NYC Administrative Code RS 5-1E MISCELLANEOUS TEST REPORTS FOR LOAD BEARING STEEL BEAM/GIRDER ASSEMBLIES NONCOMBUSTIBLE ASSEMBLIES: RESTRAINED AND UNRESTRAINED

AISI FT–902–0285–1984—Designing Fire Protection for Steel Beams.

MODIFICATIONS: The provisions of AISI FT–902–0285–1984 are modified as follows:

1. In Part V Beam Substitutions, Section 2, Beam Substitution Equation, Subscript 2 and its meaning is revised to read as follows:

Subscript 2 = refers to the beam and protection thickness specified in a fire resistive assembly approved by the Board of Standards and Appeals or accepted by the Materials and Equipment Acceptance Division.

Subsection 3) is revised to read as follows:

3) the Unrestrained Beam Rating in the approved or accepted assembly is not less than one-hour.

2. The procedures illustrated in Parts V and VI for UL listed assemblies may be applied to similar approved and accepted assemblies.

3. Beam/Girder substitutions shall only be made for similar approved or accepted fire resistive materials for similar assemblies.

4. Fire tested composite designed beams/girders shall not be substituted into assemblies that specify noncomposite beams. However, fire tested noncomposite designed beams/girders may be substituted into assemblies utilizing composite beams/girders.

5. Ducts, conduit, piping and similar mechanical, electrical and plumbing installations shall not be embedded in required fire protection materials without substantiating fire endurance test results.