NYC Administrative Code RS 5-1C MISCELLANEOUS TEST REPORTS FOR LOAD-BEARING WALL ASSEMBLIES NON-COMBUSTIBLE: ONE, ONE AND ONE-HALF, and TWO-HOUR FIRE RATINGS

This section has 4 pictures (figures, equations, or tables drawn as images) that BetaNYC's copy does not show. Read RS 5-1C at American Legal Publishing.

AISI FT–901–1981—Fire Resistance of Load-Bearing Steel Stud Walls with Gypsum Wallboard Protection with or without Cavity Insulation.

MODIFICATIONS: The provisions of AISI FT–901–1981, are modified as follows:

1. Delete all Fire Resistive Assemblies with 45 minute ratings.

2. Substitute the following for paragraph 2:

Steel Studs—Corrosion-Protected steel studs, min. 3 1/2 inches wide, min. No. 18 GSG (0.047 inch thick) galvanized steel or No. 18 MSG (0.043 inch thick) primed steel, cold-formed, shall be designed in accordance with Reference Standard RS 10–6 (Specification for the Design of Cold-Formed Steel Structural members by AISI, as modified). All design details enhancing the structural integrity of the wall assembly including the axial design load of the studs, shall be as specified by the steel stud designer and/or the producer, and shall meet all applicable requirements of the code. The maximum stud spacing of wall assemblies shall not exceed 24 inches. Studs shall be attached to floor and ceiling tracks with 1/2 inch long Type S–12 pan head, self-drilling, self-tapping steel screws on both sides of the studs, or welded in accordance with RS 10–6.

3. Substitute the following for paragraph 3:

Lateral Supporting Members (not shown)—Lateral support or bracing shall be provided in accordance with Reference Standard RS 10–6 independent sheathing.

4. Substitute the following for paragraph 4:

Wallboard, Gypsum—Gypsum wallboard shall conform to ASTM C 36 Type X and be identified as such. The wallboard shall be applied vertically with joints between layers staggered. Outer layer of three-layer construction may be applied horizontally. The thickness and number of layers and percent of design load for the 1 hour, 1 1/2 hour and 2 hour ratings shall be as specified in the table below.

5. Substitute the following for paragraph 7:

Batts and Blankets—All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Materials and Equipment Acceptance Division of the Department of Buildings for the intended use.

UL FIRE RESISTANCE DIRECTORY

Design U 425

Interior Walls—Wallboard Protection Both Sides of Wall

Rating Number of Layers and Thickness of Boards in Each Layer Percent of Design Load 1 hr. 1 layer, 5/8 in. thick 100 1 1/2 hr. 2 layers, 1/2 in. thick 100 2 hr. 2 layers, 5/8 in. thick or 80 *3 layers, 1/2 in. thick 100

* Ratings applicable to assemblies serving as exterior walls where Classified fire resistive gypsum sheathing type wallboard is substituted on the exterior face.

Exterior Walls—Wallboard Protection on Interior Side of Wall

Rating Number of Layers and Thickness of Boards in Each Layer Percent of Design Load 1 hr. 2 layers, 1/2 in. thick 100 1 1/2 hr. 2 layers, 5/8 in. thick 100 2 hr. 3 layers, 1/2 in. thick 100

1. Steel Floor and Ceiling Tracks—Top and bottom tracks of wall assemblies shall consist of steel members, min. No. 20 GSG (0.036 in. thick) galv. steel or No. 20 MSG (0.033 in.) thick primed steel, that provide a sound structural connection between steel studs and to adjacent assemblies such as a floor, ceiling and/or other walls. Attached to floor and ceiling, assemblies with steel fasteners spaced not greater than 24 in.

6. Fasteners—Screws used to attach wallboard to studs: self-tapping bugle head sheet steel type, spaced 12 in. o.c. First layer Type S-12 by 1 in. long; second layer Type S-12 by 1 1/2 in. long; third layer Type S-12 by 1 7/8 in. long.

8. Joint Tape and Compound—Vinyl or casein, dry or premixed joint compound applied in two coats to joints and screwheads of outer layer. Perforated paper tape, 2 in. wide, embedded in first layer of compound over all joints of outer layer.

COMBUSTIBLE: ONE-HOUR FIRE RATINGS:

NFoPA Report No. WHI–690–003

Report of Testing on a Load-Bearing Wood Stud Partition—Dated: October 19, 1981

Wall is constructed using 2 in. x 4 in. (nominal) wood studs spaced 16 in. on center. Fire exposed (interior) side is covered with 5/8 in. Type X Gypsum Wallboard applied vertically and fastened with 6d box nails on 7 in. centers. Unexposed side (exterior) is faced with a layer of 1/2 in. thick Fiberboard Sheathing (0.835 psf) applied vertically and fastened with 1 1/2 in. roofing nails on 3 in. centers at edges and 6 in. centers at intermediate supports. Hardboard Shiplap Edge Panel Siding, 3/8 in. thick (1.84 psf) is applied vertically over the Fiberboard Sheathing and fastened with 8d nails on 4 in. centers at edges and 8 in. centers at intermediate supports. The Cavity Spaces (stud spaces) are filled with Mineral Wool Batts having a density of 2.14 lbs./cu. ft. (Mineral wool may be rock wool or slag wool of equivalent density.) All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Material and Equipment Acceptance Division of the Department of Buildings for the intended use. The maximum load permissible on the studs in this assembly shall be 2000 lbs. each.

NFoPA Report No. WHI–694–020

Report of Testing on a Load-Bearing Wood Stud Partition—Dated: October 9, 1981

Wall is constructed using 2 in. x 4 in. (nominal) wood studs spaced 16 in. on centers. Fire exposed side (interior) is covered with 5/8 in. Type X Gypsum Wallboard applied vertically and fastened with 6d box nails on 7 in. centers. Unexposed side (exterior) is faced with 3/8 in. thick 5/8 in. between grooves) exterior grade plywood panels applied vertically and fastened with 8d nails on 6 in. centers around edges and 12 in. centers at intermediate supports. The Cavity (stud) Spaces are filled with Mineral Wool Batts having a density of 2 lbs./cu. ft. (Mineral wool may be rock wool or slag wool of equivalent density.) All insulation and noise control materials included in wall assemblies shall be Approved by the Board of Standards and Appeals or Accepted by the Material and Equipment Acceptance Division of the Department of Buildings for the intended use.

The maximum load permissible on the studs in this assembly shall be 2000 lbs. each.