NYC Administrative Code RS 17-2A STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES UP TO AND INCLUDING SIX STORIES IN HEIGHT
ANSI/NFPA No. 13R–1994—Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height.
Modifications—The provisions of NFPA No. 13R—1994 shall be subject to the following modifications. The section and paragraph numbers are from that standard.
PREFACE
Change NFPA 72, National Fire Alarm Code to Section 27-979 of the Administrative Code.
CHAPTER 1—GENERAL INFORMATION
Section 1-1—Change four stories to six stories.
Section 1-3—The definition of Multipurpose Piping shall be deleted.
Section 1-3—The definition of Residential Occupancies shall be deleted. The definition of such use as stated in Title 27, Chapter 1, subchapter 3 of the Building Code shall be used.
Section 1-5.2—Delete and substitute the following: Section 1-5.2—Other types of pipe or tube may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of pipe or tube other than that described above must involve consideration of many factors, e.g.
(a) Pressure rating
(b) Beam strength (hangers)
(c) Corrosion (chemical and electrolytic)
(d) Resistance to failure when exposed to elevated temperatures
(e) Methods of joining (strength, permanence, fire hazard)
(f) Availability of fittings (for sprinkler outlets and proper routings)
(g) Physical characteristics related to integrity during earthquakes
(h) Toxicity
(i) Combustibility
(j) Movement during sprinkler operation (water distribution)
Nonmetallic pipe and tube shall comply with the portions of the ASTM standards specified in Table 1-5.2 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe shall only be used in wet pipe systems. Nonmetallic pipe shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Table 1-5.2 Delete Special Listed Polybutylene (PB) Pipe.
Section 1-5.6 Delete and substitute the following:
Section 1-5.6 Joints for the connection of copper tube or threadless pipe shall be brazed. Brazing filler metal classed BCuP-5, BAG-2 (ANSI/AWS A5.8-89) or other approved methods may be used. Lead free solder joints may be permitted for wet pipe systems when the temperature classification of the installed sprinklers is Ordinary or Intermediate.
Section 1-5.7 Delete and substitute the following:
Section 1-5.7 Other types of fittings may be used, but only those investigated and listed for this service by a nationally recognized testing and inspection agency in accordance with Underwriters Laboratory Standard 1821 and 1887. The use of fittings other than that described above must involve consideration of many factors as described in Section 1-5.2. Nonmetallic pipe and tube fittings shall comply with the portions of the ASTM standards specified in Table 1-5.7 that apply to fire protection service in addition to the provisions of this paragraph. Nonmetallic pipe and tube fittings shall only be used in wet pipe systems. Nonmetallic pipe and tube fittings shall be installed in accordance with the manufacturer's installation instructions, and in accordance with rules promulgated by the Commissioner of Buildings.
Section 1-6.2.1 Change NFPA 13 to RS 17-2, and add the following: "The use of antifreeze solutions other than glycerine-water in sprinkler systems using plastic pipe shall not be permitted."
CHAPTER 2—WORKING PLANS, DESIGN, INSTALLATION, ACCEPTED TESTS AND MAINTENANCE
Section 2-1 Delete
Section 2-1.1 Delete
Section 2-1.1.1 Delete
Section 2-1.1.2 Delete
Section 2-1.2 Delete
Section 2-1.2.1 Delete
Figure 2-1.2.1 Delete
Section 2-1.2.2 Delete
Section 2-1.3 Delete
Section 2-1.3.1 Delete
Section 2-1.3.1.1 Delete
Section 2-1.3.1.2 Delete
Section 2-1.3.1.3 Delete
Section 2-1.3.2 Delete
Section 2-3.2 Add subparagraph (e) as follows:
(e) A common supply main to the building, serving both sprinklers and domestic uses, may be used if provision is made to prevent flow on the domestic water system upon operation of sprinklers, and closure of the main sprinkler control valve, i.e., the house control valve, will shut off the domestic water supply.
Section 2-3.3 Delete
Section 2-3.3.1 Delete
Section 2-3.3.2 Delete
Section 2-4.1.1 Delete the "exception"
Renumber Sections 2-4.1.2 and 2-4.1.3 to be as follows:
Section 2-4.1.2 to be 2-4.1.3
Section 2-4.1.3 to be 2-4.1.4
Add new Section 2-4.1.2 to read as follows:
Section 2-4.1.2 Except for the meter set controlling combined domestic water and fire sprinkler systems, sectional control valves and other valves if provided in supply pipes to sprinklers shall be locked open and supervised open by one of the following methods:
(a) Central station, proprietary or remote station signaling service, or
(b) Local signaling service that will cause the sounding of an audible signal at a constantly attended point.
Exception—Underground gate valves with roadway boxes need not be supervised.
Section 2-4.2 Delete and substitute as follows:
Section 2-4.2 Except in buildings classified in occupancy group J-1, at least one 3 in. (76 mm) single inlet fire department connection shall be provided and located in accordance with Section 27-940 of the Building Code. Buildings classified in occupancy group J-1 shall be provided with siamese connections in accordance with RS 17-2.
Section 2-6 Exception No. 1:—Delete and substitute the following: Sprinklers are not required in bathrooms, water closet compartments, general toilet rooms and shower rooms.
Section 2-6 Exception No. 2:—Delete and substitute the following: Sprinklers are not required in clothes closets, linen closets and pantries.
Section 2-6 At the end of the section add the following:
Location of sprinklers installed in buildings classified in occupancy group J-1 shall be in accordance with the requirements of RS 17-2.
Section 2-7 Delete and substitute the following:
Section 2-7 The owner is responsible for the condition of a sprinkler system and shall properly maintain the sprinkler system in accordance with the Fire Department's rules and regulations.
CHAPTER 3—REFERENCED PUBLICATIONS
Delete in its entirety.
APPENDIX A—EXPLANATORY MATERIAL
A-1-1, first paragraph, Change four to six.
A-1-5.2 Delete
A-1-5.7 Delete
A-2-1.3.2 Delete
A-2-3.3.1 Delete
Figure A-2-3.2(a), (b) and (c) Delete
APPENDIX B—REFERENCED PUBLICATIONS
Delete in its entirety.
NOTE: Subjects that are not covered under this reference standard shall be in accordance with Reference Standard 17-2.