Minimum Covering of Prestressing Steel for Various Fire Resistance Ratings

Type of Unit Cross-Sectional Area (3) Sq. In. Rating 1 Hour 2 Hour 3 Hour 4 Hour Prestressed Girders, Beams and Joists (1) (2) 40 to 150 150 to 300 over 300 2 in. 1 1/2 in. 1 1/2 in. 2 1/2 in. 2 in. 3 in. (4) 4 in. (4) Prestressed Slabs, Solid or Cored (1) (2) — 1 in. 1 1/2 in. 2 in. 2 1/2 in.

(1) Members with less covering shall be acceptable where tests show that adequate protection is provided for the required fire resistance rating.

(2) Slab thickness to resist transmission of heat shall be as for non-prestressed concrete. Unbonded tendon anchorage devices shall have 50 per cent greater covering than in the above table.

(3) In computing the cross-sectional area for joists, the area of the flange shall be added to the area of the stem, and the total width of the flange as used shall not exceed three times the average width of the stem.

(4) Adequate provisions against spalling shall be provided by means of a light reinforcement. Reinforcement spacing shall not exceed the depth of the element and shall have a 1-inch concrete covering.