NYC Administrative Code RS 14-15 MINIMUM INSTALLATION CLEARANCES FOR HEAT PRODUCTION EQUIPMENT
REFERENCE STANDARD RS 14–15 Minimum installation clearances for heat production equipment a
EQUIPMENT CLEARANCES (in.) Residential Type Equipment for Installation in Large Room b Above Top of Casing or Equipment From Top and Sides of Warm- Air Bonnet or Plenum From Front c From Back From Sides Boilers & Water Heaters— Steam boilers—15 psi Water boilers—250°F Water heaters—200°F (all water walled or jacketed) Automatic oil or comb. gas- oil Automatic gas Solid 6 6 6 — — — 24 18 48 6 6 6 6 6 6 Furnaces, Central— Gravity, upflow, downflow, horizontal and duct. Warm-air 250°F max. Automatic oil or comb. gas-oil Automatic gas Solid Electric 6 6 18 6 6 6 18 6 24 18 48 18 6 6 18 6 6 6 18 6 Furnaces, Floor— For mounting in combustible floor Automatic oil or comb. gas-oil 36 — 12 12 12 Heat Exchanger— Steam—15 psi max. Hot water—250°F max. Automatic gas 36 1 1 — 1 1 12 1 1 12 1 1 12 1 1 Room Heaters— Circulating type (vented or unvented) Radiant type (vented or unvented) Oil and solid Gas Oil and solid Gas Gas with double metal or ceramic back 36 36 36 36 36 — — — — — 24 24 36 36 36 12 12 36 18 12 12 12 36 18 18 Radiators— Steam or hot water Gas 36 — 6 6 6 Ranges— Firing Cooking Stoves (vented or unvented) Oil Gas Solid-clay-lined firepot Solid-unlined firepot 30 f 30 f 30 f 30 f — — — — — — — — 9 6 24 36 24 6 24 36 Electric 30 f — — 6 Clothes Dryers that conform to applicable standards Gas 6 — 24 6 Electric 6 — 24 0
EQUIPMENT CLEARANCES (in.) Commercial-Industrial Type Low Temperature Equipment (Any and all physical sizes except as noted) Above Top of Casing or Equipment d From Top and Sides of Warm- Air Bonnet or Plenum From Front From Back d From Sides d Boilers and Water Heaters— 100 cu. ft. or less (any psi steam) Any size (50 psi or less) All fuels All fuels 18 18 — — 48 48 18 18 18 18 Unit heaters— Floor mounted or suspended (any size) Steam or Hot Water— Oil or comb. gas-oil 1 6 — — — 24 1 18 1 18 Suspended (100 cu. ft. or less) Suspended (100 cu. ft. or less) Suspended (over 100 cu. ft.) Gas All fuels All fuels 6 18 18 — — — 18 48 48 18 18 18 Floor mounted (any size) Ranges— Floor mounted All fuels 48 — 48 18 18 Other Low Temperature Industrial Equipment floor mounted or suspended All fuels 18 18 48 18 18
EQUIPMENT CLEARANCES (in.) Commercial-Industrial Type Medium Temperature Equipment Above Top of Casing or Equipment e From Top and Sides of Warm- Air Bonnet or Plenum From Front From Back e From Sides e Boilers and water heaters— Over 50 psi or Over 100 cu. ft. All fuels 48 — 96 36 36 Other med. temp. industrial equipment—all sizes All Fuels 48 36 96 36 36 incinerators—all sizes 48 — 96 36 36 Industrial type High-Temperature Equipment High temperature equipment All sizes All fuels 180 — 360 120 120
NOTES FOR REFERENCE STANDARD RS 14–15.—
a See reference standard RS 14–16 for reduction of clearance.
b Large rooms are those that are large in comparison to the size of the equipment and have a volume equal to at least 12 times the total volume of a furnace and at least 16 times the total volume of a boiler. If the actual ceiling height of a room is greater than 8 ft., the volume of a room shall be figured on the basis of a ceiling height of 8 ft.
c The minimum dimension shall be that necessary for servicing the equipment, including access for cleaning and normal care, tube removal, etc.
d If the equipment is encased in brick, the 18 in. clearance above and at the sides and back may be reduced to not less than 12 in.
e If the equipment is encased in brick the clearance above may be reduced to not less than 36 in., and at sides and back may be reduced to not less than 18 in.
f To combustible material or metal cabinet. If the underside of such combustible material or metal cabinet is protected with asbestos mill board at least 1/4 in. thick covered with sheet metal of not less than no. 28 U.S. Standard gauge, the distance may be reduced to not less than 24 in.