NYC Administrative Code RS 15-11
Factory-built Chimneys, 1400 Degrees Fahrenheit.
1. Application. Factory-built 1400 degree Fahrenheit chimneys are intended for venting fuel gases, at a temperature not exceeding 1400 degrees Fahrenheit under continuous operating conditions, from building heating appliances and other low heat appliances as specified in the Chimney Selection Chart of the National Fire Protection Association Standard No. 211.
2. Installation. These chimneys are to be installed in accordance with the installation instructions provided with each chimney assembly. They are not to be enclosed within combustible construction, but an interior chimney is to be enclosed in a noncombustible fire resistant shaft of appropriate size and rating where the chimney extends through any story of a building above that in which the connected appliance is located. An unenclosed chimney may be placed adjacent to walls of combustible construction at the clearances specified for each chimney section in the individual listing and acceptance and in article 15 of this code.
3. Chimney system. Each 1400 degree Fahrenheit factory-built chimney consists of one or more chimney sections, a chimney cap, lateral supports, thimble and flashing assembly as needed and other parts as specified in the installation instructions provided with each chimney system.
4. Standards. The equipment shall comply with the following standards:
ANSI/UL 103–1988—Standard for chimneys, factory-built, residential type and building heating appliances (February 1989 revision).
ANSI/UL 959–1986—Standard for medium heat appliance factory-built chimneys.
5. Identification. Equipment listed and accepted by this standard shall be identified with the following: "1400 Degree Fahrenheit Chimney Part".