordance with applicable laws, rules and regulations.

(8) An approved product of combustion ionization detecting device or a combination of an approved smoke detecting device and an approved fixed temperature thermostatic device shall be installed at each elevator landing. The device shall be located in the ceiling immediately above a call button. The activation of this device shall have the same effect as specified in subparagraphs a through e of paragraph nine of this subdivision and in addition cause the overriding of the programming for car stops of all automatic elevators serving the floor where activated and bring them non-stop to the floor levels designated by section 210.13C of reference standard RS 18-1.

(9) In buildings which are provided with air-conditioning and/or mechanical ventilation systems that serve more than the floor on which the equipment is located, the activation of any of the detectors installed in such air-conditioning and/or mechanical ventilation systems in accordance with the provisions of RS 13-1 of the reference standards shall:

a. cause the fire alarm signal system to sound continuously throughout the floor where activated and the floor above.

b. cause a fire alarm signal to be transmitted to the fire department via a central station of a franchised operating company.

c. cause the fire alarm signal system to sound at the fire command station required by section 27-975 of this article and to sound an alarm in the mechanical control center and at the regularly assigned location of the fire safety director, and to operate an information display system as provided in paragraph one of this subdivision.

d. stop the air supply into and the air return from the floor where activated by actuation of approved remote control reversible fire shutters or by automatically shutting down the air supply fans and the air return fans of the floor where activated, notwithstanding the provisions of sections 1001 through 1005 of RS 13-1 of the reference standards relating to air supply and air return controls in case of fire.

e. cause the activation of the air exhaust fans and dampers in smoke shafts and/or the pressurizing fans in stair enclosures.

(10) A building equipped throughout with an automatic sprinkler system including a water flow alarm shall be exempt from the installation of any detectors pursuant to paragraph eight of this subdivision and section 1006 of reference standard RS 13-1 provided the activation of the sprinkler water flow alarm shall have the same effect as specified in subparagraphs a through e of paragraph nine of this subdivision and in addition cause the overriding of the programming for car stops of all automatic elevators serving the floor where activated and bring them non-stop to the floor levels designated by section 210.13C of reference standard RS 18-1.

(11) In existing office buildings one hundred feet or more in height where compliance would cause practical difficulty or undue hardship, the commissioner may waive or modify the requirements of paragraphs one through nine of this subdivision (f) and accept alternatives fulfilling the intent of these requirements.

(12) Existing office buildings one hundred feet or more in height shall comply with the requirements of this subdivision on or before September thirteenth, nineteen hundred eighty-one. Complete plans of the installation shall be filed with the commissioner on or before June thirteenth, nineteen hundred eighty. A permit shall be secured from the commissioner on or before September thirteenth, nineteen hundred eighty. Where compliance with the time requirements of this paragraph would cause undue hardship, the commissioner, with the approval of the fire commissioner, may extend the time for compliance, in accordance with rules and regulations to be promulgated. Before such application for a time extension shall be considered all required applications and plans must be filed and approved permits obtained and a good faith effort towards completion of the work shall have been made.

(g) Fire alarm or communication systems installed prior to December thirteenth, nineteen hundred eighty in existing office buildings, one hundred feet or more in height, may be incorporated or installed in a modified class E fire alarm signal system provided they comply with the following:

(1) It shall be a special electrically supervised approved direct wire, radio or combination thereof fire alarm signal system consisting of an interior fire alarm and voice communicating system so arranged that the operation of any station will identify its location at the fire command station as required by section 27-975 of this article, at the mechanical control center and at the regularly assigned location of the fire safety director. This identification signal shall be accomplished by means of an information display system which shall be manually resettable from the fire command station only.

(2) The nomenclature used for the location identification system shall be subject to the approval of the fire commissioner.

(3) In addition to the visual devices required above, audible signal devices indicating operation of the fire alarm signal system shall be provided in the fire command station, mechanical control center and the regularly assigned location of the fire safety director. Provisions shall be made for silencing the audible signal and transferring this signal to lamp indication.

(4) Operation of a manual station shall automatically transmit a fire alarm signal to the fire department via a central office of an operating company franchised by the board of estimate, and cause the fire alarm signal system to sound continuously throughout the floor where activated and the floor above.

(5) The fire alarm signal may be sounded over loud speakers as provided in reference standard RS 17-3B so located that their operation will be heard clearly above any ambient noise, and shall be controlled from the fire command station in such a manner that the fire alarm signal can be sounded on the individual floors or throughout the building.

(6) The electrical supply for this modified fire alarm system, including the amplifiers, shall be in accordance with applicable laws, rules and regulations.

(7) An approved product of combustion ionization detecting device or a combination of an approved smoke detecting device and an approved fixed temperature thermostatic device shall be installed at each elevator landing. The device shall be located in the ceiling immediately above a call button. The activation of this device shall have the same effect as specified in subparagraphs a through e of paragraph eight of this subdivision and in addition cause the overriding of the programming for car stops of all automatic elevators serving the floor where activated and bring them non-stop to the floor levels designated by section 210.13C of reference standard RS 18-1.

(8) In buildings which are provided with air-conditioning and/or mechanical ventilation systems that serve more than the floor on which the equipment is located, the activation of any of the detectors installed in such air-conditioning and/or mechanical ventilation systems in accordance with the provisions of RS 13-1 of the reference standards shall:

a. cause the fire alarm signal system to sound continuously throughout the floor where activated and the floor above.

b. cause a fire alarm signal to be transmitted to the fire department via a central station of a franchised operating company.

c. cause the fire alarm signal system to sound at the fire command station required by section 27-975 of this article and to sound an alarm in the mechanical control center and at the regularly assigned location of the fire safety director, and to operate an information display system as provided in paragraph one of this subdivision.

d. stop the air supply into and the air return from the floor where activated by actuation of approved remote control reversible fire shutters or by automatically shutting down the air supply fans and the air return fans of the floor where activated, notwithstanding the provisions of sections 1001 through 1005 of RS 13-1 of the reference standards relating to air supply and air return controls in case of fire.

e. cause the activation of the air exhaust fans and dampers in smoke shafts and/or the pressurizing fans in stair enclosures.

(9) A building equipped throughout with an automatic sprinkler system including a water flow alarm shall be exempt from the installation of any detectors pursuant to paragraph seven of this subdivision and section 1006 of reference standard RS 13-1 provided the activation of the sprinkler water flow alarm shall have the same effect as specified in subparagraphs a through e of paragraph eight of this subdivision and in addition cause the overriding of the programming for car stops of all automatic elevators serving the floor where activated and bring them non-stop to the floor levels designated by section 210.13C of reference standard RS 18-1.

(10) Existing office buildings one hundred feet or more in height shall comply with the requirements of this subdivision on or before September thirteenth, nineteen hundred eighty-one. Complete plans of the installation shall be filed with the commissioner on or before June thirteenth, nineteen hundred eighty. A permit shall be secured from the commissioner on or before September thirteenth, nineteen hundred eighty. Where compliance with the time requirements of this paragraph would cause undue hardship, the commissioner, with the approval of the fire commissioner, may extend the time for compliance, in accordance with rules and regulations to be promulgated. Before such application for a time extension shall be considered all required applications and plans must be filed and approved, permits obtained and a good faith effort towards completion of the work shall have been made.

(11) In existing office buildings one hundred feet or more in height where compliance would cause practical difficulty or undue hardship, the commissioner may waive or modify the requirements of paragraphs one through nine of this subdivision (g) and accept alternatives fulfilling the intent of these requirements.

(h) Buildings classified in occupancy group E, less than one hundred feet in height occupied or arranged to be occupied for an occupant load of more than one hundred persons above or below the street level or more than a total of five hundred persons in the entire building, and on or before January eighteenth, nineteen hundred seventy-five, existing office buildings less than one hundred feet in height, occupied or arranged to be occupied, as hereinabove specified, shall be provided with a system acceptable to the commissioner, which shall:

(1) consist of equipment which shall have the capability of two-way voice communication from a fire command station to the warden on each floor of the building and the mechanical control center, to be used for fire emergencies and fire drills.

(2) have the capability of transmitting a fire alarm signal from the fire command station to the fire department via a central station of a franchised operating company.

(i) (1) High-rise buildings classified in occupancy group C shall be provided with a fire alarm and communication system meeting the requirements of subdivision (k) of this section and reference standard RS 17-3A.

(2) Buildings classified in occupancy group J-1, either seventy-five feet or more in height or containing thirty or more sleeping rooms (except "residential hotels" as such term is defined by the commissioner pursuant to rules and regulations) shall be provided with a fire alarm and communication system meeting the requirements of subdivision (l) of this section and reference standard RS 17-3A. In lieu of fire warden stations, either of the following are acceptable as a two-way voice communications system:

1. A closed circuit supervised fire department telephone system meeting the following conditions in complying with requirements of RS 17-3 as applicable to standpipe fireline telephone and signaling system:

a. Means on every floor to communicate by telephone with the fire command station. A permanent telephone shall be located at the fire command station. All other floors near the main riser shall be provided with telephones or telephone jacks. Telephones or jacks shall be installed in locked cabinets capable of being opened with a fire department standard key.

b. At least six portable telephones with jack connections shall be provided unless permanent telephones are installed at every required location. The portable telephones shall be kept in a cabinet located near the fire command station and shall be provided with a lock capable of being opened with a fire department standard key. Such cabinet shall be locked at all times and marked portable telephones for fire department use.

c. A pilot light shall be provided at the fire command station to indicate that the telephone is in use or that its receiver is off the hook; or

2. A fire communication slotted coaxial cable radio system installed to provide adequate communication capability throughout the building. Adequate communication is defined as the capability for clear two-way communication between a fire department portable radio at the lobby command post and another fire department portable radio at any other point in the building. Such system shall be acceptable to the fire department.

(j) (1) Existing buildings seventy-five feet or more in height, classified in occupancy group J-1 (except "residential hotels" as such term is defined by the commissioner pursuant to rules and regulations) shall be provided with a fire alarm and communication system meeting all the applicable requirements of subdivision (m) of this section and reference standard RS 17-3B. In lieu of fire warden stations, either of the following is acceptable as a two-way voice communication system:

1. A closed circuit supervised fire department telephone system meeting the following conditions in complying with requirements of RS 17-3 as applicable to standpipe fireline telephone and signaling system:

a. Means on every floor to communicate by telephone with the fire command station. A permanent telephone shall be located at the fire command station. All other floors near the main riser shall be provided with telephones or telephone jacks. Telephones or jacks shall be installed in locked cabinets capable of being opened with a fire department standard key.

b. At least six portable telephones with jack connections shall be provided unless permanent telephones are installed at every required location. The portable telephones shall be kept in a cabinet located near the fire command station and shall be provided with a lock capable of being opened with a fire department standard key. Such cabinet shall be locked at all times and marked portable telephones for fire department use.

c. A pilot light shall be provided at the fire command station to indicate that the telephone is in use or that its receiver is off the hook; or

2. A fire communication slotted coaxial cable radio system installed to provide adequate communication capability throughout the building. Adequate communication is defined as the capability for clear two-way communication between a fire department portable radio at the lobby command post and another fire department portable radio at any other point in the building. Such system shall be acceptable to the fire department.

(2) Existing buildings less than seventy-five feet in height and containing thirty or more sleeping rooms, classified in occupancy group J-1, shall be provided with a modified Class J-1 fire alarm and communications system as follows:

(a) A fire command station shall be provided at the entry floor level in accordance with the requirements of the fire commissioner.

(b) A public address system shall be provided acceptable to the fire commissioner capable of being easily heard (80 dbs at sixty feet) in all existing corridors, hallways, passageways and stairs.

(c) The approved existing interior fire alarm system shall be acceptable provided that it shall automatically transmit a fire alarm signal (when activated) to the fire department via a central station connection of an operating company which is franchised where applicable and which is acceptable to the fire department.

(k) Buildings classified in occupancy group C, seventy-five feet or more in height, shall be provided with a class C fire alarm and communications system which shall meet the criteria contained in paragraphs one through ten of subdivision (f) of this section and the criteria contained in subdivisions (a) and (b) of section 27-975 of this article.

(l) Buildings classified in occupancy group J-1, seventy-five feet or more in height or containing thirty or more sleeping rooms, shall be provided with a class J fire alarm and communication system which shall meet the criteria contained in paragraphs one through ten of subdivision (f) of this section and the criteria contained in subdivisions (a) and (b) of section 27-975 of this article.

(m) Existing buildings classified in occupancy group J-1, seventy-five feet or more in height, shall be provided with a modified class J fire alarm and communication system which shall meet the criteria contained in paragraphs one through nine of subdivision (g) of this section and the criteria contained in subdivisions (a) and (b) of section 27-975 of this article.

(n) All other occupancies shall be provided with an individually coded closed circuit general fire alarm system when a fire alarm system is required.

§ 27-973. Location and identification of sending stations and sounding devices

Open this section

(a) Location of sending stations.

(1) There shall be at least one fire alarm sending station in each story of any building at all natural paths of egress to the street. The station shall be installed at a readily accessible location meeting the approval of the fire commissioner. The sending station shall be kept unobstructed at all times. Additional sending stations shall be installed so that no point on any floor is more than one hundred fifty feet from the nearest sending station in buildings of Group I construction and one hundred feet in buildings of Group II construction.

(2) All fire alarm stations installed or relocated after April first, nineteen hundred eighty-four shall be installed so that the handle is approximately four feet from the floor.

(b) Location of sounding devices.

(1) Sounding devices shall be of sufficient number so that the alarm shall be clearly audible to all the occupants of the building.

(2) The centerline of all gongs and signaling devices shall be located at least eight feet above the floor except that in locations where ceilings prevent the installation at this height, the centerline of the device shall be located six inches below the ceiling.

(3) Approved gongs shall be provided as the sounding devices. Where gongs are not audible, approved horns, chimes, or whistles may be installed subject to the approval of the fire commissioner.

(c) Location of instructions. An approved instruction card, properly marked and framed under glass, shall be installed at each fire alarm station. Instruction cards for individually coded systems shall indicate the code designation and location of each sending station in the building.

(d) Fastening for devices. All materials and devices used in fire alarm signal systems shall be securely fastened in position. The locations shall be selected by an architect or engineer, subject to the approval of the commissioner.

(e) Identification of equipment. Fire alarm sending stations for all systems shall be painted red. A diagonal white stripe one inch wide from upper left hand corner to lower right hand corner shall be painted or applied to sending stations which transmit a fire alarm signal to the fire department via a central station of a franchised operating company. The stripe shall not render any lettering illegible or obliterate the station number.

(f) Mixed occupancy buildings. Where a building is subdivided by fire divisions, each building section may be treated as a separate building for the purpose of fire alarm signal system installations. One control board may be used, if so arranged as to operate the signaling devices in each building section independently.

(g) Subdivided occupancy. In buildings requiring fire alarm signal systems, and in which parts are occupied by other than factory tenants and in which the fire department has approved the use of a local fire brigade, the commissioner may accept dual operation systems.

§ 27-974. Standpipe fireline telephone and signaling systems

Open this section

(a) In every building more than three hundred feet high, a telephone and signaling system shall be provided for fire department use in operating the standpipe system.

(b) Such system shall permit communication by permanent telephones in the pump rooms, on the entrance floor, and in gravity tank rooms communicating with floors, and by means of permanent or portable telephones on each floor near the main standpipe riser. The system shall be a selective ringing, common talking system supplied by a twenty-four volt direct current power source.

(c) Permanent wall telephones shall be provided with six inch gongs at each instrument. The telephones in the pump room shall be equipped with a loudspeaking receiver so that a voice can be distinctly heard at a distance of at least fifteen feet from the receiver. All other floors shall be provided with jacks, protected by break-glass boxes, or with permanent telephones.

(d) At least three portable telephones with jack connections shall be provided for each standpipe installation, unless permanent telephones are installed at every required location. The portable telephones shall be kept in a cabinet located in the main hall of the entrance floor and shall be provided with a lock capable of being opened with a fire department standard key. Such cabinet shall be locked at all times. The panel of the cabinet door shall be conspicuously marked "portable telephone for fire department use".

(e) A pilot light shall be provided over the standpipe telephone cabinet in the entrance floor to indicate if the telephone is in use or a receiver is off the hook.

(f) Standpipe signaling devices.

(1) Manual type individually coded sending stations shall be located in the main corridor of the building or other location meeting the approval of the commissioner. This system shall be so arranged that a coded signal will be transmitted to the alarm sounding devices. An eight inch gong shall be provided in the pump rooms, in elevator shafts at intervals not exceeding ten floors, and at such other locations selected by the architect or engineer, subject to the approval of the commissioner. All apparatus used in connection with the signaling system shall be of an approved type and installed as required by the provisions of reference standard RS 17-3 governing the installation of interior fire alarm systems.

(2) Adjacent to each telephone station and near the main standpipe riser, there shall be provided an approved closed circuit strap key enclosed in a sheet metal box equipped with a paracentric fire department lock and approved hinges. The strap key shall be connected in series with the box circuit of the signal sending station.

(3) A card of instructions shall be placed in the pump room giving code numbers of signaling stations, the pressure obtainable at various speeds of the fire pump motor, and such other information as the commissioner may direct.

(g) Where the building is subject to the provisions of subdivision (f) or (g) of section 27-972 of this article with respect to the requirement for a modified class E fire alarm signal system, the standpipe fireline telephone and signaling system may be combined with such fire alarm system provided:

(1) the alarms and two-way voice communication with the fire command station include the pump room and gravity tank or pressure tank room, and

(2) a designated floor station of the modified class E fire alarm signal system is located at or near the main standpipe riser on every floor.

§ 27-975. Communication system and fire command station

Open this section

Buildings classified in occupancy group E seventy-five feet or more in height, or, if less than seventy-five feet in height, with a total gross area of two hundred thousand square feet or more and existing office buildings one hundred feet or more in height, shall be provided with the following:

(a) a communication system acceptable to the commissioner consisting of:

(1) loud speakers on each floor of the building, in each elevator and each stair enclosure, which shall be capable of being operated from the fire command station.

(2) a two-way voice communication capability between the fire command station and the following locations:

a. a designated floor warden station on each floor

b. mechanical control center

c. elevators

d. air-handling control rooms

e. elevator machine rooms

(b) The fire command station shall be located in the lobby of the building on the entrance floor as part of the elevator control panel or immediately adjacent thereto. Such command station shall be adequately illuminated and shall contain the following:

(1) the loud speaker and communication capability described in subdivision (a) of this section.

(2) the audible alarm signal required in subdivision (f) and (g) of section 27-972 of this article.

(3) manually reset information display system to indicate the floor where the alarm was activated.

(4) means to control the sounding devices on any floor or throughout the building.

(5) means to manually transmit a fire alarm signal to the fire department via a central station of a franchised operating company.

(6) means for silencing the audible alarm signals when the loud speakers are in use and for activating the audible alarm systems automatically when use of the loud speakers is terminated. Switches used for this purpose shall be of the self-restoring type.

(7) display lamps to include on/off condition of air-handling systems unless such lamps are provided in the mechanical control center.

(8) means for testing the display lamps, local alarms and the connection to the central station of a franchised operating company.

(c) Existing office buildings one hundred feet or more in height shall comply with the requirements of this section on or before September thirteenth, nineteen hundred eighty-one. Complete plans of the installation shall be filed with the commissioner on or before June thirteenth, nineteen hundred eighty. A permit shall be secured from the commissioner on or before September thirteenth, nineteen hundred eighty. Where compliance with the time requirements of this subdivision would cause undue hardship, the commissioner, with the approval of the fire commissioner, may extend the time for compliance, in accordance with rules and regulations to be promulgated. Before such application for a time extension shall be considered all required applications and plans must be filed and approved, permits obtained and a good faith effort towards completion of the work shall have been made.

§ 27-976. Installation

Open this section

Installation, source of energy, wiring, and other requirements shall comply with reference standard RS17-3, RS17-3A or RS17-3B as applicable.

§ 27-977. Fire systems electrical tests

Open this section

Upon completion of a fire alarm system, and other electrical systems, the installation shall be subjected to a test to demonstrate the efficiency of operation of all the components in the system and to an acceptance test by the fire department.

§ 27-978. Definitions

Open this section

For the purposes of this article:

a. an existing building is one which is within occupancy group J-1, occupancy group J-2 or occupancy group J-3 and for which plans have been approved by the department on or prior to December thirty-first, nineteen hundred eighty-one.

b. an improvement or alteration is a physical change in an existing structure other than painting, repairs and normal replacement of maintenance items.

c. a building shall be deemed to have been substantially improved or altered if:

1. the cost of improvement or alteration exceeds the sum of one hundred fifty thousand dollars, or

2. in either occupancy group J-1 or occupancy group J-2, fifty percent or more of the dwelling units or square feet of the structure are improved or altered and the cost of such improvement or alteration exceeds the sum of fifteen thousand dollars per dwelling unit, or

3. there has been a change in the occupancy or use of the structure.

§ 27-979. Smoke detecting devices; where required

Open this section

(a) On and after January first, nineteen hundred eighty-two, all dwelling units within occupancy group J-1 and occupancy group J-2, except such units which contain operational automatic wet sprinkler systems pursuant to article four of this subchapter, and dwelling units in buildings within occupancy group J-3 shall be equipped with approved and operational smoke detecting devices as hereinafter provided. Buildings within occupancy group J-1 may, in the alternative, be equipped with a line-operated zoned smoke detecting system with central annunciation and central office tie-in for all public corridors and public spaces, pursuant to rules and regulations promulgated by the commissioner. The commissioner may, upon good cause shown, extend the period of compliance for occupancy groups J-1 and J-2 to June thirtieth, nineteen hundred eighty-two.

(b) Approved and operational smoke detecting devices shall be installed in mechanical rooms, electrical switch gear rooms and electric and telephone closets over seventy-five square feet in gross floor area in all buildings in all occupancy groups.

§ 27-980. Power sources of smoke detecting devices

Open this section

Dwelling units shall be equipped with smoke detecting devices receiving their primary power from the building wiring and there shall be no switches in the circuit other than the over-current device protecting the branch circuit; provided, however, that dwelling units in existing buildings may, in the alternative, be equipped with battery-operated smoke detecting devices except where such buildings are substantially improved or altered on or after January first, nineteen hundred eighty-two.

§ 27-981. General requirements for smoke detecting devices

Open this section

a. All smoke detecting devices required to be provided and installed pursuant to this article shall either be accepted pursuant to rules and regulations promulgated by the commissioner or be listed by a nationally recognized independent laboratory that maintains periodic inspections of production of listed equipment and whose listing states that the equipment meets nationally recognized standards. To meet the requirements of this article, such laboratory shall be one which maintains a periodic follow-up service of the devices to ensure compliance with the original listing.

b. No device shall be deemed to be in compliance with the provisions of this article unless it is of either the ionization chamber or photoelectric type. Such devices shall be in compliance with the requirements of reference standard RS 17-11 and shall be installed in a manner consistent with the requirements of reference standard RS 17-12 except that devices within occupancy group J-1 shall be installed pursuant to rules and regulations promulgated by the commissioner.

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1991/049.

§ 27-981.1. Definitions

Open this section

For the purpose of this article:

a. "Fossil fuel" shall mean coal, kerosene, oil, wood, fuel gases and other petroleum products.

b. "Fuel gases" shall include, but not be limited to, methane, natural gas, liquefied natural gas and manufactured fuel gases.

§ 27-981.2. Carbon monoxide detecting devices; where required

Open this section

a. Every dwelling unit in a building within occupancy groups J-1, J-2 or J-3 where a fossil fuel-burning furnace or boiler is located, and every dwelling unit in a building that is in close proximity to a source of carbon monoxide, as such proximity is established by the rules promulgated by the commissioner in consultation with the fire department and the department of health and mental hygiene, shall be equipped with an operational carbon monoxide detecting device approved in accordance with the rules promulgated by the commissioner in consultation with the fire department and the department of health and mental hygiene, provided that there shall be installed at least one approved and operational carbon monoxide detecting device within fifteen feet of each room lawfully used for sleeping purposes. Such carbon monoxide detecting device may be combined with a smoke detecting device that complies with the provisions of this title and any applicable rules promulgated thereunder.

b. In every building classified in occupancy group G or occupancy group H-2, at least one approved and operational carbon monoxide detecting device shall be installed in accordance with rules promulgated by the commissioner in consultation with the fire department and the department of health and mental hygiene.

c. In every building classified in occupancy groups F-1, F-3 and F-4, at least one approved and operational carbon monoxide detecting device shall be installed and maintained in accordance with rules promulgated by the commissioner in consultation with the fire department and the department of health and mental hygiene.

d. The provisions of this article shall apply retroactively to every building, in accordance with the provisions of subdivision a or subdivision b of this section, irrespective of when such building was constructed or a certificate of occupancy for such building was issued.

e. The provisions of this article may be enforced by the department, the fire department, the department of health and mental hygiene and the department of housing preservation and development.

§ 27-981.3. General requirements for carbon monoxide detecting devices

Open this section

All carbon monoxide detecting devices required to be provided and installed pursuant to this article shall be of a type authorized by rules promulgated by the commissioner.

§ 27-982. Scope

Open this section

This subchapter shall establish the minimum safety requirements for, and control the design, construction, installation, alteration, maintenance, inspection, test and operation of, all elevators, dumbwaiters, escalators, moving walks, industrial lifts and loading ramps, automotive lifts, mechanical parking garage equipment, console or stage lifts, power operated scaffolds, amusement devices, and special hoisting and conveying equipment.

§ 27-983. Standards

Open this section

The provisions of reference standard RS-18 shall be a part of this subchapter.

§ 27-984. Definitions

Open this section

For definitions to be used in the interpretation of this subchapter, see subchapter two of this chapter.

§ 27-985. Plans

Open this section

For the requirements governing the filing of plans and the work to be shown on plans, see subchapter one of this chapter.

§ 27-986. Permits

Open this section

For the requirements governing equipment work permits and equipment use permits, see subchapter one of this chapter.

§ 27-987. General requirements

Open this section

All of the equipment listed in section 27-982 of this article shall be designed, constructed, altered and maintained as required by the provisions of this subchapter and reference standard RS-18. No piping or ductwork of any kind shall be permitted within hoistway or elevator enclosures except (i) as may be required for the elevator installation and (ii) low voltage wiring required or permitted by subchapter seventeen of this chapter provided that such wiring shall be protected within the hoistway or elevator enclosures in accordance therewith.

(a) Construction equipment. Except for workers' hoists the provisions of this subchapter shall not apply to materials hoisting equipment for temporary construction use. For such equipment, the requirements of subchapter nineteen of this chapter shall apply.

(b) Portable equipment. The provisions of this subchapter shall not apply to portable elevating devices used to handle materials only except as specifically provided in reference standard RS 18-5.

(c) Fire protection and impact resistance.

(1) Fire protection. The fire resistance rating of hoistway enclosures shall be two hours and for hoistway doors and door assemblies the fire protection shall be one and one-half hours subject to the test procedures of subchapter five of this chapter.

a. vertical conveyors passing through floors shall be fire protected as required for shafts in subchapter five of this chapter.

b. inclined conveyors passing through floors shall be fire protected as required in reference standard 18-1 for escalators which are not a required means of egress.

c. horizontal conveyors passing through vertical fire divisions shall be fire protected as required in subchapter five of this chapter.

(2) Impact resistance. Elevator enclosures serving occupancy group E spaces (office spaces) in high rise buildings constructed pursuant to applications filed on or after July 1, 2006, shall comply with rules to be promulgated by the commissioner establishing minimum impact resistance standards. Such rules shall permit compliance with assemblies comprising approved reinforced construction boards affixed onto stud framing. The commissioner shall promulgate such rules on or before January 1, 2006.

(d) Elevators required. For provisions designating buildings in which elevators are required, see subdivision (c) of section 27-372 of article five of subchapter six of this chapter.

(e) Elevator mirrors. In all multiple dwellings in which there are one or more self-service passenger elevators, there shall, pursuant to such regulations as the commissioner shall prescribe, be affixed and maintained in each such elevator a mirror which will enable persons prior to entering into such elevator to view the inside thereof to determine whether any person is in such elevator.

(f) Emergency signal equipment. Elevators, other than private residence elevators, that are operated at any time without a designated operator in the car, shall be provided with emergency signal equipment in accordance with the requirements of reference standard RS 18-1.

(g) Elevators and escalators as exits. Elevators shall not be accepted as a required means of egress. Elevators shall not be installed in a common enclosure with a stairway. Escalators shall be accepted as equivalent to stairs when they comply with the requirements of section 27-378 of article five of subchapter six of this chapter.

(h) Car switch operation. Elevators with car switch operation shall be provided with a signal system by means of which signals can be given from any landing whenever the elevator is desired at that landing.

(i) Electrical requirements. All electric work shall conform to the electrical code of the city of New York.

§ 27-988. Manlifts

Open this section

The installation of manlifts is governed by the requirements of reference standard RS 18-9, and such additional safety regulations as may be promulgated by the commissioner.

§ 27-989. Elevator in readiness

Open this section

(a) Except as provided in subdivision (b) of this section, in every building seventy-five feet or more in height, all floors shall be served by at least one elevator which shall be kept available for immediate use by the fire department during all hours of the night and day, including holidays, Saturdays and Sundays. There shall be available at all times a person competent to operate the elevator, except that no attendant shall be required for buildings between seventy-five feet and one hundred fifty feet in height having elevators with automatic or continuous pressure operation with keyed switches meeting the requirements of reference standard RS 18-1 so as to permit sole use of the elevators by the fire department.

(b) In high rise buildings classified in occupancy group A, B, C, D, E, F, G or H, in buildings classified in occupancy group E with a gross area of two hundred thousand square feet or more, in buildings classified in occupancy group J-1 or J-2, in existing high rise buildings classified in occupancy groups C, F, G and H, in existing buildings classified in occupancy group J-1 (except "residential hotels," as such term is defined by the commissioner pursuant to rules and regulations) and in existing office buildings one hundred feet or more in height the number of elevators that shall be kept available for immediate use by the fire department as provided for in subdivision (a) of this section, shall be as follows:

(1) Where a floor is serviced by three or less elevator cars, every car shall be kept available.

(2) Where a floor is serviced by more than three elevator cars, at least three elevator cars with a total rated load capacity of not less than six thousand pounds shall be kept available for every floor. Such cars shall include not more than two cars which service all floors and at least one other car in another bank servicing that floor. If the total load capacity of all cars servicing the floor is less than six thousand pounds, all such cars shall be kept available.

(3) Such elevators which have automatic or continuous pressure operation shall be controlled by keyed switches meeting the requirements of reference standard RS 18-1.

(4) In high rise buildings classified in occupancy group A, B, C, D, E, F, G or H, in low rise buildings classified in occupancy group E with a gross area of two hundred thousand square feet or more and in buildings classified in occupancy group J-1 or J-2, all other automatically operated cars shall have manual operation capability.

(c) Notwithstanding the retroactive provisions of section 27-994 of article two of this subchapter:

(1) Existing office buildings one hundred feet or more in height shall comply with the requirements of this section by September thirteenth, nineteen hundred eighty-one. Complete plans of the installation shall be filed with the commissioner by June thirteenth, nineteen hundred eighty. A permit shall be secured from the commissioner by September thirteenth, nineteen hundred eighty.

(2) Existing high-rise buildings classified in occupancy group C, F, G or H and existing buildings classified in occupancy group J-1 subject to the requirements of this section shall comply with the requirements of this section on or before April first, nineteen hundred eighty-seven.

§ 27-990. Acceptance of equipment

Open this section

All equipment and devices regulated by the provisions of this subchapter shall be accepted or approved for use in accordance with the requirements of article eight of subchapter one of this chapter.

§ 27-991. Construction

Open this section

The construction, installation and alteration of all elevator and conveyor equipment and devices, shall be subject to the provisions of this subchapter and applicable reference standards as follows:

(a) Elevators, dumbwaiters, escalators and moving walks – reference standard RS 18-1.

(b) Mechanized parking garage equipment – reference standard RS 18-2.

(c) Automotive lifts – reference standard RS 18-3.

(d) Industrial lifts and hinged loading ramps – reference standard RS 18-4.

(e) Conveyors – reference standard RS 18-5.

(f) Console or stage lifts – reference standard RS 18-6.

(g) Workers' hoists – reference standard RS 18-7.

(h) Power operated scaffolds – reference standard RS 18-8.

§ 27-992. Alterations

Open this section

Alterations to elevators, escalators, dumbwaiters and other equipment provided for in this subchapter shall comply with the requirements of article four of subchapter one of this chapter. Minor alterations and ordinary repairs shall comply with the requirements of article five of subchapter one of this chapter except that elevator work shall not constitute a minor alteration or an ordinary repair when it is classified as alteration by the provisions of reference standard RS 18-1.

§ 27-993. Prohibited devices

Open this section

The installation of sidewalk elevators located outside the street line is prohibited.

§ 27-994. Retroactive provisions

Open this section

The provisions of this subchapter are not retroactive except that the provisions of this section are retroactive. Existing elevators moved to new hoistways shall conform with all the requirements for new installations. All alteration work on existing installations required by this section must be completed no later than December sixth, nineteen hundred seventy.

(a) Emergency interlock release switch. Emergency interlock release switches in elevator cars, where provided, shall be of the key-operated, continuous-pressure type and all other types now in use shall be removed or replaced with approved key-operated, continuous-pressure type switches.

(b) Machines – belt and chain-driven. Single-belted and chain-driven machines shall be permitted only on freight elevators and only when equipped with electrically released, spring applied brakes and with terminal stopping devices and electrical safety devices as required in reference standard RS 18-1.

(c) Machines – drum winding. Drum winding machines shall be equipped with electrical machine limits as set forth in reference standard RS 181.

(d) Car gate switches – additions, replacement, or relocation of. Car gate electric contacts where such devices are not provided or are found to be tied or blocked so as to render them inoperative shall be added, replaced or relocated as required by the commissioner. Installation or replacement of car gate electric contacts shall conform to the requirements of reference standard RS 18-1.

(e) Elevator hoistway-door interlocks. All existing elevators not presently equipped with hoistway doors having door interlocks shall be provided with hoistway landing doors equipped with approved type hoistway-door interlocks conforming to the requirements of reference standard RS 18-1. Approved-type interlock switches may be installed in connection with existing hoistway door closers, provided the combination door closers and interlocks conform to all the requirements for approved hoistway-door interlocks. The use of elevator parking devices and hoistway door unlocking devices for opening hoistway doors from the landing side shall conform to the requirements of reference standard RS 18-1. Exceptions: Interlocks or electric contacts shall not be used on hydraulic elevator landing doors or gates except where such elevators are provided with electric control and operating devices.

(f) Emergency signal or telephone. Automatic operation elevators or any elevator operated at any time without a designated operator shall be provided with an audible emergency signal, and except in buildings classified in occupancy groups J-1, and J-2, the cars shall be provided with a telephone, in accordance with the requirements of reference standard RS 18-1.

(1) Elevators with car switch operation shall be provided with a signal system by means of which signals can be given from any landing whenever the elevator is desired at the landing.

§ 27-995. Existing sidewalk elevators

Open this section

Existing sidewalk elevators shall not be subject to the provisions of this section.

§ 27-996. Existing hand powered freight elevators

Open this section

Existing hand powered freight elevators shall not be subject to the provisions of this article. However, adequate protection of landing openings shall be provided by hinged or sliding doors which shall remain locked at all times except when the freight elevator is in use. Auxiliary gates not less than thirty-six inches in height, substantially constructed and secured in place, of wood or metal, or equivalent metal chains shall be installed. Such gates or chains may be arranged to lift vertically, to slide horizontally, or to swing. No part of any gate or chain may project into the freight elevator shaft. Gates may be operated automatically or manually.

§ 27-996.1. Locks on elevators and elevator hoistway doors

Open this section

Notwithstanding the retroactive provisions of section 27-994 of this article, in high rise buildings and existing high rise buildings, no switch, lock or device of any kind shall be installed on any floor on or above the street floor on any elevator car or elevator hoistway door, except elevators used exclusively for freight, that shall prevent opening of such doors by anyone not having a key, unless fire department access to cars and hoistways is provided for by a city-wide standard key as described in reference standard RS 18-1. Existing high rise buildings shall comply with the requirements of this section on or before April first, nineteen hundred eighty-seven.

§ 27-996.2. Firemen service operation in existing elevators

Open this section

(a) Notwithstanding the retroactive provisions of section 27-994 of this article, where required by reference standard RS 18-1, firemen service operation shall be installed in all existing elevators serving any of the following:

(1) High rise buildings or building sections classified in occupancy group C.

(2) All buildings or building sections classified in occupancy group F, G, H or J-1 (except for "residential hotels," as such term is defined by the commissioner pursuant to rules and regulations).

(b) All work necessary to meet the requirements of this section shall be completed on or before April first, nineteen hundred eighty-seven.

§ 27-997. Acceptance tests

Open this section

No new, relocated or altered equipment shall be placed in operation until it has been tested and an equipment use permit has been issued by the commissioner. Such tests shall be made as required in section 27-999 of this article and shall be conducted by the person or firm installing, relocating or altering the equipment and shall be witnessed by a representative of the commissioner.

§ 27-998. Periodic inspection and test intervals

Open this section

Every new and existing device listed in article one of this subchapter except elevators located, (i) in owner occupied one-family or two-family dwellings provided that the elevator services only the owner occupied dwelling unit and that such dwelling unit is not occupied by boarders, roomers or lodgers, or (ii) within convents or rectories which are not accessible to non-occupants on a regular basis, or (iii) within an owner occupied dwelling unit which is not occupied by boarders, roomers or lodgers, shall be inspected and tested at least at the following intervals:

(a) Elevators – five times every two years, or as otherwise provided by the commissioner and except:

(1) Car safeties and counterweight safeties, where provided, shall be inspected at intervals not exceeding one year and shall be tested at intervals not exceeding two years.

(2) Oil buffers and governors shall be periodically inspected and shall be tested at intervals not exceeding one year.

(3) Hydraulic elevator pressure tanks and the piston rods of roped hydraulic elevators every three years.

(b) Escalators – five times every two years.

(c) Amusement devices – every six months except that the commissioner may extend the periodic inspection and test for an additional two months for amusement devices located in premises which are seasonally operated.

(d) Workers' hoists – every three months and immediately following each increase in travel.

(e) All other devices at such intervals as the commissioner may require.

(f) Additional inspections – in addition to the inspections required by subdivisions (a) through (e) of this section, the commissioner may make such additional inspections as required to enforce the provisions of this code. No fee shall be charged for such additional inspections.

(g) Fees – every owner of elevators and other devices shall pay to the department an inspection fee for each elevator or device in the amount prescribed by subdivision c of section 26-213 of title twenty-six of the administrative code.

§ 27-999. Inspection and test requirements

Open this section

Every new and existing device listed in article one of this subchapter shall be subjected to inspections and test requirements as follows:

(a) Elevators, dumbwaiters and escalators to the requirements specified in the reference standard RS 18-1 except that:

(1) Governor operated elevator car safeties shall be tested with no load in the car at the lowest operating speed.

(2) Instantaneous type car safeties, without governors, operated only as a result of the breaking or slackening of the hoist ropes shall be tested with no load in the car.

(b) Moving walks to the requirements specified in the reference standard RS 18-1.

(c) Lifts, conveyors, and amusement devices shall be inspected and subjected to the test requirements of the applicable reference standards and shall be tested to confirm the load capacity and safety of operation of the equipment, including tests of all operating protective safety devices, adequacy of the structural supports, and anchorage to floors, walls, ceilings and foundations.

(d) All other devices shall be subject to such inspections and tests as the commission may require.

§ 27-1000. Inspection agencies and elevator repair service

Open this section

(a) The required periodic inspections shall be made by the department except that two of the five inspections required every two years for elevators and escalators shall be made on behalf of the owner by an insurance company, elevator maintenance company, elevator manufacturer, elevator inspection company, or other person, each of which must be acceptable to the commissioner. The department shall promulgate rules and regulations establishing criteria as to the qualifications of such companies or persons. Such owner shall cause such inspections to be performed between January first and September fifteenth of each year. Reports by private inspections agencies shall be on such forms and in such manner as required by the commissioner. Such report shall be delivered to the owner of each elevator or escalator inspected listing all violations of any provisions of this subchapter within five days of inspection, and a signed copy of the report of each inspection shall be filed with the commissioner. The failure to have such inspection performed within the prescribed period and to file a copy of the report with the department on or before September thirtieth of each year shall be a violation of this section, which shall be punishable pursuant to the provisions of section 26-125 of title twenty-six of the administrative code. After such violation is placed the owner may file such report and the department shall enter a notation in its records of the date on which such report was received by the department. After the date of receipt by the department, the per diem penalty provided by subdivision c of section 26-125 of title twenty-six of the administrative code shall be stayed. The department shall maintain the violation on its records, with a notation of the date on which such a report was received by the department. On or before October fifteenth of each year of defects as found upon such inspection shall be corrected.

(b) In addition to the requirements of subdivision (a) of this section, all reports filed on or after April first, nineteen hundred eighty-seven for existing buildings required to install stair and elevator signs pursuant to section 27-390, elevator in readiness systems pursuant to paragraph two of subdivision (c) of section 27-989 of article one of this subchapter or firemen service operation pursuant to section 27-996.2 of article two of this subchapter, shall contain a certification that the required installation has been made. The reports shall be on such forms and in such manner as the commissioner may require. Failure to file such report by such a date shall be a violation of this section, and shall be punishable pursuant to section 26-125 of title twenty-six of the administrative code.

(c) In multiple dwellings (either J1 or J2 occupancy groups), the owner shall be required to have a contract with an elevator repair person or company authorizing the performance of emergency elevator repair work. Such repair person or company shall be one of the elevator inspection agencies or inspectors employed thereby currently acceptable to the commissioner. The name, address and telephone number of such elevator repair person or company shall be maintained on each premises, in a location readily accessible to employees of this department, and maintenance or custodial staff at the premises.

§ 27-1001. Permit required

Open this section

No construction, alteration or removal shall be commenced until a written work permit therefor shall have been issued by the commissioner in accordance with the provisions of article seventeen of subchapter one of this chapter. No equipment shall be placed in operation until an equipment use permit has been obtained in accordance with provisions of article eighteen of subchapter one of this chapter and section 27-997 of article three of this subchapter.

§ 27-1002. Temporary use permits

Open this section

Temporary use permits may be issued by the commissioner upon request in accordance with the provisions of section 27-188 of article eighteen of subchapter one of this chapter for any equipment or device regulated herein, except power operated scaffolds. Temporary use permits for elevators shall be conditioned further upon compliance with the following:

(a) The class of service to be permitted is designated on the temporary permit.

(b) The hoistway has been enclosed throughout in an enclosure complying with subdivision (b) of section 27-987 of article one of this subchapter or with a temporary enclosure in accordance with the requirements for workers' elevators (temporary elevators) of the industrial code of the state of New York, rule no. 23.

§ 27-1003. Posting of temporary use certificate

Open this section

The temporary operating certificate shall be posted in a conspicuous location on, or adjacent to, the device covered by the certificate and shall state that the device has not been finally approved by the commissioner.

§ 27-1004. Posting of inspection certificate

Open this section

a. At the time the equipment use permit is issued, an inspection certificate issued by the commissioner shall be posted. No such certificate shall be issued for elevators which are not subject to periodic inspections pursuant to section 27-998. The certificate shall be in such form as determined by the commissioner and shall be posted in the car of every passenger and freight elevator and on or near every escalator and power operated scaffold and in a frame with a transparent cover.

b. In place of posting inspection certificates in those locations specified in subdivision a of this section, certificates may be kept in the on site building manager's office. In a building where this option is elected, there must be a building manager's office open during normal business hours, and there must be posted in each location specified in subdivision a of this section a notice in a frame with a transparent cover, or a plaque with an indelible inscription, stating that the inspection certificate is located in the building manager's office and identifying the location of such office.

§ 27-1005. Operators

Open this section

Every power driven passenger elevator and freight elevator with a rise of more than one story, except automatic operation and continuous pressure elevators and sidewalk elevators, shall be in charge of a designated competent operator, who shall be at least eighteen years old, free from serious physical or mental defects, and selected with consideration of his or her abilities to perform his or her duties in a careful and competent manner, and who has been instructed in accordance with the requirements of the commissioner, except as otherwise specifically provided by law. Operators of amusement devices that require the services of a regular operator shall be at least eighteen years of age and shall have secured a certificate of competence from the commissioner. If the commissioner finds that any person engaged in running an elevator or amusement device is not competent to operate the elevator or device, the owner, agent or lessee of such elevator or amusement device shall, upon notice from the commissioner, discontinue the operation of such elevator or amusement device by such operator. Other devices listed in article one of this subchapter shall, when deemed necessary by the commissioner, be in charge of a designated competent operator conforming to such qualifications as the commissioner may prescribe except that operators for workers' hoists shall be assigned as required by the applicable provisions of reference standard RS 18-7.

§ 27-1006. Accidents

Open this section

The owner or person in charge of the equipment or devices listed in article one of this subchapter shall promptly notify the commissioner of every accident involving injury to any person requiring the services of a physician or damage to property or to apparatus exceeding one hundred dollars on, about, or in connection with such equipment, and shall afford the commissioner every facility for investigating such accident or damage. The commissioner shall make an investigation immediately thereafter, and shall prepare a full and complete report of such investigation. Such report shall give in detail all material facts and information available and the cause or causes as far as they can be determined. Such report shall be open to public inspection at all reasonable hours. When an accident involves the failure or destruction of any part of the construction or operating mechanism of such equipment, no such equipment shall be used until it has been made safe, and re-inspected by the commissioner; and the commissioner may order the discontinuance of such equipment until a new use permit has been issued by him or her for its use. No part shall be removed from the premises of the damaged construction or operating mechanism until permission to do so has been granted by the commissioner.

Title 27, Chapter 1, Appendix: Reference Standards

Open this section

BUILDING CODE REFERENCE STANDARDS

RS 2 Definitions. RS 3 Occupancy and Construction Classifications. RS 5 Fire Protection Construction Requirements. RS 6 Photoluminescent Exit Path Markings. RS 7 Special Uses and Occupancies. RS 8 Places of Assembly. RS 9 Loads. RS 10 Structural Work. RS 11 Foundations. RS 12 Light, Heat, Ventilation and Noise Control. RS 13 Mechanical Ventilation, Air Conditioning and Refrigeration Systems. RS 14 Heating and Combustion Equipment. RS 15 Chimneys and Gas Vents. RS 16 Plumbing and Gas Piping. RS 17 Fire Alarms, Detection and Extinguishing Equipment. RS 18 Elevators and Conveyors. RS 19 Safety of Public and Property During Construction Operations.

RULE OF CONSTRUCTION OF THE BUILDING CODE REFERENCE STANDARDS

Section 1.

It shall be a rule of construction for the building code reference standards of the appendix to chapter one of title twenty-seven of the administrative code of the city of New York that references to the sections of the Administrative Code repealed by Chapter 907 of the Laws of 1985, heretofore promulgated and currently in effect, should be deemed to refer to the corresponding new sections of such Code as specified in the distribution table contained in Chapter 907 or as assigned by the State Legislative Bill Drafting Commission.

§ 2. All Building Code Reference Standards enacted or adopted prior to the effective date of this revision are hereby made subject to the rule of construction established in Section "1" hereof.

RS 2-1. REFERENCE STANDARDS AGENCIES AND NATIONAL ORGANIZATIONS

Open this section

The following agencies and national organizations promulgate standards referenced in this code and its referenced standards. The abbreviations in front of the agency or national organization is used to identify it. Parentheses ( ) indicate its former abbreviation.

AA

Aluminum Association

Suite 300

900 19th St., N.W.

Washington, D.C. 20006

AAMA, (AWMA)

American Architectural Manufacturers Association

2700 River Road

Des Plaines, Illinois 60018

AASHTO, (AASHO)

American Association of State Highway and Transportation

Officials

444 North Capital Street

Washington, D.C. 20001

A-CE, (A-OCE)

Army Chief of Engineers

Attn: ENGMC-ES

1000 Independence Avenue, S.W.

Washington, D.C. 20314

ACI

American Concrete Institute

P.O. Box 19150

Redford Station

Detroit, Michigan 48219

AF&PA, (NLMA), (NFPA), (NFoPA)

American Forest and Paper Association

Suite 800

1111 19th, Street, N.W.

Washington, DC 20036

AGA

American Gas Association

1515 Wilson Boulevard

Arlington, Virginia 22209

AGMA

American Gear Manufacturers Association

1901 North Fort Meyer Drive

Arlington, Virginia 22209

AHA, (IBI)

American Hardwood Association

205 West Touky Avenue

Park Ridge, Illinois 60068

AISC

American Institute of Steel Construction, Inc.

Wrigley Building

400 North Michigan Avenue

Chicago, Illinois 60611

AISG, (A Ins A), (AIA), (NBFU)

American Insurance Services Group, Inc.

Engineering & Safety Service

85 John Street

New York, N.Y. 10038

AISI

American Iron and Steel Institute

Suite 1300

1101 17th Street, N.W.

Washington, DC 20036-4700

AITC

American Institute of Timber Construction

7012 S. Revere Pkwy., Suite 140

Englewood, CO 80112

ANSI, (USASI)

American National Standards Institute, Inc.

1430 Broadway

New York, New York 10018

APA

American Plywood Association

P.O. Box 11700

Tacoma, Washington 98411

API

American Petroleum Institute

1220 L Street, N.W.

Washington, D.C. 20005

AREA

American Railway Engineering Association

50 F Street, N.W.

Washington, D.C. 20001

ARI, (AFI), (REMA), (ACRMA), (NWAHACA)

Air Conditioning and Refrigeration Institute

1501 Wilson Boulevard

Arlington, Virginia 22209

ASCE

American Society of Civil Engineers

United Engineering Center

345 East 47th Street

New York, New York 10017

ASHRAE, (ASHAE)

American Society of Heating, Refrigerating and Air-

Conditioning Engineers

1791 Tullie Circle, N.E.

Atlanta, Georgia 30329

ASME

American Society of Mechanical Engineers

United Engineering Center

345 East 47th Street

New York, New York 10017

ASSE

American Society of Sanitary Engineering

P.O. Box 40362

Bay Village, Ohio 44140

ASTM

American Society for Testing and Materials

1916 Race Street

Philadelphia, Pennsylvania 19103

AWPA

American Wood Preservers Association

P.O. Box 849

Stevensville, Maryland 21666

AWPI

American Wood Preservers Institute

1945 Gallows Road

Vienna, Virginia 22180

AWS

American Welding Society

550 N.W. LeJeune Road

Miami, Florida 33125

AWWA

American Water Works Association

6666 West Quincy Avenue

Denver, Colorado 80235

BIA, (SCPI)

Brick Institute of America

11490 Commerce Park Drive

Reston, VA. 22091-1506

BHMA

Building Hardware Manufacturers Association, Inc.

60 East 42nd Street

New York, New York 10165

CISPI

Cast Iron Soil Pipe Institute

Suite 419

5959 Shallowford Road

Chattanooga, TN 37421

CFR

Code of Federal Regulations

Superintendent of Documents

Government Printing Office

Washington, D.C. 20402

CPSC

Consumer Product Safety Commission

Office of the Secretary

Washington, D.C. 20207

CRSI

Concrete Reinforcing Steel Institute

933 North Plum Grove Road

Schaumburg, Illinois 60173-4758

(CS)

(For Commercial or Commodity Standards, see address under DOC)

DEC

Department of Environmental Conservation

50 Wolf Road

Albany, N.Y. 12205

DOC

United States Department of Commerce National Institute of

Standards and Technology

Gaithersburg, MD 20899

(Available from Superintendent of Documents

Government Printing Office

Washington, D.C. 20402-9325)

FCC

Federal Communications Commission

1919 M Street, N.W.

Washington, D.C. 20554

FEMA

Federal Emergency Management Agency

P.O. Box 8181

Washington, D.C. 20024

FMS

Factory Mutual System

Standards-Laboratories Department

1151 Boston-Providence Turnpike

Norwood, Massachusetts 02062

FS

Federal Specifications

General Services Administration

Specification and Consumer Information

Distribution Section (WFSIS)

Washington Navy Yard Bldg. 197

Washington, D.C. 20407

GA

Gypsum Association

810 First Street, N.E.

Suite 510

Washington, D.C. 20002

HPMA, (HPI), (HPMA)

Hardwood Plywood Manufacturers Association

P.O. Box 2789

Reston, Virginia 22090-2789

HUD

U.S. Dept. of Housing and Urban Development

451 Seventh Street, S.W.

Washington, D.C. 20410

IAPMO

International Association of Plumbing and Mechanical

Officials

5032 Alhambra Avenue

Los Angeles, California 90032

(IBI)

See AHA

IC

Industrial Code Rules

New York State Department of Labor

N.Y.C. Office

One Main Street

Gair Tower

Brooklyn, New York 11201

ICBO, (UBC)

International Conference of Building Officials

5360 South Workman Mill Road

Whittier, California 90601

IEEE

Institute of Electrical and Electronics Engineers, Inc.

345 East 47th Street

New York, N.Y. 10017

IES

Illuminating Engineers Society

United Engineering Center

345 East 47th Street

New York, New York 10017

I-SANTA

Industrial Stapling and Nailing Technical

Association

435 North Michigan Avenue

Suite 1717

Chicago, Illinois 60611

ISO

International Organization for Standardization (Available from ANSI)

MHI, (MHMA)

Manufactured Housing Institute

1745 Jefferson Davis Highway

Arlington, Virginia 22202

MIL

Military Specifications

Naval Supply Depot

5801 Tabor Avenue

Philadelphia, PA 19111

NAPHCC

National Association of Plumbing, Heating, Cooling

Contractors

1016 20th Street

Washington, D.C. 20036

(NBS)

(For National Bureau of Standards, See NIST)

NCMA

National Concrete Masonry Association

P.O. Box 781

Herndon, Virginia 22070

NCRP

National Council on Radiation Protection and

Measurements

NCRP Publications

P.O. Box 30175

Washington, D.C. 20014

NFiPA, (NFPA)

National Fire Protection Association

Batterymarch Park

Quincy, MA 02269

NIST, (NBS)

National Institute of Standards and Technology

U.S. Department of Commerce

Gaithersburg, MD 20899

NSF

National Sanitation Foundation

P.O. Box 1468

Ann Arbor, Michigan 48106

NYCRR

New York Code Rules and Regulations

Publications Bureau

Department of State

162 Washington Avenue

Albany, N.Y. 12231

PDI

Plumbing Drainage Institute

1106 W. 77th Street, South Drive

Indianapolis, Indiana 46260-3318

PCA

Portland Cement Association

5420 Old Orchard Road

Skokie, Illinois 60077

PS

Office of Product Standards

National Bureau of Standards

U.S. Department of Commerce

Washington, D.C. 20234

(Available from Superintendent of Documents)

PSC

New York State Public Service Commission

NYC Office

400 Broome Street

New York, New York 10013

RCRBS

Research Council on Riveted and Bolted Structural Joints of

the Engineering Foundation

345 East 47th Street

New York, New York 10017

RCSHSB

Red Cedar Shingle and Handsplit Shake Bureau

515 116th Avenue, N.E., Suite 275

Bellevue, WA 98004

SJI

Steel Joist Institute

3127 10th Avenue North Extension

Myrtle Beach, SC 29577-6760

SMACNA

Sheet Metal and Air-Conditioning

Contractors National Association, Inc.

8224 Old Courthouse Road

Tyson's Corner

Vienna, VA 22180

SMPTE

Society of Motion Picture and Television Engineers

595 West Hartsdale Avenue

White Plains, N.Y. 10607-1824

SPIB

Southern Pine Inspection Bureau

4709 Scenic Highway

Pensacola, Florida 32504

SSSI

Steel Scaffolding & Shoring Institute

2130 Keith Building

Cleveland, Ohio 44115

TCA

Tile Council of America

4801 Montgomery Lane

Washington, D.C. 20014

TECO

Timber Engineering Company

5530 Wisconsin Avenue, N.W.

Chevy Chase, Maryland 20815

TPI

Truss Plate Institute, Inc.

583 D'Onofrio Drive

Suite 200

Madison, WI 53719

UBC

Uniform Building Code. (See the International

Conference of Building Officials.)

UL

Underwriters Laboratories, Inc.

333 Pfingsten Road

Northbrook, Illinois 60062

or

1285 Melville Road

Melville, New York 11746

ULC

Underwriters' Laboratories of Canada

7 Crouse Road

Scarborough, Ontario, Canada MIR 3A9

(USASI)

See ANSI

RS 3. OCCUPANCY AND CONSTRUCTION CLASSIFICATIONS

Open this section

List of Referenced National Standards RS 3–1 Fire Tests of Building Construction and Materials. RS 3–2 Tests for Surface Burning Characteristics of Building Materials. RS 3–3 Occupancy Group Classifications of Zoning Uses (Appendix A of Zoning Resolution).

LIST OF REFERENCED NATIONAL STANDARDS

ASTM E 119—Standard Methods of Fire Tests of Building Construction and Materials—1983

ASTM E 84—Standard Method of Test for Surface Burning Characteristics of Building Materials—1987

REFERENCE STANDARD RS 3–1

ASTM E 119—Standard Methods of Fire Tests of Building Construction and Materials—1983

REFERENCE STANDARD RS 3–2

ASTM E 84—Standard Method of Test for Surface Burning Characteristics of Building Materials—1987

REFERENCE STANDARD RS 3–3

Occupancy Group Classifications of Zoning Uses

(Appendix A of Zoning Resolution)

Use or Occupancy Zoning Resolution Use Group Building Code Occupancy Group • Adhesives manufacture, excluding manufacture of basic components 17 A, D–1 or D–2 depending on nature of materials involved • Advertising displays manufacture 17 D–1 or D–2 depending on nature of materials involved • Agricultural machinery, manufacture, including repairs 18 D–2 • Agriculture Without nuisance or sales limitations 4 B–2 (no sales) or C (sales) • Without nuisance or sales limitations 17 B–2 (no sales) or C (sales) • Aircraft manufacture (including parts) 17 D–1 • Airports Not applicable Amusement parks, children's (See children's amusement parks) • Amusement park activities 15 F–2 (outdoor) or F–3 (indoor) • Animal hospitals 16 E • Animal pounds or crematoriums 16 E (pounds) or D–2 (crematoriums) • Antique stores 6 C • Apartment hotels 2 J–2 Apparel (See clothing) • Appliances Electrical appliance manufacturing 17 D–2 • Television, radio, phonograph or household appliance stores Limited as to floor areas 6 C • Unlimited 10 C • Household appliance repair shops 8 C • Arenas, auditoriums, or stadiums Limited as to capacity 12 F–1b (indoor) or F–2 (outdoor) • Unlimited — F–1 (indoor) or F–2 (outdoor) • Art Galleries Commercial 6 F–3 • Non-commercial 3 F–3 • Art goods manufacture, religious or church, excluding foundry operations 17 D–2 • Art metal craft shops 6 C (sales) or D–2 (No sales) • Art needle work 11 D–2 • Artist's supply stores 6 C • Asphalt or asphalt products Manufacture 18 A • Athletic equipment manufacture 17 D–2 • Athletic goods stores 6 C • Auction rooms, public 9 C Auditoriums • Limited as to capacity 12 F–1a (with scenery) or F–1b (without scenery) • Unlimited — F–1a (with scenery) or F–1b (without scenery) • Automobiles Dead Storage 16 B–2 • Driving Schools 8 E • Glass or mirror shops 7 C • Laundries 16 D–2 • Manufacture, including parts, or engine rebuilding 17 D–1 • Rental establishments 8 E • Repairs, body 17 D–1 • Repairs, except body repairs 16 D–1 • Sales, open or enclosed 16 C • Seat cover or convertible top establishments, selling or installation 7 C • Showrooms, no repair services 9 C • Supply stores, no repair services 7 C • Tire sales establishments 7 C • Wrecking establishments 18 D–2 • Automotive service stations Limited as to total area 13 E • Unlimited 13 E • Awnings Custom shops, limited as to floor area 7 C • Manufacture, with no limitation on production or on floor area 17 D–1 • Bakeries Limited as to floor area used for production 6 D–1 • Unlimited (See food products processing) — D–1 • Banks, including drive-in banks 6 E • Banquet halls 9 F–4 • Barber shops 6 E • Baths, steam 9 F–3 • Beaches, commercial 13 Not applicable • Beauty parlors 6 E • Beverages Bottling works 17 D–2 • Manufacture Alcoholic 18 D–1 • Non-alcoholic 17 D–2 • Bicycle Manufacture 17 D–2 • Rental or repair shops 7 E • Sales 6 C • Billiard parlors 8 F–3 • Blacksmith shops 16 D–1 • Blueprinting establishments 9 D–2 • Boarding houses 2 J–1 • Boatels 7 J–1 • Boats or ships Building or repair, for boats less than 200 ft. in length 17 D–1 • Building or repair, for boats 200 ft. or more in length 18 D–1 • Docks, for small pleasure boats 14 Not applicable • Fuel sales, open or enclosed Unrestricted as to location 13 E • Restricted as to location 14 E • Rentals, open or enclosed 14 E • Sales, open or enclosed 16 C • Showrooms, with no repair services 9 C • Storage, repair, or painting, including the incidental sale of boats, boat parts, or accessories, with restrictions on boat size and setbacks 14 D–1 • Bone distillation 18 D–1 • Books Binding (see printing) Hand binding or tooling 11 D–2 • Stores 6 C • Bottling works, for all beverages 17 D–2 • Bowling alleys Limited as to number of lanes 8 F–3 • Unlimited 12 F–3 • Breweries 18 D–1 • Brick manufacture 18 D–2 • Brush or broom manufacture 17 D–1 • Building materials Sales, open or enclosed, limited as to lot area 16 C • Yards, for sales, storage, or handling, open or enclosed, unlimited as to lot area except in the case of lumber yards 17 C (sales) or B–2 (no sales) Bus stations • With less than 10 berths — D–1 (bus area) and F–3 (passenger area) • With 10 or more berths — D–1 (bus area) and F–3 (passenger area) • Business machines Manufacture 17 D–2 • Small, repair shops 9 E • Stores, sales, or rentals 10 C • Business schools or colleges 9 G • Camera manufacture 17 D–2 • Camps, overnight or outdoor day 13 F–2 (outdoor) or F–3 (indoor) • Candy stores 6 C • Canvas or canvas products manufacture 17 D–1 • Carnivals, temporary 13 F–2 (outdoor) or F–3 (indoor) • Carpentry shops 16 D–1 Carpet • Cleaning establishments 16 A or D–1 depending on nature of materials involved • Manufacture 17 D–1 • Carpet, rug, linoleum or other floor covering stores Unlimited 10 C • Catering establishments 9 C (outside consumption) or F–4 (banquets) • Cement manufacture 18 D–2 • Cemeteries 4 B–2 (mausoleums, crypts) • Ceramic products Manufacture, custom 11 D–2 • Manufacture 17 D–2 • Charcoal manufacture 18 D–1 Chemicals • Compounding or packaging 17 A, D–1 or D–2 depending on nature or materials involved • Manufacture 18 A, D–1 or D–2 depending on nature of materials involved • Children's amusement parks Small 13 F–2 • Medium size 15 F–2 • Large size 15 F–2 • Unlimited as to size 15 F–2 • Churches 4 F–1b • Cigar stores 6 C • Circuses, temporary 13 F–1a • Clay manufacture 18 D–2 • Clay pits — Not applicable Cleaning or cleaning and dyeing establishments (see dry cleaning) • Clocks Manufacture 17 D–2 • Stores or repair shops 6 C (sales) or E (repair) • Clothing Accessory stores (See Clothing stores) — • Custom manufacture or altering for retail 11 A or D–1 depending upon nature of materials involved • Manufacture 17 A or D–1 depending upon nature of materials involved • Rental establishments 9 E • Stores Limited as to floor area 6 C • Unlimited 10 C Clubs Night (See eating or drinking places) Non-commercial • All types except those with outdoor swimming pools 4 J–1 (with residence) or E (without residence) • Clubs with outdoor swimming pools more than 500 ft. from all lot lines 4 J–1 (with residence) or E (without residence) • All types, including outdoor swimming pool clubs or clubs with outdoor swimming pools less than 500 ft. from any lot line 6, 14 J–1 (with residence) or E (without residence) • Coal Products manufacture 18 A • Sales, open or enclosed Limited as to lot area 16 A Unlimited (See coal storage) • Storage, open or enclosed 18 A • Coin stores 6 C • Coke products Manufacture 18 A • Colleges or universities, including professional schools, or college or school dormitories or fraternity or sorority houses, but excluding business colleges or trade schools 3 G (classroom buildings), J–2 (dormitories) Commercial parking garages or lots (See parking garages, public or parking lots, public) • Community centers 4 F–3 Concrete batching (See building materials yards) Concrete products manufacture (See stone processing or stone products) • Construction machinery manufacture, including repairs 18 D–2 • Contractors' establishments-electrical, glazing, heating, painting, paper hanging, plumbing, roofing, or ventilating Limited as to floor area 7 E • Limited as to open storage 16 E Unlimited (See contractors' yards) • Contractors' yards 17 Not Applicable Convalescent homes (See nursing homes) • Convents 3 J–3 • Cork products Manufacture 17 D–1 • Cosmetics or toiletries Manufacture 17 A or D–1 depending upon nature of materials involved • Costume rental establishments 9 C • Cotton ginning or cotton wadding or linter manufacture 17 A • Court houses 6 F–1b • Crating establishments 16 A Crematoriums • Animal 16 B–2 (urn storage) and F–1b (chapel) • Human 16 B–2 (urn storage) and F–1b (chapel) • Dance halls, public 12 F–4 Dance studios (See studios) • Day camps, outdoor 13 F–2 Delicatessen stores (See food stores) • Dental Instruments manufacture 11 D–2 Laboratories (See laboratories, medical or dental) Offices (see medical offices) • Department Stores 10 C • Diaper supply establishments 16 E • Disinfectants manufacture 18 D–1 Dormitories, college or school (See colleges or universities) • Drafting instruments Manufacture 11 D–2 • Dressmaking shops, custom 6 D–1 Drinking places (See eating or drinking places) • Drive-in theaters F–2 • Drug stores 6 C • Dry cleaning or clothes pressing establishments, limited as to floor area, solvents and machine capacity 6 D–1 or D–2 (See Section 705.0) • Dry cleaning or cleaning and dyeing establishments, without restrictions 16 D–1 or D–2 (See Section 705.0) • Dry goods stores Limited as to floor area 6 C • Unlimited 10 C • Dumps 18 Not applicable • Eating or drinking places With restrictions on entertainment 6 F–4 • Without restrictions on entertainment or dancing but limited to location in hotels 10 F–4 • Without restrictions 12 F–4 • Electric Power or steam generating plants 18 D–1 • Substations Public transit or railroad Small or medium size 17 D–2 • Large 17 D–2 • Utility Small 6 D–2 • Medium size 17 D–2 • Large 17 D–2 • Electrical Appliance Manufacture 17 D–2 • Stores (See appliances, television, radio, phonograph, or household appliance stores) C Contractors (See contractors' establishments) • Equipment assembly, not including electrical machinery 17 D–2 • Supplies, manufacturing 17 D–2 • Electrolysis studios 6 E Electrotyping or stereotyping (See printing) Engraving or photo-engraving (See printing) • Excelsior manufacture 18 A • Exterminators 7 E Fabric stores (See dry goods stores) • Fairs, temporary 13 F–2 (outdoors) or F–3 (indoors) • Feathers Bulk processing, washing, curing, or dyeing 18 A • Products manufacture, except washing, curing, or dyeing 17 A • Felt Bulk processing, washing, curing, or dyeing 18 D–1 • Products manufacture, except washing, curing, or dyeing 17 D–1 • Fertilizer manufacture 18 D–1 Filling stations (See automotive service stations) • Film, photographic, manufacture 18 D–1 • Fire Stations 6,14 D–2 (garage) and J–2 (dormitory) • Fish products, packing or processing 18 D–1 • Fishing tackle or equipment rental or sales 6,14 C • Florist shops 6 C • Food Products processing, except meat slaughtering or preparation of fish for packing 17 D–1 • Stores, including supermarkets, grocery stores, meat markets, or delicatessen stores 6 C • Foundries, ferrous or non-ferrous 18 D–1 Fraternity houses (See colleges or universities) • Frozen food lockers 6 B–2 • Fuel briquettes manufacture 18 D–1 • Fuel sales, open or enclosed Limited as to lot area 16 E Unlimited (See coal storage, petroleum storage, or lumber yards) • Funeral establishments 7 F–1b • Fungicides manufacture 18 D–1 • Fur Goods manufacture, not including tanning or dyeing 17 D–2 • Tanning, curing, finishing, or dyeing 18 A • Furniture Custom shops 16 D–1 • Manufacture 17 A or D–1 depending upon nature of materials involved • Stores Limited as to floor area 6 C • Unlimited 10 C • Furriers shops, custom 6 C Garages (See parking garages, public) • Garbage incineration or reduction 18 D–1 • Garden supply stores 6 C Gardens, truck (See agriculture) • Gas Manufacture 18 A • Public utility stations for metering or regulating 6 D–1 • Storage 18 A • Substations 6 D–1 Gasoline service stations (See automotive service stations) • Gelatin manufacture 18 D–1 • Generating plants, electric or steam 18 D–1 • Gift shops 6 C • Glass Cutting shops 16 D–2 • Manufacture 18 D–2 • Products manufacture from previously manufactured glass 17 D–2 Glazing contractors (See contractors' establishments) • Glue manufacture 18 D–1 • Golf Courses 4 Not applicable • Courses, miniature 13 F–3 (indoor) • Driving ranges 13 F–3 (indoor) • Grain Milling or processing 18 A • Storage 18 A • Graphite or graphite products Manufacture 18 D–1 • Gravel pits Not applicable Greenhouses (See agriculture) Grocery stores (See food stores) • Group homes 1, 2 J–3 • Gymnasiums 9 F–3 • Gypsum manufacture 18 D–2 • Hair Bulk processing, washing, curing, or dyeing 18 D–2 • Products manufacture (except washing, curing, or dyeing) 17 D–2 • Products manufacture, custom 11 D–2 • Hardware Manufacture 17 D–2 • Stores 6 C • Hat Bodies manufacture 17 D–1 • Repair shops 6 C • Health centers 4 H–2 Health services (See physical culture establishments) Heating contractors (See contractors' establishments) • Heating equipment showrooms, without repair facilities 9 E • Heliports D–1 • Hemp products manufacture D–1 • Home occupations E • Hosiery manufacture 17 D–1 • Hospitals, except animal hospitals Non-profit or voluntary, and related facilities 4 H–2 • Proprietary, and related facilities 4 H–2 • Hotels Transient 5 J–1 • Apartment 2 J–2 • Household Appliance repair shops 8 E Appliance stores (See appliances, television, radio, phonograph, or household appliance stores) • Equipment or machinery repair shops 16 D–2 • Ice cream stores 6 C • Ice Manufacture, dry or natural 17 D–2 • Sales, open or enclosed Limited as to lot area 16 C • Unlimited (See refrigerating plants) C • Ice skating rinks, outdoor 4 F–2 • Incineration or reduction of garbage, offal, or dead animals 18 D–1 • Ink or inked ribbon manufacture 17 A or D–1 depending on nature of materials involved • Insecticides manufacture 18 D–1 Institutions, philanthropic or non-profit • With sleeping accommodations 3 J–1 or J–2 depending on whether short or long term basis • Without sleeping accommodations 4 E • Interior decorating establishments Limited as to floor area for processing, servicing, or repairs 6 C • Unlimited (See furniture, textiles, or upholstering) C • Jewelry Manufacture Costume 17 D–2 • From precious metals 11 D–2 • Shops 6 C • Junk Yards 18 Not applicable • Jute products manufacture 17 D–1 • Kennels 16 E • Laboratories Medical or dental, for research or testing, with limitations on objectionable effects 9 D–2 • Research, experimental, or testing 17 D–2 • Lampblack manufacture 18 D–1 • Laundries, with no limitations on type of operation 16 D–2 • Laundry establishments, hand or automatic self-service 6 E • Leather Tanning, curing, finishing or dyeing 18 A • Goods stores 6 C • Products manufacture 17 D–1 • Libraries 3 G • Linen supply establishments 16 E • Linoleum Manufacture 18 A • Stores (See carpet stores) C • Liquor stores, package 6 C • Loan offices 6 E • Locksmith shops 6 E Lots (See parking lots, public) • Luggage Manufacture 17 D–1 • Stores 6 C • Lumber Processing or woodwork, bulk 18 D–1 Sales Limited as to lot area (See building materials sales) D–1 • Unlimited 18 D–1 • Yards Limited as to lot area 17 D–1 • Unlimited 18 D–1 • Machine Shops including tool, die or pattern making 16 D–2 • Tools manufacture 17 D–2 • Machinery Manufacture or repair Heavy 18 D–2 • Miscellaneous or electrical equipment 17 D–2 • Rental or sales establishments 16 C • Repair shops 16 E Machines, business (See business machines) • Manure storage 18 B–2 Markets Retail, including meat (See food stores) • Wholesale, produce or meat 17 C • Masseurs 9 E • Matches manufacture 18 A • Mattress manufacture, rebuilding or renovating 17 A • Meat Markets Retail (See food stores) C • Wholesale 17 C • Slaughtering or preparation for packing 18 D–1 • Medical Appliances Custom manufacture 11 D–2 • Manufacture 17 D–2 • Stores 6 C • Instruments, manufacture 11 D–2 Laboratories (See laboratories, medical) • Offices or group medical centers Limited as to location within building 4 E • Unlimited 6 E • Meeting halls 6 F–1b • Metals manufacture Alloys or foil, miscellaneous 18 D–2 • Casting or foundry products, heavy 18 D–2 • Finishing, plating, grinding, sharpening, polishing, cleaning, rust-proofing, heat treatment, or similar processes 17 D–1 • Ores reduction or refining 18 D–2 • Products treatment or processing 18 D–2 • Reduction, refining, smelting, or alloying 18 D–2 • Stamping or extrusion 17 D–2 • Treatment or processing 18 D–2 • Millinery shops 6 C • Mining machinery manufacture, including repairs 18 D–2 • Mirror silvering shops 16 D–2 • Monasteries 3 J–3 • Monument Sales establishments, with incidental processing to order 7 C • Works, with no limitations on processing 18 D–2 • Motels 7 J–1 • Motion picture production 17 D–1 • Motor cycles Manufacture 17 D–1 • Repairs, body 17 D–1 • Repairs, except body repairs 16 D–2 • Sales, open or enclosed 16 E • Showrooms, with no repair services 9 E Motor freight stations (See trucking terminals) • Motor vehicles, dead storage 16 B–2 • Moving or storage offices Limited as to storage 7 E • Unlimited 16 E • Museums 3 F–3 • Music stores 6 C Music studios (See studios) • Musical instruments Manufacture Excluding pianos and organs 11 D–2 • Including pianos or organs 17 D–1 • Repair shops 9 D–2 • Newspaper publishing 17 E • Newsstands, open or enclosed 6 C • Novelty products manufacture 17 D–1 • Novitiates 3 J–3 Nurseries (See agriculture) • Nursing homes Philanthropic or non-profit 3 H–2 • Proprietary 3 H–2 • Oakum products manufacture 17 D–1 • Office equipment or machinery repair shops 16 E • Office or business machine stores, sales or rental 10 E • Offices Business, professional or governmental 6 E • Dental, medical, or osteopathic (See medical offices) Wholesale, with storage restricted to samples 10 E • Oil cloth manufacture 18 A • Oil, public utility stations for metering or regulating 6 D–1 • Oil sales, open or enclosed Limited as to lot area 16 C • Unlimited (See petroleum or petroleum products storage) C • Optical Equipment manufacture 17 D–2 • Goods manufacture 11 D–1 • Optician or optometrist establishments 6 E • Orthopedic Appliances Custom manufacture 11 D–2 • Manufacture 17 D–1 • Stores 6 C • Instruments, manufacture 11 D–2 Osteopathic offices (See medical offices) • Outdoor, roller 13 F–2 • Packing or crating establishments 16 D–1 • Packing materials manufacture 18 D–1 • Paint Manufacture 18 A • Stores 6 C Painting contractors (See contractors' establishments) • Paper Mills (See wood pulp or fiber) D–1 • Products manufacture 18 D–1 • Stock companies 18 B–1 Paper-hanging contractors (See contractors' establishments) • Parish houses 4 J–3 • Parks, public or private 4 Not applicable • Parking garages, public Capacity of 100 spaces or less 8 B–1 or B–2 See Section • Capacity of 101 to 150 spaces 8 B–1 or B–2 709.2 • Capacity of more than 150 spaces B–1 or B–2 • Parking lots, public Capacity of 100 spaces or less 8 (See Section 712.0) • Capacity of 101 to 150 spaces 8 (See Section 712.0) • Capacity of more than 150 spaces (See Section 712.0) • Pawn shops 8 C • Peat storage 18 B–2 • Penny arcades 15 F–3 • Perfume or perfumed soaps, compounding only, not including soap manufacture 17 A • Pet shops 6 C • Petroleum or petroleum products Refining 18 A • Storage or handling 18 A Pharmaceutical products manufacture 17 A or D–1 depending on nature of materials used • Phonograph Repair shops 8 E • Stores (See appliances) C Photographic Developing or printing establishments 4 • Retail 6 C • Wholesale Limited as to floor area 9 D–2 • Unlimited 16 D–2 • Equipment Manufacture (except film) 17 D–2 • Stores 6 C • Studios 6 E • Supply stores 6 C • Photostating establishments 9 C • Physical culture establishments 9 F–3 • Picture framing stores 6 C • Plastics Products, manufacture 17 A • Raw, manufacture 18 A Platemaking (See printing) • Playgrounds F–2 Plumbing Contractors (See contractors' establishments) Equipment manufacture (See tools or hardware mfg.) • Showrooms, without repair facilities 9 E • Police Stations 6 E (offices) and H–1 (cells) • Pool halls 8 F–3 • Porcelain products manufacture 18 D–2 • Post offices 6 E • Poultry Killing establishments, for retail sales on the same zoning lot only 16 D–1 • Packing or slaughtering 18 D–1 • Precision instruments manufacture Optical equipment, clocks, or similar products 17 D–2 • Medical, dental, or drafting instruments, optical goods, or similar products 11 D–2 • Printing Custom 11 D–1 • Limited as to floor area 9 D–1 • Unlimited 17 D–1 • Prisons 12 H–1 • Produce or meat markets, wholesale 17 C • Public auction rooms 9 C • Public transit yards 16 Not applicable • Publishing 17 D–1 • Pumping stations, water or sewage 6 D–2 • Rabbit Killing establishments, for retail sales on the same zoning lot only 16 D–1 • Packaging or slaughtering 18 D–1 • Racetracks F–2 • Radio Appliance repair shops 8 C • Stores (See appliances) C • Studios 10 E • Towers, non-accessory K • Radioactive waste disposal services 18 D–1 • Railroad Equipment manufacture, including railroad cars or locomotives 18 D–2 • Passenger stations F–3 • Right-of-way 4 Not applicable • Substations Small or medium size 17 D–2 • Large 17 D–2 • Railroads, including rights-of-way, freight terminals, yards or appurtenances, or facilities or services used or required in railroad operations, but not including passenger stations 17 Not applicable • Record stores 6 C • Recreation centers, non-commercial 4 F–2 (outdoor) F–3 (indoor) • Rectories 4 J–3 • Reducing salons 9 F–3 • Refreshments stands, drive-in 7 F–2 • Refrigerating plants 18 D–2 • Religious or church art goods manufacture 17 D–2 • Residences Single-family detached 1 J–3 • One-family semi-detached or two-family detached or semi-detached 2 J–3 • Boarding or rooming houses 2 J–1 • All other 2 J–1 or J–2 Rest homes (See nursing homes) • Riding academies, open or enclosed 16 E (offices) and B–1 (stables) Roofing contractors (See contractors' establishments) • Rooming houses 2 J–1 • Rubber Processing or manufacture, natural or synthetic 18 D–1 • Products manufacture (excluding all natural or synthetic rubber processing) 17 D–1 Rug stores (See carpet stores) • Sailmaking establishments 7,14 D–1 • Salvage storage 18 B–1 or B–2, depending on materials • Sand pits Not applicable • Sanitariums Philanthropic or non-profit 3 H–2 • Proprietary 3 H–2 • Sawmills 18 D–1 • Scenery construction 17 D–1 Schools Dormitories (See colleges or universities) • Nursery, kindergarten, elementary or secondary schools 3 G • With no living or sleeping accommodations 3 G • Trade or other schools for adults, limited as to objectionable effects 9 G • Trade schools for adults, unlimited 16 G • Scrap metal, paper, or rag storage 18 B–1 • Seed stores 6 C • Seminaries 4 G • Settlement houses 4 J–1 • Sewage Disposal plants 18 D–1 • Pumping stations 6 D–2 • Sewing machine stores, selling household machines only 6 C • Ship chandlers 11 C • Ship or boat building or repair yards, for ships 200 ft. in length or over 18 D–1 • Shipping, waterfront 17 Not applicable • Shoddy manufacture 17 A • Shoes Manufacture 17 E • Repair shops 6 D–1 • Stores 6 C • Sign painting shops Limited as to floor area 7 D–2 • Unlimited 16 D–1 • Silver plating shops, custom 16 D–2 • Silverware manufacture, plate or sterling 17 D–2 • Sisal products manufacture 17 A • Size manufacture 18 D–1 • Skating rinks Indoor 12 F–3 • Outdoor, ice 4 Not applicable • Outdoor, roller 13 F–2 • Slag piles 18 F–2 • Slaughtering of animals or poultry 18 D–1 • Soap or detergents Manufacture, including fat rendering 18 A • Packaging only 17 D–1 • Soldering shops 16 D–2 • Solvent extracting 18 A Sorority houses (See colleges or universities) • Sporting equipment manufacture 17 D–1 • Sporting goods stores 6 C • Stable for horses 16 B–1 • Stadiums Limited as to capacity 12 F–2 • Unlimited F–2 • Stamp stores 6 C • Stationery stores 6 C • Statuary, mannequins, figurines, religious or church art goods manufacture, excluding foundry operations 17 D–2 • Steel products Miscellaneous fabrication or assembly 17 D–2 • Structural products manufacture 18 D–2 • Stock yards or slaughtering of animals or poultry 18 D–1 • Stone processing or stone products 18 D–2 • Storage Wholesale 16 B–2 • Offices (See moving or storage offices) E • Studios Music, dancing, or theatrical 9 F–3 • Radio or television 10 F–1a (with scenery) or F–1b (without scenery) • Sugar Refining 18 D–1 • Swimming pools Commercial 13 F–2 (outdoor) or F–3 (indoor) • Non-commercial (See clubs) F–2 (outdoor) or F–3 (indoor) • Table tennis halls 12 F–3 • Tailor shops, custom 6 E • Tanning (See leather or fur) A • Tapestries manufacture 11 D–1 • Tar products manufacture 18 D–1 • Taxidermist shops 7 C • Telegraph offices 6 E • Telephone exchanges or other communications equipment structures 6 E • Television Repair shops 8 C • Stores (See appliances) C • Studios 10 F–1a (scenery) or F–1b (no scenery) or D–2 (no audience) • Towers, non-accessory K • Tennis courts, outdoor 4 F–2 • Terminal facilities at river crossings for access to electric, gas, or steam lines 6 D–2 • Textiles Bleaching 18 D–1 • Products manufacture 17 D–1 • Spinning, weaving, manufacturing, dyeing, printing, knit goods, yarn, thread, or cordage 17 D–1 Theaters • Limited capacity 8 F–1a (with scenery) or F–1b (without scenery) • Unlimited capacity 8 F–1a (with scenery) or F–1b (without scenery) • Theaters, drive-in — F–2 Theatrical studios (See studios) • Tile Manufacture 18 D–2 • Tire sales establishments including installation services 7 C • Tobacco Curing or manufacture, or tobacco products manufacture 17 D–1 • Stores 6 C • Toiletries manufacture, not including soap manufacture 17 A or D–1 depending upon materials involved • Tool or hardware manufacture 17 D–2 • Topsoil storage 18 B–2 • Tourist cabins 7 J–1 • Towel supply establishments 16 E • Toys Manufacture 17 D–1 • Stores 6 C • Trade or other schools for adults Limited as to objectionable effects 9 G • Unlimited 16 G • Trade expositions Limited as to rated capacity 12 F–2 (outdoor) F–3 (indoor) • Unlimited F–2 (outdoor) F–3 (indoor) • Trailer camps 7 (See section 714.0) • Trailer Manufacture, including parts 17 D–1 • Repairs, body 17 D–1 • Sales, open or enclosed 16 C • Showrooms, with no repair services 9 E • Transit substations Small or medium size 17 D–2 • Large 17 D–2 • Travel bureaus 6 E Truck gardens (See Agriculture) Truck • Manufacture (including parts) or engine rebuilding 17 D–1 • Repairs, body 17 D–2 • Repairs, except body repairs 16 D–2 • Sales, open or enclosed 16 C • Showrooms, with no repair services 9 E • Trucking terminals or motor freight stations Limited as to lot area 16 B–1 • Unlimited 17 B–1 • Turpentine manufacture 18 A • Typewriter stores 6 C • Typewriter or other small business machine repair shops 9 C Typography (See printing) • Umbrellas Manufacture 17 D–1 • Repair shops 9 D–2 Undertakers (See funeral establishments) • Upholstering Bulk, including shops not dealing directly with consumers 17 D–1 • Shops dealing directly with consumers 8 D–2 • Variety stores Limited as to floor area 6 C • Unlimited 10 C • Varnish manufacture 18 A • Vehicles Dead storage of motor 16 B–2 • Manufacture, children's 17 D–1 • Storage, commercial or public utility, open or enclosed 16 B–1 (enclosed) (See Section 710.0 for open) • Venetian blind, window shade, or awning Custom shops, limited as to floor area 7 C • Manufacture, with no limitation on production or on floor area 17 A or D–1 depending upon nature of materials involved Ventilating contractors (See contractors' establishments) • Ventilating equipment showrooms, without repair facilities 9 E • Wallpaper stores 6 C • Warehouses 16 B–1 or B–2, depending on nature of materials stored • Watch or clock stores or repair shops 6 C • Watch making 11 D–2 • Waterfront shipping 17 Not applicable • Water pumping stations 6 D–2 • Wax products manufacture 17 A • Weaving, hand 11 D–1 • Wedding chapels 9 F–1b • Welding shops 16 D–1 • Welfare centers 4 E Wholesale establishments • Accessory storage limited to 1,500 sq. ft. 7 B–1 or B–2 depending on nature of materials stored • Accessory storage limited to 2,500 sq. ft. 11 B–1 or B–2 depending on nature of materials stored • Unlimited accessory storage 16 B–1 or B–2 depending on nature of materials stored • Wholesale offices or showrooms, with storage restricted to samples 10 E • Window shades Custom shops, limited as to floor area 7 C • Manufacture, without limitation on production or on floor area 17 D–1 • Wood Bulk processing or woodworking 18 D–1 • Distillation 18 D–1 • Products manufacture 17 D–1 • Pulp or fiber, reduction or processing, including paper mill operations 18 D–1 • Sales, open or enclosed Limited as to lot area 16 C • Unlimited (See lumber yards) — C • Woodworking shops, custom 16 A or D–1 depending upon nature of materials involved • Wool scouring or pulling D–1

RS 4. BUILDING LIMITATIONS [Repealed]

Open this section

Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 1987/058 and L.L. 2013/141.

RS 5. FIRE PROTECTION CONSTRUCTION REQUIREMENTS

Open this section

List of Referenced National Standards RS 5–1A Fire Resistance Ratings. RS 5–1B Fire Resistance Design Manual. RS 5–1C Miscellaneous Test Reports for Load-Bearing Wall Assemblies. RS 5–1D Miscellaneous Test Reports for Load-Bearing Steel Column Assemblies. RS 5–1E Miscellaneous Test Reports for Load Bearing Steel Beam/Girder Assemblies. RS 5–1F Methods of Analytical Determination of Fire Resistance of Load Bearing Steel Truss Assemblies. RS 5–2 Fire Test of Building Construction Materials. RS 5–3 Structural Lumber Fire Retardant Treatment by Pressure Processes. RS 5–4 Plywood Fire Retardant Treatment by Pressure Processes. RS 5–5 Surface Burning Characteristics of Building Materials. RS 5–6 Fire Tests of Door Assemblies. RS 5–7 Fire Tests of Window Assemblies. RS 5–8 Fire Doors and Windows. RS 5–9 Roof Covering Classifications. RS 5–10 Fire Tests of Roof Coverings. RS 5–11 Smoke and Heat Venting. RS 5–12 Rate of Burning of Self-Supporting Plastics in a Horizontal Position. RS 5–13 Rate of Burning of Flexible Plastics in a Vertical Position. RS 5–14 Thickness of Solid Electrical Insulation. RS 5–15 Minimum Covering of Prestressing Steel for Various Fire Resistance Ratings. RS 5–16 Acoustical Tile and Lay-In Panel Ceiling Suspension Systems. RS 5–17 Standards for the Installation of Smoke Shafts. RS 5–18 Standards for the Pressurization of Stairs. RS 5–19 Standards for the Fire Test of Through-Penetration Fire Stops. RS 5–20 Flammability of Carpets. RS 5–21 Fire Test of Exterior, Nonload-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate-Scale, Multistory Test Apparatus.

LIST OF REFERENCED NATIONAL STANDARDS

AISG—Fire Resistance Ratings, as Modified—1985

AISI FT–900–0480—Designing Fire Protection for Steel Columns, Third Edition—1980

AISI FT–901—Fire Resistant Rating of Load Bearing Steel Stud Walls—1981

AISI FT–902–0285—Designing Fire Protection for Steel Beams—1984

AISI FT–227–1281—Designing Fire Protection for Steel Trusses, Second Edition—1981

GA–600—Fire Resistance Design Manual, Twelfth Edition, as Modified—1988

NFoPA—Report No. WHI–694–020, Report of Testing on a Load Bearing Stud Partition—1981

NFoPA—Report No. WHI–690–003, Report of Testing on a Load-Bearing Stud Partition—1981

ASTM E 119—Standard Methods of Fire Tests of Building Construction and Materials—1988

AWPA C 20—Structural Lumber—Fire Retardant Treatment by Pressure Processes—1988

AWPA C 27—Plywood Fire Retardant Treatment by Pressure Processes—1988

ASTM E 84—Standard Method of Test for Surface Burning Characteristics of Building Materials—1987

ANSI/ASTM E 69—Standard Test Method for Combustible Properties of Treated Wood by Fire-Tube Apparatus—1980

ANSI/ASTM E 160—Standard Test Method for Combustible Properties of Treated Wood by Crib Test—1980

ANSI/ASTM E 152—Standard Methods of Fire Test of Door Assemblies—1981a

ANSI/ASTM E 163—Standard Methods of Fire Test of Window Assemblies—1984

NFiPA 80—Standard for Fire Doors and Windows—1986

ANSI/ASTM E 108—Standard Methods of Fire Test of Roof Coverings—1983

NFiPA 204M—Guide for Smoke and Heat Venting—1985

ANSI/ASTM D 635—Standard Test for Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastics in a Horizontal Position—1981

ANSI/ASTM D 568—Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Flexible Plastics in a Vertical Position—1977

ANSI/ASTM D 374—Standard Test Methods for Thickness of Solid Electrical Insulation—1979

ASTM E 814—Standard Method of Fire Tests of Through-Penetration Fire Stops—1983

DOC FF1—Methanine Pill Test—1970

ASTM E 648—Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source—1988

ASTM E 662—Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials—1983

UBC Std. 26-9—Method of Test for the Evaluation of Flammability Characteristics of Exterior, Nonload-Bearing Wall Assemblies Containing Combustible Components Using the Intermediate-Scale, Multistory Test Apparatus—1997

RS 5-1A

Open this section

AISG1985—Fire Resistance Ratings, as modified.

MODIFICATIONS—The provisions of the AISG Fire Resistance Ratings shall be subject to the following modifications:

1. Delete the following pages in their entirety: 22, 24, 45, 46, 48, 52, 54, 76, 84, 97, 98, 99, 102, 110, 115, 117.

2. Delete the specified items on the following pages:

PAGE DESCRIPTION—SPECIFIED ITEMS

25 Protection Type—Unprotected

Rating(s) of 45 and 30 min. comb.

28 Protection Type—None

Rating(s) of 45 min. comb.

29 2 1/2 slab thickness-Rating 30 min.

41 Ceiling Type—None

Rating 5 min.

47 Ceiling Type—Gypsum Wallboard

Rating of 30 min. comb.

48 Ceiling Type—Gypsum Wallboard

Rating of 25 min. comb.

50 Ceiling Type—Plaster on Gypsum Lath

Rating(s) of 45 min. and 30 min. comb.

62 Type—Calcareous Gravel

Rating(s) 30 min. and 20 min. comb.

63 Type—Cinder

Rating 45 min.

65 Type—Expanded clay, shale or slate (Rotary kiln)

Rating 45 min.

68 Type—Siliceous Gravel

Rating(s) 20 min. and 15 min.

77 Plaster Type—Gypsum Neat

Rating 45 min.

83 Plaster Type—Gypsum and Sand

Rating 45 min.

91 Plaster Type—Portland Cement and Sand

Rating(s) 45 min. and 30 min.

95 Type—Clay or Shale

Rating 45 min.

103 Finish Type—Laminated Wood

Rating(s) 45 min., 30 min., 25 min.,

15 min. and 10 min. comb.

104 Finish Type—Asbestos Cement Board

Rating(s) 40 min. and 30 min. comb.

107 Plaster Type—Gypsum and Sand

Rating(s) 45 min. and 30 min. comb.

109 Plaster Type—Gypsum and Sand

Rating(s) 45 min., 30 min. and 20 min. comb.

111 Plaster Type—Gypsum and Sand

Rating 30 min. comb.

—Lime and Sand

Rating(s) 45 min., 30 min. and 25 min. comb.

112 Finish Type—Asbestos Cement Board

Rating(s) 30 min. and 10 min. comb.

114 Finish Type—Gypsum Wallboard

Rating(s) 45 min., 30 min. and 25 min. comb.

117 Finish Type—Wood

Rating 45 min. comb.

3. An equivalent blend of mineral fibers and cementitious binders may be substituted for asbestos-cement material on the following pages: 46, 51, 52, 92, 104, 112, 114.

RS 5-1B

Open this section

GA–600 1988—Fire Resistance Design Manual, Twelfth Edition, as Modified.

MODIFICATIONS.—The provisions of GA–600–1988 shall be subject to the following modifications:

1. Revise the heading on the top of page five in the section on USE OF MANUAL to read as follows:

LIMITING HEIGHTS

(a) NONLOAD-BEARING PARTITIONS

2. Insert the following after the paragraphs on (a) NONLOAD-BEARING PARTITIONS and before the heading PERFORMANCE OF PLASTER:

(b) LOAD BEARING PARTITIONS

Lateral bracing and height limitations shall be designed in accordance with the applicable reference standard independent of the sheathing.

3. In the section on GENERAL EXPLANATORY NOTES under the heading USE OF MANUAL, add the following paragraph:

15. All concrete slabs shall be structurally adequate. Such slabs shall have a minimum compressive strength of 3000 psi., with the reinforcement and thickness at least that as shown in the test.

4. In the assemblies listed under the heading WALLS AND INTERIOR PARTITIONS, NONCOMBUSTIBLE, the following requirements are added to the Detailed Description for (LOAD BEARING) assemblies:

WP 1204, WP 1206, WP 1635, WP 1714 and WP 1716 under the GA and Company Codes:

Steel Studs.—Steel studs shall be a minimum of 3 1/2 inches wide and a minimum galvanized steel or 18GA (.0478) or heavier, primed steel, cold-formed, and shall comply with Reference Standard RS 10–6 (Specification for the Design of Cold-Formed Steel Structural members by AISI, as modified). Lateral supporting members and all details enhancing the structural integrity of the wall assembly shall be as specified by the steel stud designer, and shall meet the applicable requirements of the Code.

5. In the assemblies listed under METAL CLAD EXTERIOR WALLS, assemblies WP 9010, WP 9060, WP 9225, WP 9325, under the GA File No. heading, are deleted in its entirety.

6. Insert the following heading after the paragraph on USE OF PLENUM SPACE in the section on FLOOR-CEILINGS:

SUSPENSION SYSTEMS

Suspended ceilings contained herein shall comply with the requirements of Reference Standard RS 5–16.

7. In the assemblies listed under FLOOR-CEILING ASSEMBLIES, NON-COMBUSTIBLE, assembly FC 4120, under the GA File No. heading, is deleted in its entirety.

8. In the assemblies listed under FLOOR-CEILING ASSEMBLIES, WOOD-FRAMED, assembly FC 5105, under the GA File No. heading, is deleted in their entirety.

9. In the assemblies listed under BEAMS, GIRDERS, AND TRUSSES, assemblies BM 3310, BM 4410 and BM 4420, under the GA File No. heading, are deleted in their entirety.

10. The following assemblies which were listed in the Gypsum Association Fire Resistance Manual, Eleventh Edition, but do not appear in the Twelfth Edition, may continue to be used:

WP 1016 WP 1725 WP 1260 WP 7083 WP 1300 WP 7086 FC 5010 FC 5430 FC 5108

RS 5-1C. MISCELLANEOUS TEST REPORTS FOR LOAD-BEARING WALL ASSEMBLIES NON-COMBUSTIBLE: ONE, ONE AND ONE-HALF, and TWO-HOUR FIRE RATINGS

Open this section

This section has 4 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 5-1C at American Legal Publishing.

AISI FT–901–1981—Fire Resistance of Load-Bearing Steel Stud Walls with Gypsum Wallboard Protection with or without Cavity Insulation.

MODIFICATIONS: The provisions of AISI FT–901–1981, are modified as follows:

1. Delete all Fire Resistive Assemblies with 45 minute ratings.

2. Substitute the following for paragraph 2:

Steel Studs—Corrosion-Protected steel studs, min. 3 1/2 inches wide, min. No. 18 GSG (0.047 inch thick) galvanized steel or No. 18 MSG (0.043 inch thick) primed steel, cold-formed, shall be designed in accordance with Reference Standard RS 10–6 (Specification for the Design of Cold-Formed Steel Structural members by AISI, as modified). All design details enhancing the structural integrity of the wall assembly including the axial design load of the studs, shall be as specified by the steel stud designer and/or the producer, and shall meet all applicable requirements of the code. The maximum stud spacing of wall assemblies shall not exceed 24 inches. Studs shall be attached to floor and ceiling tracks with 1/2 inch long Type S–12 pan head, self-drilling, self-tapping steel screws on both sides of the studs, or welded in accordance with RS 10–6.

3. Substitute the following for paragraph 3:

Lateral Supporting Members (not shown)—Lateral support or bracing shall be provided in accordance with Reference Standard RS 10–6 independent sheathing.

4. Substitute the following for paragraph 4:

Wallboard, Gypsum—Gypsum wallboard shall conform to ASTM C 36 Type X and be identified as such. The wallboard shall be applied vertically with joints between layers staggered. Outer layer of three-layer construction may be applied horizontally. The thickness and number of layers and percent of design load for the 1 hour, 1 1/2 hour and 2 hour ratings shall be as specified in the table below.

5. Substitute the following for paragraph 7:

Batts and Blankets—All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Materials and Equipment Acceptance Division of the Department of Buildings for the intended use.

UL FIRE RESISTANCE DIRECTORY

Design U 425

Interior Walls—Wallboard Protection Both Sides of Wall

Rating Number of Layers and Thickness of Boards in Each Layer Percent of Design Load 1 hr. 1 layer, 5/8 in. thick 100 1 1/2 hr. 2 layers, 1/2 in. thick 100 2 hr. 2 layers, 5/8 in. thick or 80 *3 layers, 1/2 in. thick 100

* Ratings applicable to assemblies serving as exterior walls where Classified fire resistive gypsum sheathing type wallboard is substituted on the exterior face.

Exterior Walls—Wallboard Protection on Interior Side of Wall

Rating Number of Layers and Thickness of Boards in Each Layer Percent of Design Load 1 hr. 2 layers, 1/2 in. thick 100 1 1/2 hr. 2 layers, 5/8 in. thick 100 2 hr. 3 layers, 1/2 in. thick 100

1. Steel Floor and Ceiling Tracks—Top and bottom tracks of wall assemblies shall consist of steel members, min. No. 20 GSG (0.036 in. thick) galv. steel or No. 20 MSG (0.033 in.) thick primed steel, that provide a sound structural connection between steel studs and to adjacent assemblies such as a floor, ceiling and/or other walls. Attached to floor and ceiling, assemblies with steel fasteners spaced not greater than 24 in.

6. Fasteners—Screws used to attach wallboard to studs: self-tapping bugle head sheet steel type, spaced 12 in. o.c. First layer Type S-12 by 1 in. long; second layer Type S-12 by 1 1/2 in. long; third layer Type S-12 by 1 7/8 in. long.

8. Joint Tape and Compound—Vinyl or casein, dry or premixed joint compound applied in two coats to joints and screwheads of outer layer. Perforated paper tape, 2 in. wide, embedded in first layer of compound over all joints of outer layer.

COMBUSTIBLE: ONE-HOUR FIRE RATINGS:

NFoPA Report No. WHI–690–003

Report of Testing on a Load-Bearing Wood Stud Partition—Dated: October 19, 1981

Wall is constructed using 2 in. x 4 in. (nominal) wood studs spaced 16 in. on center. Fire exposed (interior) side is covered with 5/8 in. Type X Gypsum Wallboard applied vertically and fastened with 6d box nails on 7 in. centers. Unexposed side (exterior) is faced with a layer of 1/2 in. thick Fiberboard Sheathing (0.835 psf) applied vertically and fastened with 1 1/2 in. roofing nails on 3 in. centers at edges and 6 in. centers at intermediate supports. Hardboard Shiplap Edge Panel Siding, 3/8 in. thick (1.84 psf) is applied vertically over the Fiberboard Sheathing and fastened with 8d nails on 4 in. centers at edges and 8 in. centers at intermediate supports. The Cavity Spaces (stud spaces) are filled with Mineral Wool Batts having a density of 2.14 lbs./cu. ft. (Mineral wool may be rock wool or slag wool of equivalent density.) All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Material and Equipment Acceptance Division of the Department of Buildings for the intended use. The maximum load permissible on the studs in this assembly shall be 2000 lbs. each.

NFoPA Report No. WHI–694–020

Report of Testing on a Load-Bearing Wood Stud Partition—Dated: October 9, 1981

Wall is constructed using 2 in. x 4 in. (nominal) wood studs spaced 16 in. on centers. Fire exposed side (interior) is covered with 5/8 in. Type X Gypsum Wallboard applied vertically and fastened with 6d box nails on 7 in. centers. Unexposed side (exterior) is faced with 3/8 in. thick 5/8 in. between grooves) exterior grade plywood panels applied vertically and fastened with 8d nails on 6 in. centers around edges and 12 in. centers at intermediate supports. The Cavity (stud) Spaces are filled with Mineral Wool Batts having a density of 2 lbs./cu. ft. (Mineral wool may be rock wool or slag wool of equivalent density.) All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Material and Equipment Acceptance Division of the Department of Buildings for the intended use.

The maximum load permissible on the studs in this assembly shall be 2000 lbs. each.

RS 5-1D. MISCELLANEOUS TEST REPORTS FOR LOAD BEARING STEEL COLUMN ASSEMBLIES NONCOMBUSTIBLE: DESIGN OF ONE, ONE AND ONE-HALF, TWO, THREE AND FOUR HOUR FIRE RATINGS OF PROTECTED COLUMNS

Open this section

AISI FT–900–0480–1980 Designing Fire Protection for Steel Columns, third edition.

MODIFICATIONS: The provisions of AISI FT–900–0480–1980 are modified as follows:

1. In Part I—Fire Resistance Ratings for Columns Protected with Gypsum Wallboard values determined by formula shall govern when interpolating graphical or tabular results.

2. In Part I—Fire Resistance Ratings for Columns Protected with Gypsum Wallboard, all reference to approved gypsum wallboard shall infer material conforming to ASTM C 36 Type X and be identified as such. All gypsum wallboard used in fire resistive steel column assemblies designed in accordance with this Reference Standard shall be installed in accordance with one of the methods recommended in this reference standard.

3. Constants C1 and C2 shall be applicable only to the materials identified in Section C of Part II—Calculating Fire Resistance Ratings for Columns Protected with Spray-Applied Materials. Constants for other spray-applied fire proofing materials shall be determined by ASTM E 119 fire tests. The tests and their evaluation shall be submitted to the Material and Acceptance Division (MEA) for acceptance.

4. The formulas for determining thickness of fire protection materials shall not be used with columns or built-up sections that have W/D ratios larger than those of the W14x233 shape. Fire protection thickness may be applied to columns larger than the W14x233 provided the thickness of fire protection materials to be applied to columns are the same as those required for the W14x233 column.

5. In absence of substantiating fire endurance test results, ducts, conduit, piping and similar mechanical, electrical and plumbing installations shall not be embedded in any required fire protection materials.

6. The formulas in Part II for calculating the fire-resistance ratings of columns protected with spray-applied material may not be used for tubular or round columns of eight (8) inches or less in width or diameter.

RS 5-1E. MISCELLANEOUS TEST REPORTS FOR LOAD BEARING STEEL BEAM/GIRDER ASSEMBLIES NONCOMBUSTIBLE ASSEMBLIES: RESTRAINED AND UNRESTRAINED

Open this section

AISI FT–902–0285–1984—Designing Fire Protection for Steel Beams.

MODIFICATIONS: The provisions of AISI FT–902–0285–1984 are modified as follows:

1. In Part V Beam Substitutions, Section 2, Beam Substitution Equation, Subscript 2 and its meaning is revised to read as follows:

Subscript 2 = refers to the beam and protection thickness specified in a fire resistive assembly approved by the Board of Standards and Appeals or accepted by the Materials and Equipment Acceptance Division.

Subsection 3) is revised to read as follows:

3) the Unrestrained Beam Rating in the approved or accepted assembly is not less than one-hour.

2. The procedures illustrated in Parts V and VI for UL listed assemblies may be applied to similar approved and accepted assemblies.

3. Beam/Girder substitutions shall only be made for similar approved or accepted fire resistive materials for similar assemblies.

4. Fire tested composite designed beams/girders shall not be substituted into assemblies that specify noncomposite beams. However, fire tested noncomposite designed beams/girders may be substituted into assemblies utilizing composite beams/girders.

5. Ducts, conduit, piping and similar mechanical, electrical and plumbing installations shall not be embedded in required fire protection materials without substantiating fire endurance test results.

RS 5-1F. METHODS OF ANALYTICAL DETERMINATION OF FIRE RESISTANCE OF LOAD BEARING STEEL TRUSS ASSEMBLIES NONCOMBUSTIBLE ASSEMBLIES: RESTRAINED AND UNRESTRAINED

Open this section

AISI FT–227–1281–1981—Designing Fire Protection for Steel Trusses.

MODIFICATIONS: The provisions of AISI FT–227–1281–1981 are modified as follows:

1. Analytically determined fire protection systems for trusses shall be based on fire resistive assemblies approved by the Board of Standards and Appeals or accepted by the Materials and Equipment Acceptance Division.

2. Methods of determining fire resistance of trusses utilizing the column formulas contained in AISI FT–900–0480 shall comply with the requirements and modifications specified in Reference Standard RS 5–1D.

RS 5-2

Open this section

ASTM E–119—a) Standard methods Fire Test of Building Construction or Materials—1988 or

b) a combination of small scale and/or half scale tests and engineering evaluation acceptable to the commissioner in conjunction with evaluation of full scale test conforming with ASTM E 119 for a variety of assemblies or combination of materials, or

c) a combination of small-scale, half-scale or full size tests representative of the actual fire exposure of the occupancy and engineering evaluations all acceptable to the commissioner. In either (a), (b), or

d) the materials or combinations of materials constructed shall be in accordance with the specifications of the materials used.

RS 5-3

Open this section

AWPA C20–1988—Structural Lumber-Fire Retardant Treatment by Pressure Processes.

RS 5-4

Open this section

AWPA C27–1988—Plywood Fire Retardant Treatment by Pressure Processes.

RS 5-5

Open this section

a) ASTM E 84–1987—Standard Method for Surface Burning Characteristics of Building Materials, or

b) a combination of small scale tests and engineering evaluations acceptable to the commissioner in conjunction with evaluation of full scale tests conforming with ASTM E 84 for a variety of assemblies or combinations of materials. In the case of fire-retardant treated wood, the small scale tests utilized in conjunction with the full scale tests shall conform to either ANSI/ASTM E 69–1980—Standard Test Method for Combustible Properties of Treated Wood by Fire-Tube Apparatus or ANSI/ASTM E 160–1980—Standard Test Method for Combustible Properties of Treated Wood by the Crib Test.

RS 5-6

Open this section

ANSI/ASTM E 152–1981a—Standard Methods of Fire Tests of Door Assemblies.

RS 5-7

Open this section

ANSI/ASTM E 163–1984—Standard Method of Fire Tests of Window Assemblies.

RS 5-8

Open this section

ANFiPA 80–1986—Standard for Fire Doors and Windows.

RS 5-9

Open this section

Roof Covering Classifications

Description Maximum Incline (In. to Ft.) Class A Class B Class C Brick (1) Brick, 2 1/4 in. thick. (2) Reinforced portland cement, 1 in. thick. Concrete (3) Concrete or clay floor or deck tile, 1 in. thick. Tile (4) Flat or French-type clay or concrete tile, 3/8 in. thick with 1 1/2 in. or more end lap and head lock, spacing body of tile 1/2 in. or more above roof sheathing, with underlay of one layer of Type 15 asphalt-saturated asbestos felt or one layer of Type 30 or two layers of Type 15 asphalt-saturated rag felt. (5) Clay or concrete roof tile, Spanish or Mission pattern, 7/16 in. thick, 3 in. end lap, same underlay as above. (6) Slate, 3/16 in. thick, laid American method. Metal Roofing 12 (6) Sheet roofing of 16 oz. copper or of 30-gauge steel or iron protected against corrosion. Limited to non-combustible roof decks or noncombustible roof supports when no separate roof deck is provided. Sheet roofing of 16 oz. copper or of 30-gauge steel or iron tile, protected against corrosion; or shingle-pattern roofings with underlay of one layer of Type 15 saturated asbestos-felt, or one layer of Type 30 or two layers of Type 15 asphalt-saturated rag felt. Sheet roofing of 16 oz. copper or of 30-gauge steel or iron tile, protected against corrosion; or shingle-pattern roofings, either without underlay or with underlay of rosin-sized paper.Zinc sheets or shingle roofings with an underlay of one layer of Type 30 or two layers of Type 15 asphalt-saturated rag-felt or one layer of 14 lbs. unsaturated or one layer of Type 15 asphalt-saturated asbestos felt. Cement-Asbestos Shingles Exceeding 4 (6) Laid to provide two or more thicknesses over one layer of Type 15 asphalt-saturated asbestos felt. Laid to provide one or more thicknesses over one layer of Type 15 asphalt-saturated asbestos felt.

RS 5-10

Open this section

a) ANSI/ASTM E 108–1987—Standard Method of Fire Tests of Roof Coverings, or

b) a combination of small scale and/or half scale tests and engineering evaluations acceptable to the commissioner in conjunction with evaluations of full scale tests conforming with ASTM E 108 for a variety of assemblies or combinations of materials.

RS 5-11

Open this section

NFiPA 204M–1985—Guide for Smoke and Heat Venting.

RS 5-12

Open this section

ANSI/ASTM D 635–1981—Standard Test for Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastics in a Horizontal Position.

RS 5-13

Open this section

ANSI/ASTM D 568–1977—Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Flexible Plastics in a Vertical Position.

RS 5-14

Open this section

ANSI/ASTM D 374–1979—Standard Test Methods for Thickness of Solid Electrical Insulation.

RS 5-15

Open this section

Minimum Covering of Prestressing Steel for Various Fire Resistance Ratings

Type of Unit Cross-Sectional Area (3) Sq. In. Rating 1 Hour 2 Hour 3 Hour 4 Hour Prestressed Girders, Beams and Joists (1) (2) 40 to 150 150 to 300 over 300 2 in. 1 1/2 in. 1 1/2 in. 2 1/2 in. 2 in. 3 in. (4) 4 in. (4) Prestressed Slabs, Solid or Cored (1) (2) — 1 in. 1 1/2 in. 2 in. 2 1/2 in.

(1) Members with less covering shall be acceptable where tests show that adequate protection is provided for the required fire resistance rating.

(2) Slab thickness to resist transmission of heat shall be as for non-prestressed concrete. Unbonded tendon anchorage devices shall have 50 per cent greater covering than in the above table.

(3) In computing the cross-sectional area for joists, the area of the flange shall be added to the area of the stem, and the total width of the flange as used shall not exceed three times the average width of the stem.

(4) Adequate provisions against spalling shall be provided by means of a light reinforcement. Reinforcement spacing shall not exceed the depth of the element and shall have a 1-inch concrete covering.

SECTION 1 – GENERAL (REFERENCE STANDARD RS 5–16 ACOUSTICAL TILE AND LAY-IN PANEL CEILING SUSPENSION SYSTEMS)

Open this section

1.1 SCOPE.—This standard covers ceiling suspension systems used primarily to support acoustical tile or acoustical lay-in panels weighing less than four pounds per square foot, not contributing to the fire-resistance rating of a floor or roof assembly and not used for meeting the noise control requirements of the building code.

SECTION 2 – DEFINITIONS (REFERENCE STANDARD RS 5–16 ACOUSTICAL TILE AND LAY-IN PANEL CEILING SUSPENSION SYSTEMS)

Open this section

This section has 1 picture (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read SECTION 2 – DEFINITIONS at American Legal Publishing.

2.1 Where the following terms appear in this standard, they shall have the meaning herein indicated:

Backing board—The term "backing board" shall mean a flat sheet of gypsum to which acoustical tile is attached using adhesive, screws, staples or other suitable means. (Fig. 1C)

Carrying channel—The term "carrying channel" shall mean the three sided or "[" shaped metal sections which support the entire structural grid net work (Figs. 1A, B, C). The carrying channels are suspended by hangers from the existing structure and main runners are then attached to the channels.

Ceiling suspension system—The term "ceiling suspension system" shall mean the entire network or grid of structural components which provides support for acoustical ceiling tile, acoustical ceiling panels, lighting fixtures, and air diffusers.

Cross runner—The term "cross runner" shall mean the secondary or cross beams of a mechanical ceiling suspension (Fig. 1A). The cross runners normally support only the acoustical tile. In some forms of suspension systems, however, the cross runners also provide support for other cross runners.

Hanger—The term "hanger" shall mean the member employed to suspend the acoustical ceiling from the existing structure (wood joists, steel bar joists, steel beams, concrete slabs, etc.) (Figs. 1A, B, C).

Main runner—The term "main runner" shall mean the primary or main beams of the type of ceiling suspension system in (Figs. 1A, B). The main runners provide direct support for cross runners, and they may support lighting fixtures and air diffusers. In addition, the acoustical tile may also be directly supported by the main runners.

Nailing bar—The term "nailing bar" or "furring bar" shall mean the continuous sheet metal strips to which a backing board is attached using either nails or screws (Fig. 1C).The nailing bars are installed perpendicular to and supported by the carrying channels.

Spline—The term "spline" shall mean a strip of sheet metal or fiber inserted in the kerfs of adjacent acoustical tile to form a concealed mechanical joint seal (Fig. 1B).

Wall molding—The term "wall molding" shall mean the edge angles or channels of a mechanical ceiling suspension system which are attached to a wall. (Figs. 1A, B) the wall molding provides support for acoustical tile, and cross runners which are located at the periphery of the ceiling.

SECTION 3 – DESIGN

Open this section

3.1 The provisions of the building code for stresses shall apply.

3.2 The hangers shall be spaced at 4'–6" or less on centers. Each hanger shall be capable of carrying all loads suspended therefrom plus an additional 200 pounds located at midspan. The midspan deflection as attested in accordance with the test method described in Section 6 of this standard or as calculated shall not exceed 1/360 of the span. The connections of the carrying channel to the hangers shall be adequate for the load supported by the carrying channel plus 200 pounds.

3.4 The main runner or nailing bar shall be capable of carrying all loads suspended therefrom. The midspan deflection as tested in accordance with the test method described in Section 6 of this standard or as calculated shall not exceed 1/360 of the span. Each connection of the main runner or nailing bar to the carrying channels shall be adequate for the load supported by the main runner plus two (200) pounds.

3.5 Cross runners shall be capable of carrying all loads suspended therefrom. The midspan deflection as tested in accordance with the test method described in Section 6 of this standard or as calculated shall not exceed 1/360 of the span.

3.6 Splines shall not be considered as providing nor shall be used for providing, structural support for the ceiling material.

3.7 All connection devices other than bolts shall be approved by the Board of Standards and Appeals. However they may be accepted under the code test method when test results indicating a factor of safety of four are filed in accordance with the provisions of section 27-131 of the building code.

SECTION 4 – COATINGS

Open this section

4.1 PROTECTIVE COATINGS.—Component materials which oxidize or corrode when exposed to normal use environments shall be provided with protective coatings.

4.1.1 Sheet steel—Components fabricated from sheet steel shall be given an electro-galvanized, hot dipped galvanized cadmium coating, or zinc coating.

4.1.2 Aluminum alloy—Components fabricated from aluminum alloys shall be anodized when exposed to a corrosive atmosphere.

SECTION 5 – INSTALLATION

Open this section

This section has 5 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read SECTION 5 – INSTALLATION at American Legal Publishing.

5.1 INSTALLATION OF COMPONENTS.—The components of acoustical ceiling suspension systems shall be installed in accordance with the following requirements and Figures 2A and 2B.

5.1.1 HANGERS

5.1.1.1 Building of construction group I—For requirements see Figs. 2A and 2B.

5.1.1.2 Buildings of construction group II—Every other hanger supported from wood members shall be attached by two 1/4" diameter through bolts or clinched nails. The remaining hangers shall be attached as described above or by two 1/4" diameter barbed anchor nails 2 1/4" long with oval heads. All bolts and nails shall be at least 2 in. above the bottom of the wood members.

5.1.1.3 Spacing—Hangers for carrying channels shall be spaced at most 4'–6" on centers.

5.1.1.4 Minimum sizes and quality—Hangers for suspending carrying channels shall be a minimum of 1/8" diameter galvanized steel rods or flat bars at least 1" x 1/8".

5.1.1.5 Use of existing hangers—Existing hangers may not be used unless they comply, or are made to comply, with all the above provisions relating to hangers.

5.1.2 CARRYING CHANNELS

5.1.2.1 Leveling Requirements—Carrying channels shall be installed so that they are level within 1/8 in. in 12 ft. leveling shall be performed with the supporting hangers taut. Local kinks or bends shall not be made in hangers as a means of leveling the carrying channels.

5.1.2.2 Attachment to hangers—Carrying channels shall be attached to the hangers in a manner that will prevent any vertical movement or rotation.

5.1.3 MAIN RUNNERS

5.1.3.1 Leveling requirements—Main runners shall be installed so that they are all level within 1/8" in 12 ft. Leveling shall be performed with the main runner in firm contact with the carrying channel.

5.1.3.2 Attachment to carrying channels—Main runners shall be attached to the carrying channels in a manner that will prevent any vertical movement or rotation.

NEW SUSPENDED CEILINGS BELOW EXISTING SUSPENDED CEILINGS

5.2.1 Buildings of construction group I—In buildings of construction group I not more than one existing suspended ceiling may be retained above the new suspended ceiling. All other existing suspended ceilings must be removed. Where an existing ceiling is retained the new main runners shall be supported directly from the carrying channels adjacent to the hangers.

5.2.2 Buildings of construction group II—In buildings of construction groups II, all existing suspended ceilings shall be removed prior to installation of new suspended ceiling.

5.2.3 Existing hangers—Existing hangers shall not be used for new suspended ceiling unless found to be in sound structural condition and comply with all the requirements of this standard relating to hangers.

5.3 CEILING FIXTURES

5.3.1 General—Fixtures installed in acoustical tile or lay-in panel ceilings shall be mounted in a manner that will not compromise ceiling performance. Figures 3A, 3B and 3C are to be used as a guide.

5.3.2 Maximum fixture weights–Fixtures exceeding 80 lbs. in weight shall be supported independent of ceiling suspension system. Fixtures weighing 80 lbs. or less may be supported from the carrying channels. Fixtures weighing 50 lbs. or less may be supported from the main runners.

5.3.3 Eccentric loading—Fixtures shall be installed so that the main runners or carrying channels will be eccentrically loaded unless suitable accessory devices (Figs. 3 A, B, C) are employed and the main runner and/or carrying channel design provides for the torsional stresses.

5.3.4 Plans The plans shall show the necessary details of the acoustical ceiling to satisfactorily identify the number, size, spacing, location, weights, and types of fixtures and means employed to comply with this section.

SECTION 6 – TEST METHOD FOR DETERMINING DEFLECTION

Open this section

This section has 2 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read SECTION 6 – TEST METHOD FOR DETERMINING DEFLECTION at American Legal Publishing.

6.1 INTRODUCTION.—The test method outlined provides the means by which data can be secured for characterizing the structural performance of individual suspension systems. The method consists of placing structural members as beams on simple supports, and subjecting them to simulated uniformly distributed loads over their length. The loading is incrementally imposed and the performance of the structural member is obtained from observing the resulting beam deflections.

6.2 SCOPE.—The test method shall be used for evaluating the load deflection performance of structural members of all acoustical tile and lay-in panel suspension systems. A simple experimental facility is described which can be adjusted as required to permit testing of structural members of different sizes, having various section configurations, and on different appropriate span lengths.

Some suspension systems incorporate a locking assembly system which enhances performance by providing some continuity or load transfer capability between adjacent sections of the ceiling grid. This test method does not provide the means for making a complete evaluation of continuous beam systems, nor for assessing the continuity contribution to overall system performance. However, the method can be used for evaluating primary structural members in conjunction with secondary members which interlock, as well as with those of noninterlocking type.

6.3 LOADING FACILITY.—The loading of structural members shall be performed in a manner which closely simulates their use in suspension systems. Span distances, spacing between secondary supports, etc., shall all be typical of ceiling grid designs in which the structural member is used.

6.3.1 Support frame—A rectangular support frame having the essential features of the unit described below shall be provided.

6.3.1.1 The frame (Fig. 4) shall have the capability for length adjustment to permit testing of structural members on clear spans for a maximum of 8 ft. to a minimum of 3 ft. It shall have the capability for overall width adjustment with a maximum length of 4 ft. and a maximum length of 1 ft.

6.3.1.2 The support frame shall have sufficient stiffness so that no significant deflection occurs within the frame during load tests of suspension system structural members.

6.3.1.3 The support frame may either be ceiling mounted or floor supported.

6.3.2 Test loading—The main runner weight shall not be used for evaluating load-deflection performance. One-half the weight of the cross runners shall be included as part of the test load.

6.3.2.1 Individual test weights appropriate for evaluating the structural member shall be provided. Loads weighing up to 1 lb. shall be provided so that their actual weight is within 0.01 lb. of their marked weight. Weights over 1 lb. shall be within 1 percent of their marked weight. Loading weights of the sizes required can be conveniently provided by weighing lead shot into cloth bags and tying them closed.

6.3.2.2 A sufficient number of weights of suitable mass shall be provided to permit evaluation of the structural member through its elastic range by loading in approximately ten equal load increments. When elastic performance of the member under test is exceeded, loading shall continue using a suitably reduced load increment until significant sectioning yielding has been produced.

6.3.2.3 A complete load increment shall be applied simulating a uniformly distributed load imposed over the entire section length before measuring the deflection of the structural member.

6.3.2.4 Provision shall be made for imposing test loads on the structural member in a symmetrical manner.

6.3.3 Deflection measurements—The deflection of structural members shall be observed after application of each full load increment during the entire test.

6.3.3.1 The deflection of structural members being tested shall be measured with dial indicators capable of direct reading to 0.001 in.

6.3.3.2 Dial indicators shall be mounted from a separate gauge from (Fig. 4) having three points of support. The gauge frame shall be supported from the test loading frame and be properly positioned to locate the dial stems vertically over the structural member being tested.

6.3.3.3 The dial indicators used shall have sufficient travel capability to permit the deflection performance of the structural members to be observed during the entire test without requiring resetting.

6.4 STRUCTURAL MEMBERS.—The manufacturer, installer, or architect or engineer, shall determine the load-deflection performance.

6.4.1 The structural members tested shall be identical to the sections used in the final system design. All cutouts, slots, etc., as exist in the system component shall be included in the sections evaluated.

6.4.2 Allowable mill variations of sheet stock thickness have a significant effect on section stiffness and load carrying ability. Consequently, load-deflection studies of structural members shall utilize sections fabricated in accordance with system manufacturers' published metal thicknesses and dimensions.

6.5 PROCEDURE.—The procedures used for evaluating performance of suspension system structural members shall utilize the general principle of following actual field installation practice wherever possible. As an example of the general procedure to be followed, the setup and testing of a primary structural member is described below.

6.5.1 Experimental setup—In preparation for testing, the length and width of the support frame shall be adjusted to the typical grid dimensions that are established as appropriate to the evaluation of the structural member. The primary structural member shall be installed along the longitudinal centerline of the frame and supported at its ends as an essentially simply supported beam (Fig. 4). Where secondary members are used, they shall be installed normal to the direction of the primary structural member and at the midpoint and quarterpoint locations along the test span length. One end of such secondary members shall be supported from the side of the test frame and at the other from the flange of the primary structural member (Fig.4). Clearances between the ends of the secondary structural member in the test setup shall be typical of that which exists in the actual ceiling grid.

Where interlocking secondary structural members are used, they shall be assembled into the central primary structural member being tested in customary fashion and using conventional center distance spacing. The other end of the secondary member shall be simply supported from the perimeter support frame. No interlocking of the secondary member and the perimeter support frame shall be permitted.

6.5.2 Section loading—With the structural member to be evaluated installed in the support frame, the gauge frame shall be positioned to mount the vertical displacement deflection dials directly over the test section at the midspan and quarterspan locations at which time dials are positioned to read zero (Fig. 4). The test loads shall be applied to the structural member in a manner representative of that which exists in service. For test purposes simple wire hangers shall be provided to suitably introduce the load to the section. Extending from such hangers, attachment wires, cords or lightweight chains shall be provided to permit the preweighed incremental test weights to be added as required. The weight of hangers, wires, pans, etc. shall be incorporated as part of the test load.

The test weights, simulating the weight of ceiling tile of panel, shall be applied to the structural member starting 6 in. from the end supports, and at 1 ft. intervals thereafter, always proceeding from the ends toward the center of the span in applying load. After the first uniformly distributed load increment has been applied, the midspan and quarter-span deflection of the structural member shall be measured and recorded. Loading of the structural member shall be continued in the same manner, applying successive increments of uniformly distributed load and observing deflections after each increment. Loading shall be continued until it is apparent that the test section has yielded.

The load deflection performance of secondary structural members of acoustical tile and lay-in panel ceiling systems shall be similarly determined. The units shall be set up and tested in a manner appropriate to their use in actual grid systems.

6.6 EXPERIMENTAL DATA.—A test log shall be prepared to record all pertinent data regarding the structural member being evaluated and the principal accessory items used. Such information as the following shall be provided:

Manufacturer's name.

Suspension system identification.

Test section identification.

Description of section: measure overall height and thickness of basic stock, type of material, section weight, etc.

Test span length.

Spacing of lateral supports.

Identification of accessory items and how used.

Sketch of experimental setup, giving dimensions of grid, dial gauge locations, load spacing, etc.

Record of the incrementally applied uniformly distributed loads and the resultant midspan and quarter-span deflection and the resultant midspan and quarter-span deflections measurements for each loading.

6.7 SECTION PERFORMANCE.—The performance of structural members of suspension systems shall be represented by individual load-deflection plots obtained from tests performed at each different span length used in service.

6.7.2 The results of replicate tests of three individual sections each tested on the same span length, shall be plotted and averaged to obtain a characteristic load-deflection curve for the structural member.

6.7.3 The average load-deflection curve shall be used to establish the maximum uniformly distributed load which the structural member can successfully sustain prior to reaching the deflection limit of 3/360th of the span length in inches. (Fig. 5)

6.7.4 The load-deflection curve shall be used to establish the maximum loading intensity beyond which the structural member begins to yield.

6.8 SUSPENSION SYSTEM PERFORMANCE.—Published performance data for individual suspension systems shall be developed by the manufacturer upon the basis of results obtained from load-deflection tests of its principal structural members. Where a ceiling design incorporates a number of components, each of which experiences some deflection as used in the system, the additive nature of these displacements shall be recognized in setting an allowable system deflection criteria.