NYC Administrative Code RS 5-1D MISCELLANEOUS TEST REPORTS FOR LOAD BEARING STEEL COLUMN ASSEMBLIES NONCOMBUSTIBLE: DESIGN OF ONE, ONE AND ONE-HALF, TWO, THREE AND FOUR HOUR FIRE RATINGS OF PROTECTED COLUMNS

AISI FT–900–0480–1980 Designing Fire Protection for Steel Columns, third edition.

MODIFICATIONS: The provisions of AISI FT–900–0480–1980 are modified as follows:

1. In Part I—Fire Resistance Ratings for Columns Protected with Gypsum Wallboard values determined by formula shall govern when interpolating graphical or tabular results.

2. In Part I—Fire Resistance Ratings for Columns Protected with Gypsum Wallboard, all reference to approved gypsum wallboard shall infer material conforming to ASTM C 36 Type X and be identified as such. All gypsum wallboard used in fire resistive steel column assemblies designed in accordance with this Reference Standard shall be installed in accordance with one of the methods recommended in this reference standard.

3. Constants C1 and C2 shall be applicable only to the materials identified in Section C of Part II—Calculating Fire Resistance Ratings for Columns Protected with Spray-Applied Materials. Constants for other spray-applied fire proofing materials shall be determined by ASTM E 119 fire tests. The tests and their evaluation shall be submitted to the Material and Acceptance Division (MEA) for acceptance.

4. The formulas for determining thickness of fire protection materials shall not be used with columns or built-up sections that have W/D ratios larger than those of the W14x233 shape. Fire protection thickness may be applied to columns larger than the W14x233 provided the thickness of fire protection materials to be applied to columns are the same as those required for the W14x233 column.

5. In absence of substantiating fire endurance test results, ducts, conduit, piping and similar mechanical, electrical and plumbing installations shall not be embedded in any required fire protection materials.

6. The formulas in Part II for calculating the fire-resistance ratings of columns protected with spray-applied material may not be used for tubular or round columns of eight (8) inches or less in width or diameter.